Rooftop unit / air handler controller · BACnet points list
Trane Symbio 800 IntelliPak BACnet points list
Updated 28 October 2026
IntelliPak rooftops with Symbio 800 controls publish about 380 BACnet objects covering supply and exhaust fans, economizer, DX compressors, heat, energy recovery and power metering. Writable objects are AV/BV/MV setpoints and BAS commands, some with a heartbeat. Power meter points only appear when the meter option is installed.
This page lists 380 BACnet objects for the Trane Symbio 800 IntelliPak — 95 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 IntelliPak
- Equipment
- Rooftop unit / air handler controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 380 (95 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- 62000663-4-20-0006
- Also known as
- Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 IntelliPak
Schedule the unit with MV 10106 Occupancy Request and write the BAS setpoints you need: space, discharge air, duct static. MI 10119 Arbitration Method must read 'Full (Auto) Source' for BAS values to win over local ones. Sensor BAS points and the External setpoints AV 10183-10187 carry a 900 s heartbeat in the points list, so rewrite them periodically.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 10106 | Occupancy Request | Occupancy command from the BMS schedule | Write |
| MV 10104 | Heat Cool Mode Request | Mode command from the BMS | Write |
| AV 10127 | Space Temperature Setpoint BAS | Space setpoint from the BMS | Write |
| AV 10121 | Discharge Air Cooling Setpoint BAS | Supply air cooling setpoint from the BMS | Write |
| AV 10143 | Duct Static Pressure Setpoint BAS | Duct static setpoint on VAV units | Write |
| MI 10119 | Arbitration Method | Must read Full (Auto) for BAS values to be used | Read |
| MI 10103 | Occupancy Status | Confirms the occupancy in effect | Read |
| BI 10226 | Supply Fan Output Status | Supply fan running (1 = on) | Read |
| AI 10124 | Discharge Air Temperature | Supply air temperature in use (BAS or local sensor) | Read |
| BI 10176 | Diagnostic Present | Summary alarm | Read |
Enable & remote start
The integration guide describes an arbitration method: with 'full/auto' the BMS value is used ahead of local or default values, and with 'local' BMS values are ignored. MI 10119 Arbitration Method (read-only) shows which is active; the documents don't name a BACnet point to change it. BI 10211 Equipment Stop Status reports stop/auto; no BAS start/stop command is listed.
Heartbeat & communication loss
The points list gives a 900 s heartbeat for the sensor BAS values (AV 10111, 10113-10116, 10118, 10119) and the External setpoints (AV 10183-10187). The Symbio 800 integration guide doesn't describe what happens when it expires.
Sensors & values from the BMS
Write BMS values to the '... BAS' AVs (AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS, AV 10119 Space Humidity BAS, AV 10118 Space CO2 Concentration BAS, AV 10111 Discharge Air Temperature BAS). The '... Arbitrator' AVs show all sources in their priority array; the guide notes the default for sensor arbitrators is invalid, so the value must come from the BMS or a local sensor. Direct capacity/fan/damper control uses the 'Setpoint External' AVs together with their 'Setpoint Enable External' BVs (e.g. AV 10187 with BV 10131).
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- BI-11000 to BI-11999 are reserved for user-created diagnostic points made in Tracer TU.
- Arbitrator objects show as writable but are meant to be read; write the matching '... BAS' object instead.
Trane Symbio 800 IntelliPak BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10101 | Cooling Capacity Status | Actual operating unit cooling capacity | % | Read | |
| AI | 10102 | Heating Capacity Primary Status | Unit (primary) heating capacity | % | Read | |
| AI | 10104 | Outdoor Air Relative Humidity Local | Outdoor air humidity value from sensor connected to the controller | % | Read | |
| AI | 10105 | Outdoor Air Flow Local | CFM | Read | ||
| AI | 10107 | Space Static Pressure Local | Space statice pressure from a sensor connected to the controller | Inches of Water | Read | |
| AI | 10110 | Return Air Humidity Local | Return air humidity value from sensor connected to the controller | % | Read | |
| AI | 10111 | Outdoor Air Damper Position | Position of the outside air damper as requested by the controller | % | Read | |
| AI | 10112 | Exhaust Damper Position | Unit exhaust damper position | % | Read | |
| AI | 10113 | Return Plenum Static Pressure | Return plenum pressure value measured by a unit mounted sensor | Inches of Water | Read | |
| AI | 10114 | Outdoor Air Minimum Flow Setpoint Active | Active minimum outdoor air flow setpoint being used by the controller | CFM | Read | |
| AI | 10116 | Space Humidity Active | Active space relative humidity being used by the controller | % | Read | |
