Water-cooled screw chiller controller · BACnet points list
Trane Symbio 800 Series R RTWD BACnet points list
Updated 28 October 2026
RTWD chillers with Symbio 800 publish about 685 BACnet objects; roughly three-quarters are diagnostic binary inputs. Operating data such as water temperatures, refrigerant pressures, compressor starts and run hours are AIs. Setpoints, lockouts, pump requests and the auto/stop command are AV/BV/MV objects.
This page lists 685 BACnet objects for the Trane Symbio 800 Series R RTWD — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 Series R RTWD
- Equipment
- Water-cooled screw chiller controller
- Equipment type
- Chillers
- BACnet objects
- 685 (20 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 Series R RTWD
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10100 | Chiller Auto Stop Command BAS | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10103 | Chiller Running State | Chiller on/off status | Read |
| BI 10101 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10103 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10108 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10108 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10120 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
Trane Symbio 800 Series R RTWD BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Cool/Heat Setpoint Temperature | Presently in use Chilled/Hot Water Setpoint | Temperature | Read | |
| AI | 10101 | Active Demand Limit Setpoint | Presently in use or "active" setting of the Demand Limit | Percentage | Read | |
| AI | 10102 | Evaporator Entering Water Temperature | This is present Evaporator Entering or Return water temperature | Temperature | Read | |
| AImin | 10103 | Evaporator Leaving Water Temperature | This is the temperature of the water leaving the evaporator | Temperature | Read | |
| AI | 10104 | Outdoor Air Temperature | The temperature of the outdoor air temperature sensor | Temperature | Read | |
| AI | 10105 | Number of Circuits | Read | |||
| AI | 10106 | Number of Compressors, Circuit 1 | Read | |||
| AI | 10107 | Number of Compressors, Circuit 2 | Read | |||
| AImin | 10108 | Actual Running Capacity | Actual chiller running capacity (same as Total Compressor Current %RLA) | Percentage | Read | |
| AI | 10109 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Evaporator Absolute Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10110 | Condenser Refrigerant Absolute Pressure Circuit 1 | Condenser Absolute Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10111 | Differential Refrigerant Pressure Ckt1 | Displays the differential pressure for the respective circuit as defined by | Pressure, Fluidic | Read | |
| AI | 10112 | Evaporator Shell Refrigerant Pressure Ckt1 | Pressure, Fluidic | Read | ||
| AI | 10113 | Evaporator Saturated Rfgt Temp Ckt1 | Temperature | Read | ||
| AI | 10114 | Condenser Saturated Rfgt Temp Ckt1 | Temperature | Read | ||
| AI | 10115 | Discharge Temperature Cprsr1A | Temperature | Read | ||
| AI | 10116 | Oil Absolute Pressure Cprsr1A | Absolute oil pressure for the compressor 1A | Pressure, Fluidic | Read | |
| AI | 10117 | Starts Cprsr1A | The total number of starts that the given compressor has experienced | Read | ||
| AI | 10118 | Running Time Cprsr1A | The total accumulated running time | Read | ||
| AI | 10119 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Evaporator Absolute Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10120 | Condenser Refrigerant Absolute Pressure Circuit 2 | Condenser Absolute Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10121 | Differential Refrigerant Pressure Ckt2 | Displays the differential pressure for the respective circuit as defined by | Pressure, Fluidic | Read | |
| AI | 10122 | Evaporator Shell Refrigerant Pressure Ckt2 | Pressure, Fluidic | Read | ||
| AI | 10123 | Evaporator Saturated Rfgt Temp Ckt2 | Temperature | Read | ||
| AI | 10124 | Condenser Saturated Rfgt Temp Ckt2 | Temperature | Read | ||
| AI | 10125 | Compressor Suction Temperature | Temperature | Read | ||
| AI | 10126 | Discharge Temperature Cprsr2A | Temperature | Read | ||
| AI | 10127 | Oil Absolute Pressure Cprsr2A | Absolute oil pressure for the compressor 2A | Pressure, Fluidic | Read | |
| AI | 10128 | Discharge Temperature Cprsr1B | Temperature | Read | ||
| AI | 10129 | Oil Absolute Pressure Cprsr1B | Absolute oil pressure for the compressor 1B | Pressure, Fluidic | Read | |
| AI | 10130 | Starts Cprsr1B | The total number of starts that the given compressor has experienced | Read | ||
| AI | 10131 | Running Time Cprsr1B | The total accumulated running time | Read | ||
| AI | 10132 | Starts Cprsr2A | The total number of starts that the given compressor has experienced | Read | ||
| AI | 10133 | Running Time Cprsr2A | The total accumulated running time | Read | ||
| AI | 10134 | Discharge Temperature Cprsr2B | Temperature | Read | ||
| AI | 10135 | Oil Absolute Pressure Cprsr2B | Absolute oil pressure for the compressor 2B | Pressure, Fluidic | Read | |
| AI | 10136 | Starts Cprsr2B | The total number of starts that the given compressor has experienced | Read | ||
| AI | 10137 | Running Time Cprsr2B | The total accumulated running time | Read | ||
| AI | 10138 | Motor Voltage AB Starter 1A | Motor voltage Vab for the respective compressor | Voltage | Read | |
| AI | 10139 | Motor Voltage AB Starter 1B | Motor voltage Vab for the respective compressor | Voltage | Read | |
| AI | 10140 | Motor Voltage AB Starter 2A | Motor voltage Vab for the respective compressor | Voltage | Read | |
| AI | 10141 | Motor Voltage AB Starter 2B | Motor voltage Vab for the respective compressor | Voltage | Read | |
| AI | 10142 | Oil Temperature Circuit 1 | The oil temperature for the respective compressor | Temperature | Read | |
| AI | 10143 | Oil Temperature Circuit 2 | The oil temperature for the respective compressor | Temperature | Read | |
| AI | 10144 | Condenser Entering Water Temperature | This is present Condenser Entering or Return water temperature | Temperature | Read | |
| AI | 10145 | Condenser Leaving Water Temperature | This is the temperature of the water leaving the Condenser | Temperature | Read | |
| AI | 10146 | Unit Power Consumption | Estimate of the total Chiller Power being presently utilized | Power, Electrical | Read | |
| AI | 10147 | Energy Consumption NonReset | Cumulate energy consumption of unit | Energy, Electrical | Read | |
| AI | 10148 | Energy Consumption Resettable | Energy, Electrical | Read | ||
| AI | 10149 | Motor Current L1 Starter 1A | Motor current phase A in amps for the respective compressor | Current | Read | |
| AI | 10150 | Motor Current L2 Starter 1A | Motor current phase B in amps for the respective compressor | Current | Read | |
| AI | 10151 | Motor Current L3 Starter 1A | Motor current phase C in amps for the respective compressor | Current | Read | |
| AI | 10152 | Motor Current L1 % RLA Starter 1A | Motor current phase A in % RLA for the respective compressor | Percentage | Read | |
| AI | 10153 | Motor Current L2 % RLA Starter 1A | Motor current phase B in % RLA for the respective compressor | Percentage | Read | |
| AI | 10154 | Motor Current L3 % RLA Starter 1A | Motor current phase C in % RLA for the respective compressor | Percentage | Read | |
| AI | 10155 | Motor Current L1 Starter 2A | Motor current phase A in amps for the respective compressor | Current | Read | |
| AI | 10156 | Motor Current L2 Starter 2A | Motor current phase B in amps for the respective compressor | Current | Read | |
| AI | 10157 | Motor Current L3 Starter 2A | Motor current phase C in amps for the respective compressor | Current | Read | |
| AI | 10158 | Motor Current L1 % RLA Starter 2A | Motor current phase A in % RLA for the respective compressor | Percentage | Read | |
| AI | 10159 | Motor Current L2 % RLA Starter 2A | Motor current phase B in % RLA for the respective compressor | Percentage | Read | |
| AI | 10160 | Motor Current L3 % RLA Starter 2A | Motor current phase C in % RLA for the respective compressor | Percentage | Read | |
| AI | 10161 | Motor Current L1 Starter 1B | Motor current phase A in amps for the respective compressor | Current | Read | |
| AI | 10162 | Motor Current L2 Starter 1B | Motor current phase B in amps for the respective compressor | Current | Read | |
| AI | 10163 | Motor Current L3 Starter 1B | Motor current phase C in amps for the respective compressor | Current | Read | |
| AI | 10164 | Motor Current L1 % RLA Starter 1B | Motor current phase A in % RLA for the respective compressor | Percentage | Read | |
| AI | 10165 | Motor Current L2 % RLA Starter 1B | Motor current phase B in % RLA for the respective compressor | Percentage | Read | |
| AI | 10166 | Motor Current L3 % RLA Starter 1B | Motor current phase C in % RLA for the respective compressor | Percentage | Read | |
| AI | 10167 | Motor Current L1 Starter 2B | Motor current phase A in amps for the respective compressor | Current | Read | |
| AI | 10168 | Motor Current L2 Starter 2B | Motor current phase B in amps for the respective compressor | Current | Read | |
| AI | 10169 | Motor Current L3 Starter 2B | Motor current phase C in amps for the respective compressor | Current | Read | |
| AI | 10170 | Motor Current L1 % RLA Starter 2B | Motor current phase A in % RLA for the respective compressor | Percentage | Read | |
| AI | 10171 | Motor Current L2 % RLA Starter 2B | Motor current phase B in % RLA for the respective compressor | Percentage | Read | |
| AI | 10172 | Motor Current L3 % RLA Starter 2B | Motor current phase C in % RLA for the respective compressor | Percentage | Read | |
| AI | 10173 | Motor Current A Cprsr1A | Motor Current U AFD 1A | Current | Read | |
| AI | 10174 | Motor Current B Cprsr1A | Motor Current V AFD 1A | Current | Read | |
| AI | 10175 | Motor Current C Cprsr1A | Motor Current W AFD 1A | Current | Read | |
| AI | 10176 | Motor % RLA A Cprsr1A | Motor Current U % RLA AFD 1A | Percentage | Read | |
| AI | 10177 | Motor % RLA B Cprsr1A | Motor Current V % RLA AFD 1A | Percentage | Read | |
| AI | 10178 | Motor % RLA C Cprsr1A | Motor Current W % RLA AFD 1A | Percentage | Read | |
| AI | 10179 | Motor Current A Cprsr2A | Motor Current U AFD 2A | Current | Read | |
| AI | 10180 | Motor Current B Cprsr2A | Motor Current V AFD 2A | Current | Read | |
| AI | 10181 | Motor Current C Cprsr2A | Motor Current W AFD 2A | Current | Read | |
| AI | 10182 | Motor % RLA A Cprsr2A | Motor Current U % RLA AFD 2A | Percentage | Read | |
| AI | 10183 | Motor % RLA B Cprsr2A | Motor Current V % RLA AFD 2A | Percentage | Read | |
| AI | 10184 | Motor % RLA C Cprsr2A | Motor Current W % RLA AFD 2A | Percentage | Read | |
| AI | 10185 | Average Motor Current % RLA AFD 1A | Motor average RLA for for the respective compressor | Percentage | Read | |
| AI | 10186 | Average Motor Current % RLA AFD 2A | Motor average RLA for for the respective compressor | Percentage | Read | |
| AI | 10187 | Unit Source ID (Last Diagnostic Code) | Last Logged Diagnostic Spec BAS | Read | ||
| AI | 10188 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10189 | Active Chilled Water Setpoint | Presently in use Chilled Water Setpoint | Temperature | Read | |
| AI | 10190 | Active Hot Water Setpoint | Presently in use Hot Water Setpoint | Temperature | Read | |
| AI | 10191 | Unit Load Command | Percentage | Read | ||
| AI | 10192 | Air Flow Percentage Circuit 1 | Air Flow Ckt1 | Percentage | Read | |
| AI | 10193 | Air Flow Percentage Circuit 2 | Air Flow Ckt2 | Percentage | Read | |
| AI | 10194 | Evaporator Refrigerant Pressure Circuit 1 | Evaporator Gauge Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10195 | Condenser Refrigerant Pressure Circuit 1 | Condenser Gauge Refrigerant Pressure circuit 1 | Pressure, Fluidic | Read | |
| AI | 10196 | Evaporator Refrigerant Pressure Circuit 2 | Evaporator Gauge Refrigerant Pressure circuit 2 | Pressure, Fluidic | Read | |
| AI | 10197 | Condenser Refrigerant Pressure Circuit 2 | Condenser Gauge Refrigerant Pressure circuit 2 | Pressure, Fluidic | Read | |
| AI | 10198 | Condenser Control Output | Condenser Head Pressure Control Output | Percentage | Read | |
| AI | 10199 | Oil Pressure Cprsr1A | Gauge oil pressure for the compressor 1A | Pressure, Fluidic | Read | |
| AI | 10200 | Oil Pressure Cprsr2A | Gauge oil pressure for the compressor 2A | Pressure, Fluidic | Read | |
| AI | 10201 | Oil Pressure Cprsr1B | Gauge oil pressure for the compressor 1B | Pressure, Fluidic | Read | |
| AI | 10202 | Oil Pressure Cprsr2B | Gauge oil pressure for the compressor 2B | Pressure, Fluidic | Read | |
| AI | 10203 | Evaporator Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10204 | Evaporator Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10205 | Condenser Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10206 | Condenser Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10207 | Average Line Current Circuit 1 | Average Line Current Meter 1 | Current | Read | |
| AI | 10208 | Average Line Current Circuit 2 | Average Line Current Meter 2 | Current | Read | |
| AI | 10209 | Average Line Voltage Circuit 1 | Average Line Voltage Meter 1 | Voltage | Read | |
| AI | 10210 | Average Line Voltage Circuit 2 | Average Line Voltage Meter 2 | Voltage | Read | |
| AI | 10211 | Line Current L1 Circuit 1 | Line Current L1 Meter 1 | Current | Read | |
| AI | 10212 | Line Current L2 Circuit 1 | Line Current L2 Meter 1 | Current | Read | |
| AI | 10213 | Line Current L3 Circuit 1 | Line Current L3 Meter 1 | Current | Read | |
| AI | 10214 | Line Current L1 Circuit 2 | Line Current L1 Meter 2 | Current | Read | |
| AI | 10215 | Line Current L2 Circuit 2 | Line Current L3 Meter 2 | Current | Read | |
| AI | 10216 | Line Current L3 Circuit 2 | Line Current L3 Meter 2 | Current | Read | |
| AI | 10217 | Voltage L1-L2 Circuit 1 | Line Voltage L1-L2 Meter 1 | Voltage | Read | |
| AI | 10218 | Voltage L2-L3 Circuit 1 | Line Voltage L2-L3 Meter 1 | Voltage | Read | |
| AI | 10219 | Voltage L1-L3 Circuit 1 | Line Voltage L1-L3 Meter 1 | Voltage | Read | |
| AI | 10220 | Voltage L1-L2 Circuit 2 | Line Voltage L1-L2 Meter 2 | Voltage | Read | |
| AI | 10221 | Voltage L2-L1 Circuit 2 | Line Voltage L2-L3 Meter 2 | Voltage | Read | |
| AI | 10222 | Voltage L1-L3 Circuit 2 | Line Voltage L1-L3 Meter 2 | Voltage | Read | |
| AI | 10223 | Line Frequency Circuit 1 | Line Frequency Meter 1 | Read | ||
| AI | 10224 | Line Frequency Circuit 2 | Line Frequency Meter 2 | Read | ||
| AI | 10225 | Power Factor Circuit 1 | Power Factor Meter 1 | Read | ||
| AI | 10226 | Power Factor Circuit 2 | Power Factor Meter 2 | Read | ||
| AI | 10227 | Power Demand Circuit 1 | Power Demand Meter 1 | Power, Electrical | Read | |
| AI | 10228 | Power Demand Circuit 2 | Power Demand Meter 2 | Power, Electrical | Read | |
| AI | 10229 | Power Factor | Unit Power Factor | Read | ||
| AI | 10230 | Current L1 | Meter Line Current L1 | Current | Read | |
| AI | 10231 | Current L2 | Meter Line Current L2 | Current | Read | |
| AI | 10232 | Current L3 | Meter Line Current L3 | Current | Read | |
| AI | 10233 | Average Current | Meter Average Line Current | Current | Read | |
| AI | 10234 | Voltage L1-L2 | Meter Line Voltage L1-L2 | Voltage | Read | |
| AI | 10235 | Voltage L2-L3 | Meter Line Voltage L2-L3 | Voltage | Read | |
| AI | 10236 | Voltage L1-L3 | Meter Line Voltage L1-L3 | Voltage | Read | |
| AI | 10237 | Average Voltage L-L | Meter Average Line Voltage | Voltage | Read | |
| AI | 10238 | Line Frequency | Unit Line Frequency | Read | ||
| AI | 10239 | Unit Power Demand | Chiller Power Demand | Power, Electrical | Read | |
| AI | 10240 | Active Cooling Differential to Start | Presently in use Cooling Differential to Start Setpoint | Temperature, Delta | Read | |
| AI | 10241 | Active Cooling Differential to Stop | Presently in use Cooling Differential to Stop Setpoint | Temperature, Delta | Read | |
| AI | 10242 | Active Heating Differential to Start | Presently in use Heating Differential to Start Setpoint | Temperature, Delta | Read | |
| AI | 10243 | Active Heating Differential to Stop | Presently in use Heating Differential to Stop Setpoint | Temperature, Delta | Read | |
| AVmin | 10100 | Chilled Water Setpoint | Desired evaporator leaving water temperature if chiller is in cooling mode | Temperature | Write | |
| AVmin | 10101 | Demand Limit Setpoint | Sets the maximum capacity that the chiller can use | Percentage | Write | |
| AV | 10102 | Hot Water Setpoint | Desired condenser leaving water temperature if chiller is in heating mode | Temperature | Write | |
| AV | 10103 | BAS Cooling Differential to Start | Desired Cooling Differential to Start if chiller is in cooling mode | Temperature, Delta | Write | |
| AV | 10104 | BAS Cooling Differential to Stop | Desired Cooling Differential to Stop if chiller is in cooling mode | Temperature, Delta | Write | |
| AV | 10105 | BAS Heating Differential to Start | Desired Heating Differential to Start if chiller is in heating mode | Temperature, Delta | Write | |
| AV | 10106 | BAS Heating Differential to Stop | Desired Heating Differential to Stop if chiller is in heating mode | Temperature, Delta | Write | |
| BI | 10100 | Run Enable | The chiller is available to run or is currently running | Read | 0 = Run Not Enabled, 1 = Run Enabled | |
| BImin | 10101 | Local Setpoint Control | The chiller is being controlled by local setpoints instead of BAS setpoints | Read | 0 = Remote Control, 1 = Local Control | |
| BI | 10102 | Limit Mode Relay Status | The Chiller is in a Limit mode | Read | 0 = Off, 1 = On | |
| BImin | 10103 | Chiller Running State | Primary running mode of the chiller sequence | Read | 0 = Off, 1 = On | |
| BI | 10104 | Maximum Capacity | Read | 0 = Off, 1 = On | ||
| BI | 10105 | Manual Override Exists | There is a Manual Override active | Read | 0 = Off, 1 = On | |
| BI | 10106 | Emergency Stop | Displays the Status of the Emergency Stop | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | |
| BI | 10107 | Evaporator Water Flow Status | Water flow through the evaporator | Read | 0 = No Flow, 1 = Flow | |
| BImin | 10108 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10109 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10110 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10111 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10112 | Diagnostic Present: Information | /eVar/Pltm1DiagPrsntInfo/ | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10113 | Diagnostic Present: Advisory | /eVar/Pltm1DiagPrsntAdvsry/ | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10114 | Diagnostic Present: Critical | /eVar/Pltm1DiagPrsntCrtcl/ | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10115 | Diagnostic Present: Service Required | /eVar/Pltm1DiagPrsntSvcRqrd/ | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10116 | Compressor 1A Running Status | Running status of compressor 1A | Read | 0 = Stop, 1 = Auto | |
| BI | 10117 | Compressor 1B Running Status | Running status of compressor 1B | Read | 0 = Stop, 1 = Auto | |
| BI | 10118 | Compressor 2A Running Status | Running status of compressor 2A | Read | 0 = Stop, 1 = Auto | |
| BI | 10119 | Compressor 2B Running Status | Running status of compressor 2B | Read | 0 = Stop, 1 = Auto | |
| BI | 10120 | External Auto Stop | Status of External Auto Stop input | Read | 0 = Stop, 1 = Auto | |
| BI | 10121 | Condenser Water Pump Command | This provides a status of the Chillers Condenser Water Pump output | Read | 0 = Inactive, 1 = Active | |
| BI | 10122 | Evaporator Water Pump Command | This provides a status of the Chillers Evaporator Water Pump output | Read | 0 = Off, 1 = On | |
| BI | 10123 | Condenser Water Flow Status | Water flow through the condenser | Read | 0 = Inactive, 1 = Active | |
| BI | 10124 | Front Panel Auto Stop Status | Status of Front Auto Stop input | Read | 0 = Stop, 1 = Auto | |
| BI | 10125 | Circuit Manual Reset Indicator (CMR) Ckt1 | Or not there is an alarm present | Read | 0 = Inactive, 1 = Active | |
| BI | 10126 | Circuit Manual Reset Indicator (CMR) Ckt2 | Or not there is an alarm present | Read | 0 = Inactive, 1 = Active | |
| BI | 10127 | Circuit Auto Reset Indicator (CAR) Ckt1 | Or not there is non-latching alarm present on circuit 1 | Read | 0 = Inactive, 1 = Active | |
| BI | 10128 | Circuit Auto Reset Indicator (CAR) Ckt2 | Or not there is non-latching alarm present on circuit 2 | Read | 0 = Inactive, 1 = Active | |
| BI | 10129 | Head Pressure Relief Request | Head Relief Request Relay | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10130 | Alarm - General Latching Unit | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10131 | Alarm - General Non Latching Unit | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10132 | Alarm - General Latching Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10133 | Alarm - General Latching Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10134 | Alarm - General Non Latching Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10135 | Alarm - General Non Latching Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10136 | Noise Reduction Request Active | Status of Noise Reduction Request | Read | 0 = Off, 1 = On | |
| BI | 11000 | Comm Loss: %RLA Indication Output (Vdc) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Comm Loss: AFD 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Comm Loss: AFD 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Comm Loss: AFD Fault Input 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Comm Loss: AFD Fault Input 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Comm Loss: AFD Fault Input 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Comm Loss: AFD Fault Input 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Comm Loss: AFD Run Command 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Comm Loss: AFD Run Command 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Comm Loss: AFD Speed Command 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Comm Loss: AFD Speed Command 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Comm Loss: AFD Speed Command 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Comm Loss: AFD Speed Command 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Comm Loss: AOC Inlet Oil Temperature 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Comm Loss: AOC Inlet Oil Temperature 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Comm Loss: Auxiliary Setpoint Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Comm Loss: Chiller Bypass Valve Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Comm Loss: Cond Head Press Cntrl Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Comm Loss: Cond Rfgt Liquid Level Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Comm Loss: Cond Rfgt Liquid Level Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Comm Loss: Cond Water Pump Analog Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Comm Loss: Condenser Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Comm Loss: Condenser Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Comm Loss: Condenser Rfgt Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Comm Loss: Condenser Rfgt Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Comm Loss: Condenser Rfgt Pressure Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Comm Loss: Condenser Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Comm Loss: Condenser Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Comm Loss: Cprsr Disch Rfgt Temp 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Comm Loss: Cprsr Disch Rfgt Temp 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Comm Loss: Cprsr Disch Rfgt Temp 