Split system controller · BACnet points list
Trane Symbio 800 IntelliCore Split System (RAUK) BACnet points list
Updated 28 October 2026
The Symbio 800 on IntelliCore RAUK split systems exposes about 135 objects with 5-digit instances (AI-10101...). Many points depend on unit size (second circuit from 40 T, third compressor on some sizes), on the system control type (no system control, supply-air VAV or EVP) and on the power-monitoring option. The BAS writes auto/stop, discharge cooling setpoint, demand limit, lockouts and the discharge and outdoor air temperatures.
This page lists 136 BACnet objects for the Trane Symbio 800 IntelliCore Split System (RAUK) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 IntelliCore Split System (RAUK)
- Equipment
- Split system controller
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 136 (16 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- 62000844-1-00-0003
- Also known as
- IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 IntelliCore Split System (RAUK)
Use BV 10140 Auto Stop Command BAS to run or stop the unit. On supply-air VAV or EVP units write AV 10121 Discharge Cooling Setpoint BAS; to limit capacity set AV 10163 Demand Limit Setpoint and turn on BV 10116 Demand Limit Request BAS. MI 10119 Arbitration Method must read Full Source for BAS values to be used. Sensor BAS points carry a 900 s heartbeat.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10140 | Auto Stop Command BAS | BMS auto/stop command (0 = Stop, 1 = Auto) | Write |
| AV 10121 | Discharge Cooling Setpoint BAS | Discharge air cooling setpoint (VAV/EVP control) | Write |
| AV 10163 | Demand Limit Setpoint | Demand limit from the BMS, % | Write |
| BV 10116 | Demand Limit Request BAS | Must be Limited for the demand limit to apply | Write |
| MI 10119 | Arbitration Method | Must read Full Source for BAS values to be used | Read |
| MI 10140 | Unit Status | Off, waiting or cooling running | Read |
| AI 10101 | Cooling Capacity Status | Actual cooling capacity, % | Read |
| AI 10124 | Discharge Temperature | Discharge temperature in use | Read |
| BI 10176 | Diagnostic Present | Summary alarm | Read |
Enable & remote start
BV 10140 Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10211 Equipment Stop Status reports the hardwired auto/stop input and BI 13000 Front Panel Auto Stop Status the local setting; BI 10210 shows an emergency stop that needs a manual reset. The integration guide describes the arbitration method: with Full the BMS value is used ahead of local or default values, with Local BMS values are ignored. MI 10119 Arbitration Method (read-only) shows which is active.
Heartbeat & communication loss
The points list gives a 900 s heartbeat for AV 10111 Discharge Temperature BAS and AV 10113 Outdoor Air Temperature BAS; the other AVs list 0. The documents don't describe what happens when it expires.
Sensors & values from the BMS
Write AV 10113 Outdoor Air Temperature BAS or AV 10111 Discharge Temperature BAS and keep refreshing them within the heartbeat. AV 10103 and AV 10101 (Arbitrator) show every source in their priority array, and AI 10118 Outdoor Air Temperature Active and AI 10124 Discharge Temperature show the value in use. The guide notes the default for sensor arbitrators is invalid, so the value must come from the BMS or a local sensor.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- Arbitrator objects show as writable but are meant to be read; write the matching '... BAS' object instead.
- AV 10139 Cooling Capacity Enable is also described as a BAS percentage that limits cooling capacity; the document doesn't say how it relates to AV 10163.
- Points for circuit 2, extra compressors, the economizer and power monitoring only exist on the unit sizes and options that have them.