| AI | 10117 | Outdoor Air Dew Point | °F | Read | ||
| AI | 10118 | Outdoor Air Temperature Active | Active outdoor air temperature currently being used by the controller | °F | Read | |
| AI | 10120 | Outdoor Air Humidity Active | Active outdoor air humidity value | % | Read | |
| AI | 10121 | Discharge Air Cooling Setpoint Active | Discharge air temperature cooling setpoint value resulting from any setpoint arbitration | °F | Read | |
| AI | 10122 | Discharge Air Heating Setpoint Active | Discharge air temperature heating setpoint value resulting from any setpoint arbitration | °F | Read | |
| AI | 10123 | Duct Static Pressure Setpoint Active | Duct static pressure control setpoint value resulting from any setpoint arbitration | Inches of Water | Read | |
| AImin | 10124 | Discharge Air Temperature | Actual discharge air temperature being used by the controller | °F | Read | |
| AI | 10125 | Mixed Air Temperature Local | Mixed air temperature value from a sensor physically connected to the controller | °F | Read | |
| AI | 10126 | Return Air Temperature | Actual return air temperature being used by the controller | °F | Read | |
| AI | 10128 | Space Static Pressure Setpoint Active | Active space static pressure being used by the controller | Inches of Water | Read | |
| AI | 10135 | Space Dehumidification Setpoint Active | Active (occupied) space dehumidification setpoint, considering all potential sources | % | Read | |
| AI | 10152 | Exhaust Fan Speed Status | Commanded speed of the modulating exhaust fan | % | Read | |
| AI | 10153 | Return Fan Speed Status | Unit commanded return fan speed | % | Read | |
| AI | 10154 | Economizer Minimum Position Setpoint Active | Economizer minimum position setpoint value resulting from any setpoint arbitration | % | Read | |
| AI | 10155 | Duct Static Pressure Local | Duct static pressure value from a sensor physically connected to the controller | Inches of Water | Read | |
| AI | 10156 | Outdoor Air Temperature Local | Outdoor air temperature value from a sensor physically connected to the controller | °F | Read | |
| AI | 10157 | Dehumidification Control Status | Status of the unit dehumidification capacity | % | Read | |
| AI | 10161 | Condenser Capacity | Status of the unit condenser capacity, in percent | % | Read | |
| AI | 10166 | Energy Recovery Leaving Exhaust Temperatue Status | Energy recovery leaving exhaust temperature | °F | Read | |
| AI | 10167 | Energy Recovery Outdoor Air Bypass Damper Status | Energy recovery outdoor air bypass damper position | % | Read | |
| AI | 10168 | Energy Recovery Exhaust Air Bypass Damper Position | % | Read | ||
| AI | 10172 | Reheat Capacity Status | Unit reheat capacity being requested by the controller, in percent | % | Read | |
| AI | 10173 | Supply Fan Speed Status | Commanded speed of the supply fan, in percent | % | Read | |
| AI | 10181 | Discharge Air Temperature Local | Discharge air temperature value from a sensor physically connected to the controller | °F | Read | |
| AI | 10182 | Duct Static Pressure Active | Duct static pressure value being used by the unit | Inches of Water | Read | |
| AI | 10183 | Outdoor Air Enthalpy Active | Outdoor air enthalpy value being utilized by the unit | BTU/lb | Read | |
| AI | 10185 | Outdoor Air Flow Active | Active outdoor air flow being used by the controller | CFM | Read | |
| AI | 10186 | Space Temperature Active | Active space temperature being used by the controller | °F | Read | |
| AI | 10187 | Space Static Pressure Active | Space static pressure value from a unit mounted sensor | Inches of Water | Read | |
| AI | 10188 | Space CO2 Concentration Active | Active space CO2 concentration being used by the controller | PPM | Read | |
| AI | 10190 | Space Temperature Cooling Setpoint Input | (occupied) cooling temperature setpoint from the connected space sensor | °F | Read | |
| AI | 10191 | Space Temperature Heating Setpoint Input | (occupied) heating temperature setpoint from the connected space sensor | °F | Read | |
| AI | 10197 | Heat Type | Identifies the product heat type | Read | ||
| AI | 10198 | Cabinet Style | Cabinet style of the unit | Read | ||
| AI | 10199 | Cool Type | Type of cooling in the unit | Read | ||
| AI | 10200 | Preheat Type | Type of preheat in the unit | Read | ||
| AI | 10201 | Reheat Type | Type of reheat in the unit | Read | ||
| AI | 10202 | Supply Fan Type | Type of supply fan in the unit | Read | ||
| AI | 10203 | Exhaust Or Return Fan Type | Type of exhaust fan or return fan in the unit | Read | ||
| AI | 10204 | Exhaust Fan Speed Setpoint Active | Active setpoint input to exhaust/relief fan control | % | Read | |
| AI | 10206 | Number of Circuits | Number of refrigeration circuits in the unit | Read | ||