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Comm Loss: Cprsr Disch Rfgt Temp 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Comm Loss: Electronic Expansion Valve Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Comm Loss: Electronic Expansion Valve Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Comm Loss: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Comm Loss: Energy Meter Pulse Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11036 | Comm Loss: Evap Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11037 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Comm Loss: Evap Iso Valve Close Switch Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Comm Loss: Evap Iso Valve Close Switch Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Comm Loss: Evap Iso Valve Open Switch Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Comm Loss: Evap Iso Valve Open Switch Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Comm Loss: Evap Isolation Valve Relay Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Comm Loss: Evap Isolation Valve Relay Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Comm Loss: Evap Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Comm Loss: Evap Oil Return Level Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Comm Loss: Evap Oil Return Level Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Comm Loss: Evap Pump Inv1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Comm Loss: Evap Pump Inv1 Run Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Comm Loss: Evap Rfgt Liquid Level Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Comm Loss: Evap Rfgt Liquid Level Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Comm Loss: Evap Rfgt Pool Temp Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Comm Loss: Evap Rfgt Pool Temp Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Comm Loss: Evap Shell Rfgt Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Comm Loss: Evap Shell Rfgt Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Comm Loss: Evap Water Pump Analog Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Comm Loss: Evap Water Pump Inv Freq Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Comm Loss: Evaporator Pump 1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Comm Loss: Evaporator Pump 2 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Comm Loss: Evaporator Water Pump 1 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Comm Loss: Evaporator Water Pump 2 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Comm Loss: Ext Noise Reduction Request | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Comm Loss: External Ckt2 Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Comm Loss: External Ckt1 Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Comm Loss: External Hot Water Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Comm Loss: Fan Control Relays, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Comm Loss: Fan Control Relays, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Comm Loss: Fan Inverter Fault Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Comm Loss: Fan Inverter Fault Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Comm Loss: Fan Inverter Speed Command Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Comm Loss: Fan Inverter Speed Command Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Comm Loss: High Pressure Cutout Sw 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Comm Loss: High Pressure Cutout Sw 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Comm Loss: High Pressure Cutout Sw 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Comm Loss: High Pressure Cutout Sw 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Comm Loss: High Pressure Cutout Switch Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Comm Loss: High Pressure Cutout Switch Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Comm Loss: HR Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Comm Loss: HR Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: Ice Building Status Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Comm Loss: Liquid Line Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Comm Loss: Liquid Line Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Comm Loss: Liquid Line Temperature Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Comm Loss: Liquid Line Temperature Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Comm Loss: Motor RLA Input 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Comm Loss: Motor RLA Input 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: Motor RLA Input 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Comm Loss: Motor RLA Input 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Comm Loss: Motor Winding Tstat Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Comm Loss: Motor Winding Tstat Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11096 | Comm Loss: Noise Reduction Request Relay Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Comm Loss: Noise Reduction Request Relay Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Comm Loss: Off-cycle Freeze Prot Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Comm Loss: Oil Heater Relay 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Comm Loss: Oil Heater Relay 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Comm Loss: Oil Loss Level Sensor Input Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Comm Loss: Oil Loss Level Sensor Input Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss: Oil Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Comm Loss: Oil Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Comm Loss: Oil Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Comm Loss: Oil Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Comm Loss: Oil Return Gas Pump Drain Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Comm Loss: Oil Return Gas Pump Drain Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11109 | Comm Loss: Oil Return Gas Pump Fill Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11110 | Comm Loss: Oil Return Gas Pump Fill Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11111 | Comm Loss: Oil Return Purge Valve Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Comm Loss: Oil Return Purge Valve Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: Oil Temp, Ckt 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: Oil Temp, Ckt 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Comm Loss: Reversing Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Comm Loss: Slide Valve Load 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: Slide Valve Load 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Comm Loss: Slide Valve Load 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Slide Valve Load 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Comm Loss: Slide Valve Unload 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Comm Loss: Slide Valve Unload 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Comm Loss: Slide Valve Unload 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Comm Loss: Slide Valve Unload 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Comm Loss: Starter 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Comm Loss: Starter 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Comm Loss: Starter 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Comm Loss: Starter 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Step Load 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Step Load 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Comm Loss: Step Load 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Comm Loss: Step Load 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Comm Loss: Suction Rfgt Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Suction Rfgt Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Suction Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Comm Loss: Suction Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Suction Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: Suction Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Comm Loss: Suction Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Comm Loss: Water System Diff Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Winding Temp 1, Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Winding Temp 1, Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Comm Loss: Winding Temp 2, Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Diagnostic: AFD %RLA Feedback 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Diagnostic: AFD %RLA Feedback 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Diagnostic: AFD %RLA Feedback 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Diagnostic: AFD %RLA Feedback 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Diagnostic: AFD Bump Complete 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Diagnostic: AFD Bump Complete 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Diagnostic: AFD Bump Current High 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Diagnostic: AFD Bump Current High 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Diagnostic: AFD Comm Loss – 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Diagnostic: AFD Comm Loss – 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Diagnostic: AFD Comm Loss – 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Diagnostic: AFD Comm Loss – 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Diagnostic: AFD Failure to Arm or Start 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Diagnostic: AFD Failure to Arm or Start 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Diagnostic: AFD Failure to Arm or Start 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Diagnostic: AFD Failure to Arm or Start 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Diagnostic: AFD Fault 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Diagnostic: AFD Fault 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Diagnostic: AFD Fault 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Diagnostic: AFD Fault 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Diagnostic: AFD Fault Mains 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Diagnostic: AFD Fault Mains 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Diagnostic: AFD Harmonic Filter Over Temperature 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Diagnostic: AFD Harmonic Filter Over Temperature 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Diagnostic: AFD High Pressure Cutout 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Diagnostic: AFD High Pressure Cutout 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Diagnostic: AFD Interrupt Failure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Diagnostic: AFD Interrupt Failure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Diagnostic: AFD Motor Current Overload 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Diagnostic: AFD Motor Current Overload 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Diagnostic: AFD Motor Current Overload 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Diagnostic: AFD Motor Current Overload 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Diagnostic: AFD Motor Fault 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Diagnostic: AFD Motor Fault 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Diagnostic: AFD Motor Speed Too High 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Diagnostic: AFD Motor Speed Too High 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Diagnostic: AFD Motor Speed Too Low 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Diagnostic: AFD Motor Speed Too Low 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Diagnostic: AFD Pump Out Speed Low 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Diagnostic: AFD Pump Out Speed Low 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Diagnostic: AFD Unexpected Shutdown 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Diagnostic: AFD Unexpected Shutdown 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Diagnostic: AFD Unhandled Fault 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Diagnostic: AFD Unhandled Fault 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Diagnostic: AOC Inlet Oil Temperature Sensor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Diagnostic: AOC Inlet Oil Temperature Sensor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: Check Clock | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: Chiller Service Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Diagnostic: Comm Loss: Winding Temp 2, Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Diagnostic: Cond Rfgt Liquid Level Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: Cond Rfgt Liquid Level Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: Condenser Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: Condenser Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: Condenser Rfgt Pressure Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: Condenser Rfgt Pressure Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Diagnostic: Condenser Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Diagnostic: Condenser Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Diagnostic: Cprsr Did Not Accel: Shutdown 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Diagnostic: Cprsr Did Not Accel: Shutdown 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11205 | Diagnostic: Cprsr Did Not Accel: Shutdown 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Diagnostic: Cprsr Did Not Accel: Shutdown 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Diagnostic: Cprsr Did Not Accel: Transition 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Diagnostic: Cprsr Did Not Accel: Transition 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Diagnostic: Cprsr Did Not Accel: Transition 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: Cprsr Did Not Accel: Transition 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Diagnostic: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Diagnostic: Evap Iso Valve Illegal Switch State Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Diagnostic: Evap Iso Valve Illegal Switch State Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11219 | Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11220 | Diagnostic: Evap Isolation Valve Failed To Close Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: Evap Isolation Valve Failed To Close Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: Evap Isolation Valve Failed To Open Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: Evap Isolation Valve Failed To Open Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: Evap Isolation Valve Open Switch Failure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: Evap Isolation Valve Open Switch Failure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11226 | Diagnostic: Evap Pump 1 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11227 | Diagnostic: Evap Pump 2 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11228 | Diagnostic: Evap Rfgt Pool Temp Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11229 | Diagnostic: Evap Rfgt Pool Temp Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: Evap Spillover Liquid Level Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Diagnostic: Evap Spillover Liquid Level Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Diagnostic: Evap Water Pump 1 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: Evap Water Pump 2 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: Evaporator Approach Error Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Diagnostic: Evaporator Approach Error Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Diagnostic: Evaporator Oil Return Level Sensor, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Diagnostic: Evaporator Oil Return Level Sensor, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11244 | Diagnostic: Evaporator Pump 1 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11245 | Diagnostic: Evaporator Pump 2 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11246 | Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11247 | Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11248 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11249 | Diagnostic: Evaporator Water Flow Lost Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11250 | Diagnostic: Evaporator Water Flow Lost Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11251 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11252 | Diagnostic: Evaporator Water Flow Overdue Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11253 | Diagnostic: Evaporator Water Flow Overdue Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11254 | Diagnostic: Excessive Condenser Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11255 | Diagnostic: Excessive Condenser Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11256 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11257 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11258 | Diagnostic: EXV Pressure Equalization Failed Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11259 | Diagnostic: EXV Pressure Equalization Failed Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11260 | Diagnostic: Fan Inverter Fault Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11261 | Diagnostic: Fan Inverter Fault Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11262 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11263 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11264 | Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11265 | Diagnostic: High Cprsr Rfgt Discharge Temp 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11266 | Diagnostic: High Cprsr Rfgt Discharge Temp 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11267 | Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11268 | Diagnostic: High Cprsr Rfgt Discharge Temp 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11269 | Diagnostic: High Cprsr Rfgt Discharge Temp 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11270 | Diagnostic: High Differential Refrigerant Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11271 | Diagnostic: High Differential Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11272 | Diagnostic: High Differential Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11273 | Diagnostic: High Differential Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11274 | Diagnostic: High Differential Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11275 | Diagnostic: High Evap Shell Rfgt Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11276 | Diagnostic: High Evap Shell Rfgt Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11277 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11278 | Diagnostic: High Motor Winding Temperature 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11279 | Diagnostic: High Motor Winding Temperature 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11280 | Diagnostic: High Motor Winding Temperature Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11281 | Diagnostic: High Motor Winding Temperature Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11282 | Diagnostic: High Oil Temperature Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11283 | Diagnostic: High Oil Temperature Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11284 | Diagnostic: High Pressure Cutout Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11285 | Diagnostic: High Pressure Cutout Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11286 | Diagnostic: High Pressure Cutout 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11287 | Diagnostic: High Pressure Cutout 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11288 | Diagnostic: High Pressure Cutout 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11289 | Diagnostic: High Pressure Cutout 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11290 | Diagnostic: High Refrigerant Pressure Ratio | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11291 | Diagnostic: High Refrigerant Pressure Ratio 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11292 | Diagnostic: High Refrigerant Pressure Ratio 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11293 | Diagnostic: High Refrigerant Pressure Ratio 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11294 | Diagnostic: High Refrigerant Pressure Ratio 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11295 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11296 | Diagnostic: Liquid Line Pressure Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11297 | Diagnostic: Liquid Line Pressure Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11298 | Diagnostic: Liquid Line Temp Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11299 | Diagnostic: Liquid Line Temp Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11300 | Diagnostic: Loss of Oil for Compressor (Running) Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11301 | Diagnostic: Loss of Oil for Compressor (Running) Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11302 | Diagnostic: Loss of Oil for Compressor (Stopped) Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11303 | Diagnostic: Loss of Oil for Compressor (Stopped) Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11304 | Diagnostic: Low Condenser Rfgt Temp Ckt 1: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11305 | Diagnostic: Low Condenser Rfgt Temp Ckt 2: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11306 | Diagnostic: Low Differential Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11307 | Diagnostic: Low Differential Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11308 | Diagnostic: Low Differential Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11309 | Diagnostic: Low Differential Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11310 | Diagnostic: Low Discharge Superheat 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11311 | Diagnostic: Low Discharge Superheat 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11312 | Diagnostic: Low Discharge Superheat 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11313 | Diagnostic: Low Discharge Superheat 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11314 | Diagnostic: Low Evaporator Oil Return Level Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11315 | Diagnostic: Low Evaporator Oil Return Level Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11316 | Diagnostic: Low Evaporator Refrigerant Pressure Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11317 | Diagnostic: Low Evaporator Refrigerant Pressure Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11318 | Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11319 | Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11320 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11321 | Diagnostic: Low Evaporator Water Temp (Unit On) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11322 | Diagnostic: Low Oil Flow 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11323 | Diagnostic: Low Oil Flow 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11324 | Diagnostic: Low Oil Flow 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11325 | Diagnostic: Low Oil Flow 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11326 | Diagnostic: Low Refrigerant Temperature Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11327 | Diagnostic: Low Refrigerant Temperature Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11328 | Diagnostic: Mfr Maintenance Recommended 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11329 | Diagnostic: Mfr Maintenance Recommended 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11330 | Diagnostic: Mfr Maintenance Recommended 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11331 | Diagnostic: Mfr Maintenance Recommended 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11332 | Diagnostic: Momentary Power Loss 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11333 | Diagnostic: Momentary Power Loss 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11334 | Diagnostic: Momentary Power Loss 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11335 | Diagnostic: Momentary Power Loss 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11336 | Diagnostic: Motor Current Overload 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11337 | Diagnostic: Motor Current Overload 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11338 | Diagnostic: Motor Current Overload 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11339 | Diagnostic: Motor Current Overload 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11340 | Diagnostic: Motor Winding Temp Sensor Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11341 | Diagnostic: Motor Winding Temp Sensor Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11342 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11343 | Diagnostic: MP: Non-Volatile Block Test Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11344 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11345 | Diagnostic: Need Cprsr 1A To Run For Oil Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11346 | Diagnostic: No Differential Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11347 | Diagnostic: No Differential Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11348 | Diagnostic: No Differential Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11349 | Diagnostic: No Differential Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11350 | Diagnostic: Oil Analysis Recommended Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11351 | Diagnostic: Oil Analysis Recommended Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11352 | Diagnostic: Oil Filter Change Recommended Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11353 | Diagnostic: Oil Filter Change Recommended Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11354 | Diagnostic: Oil Flow Protection Fault 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11355 | Diagnostic: Oil Flow Protection Fault 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11356 | Diagnostic: Oil Flow Protection Fault 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11357 | Diagnostic: Oil Flow Protection Fault 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11358 | Diagnostic: Oil Pressure Sensor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11359 | Diagnostic: Oil Pressure Sensor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11360 | Diagnostic: Oil Pressure Sensor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11361 | Diagnostic: Oil Pressure Sensor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11362 | Diagnostic: Oil Temperature Sensor, Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11363 | Diagnostic: Oil Temperature Sensor, Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11364 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11365 | Diagnostic: Over Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11366 | Diagnostic: Over Voltage 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11367 | Diagnostic: Over Voltage 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11368 | Diagnostic: Phase Loss 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11369 | Diagnostic: Phase Loss 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11370 | Diagnostic: Phase Loss 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11371 | Diagnostic: Phase Loss 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11372 | Diagnostic: Phase Reversal 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11373 | Diagnostic: Phase Reversal 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11374 | Diagnostic: Phase Reversal 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11375 | Diagnostic: Phase Reversal 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11376 | Diagnostic: Power Loss 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11377 | Diagnostic: Power Loss 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11378 | Diagnostic: Power Loss 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11379 | Diagnostic: Power Loss 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11380 | Diagnostic: Pumpdown Terminated Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11381 | Diagnostic: Pumpdown Terminated Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11382 | Diagnostic: Pumpdown Terminated By Time Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11383 | Diagnostic: Pumpdown Terminated By Time Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11384 | Diagnostic: Refrigerant Charge Loss Detected Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11385 | Diagnostic: Refrigerant Charge Loss Detected Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11386 | Diagnostic: Restart Inhibit Invoked 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11387 | Diagnostic: Restart Inhibit Invoked 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11388 | Diagnostic: Restart Inhibit Invoked 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11389 | Diagnostic: Restart Inhibit Invoked 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11390 | Diagnostic: Severe Current Imbalance 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11391 | Diagnostic: Severe Current Imbalance 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11392 | Diagnostic: Severe Current Imbalance 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11393 | Diagnostic: Severe Current Imbalance 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11394 | Diagnostic: Software Error 1001: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11395 | Diagnostic: Software Error 1002: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11396 | Diagnostic: Software Error 1003: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11397 | Diagnostic: Starter Comm Loss: Main Processor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11398 | Diagnostic: Starter Comm Loss: Main Processor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11399 | Diagnostic: Starter Comm Loss: Main Processor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11400 | Diagnostic: Starter Comm Loss: Main Processor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11401 | Diagnostic: Starter Contactor Interrupt Failure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11402 | Diagnostic: Starter Contactor Interrupt Failure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11403 | Diagnostic: Starter Contactor Interrupt Failure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11404 | Diagnostic: Starter Contactor Interrupt Failure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11405 | Diagnostic: Starter Did Not Fully Accelerate 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11406 | Diagnostic: Starter Did Not Fully Accelerate 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11407 | Diagnostic: Starter Did Not Fully Accelerate 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11408 | Diagnostic: Starter Did Not Transition 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11409 | Diagnostic: Starter Did Not Transition 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11410 | Diagnostic: Starter Did Not Transition 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11411 | Diagnostic: Starter Did Not Transition 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11412 | Diagnostic: Starter Dry Run Test 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11413 | Diagnostic: Starter Dry Run Test 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11414 | Diagnostic: Starter Dry Run Test 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11415 | Diagnostic: Starter Dry Run Test 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11416 | Diagnostic: Starter Failed to Arm/Start 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11417 | Diagnostic: Starter Failed to Arm/Start 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11418 | Diagnostic: Starter Failed to Arm/Start 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11419 | Diagnostic: Starter Failed to Arm/Start 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11420 | Diagnostic: Starter Fault Type I 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11421 | Diagnostic: Starter Fault Type I 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11422 | Diagnostic: Starter Fault Type I 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11423 | Diagnostic: Starter Fault Type I 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11424 | Diagnostic: Starter Fault Type II 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11425 | Diagnostic: Starter Fault Type II 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11426 | Diagnostic: Starter Fault Type II 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11427 | Diagnostic: Starter Fault Type II 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11428 | Diagnostic: Starter Fault Type III 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11429 | Diagnostic: Starter Fault Type III 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11430 | Diagnostic: Starter Fault Type III 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11431 | Diagnostic: Starter Fault Type III 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11432 | Diagnostic: Starter Module Memory Error Type 1 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11433 | Diagnostic: Starter Module Memory Error Type 1 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11434 | Diagnostic: Starter Module Memory Error Type 1 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11435 | Diagnostic: Starter Module Memory Error Type 1 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11436 | Diagnostic: Starter Module Memory Error Type 2 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11437 | Diagnostic: Starter Module Memory Error Type 2 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11438 | Diagnostic: Starter Module Memory Error Type 2 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11439 | Diagnostic: Starter Module Memory Error Type 2 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11440 | Diagnostic: Starts/Hours Modified 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11441 | Diagnostic: Starts/Hours Modified 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11442 | Diagnostic: Starts/Hours Modified 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11443 | Diagnostic: Starts/Hours Modified 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11444 | Diagnostic: Suction Pressure Transducer Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11445 | Diagnostic: Suction Pressure Transducer Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11446 | Diagnostic: Suction Refrigerant Pressure Sensor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11447 | Diagnostic: Suction Refrigerant Pressure Sensor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11448 | Diagnostic: Suction Refrigerant Pressure Sensor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11449 | Diagnostic: Suction Refrigerant Pressure Sensor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11450 | Diagnostic: Suction Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11451 | Diagnostic: Transition Complete Input Opened 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11452 | Diagnostic: Transition Complete Input Opened 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11453 | Diagnostic: Transition Complete Input Opened 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11454 | Diagnostic: Transition Complete Input Opened 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11455 | Diagnostic: Transition Complete Input Shorted 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11456 | Diagnostic: Transition Complete Input Shorted 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11457 | Diagnostic: Transition Complete Input Shorted 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11458 | Diagnostic: Transition Complete Input Shorted 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11459 | Diagnostic: Under Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11460 | Diagnostic: Under Voltage 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11461 | Diagnostic: Under Voltage 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11462 | Diagnostic: Unexpected Starter Shutdown 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11463 | Diagnostic: Unexpected Starter Shutdown 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11464 | Diagnostic: Unexpected Starter Shutdown 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11465 | Diagnostic: Unexpected Starter Shutdown 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11466 | Diagnostic: Very Low Discharge Superheat 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11467 | Diagnostic: Very Low Discharge Superheat 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11468 | Diagnostic: Very Low Evap Rfgt Pressure 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11469 | Diagnostic: Very Low Evap Rfgt Pressure 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11470 | Diagnostic: Very Low Evap Rfgt Pressure 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11471 | Diagnostic: Very Low Evap Rfgt Pressure 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11472 | Diagnostic: Water System Differential Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11473 | Diagnostic: Energy Meter Write Value Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11474 | Diagnostic: Write Command Failure Energy Meter 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11475 | Diagnostic: Write Command Failure Energy Meter 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11476 | Diagnostic: High Evaporator Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11477 | Comm Loss: Starter Panel High Temperature Limit | Read | 0 = Normal, 1 = In Alarm | ||
| BVmin | 10100 | Chiller Auto Stop Command BAS | BAS command for Chiller Auto Stop | Write | 0 = Stop, 1 = Auto | |
| BV | 10101 | Reset Diagnostic | BAS diagnostic reset command to clear resettable active diagnostics | Write | 0 = Normal, 1 = Reset | |
| BV | 10102 | Circuit 1 Lockout BAS | BAS to lock circuit 1 | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10103 | Circuit 2 Lockout BAS | BAS to lock circuit 2 | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10104 | Energy Consumption Reset | BAS command to reset Energy Consumption Resettable counter | Write | 0 = Accumulating, 1 = Reset | |
| BV | 10105 | Noise Reduction Request BAS | BAS Noise Reduction Command | Write | 0 = Normal, 1 = Reduce Noise | |
| BV | 10106 | Compressor 1A Lockout BAS | BAS Compressor 1A Lockout | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10107 | Compressor 1B Lockout BAS | BAS Compressor 1B Lockout | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10108 | Compressor 2A Lockout BAS | BAS Compressor 2A Lockout | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10109 | Compressor 2B Lockout BAS | BAS Compressor 2B Lockout | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10110 | Evaporator Water Pump Request BAS | BAS Evaporator Water Pump Request | Write | 0 = Auto, 1 = On | |
| BV | 10111 | Condenser Water Pump Request BAS | BAS Condenser Water Pump Request | Write | 0 = Auto, 1 = On | |
| MI | 10100 | Running Mode | Running state of the chiller | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | |
| MI | 10101 | Operating Mode | Operating mode of the chiller | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | |
| MI | 10103 | Refrigerant Type | Chiller refrigerant type | Read | 5 = R-134a, 13 = R-513A, 16 = R-1234ze(E), 18 = R-515B | |
| MI | 10104 | Manufacturing Location | Location that the chiller was manufactured | Read | 3 = Pueblo, 4 = Charmes | |
| MI | 10105 | Cooling Type | Cooling Type of chiller | Read | 1 = Water Cooled, 2 = Air Cooled | |
| MI | 10106 | Model Information [GEN2] | Model information of chiller | Read | 17 = RTWF, 30 = RTSF, 41 = RTWF XSE, 45 = RTWD, 46 = RTUD | |
| MVmin | 10100 | Chiller Mode Command BAS | Command the chiller Mode | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Object ID lookup: Trane Symbio 800 Series R RTWD point IDs by name
AI10100Active Cool/Heat Setpoint TemperatureAI10101Active Demand Limit SetpointAI10102Evaporator Entering Water TemperatureAI10103Evaporator Leaving Water TemperatureAI10104Outdoor Air TemperatureAI10105Number of CircuitsAI10106Number of Compressors, Circuit 1AI10107Number of Compressors, Circuit 2AI10108Actual Running CapacityAI10109Evaporator Refrigerant Absolute Pressure Circuit 1AI10110Condenser Refrigerant Absolute Pressure Circuit 1AI10111Differential Refrigerant Pressure Ckt1AI10112Evaporator Shell Refrigerant Pressure Ckt1AI10113Evaporator Saturated Rfgt Temp Ckt1AI10114Condenser Saturated Rfgt Temp Ckt1AI10115Discharge Temperature Cprsr1AAI10116Oil Absolute Pressure Cprsr1AAI10117Starts Cprsr1AAI10118Running Time Cprsr1AAI10119Evaporator Refrigerant Absolute Pressure Circuit 2AI10120Condenser Refrigerant Absolute Pressure Circuit 2AI10121Differential Refrigerant Pressure Ckt2AI10122Evaporator Shell Refrigerant Pressure Ckt2AI10123Evaporator Saturated Rfgt Temp Ckt2AI10124Condenser Saturated Rfgt Temp Ckt2AI10125Compressor Suction TemperatureAI10126Discharge Temperature Cprsr2AAI10127Oil Absolute Pressure Cprsr2AAI10128Discharge Temperature Cprsr1BAI10129Oil Absolute Pressure Cprsr1BAI10130Starts Cprsr1BAI10131Running Time Cprsr1BAI10132Starts Cprsr2AAI10133Running Time Cprsr2AAI10134Discharge Temperature Cprsr2BAI10135Oil Absolute Pressure Cprsr2BAI10136Starts Cprsr2BAI10137Running Time Cprsr2BAI10138Motor Voltage AB Starter 1AAI10139Motor Voltage AB Starter 1BAI10140Motor Voltage AB Starter 2AAI10141Motor Voltage AB Starter 2BAI10142Oil Temperature Circuit 1AI10143Oil Temperature Circuit 2AI10144Condenser Entering Water TemperatureAI10145Condenser Leaving Water TemperatureAI10146Unit Power ConsumptionAI10147Energy Consumption NonResetAI10148Energy Consumption ResettableAI10149Motor Current L1 Starter 1AAI10150Motor Current L2 Starter 1AAI10151Motor Current L3 Starter 1AAI10152Motor Current L1 % RLA Starter 1AAI10153Motor Current L2 % RLA Starter 1AAI10154Motor Current L3 % RLA Starter 1AAI10155Motor Current L1 Starter 2AAI10156Motor Current L2 Starter 2AAI10157Motor Current L3 Starter 2AAI10158Motor Current L1 % RLA Starter 2AAI10159Motor Current L2 % RLA Starter 2AAI10160Motor Current L3 % RLA Starter 2AAI10161Motor Current L1 Starter 1BAI10162Motor Current L2 Starter 1BAI10163Motor Current L3 Starter 1BAI10164Motor Current L1 % RLA Starter 1BAI10165Motor Current L2 % RLA Starter 1BAI10166Motor Current L3 % RLA Starter 1BAI10167Motor Current L1 Starter 2BAI10168Motor Current L2 Starter 2BAI10169Motor Current L3 Starter 2BAI10170Motor Current L1 % RLA Starter 2BAI10171Motor Current L2 % RLA Starter 2BAI10172Motor Current L3 % RLA Starter 2BAI10173Motor Current A Cprsr1AAI10174Motor Current B Cprsr1AAI10175Motor Current C Cprsr1AAI10176Motor % RLA A Cprsr1AAI10177Motor % RLA B Cprsr1AAI10178Motor % RLA C Cprsr1AAI10179Motor Current A Cprsr2AAI10180Motor Current B Cprsr2AAI10181Motor Current C Cprsr2AAI10182Motor % RLA A Cprsr2AAI10183Motor % RLA B Cprsr2AAI10184Motor % RLA C Cprsr2AAI10185Average Motor Current % RLA AFD 1AAI10186Average Motor Current % RLA AFD 2AAI10187Unit Source ID (Last Diagnostic Code)AI10188Chiller Design CapacityAI10189Active Chilled Water SetpointAI10190Active Hot Water SetpointAI10191Unit Load CommandAI10192Air Flow Percentage Circuit 1AI10193Air Flow Percentage Circuit 2AI10194Evaporator Refrigerant Pressure Circuit 1AI10195Condenser Refrigerant Pressure Circuit 1AI10196Evaporator Refrigerant Pressure Circuit 2AI10197Condenser Refrigerant Pressure Circuit 2AI10198Condenser Control OutputAI10199Oil Pressure Cprsr1AAI10200Oil Pressure Cprsr2AAI10201Oil Pressure Cprsr1BAI10202Oil Pressure Cprsr2BAI10203Evaporator Approach Temperature Circuit 1AI10204Evaporator Approach Temperature Circuit 2AI10205Condenser Approach Temperature Circuit 1AI10206Condenser Approach Temperature Circuit 2AI10207Average Line Current Circuit 1AI10208Average Line Current Circuit 2AI10209Average Line Voltage Circuit 1AI10210Average Line Voltage Circuit 2AI10211Line Current L1 Circuit 1AI10212Line Current L2 Circuit 1AI10213Line Current L3 Circuit 1AI10214Line Current L1 Circuit 2AI10215Line Current L2 Circuit 2AI10216Line Current L3 Circuit 2AI10217Voltage L1-L2 Circuit 1AI10218Voltage L2-L3 Circuit 1AI10219Voltage L1-L3 Circuit 1AI10220Voltage L1-L2 Circuit 2AI10221Voltage L2-L1 Circuit 2AI10222Voltage L1-L3 Circuit 2AI10223Line Frequency Circuit 1AI10224Line Frequency Circuit 2AI10225Power Factor Circuit 1AI10226Power Factor Circuit 2AI10227Power Demand Circuit 1AI10228Power Demand Circuit 2AI10229Power FactorAI10230Current L1AI10231Current L2AI10232Current L3AI10233Average CurrentAI10234Voltage L1-L2AI10235Voltage L2-L3AI10236Voltage L1-L3AI10237Average Voltage L-LAI10238Line FrequencyAI10239Unit Power DemandAI10240Active Cooling Differential to StartAI10241Active Cooling Differential to StopAI10242Active Heating Differential to StartAI10243Active Heating Differential to StopAV10100Chilled Water SetpointAV10101Demand Limit SetpointAV10102Hot Water SetpointAV10103BAS Cooling Differential to StartAV10104BAS Cooling Differential to StopAV10105BAS Heating Differential to StartAV10106BAS Heating Differential to StopBI10100Run EnableBI10101Local Setpoint ControlBI10102Limit Mode Relay StatusBI10103Chiller Running StateBI10104Maximum CapacityBI10105Manual Override ExistsBI10106Emergency StopBI10107Evaporator Water Flow StatusBI10108Diagnostic PresentBI10109Diagnostic Shutdown PresentBI10110Diagnostic: Manual Reset RequiredBI10111Diagnostic: Local Manual Reset RequiredBI10112Diagnostic Present: InformationBI10113Diagnostic Present: AdvisoryBI10114Diagnostic Present: CriticalBI10115Diagnostic Present: Service RequiredBI10116Compressor 1A Running StatusBI10117Compressor 1B Running StatusBI10118Compressor 2A Running StatusBI10119Compressor 2B Running StatusBI10120External Auto StopBI10121Condenser Water Pump CommandBI10122Evaporator Water Pump CommandBI10123Condenser Water Flow StatusBI10124Front Panel Auto Stop StatusBI10125Circuit Manual Reset Indicator (CMR) Ckt1BI10126Circuit Manual Reset Indicator (CMR) Ckt2BI10127Circuit Auto Reset Indicator (CAR) Ckt1BI10128Circuit Auto Reset Indicator (CAR) Ckt2BI10129Head Pressure Relief RequestBI10130Alarm - General Latching UnitBI10131Alarm - General Non Latching UnitBI10132Alarm - General Latching Ckt1BI10133Alarm - General Latching Ckt2BI10134Alarm - General Non Latching Ckt1BI10135Alarm - General Non Latching Ckt2BI10136Noise Reduction Request ActiveBI11000Comm Loss: %RLA Indication Output (Vdc)BI11001Comm Loss: AFD 1ABI11002Comm Loss: AFD 2ABI11003Comm Loss: AFD Fault Input 1ABI11004Comm Loss: AFD Fault Input 1BBI11005Comm Loss: AFD Fault Input 2ABI11006Comm Loss: AFD Fault Input 2BBI11007Comm Loss: AFD Run Command 1ABI11008Comm Loss: AFD Run Command 2ABI11009Comm Loss: AFD Speed Command 1ABI11010Comm Loss: AFD Speed Command 1BBI11011Comm Loss: AFD Speed Command 2ABI11012Comm Loss: AFD Speed Command 2BBI11013Comm Loss: AOC Inlet Oil Temperature 1ABI11014Comm Loss: AOC Inlet Oil Temperature 2ABI11015Comm Loss: Auxiliary Setpoint CommandBI11016Comm Loss: Chiller Bypass Valve OutputBI11017Comm Loss: Cond Head Press Cntrl OutputBI11018Comm Loss: Cond Rfgt Liquid Level Ckt1BI11019Comm Loss: Cond Rfgt Liquid Level Ckt2BI11020Comm Loss: Cond Water Pump Analog OutputBI11021Comm Loss: Condenser Entering Water TempBI11022Comm Loss: Condenser Leaving Water TempBI11023Comm Loss: Condenser Rfgt Pressure Ckt2BI11024Comm Loss: Condenser Rfgt Pressure Ckt1BI11025Comm Loss: Condenser Rfgt Pressure OutputBI11026Comm Loss: Condenser Water Flow SwitchBI11027Comm Loss: Condenser Water Pump RelayBI11028Comm Loss: Cprsr Disch Rfgt Temp 1ABI11029Comm Loss: Cprsr Disch Rfgt Temp 1BBI11030Comm Loss: Cprsr Disch Rfgt Temp 2ABI11031Comm Loss: Cprsr Disch Rfgt Temp 2BBI11032Comm Loss: Electronic Expansion Valve Ckt1BI11033Comm Loss: Electronic Expansion Valve Ckt2BI11034Comm Loss: Emergency Stop Feedback InputBI11035Comm Loss: Energy Meter Pulse InputBI11036Comm Loss: Evap Entering Water PressureBI11037Comm Loss: Evap Entering Water TempBI11038Comm Loss: Evap Iso Valve Close Switch Ckt1BI11039Comm Loss: Evap Iso Valve Close Switch Ckt2BI11040Comm Loss: Evap Iso Valve Open Switch Ckt1BI11041Comm Loss: Evap Iso Valve Open Switch Ckt2BI11042Comm Loss: Evap Isolation Valve Relay Ckt1BI11043Comm Loss: Evap Isolation Valve Relay Ckt2BI11044Comm Loss: Evap Leaving Water PressureBI11045Comm Loss: Evap Leaving Water TempBI11046Comm Loss: Evap Oil Return Level Ckt1BI11047Comm Loss: Evap Oil Return Level Ckt2BI11048Comm Loss: Evap Pump Inv1 Fault InputBI11049Comm Loss: Evap Pump Inv1 Run CommandBI11050Comm Loss: Evap Rfgt Liquid Level Ckt1BI11051Comm Loss: Evap Rfgt Liquid Level Ckt2BI11052Comm Loss: Evap Rfgt Pool Temp Ckt1BI11053Comm Loss: Evap Rfgt Pool Temp Ckt2BI11054Comm Loss: Evap Shell Rfgt Pressure Ckt1BI11055Comm Loss: Evap Shell Rfgt Pressure Ckt2BI11056Comm Loss: Evap Water Pump Analog OutputBI11057Comm Loss: Evap Water Pump Inv Freq InputBI11058Comm Loss: Evaporator Pump 1 Fault InputBI11059Comm Loss: Evaporator Pump 2 Fault InputBI11060Comm Loss: Evaporator Water Flow SwitchBI11061Comm Loss: Evaporator Water Pump 1 RelayBI11062Comm Loss: Evaporator Water Pump 2 RelayBI11063Comm Loss: Ext Chilled/Hot Water SetpointBI11064Comm Loss: Ext Demand Limit SetpointBI11065Comm Loss: Ext Noise Reduction RequestBI11066Comm Loss: External Auto/StopBI11067Comm Loss: External Ckt2 LockoutBI11068Comm Loss: External Ckt1 LockoutBI11069Comm Loss: External Hot Water CommandBI11070Comm Loss: External Ice Building CommandBI11071Comm Loss: Fan Control Relays, Ckt1BI11072Comm Loss: Fan Control Relays, Ckt2BI11073Comm Loss: Fan Inverter Fault Ckt1BI11074Comm Loss: Fan Inverter Fault Ckt2BI11075Comm Loss: Fan Inverter Speed Command Ckt1BI11076Comm Loss: Fan Inverter Speed Command Ckt2BI11077Comm Loss: High Pressure Cutout Sw 1ABI11078Comm Loss: High Pressure Cutout Sw 1BBI11079Comm Loss: High Pressure Cutout Sw 2ABI11080Comm Loss: High Pressure Cutout Sw 2BBI11081Comm Loss: High Pressure Cutout Switch Ckt2BI11082Comm Loss: High Pressure Cutout Switch Ckt1BI11083Comm Loss: HR Entering Water Temp SensorBI11084Comm Loss: HR Leaving Water Temp SensorBI11085Comm Loss: Ice Building Status RelayBI11086Comm Loss: Liquid Line Pressure Ckt1BI11087Comm Loss: Liquid Line Pressure Ckt2BI11088Comm Loss: Liquid Line Temperature Ckt1BI11089Comm Loss: Liquid Line Temperature Ckt2BI11090Comm Loss: Motor RLA Input 1ABI11091Comm Loss: Motor RLA Input 1BBI11092Comm Loss: Motor RLA Input 2ABI11093Comm Loss: Motor RLA Input 2BBI11094Comm Loss: Motor Winding Tstat Cprsr1ABI11095Comm Loss: Motor Winding Tstat Cprsr2ABI11096Comm Loss: Noise Reduction Request Relay Ckt1BI11097Comm Loss: Noise Reduction Request Relay Ckt2BI11098Comm Loss: Off-cycle Freeze Prot RelayBI11099Comm Loss: Oil Heater Relay 1ABI11100Comm Loss: Oil Heater Relay 2ABI11101Comm Loss: Oil Loss Level Sensor Input Ckt1BI11102Comm Loss: Oil Loss Level Sensor Input Ckt2BI11103Comm Loss: Oil Pressure 1ABI11104Comm Loss: Oil Pressure 1BBI11105Comm Loss: Oil Pressure 2ABI11106Comm Loss: Oil Pressure 2BBI11107Comm Loss: Oil Return Gas Pump Drain Ckt1BI11108Comm Loss: Oil Return Gas Pump Drain Ckt2BI11109Comm Loss: Oil Return Gas Pump Fill Ckt1BI11110Comm Loss: Oil Return Gas Pump Fill Ckt2BI11111Comm Loss: Oil Return Purge Valve Ckt1BI11112Comm Loss: Oil Return Purge Valve Ckt2BI11113Comm Loss: Oil Temp, Ckt 1BI11114Comm Loss: Oil Temp, Ckt 2BI11115Comm Loss: Outdoor Air TemperatureBI11116Comm Loss: Programmable Relay Board 1BI11117Comm Loss: Programmable Relay Board 2BI11118Comm Loss: Reversing ValveBI11119Comm Loss: Slide Valve Load 1ABI11120Comm Loss: Slide Valve Load 1BBI11121Comm Loss: Slide Valve Load 2ABI11122Comm Loss: Slide Valve Load 2BBI11123Comm Loss: Slide Valve Unload 1ABI11124Comm Loss: Slide Valve Unload 1BBI11125Comm Loss: Slide Valve Unload 2ABI11126Comm Loss: Slide Valve Unload 2BBI11127Comm Loss: Starter 1ABI11128Comm Loss: Starter 1BBI11129Comm Loss: Starter 2ABI11130Comm Loss: Starter 2BBI11131Comm Loss: Step Load 1ABI11132Comm Loss: Step Load 1BBI11133Comm Loss: Step Load 2ABI11134Comm Loss: Step Load 2BBI11135Comm Loss: Suction Rfgt Pressure Ckt2BI11136Comm Loss: Suction Rfgt Pressure Ckt1BI11137Comm Loss: Suction Rfgt Pressure 1ABI11138Comm Loss: Suction Rfgt Pressure 1BBI11139Comm Loss: Suction Rfgt Pressure 2ABI11140Comm Loss: Suction Rfgt Pressure 2BBI11141Comm Loss: Suction TemperatureBI11142Comm Loss: Water System Diff PressureBI11143Comm Loss: Winding Temp 1, Cprsr1ABI11144Comm Loss: Winding Temp 1, Cprsr2ABI11145Comm Loss: Winding Temp 2, Cprsr1ABI11146Diagnostic: AFD %RLA Feedback 1ABI11147Diagnostic: AFD %RLA Feedback 1BBI11148Diagnostic: AFD %RLA Feedback 2ABI11149Diagnostic: AFD %RLA Feedback 2BBI11150Diagnostic: AFD Bump Complete 1ABI11151Diagnostic: AFD Bump Complete 2ABI11152Diagnostic: AFD Bump Current High 1ABI11153Diagnostic: AFD Bump Current High 2ABI11154Diagnostic: AFD Comm Loss – 1ABI11155Diagnostic: AFD Comm Loss – 1BBI11156Diagnostic: AFD Comm Loss – 2ABI11157Diagnostic: AFD Comm Loss – 2BBI11158Diagnostic: AFD Failure to Arm or Start 1ABI11159Diagnostic: AFD Failure to Arm or Start 1BBI11160Diagnostic: AFD Failure to Arm or Start 2ABI11161Diagnostic: AFD Failure to Arm or Start 2BBI11162Diagnostic: AFD Fault 1ABI11163Diagnostic: AFD Fault 1BBI11164Diagnostic: AFD Fault 2ABI11165Diagnostic: AFD Fault 2BBI11166Diagnostic: AFD Fault Mains 1ABI11167Diagnostic: AFD Fault Mains 2ABI11168Diagnostic: AFD Harmonic Filter Over Temperature 1ABI11169Diagnostic: AFD Harmonic Filter Over Temperature 2ABI11170Diagnostic: AFD High Pressure Cutout 1ABI11171Diagnostic: AFD High Pressure Cutout 2ABI11172Diagnostic: AFD Interrupt Failure 1ABI11173Diagnostic: AFD Interrupt Failure 2ABI11174Diagnostic: AFD Motor Current Overload 1ABI11175Diagnostic: AFD Motor Current Overload 1BBI11176Diagnostic: AFD Motor Current Overload 2ABI11177Diagnostic: AFD Motor Current Overload 2BBI11178Diagnostic: AFD Motor Fault 1ABI11179Diagnostic: AFD Motor Fault 2ABI11180Diagnostic: AFD Motor Speed Too High 1ABI11181Diagnostic: AFD Motor Speed Too High 2ABI11182Diagnostic: AFD Motor Speed Too Low 1ABI11183Diagnostic: AFD Motor Speed Too Low 2ABI11184Diagnostic: AFD Pump Out Speed Low 1ABI11185Diagnostic: AFD Pump Out Speed Low 2ABI11186Diagnostic: AFD Unexpected Shutdown 1ABI11187Diagnostic: AFD Unexpected Shutdown 2ABI11188Diagnostic: AFD Unhandled Fault 1ABI11189Diagnostic: AFD Unhandled Fault 2ABI11190Diagnostic: AOC Inlet Oil Temperature Sensor 1ABI11191Diagnostic: AOC Inlet Oil Temperature Sensor 2ABI11192Diagnostic: Check ClockBI11193Diagnostic: Chiller Service RecommendedBI11194Diagnostic: Comm Loss: Winding Temp 2, Cprsr2ABI11195Diagnostic: Cond Rfgt Liquid Level Sensor Ckt1BI11196Diagnostic: Cond Rfgt Liquid Level Sensor Ckt2BI11197Diagnostic: Condenser Entering Water Temp SensorBI11198Diagnostic: Condenser Leaving Water Temp SensorBI11199Diagnostic: Condenser Rfgt Pressure Sensor Ckt2BI11200Diagnostic: Condenser Rfgt Pressure Sensor Ckt1BI11201Diagnostic: Condenser Water Flow LostBI11202Diagnostic: Condenser Water Flow OverdueBI11203Diagnostic: Cprsr Did Not Accel: Shutdown 1ABI11204Diagnostic: Cprsr Did Not Accel: Shutdown 1BBI11205Diagnostic: Cprsr Did Not Accel: Shutdown 2ABI11206Diagnostic: Cprsr Did Not Accel: Shutdown 2BBI11207Diagnostic: Cprsr Did Not Accel: Transition 1ABI11208Diagnostic: Cprsr Did Not Accel: Transition 1BBI11209Diagnostic: Cprsr Did Not Accel: Transition 2ABI11210Diagnostic: Cprsr Did Not Accel: Transition 2BBI11211Diagnostic: Cprsr Disch Rfgt Temp Sensor 1ABI11212Diagnostic: Cprsr Disch Rfgt Temp Sensor 1BBI11213Diagnostic: Cprsr Disch Rfgt Temp Sensor 2ABI11214Diagnostic: Cprsr Disch Rfgt Temp Sensor 2BBI11215Diagnostic: Emergency Stop Feedback InputBI11216Diagnostic: Evap Iso Valve Illegal Switch State Ckt1BI11217Diagnostic: Evap Iso Valve Illegal Switch State Ckt2BI11218Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt1BI11219Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt2BI11220Diagnostic: Evap Isolation Valve Failed To Close Ckt1BI11221Diagnostic: Evap Isolation Valve Failed To Close Ckt2BI11222Diagnostic: Evap Isolation Valve Failed To Open Ckt1BI11223Diagnostic: Evap Isolation Valve Failed To Open Ckt2BI11224Diagnostic: Evap Isolation Valve Open Switch Failure Ckt1BI11225Diagnostic: Evap Isolation Valve Open Switch Failure Ckt2BI11226Diagnostic: Evap Pump 1 Starts Run time WrittenBI11227Diagnostic: Evap Pump 2 Starts Run time WrittenBI11228Diagnostic: Evap Rfgt Pool Temp Sensor Ckt1BI11229Diagnostic: Evap Rfgt Pool Temp Sensor Ckt2BI11230Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt1BI11231Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt2BI11232Diagnostic: Evap Spillover Liquid Level Sensor Ckt1BI11233Diagnostic: Evap Spillover Liquid Level Sensor Ckt2BI11234Diagnostic: Evap Water Pump 1 Svc RecommendedBI11235Diagnostic: Evap Water Pump 2 Svc RecommendedBI11236Diagnostic: Evaporator Approach Error Ckt2BI11237Diagnostic: Evaporator Approach Error Ckt1BI11238Diagnostic: Evaporator Entering Water PressureBI11239Diagnostic: Evaporator Entering Water Temp SensorBI11240Diagnostic: Evaporator Leaving Water PressureBI11241Diagnostic: Evaporator Leaving Water Temp SensorBI11242Diagnostic: Evaporator Oil Return Level Sensor, Ckt1BI11243Diagnostic: Evaporator Oil Return Level Sensor, Ckt2BI11244Diagnostic: Evaporator Pump 1 FaultBI11245Diagnostic: Evaporator Pump 2 FaultBI11246Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt1BI11247Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt2BI11248Diagnostic: Evaporator Water Flow LostBI11249Diagnostic: Evaporator Water Flow Lost Pump1BI11250Diagnostic: Evaporator Water Flow Lost Pump2BI11251Diagnostic: Evaporator Water Flow OverdueBI11252Diagnostic: Evaporator Water Flow Overdue Pump1BI11253Diagnostic: Evaporator Water Flow Overdue Pump2BI11254Diagnostic: Excessive Condenser Pressure Ckt2BI11255Diagnostic: Excessive Condenser Pressure Ckt1BI11256Diagnostic: External Chilled/Hot Water SetpointBI11257Diagnostic: External Demand Limit SetpointBI11258Diagnostic: EXV Pressure Equalization Failed Ckt1BI11259Diagnostic: EXV Pressure Equalization Failed Ckt2BI11260Diagnostic: Fan Inverter Fault Ckt1BI11261Diagnostic: Fan Inverter Fault Ckt2BI11262Diagnostic: Heat Recovery Entering Water Temp SensorBI11263Diagnostic: Heat Recovery Leaving Water Temp SensorBI11264Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 1ABI11265Diagnostic: High Cprsr Rfgt Discharge Temp 1ABI11266Diagnostic: High Cprsr Rfgt Discharge Temp 1BBI11267Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 2ABI11268Diagnostic: High Cprsr Rfgt Discharge Temp 2ABI11269Diagnostic: High Cprsr Rfgt Discharge Temp 2BBI11270Diagnostic: High Differential Refrigerant PressureBI11271Diagnostic: High Differential Rfgt Pressure 1ABI11272Diagnostic: High Differential Rfgt Pressure 1BBI11273Diagnostic: High Differential Rfgt Pressure 2ABI11274Diagnostic: High Differential Rfgt Pressure 2BBI11275Diagnostic: High Evap Shell Rfgt Pressure Ckt1BI11276Diagnostic: High Evap Shell Rfgt Pressure Ckt2BI11277Diagnostic: High Evaporator Water TemperatureBI11278Diagnostic: High Motor Winding Temperature 1ABI11279Diagnostic: High Motor Winding Temperature 2ABI11280Diagnostic: High Motor Winding Temperature Cprsr1ABI11281Diagnostic: High Motor Winding Temperature Cprsr2ABI11282Diagnostic: High Oil Temperature Ckt1BI11283Diagnostic: High Oil Temperature Ckt2BI11284Diagnostic: High Pressure Cutout Ckt2BI11285Diagnostic: High Pressure Cutout Ckt1BI11286Diagnostic: High Pressure Cutout 1ABI11287Diagnostic: High Pressure Cutout 1BBI11288Diagnostic: High Pressure Cutout 2ABI11289Diagnostic: High Pressure Cutout 2BBI11290Diagnostic: High Refrigerant Pressure RatioBI11291Diagnostic: High Refrigerant Pressure Ratio 1ABI11292Diagnostic: High Refrigerant Pressure Ratio 1BBI11293Diagnostic: High Refrigerant Pressure Ratio 2ABI11294Diagnostic: High Refrigerant Pressure Ratio 2BBI11295Diagnostic: Inverted Evaporator Water TemperatureBI11296Diagnostic: Liquid Line Pressure Sensor Ckt1BI11297Diagnostic: Liquid Line Pressure Sensor Ckt2BI11298Diagnostic: Liquid Line Temp Sensor Ckt1BI11299Diagnostic: Liquid Line Temp Sensor Ckt2BI11300Diagnostic: Loss of Oil for Compressor (Running) Ckt1BI11301Diagnostic: Loss of Oil for Compressor (Running) Ckt2BI11302Diagnostic: Loss of Oil for Compressor (Stopped) Ckt1BI11303Diagnostic: Loss of Oil for Compressor (Stopped) Ckt2BI11304Diagnostic: Low Condenser Rfgt Temp Ckt 1: Unit OffBI11305Diagnostic: Low Condenser Rfgt Temp Ckt 2: Unit OffBI11306Diagnostic: Low Differential Rfgt Pressure 1ABI11307Diagnostic: Low Differential Rfgt Pressure 1BBI11308Diagnostic: Low Differential Rfgt Pressure 2ABI11309Diagnostic: Low Differential Rfgt Pressure 2BBI11310Diagnostic: Low Discharge Superheat 1ABI11311Diagnostic: Low Discharge Superheat 1BBI11312Diagnostic: Low Discharge Superheat 2ABI11313Diagnostic: Low Discharge Superheat 2BBI11314Diagnostic: Low Evaporator Oil Return Level Ckt1BI11315Diagnostic: Low Evaporator Oil Return Level Ckt2BI11316Diagnostic: Low Evaporator Refrigerant Pressure Ckt1BI11317Diagnostic: Low Evaporator Refrigerant Pressure Ckt2BI11318Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit OffBI11319Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit OffBI11320Diagnostic: Low Evaporator Water Temp (Unit Off)BI11321Diagnostic: Low Evaporator Water Temp (Unit On)BI11322Diagnostic: Low Oil Flow 1ABI11323Diagnostic: Low Oil Flow 1BBI11324Diagnostic: Low Oil Flow 2ABI11325Diagnostic: Low Oil Flow 2BBI11326Diagnostic: Low Refrigerant Temperature Ckt2BI11327Diagnostic: Low Refrigerant Temperature Ckt1BI11328Diagnostic: Mfr Maintenance Recommended 1ABI11329Diagnostic: Mfr Maintenance Recommended 1BBI11330Diagnostic: Mfr Maintenance Recommended 2ABI11331Diagnostic: Mfr Maintenance Recommended 2BBI11332Diagnostic: Momentary Power Loss 1ABI11333Diagnostic: Momentary Power Loss 1BBI11334Diagnostic: Momentary Power Loss 2ABI11335Diagnostic: Momentary Power Loss 2BBI11336Diagnostic: Motor Current Overload 1ABI11337Diagnostic: Motor Current Overload 1BBI11338Diagnostic: Motor Current Overload 2ABI11339Diagnostic: Motor Current Overload 2BBI11340Diagnostic: Motor Winding Temp Sensor Cprsr1ABI11341Diagnostic: Motor Winding Temp Sensor Cprsr2ABI11342Diagnostic: MP: Invalid ConfigurationBI11343Diagnostic: MP: Non-Volatile Block Test ErrorBI11344Diagnostic: MP: Reset Has OccurredBI11345Diagnostic: Need Cprsr 1A To Run For Oil FlowBI11346Diagnostic: No Differential Rfgt Pressure 1ABI11347Diagnostic: No Differential Rfgt Pressure 1BBI11348Diagnostic: No Differential Rfgt Pressure 2ABI11349Diagnostic: No Differential Rfgt Pressure 2BBI11350Diagnostic: Oil Analysis Recommended Ckt1BI11351Diagnostic: Oil Analysis Recommended Ckt2BI11352Diagnostic: Oil Filter Change Recommended Cprsr1ABI11353Diagnostic: Oil Filter Change Recommended Cprsr2ABI11354Diagnostic: Oil Flow Protection Fault 1ABI11355Diagnostic: Oil Flow Protection Fault 1BBI11356Diagnostic: Oil Flow Protection Fault 2ABI11357Diagnostic: Oil Flow Protection Fault 2BBI11358Diagnostic: Oil Pressure Sensor 1ABI11359Diagnostic: Oil Pressure Sensor 1BBI11360Diagnostic: Oil Pressure Sensor 2ABI11361Diagnostic: Oil Pressure Sensor 2BBI11362Diagnostic: Oil Temperature Sensor, Circuit 1BI11363Diagnostic: Oil Temperature Sensor, Circuit 2BI11364Diagnostic: Outdoor Air Temperature SensorBI11365Diagnostic: Over VoltageBI11366Diagnostic: Over Voltage 1ABI11367Diagnostic: Over Voltage 2ABI11368Diagnostic: Phase Loss 1ABI11369Diagnostic: Phase Loss 1BBI11370Diagnostic: Phase Loss 2ABI11371Diagnostic: Phase Loss 2BBI11372Diagnostic: Phase Reversal 1ABI11373Diagnostic: Phase Reversal 1BBI11374Diagnostic: Phase Reversal 2ABI11375Diagnostic: Phase Reversal 2BBI11376Diagnostic: Power Loss 1ABI11377Diagnostic: Power Loss 1BBI11378Diagnostic: Power Loss 2ABI11379Diagnostic: Power Loss 2BBI11380Diagnostic: Pumpdown Terminated Ckt1BI11381Diagnostic: Pumpdown Terminated Ckt2BI11382Diagnostic: Pumpdown Terminated By Time Ckt2BI11383Diagnostic: Pumpdown Terminated By Time Ckt1BI11384Diagnostic: Refrigerant Charge Loss Detected Ckt1BI11385Diagnostic: Refrigerant Charge Loss Detected Ckt2BI11386Diagnostic: Restart Inhibit Invoked 1ABI11387Diagnostic: Restart Inhibit Invoked 1BBI11388Diagnostic: Restart Inhibit Invoked 2ABI11389Diagnostic: Restart Inhibit Invoked 2BBI11390Diagnostic: Severe Current Imbalance 1ABI11391Diagnostic: Severe Current Imbalance 1BBI11392Diagnostic: Severe Current Imbalance 2ABI11393Diagnostic: Severe Current Imbalance 2BBI11394Diagnostic: Software Error 1001: Call Trane ServiceBI11395Diagnostic: Software Error 1002: Call Trane ServiceBI11396Diagnostic: Software Error 1003: Call Trane ServiceBI11397Diagnostic: Starter Comm Loss: Main Processor 1ABI11398Diagnostic: Starter Comm Loss: Main Processor 1BBI11399Diagnostic: Starter Comm Loss: Main Processor 2ABI11400Diagnostic: Starter Comm Loss: Main Processor 2BBI11401Diagnostic: Starter Contactor Interrupt Failure 1ABI11402Diagnostic: Starter Contactor Interrupt Failure 1BBI11403Diagnostic: Starter Contactor Interrupt Failure 2ABI11404Diagnostic: Starter Contactor Interrupt Failure 2BBI11405Diagnostic: Starter Did Not Fully Accelerate 1BBI11406Diagnostic: Starter Did Not Fully Accelerate 1ABI11407Diagnostic: Starter Did Not Fully Accelerate 2BBI11408Diagnostic: Starter Did Not Transition 1ABI11409Diagnostic: Starter Did Not Transition 1BBI11410Diagnostic: Starter Did Not Transition 2ABI11411Diagnostic: Starter Did Not Transition 2BBI11412Diagnostic: Starter Dry Run Test 1ABI11413Diagnostic: Starter Dry Run Test 1BBI11414Diagnostic: Starter Dry Run Test 2ABI11415Diagnostic: Starter Dry Run Test 2BBI11416Diagnostic: Starter Failed to Arm/Start 1ABI11417Diagnostic: Starter Failed to Arm/Start 1BBI11418Diagnostic: Starter Failed to Arm/Start 2ABI11419Diagnostic: Starter Failed to Arm/Start 2BBI11420Diagnostic: Starter Fault Type I 1ABI11421Diagnostic: Starter Fault Type I 1BBI11422Diagnostic: Starter Fault Type I 2ABI11423Diagnostic: Starter Fault Type I 2BBI11424Diagnostic: Starter Fault Type II 1ABI11425Diagnostic: Starter Fault Type II 1BBI11426Diagnostic: Starter Fault Type II 2ABI11427Diagnostic: Starter Fault Type II 2BBI11428Diagnostic: Starter Fault Type III 1ABI11429Diagnostic: Starter Fault Type III 1BBI11430Diagnostic: Starter Fault Type III 2ABI11431Diagnostic: Starter Fault Type III 2BBI11432Diagnostic: Starter Module Memory Error Type 1 1ABI11433Diagnostic: Starter Module Memory Error Type 1 1BBI11434Diagnostic: Starter Module Memory Error Type 1 2ABI11435Diagnostic: Starter Module Memory Error Type 1 2BBI11436Diagnostic: Starter Module Memory Error Type 2 1ABI11437Diagnostic: Starter Module Memory Error Type 2 1BBI11438Diagnostic: Starter Module Memory Error Type 2 2ABI11439Diagnostic: Starter Module Memory Error Type 2 2BBI11440Diagnostic: Starts/Hours Modified 1ABI11441Diagnostic: Starts/Hours Modified 1BBI11442Diagnostic: Starts/Hours Modified 2ABI11443Diagnostic: Starts/Hours Modified 2BBI11444Diagnostic: Suction Pressure Transducer Ckt2BI11445Diagnostic: Suction Pressure Transducer Ckt1BI11446Diagnostic: Suction Refrigerant Pressure Sensor 1ABI11447Diagnostic: Suction Refrigerant Pressure Sensor 1BBI11448Diagnostic: Suction Refrigerant Pressure Sensor 2ABI11449Diagnostic: Suction Refrigerant Pressure Sensor 2BBI11450Diagnostic: Suction Temperature SensorBI11451Diagnostic: Transition Complete Input Opened 1ABI11452Diagnostic: Transition Complete Input Opened 1BBI11453Diagnostic: Transition Complete Input Opened 2ABI11454Diagnostic: Transition Complete Input Opened 2BBI11455Diagnostic: Transition Complete Input Shorted 1ABI11456Diagnostic: Transition Complete Input Shorted 1BBI11457Diagnostic: Transition Complete Input Shorted 2ABI11458Diagnostic: Transition Complete Input Shorted 2BBI11459Diagnostic: Under VoltageBI11460Diagnostic: Under Voltage 1ABI11461Diagnostic: Under Voltage 2ABI11462Diagnostic: Unexpected Starter Shutdown 1ABI11463Diagnostic: Unexpected Starter Shutdown 1BBI11464Diagnostic: Unexpected Starter Shutdown 2ABI11465Diagnostic: Unexpected Starter Shutdown 2BBI11466Diagnostic: Very Low Discharge Superheat 1ABI11467Diagnostic: Very Low Discharge Superheat 2ABI11468Diagnostic: Very Low Evap Rfgt Pressure 1ABI11469Diagnostic: Very Low Evap Rfgt Pressure 1BBI11470Diagnostic: Very Low Evap Rfgt Pressure 2ABI11471Diagnostic: Very Low Evap Rfgt Pressure 2BBI11472Diagnostic: Water System Differential PressureBI11473Diagnostic: Energy Meter Write Value FailureBI11474Diagnostic: Write Command Failure Energy Meter 1BI11475Diagnostic: Write Command Failure Energy Meter 2BI11476Diagnostic: High Evaporator PressureBI11477Comm Loss: Starter Panel High Temperature LimitBV10100Chiller Auto Stop Command BASBV10101Reset DiagnosticBV10102Circuit 1 Lockout BASBV10103Circuit 2 Lockout BASBV10104Energy Consumption ResetBV10105Noise Reduction Request BASBV10106Compressor 1A Lockout BASBV10107Compressor 1B Lockout BASBV10108Compressor 2A Lockout BASBV10109Compressor 2B Lockout BASBV10110Evaporator Water Pump Request BASBV10111Condenser Water Pump Request BASMI10100Running ModeMI10101Operating ModeMI10103Refrigerant TypeMI10104Manufacturing LocationMI10105Cooling TypeMI10106Model Information [GEN2]MV10100Chiller Mode Command BAS
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the actual engineering unit is the factory-configured I-P or SI set.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Series R RTWD and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 Series R RTWD
How many BACnet points does the Trane Symbio 800 Series R RTWD have?
This list has 685 BACnet objects: 144 analog inputs, 7 analog values, 515 binary inputs, 12 binary values, 6 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 Series R RTWD BACnet points are writable?
20 of the 685 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 Series R RTWD BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - Series R Model RTWD (BAS-PTS017A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS017A-EN_11152024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 Series R RTWD?
Start with BV 10100 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10103 Chiller Running State (Chiller on/off status); BI 10101 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10103 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10108 Actual Running Capacity (Actual running capacity in percent); BI 10108 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 Series R RTWD?
BV 10100 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10120 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.
How do I check these points on the real Symbio 800 Series R RTWD?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet - Series R Model RTWD · BAS-PTS017A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.