Trane Symbio 800 IntelliCore Split System (RAUK) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 10101 | Cooling Capacity Status | Actual operating unit cooling capacity | % | Read | |
| AI | 10111 | Outdoor Air Damper Position | Requested position of the Outdoor Air Damper | % | Read | |
| AI | 10118 | Outdoor Air Temperature Active | Active outdoor air temperature currently being used by the controller | °F | Read | |
| AI | 10121 | Discharge Cooling Setpoint Active | Discharge temperature cooling setpoint value resulting from arbitration | °F | Read | |
| AImin | 10124 | Discharge Temperature | Actual discharge temperature being used by the controller | °F | Read | |
| AI | 10154 | Economizer Minimum Position Setpoint Active | Economizer minimum position setpoint value resulting from arbitration | % | Read | |
| AI | 10156 | Outdoor Air Temperature Local | Outdoor air temperature value from a sensor connected to the controller | °F | Read | |
| AI | 10161 | Condenser Capacity | Status of the unit condenser capacity | % | Read | |
| AI | 10181 | Discharge Temperature Local | Discharge temperature value from a sensor connected to the controller | °F | Read | |
| AI | 10206 | Number of Circuits | Number of refrigeration circuits in the unit | Read | ||
| AI | 10207 | Number of Compressors Circuit 1 | Number of compressors on DX circuit 1 of the unit | Read | ||
| AI | 10208 | Number of Compressors Circuit 2 | Number of compressors on DX circuit 2 of the unit | Read | ||
| AI | 10224 | Average Current | Amps | Read | ||
| AI | 10227 | Run Time - Compressor 1A | Run time of Compressor 1A | seconds | Read | |
| AI | 10228 | Starts - Compressor 1A | Number of starts for Compressor 1A | Read | ||
| AI | 10229 | Run Time - Compressor 1B | Run time of Compressor 1B | seconds | Read | |
| AI | 10230 | Starts - Compressor 1B | Number of starts for Compressor 1B | Read | ||
| AI | 10231 | Run Time - Compressor 1C | Run time of Compressor 1C | seconds | Read | |
| AI | 10232 | Starts - Compressor 1C | Number of starts for Compressor 1C | Read | ||
| AI | 10233 | Run Time - Compressor 2A | Run time of Compressor 2A | seconds | Read | |
| AI | 10234 | Starts - Compressor 2A | Number of starts for Compressor 2A | Read | ||
| AI | 10235 | Run Time - Compressor 2B | Run time of Compressor 2B | seconds | Read | |
| AI | 10236 | Starts - Compressor 2B | Number of starts for Compressor 2B | Read | ||
| AI | 10237 | Run Time - Compressor 2C | Run time of Compressor 2C | seconds | Read | |
| AI | 10238 | Starts - Compressor 2C | Number of starts for Compressor 2C | Read | ||
| AI | 10239 | Current L1 | Current for line/leg 1 | Amps | Read | |
| AI | 10240 | Current L2 | Current for line/leg 2 | Amps | Read | |
| AI | 10241 | Current L3 | Current for line/leg 3 | Amps | Read | |
| AI | 10242 | Current Neutral | Current for neutral | Amps | Read | |
| AI | 10243 | Discharge Cooling Setpoint Status | Actual discharge temperature cooling setpoint value | °F | Read | |
| AI | 10246 | Discharge Gauge Pressure Circuit 1 | Refrigerant discharge gauge pressure for DX circuit 1 | PSI | Read | |
| AI | 10247 | Discharge Gauge Pressure Circuit 2 | Refrigerant discharge gauge pressure for DX circuit 2 | PSI | Read | |
| AI | 10249 | Energy Consumption Lifetime | Total energy consumption of the unit (for the lifetime) | kWh | Read | |
| AI | 10255 | Line Frequency | Line frequency when the optional power monitoring option is included | Read | ||
| AI | 10258 | Power Factor | Reported power factor from the optional power monitoring option, when applicable | Read | ||
| AI | 10262 | Suction Gauge Pressure Circuit 1 | Gauge suction pressure for DX circuit 1, in PSIG | PSI | Read | |
| AI | 10263 | Suction Gauge Pressure Circuit 2 | Gauge suction pressure for DX circuit 2, in PSIG | PSI | Read | |
| AI | 10268 | Total Apparent Energy | Total apparent energy as reported by the optional power monitoring feature | kWh | Read | |
| AI | 10269 | Energy Consumption | Total energy consumption of the unit (since last accumulation reset) | kWh | Read | |
| AI | 10270 | Total Reactive Energy | Total reactive energy as reported by the optional power monitoring feature | kWh | Read | |
| AI | 10271 | Total Real Power | Total real power as reported by the optional power monitoring feature | kWh | Read | |
| AI | 10272 | Total Apparent Power | Total apparent power as reported by the optional power monitoring feature | kWh | Read | |
| AI | 10273 | Total Reactive Power | Total reactive power as reported by the optional power monitoring feature | kWh | Read | |
| AI | 10275 | Voltage L1-L2 | Voltage between line/leg L1 and L2 | Volts | Read | |
| AI | 10276 | Voltage L1-L3 | Voltage between line/leg L1 and L3 | Volts | Read | |
| AI | 10277 | Voltage L1-N | Voltage between line/leg L1 and Neutral | Volts | Read | |
| AI | 10278 | Voltage L2-L3 | Voltage between line/leg L2 and L3 | Volts | Read | |
| AI | 10279 | Voltage L2-N | Voltage between line/leg L2 and Neutral | Volts | Read | |
| AI | 10280 | Voltage L3-N | Voltage between line/leg L3 and Neutral | Volts | Read | |
| AI | 10282 | Air Flow Percentage Circuit 1 | Requested condenser percentage for circuit 1 | % | Read | |
| AI | 10283 | Air Flow Percentage Circuit 2 | Requested condenser percentage for circuit 2 | % | Read | |
| AI | 10284 | Discharge Saturated Refrigerant Temperature Circuit 1 | Discharge saturation temperature for DX circuit 1 | °F | Read | |
| AI | 10285 | Discharge Saturated Refrigerant Temperature Circuit 2 | Discharge saturation temperature for DX circuit 2 | °F | Read | |
| AI | 10286 | Suction Saturated Refrigerant Temperature Circuit 1 | Suction saturated refrigerant temperature for DX circuit 1 | °F | Read | |
| AI | 10287 | Suction Saturated Refrigerant Temperature Circuit 2 | Suction saturated refrigerant temperature for DX circuit 2 | °F | Read | |
| AI | 10288 | Suction Temperature Ckt1 | Suction temperature for DX circuit 1 | °F | Read | |
| AI | 10290 | Suction Temperature Ckt2 | Suction temperature for DX circuit 2 | °F | Read | |
| AI | 10324 | Run Time - Compressor 1A (Hours) | Run time of Compressor 1A, in hours | Hours | Read | |
| AI | 10325 | Run Time - Compressor 1B (Hours) | Run time of Compressor 1B, in hours | Hours | Read | |
| AI | 10326 | Run Time - Compressor 1C (Hours) | Run time of Compressor 1C, in hours | Hours | Read | |
| AI | 10327 | Run Time - Compressor 2A (Hours) | Run time of Compressor 2A, in hours | Hours | Read | |
| AI | 10328 | Run Time - Compressor 2B (Hours) | Run time of Compressor 2B, in hours | Hours | Read | |
| AI | 10329 | Run Time - Compressor 2C (Hours) | Run time of Compressor 2C, in hours | Hours | Read | |
| AI | 10330 | Discharge Pressure Circuit 1 | Refrigerant discharge absolute pressure for DX circuit 1, in PSIA | PSI | Read | |
| AI | 10331 | Discharge Pressure Circuit 2 | Refrigerant discharge absolute pressure for DX circuit 2, in PSIA | PSI | Read | |
| AI | 10332 | Suction Pressure Circuit 1 | Absolute suction pressure for DX circuit 1, in PSIA | PSI | Read | |
| AI | 10333 | Suction Pressure Circuit 2 | Absolute suction pressure for DX circuit 2, in PSIA | PSI | Read | |
| AI | 10400 | Local Atmospheric Pressure | Status of the Local Atmospheric Pressure Setting | PSI | Read | |
| AI | 10401 | Unit Design Capacity | Design capacity for the Unit | kWh | Read | |
| AI | 10402 | Ctrl Box Ventilation Fan Run Time | Run time of Control Box Fan | Hours | Read | |
| AV | 10101 | Discharge Temperature Arbitrator | Actual discharge temperature being used by the controller | °F | Write | |
| AV | 10103 | Outdoor Air Temperature Arbitrator | Actual outdoor air temperature being used by the controller | °F | Write | |
| AV | 10111 | Discharge Temperature BAS | Discharge temperature sensor value | °F | Write | |
| AV | 10113 | Outdoor Air Temperature BAS | Outdoor air temperature sensor value | °F | Write | |
| AVmin | 10121 | Discharge Cooling Setpoint BAS | Discharge air temperature cooling setpoint value | °F | Write | |
| AV | 10139 | Cooling Capacity Enable | Deman limit the cooling capacity | % | Write | |
| AV | 10144 | Economizer Minimum Position Setpoint BAS | Economizer minimum position setpoint | % | Write | |
| AV | 10150 | Economizer Outdoor Air Enable Setpoint BAS | °F | Write | ||
| AVmin | 10163 | Demand Limit Setpoint | Demand limit the unit | % | Write | |
| BI | 10001 | microSD | A micro SD card is present | Read | 0 = MicroSD card is not present, 1 = MicroSD card is present | |
| BI | 10002 | USB Port 1 | A USB device is present in port 1 | Read | 0 = USB device is not present, 1 = USB device is present | |
| BI | 10003 | USB Port 2 | A USB device is present in port 2 | Read | 0 = USB device is not present, 1 = USB device is present | |
| BI | 10004 | USB Port 3 | A USB device is present in port 3 | Read | 0 = USB device is not present, 1 = USB device is present | |
| BI | 10005 | USB Port 4 | A USB device is present in port 4 | Read | 0 = USB device is not present, 1 = USB device is present | |
| BI | 10105 | FDD: Unit Economizing When It Should Not | FDD: Indicates when the unit is economizing but should not be | Read | 0 = Inactive, 1 = Active | |
| BI | 10106 | FDD: Unit Not Economizing When it Should Be | FDD: Indicates when the unit is not economizing but should be | Read | 0 = Inactive, 1 = Active | |
| BI | 10111 | Compressor 1A Status | Operating status of compressor 1A | Read | 0 = Off, 1 = Running | |
| BI | 10112 | Compressor 1B Status | Operating status of compressor 1B | Read | 0 = Off, 1 = Running | |
| BI | 10113 | Compressor 1C Status | Operating status of compressor 1C | Read | 0 = Off, 1 = Running | |
| BI | 10114 | Compressor 2A Status | Operating status of compressor 2A | Read | 0 = Off, 1 = Running | |
| BI | 10115 | Compressor 2B Status | Operating status of compressor 2B | Read | 0 = Off, 1 = Running | |
| BI | 10116 | Compressor 2C Status | Operating status of compressor 2C | Read | 0 = Off, 1 = Running | |
| BI | 10132 | FDD: Outdoor Air Temperature Sensor Failure | FDD: Indicates when the outdoor air temperature sensor has failed | Read | 0 = Inactive, 1 = Active | |
| BI | 10155 | Rapid Restart Status | Active status of the Rapid Restart event | Read | 0 = Inactive, 1 = Active | |
| BI | 10164 | Coil Frost Protection Status Circuit 1 | Active when actively in coil frost protection for circuit 1 | Read | 0 = Inactive, 1 = Active | |
| BI | 10165 | Coil Frost Protection Status Circuit 2 | Active when actively in coil frost protection for circuit 2 | Read | 0 = Inactive, 1 = Active | |
| BImin | 10176 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10202 | Condenser Fan Circuit 1 Relay 1 Status | Status of condenser fan circuit 1, relay 1 | Read | 0 = Off, 1 = On | |
| BI | 10203 | Condenser Fan Circuit 1 Relay 2 Status | Status of condenser fan circuit 1, relay 2 | Read | 0 = Off, 1 = On | |
| BI | 10204 | Condenser Fan Circuit 1 Relay 3 Status | Status of condenser fan circuit 1, relay 3 | Read | 0 = Off, 1 = On | |
| BI | 10205 | Condenser Fan Circuit 1 Relay 4 Status | Status of condenser fan circuit 1, relay 4 | Read | 0 = Off, 1 = On | |
| BI | 10206 | Condenser Fan Circuit 2 Relay 1 Status | Status of condenser fan circuit 2, relay 1 | Read | 0 = Off, 1 = On | |
| BI | 10207 | Condenser Fan Circuit 2 Relay 2 Status | Status of condenser fan circuit 2, relay 2 | Read | 0 = Off, 1 = On | |
| BI | 10208 | Condenser Fan Circuit 2 Relay 3 Status | Status of condenser fan circuit 2, relay 3 | Read | 0 = Off, 1 = On | |
| BI | 10209 | Condenser Fan Circuit 2 Relay 4 Status | Status of condenser fan circuit 2, relay 4 | Read | 0 = Off, 1 = On | |
| BI | 10210 | Emergency Stop | Status of the emergency stop function of the unit | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | |
| BI | 10211 | Equipment Stop Status | Status of the externally- wired auto/stop input | Read | 0 = Stop, 1 = Auto | |
| BI | 10218 | Diagnostic: Manual Reset Required | A diagnostic exists that requires manual reset | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10219 | Economizer Airside Status | Status of airside economizing | Read | 0 = Inactive, 1 = Active | |
| BI | 10605 | Diagnostic: Loss of Charge Lockout Ckt1 | A loss of charge lockout diagnostic exists for DX circuit 1 | Read | 0 = No, 1 = Yes | |
| BI | 10606 | Diagnostic: Loss of Charge Lockout Ckt2 | A loss of charge lockout diagnostic exists for DX circuit 2 | Read | 1 = No, 1 = Yes | |
| BI | 10619 | Diagnostic Shutdown Present | Unit is shut down due to diagnostics | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10620 | Diagnostic: Local Manual Reset Required | Diagnostic Reset required [Local only] | Read | 0 = Normal, 1 = In Alarm | |
| BI | 13000 | Front Panel Auto Stop Status | Status of the the Local Auto Stop setting | Read | 0 = Stop, 1 = Auto | |
| BI | 13002 | Manual Override Exists | Indicator of a Manual Override being active | Read | 0 = Off, 1 = On | |
| BI | 13003 | Frostat Input Status Circuit 1 | Status of the Frostat input, circuit 1 | Read | 0 = Open, 1 = Closed | |
| BI | 13004 | Frostat Input Status Circuit 2 | Status of the Frostat input, circuit 2 | Read | 0 = Open, 1 = Closed | |
| BI | 13005 | Freezestat Input Status | Status of the Freezestat Input | Read | 0 = Open, 1 = Closed | |
| BI | 13006 | Refrigerant Leak Detection | Active status of a refrigerant leak event | Read | 0 = Open, 1 = Closed | |
| BV | 10110 | Reset Diagnostic | Request to reset any remote controller diangostic | Write | 0 = Normal, 1 = Reset | |
| BV | 10115 | Cooling Lockout BAS | Command to (temporarily) prevent all mechanical cooling | Write | 0 = Normal, 1 = Locked Out | |
| BVmin | 10116 | Demand Limit Request BAS | Demand limit the unit | Write | 0 = Not Limited, 1 = Limited | |
| BV | 10117 | Energy Consumption Reset | Reset the energy consumption accumulated total | Write | 0 = Accumulating, 1 = Reset | |
| BV | 10120 | Rapid Restart Enable | Enables/Disables rapid restart operation | Write | 0 = Disable, 1 = Enable | |
| BVmin | 10140 | Auto Stop Command BAS | BAS Auto Stop Command | Write | 0 = Stop, 1 = Auto | |
| MI | 10105 | Cooling Reset Type Status | Type of cooling reset used by the controller | Read | 1 = None, 2 = Outdor Air | |
| MI | 10108 | Economizer Type | General description of the type of economizer system | Read | 1 = None, 2 = 2 Position Ventilation, 3 = Modulation Economizer, 4 = 2 Position Ventilation/Waterside Economizer, 5 = Waterside Economizer, 6 = Airside/Waterside Economizer, 7 = TRAQ Damper, 8 = Airside Economizer and TRAQ Damper/Sensor, 9 = Waterside Economizer and TRAQ | |
| MI | 10109 | Condenser Type | General description of the equipment condenser system | Read | 1 = None, 2 = Air Cooled Condenser, 3 = Water Cooled Condenser, 4 = Evaporative Condenser | |
| MI | 10117 | Refrigerant Type | Type of refrigerant used in the equipment | Read | 1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134A, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E), 17 = R-454B | |
| MImin | 10119 | Arbitration Method | Read | 1 = Full Source, 2 = Local Source, 3 = Default Source | ||
| MI | 10121 | Electrical Service Type | Electrical service type used for the unit | Read | 1 = A+N, 2 = A+B, 3 = A+B+N, 4 = A+B+C, 5 = A+B+C+N | |
| MI | 10132 | Economizer Decision Method | Method of enabling airside economizing | Read | 1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy | |
| MImin | 10140 | Unit Status | Read | 1 = Off, 2 = Waiting, 3 = Running | ||
| MI | 10144 | Economizer System Status | Status of enabling economizing | Read | 1 = Disabled, 2 = Enabled, 3 = Not Present | |
| MI | 10145 | Model Information [GEN2] | Model Information | Read | 64 = RAUK | |
| MV | 10103 | Economizer Airside Enable BAS | Enable airside economizing | Write | 1 = Disabled, 2 = Enabled, 3 = Auto |
No points match these filters.
Object ID lookup: Trane Symbio 800 IntelliCore Split System point IDs by name
AI10101Cooling Capacity StatusAI10111Outdoor Air Damper PositionAI10118Outdoor Air Temperature ActiveAI10121Discharge Cooling Setpoint ActiveAI10124Discharge TemperatureAI10154Economizer Minimum Position Setpoint ActiveAI10156Outdoor Air Temperature LocalAI10161Condenser CapacityAI10181Discharge Temperature LocalAI10206Number of CircuitsAI10207Number of Compressors Circuit 1AI10208Number of Compressors Circuit 2AI10224Average CurrentAI10227Run Time - Compressor 1AAI10228Starts - Compressor 1AAI10229Run Time - Compressor 1BAI10230Starts - Compressor 1BAI10231Run Time - Compressor 1CAI10232Starts - Compressor 1CAI10233Run Time - Compressor 2AAI10234Starts - Compressor 2AAI10235Run Time - Compressor 2BAI10236Starts - Compressor 2BAI10237Run Time - Compressor 2CAI10238Starts - Compressor 2CAI10239Current L1AI10240Current L2AI10241Current L3AI10242Current NeutralAI10243Discharge Cooling Setpoint StatusAI10246Discharge Gauge Pressure Circuit 1AI10247Discharge Gauge Pressure Circuit 2AI10249Energy Consumption LifetimeAI10255Line FrequencyAI10258Power FactorAI10262Suction Gauge Pressure Circuit 1AI10263Suction Gauge Pressure Circuit 2AI10268Total Apparent EnergyAI10269Energy ConsumptionAI10270Total Reactive EnergyAI10271Total Real PowerAI10272Total Apparent PowerAI10273Total Reactive PowerAI10275Voltage L1-L2AI10276Voltage L1-L3AI10277Voltage L1-NAI10278Voltage L2-L3AI10279Voltage L2-NAI10280Voltage L3-NAI10282Air Flow Percentage Circuit 1AI10283Air Flow Percentage Circuit 2AI10284Discharge Saturated Refrigerant Temperature Circuit 1AI10285Discharge Saturated Refrigerant Temperature Circuit 2AI10286Suction Saturated Refrigerant Temperature Circuit 1AI10287Suction Saturated Refrigerant Temperature Circuit 2AI10288Suction Temperature Ckt1AI10290Suction Temperature Ckt2AI10324Run Time - Compressor 1A (Hours)AI10325Run Time - Compressor 1B (Hours)AI10326Run Time - Compressor 1C (Hours)AI10327Run Time - Compressor 2A (Hours)AI10328Run Time - Compressor 2B (Hours)AI10329Run Time - Compressor 2C (Hours)AI10330Discharge Pressure Circuit 1AI10331Discharge Pressure Circuit 2AI10332Suction Pressure Circuit 1AI10333Suction Pressure Circuit 2AI10400Local Atmospheric PressureAI10401Unit Design CapacityAI10402Ctrl Box Ventilation Fan Run TimeAV10101Discharge Temperature ArbitratorAV10103Outdoor Air Temperature ArbitratorAV10111Discharge Temperature BASAV10113Outdoor Air Temperature BASAV10121Discharge Cooling Setpoint BASAV10139Cooling Capacity EnableAV10144Economizer Minimum Position Setpoint BASAV10150Economizer Outdoor Air Enable Setpoint BASAV10163Demand Limit SetpointBI10001microSDBI10002USB Port 1BI10003USB Port 2BI10004USB Port 3BI10005USB Port 4BI10105FDD: Unit Economizing When It Should NotBI10106FDD: Unit Not Economizing When it Should BeBI10111Compressor 1A StatusBI10112Compressor 1B StatusBI10113Compressor 1C StatusBI10114Compressor 2A StatusBI10115Compressor 2B StatusBI10116Compressor 2C StatusBI10132FDD: Outdoor Air Temperature Sensor FailureBI10155Rapid Restart StatusBI10164Coil Frost Protection Status Circuit 1BI10165Coil Frost Protection Status Circuit 2BI10176Diagnostic PresentBI10202Condenser Fan Circuit 1 Relay 1 StatusBI10203Condenser Fan Circuit 1 Relay 2 StatusBI10204Condenser Fan Circuit 1 Relay 3 StatusBI10205Condenser Fan Circuit 1 Relay 4 StatusBI10206Condenser Fan Circuit 2 Relay 1 StatusBI10207Condenser Fan Circuit 2 Relay 2 StatusBI10208Condenser Fan Circuit 2 Relay 3 StatusBI10209Condenser Fan Circuit 2 Relay 4 StatusBI10210Emergency StopBI10211Equipment Stop StatusBI10218Diagnostic: Manual Reset RequiredBI10219Economizer Airside StatusBI10605Diagnostic: Loss of Charge Lockout Ckt1BI10606Diagnostic: Loss of Charge Lockout Ckt2BI10619Diagnostic Shutdown PresentBI10620Diagnostic: Local Manual Reset RequiredBI13000Front Panel Auto Stop StatusBI13002Manual Override ExistsBI13003Frostat Input Status Circuit 1BI13004Frostat Input Status Circuit 2BI13005Freezestat Input StatusBI13006Refrigerant Leak DetectionBV10110Reset DiagnosticBV10115Cooling Lockout BASBV10116Demand Limit Request BASBV10117Energy Consumption ResetBV10120Rapid Restart EnableBV10140Auto Stop Command BASMI10105Cooling Reset Type StatusMI10108Economizer TypeMI10109Condenser TypeMI10117Refrigerant TypeMI10119Arbitration MethodMI10121Electrical Service TypeMI10132Economizer Decision MethodMI10140Unit StatusMI10144Economizer System StatusMI10145Model Information [GEN2]MV10103Economizer Airside Enable BAS
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- Name suffixes carry meaning: Status/Local/Active/Input are read-only, BAS/Command/Request/Setpoint value objects are the ones a BAS writes, and Arbitrator objects show which source is winning.
- Compressor run-time AIs (AI 10227, 10229...) report seconds to a third-party BAS and hours to Tracer SC+, per the source footnote; AI 10324-10329 give hours.
- BI 10606 states are printed as '1 = No, 1 = Yes' in the source; BI 10605 uses 0 = No, 1 = Yes.
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 IntelliCore Split System (RAUK) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 IntelliCore Split System (RAUK)
How many BACnet points does the Trane Symbio 800 IntelliCore Split System (RAUK) have?
This list has 136 BACnet objects: 70 analog inputs, 9 analog values, 40 binary inputs, 6 binary values, 10 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 IntelliCore Split System (RAUK) BACnet points are writable?
16 of the 136 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Trane Symbio 800 IntelliCore Split System (RAUK) BACnet documentation?
The source is Symbio 800 Integration Points List BACnet/Modbus - IntelliCore Split System (RAUK) (BAS-PTS036A-EN), revision 12/04/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS036A-EN_12042024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 IntelliCore Split System (RAUK)?
Start with BV 10140 Auto Stop Command BAS (BMS auto/stop command (0 = Stop, 1 = Auto)); AV 10121 Discharge Cooling Setpoint BAS (Discharge air cooling setpoint (VAV/EVP control)); AV 10163 Demand Limit Setpoint (Demand limit from the BMS, %); BV 10116 Demand Limit Request BAS (Must be Limited for the demand limit to apply); MI 10119 Arbitration Method (Must read Full Source for BAS values to be used); MI 10140 Unit Status (Off, waiting or cooling running); AI 10101 Cooling Capacity Status (Actual cooling capacity, %); AI 10124 Discharge Temperature (Discharge temperature in use); BI 10176 Diagnostic Present (Summary alarm).
How do I enable BMS control of the Trane Symbio 800 IntelliCore Split System (RAUK)?
BV 10140 Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop. BI 10211 Equipment Stop Status reports the hardwired auto/stop input and BI 13000 Front Panel Auto Stop Status the local setting; BI 10210 shows an emergency stop that needs a manual reset. The integration guide describes the arbitration method: with Full the BMS value is used ahead of local or default values, with Local BMS values are ignored. MI 10119 Arbitration Method (read-only) shows which is active.
Does the Trane Symbio 800 IntelliCore Split System (RAUK) need a BACnet heartbeat or have a communication timeout?
The points list gives a 900 s heartbeat for AV 10111 Discharge Temperature BAS and AV 10113 Outdoor Air Temperature BAS; the other AVs list 0. The documents don't describe what happens when it expires.
Can the BMS supply sensor values to the Trane Symbio 800 IntelliCore Split System (RAUK)?
Write AV 10113 Outdoor Air Temperature BAS or AV 10111 Discharge Temperature BAS and keep refreshing them within the heartbeat. AV 10103 and AV 10101 (Arbitrator) show every source in their priority array, and AI 10118 Outdoor Air Temperature Active and AI 10124 Discharge Temperature show the value in use. The guide notes the default for sensor arbitrators is invalid, so the value must come from the BMS or a local sensor.
How do I check these points on the real Symbio 800 IntelliCore Split System (RAUK)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet/Modbus - IntelliCore Split System (RAUK) · BAS-PTS036A-EN · rev. 12/04/2024. Object names, instances and units are reproduced as published; descriptions are our own.