| AI | 10207 | Number of Compressors Circuit 1 | Number of compressors on DX circuit 1 of the unit | Read | ||
| AI | 10208 | Number of Compressors Circuit 2 | Number of compressors on DX circuit 2 of the unit | Read | ||
| AI | 10210 | Return Isolation Damper Input | Requested position of the return isolation damper | % | Read | |
| AI | 10213 | Space CO2 Concentration Input | Space CO2 concentration from a sensor connected to the controller | PPM | Read | |
| AI | 10214 | Space Dehumidification Unoccupied Setpoint Active | Active unoccupied space dehumidification setpoint, considering all potential sources | % | Read | |
| AI | 10215 | Space Humidity Input | Space relative humidity from a sensor connected to the controller | % | Read | |
| AI | 10216 | Space Temp Cooling Setpoint Status | (occupied) cooling temperature setpoint from the connected space sensor module | °F | Read | |
| AI | 10217 | Space Temp Heating Setpoint Status | (occupied) heating temperature setpoint from the connected space sensor module | °F | Read | |
| AI | 10218 | Space Temperature Input | °F | Read | ||
| AI | 10221 | Space Temperature Setpoint Active | Active space temperature setpoint being used by the controller | °F | Read | |
| AI | 10222 | Supply Isolation Damper Input | Requested position of the supply isolation damper, when present | % | Read | |
| AI | 10224 | Average Current | Amps | Read | ||
| AI | 10227 | Run Time - Compressor 1A | Run time of Compressor 1A | Read | ||
| AI | 10228 | Starts - Compressor 1A | Number of starts for Compressor 1A | Read | ||
| AI | 10229 | Run Time - Compressor 1B | Run time of Compressor 1B | Read | ||
| AI | 10230 | Starts - Compressor 1B | Number of starts for Compressor 1B | Read | ||
| AI | 10231 | Run Time - Compressor 1C | Run time of Compressor 1C | Read | ||
| AI | 10232 | Starts - Compressor 1C | Number of starts for Compressor 1C | Read | ||
| AI | 10233 | Run Time - Compressor 2A | Run time of Compressor 2A | Read | ||
| AI | 10234 | Starts - Compressor 2A | Number of starts for Compressor 2A | Read | ||
| AI | 10235 | Run Time - Compressor 2B | Run time of Compressor 2B | Read | ||
| AI | 10236 | Starts - Compressor 2B | Number of starts for Compressor 2B | Read | ||
| AI | 10237 | Run Time - Compressor 2C | Run time of Compressor 2C | Read | ||
| AI | 10238 | Starts - Compressor 2C | Number of starts for Compressor 2C | Read | ||
| AI | 10239 | Current L1 | Amps | Read | ||
| AI | 10240 | Current L2 | Amps | Read | ||
| AI | 10241 | Current L3 | Amps | Read | ||
| AI | 10242 | Current Neutral | Amps | Read | ||
| AI | 10243 | Discharge Air Cooling Setpoint Status | °F | Read | ||
| AI | 10244 | Discharge Air Heating Setpoint Status | °F | Read | ||
| AI | 10246 | Discharge Gauge Pressure Circuit 1 | Refrigerant discharge gauge pressure for DX circuit 1 | PSI | Read | |
| AI | 10247 | Discharge Gauge Pressure Circuit 2 | Refrigerant discharge gauge pressure for DX circuit 2 | PSI | Read | |
| AI | 10249 | Energy Consumption Lifetime | Total energy consumption of the unit (for the lifetime of the unit) | kWh | Read | |
| AI | 10250 | Evaporator Leaving Air Temperature | Leaving air temperature of the evaporator | °F | Read | |
| AI | 10251 | Evaporator Leaving Air Temperature Evap A | Leaving air temperature of evaporator A when a split evaporator is used | °F | Read | |
| AI | 10252 | Evaporator Leaving Air Temperature Evap B | Leaving air temperature of evaporator B when a split evaporator is used | °F | Read | |
| AI | 10253 | Evaporator Leaving Air Temperature Setpoint Active | Evaporator leaving air temperature setpoint value resulting from any setpoint arbitration | °F | Read | |
| AI | 10254 | Final Filter Differential Pressure Local | Status of the final filter differential pressure sensor input on the controller | Inches of Water | Read | |
| AI | 10255 | Line Frequency | Line frequency when the optional power monitoring option is included | Read | ||
| AI | 10256 | Mixed Air Temperature Evap A | Mixed air temperature associated with evaporator A | °F | Read | |
| AI | 10257 | Mixed Air Temperature Evap B | Mixed air temperature associated with evaporator B | °F | Read | |
| AI | 10258 | Power Factor | Reported power factor from the optional power monitoring option, when applicable | Read | ||
| AI | 10259 | Prefilter Differential Pressure Local | Inches of Water | Read | ||
| AI | 10262 | Suction Gauge Pressure Circuit 1 | Suction pressure for DX circuit 1, in PSIG | PSI | Read | |
| AI | 10263 | Suction Gauge Pressure Circuit 2 | Suction pressure for DX circuit 2, in PSIG | PSI | Read | |
| AI | 10268 | Total Apparent Energy | Total apparent energy as reported by the optional power monitoring feature | kWh | Read | |
| AI | 10269 | Energy Consumption | Total energy consumption of the unit (since last accumulation reset) | kWh | Read | |
| AI | 10270 | Total Reactive Energy | Total reactive energy as reported by the optional power monitoring feature | kWh | Read | |
| AI | 10271 | Total Real Power | Total real power as reported by the optional power monitoring feature | kW | Read | |
| AI | 10272 | Total Apparent Power | Total apparent power as reported by the optional power monitoring feature | kW | Read | |
| AI | 10273 | Total Reactive Power | Total reactive power as reported by the optional power monitoring feature | kW | Read | |
| AI | 10274 | Unit Source ID | Individual diagnostics are reported with dedicated points, variables, registers | Read | ||
| AI | 10275 | Voltage L1-L2 | Voltage between line/leg L1 and L2 | Volts | Read | |
| AI | 10276 | Voltage L1-L3 | Voltage between line/leg L1 and L3 | Volts | Read | |
| AI | 10277 | Voltage L1-N | Voltage between line/leg L1 and Neutral | Volts | Read | |
| AI | 10278 | Voltage L2-L3 | Voltage between line/leg L2 and L3 | Volts | Read | |
| AI | 10279 | Voltage L2-N | Voltage between line/leg L2 and Neutral | Volts | Read | |
| AI | 10280 | Voltage L3-N | Voltage between line/leg L3 and Neutral | Volts | Read | |
| AI | 10281 | Discharge Air Temperature Setpoint Active | Discharge air temperature setpoint value resulting from any setpoint arbitration | °F | Read | |
| AI | 10282 | Air Flow Percentage Circuit 1 | Requested condenser percentage for circuit 1 | % | Read | |
| AI | 10283 | Air Flow Percentage Circuit 2 | Requested condenser percentage for circuit 2 | % | Read | |
| AI | 10284 | Discharge Saturated Refrigeration Temperature Circuit 1 | Discharge saturated refrigerant temperature for DX circuit 2 | °F | Read | |
| AI | 10285 | Discharge Saturated Refrigeration Temperature Circuit 2 | Discharge saturated refrigerant temperature for DX circuit 2 | °F | Read | |
| AI | 10286 | Suction Saturated Refrigerant Temperature Circuit 1 | Suction saturated refrigerant temperature for DX circuit 1 | °F | Read | |
| AI | 10287 | Suction Saturated Refrigerant Temperature Circuit 2 | Suction saturated refrigerant temperature for DX circuit 2 | °F | Read | |
| AI | 10288 | Suction Temperature Evap 1A | Suction temperature for evaporator 1A | °F | Read | |
| AI | 10289 | Suction Temperature Evap 1B | Suction temperature for evaporator 1B | °F | Read | |
| AI | 10290 | Suction Temperature Evap 2A | Suction temperature for evaporator 2A | °F | Read | |
| AI | 10291 | Suction Temperature Evap 2B | Suction temperature for evaporator 2B | °F | Read | |
| AI | 10292 | Occupied Cooling Setpoint | Active occupied cooling setpoint being | °F | Read | |
| AI | 10293 | Occupied Heating Setpoint | Active occupied heating setpoint being | °F | Read | |
| AI | 10294 | Occupied Standby Cooling Setpoint | Active occupied standby cooling setpoint being | °F | Read | |
| AI | 10295 | Occupied Standby Heating Setpoint | Active occupied standby heating setpoint being | °F | Read | |
| AI | 10296 | Supply Fan Speed Setpoint Active | Active setpoint input to supply fan control | % | Read | |
| AI | 10297 | Discharge Air Temperature Maximum Cool Limit Active | Maximum cooling setpoint allowed to be calculated by Space Temp Control | °F | Read | |
| AI | 10298 | Discharge Air Temperature Minimum Heat Limit Active | Minimum heating setpoint allowed to be calculated by Space Temp Control | °F | Read | |
| AI | 10299 | Discharge Air Temperature Minimum Cool Limit Active | Minimum cooling setpoint allowed to be calculated by Space Temp Control | °F | Read | |
| AI | 10300 | Discharge Air Temperature Maximum Heat Limit Active | Minimum heating setpoint allowed to be calculated by Space Temp Control | °F | Read | |
| AI | 10303 | Energy Recovery Wheel Filter Differential Pressure | Differntial pressure across the energy wheel filter while bypass dampers are closed | Inches of Water | Read | |
| AI | 10304 | Average Current Meter 2 | Average current for the second power meter | Amps | Read | |
| AI | 10305 | Current L1 Meter 2 | Current for line/leg 1 for the second power meter | Amps | Read | |
| AI | 10306 | Current L2 Meter 2 | Current for line/leg 2 for the second power meter | Amps | Read | |
| AI | 10307 | Current L3 Meter 2 | Current for line/leg 3 for the second power meter | Amps | Read | |
| AI | 10308 | Current Neutral Meter 2 | Current for neutral for the second power meter | Amps | Read | |
| AI | 10309 | Energy Consumption Meter 2 | kWh | Read | ||
| AI | 10310 | Energy Consumption Lifetime Meter 2 | Energy consumption for the second power meter | kWh | Read | |
| AI | 10311 | Line Frequency Meter 2 | Line frequency for the second power meter | Read | ||
| AI | 10312 | Power Factor Meter 2 | Power factor for the second power meter | Read | ||
| AI | 10313 | Total Apparent Energy Meter 2 | Total apparent energy for the second power meter | kWh | Read | |
| AI | 10314 | Total Apparent Power Meter 2 | Total apparent power for the second power meter | kW | Read | |
| AI | 10315 | Total Reactive Energy Meter 2 | Total reactive energy for the second power meter | kWh | Read | |
| AI | 10316 | Total Reactive Power Meter 2 | Total reactive power for the second power meter | kW | Read | |
| AI | 10317 | Total Real Power Meter 2 | Total real power for the second power meter | kW | Read | |
| AI | 10318 | Voltage L1-L2 Meter 2 | Voltage between line/leg L1 and L2 for the second power meter | Volts | Read | |
| AI | 10319 | Voltage L1-L3 Meter 2 | Voltage between line/leg L1 and L3 for the second power meter | Volts | Read | |
| AI | 10320 | Voltage L1-N Meter 2 | Voltage between line/leg L1 and Neutral for the second power meter | Volts | Read | |
| AI | 10321 | Voltage L2-L3 Meter 2 | Voltage between line/leg L2 and L3 for the second power meter | Volts | Read | |
| AI | 10322 | Voltage L2-N Meter 2 | Voltage between line/leg L2 and Neutral for the second power meter | Volts | Read | |
| AI | 10323 | Voltage L3-N Meter 2 | Voltage between line/leg L3 and Neutral for the second power meter | Volts | Read | |
| AI | 10324 | Run Time - Compressor 1A (Hours) | Run time of Compressor 1A, in hours | Read | ||
| AI | 10325 | Run Time - Compressor 1B (Hours) | Run time of Compressor 1B, in hours | Read | ||
| AI | 10326 | Run Time - Compressor 1C (Hours) | Run time of Compressor 1C, in hours | Read | ||
| AI | 10327 | Run Time - Compressor 2A (Hours) | Run time of Compressor 2A, in hours | Read | ||
| AI | 10328 | Run Time - Compressor 2B (Hours) | Run time of Compressor 2B, in hours | Read | ||
| AI | 10329 | Run Time - Compressor 2C (Hours) | Run time of Compressor 2C, in hours | Read | ||
| AI | 10330 | Discharge Pressure Circuit 1 | Refrigerant discharge absolute pressure for DX circuit 1 | PSI | Read | |
| AI | 10331 | Discharge Pressure Circuit 2 | Refrigerant discharge absolute pressure for DX circuit 2 | PSI | Read | |
| AI | 10332 | Suction Pressure Circuit 1 | Suction pressure for DX circuit 1, in PSIA | PSI | Read | |
| AI | 10333 | Suction Pressure Circuit 2 | Suction pressure for DX circuit 2, in PSIA | PSI | Read | |
| AI | 10334 | Space Dew Point | Calculated space dew point from space humid active, space temp active | °F | Read | |
| AI | 10335 | Space Dew Point Setpoint Active | Active occupied space dew point setpoint | °F | Read | |
| AI | 10336 | Space Dew Point Unocc Setpoint Active | Active unoccupied space dew point setpoint | °F | Read | |
| AI | 10337 | Heating Capacity Setpoint Active | Status of current heating capacity request | % | Read | |
| AI | 10338 | Outdoor Air Damper Position Setpoint Active | Status of current outdoor air damper position request | % | Read | |
| AI | 10339 | Return Fan Speed Setpoint Active | Status of current return fan speed request | % | Read | |
| AI | 10340 | Cooling Capacity Setpoint Active | Status of current cooling capacity request | % | Read | |
| AI | 10341 | Rfgt LFL Conc Alarm Threshold Sensor A | Internal sensor % of refrigerant to trip alarm A | % | Read | |
| AI | 10342 | Rfgt LFL Conc Alarm Threshold Sensor B | Internal sensor % of refrigerant to trip alarm B | % | Read | |
| AI | 10343 | Refrigerant LFL Concentration Sensor A | Actual refrigerant being measured by sensor A | % | Read | |
| AI | 10344 | Refrigerant LFL Concentration Sensor B | Actual refrigerant being measured by sensor B | % | Read | |
| AI | 10345 | Rfgt LFL Conc Alarm Threshold Sensor C | Internal sensor % of refrigerant to trip alarm C | % | Read | |
| AI | 10346 | Rfgt LFL Conc Alarm Threshold Sensor D | Internal sensor % of refrigerant to trip alarm D | % | Read | |
| AI | 10347 | Refrigerant LFL Concentration Sensor C | Actual refrigerant being measured by sensor C | % | Read | |
| AI | 10348 | Refrigerant LFL Concentration Sensor D | Actual refrigerant being measured by sensor D | % | Read | |
| AI | 10349 | Exhaust Fan 1 VFD Power | Current power being used by Exhaust Fan 1 | kW | Read | |
| AI | 10350 | Exhaust Fan 2 VFD Power | Current power being used by Exhaust Fan 2 | kW | Read | |
| AI | 10351 | Exhaust Fan 3 VFD Power | Current power being used by Exhaust Fan 3 | kW | Read | |
| AI | 10352 | Supply Fan 1 VFD Power | Current power being used by Supply Fan 1 | kW | Read | |
| AI | 10353 | Supply Fan 2 VFD Power | Current power being used by Supply Fan 2 | kW | Read | |
| AI | 10354 | Return Fan VFD Power | Current power being used by Return Fan 1 | kW | Read | |
| AI | 10355 | Return Air Enthalpy Active | The return air enthalpy value being utilized by the unit | BTU/lb | Read | |
| AI | 10356 | Return Plenum Static Pressure Setpoint (Target) | Lculated return plenum pressure tar | Inches of Water | Read | |
| AV | 10101 | Discharge Air Temperature Arbitrator | Actual discharge air temperature being used by the controller | °F | Write | |
| AV | 10103 | Outdoor Air Temperature Arbitrator | Actual outdoor air temperature being used by the controller | °F | Write | |
| AV | 10104 | Outdoor Air Humidity Arbitrator | Actual outdoor air humidity being used by the controller | % | Write | |
| AV | 10105 | Outdoor Air Flow Arbitrator | Actual outdoor air flow being used by the controller | CFM | Write | |
| AV | 10106 | Space Temperature Arbitrator | Actual space temperature being used by the controller | °F | Write | |
| AV | 10107 | Space Static Pressure Arbitrator | Space static pressure value from a unit mounted sensor | Inches of Water | Write | |
| AV | 10108 | Space CO2 Concentration Arbitrator | Actual space CO2 concentration being used by the controller | PPM | Write | |
| AV | 10109 | Space Humidity Arbitrator | Actual space relative humidity being used by the controller | % | Write | |
| AV | 10111 | Discharge Air Temperature BAS | Send the discharge air temperature sensor value | °F | Write | |
| AV | 10113 | Outdoor Air Temperature BAS | Send the outdoor air temperature sensor value | °F | Write | |
| AV | 10114 | Space Temperature BAS | Send the space temperature value | °F | Write | |
| AV | 10115 | Outdoor Air Flow BAS | Send the outdoor air flow value | CFM | Write | |
| AV | 10116 | Outdoor Air Humidity BAS | Send the outdoor air humidity sensor value | % | Write | |
| AV | 10118 | Space CO2 Concentration BAS | Send the space CO2 concentration value | PPM | Write | |
| AV | 10119 | Space Humidity BAS | Send the space relative humidity value | % | Write | |
| AVmin | 10121 | Discharge Air Cooling Setpoint BAS | Discharge air temperature cooling setpoint value | °F | Write | |
| AV | 10122 | Discharge Air Heating Setpoint BAS | Discharge air temperature heating setpoint value | °F | Write | |
| AV | 10123 | Unoccupied Cooling Setpoint | Define the cooling temperature setpoint used for control in unoccupied mode | °F | Write | |
| AV | 10124 | Unoccupied Heating Setpoint | Define the heating temperature setpoint used for control in unoccupied mode | °F | Write | |
| AV | 10125 | Outdoor Air Minimum Flow Setpoint BAS | Send the requested minimum outdoor air flow setpoint | CFM | Write | |
| AVmin | 10127 | Space Temperature Setpoint BAS | BAS-supplied space temperature setpoint value | °F | Write | |
| AV | 10128 | Space Static Pressure Setpoint BAS | Send the space static pressure value | Inches of Water | Write | |
| AV | 10130 | Occupied Offset | Define the difference between the occupied cooling and heating setpoints | Delta °F | Write | |
| AV | 10134 | Discharge Air Reheat Setpoint BAS | Discharge air temperature reheat setpoint value, for dehumidification control | °F | Write | |
| AV | 10135 | Space Dehumidification Setpoint BAS | Define the (occupied) space dehumidification setpoint | % | Write | |
| AV | 10136 | Supply Fan Speed Setpoint | BAS supplied supply fan speed setpoint value | % | Write | |
| AV | 10137 | Exhaust Fan Speed Setpoint | BAS supplied exhaust fan speed setpoint value | % | Write | |
| AV | 10139 | Cooling Capacity Enable | % | Write | ||
| AV | 10140 | Heat Primary Enable BAS | % | Write | ||
| AV | 10141 | Morning Warmup Setpoint BAS | Normally provided by the BMS, defines the space temperature below | °F | Write | |
| AV | 10142 | Occupied Standby Offset | Define the difference between the occupied standby cooling and heating setpoints | Delta °F | Write | |
| AVmin | 10143 | Duct Static Pressure Setpoint BAS | Duct static pressure setpoint value | Inches of Water | Write | |
| AV | 10144 | Economizer Minimum Position Setpoint BAS | Ecominizer minimum position setpoint | % | Write | |
| AV | 10147 | Cooling Setpoint High Limit | Occupied cooling setpoint high limit for space comfort control applications | °F | Write | |
| AV | 10148 | Cooling Setpoint Low Limit | Occupied cooling setpoint low limit for space comfort control applications | °F | Write | |
| AV | 10149 | Daytime Warmup Setpoint BAS | Defines the space temp below which daytime warmup will be enabled | °F | Write | |
| AV | 10150 | Economizer Outdoor Air Enable Setpoint BAS | °F | Write | ||
| AV | 10152 | Heating Setpoint High Limit | Occupied heating setpoint high limit for space comfort control applications | °F | Write | |
| AV | 10153 | Heating Setpoint Low Limit | Occupied heating setpoint low limit for space comfort control applications | °F | Write | |
| AV | 10156 | Space Dehumidification Unoccupied Setpoint BAS | Define the unoccupied space dehumidification setpoint | % | Write | |
| AV | 10159 | Occupied Cooling Setpoint BAS | Define the occupied cooling setpoint | °F | Write | |
| AV | 10160 | Occupied Heating Setpoint BAS | Define the occupied heating setpoint | °F | Write | |
| AV | 10161 | Occupied Standby Cooling Setpoint BAS | Define the occupied standby cooling setpoint | °F | Write | |
| AV | 10162 | Occupied Standby Heating Setpoint BAS | Active occupied standby heating setpoint being | °F | Write | |
| AV | 10163 | Demand Limit Setpoint | Demand limit the unit | % | Write | |
| AV | 10164 | Evaporator Leaving Air Temperature Setpoint | °F | Write | ||
| AV | 10165 | Pre Cool Setpoint | Normally provided by the BAS, defines the space temperature above | °F | Write | |
| AV | 10166 | Discharge Air Temperature Maximum Heat Limit | Discharge air temperature maximum heat limit, above | °F | Write | |
| AV | 10167 | Discharge Air Temperature Minimum Cool Limit | Discharge air temperature minimum cool limit, below | °F | Write | |
| AV | 10168 | Exhaust Enable Position Setpoint | Indicate the outdoor air damper position above | % | Write | |
| AV | 10169 | Occupied Bypass Time | Minutes | Write | ||
| AV | 10170 | Economizer Outdoor Air Enthalpy Enable Setpoint BAS | BTU/lb | Write | ||
| AV | 10175 | Space CO2 High Limit | Define the CO2 high limit, for ventilation purposes | PPM | Write | |
| AV | 10176 | Space CO2 Low Limit | Define the CO2 low limit | PPM | Write | |
| AV | 10177 | Supply Fan Speed Setpoint External Heat | Specifies the supply fan speed setpoint during external heat modes of operation | % | Write | |
| AV | 10178 | Discharge Air Temperature Maximum Cool Limit | Normally used by BAS to limit space temperature control calculated cooling setpoint | °F | Write | |
| AV | 10179 | Discharge Air Temperature Minimum Heat Limit | Normally used by BAS to limit space temperature control calculated heating setpoint | °F | Write | |
| AV | 10180 | Space Dew Point Setpoint BAS | °F | Write | ||
| AV | 10181 | Space Dew Point Unocc Setpoint BAS | °F | Write | ||
| AV | 10182 | Heating Capacity Setpoint External | Remote heating capacity request | % | Write | |
| AV | 10183 | Outdoor Air Damper Position Setpoint External | Remote outdoor air damper position request | % | Write | |
| AV | 10184 | Exhaust Fan Speed Setpoint External | Remote exhaust fan speed request | % | Write | |
| AV | 10185 | Return Fan Speed Setpoint External | Remote rturn fan speed request | % | Write | |
| AV | 10186 | Supply Fan Speed Setpoint External | Remote supply fan speed request | % | Write | |
| AV | 10187 | Cooling Capacity Setpoint External | Remote cooling capacity request | % | Write | |
| BI | 10001 | microSD | When a micro SD card is present | Read | 0 = MicroSD card is not present, 1 = MicroSD card is present | |
| BI | 10002 | USB Port 1 | When a USB device is present in port 1 | Read | 0 = USB device is not present, 1 = USB device is present | |
| BI | 10003 | USB Port 2 | When a USB device is present in port 2 | Read | 0 = USB device is not present, 1 = USB device is present | |
| BI | 10004 | USB Port 3 | When a USB device is present in port 3 | Read | 0 = USB device is not present, 1 = USB device is present | |
| BI | 10005 | USB Port 4 | When a USB device is present in port 4 | Read | 0 = USB device is not present, 1 = USB device is present | |
| BI | 10105 | FDD: Unit Economizing When It Should Not | FDD: Indicates when the unit is economizing but should not be | Read | 0 = Inactive, 1 = Active | |
| BI | 10106 | FDD: Unit Not Economizing When it Should Be | FDD: Indicates when the unit is not economizing but should be | Read | 0 = Inactive, 1 = Active | |
| BI | 10107 | FDD: Excessive Outdoor Air | FDD: Indicates an excessive outdoor air condition | Read | 0 = Inactive, 1 = Active | |
| BI | 10108 | FDD: Outdoor Air Damper Not Modulating | Read | 0 = Inactive, 1 = Active | ||
| BI | 10111 | Compressor 1A Status | Operating status of compressor 1A | Read | 0 = Off, 1 = Running | |
| BI | 10112 | Compressor 1B Status | Operating status of compressor 1B | Read | 0 = Off, 1 = Running | |
| BI | 10113 | Compressor 1C Status | Operating status of compressor 1C | Read | 0 = Off, 1 = Running | |
| BI | 10114 | Compressor 2A Status | Operating status of compressor 2A | Read | 0 = Off, 1 = Running | |
| BI | 10115 | Compressor 2B Status | Operating status of compressor 2B | Read | 0 = Off, 1 = Running | |
| BI | 10116 | Compressor 2C Status | Operating status of compressor 2C | Read | 0 = Off, 1 = Running | |
| BI | 10132 | FDD: Outdoor Air Temperature Sensor Failure | FDD: Indicates when the outdoor air temperature sensor has failed | Read | 0 = Inactive, 1 = Active | |
| BI | 10140 | Unit Running State | The unit is off or on | Read | 0 = Off, 1 = Running | |
| BI | 10143 | VAV Box Command | Read | 0 = Auto, 1 = Open | ||
| BI | 10144 | Alarm Relay Output Status | State of the alarm output of the controller | Read | 0 = De-energized, 1 =Energized | |
| BI | 10149 | Return Fan Output Status | State of the return fan | Read | 0 = Off, 1 = On | |
| BI | 10154 | Supply Fan Configuration Status | Supply fan configuration | Read | 0 = Cycling, 1 =Continuouos | |
| BI | 10155 | Rapid Restart Status | Active status of the Rapid Restart event | Read | 0 = Inactive, 1 = Active | |
| BI | 10161 | Morning Warmup Active | Active status of the Morning Warmup event | Read | 0 = Inactive, 1 = Active | |
| BI | 10162 | Daytime Warmup Active | Active status of the Daytime Warmup event | Read | 0 = Inactive, 1 = Active | |
| BI | 10164 | Coil Frost Protection Status Circuit 1 | Status of evaporator frost protection function for circuit 1 | Read | 0 = Inactive, 1 = Active | |
| BI | 10165 | Coil Frost Protection Status Circuit 2 | Status of evaporator frost protection function for circuit 2 | Read | 0 = Inactive, 1 = Active | |
| BI | 10166 | Energy Recovery Status | Status of the energy recovery device (Wheel) | Read | 0 = Inactive, 1 = Active | |
| BI | 10167 | Energy Recovery Preheat Status | Status of the energy recovery preheat | Read | 0 = Inactive, 1 = Active | |
| BI | 10168 | Energy Recovery Frost Avoidance Status | Status of the Recovery Frost Avoidance function | Read | 0 = Inactive, 1 = Active | |
| BI | 10170 | Condensate Overflow Input | Status of the condensate overflow input | Read | 0 = Normal, 1 = Overflow | |
| BI | 10172 | Occupancy Input | Status of the occupancy input (see below) | Read | 0 = Occupied, 1 =Unoccupied | |
| BI | 10173 | Precool Active | When the pre-cool mode is active | Read | 0 = Inactive, 1 = Active | |
| BI | 10174 | Supply Air Tempering Status | Or not the supply air tempering feature is enabled | Read | 0 = Disable, 1 = Enable | |
| BI | 10175 | Timed Override Timer Is Active | Or not the timed override timer is active | Read | 0 = Inactive, 1 = Active | |
| BImin | 10176 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10201 | Changeover Input | Status of the (heat/cool) changeover input | Read | 0 = Heating, 1 = Cooling | |
| BI | 10202 | Condenser Fan Circuit 1 Relay 1 Status | Status of condenser fan circuit 1, relay 1 | Read | 0 = Off, 1 = On | |
| BI | 10203 | Condenser Fan Circuit 1 Relay 2 Status | Status of condenser fan circuit 1, relay 2 | Read | 0 = Off, 1 = On | |
| BI | 10204 | Condenser Fan Circuit 1 Relay 3 Status | Status of condenser fan circuit 1, relay 3 | Read | 0 = Off, 1 = On | |
| BI | 10205 | Condenser Fan Circuit 1 Relay 4 Status | Status of condenser fan circuit 1, relay 4 | Read | 0 = Off, 1 = On | |
| BI | 10206 | Condenser Fan Circuit 2 Relay 1 Status | Status of condenser fan circuit 2, relay 1 | Read | 0 = Off, 1 = On | |
| BI | 10207 | Condenser Fan Circuit 2 Relay 2 Status | Status of condenser fan circuit 2, relay 2 | Read | 0 = Off, 1 = On | |
| BI | 10208 | Condenser Fan Circuit 2 Relay 3 Status | Status of condenser fan circuit 2, relay 3 | Read | 0 = Off, 1 = On | |
| BI | 10209 | Condenser Fan Circuit 2 Relay 4 Status | Status of condenser fan circuit 2, relay 4 | Read | 0 = Off, 1 = On | |
| BI | 10210 | Emergency Stop | Status of the emergency stop function of the unit | Read | 0 = Auto, 1 =Emergency Stop - Manual Reset Required | |
| BI | 10211 | Equipment Stop Status | Status of the externally-wired auto/stop input | Read | 0 = Stop, 1 = Auto | |
| BI | 10212 | Supply Fan Bypass Status | Status of the supply fan bypass from the variable frequency drive (VFD) | Read | 0 = Inactive, 1 = Active | |
| BI | 10213 | Ventilation Mode A Local | When the controller is actively in the Ventilation Override Mode A | Read | 0 = Inactive, 1 = Active | |
| BI | 10214 | Ventilation Mode B Local | When the controller is actively in the Ventilation Override Mode B | Read | 0 = Inactive, 1 = Active | |
| BI | 10215 | Ventilation Mode C Local | When the controller is actively in the Ventilation Override Mode C | Read | 0 = Inactive, 1 = Active | |
| BI | 10216 | Ventilation Mode D Local | When the controller is actively in the Ventilation Override Mode D | Read | 0 = Inactive, 1 = Active | |
| BI | 10217 | Ventilation Mode E Local | When the controller is actively in the Ventilation Override Mode E | Read | 0 = Inactive, 1 = Active | |
| BI | 10218 | Diagnostic: Manual Reset Required | When a diagnostic exists that requires manual reset | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10219 | Economizer Airside Status | Status of airside economizing | Read | 0 = Inactive, 1 = Active | |
| BI | 10221 | Exhaust Fan Output Status | Status of the exhaust fan output on the controller | Read | 0 = Off, 1 = On | |
| BI | 10222 | Heat Output 1 Status | Commanded state of heating output 1 | Read | 0 = Off, 1 = On | |
| BI | 10223 | Heat Output 2 Status | Commanded state of heating output 2 | Read | 0 = Off, 1 = On | |
| BI | 10224 | Heat Output 3 Status | Commanded state of heating output 3 | Read | 0 = Off, 1 = On | |
| BI | 10225 | Heat Output 4 Status | Commanded state of heating output 4 | Read | 0 = Off, 1 = On | |
| BImin | 10226 | Supply Fan Output Status | Status of the supply fan output of the controller | Read | 0 = