Updated 28 October 2026
Duplex CenTraVac chillers use the same object names and types as the simplex list, but different instance numbers, and add circuit 2 / compressor 2 points, for about 720 objects in total. Setpoints and commands are AV/BV/MV objects; status is AI/BI/MI. Most binary inputs are per-alarm diagnostic flags.
This page lists 717 BACnet objects for the Trane Symbio 800 CenTraVac (Duplex) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 CenTraVac (Duplex)
- Equipment
- Centrifugal chiller controller
- Equipment type
- Chillers
- BACnet objects
- 717 (17 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 CenTraVac (Duplex)
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10104 | Chiller Auto Stop Command BAS | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10111 | Chiller Running State | Chiller on/off status | Read |
| BI 10104 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10106 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10151 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10116 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10126 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10103 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
Trane Symbio 800 CenTraVac (Duplex) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Chilled Water Setpoint | Temperature | Read | ||
| AI | 10101 | Chilled Water Setpoint Status | Temperature | Read | ||
| AI | 10102 | Active Base Loading Setpoint | Percentage | Read | ||
| AI | 10103 | Hot Water Setpoint Active | Temperature | Read | ||
| AI | 10104 | Calculated Chiller Capacity | Power, Cooling | Read | ||
| AI | 10105 | Active Cool/Heat Setpoint Temperature | Temperature | Read | ||
| AImin | 10106 | Evaporator Leaving Water Temperature | Temperature | Read | ||
| AI | 10107 | Evaporator Entering Water Temperature | Temperature | Read | ||
| AI | 10108 | Condenser Entering Water Temperature | Temperature | Read | ||
| AI | 10109 | Condenser Leaving Water Temperature | Temperature | Read | ||
| AI | 10110 | Evaporator Water Flow Rate | Flow, Water | Read | ||
| AI | 10111 | Evaporator Differential Water Pressure | Differential Pressure | Read | ||
| AI | 10112 | Condenser Water Flow Rate | Flow, Water | Read | ||
| AI | 10113 | Condenser Differential Water Pressure | Differential Pressure | Read | ||
| AI | 10114 | AFD Last Diagnostic Code Ckt1 | Read | |||
| AI | 10115 | Unit Source ID (Last Diagnostic Code) | Read | |||
| AI | 10116 | Refrigerant Monitor | Concentration | Read | ||
| AI | 10117 | Evaporator Refrigerant Pressure Circuit 1 | Pressure | Read | ||
| AI | 10118 | Condenser Refrigerant Pressure Circuit 1 | Pressure | Read | ||
| AI | 10119 | Differential Refrigerant Pressure Circuit 1 | Differential Pressure | Read | ||
| AI | 10120 | Low Side Oil Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10121 | High Side Oil Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10122 | Oil Differential Pressure Circuit 1 | Differential Pressure | Read | ||
| AI | 10123 | Oil Temperature - Compressor 1A | Temperature | Read | ||
| AI | 10124 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature | Read | ||
| AI | 10125 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature | Read | ||
| AI | 10126 | Refrigerant Discharge Temperature - Compressor 1A | Temperature | Read | ||
| AI | 10127 | Inlet Guide Vane 1 Percent Open Circuit 1 | Percentage | Read | ||
| AI | 10128 | Inlet Guide Vane 2 Percent Open Circuit 1 | Percentage | Read | ||
| AI | 10129 | Purge Carbon Tank Temperature Circuit 1 | Temperature | Read | ||
| AI | 10130 | Purge Liquid Temperature Circuit 1 | Temperature | Read | ||
| AI | 10131 | Purge Refrigerant Compressor Suction Temperature Circuit 1 | Temperature | Read | ||
| AI | 10132 | Time Until Next Purge Run Circuit 1 (in seconds) | Read | |||
| AI | 10133 | Purge Pumpout Chiller On % (7 Days) Circuit 1 | Percentage | Read | ||
| AI | 10134 | Purge Pumpout Chiller Off % (7 Days) Circuit 1 | Percentage | Read | ||
| AI | 10135 | Purge 24 Hour Pumpout Circuit 1 (in seconds) | Read | |||
| AI | 10136 | Purge Pumpout - Life Circuit 1 (in seconds) | Read | |||
| AI | 10137 | Refrigeration - Life Circuit 1 (in seconds) | Read | |||
| AI | 10138 | Starts - Compressor 1A | Read | |||
| AI | 10139 | Run Time - Compressor 1A (in seconds) | Read | |||
| AI | 10140 | Phase AB Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10141 | Phase BC Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10142 | Phase CA Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10143 | Starter Average Phase Volt Circuit 1 | Voltage | Read | ||
| AI | 10144 | Line 1 Current - Compressor 1A | Current | Read | ||
| AI | 10145 | Line 2 Current - Compressor 1A | Current | Read | ||
| AI | 10146 | Line 3 Current - Compressor 1A | Current | Read | ||
| AI | 10147 | Average Line Current Circuit 1 | Current | Read | ||
| AI | 10148 | Line 1 Current RLA - Compressor 1A | Percentage | Read | ||
| AI | 10149 | Line 2 Current RLA - Compressor 1A | Percentage | Read | ||
| AI | 10150 | Line 3 Current RLA - Compressor 1A | Percentage | Read | ||
| AImin | 10151 | Actual Running Capacity | Percentage | Read | ||
| AI | 10153 | Starter Load Power Factor - Compressor 1A | Read | |||
| AI | 10154 | Inboard Bearing Temperature Circuit 1 | Temperature | Read | ||
| AI | 10155 | Outboard Bearing Temperature Circuit 1 | Temperature | Read | ||
| AI | 10156 | Motor Winding Temperature 1 Circuit 1 | Temperature | Read | ||
| AI | 10157 | Motor Winding Temperature 2 Circuit 1 | Temperature | Read | ||
| AI | 10158 | Motor Winding Temperature 3 Circuit 1 | Temperature | Read | ||
| AI | 10159 | AFD Frequency Circuit 1 | Read | |||
| AI | 10160 | AFD Transistor Temperature Circuit 1 | Temperature | Read | ||
| AI | 10161 | Drive Average Line Current Circuit 1 | Current | Read | ||
| AI | 10162 | Drive Line Frequency Circuit 1 | Read | |||
| AI | 10163 | Drive Motor Voltage Circuit 1 | Voltage | Read | ||
| AI | 10164 | Drive Inverter Base Temperature Circuit 1 | Temperature | Read | ||
| AI | 10165 | Drive Rectifier Base Temperature Circuit 1 | Temperature | Read | ||
| AI | 10166 | Drive Output Power Circuit 1 | Power, Electrical | Read | ||
| AI | 10167 | Frequency Command Circuit 1 | Read | |||
| AI | 10168 | Outboard Bearing Pad Temperature #1 Ckt1 | Temperature | Read | ||
| AI | 10169 | Outboard Bearing Pad Temperature #2 Ckt1 | Temperature | Read | ||
| AI | 10170 | Outboard Bearing Pad Temperature #3 Ckt1 | Temperature | Read | ||
| AI | 10171 | Restart Inhibit Time Remaining Circuit 1 | Read | |||
| AI | 10172 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10173 | Entering Condenser Water Pressure | Pressure | Read | ||
| AI | 10174 | Entering Evaporator Water Pressure | Pressure | Read | ||
| AI | 10175 | Leaving Condenser Water Pressure | Pressure | Read | ||
| AI | 10176 | Leaving Evaporator Water Pressure | Pressure | Read | ||
| AI | 10177 | Condenser Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10178 | Evaporator Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10179 | Drive DC Bus Voltage Circuit 1 | Voltage | Read | ||
| AI | 10180 | Drive Motor Average Current RLA Circuit 1 | Percentage | Read | ||
| AI | 10182 | Active Demand Limit Setpoint | Percentage | Read | ||
| AI | 10183 | Active Demand Limit Setpoint | Percentage | Read | ||
| AI | 10184 | Demand Limit Setpoint Status | Percentage | Read | ||
| AI | 10185 | Number of Circuits | Read | |||
| AI | 10186 | Number of Compressors Circuit 1 | Read | |||
| AI | 10187 | Number of Compressors Circuit 2 | Read | |||
| AI | 10188 | Low Side Oil Pressure - Compressor 2A | Pressure | Read | ||
| AI | 10189 | High Side Oil Pressure - Compressor 2A | Pressure | Read | ||
| AI | 10190 | Oil Differential Pressure Circuit 2 | Differential Pressure | Read | ||
| AI | 10191 | Oil Temperature - Compressor 2A | Temperature | Read | ||
| AI | 10192 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Temperature | Read | ||
| AI | 10193 | Condenser Saturated Refrigerant Temperature Circuit 2 | Temperature | Read | ||
| AI | 10194 | Refrigerant Discharge Temperature - Compressor 2A | Temperature | Read | ||
| AI | 10195 | Inlet Guide Vane 1 Percent Open Circuit 2 | Percentage | Read | ||
| AI | 10196 | Inlet Guide Vane 2 Percent Open Circuit 2 | Percentage | Read | ||
| AI | 10197 | Purge Carbon Tank Temperature Circuit 2 | Temperature | Read | ||
| AI | 10198 | Purge Liquid Temperature Circuit 2 | Temperature | Read | ||
| AI | 10199 | Purge Refrigerant Compressor Suction Temperature Circuit 2 | Temperature | Read | ||
| AI | 10200 | Time Until Next Purge Run Circuit 2 (in seconds) | Read | |||
| AI | 10201 | Refrigeration - Life Circuit 2 (in seconds) | Read | |||
| AI | 10202 | Starts - Compressor 2A | Read | |||
| AI | 10203 | Run Time - Compressor 2A (in seconds) | Read | |||
| AI | 10204 | Starter Average Phase Volt Circuit 2 | Voltage | Read | ||
| AI | 10205 | Line 1 Current - Compressor 2A | Current | Read | ||
| AI | 10206 | Line 2 Current - Compressor 2A | Current | Read | ||
| AI | 10207 | Line 3 Current - Compressor 2A | Current | Read | ||
| AI | 10208 | Average Line Current Circuit 2 | Current | Read | ||
| AI | 10209 | Drive Average Line Current Circuit 2 | Current | Read | ||
| AI | 10210 | Starter Load Power Factor - Compressor 2A | Read | |||
| AI | 10211 | Inboard Bearing Temperature Circuit 2 | Temperature | Read | ||
| AI | 10212 | Outboard Bearing Temperature Circuit 2 | Temperature | Read | ||
| AI | 10213 | Motor Winding Temperature 1 Circuit 2 | Temperature | Read | ||
| AI | 10214 | Motor Winding Temperature 2 Circuit 2 | Temperature | Read | ||
| AI | 10215 | Motor Winding Temperature 3 Circuit 2 | Temperature | Read | ||
| AI | 10216 | AFD Transistor Temperature Circuit 2 | Temperature | Read | ||
| AI | 10217 | Heat Recovery Entering Water Temp | Temperature | Read | ||
| AI | 10218 | Heat Recovery Leaving Water Temp | Temperature | Read | ||
| AI | 10219 | Purge Pumpout Chiller On % (7 Days) Circuit 2 | Percentage | Read | ||
| AI | 10220 | Purge Pumpout Chiller Off % (7 Days) Circuit 2 | Percentage | Read | ||
| AI | 10221 | Purge 24 Hour Pumpout Circuit 2 (in seconds) | Read | |||
| AI | 10222 | Phase AB Voltage - Compressor 2A | Voltage | Read | ||
| AI | 10223 | Phase BC Voltage - Compressor 2A | Voltage | Read | ||
| AI | 10224 | Phase CA Voltage - Compressor 2A | Voltage | Read | ||
| AI | 10225 | Purge Pumpout - Life Circuit 2 (in seconds) | Read | |||
| AI | 10226 | Drive Motor Average Current RLA Circuit 2 | Percentage | Read | ||
| AI | 10227 | Drive Inverter Base Temperature Circuit 2 | Temperature | Read | ||
| AI | 10228 | Drive Rectifier Base Temperature Circuit 2 | Temperature | Read | ||
| AI | 10229 | Outboard Bearing Pad Temperature #1 Ckt2 | Temperature | Read | ||
| AI | 10230 | Outboard Bearing Pad Temperature #2 Ckt2 | Temperature | Read | ||
| AI | 10231 | Outboard Bearing Pad Temperature #3 Ckt2 | Temperature | Read | ||
| AI | 10232 | Evaporator Refrigerant Pressure Circuit 2 | Pressure | Read | ||
| AI | 10233 | Condenser Refrigerant Pressure Circuit 2 | Pressure | Read | ||
| AI | 10234 | Differential Refrigerant Pressure Circuit 2 | Differential Pressure | Read | ||
| AI | 10235 | Restart Inhibit Time Remaining Circuit 2 | Read | |||
| AI | 10236 | AFD Frequency Circuit 2 | Read | |||
| AI | 10237 | Drive Line Frequency Circuit 2 | Read | |||
| AI | 10238 | Frequency Command Circuit 2 | Read | |||
| AI | 10239 | Drive DC Bus Voltage Circuit 2 | Voltage | Read | ||
| AI | 10240 | Drive Output Power Circuit 2 | Power, Electrical | Read | ||
| AI | 10241 | Line 1 Current RLA - Compressor 2A | Percentage | Read | ||
| AI | 10242 | Line 2 Current RLA - Compressor 2A | Percentage | Read | ||
| AI | 10243 | Line 3 Current RLA - Compressor 2A | Percentage | Read | ||
| AI | 10244 | Drive Current Line 1 Circuit 1 | Current | Read | ||
| AI | 10245 | Drive Current Line 2 Circuit 1 | Current | Read | ||
| AI | 10246 | Drive Current Line 3 Circuit 1 | Current | Read | ||
| AI | 10247 | Drive Current Line 1 Circuit 2 | Current | Read | ||
| AI | 10248 | Drive Current Line 2 Circuit 2 | Current | Read | ||
| AI | 10249 | Drive Current Line 3 Circuit 2 | Current | Read | ||
| AI | 10250 | Starter Input Power Consumption Ckt1 | Power, Electrical | Read | ||
| AI | 10251 | Starter Input Power Consumption Ckt2 | Power, Electrical | Read | ||
| AI | 10252 | Drive Motor Voltage Circuit 2 | Voltage | Read | ||
| AI | 10253 | Chiller Control Signal | Percentage | Read | ||
| AI | 10254 | Head Pressure Control Status | Percentage | Read | ||
| AI | 10255 | AFD Last Diagnostic Code Ckt2 | Read | |||
| AI | 10256 | Voltage L1-L2 Circuit 1 | Voltage | Read | ||
| AI | 10257 | Voltage L1-L3 Circuit 1 | Voltage | Read | ||
| AI | 10258 | Voltage L2-L3 Circuit 1 | Voltage | Read | ||
| AI | 10259 | Voltage L1-L2 Circuit 2 | Voltage | Read | ||
| AI | 10260 | Voltage L1-L3 Circuit 2 | Voltage | Read | ||
| AI | 10261 | Voltage L2-L3 Circuit 2 | Voltage | Read | ||
| AI | 10262 | Average Line Voltage Circuit 1 | Voltage | Read | ||
| AI | 10263 | Average Line Voltage Circuit 2 | Voltage | Read | ||
| AI | 10264 | Line Current L1 Circuit 1 | Current | Read | ||
| AI | 10265 | Line Current L2 Circuit 1 | Current | Read | ||
| AI | 10266 | Line Current L3 Circuit 1 | Current | Read | ||
| AI | 10267 | Line Current L1 Circuit 2 | Current | Read | ||
| AI | 10268 | Line Current L2 Circuit 2 | Current | Read | ||
| AI | 10269 | Line Current L3 Circuit 2 | Current | Read | ||
| AI | 10270 | Unit Average Line Current Circuit 1 | Current | Read | ||
| AI | 10271 | Unit Average Line Current Circuit 2 | Current | Read | ||
| AI | 10272 | Line Frequency Circuit 1 | Read | |||
| AI | 10273 | Line Frequency Circuit 2 | Read | |||
| AI | 10274 | Power Factor Circuit 1 | Read | |||
| AI | 10275 | Power Factor Circuit 2 | Read | |||
| AI | 10276 | Power Demand Circuit 1 | Power, Electrical | Read | ||
| AI | 10277 | Power Demand Circuit 2 | Power, Electrical | Read | ||
| AI | 10278 | Total Real Power | Power, Electrical | Read | ||
| AI | 10279 | Unit Power Consumption | Power, Electrical | Read | ||
| AI | 10280 | Energy Consumption | Energy, Electrical | Read | ||
| AI | 10281 | Energy Consumption Lifetime | Energy, Electrical | Read | ||
| AI | 10282 | Condenser Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10283 | Evaporator Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10284 | Drive Input Voltage Calculated 1A | Voltage | Read | ||
| AI | 10285 | Drive Input Voltage Calculated 2A | Voltage | Read | ||
| AI | 10286 | Drive Heatsink Temperature Compressor 1A | Temperature | Read | ||
| AI | 10287 | Drive Heatsink Temperature Compressor 2A | Temperature | Read | ||
| AI | 10288 | Outdoor Air Temperature Local | Temperature | Read | ||
| AI | 10289 | Heat Recovery Differential Water Pressure | Pressure | Read | ||
| AI | 10290 | Heat Recovery Water Flow Rate | Flow, Water | Read | ||
| AI | 10291 | Heat Recovery Calculated Capacity | Power, Heating | Read | ||
| AI | 10292 | Heat Recovery Entering Water Pressure | Pressure | Read | ||
| AI | 10293 | Heat Recovery Leaving Water Pressure | Pressure | Read | ||
| AI | 10294 | Heat Recovery Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10295 | Heat Recovery Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10296 | High Side Oil Gauge Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10297 | Low Side Oil Gauge Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10298 | High Side Oil Gauge Pressure - Compressor 2A | Pressure | Read | ||
| AI | 10299 | Low Side Oil Gauge Pressure - Compressor 2A | Pressure | Read | ||
| AI | 10300 | Condenser Refrigerant Gauge Pressure Circuit 1 | Pressure | Read | ||
| AI | 10301 | Condenser Refrigerant Gauge Pressure Circuit 2 | Pressure | Read | ||
| AI | 10302 | Entering Condenser Water Gauge Pressure | Pressure | Read | ||
| AI | 10303 | Entering Evaporator Water Gauge Pressure | Pressure | Read | ||
| AI | 10304 | Evaporator Refrigerant Gauge Pressure Circuit 1 | Pressure | Read | ||
| AI | 10305 | Evaporator Refrigerant Gauge Pressure Circuit 2 | Pressure | Read | ||
| AI | 10306 | Heat Recovery Entering Water Gauge Pressure | Pressure | Read | ||
| AI | 10307 | Heat Recovery Leaving Water Gauge Pressure | Pressure | Read | ||
| AI | 10308 | Leaving Condenser Water Gauge Pressure | Pressure | Read | ||
| AI | 10309 | Leaving Evaporator Water Gauge Pressure | Pressure | Read | ||
| AI | 10310 | Compressor Discharge Superheat Circuit 1 | Temperature, Delta | Read | ||
| AI | 10311 | Compressor Discharge Superheat Circuit 2 | Temperature, Delta | Read | ||
| AI | 10312 | Unit Load Command | Percentage | Read | ||
| AI | 10313 | Drive Motor Current U RLA Circuit 1 | Percentage | Read | ||
| AI | 10314 | Drive Motor Current V RLA Circuit 1 | Percentage | Read | ||
| AI | 10315 | Drive Motor Current W RLA Circuit 1 | Percentage | Read | ||
| AI | 10316 | Drive Motor Current U Circuit 1 | Current | Read | ||
| AI | 10317 | Drive Motor Current V Circuit 1 | Current | Read | ||
| AI | 10318 | Drive Motor Current W Circuit 1 | Current | Read | ||
| AI | 10319 | Drive Motor Current U RLA Circuit 2 | Percentage | Read | ||
| AI | 10320 | Drive Motor Current V RLA Circuit 2 | Percentage | Read | ||
| AI | 10321 | Drive Motor Current W RLA Circuit 2 | Percentage | Read | ||
| AI | 10322 | Drive Motor Current U Circuit 2 | Current | Read | ||
| AI | 10323 | Drive Motor Current V Circuit 2 | Current | Read | ||
| AI | 10324 | Drive Motor Current W Circuit 2 | Current | Read | ||
| AI | 10325 | Active Cooling Differential to Start | Temperature, Delta | Read | ||
| AI | 10326 | Active Cooling Differential to Stop | Temperature, Delta | Read | ||
| AI | 10327 | Active Heating Differential to Start | Temperature, Delta | Read | ||
| AI | 10328 | Active Heating Differential to Stop | Temperature, Delta | Read | ||
| AVmin | 10100 | Chilled Water Setpoint | Temperature | Write | ||
| AVmin | 10101 | Demand Limit Setpoint | Percent | Write | ||
| AV | 10102 | Hot Water Setpoint | Temperature | Write | ||
| AV | 10103 | Base Loading Setpoint | Percent | Write | ||
| AV | 10104 | BAS Cooling Differential to Start | Temperature, Delta | Write | ||
| AV | 10105 | BAS Cooling Differential to Stop | Temperature, Delta | Write | ||
| AV | 10106 | BAS Heating Differential to Start | Temperature, Delta | Write | ||
| AV | 10107 | BAS Heating Differential to Stop | Temperature, Delta | Write | ||
| BI | 10101 | Manual Override Exists | Read | 0 = Off, 1 = On | ||
| BI | 10102 | Base Loading Request Active | Read | 0 = Inactive, 1 = Active | ||
| BI | 10103 | Run Enabled | Read | 0 = Run Not Enabled, 1 = Run Enabled | ||
| BImin | 10104 | Local Setpoint Control | Read | 0 = Remote Control, 1 = Local Control | ||
| BI | 10105 | Maximum Capacity | Read | 0 = Off, 1 = On | ||
| BI | 10106 | Capacity Limited | Read | 0 = Not Limited, 1 = Limited | ||
| BI | 10107 | Head Relief Request | Read | 0 = Off, 1 = On | ||
| BI | 10108 | Purge Compressor Relay Circuit 1 | Read | 0 = Off, 1 = On | ||
| BI | 10109 | Pump Out Relay Circuit 1 | Read | 0 = Off, 1 = On | ||
| BI | 10110 | Purge Regenerating Valve Solenoid Circuit 1 | Read | 0 = Off, 1 = On | ||
| BImin | 10111 | Chiller Running State | Read | 0 = Off, 1 = On | ||
| BI | 10112 | Evaporator Water Pump Request | Read | 0 = Off, 1 = On | ||
| BI | 10113 | Evaporator Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BI | 10114 | Condenser Water Pump Request | Read | 0 = Off, 1 = On | ||
| BI | 10115 | Condenser Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BImin | 10116 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10117 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10118 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10119 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10120 | Diagnostic Present: Information | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10121 | Diagnostic Present: Advisory | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10122 | Diagnostic Present: Critical | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10123 | Diagnostic Present: Service Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10124 | Compressor 1A Status | Read | 0 = Off, 1 = Running | ||
| BI | 10125 | Front Panel Auto Stop | Read | 0 = Stop, 1 = Auto | ||
| BI | 10126 | External Auto Stop Input Status | Read | 0 = Stop, 1 = Auto | ||
| BI | 10127 | Purge Compressor Relay Circuit 2 | Read | 0 = Off, 1 = On | ||
| BI | 10128 | Purge Regenerating Valve Solenoid Circuit 2 | Read | 0 = Off, 1 = On | ||
| BI | 10130 | Pump Out Relay Circuit 2 | Read | 0 = Off, 1 = On | ||
| BI | 10131 | Compressor 2A Status | Read | 0 = Off, 1 = Running | ||
| BI | 10132 | Emergency Stop | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | ||
| BI | 10133 | Circuit 1 Cooling Available | Read | 0 = No, 1 = Yes | ||
| BI | 10134 | Circuit 2 Cooling Available | Read | 0 = No, 1 = Yes | ||
| BI | 10135 | Circuit 1 Lockout Front Panel | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10136 | Circuit 2 Lockout Front Panel | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10137 | Circuit 1 Lockout External | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10138 | Circuit 2 Lockout External | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10139 | Circuit 1 Lockout Active | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10140 | Circuit 2 Lockout Active | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10141 | Diagnostic Shutdown Present: AFD/Starter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10142 | Diagnostic Shutdown Present: AFD/Starter Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10143 | Heat Recovery Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BI | 11000 | Diagnostic: AFD Comm Loss: Main Processor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Diagnostic: AFD Comm Loss: Main Processor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Diagnostic: AFD Control Board Memory Error Type 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Diagnostic: AFD DPI Communication Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Diagnostic: AFD DPI Communication Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Diagnostic: AFD Fatal Software Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Diagnostic: AFD Fatal Software Error Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Diagnostic: AFD General Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Diagnostic: AFD General Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Diagnostic: AFD Ground Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Diagnostic: AFD Ground Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Diagnostic: AFD High Bus Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Diagnostic: AFD High Bus Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Diagnostic: AFD High Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Diagnostic: AFD High Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Diagnostic: AFD I/O Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Diagnostic: AFD I/O Board Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Diagnostic: AFD Instantaneous Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Diagnostic: AFD Instantaneous Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Diagnostic: AFD Interrupt Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Diagnostic: AFD Interrupt Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Diagnostic: AFD Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Diagnostic: AFD Motor Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Diagnostic: AFD Motor Short Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Diagnostic: AFD Motor Short Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Diagnostic: AFD Output Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Diagnostic: AFD Output Phase Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Diagnostic: AFD Power Intfc Controller Board Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Diagnostic: AFD Power Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Diagnostic: AFD Power Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Diagnostic: AFD Power Structure Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Diagnostic: AFD Power Structure Board Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Diagnostic: At Speed Input Opened Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Diagnostic: At Speed Input Opened Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Diagnostic: At Speed Input Shorted Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Diagnostic: At Speed Input Shorted Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Diagnostic: Check Clock | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Diagnostic: Check Oil Filter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Diagnostic: Check Oil Filter Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Diagnostic: Check Oil Heater Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Diagnostic: Check Oil Heater Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Comm Loss: Adaptive Frequency Drive Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Comm Loss: Adaptive Frequency Drive Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Comm Loss: AFD Speed Signal VDC Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Comm Loss: AFD Speed Signal VDC Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Comm Loss: Compressor Motor % RLA Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Comm Loss: Compressor Motor % RLA Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Comm Loss: Cond Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Comm Loss: Cond Head Press Cntrl Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Comm Loss: Cond High Pressure Cutout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Comm Loss: Cond High Pressure Cutout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Comm Loss: Cond Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Comm Loss: Cond Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Comm Loss: Cond Rfgt Pressure Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Comm Loss: Cond Rfgt Pressure Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Comm Loss: Cond Saturated Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Comm Loss: Cond Saturated Rfgt Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Comm Loss: Condenser Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Comm Loss: Condenser Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Comm Loss: Condenser Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Comm Loss: Condenser Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Comm Loss: Condenser Liquid Level Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Comm Loss: Condenser Liquid Level Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Comm Loss: Condenser Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Comm Loss: Condenser Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Comm Loss: Economizer Bypass Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Comm Loss: Economizer Bypass Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Comm Loss: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Comm Loss: Energy Meter 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Comm Loss: Energy Meter 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Comm Loss: Evap Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Comm Loss: Evap Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Comm Loss: Evap Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Comm Loss: Evap Sat Refrig Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Comm Loss: Evap Sat Refrig Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Comm Loss: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Comm Loss: Evaporator Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Comm Loss: Ext Base Loading Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Comm Loss: Ext Base Loading Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Comm Loss: External Ckt Lockout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Comm Loss: External Ckt Lockout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Comm Loss: External Hot Water Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Comm Loss: Generator Fault Input Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Comm Loss: Generator Fault Input Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Comm Loss: Generator Speed Signal Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Comm Loss: Generator Speed Signal Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss: Generator Start/Stop Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Comm Loss: Generator Start/Stop Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Comm Loss: Generator Up To Speed Input Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Comm Loss: Generator Up To Speed Input Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Comm Loss: Heat Recovery Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Comm Loss: Heat Recovery Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Comm Loss: Ice Building Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: IGV First Stage Actuator Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: IGV First Stage Actuator Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Comm Loss: IGV Second Stage Actuator Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Comm Loss: IGV Second Stage Actuator Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Comm Loss: Inboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Comm Loss: Inboard Bearing Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Comm Loss: Motor Winding Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: Motor Winding Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Comm Loss: Motor Winding Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Motor Winding Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Comm Loss: Motor Winding Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Comm Loss: Motor Winding Temperature 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Comm Loss: Oil Cooler Solenoid Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Comm Loss: Oil Cooler Solenoid Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Comm Loss: Oil Pump Discharge Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Comm Loss: Oil Pump Discharge Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Comm Loss: Oil Tank Heater 4E1 Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Oil Tank Heater 4E2 Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Comm Loss: Oil Tank Heater Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Comm Loss: Oil Tank Heater Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Comm Loss: Oil Tank Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Oil Tank Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Oil Tank Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Comm Loss: Oil Tank Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Oil Vent Line Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: Oil Vent Line Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Comm Loss: Oil/Refrigerant Pump Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Comm Loss: Oil/Refrigerant Pump Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Outboard Bearing Pad Temp 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Comm Loss: Outboard Bearing Pad Temp 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Comm Loss: Outboard Bearing Pad Temp 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Comm Loss: Outboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Comm Loss: Outboard Bearing Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Comm Loss: Purge Alarm Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Comm Loss: Purge Alarm Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Comm Loss: Purge Carbon Tank Heater Rly Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Comm Loss: Purge Carbon Tank Heater Rly Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Comm Loss: Purge Carbon Tank Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Comm Loss: Purge Carbon Tank Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Comm Loss: Purge Condensing Unit Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Comm Loss: Purge Condensing Unit Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Comm Loss: Purge Exhaust Solenoid Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Comm Loss: Purge Exhaust Solenoid Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Comm Loss: Purge Liquid Level Switch Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Comm Loss: Purge Liquid Level Switch Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Comm Loss: Purge Liquid Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Comm Loss: Purge Liquid Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Comm Loss: Purge Pumpout Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Comm Loss: Purge Pumpout Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Comm Loss: Purge Pumpout Solenoid Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Comm Loss: Purge Pumpout Solenoid Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Comm Loss: Purge Regen Solenoid Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Comm Loss: Purge Regen Solenoid Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Comm Loss: Refrigerant Monitor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Comm Loss: Starter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Comm Loss: Starter Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Comm Loss: Starter Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Comm Loss: Starter Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Comm Loss: Unit Purge Alarm Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Diagnostic: Condenser Diff Water Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Diagnostic: Condenser Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Diagnostic: Condenser Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Diagnostic: Condenser High Pressure Cutout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Diagnostic: Condenser High Pressure Cutout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Diagnostic: Condenser Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: Condenser Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: Condenser Liquid Level Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Diagnostic: Condenser Liquid Level Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: Condenser Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: Condenser Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Diagnostic: Differential Oil Pressure Overdue Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Diagnostic: Differential Oil Pressure Overdue Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Diagnostic: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Diagnostic: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: Excessive Loss of Communication | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: Extended Compressor Surge Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: Extended Compressor Surge Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: External Base Loading Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: Generator Fault Relay Open Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Diagnostic: Generator Fault Relay Open Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: Generator Ready Signal Overdue Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Diagnostic: Generator Ready Signal Overdue Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: High Differential Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: High Differential Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Diagnostic: High Inboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11244 | Diagnostic: High Inboard Bearing Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11245 | Diagnostic: High Motor Winding Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11246 | Diagnostic: High Motor Winding Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11247 | Diagnostic: High Motor Winding Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11248 | Diagnostic: High Motor Winding Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11249 | Diagnostic: High Motor Winding Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11250 | Diagnostic: High Motor Winding Temperature 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11251 | Diagnostic: High Oil Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11252 | Diagnostic: High Oil Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11253 | Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11254 | Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11255 | Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11256 | Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11257 | Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11258 | Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11259 | Diagnostic: High Outboard Bearing Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11260 | Diagnostic: High Outboard Bearing Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11261 | Diagnostic: High Vacuum Lockout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11262 | Diagnostic: High Vacuum Lockout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11266 | Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11267 | Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11268 | Diagnostic: Inboard Bearing Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11269 | Diagnostic: Inboard Bearing Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11270 | Diagnostic: Inverted Condenser Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11271 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11272 | Diagnostic: Loss of Economizer Bypass Valve Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11273 | Diagnostic: Loss of Economizer Bypass Valve Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11274 | Diagnostic: Low Differential Oil Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11275 | Diagnostic: Low Differential Oil Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11276 | Diagnostic: Low Evap Leaving Water Temp: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11277 | Diagnostic: Low Evap Leaving Water Temp: Unit On | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11278 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11279 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11280 | Diagnostic: Low Evaporator Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11281 | Diagnostic: Low Oil Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11282 | Diagnostic: Low Oil Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11283 | Diagnostic: Momentary Power Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11284 | Diagnostic: Momentary Power Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11285 | Diagnostic: Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11286 | Diagnostic: Motor Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11287 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11288 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11289 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11290 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11291 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11292 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11293 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11294 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11295 | Diagnostic: Oil Pressure Sensor Calibration Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11296 | Diagnostic: Oil Pressure Sensor Calibration Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11297 | Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11298 | Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11299 | Diagnostic: Oil Tank Pressure Transducer Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11300 | Diagnostic: Oil Tank Pressure Transducer Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11301 | Diagnostic: Oil Tank Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11302 | Diagnostic: Oil Tank Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11303 | Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11304 | Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11305 | Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11306 | Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11307 | Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11308 | Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11309 | Diagnostic: Outboard Bearing Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11310 | Diagnostic: Outboard Bearing Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11311 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11312 | Diagnostic: Over Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11313 | Diagnostic: Over Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11314 | Diagnostic: Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11315 | Diagnostic: Phase Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11316 | Diagnostic: Phase Reversal Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11317 | Diagnostic: Phase Reversal Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11318 | Diagnostic: Power Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11319 | Diagnostic: Power Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11320 | Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11321 | Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11322 | Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11323 | Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11324 | Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11325 | Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11326 | Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11327 | Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11328 | Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11329 | Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11330 | Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11331 | Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11332 | Diagnostic: Purge Liquid Level Too High Continuously Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11333 | Diagnostic: Purge Liquid Level Too High Continuously Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11334 | Diagnostic: Purge Liquid Level Too High Warning Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11335 | Diagnostic: Purge Liquid Level Too High Warning Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11336 | Diagnostic: Purge Liquid Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11337 | Diagnostic: Purge Liquid Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11338 | Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11339 | Diagnostic: Purge Regen Cooldown Temp Too High Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11341 | Diagnostic: Refrigerant Monitor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11342 | Diagnostic: Restart Inhibit Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11343 | Diagnostic: Restart Inhibit Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11344 | Diagnostic: Severe Current Unbalance Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11345 | Diagnostic: Severe Current Unbalance Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11346 | Diagnostic: Software Error 1001: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11347 | Diagnostic: Software Error 1004: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11348 | Diagnostic: Starter Comm Loss: Main Processor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11349 | Diagnostic: Starter Comm Loss: Main Processor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11350 | Diagnostic: Starter Contactor Interrupt Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11351 | Diagnostic: Starter Contactor Interrupt Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11352 | Diagnostic: Starter Did Not Fully Accelerate Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11353 | Diagnostic: Starter Did Not Fully Accelerate Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11354 | Diagnostic: Starter Did Not Transition Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11355 | Diagnostic: Starter Did Not Transition Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11356 | Diagnostic: Starter Dry Run Test Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11357 | Diagnostic: Starter Dry Run Test Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11358 | Diagnostic: Starter Failed to Arm/ Start Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11359 | Diagnostic: Starter Failed to Arm/ Start Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11360 | Diagnostic: Starter Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11361 | Diagnostic: Starter Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11362 | Diagnostic: Starter Fault Type I Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11363 | Diagnostic: Starter Fault Type I Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11364 | Diagnostic: Starter Fault Type II Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11365 | Diagnostic: Starter Fault Type II Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11366 | Diagnostic: Starter Fault Type III Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11367 | Diagnostic: Starter Fault Type III Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11368 | Diagnostic: Starter Module Memory Error Type 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11369 | Diagnostic: Starter Module Memory Error Type 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11370 | Diagnostic: Starter Module Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11371 | Diagnostic: Starter Module Memory Error Type 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11372 | Diagnostic: Transition Complete Input Opened Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11373 | Diagnostic: Transition Complete Input Opened Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11374 | Diagnostic: Transition Complete Input Shorted Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11375 | Diagnostic: Transition Complete Input Shorted Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11376 | Diagnostic: Under Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11377 | Diagnostic: Under Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11378 | Diagnostic: Unexpected Differential Oil Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11379 | Diagnostic: Unexpected Differential Oil Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11380 | Diagnostic: Unexpected Starter Shutdown Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11381 | Diagnostic: Unexpected Starter Shutdown Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11382 | Diagnostic: AFD Bus Over Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11383 | Diagnostic: AFD Bus Over Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11384 | Diagnostic: AFD Bus Under Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11385 | Diagnostic: AFD Bus Under Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11386 | Diagnostic: AFD Motor Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11387 | Diagnostic: AFD Motor Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11388 | Diagnostic: AFD Precharge Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11389 | Diagnostic: AFD Precharge Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11390 | Diagnostic: AFD Over Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11391 | Diagnostic: AFD Over Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11392 | Diagnostic: AFD Mains Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11393 | Diagnostic: AFD Mains Phase Loss Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11394 | Diagnostic: AFD Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11395 | Diagnostic: AFD Motor Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11396 | Diagnostic: AFD Ground Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11397 | Diagnostic: AFD Ground Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11398 | Diagnostic: AFD Short Circuit Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11399 | Diagnostic: AFD Short Circuit Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11400 | Diagnostic: AFD Safe Stop Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11401 | Diagnostic: AFD Safe Stop Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11402 | Diagnostic: AFD Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11403 | Diagnostic: AFD Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11404 | Diagnostic: AFD Speed Configuration Mismatch Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11405 | Diagnostic: AFD Speed Configuration Mismatch Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11406 | Diagnostic: AFD General Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11407 | Diagnostic: AFD General Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11408 | Comm Loss: Heat Recovery Differential Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11409 | Comm Loss: Heat Recovery Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11410 | Comm Loss: Heat Recovery Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11411 | Comm Loss: Heat Recovery Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11412 | Comm Loss: External Diagnostic Reset | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11413 | Diagnostic: Heat Recovery Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11414 | Diagnostic: Heat Recovery Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11415 | Diagnostic: Heat Recovery Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11416 | Diagnostic: Inverted Heat Recovery Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11417 | Comm Loss: Condenser Rfgt Valve Feedback Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11418 | Comm Loss: Condenser Rfgt Valve Feedback Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11419 | Comm Loss: Economizer Rfgt Valve Feedback Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11420 | Comm Loss: Economizer Rfgt Valve Feedback Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11421 | Comm Loss: Economizer Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11422 | Comm Loss: Economizer Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11423 | Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11424 | Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11425 | Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11426 | Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11427 | Diagnostic: Low Condenser Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11428 | Diagnostic: Low Heat Recovery Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11429 | Diagnostic: Economizer Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11430 | Diagnostic: Economizer Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11431 | Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11432 | Diagnostic: AFD Emergency Stop Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11433 | Diagnostic: AFD Drive Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11434 | Diagnostic: AFD Inverter Heatsink Over Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11435 | Diagnostic: AFD Emergency Stop Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11436 | Diagnostic: AFD Drive Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11437 | Comm Loss: Condenser Rfgt Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11438 | Comm Loss: Condenser Rfgt Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11439 | Comm Loss: Economizer Rfgt Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11440 | Comm Loss: Economizer Rfgt Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BV | 10100 | Base Loading Request | Write | 0 = Off, 1 = On | ||
| BV | 10101 | Reset Diagnostic | Write | 0 = Normal, 1 = Reset | ||
| BV | 10102 | Evaporator Water Pump Request BAS | Write | 0 = Auto, 1 = On | ||
| BV | 10103 | Condenser Water Pump Request BAS | Write | 0 = Auto, 1 = On | ||
| BVmin | 10104 | Chiller Auto Stop Command BAS | Write | 0 = Stop, 1 = Auto | ||
| BV | 10105 | Circuit 1 Lockout BAS | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10106 | Circuit 2 Lockout BAS | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10107 | Energy Consumption Reset | Write | 0 = Accumulating, 1 = Reset | ||
| MI | 10100 | Running Mode | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | ||
| MI | 10101 | Operating Mode | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | ||
| MI | 10102 | Chiller Setpoint Source | Read | 1 = BAS, 2 = External, 3 = Front Panel | ||
| MI | 10103 | Cooling Type | Read | 1 = Water Cooled | ||
| MI | 10104 | Refrigerant Type | Read | 1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A | ||
| MI | 10105 | Manufacturing Location | Read | 1 = Field Applied, 2 = La Crosse, 15 = Taicang | ||
| MI | 10106 | Model Information [GEN2] | Read | 1 = CVHF, 2 = CVGF, 3 = CVHS, 11 = CDHF, 12 = CVR, 13 = CVHH, 14 = CDHH, 20 = CVHM, 38 = CVHE, 39 = CVHG, 40 = CVHL, 43 = CDHG | ||
| MVmin | 10100 | Chiller Mode Command BAS | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Object ID lookup: Trane Symbio 800 CenTraVac (Duplex) point IDs by name
AI10100Active Chilled Water SetpointAI10101Chilled Water Setpoint StatusAI10102Active Base Loading SetpointAI10103Hot Water Setpoint ActiveAI10104Calculated Chiller CapacityAI10105Active Cool/Heat Setpoint TemperatureAI10106Evaporator Leaving Water TemperatureAI10107Evaporator Entering Water TemperatureAI10108Condenser Entering Water TemperatureAI10109Condenser Leaving Water TemperatureAI10110Evaporator Water Flow RateAI10111Evaporator Differential Water PressureAI10112Condenser Water Flow RateAI10113Condenser Differential Water PressureAI10114AFD Last Diagnostic Code Ckt1AI10115Unit Source ID (Last Diagnostic Code)AI10116Refrigerant MonitorAI10117Evaporator Refrigerant Pressure Circuit 1AI10118Condenser Refrigerant Pressure Circuit 1AI10119Differential Refrigerant Pressure Circuit 1AI10120Low Side Oil Pressure - Compressor 1AAI10121High Side Oil Pressure - Compressor 1AAI10122Oil Differential Pressure Circuit 1AI10123Oil Temperature - Compressor 1AAI10124Evaporator Saturated Refrigerant Temperature Circuit 1AI10125Condenser Saturated Refrigerant Temperature Circuit 1AI10126Refrigerant Discharge Temperature - Compressor 1AAI10127Inlet Guide Vane 1 Percent Open Circuit 1AI10128Inlet Guide Vane 2 Percent Open Circuit 1AI10129Purge Carbon Tank Temperature Circuit 1AI10130Purge Liquid Temperature Circuit 1AI10131Purge Refrigerant Compressor Suction Temperature Circuit 1AI10132Time Until Next Purge Run Circuit 1 (in seconds)AI10133Purge Pumpout Chiller On % (7 Days) Circuit 1AI10134Purge Pumpout Chiller Off % (7 Days) Circuit 1AI10135Purge 24 Hour Pumpout Circuit 1 (in seconds)AI10136Purge Pumpout - Life Circuit 1 (in seconds)AI10137Refrigeration - Life Circuit 1 (in seconds)AI10138Starts - Compressor 1AAI10139Run Time - Compressor 1A (in seconds)AI10140Phase AB Voltage - Compressor 1AAI10141Phase BC Voltage - Compressor 1AAI10142Phase CA Voltage - Compressor 1AAI10143Starter Average Phase Volt Circuit 1AI10144Line 1 Current - Compressor 1AAI10145Line 2 Current - Compressor 1AAI10146Line 3 Current - Compressor 1AAI10147Average Line Current Circuit 1AI10148Line 1 Current RLA - Compressor 1AAI10149Line 2 Current RLA - Compressor 1AAI10150Line 3 Current RLA - Compressor 1AAI10151Actual Running CapacityAI10153Starter Load Power Factor - Compressor 1AAI10154Inboard Bearing Temperature Circuit 1AI10155Outboard Bearing Temperature Circuit 1AI10156Motor Winding Temperature 1 Circuit 1AI10157Motor Winding Temperature 2 Circuit 1AI10158Motor Winding Temperature 3 Circuit 1AI10159AFD Frequency Circuit 1AI10160AFD Transistor Temperature Circuit 1AI10161Drive Average Line Current Circuit 1AI10162Drive Line Frequency Circuit 1AI10163Drive Motor Voltage Circuit 1AI10164Drive Inverter Base Temperature Circuit 1AI10165Drive Rectifier Base Temperature Circuit 1AI10166Drive Output Power Circuit 1AI10167Frequency Command Circuit 1AI10168Outboard Bearing Pad Temperature #1 Ckt1AI10169Outboard Bearing Pad Temperature #2 Ckt1AI10170Outboard Bearing Pad Temperature #3 Ckt1AI10171Restart Inhibit Time Remaining Circuit 1AI10172Chiller Design CapacityAI10173Entering Condenser Water PressureAI10174Entering Evaporator Water PressureAI10175Leaving Condenser Water PressureAI10176Leaving Evaporator Water PressureAI10177Condenser Approach Temperature Circuit 1AI10178Evaporator Approach Temperature Circuit 1AI10179Drive DC Bus Voltage Circuit 1AI10180Drive Motor Average Current RLA Circuit 1AI10182Active Demand Limit SetpointAI10183Active Demand Limit SetpointAI10184Demand Limit Setpoint StatusAI10185Number of CircuitsAI10186Number of Compressors Circuit 1AI10187Number of Compressors Circuit 2AI10188Low Side Oil Pressure - Compressor 2AAI10189High Side Oil Pressure - Compressor 2AAI10190Oil Differential Pressure Circuit 2AI10191Oil Temperature - Compressor 2AAI10192Evaporator Saturated Refrigerant Temperature Circuit 2AI10193Condenser Saturated Refrigerant Temperature Circuit 2AI10194Refrigerant Discharge Temperature - Compressor 2AAI10195Inlet Guide Vane 1 Percent Open Circuit 2AI10196Inlet Guide Vane 2 Percent Open Circuit 2AI10197Purge Carbon Tank Temperature Circuit 2AI10198Purge Liquid Temperature Circuit 2AI10199Purge Refrigerant Compressor Suction Temperature Circuit 2AI10200Time Until Next Purge Run Circuit 2 (in seconds)AI10201Refrigeration - Life Circuit 2 (in seconds)AI10202Starts - Compressor 2AAI10203Run Time - Compressor 2A (in seconds)AI10204Starter Average Phase Volt Circuit 2AI10205Line 1 Current - Compressor 2AAI10206Line 2 Current - Compressor 2AAI10207Line 3 Current - Compressor 2AAI10208Average Line Current Circuit 2AI10209Drive Average Line Current Circuit 2AI10210Starter Load Power Factor - Compressor 2AAI10211Inboard Bearing Temperature Circuit 2AI10212Outboard Bearing Temperature Circuit 2AI10213Motor Winding Temperature 1 Circuit 2AI10214Motor Winding Temperature 2 Circuit 2AI10215Motor Winding Temperature 3 Circuit 2AI10216AFD Transistor Temperature Circuit 2AI10217Heat Recovery Entering Water TempAI10218Heat Recovery Leaving Water TempAI10219Purge Pumpout Chiller On % (7 Days) Circuit 2AI10220Purge Pumpout Chiller Off % (7 Days) Circuit 2AI10221Purge 24 Hour Pumpout Circuit 2 (in seconds)AI10222Phase AB Voltage - Compressor 2AAI10223Phase BC Voltage - Compressor 2AAI10224Phase CA Voltage - Compressor 2AAI10225Purge Pumpout - Life Circuit 2 (in seconds)AI10226Drive Motor Average Current RLA Circuit 2AI10227Drive Inverter Base Temperature Circuit 2AI10228Drive Rectifier Base Temperature Circuit 2AI10229Outboard Bearing Pad Temperature #1 Ckt2AI10230Outboard Bearing Pad Temperature #2 Ckt2AI10231Outboard Bearing Pad Temperature #3 Ckt2AI10232Evaporator Refrigerant Pressure Circuit 2AI10233Condenser Refrigerant Pressure Circuit 2AI10234Differential Refrigerant Pressure Circuit 2AI10235Restart Inhibit Time Remaining Circuit 2AI10236AFD Frequency Circuit 2AI10237Drive Line Frequency Circuit 2AI10238Frequency Command Circuit 2AI10239Drive DC Bus Voltage Circuit 2AI10240Drive Output Power Circuit 2AI10241Line 1 Current RLA - Compressor 2AAI10242Line 2 Current RLA - Compressor 2AAI10243Line 3 Current RLA - Compressor 2AAI10244Drive Current Line 1 Circuit 1AI10245Drive Current Line 2 Circuit 1AI10246Drive Current Line 3 Circuit 1AI10247Drive Current Line 1 Circuit 2AI10248Drive Current Line 2 Circuit 2AI10249Drive Current Line 3 Circuit 2AI10250Starter Input Power Consumption Ckt1AI10251Starter Input Power Consumption Ckt2AI10252Drive Motor Voltage Circuit 2AI10253Chiller Control SignalAI10254Head Pressure Control StatusAI10255AFD Last Diagnostic Code Ckt2AI10256Voltage L1-L2 Circuit 1AI10257Voltage L1-L3 Circuit 1AI10258Voltage L2-L3 Circuit 1AI10259Voltage L1-L2 Circuit 2AI10260Voltage L1-L3 Circuit 2AI10261Voltage L2-L3 Circuit 2AI10262Average Line Voltage Circuit 1AI10263Average Line Voltage Circuit 2AI10264Line Current L1 Circuit 1AI10265Line Current L2 Circuit 1AI10266Line Current L3 Circuit 1AI10267Line Current L1 Circuit 2AI10268Line Current L2 Circuit 2AI10269Line Current L3 Circuit 2AI10270Unit Average Line Current Circuit 1AI10271Unit Average Line Current Circuit 2AI10272Line Frequency Circuit 1AI10273Line Frequency Circuit 2AI10274Power Factor Circuit 1AI10275Power Factor Circuit 2AI10276Power Demand Circuit 1AI10277Power Demand Circuit 2AI10278Total Real PowerAI10279Unit Power ConsumptionAI10280Energy ConsumptionAI10281Energy Consumption LifetimeAI10282Condenser Approach Temperature Circuit 2AI10283Evaporator Approach Temperature Circuit 2AI10284Drive Input Voltage Calculated 1AAI10285Drive Input Voltage Calculated 2AAI10286Drive Heatsink Temperature Compressor 1AAI10287Drive Heatsink Temperature Compressor 2AAI10288Outdoor Air Temperature LocalAI10289Heat Recovery Differential Water PressureAI10290Heat Recovery Water Flow RateAI10291Heat Recovery Calculated CapacityAI10292Heat Recovery Entering Water PressureAI10293Heat Recovery Leaving Water PressureAI10294Heat Recovery Approach Temperature Circuit 1AI10295Heat Recovery Approach Temperature Circuit 2AI10296High Side Oil Gauge Pressure - Compressor 1AAI10297Low Side Oil Gauge Pressure - Compressor 1AAI10298High Side Oil Gauge Pressure - Compressor 2AAI10299Low Side Oil Gauge Pressure - Compressor 2AAI10300Condenser Refrigerant Gauge Pressure Circuit 1AI10301Condenser Refrigerant Gauge Pressure Circuit 2AI10302Entering Condenser Water Gauge PressureAI10303Entering Evaporator Water Gauge PressureAI10304Evaporator Refrigerant Gauge Pressure Circuit 1AI10305Evaporator Refrigerant Gauge Pressure Circuit 2AI10306Heat Recovery Entering Water Gauge PressureAI10307Heat Recovery Leaving Water Gauge PressureAI10308Leaving Condenser Water Gauge PressureAI10309Leaving Evaporator Water Gauge PressureAI10310Compressor Discharge Superheat Circuit 1AI10311Compressor Discharge Superheat Circuit 2AI10312Unit Load CommandAI10313Drive Motor Current U RLA Circuit 1AI10314Drive Motor Current V RLA Circuit 1AI10315Drive Motor Current W RLA Circuit 1AI10316Drive Motor Current U Circuit 1AI10317Drive Motor Current V Circuit 1AI10318Drive Motor Current W Circuit 1AI10319Drive Motor Current U RLA Circuit 2AI10320Drive Motor Current V RLA Circuit 2AI10321Drive Motor Current W RLA Circuit 2AI10322Drive Motor Current U Circuit 2AI10323Drive Motor Current V Circuit 2AI10324Drive Motor Current W Circuit 2AI10325Active Cooling Differential to StartAI10326Active Cooling Differential to StopAI10327Active Heating Differential to StartAI10328Active Heating Differential to StopAV10100Chilled Water SetpointAV10101Demand Limit SetpointAV10102Hot Water SetpointAV10103Base Loading SetpointAV10104BAS Cooling Differential to StartAV10105BAS Cooling Differential to StopAV10106BAS Heating Differential to StartAV10107BAS Heating Differential to StopBI10101Manual Override ExistsBI10102Base Loading Request ActiveBI10103Run EnabledBI10104Local Setpoint ControlBI10105Maximum CapacityBI10106Capacity LimitedBI10107Head Relief RequestBI10108Purge Compressor Relay Circuit 1BI10109Pump Out Relay Circuit 1BI10110Purge Regenerating Valve Solenoid Circuit 1BI10111Chiller Running StateBI10112Evaporator Water Pump RequestBI10113Evaporator Water Flow StatusBI10114Condenser Water Pump RequestBI10115Condenser Water Flow StatusBI10116Diagnostic PresentBI10117Diagnostic Shutdown PresentBI10118Diagnostic: Manual Reset RequiredBI10119Diagnostic: Local Manual Reset RequiredBI10120Diagnostic Present: InformationBI10121Diagnostic Present: AdvisoryBI10122Diagnostic Present: CriticalBI10123Diagnostic Present: Service RequiredBI10124Compressor 1A StatusBI10125Front Panel Auto StopBI10126External Auto Stop Input StatusBI10127Purge Compressor Relay Circuit 2BI10128Purge Regenerating Valve Solenoid Circuit 2BI10130Pump Out Relay Circuit 2BI10131Compressor 2A StatusBI10132Emergency StopBI10133Circuit 1 Cooling AvailableBI10134Circuit 2 Cooling AvailableBI10135Circuit 1 Lockout Front PanelBI10136Circuit 2 Lockout Front PanelBI10137Circuit 1 Lockout ExternalBI10138Circuit 2 Lockout ExternalBI10139Circuit 1 Lockout ActiveBI10140Circuit 2 Lockout ActiveBI10141Diagnostic Shutdown Present: AFD/Starter Circuit 1BI10142Diagnostic Shutdown Present: AFD/Starter Circuit 2BI10143Heat Recovery Water Flow StatusBI11000Diagnostic: AFD Comm Loss: Main Processor Circuit 1BI11001Diagnostic: AFD Comm Loss: Main Processor Circuit 2BI11002Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1BI11003Diagnostic: AFD Control Board Memory Error Type 2 Circuit 2BI11004Diagnostic: AFD DPI Communication Failure Circuit 1BI11005Diagnostic: AFD DPI Communication Failure Circuit 2BI11006Diagnostic: AFD Fatal Software Error Circuit 1BI11007Diagnostic: AFD Fatal Software Error Circuit 2BI11008Diagnostic: AFD General Failure Circuit 1BI11009Diagnostic: AFD General Failure Circuit 2BI11010Diagnostic: AFD Ground Fault Circuit 1BI11011Diagnostic: AFD Ground Fault Circuit 2BI11012Diagnostic: AFD High Bus Voltage Circuit 1BI11013Diagnostic: AFD High Bus Voltage Circuit 2BI11014Diagnostic: AFD High Temperature Circuit 1BI11015Diagnostic: AFD High Temperature Circuit 2BI11016Diagnostic: AFD I/O Board Failure Circuit 1BI11017Diagnostic: AFD I/O Board Failure Circuit 2BI11018Diagnostic: AFD Instantaneous Current Overload Circuit 1BI11019Diagnostic: AFD Instantaneous Current Overload Circuit 2BI11020Diagnostic: AFD Interrupt Failure Circuit 1BI11021Diagnostic: AFD Interrupt Failure Circuit 2BI11022Diagnostic: AFD Motor Current Overload Circuit 1BI11023Diagnostic: AFD Motor Current Overload Circuit 2BI11024Diagnostic: AFD Motor Short Circuit 1BI11025Diagnostic: AFD Motor Short Circuit 2BI11026Diagnostic: AFD Output Phase Loss Circuit 1BI11027Diagnostic: AFD Output Phase Loss Circuit 2BI11028Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1BI11029Diagnostic: AFD Power Intfc Controller Board Failure Circuit 2BI11030Diagnostic: AFD Power Loss Circuit 1BI11031Diagnostic: AFD Power Loss Circuit 2BI11032Diagnostic: AFD Power Structure Board Failure Circuit 1BI11033Diagnostic: AFD Power Structure Board Failure Circuit 2BI11034Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1BI11035Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 2BI11038Diagnostic: At Speed Input Opened Circuit 1BI11039Diagnostic: At Speed Input Opened Circuit 2BI11040Diagnostic: At Speed Input Shorted Circuit 1BI11041Diagnostic: At Speed Input Shorted Circuit 2BI11042Diagnostic: Check ClockBI11043Diagnostic: Check Oil Filter Circuit 1BI11044Diagnostic: Check Oil Filter Circuit 2BI11045Diagnostic: Check Oil Heater Circuit 1BI11046Diagnostic: Check Oil Heater Circuit 2BI11047Comm Loss: Adaptive Frequency Drive Circuit 1BI11048Comm Loss: Adaptive Frequency Drive Circuit 2BI11049Comm Loss: AFD Speed Signal VDC Output Circuit 1BI11050Comm Loss: AFD Speed Signal VDC Output Circuit 2BI11051Comm Loss: Compressor Motor % RLA Output Circuit 1BI11052Comm Loss: Compressor Motor % RLA Output Circuit 2BI11053Comm Loss: Cond Diff Water PressureBI11054Comm Loss: Cond Head Press Cntrl OutputBI11055Comm Loss: Cond High Pressure Cutout Circuit 1BI11056Comm Loss: Cond High Pressure Cutout Circuit 2BI11057Comm Loss: Cond Refrigerant Pressure Circuit 1BI11058Comm Loss: Cond Refrigerant Pressure Circuit 2BI11059Comm Loss: Cond Rfgt Pressure Output Circuit 1BI11060Comm Loss: Cond Rfgt Pressure Output Circuit 2BI11061Comm Loss: Cond Saturated Rfgt Temp Circuit 1BI11062Comm Loss: Cond Saturated Rfgt Temp Circuit 2BI11063Comm Loss: Condenser Entering Water PressureBI11064Comm Loss: Condenser Entering Water TempBI11065Comm Loss: Condenser Leaving Water PressureBI11066Comm Loss: Condenser Leaving Water TempBI11067Comm Loss: Condenser Liquid Level Sensor Circuit 1BI11068Comm Loss: Condenser Liquid Level Sensor Circuit 2BI11069Comm Loss: Condenser Water Flow SwitchBI11070Comm Loss: Condenser Water Pump RelayBI11071Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1BI11072Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2BI11073Comm Loss: Economizer Bypass Valve Circuit 1BI11074Comm Loss: Economizer Bypass Valve Circuit 2BI11075Comm Loss: Emergency StopBI11076Comm Loss: Energy Meter 1 Circuit 1BI11077Comm Loss: Energy Meter 2 Circuit 2BI11078Comm Loss: Evap Diff Water PressureBI11079Comm Loss: Evap Entering Water TempBI11080Comm Loss: Evap Leaving Water TempBI11081Comm Loss: Evap Refrigerant Pressure Circuit 1BI11082Comm Loss: Evap Refrigerant Pressure Circuit 2BI11083Comm Loss: Evap Sat Refrig Temp Circuit 1BI11084Comm Loss: Evap Sat Refrig Temp Circuit 2BI11085Comm Loss: Evaporator Entering Water PressureBI11086Comm Loss: Evaporator Leaving Water PressureBI11087Comm Loss: Evaporator Water Flow SwitchBI11088Comm Loss: Evaporator Water Pump RelayBI11089Comm Loss: Ext Base Loading CommandBI11090Comm Loss: Ext Base Loading SetpointBI11091Comm Loss: Ext Chilled/Hot Water SetpointBI11092Comm Loss: Ext Demand Limit SetpointBI11093Comm Loss: External Auto/StopBI11094Comm Loss: External Ckt Lockout Circuit 1BI11095Comm Loss: External Ckt Lockout Circuit 2BI11097Comm Loss: External Hot Water CommandBI11098Comm Loss: External Ice Building CommandBI11099Comm Loss: Generator Fault Input Circuit 1BI11100Comm Loss: Generator Fault Input Circuit 2BI11101Comm Loss: Generator Speed Signal Output Circuit 1BI11102Comm Loss: Generator Speed Signal Output Circuit 2BI11103Comm Loss: Generator Start/Stop Relay Circuit 1BI11104Comm Loss: Generator Start/Stop Relay Circuit 2BI11105Comm Loss: Generator Up To Speed Input Circuit 1BI11106Comm Loss: Generator Up To Speed Input Circuit 2BI11107Comm Loss: Heat Recovery Entering Water TempBI11108Comm Loss: Heat Recovery Leaving Water TempBI11112Comm Loss: Ice Building RelayBI11113Comm Loss: IGV First Stage Actuator Circuit 1BI11114Comm Loss: IGV First Stage Actuator Circuit 2BI11115Comm Loss: IGV Second Stage Actuator Circuit 1BI11116Comm Loss: IGV Second Stage Actuator Circuit 2BI11117Comm Loss: Inboard Bearing Temperature Circuit 1BI11118Comm Loss: Inboard Bearing Temperature Circuit 2BI11119Comm Loss: Motor Winding Temperature 1 Circuit 1BI11120Comm Loss: Motor Winding Temperature 1 Circuit 2BI11121Comm Loss: Motor Winding Temperature 2 Circuit 1BI11122Comm Loss: Motor Winding Temperature 2 Circuit 2BI11123Comm Loss: Motor Winding Temperature 3 Circuit 1BI11124Comm Loss: Motor Winding Temperature 3 Circuit 2BI11125Comm Loss: Oil Cooler Solenoid Circuit 1BI11126Comm Loss: Oil Cooler Solenoid Circuit 2BI11127Comm Loss: Oil Pump Discharge Pressure Circuit 1BI11128Comm Loss: Oil Pump Discharge Pressure Circuit 2BI11129Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1BI11130Comm Loss: Oil Tank Heater 4E1 Relay Circuit 2BI11131Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1BI11132Comm Loss: Oil Tank Heater 4E2 Relay Circuit 2BI11133Comm Loss: Oil Tank Heater Relay Circuit 1BI11134Comm Loss: Oil Tank Heater Relay Circuit 2BI11135Comm Loss: Oil Tank Pressure Circuit 1BI11136Comm Loss: Oil Tank Pressure Circuit 2BI11137Comm Loss: Oil Tank Temperature Circuit 1BI11138Comm Loss: Oil Tank Temperature Circuit 2BI11139Comm Loss: Oil Vent Line Circuit 1BI11140Comm Loss: Oil Vent Line Circuit 2BI11141Comm Loss: Oil/Refrigerant Pump Relay Circuit 1BI11142Comm Loss: Oil/Refrigerant Pump Relay Circuit 2BI11143Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1BI11144Comm Loss: Outboard Bearing Pad Temp 1 Circuit 2BI11145Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1BI11146Comm Loss: Outboard Bearing Pad Temp 2 Circuit 2BI11147Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1BI11148Comm Loss: Outboard Bearing Pad Temp 3 Circuit 2BI11149Comm Loss: Outboard Bearing Temperature Circuit 1BI11150Comm Loss: Outboard Bearing Temperature Circuit 2BI11151Comm Loss: Outdoor Air TemperatureBI11152Comm Loss: Programmable Relay Board 1BI11153Comm Loss: Programmable Relay Board 2BI11154Comm Loss: Purge Alarm Relay Circuit 1BI11155Comm Loss: Purge Alarm Relay Circuit 2BI11156Comm Loss: Purge Carbon Tank Heater Rly Circuit 1BI11157Comm Loss: Purge Carbon Tank Heater Rly Circuit 2BI11158Comm Loss: Purge Carbon Tank Temperature Circuit 1BI11159Comm Loss: Purge Carbon Tank Temperature Circuit 2BI11160Comm Loss: Purge Condensing Unit Relay Circuit 1BI11161Comm Loss: Purge Condensing Unit Relay Circuit 2BI11162Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1BI11163Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 2BI11164Comm Loss: Purge Exhaust Solenoid Output Circuit 1BI11165Comm Loss: Purge Exhaust Solenoid Output Circuit 2BI11166Comm Loss: Purge Liquid Level Switch Circuit 1BI11167Comm Loss: Purge Liquid Level Switch Circuit 2BI11168Comm Loss: Purge Liquid Temperature Circuit 1BI11169Comm Loss: Purge Liquid Temperature Circuit 2BI11170Comm Loss: Purge Pumpout Relay Circuit 1BI11171Comm Loss: Purge Pumpout Relay Circuit 2BI11172Comm Loss: Purge Pumpout Solenoid Output Circuit 1BI11173Comm Loss: Purge Pumpout Solenoid Output Circuit 2BI11174Comm Loss: Purge Regen Solenoid Relay Circuit 1BI11175Comm Loss: Purge Regen Solenoid Relay Circuit 2BI11176Comm Loss: Refrigerant Monitor InputBI11177Comm Loss: Starter Circuit 1BI11178Comm Loss: Starter Circuit 2BI11179Comm Loss: Starter Fault Circuit 1BI11180Comm Loss: Starter Fault Circuit 2BI11181Comm Loss: Unit Purge Alarm RelayBI11182Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 1BI11183Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 2BI11184Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 1BI11185Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 2BI11186Diagnostic: Condenser Diff Water Pressure XdcrBI11187Diagnostic: Condenser Entering Water PressureBI11188Diagnostic: Condenser Entering Water Temp SensorBI11189Diagnostic: Condenser High Pressure Cutout Circuit 1BI11190Diagnostic: Condenser High Pressure Cutout Circuit 2BI11191Diagnostic: Condenser Leaving Water PressureBI11192Diagnostic: Condenser Leaving Water Temp SensorBI11193Diagnostic: Condenser Liquid Level Sensor Circuit 1BI11194Diagnostic: Condenser Liquid Level Sensor Circuit 2BI11195Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 1BI11196Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 2BI11197Diagnostic: Condenser Water Flow LostBI11198Diagnostic: Condenser Water Flow OverdueBI11199Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 1BI11200Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 2BI11201Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 1BI11202Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 2BI11203Diagnostic: Differential Oil Pressure Overdue Circuit 1BI11204Diagnostic: Differential Oil Pressure Overdue Circuit 2BI11206Diagnostic: Emergency StopBI11207Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 1BI11208Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 2BI11209Diagnostic: Evaporator Diff Water Pressure XdcrBI11210Diagnostic: Evaporator Entering Water PressureBI11211Diagnostic: Evaporator Entering Water Temp SensorBI11212Diagnostic: Evaporator Leaving Water PressureBI11213Diagnostic: Evaporator Leaving Water Temp SensorBI11214Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1BI11215Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 2BI11216Diagnostic: Evaporator Water Flow LostBI11217Diagnostic: Evaporator Water Flow OverdueBI11218Diagnostic: Excessive Loss of CommunicationBI11221Diagnostic: Extended Compressor Surge Circuit 1BI11222Diagnostic: Extended Compressor Surge Circuit 2BI11223Diagnostic: External Base Loading SetpointBI11224Diagnostic: External Chilled/Hot Water SetpointBI11225Diagnostic: External Demand Limit SetpointBI11230Diagnostic: Generator Fault Relay Open Circuit 1BI11231Diagnostic: Generator Fault Relay Open Circuit 2BI11232Diagnostic: Generator Ready Signal Overdue Circuit 1BI11233Diagnostic: Generator Ready Signal Overdue Circuit 2BI11234Diagnostic: Heat Recovery Entering Water Temp SensorBI11235Diagnostic: Heat Recovery Leaving Water Temp SensorBI11236Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 1BI11237Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 2BI11238Diagnostic: High Differential Refrigerant Pressure Circuit 1BI11239Diagnostic: High Differential Refrigerant Pressure Circuit 2BI11240Diagnostic: High Evaporator Refrigerant Temperature Circuit 1BI11241Diagnostic: High Evaporator Refrigerant Temperature Circuit 2BI11242Diagnostic: High Evaporator Water TemperatureBI11243Diagnostic: High Inboard Bearing Temperature Circuit 1BI11244Diagnostic: High Inboard Bearing Temperature Circuit 2BI11245Diagnostic: High Motor Winding Temperature 1 Circuit 1BI11246Diagnostic: High Motor Winding Temperature 1 Circuit 2BI11247Diagnostic: High Motor Winding Temperature 2 Circuit 1BI11248Diagnostic: High Motor Winding Temperature 2 Circuit 2BI11249Diagnostic: High Motor Winding Temperature 3 Circuit 1BI11250Diagnostic: High Motor Winding Temperature 3 Circuit 2BI11251Diagnostic: High Oil Temperature Circuit 1BI11252Diagnostic: High Oil Temperature Circuit 2BI11253Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1BI11254Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 2BI11255Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1BI11256Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 2BI11257Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1BI11258Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 2BI11259Diagnostic: High Outboard Bearing Temp Circuit 1BI11260Diagnostic: High Outboard Bearing Temp Circuit 2BI11261Diagnostic: High Vacuum Lockout Circuit 1BI11262Diagnostic: High Vacuum Lockout Circuit 2BI11266Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 1BI11267Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 2BI11268Diagnostic: Inboard Bearing Temp Sensor Circuit 1BI11269Diagnostic: Inboard Bearing Temp Sensor Circuit 2BI11270Diagnostic: Inverted Condenser Water TemperatureBI11271Diagnostic: Inverted Evaporator Water TemperatureBI11272Diagnostic: Loss of Economizer Bypass Valve Control Circuit 1BI11273Diagnostic: Loss of Economizer Bypass Valve Control Circuit 2BI11274Diagnostic: Low Differential Oil Pressure Circuit 1BI11275Diagnostic: Low Differential Oil Pressure Circuit 2BI11276Diagnostic: Low Evap Leaving Water Temp: Unit OffBI11277Diagnostic: Low Evap Leaving Water Temp: Unit OnBI11278Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1BI11279Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2BI11280Diagnostic: Low Evaporator Water FlowBI11281Diagnostic: Low Oil Temperature Circuit 1BI11282Diagnostic: Low Oil Temperature Circuit 2BI11283Diagnostic: Momentary Power Loss Circuit 1BI11284Diagnostic: Momentary Power Loss Circuit 2BI11285Diagnostic: Motor Current Overload Circuit 1BI11286Diagnostic: Motor Current Overload Circuit 2BI11287Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1BI11288Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2BI11289Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1BI11290Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2BI11291Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1BI11292Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2BI11293Diagnostic: MP: Invalid ConfigurationBI11294Diagnostic: MP: Reset Has OccurredBI11295Diagnostic: Oil Pressure Sensor Calibration Circuit 1BI11296Diagnostic: Oil Pressure Sensor Calibration Circuit 2BI11297Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1BI11298Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 2BI11299Diagnostic: Oil Tank Pressure Transducer Circuit 1BI11300Diagnostic: Oil Tank Pressure Transducer Circuit 2BI11301Diagnostic: Oil Tank Temperature Sensor Circuit 1BI11302Diagnostic: Oil Tank Temperature Sensor Circuit 2BI11303Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1BI11304Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 2BI11305Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1BI11306Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 2BI11307Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1BI11308Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 2BI11309Diagnostic: Outboard Bearing Temperature Sensor Circuit 1BI11310Diagnostic: Outboard Bearing Temperature Sensor Circuit 2BI11311Diagnostic: Outdoor Air Temperature SensorBI11312Diagnostic: Over Voltage Circuit 1BI11313Diagnostic: Over Voltage Circuit 2BI11314Diagnostic: Phase Loss Circuit 1BI11315Diagnostic: Phase Loss Circuit 2BI11316Diagnostic: Phase Reversal Circuit 1BI11317Diagnostic: Phase Reversal Circuit 2BI11318Diagnostic: Power Loss Circuit 1BI11319Diagnostic: Power Loss Circuit 2BI11320Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1BI11321Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 2BI11322Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1BI11323Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 2BI11324Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1BI11325Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 2BI11326Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1BI11327Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 2BI11328Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1BI11329Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 2BI11330Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1BI11331Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 2BI11332Diagnostic: Purge Liquid Level Too High Continuously Circuit 1BI11333Diagnostic: Purge Liquid Level Too High Continuously Circuit 2BI11334Diagnostic: Purge Liquid Level Too High Warning Circuit 1BI11335Diagnostic: Purge Liquid Level Too High Warning Circuit 2BI11336Diagnostic: Purge Liquid Temperature Sensor Circuit 1BI11337Diagnostic: Purge Liquid Temperature Sensor Circuit 2BI11338Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1BI11339Diagnostic: Purge Regen Cooldown Temp Too High Circuit 2BI11341Diagnostic: Refrigerant Monitor InputBI11342Diagnostic: Restart Inhibit Circuit 1BI11343Diagnostic: Restart Inhibit Circuit 2BI11344Diagnostic: Severe Current Unbalance Circuit 1BI11345Diagnostic: Severe Current Unbalance Circuit 2BI11346Diagnostic: Software Error 1001: Call Trane ServiceBI11347Diagnostic: Software Error 1004: Call Trane ServiceBI11348Diagnostic: Starter Comm Loss: Main Processor Circuit 1BI11349Diagnostic: Starter Comm Loss: Main Processor Circuit 2BI11350Diagnostic: Starter Contactor Interrupt Failure Circuit 1BI11351Diagnostic: Starter Contactor Interrupt Failure Circuit 2BI11352Diagnostic: Starter Did Not Fully Accelerate Circuit 1BI11353Diagnostic: Starter Did Not Fully Accelerate Circuit 2BI11354Diagnostic: Starter Did Not Transition Circuit 1BI11355Diagnostic: Starter Did Not Transition Circuit 2BI11356Diagnostic: Starter Dry Run Test Circuit 1BI11357Diagnostic: Starter Dry Run Test Circuit 2BI11358Diagnostic: Starter Failed to Arm/ Start Circuit 1BI11359Diagnostic: Starter Failed to Arm/ Start Circuit 2BI11360Diagnostic: Starter Fault Circuit 1BI11361Diagnostic: Starter Fault Circuit 2BI11362Diagnostic: Starter Fault Type I Circuit 1BI11363Diagnostic: Starter Fault Type I Circuit 2BI11364Diagnostic: Starter Fault Type II Circuit 1BI11365Diagnostic: Starter Fault Type II Circuit 2BI11366Diagnostic: Starter Fault Type III Circuit 1BI11367Diagnostic: Starter Fault Type III Circuit 2BI11368Diagnostic: Starter Module Memory Error Type 1 Circuit 1BI11369Diagnostic: Starter Module Memory Error Type 1 Circuit 2BI11370Diagnostic: Starter Module Memory Error Type 2 Circuit 1BI11371Diagnostic: Starter Module Memory Error Type 2 Circuit 2BI11372Diagnostic: Transition Complete Input Opened Circuit 1BI11373Diagnostic: Transition Complete Input Opened Circuit 2BI11374Diagnostic: Transition Complete Input Shorted Circuit 1BI11375Diagnostic: Transition Complete Input Shorted Circuit 2BI11376Diagnostic: Under Voltage Circuit 1BI11377Diagnostic: Under Voltage Circuit 2BI11378Diagnostic: Unexpected Differential Oil Pressure Circuit 1BI11379Diagnostic: Unexpected Differential Oil Pressure Circuit 2BI11380Diagnostic: Unexpected Starter Shutdown Circuit 1BI11381Diagnostic: Unexpected Starter Shutdown Circuit 2BI11382Diagnostic: AFD Bus Over Voltage Circuit 1BI11383Diagnostic: AFD Bus Over Voltage Circuit 2BI11384Diagnostic: AFD Bus Under Voltage Circuit 1BI11385Diagnostic: AFD Bus Under Voltage Circuit 2BI11386Diagnostic: AFD Motor Fault Circuit 1BI11387Diagnostic: AFD Motor Fault Circuit 2BI11388Diagnostic: AFD Precharge Fault Circuit 1BI11389Diagnostic: AFD Precharge Fault Circuit 2BI11390Diagnostic: AFD Over Temperature Circuit 1BI11391Diagnostic: AFD Over Temperature Circuit 2BI11392Diagnostic: AFD Mains Phase Loss Circuit 1BI11393Diagnostic: AFD Mains Phase Loss Circuit 2BI11394Diagnostic: AFD Motor Current Overload Circuit 1BI11395Diagnostic: AFD Motor Current Overload Circuit 2BI11396Diagnostic: AFD Ground Fault Circuit 1BI11397Diagnostic: AFD Ground Fault Circuit 2BI11398Diagnostic: AFD Short Circuit Circuit 1BI11399Diagnostic: AFD Short Circuit Circuit 2BI11400Diagnostic: AFD Safe Stop Circuit 1BI11401Diagnostic: AFD Safe Stop Circuit 2BI11402Diagnostic: AFD Fault Circuit 1BI11403Diagnostic: AFD Fault Circuit 2BI11404Diagnostic: AFD Speed Configuration Mismatch Circuit 1BI11405Diagnostic: AFD Speed Configuration Mismatch Circuit 2BI11406Diagnostic: AFD General Failure Circuit 1BI11407Diagnostic: AFD General Failure Circuit 2BI11408Comm Loss: Heat Recovery Differential Water PressureBI11409Comm Loss: Heat Recovery Entering Water PressureBI11410Comm Loss: Heat Recovery Leaving Water PressureBI11411Comm Loss: Heat Recovery Water Flow SwitchBI11412Comm Loss: External Diagnostic ResetBI11413Diagnostic: Heat Recovery Diff Water PressureBI11414Diagnostic: Heat Recovery Entering Water PressureBI11415Diagnostic: Heat Recovery Leaving Water PressureBI11416Diagnostic: Inverted Heat Recovery Water TemperatureBI11417Comm Loss: Condenser Rfgt Valve Feedback Circuit 1BI11418Comm Loss: Condenser Rfgt Valve Feedback Circuit 2BI11419Comm Loss: Economizer Rfgt Valve Feedback Circuit 1BI11420Comm Loss: Economizer Rfgt Valve Feedback Circuit 2BI11421Comm Loss: Economizer Refrigerant Pressure Circuit 1BI11422Comm Loss: Economizer Refrigerant Pressure Circuit 2BI11423Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 1BI11424Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 2BI11425Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 1BI11426Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 2BI11427Diagnostic: Low Condenser Water FlowBI11428Diagnostic: Low Heat Recovery Water FlowBI11429Diagnostic: Economizer Refrigerant Pressure Circuit 1BI11430Diagnostic: Economizer Refrigerant Pressure Circuit 2BI11431Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1BI11432Diagnostic: AFD Emergency Stop Fault Circuit 1BI11433Diagnostic: AFD Drive Fault Circuit 1BI11434Diagnostic: AFD Inverter Heatsink Over Temp Circuit 2BI11435Diagnostic: AFD Emergency Stop Fault Circuit 2BI11436Diagnostic: AFD Drive Fault Circuit 2BI11437Comm Loss: Condenser Rfgt Valve Circuit 1BI11438Comm Loss: Condenser Rfgt Valve Circuit 2BI11439Comm Loss: Economizer Rfgt Valve Circuit 1BI11440Comm Loss: Economizer Rfgt Valve Circuit 2BV10100Base Loading RequestBV10101Reset DiagnosticBV10102Evaporator Water Pump Request BASBV10103Condenser Water Pump Request BASBV10104Chiller Auto Stop Command BASBV10105Circuit 1 Lockout BASBV10106Circuit 2 Lockout BASBV10107Energy Consumption ResetMI10100Running ModeMI10101Operating ModeMI10102Chiller Setpoint SourceMI10103Cooling TypeMI10104Refrigerant TypeMI10105Manufacturing LocationMI10106Model Information [GEN2]MV10100Chiller Mode Command BAS
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the communicated engineering unit follows the factory-configured unit system (I-P or SI), not the web UI display setting.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- Same document as the simplex list; this is the duplex table only.
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 CenTraVac (Duplex) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 CenTraVac (Duplex)
How many BACnet points does the Trane Symbio 800 CenTraVac (Duplex) have?
This list has 717 BACnet objects: 227 analog inputs, 8 analog values, 466 binary inputs, 8 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 CenTraVac (Duplex) BACnet points are writable?
17 of the 717 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 CenTraVac (Duplex) BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - CenTraVac (BAS-PTS009C-EN), revision 12/12/2025, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 CenTraVac (Duplex)?
Start with BV 10104 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10111 Chiller Running State (Chiller on/off status); BI 10104 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10106 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10151 Actual Running Capacity (Actual running capacity in percent); BI 10116 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 CenTraVac (Duplex)?
BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10126 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10103 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
How do I check these points on the real Symbio 800 CenTraVac (Duplex)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet - CenTraVac · BAS-PTS009C-EN · rev. 12/12/2025. Object names, instances and units are reproduced as published; descriptions are our own.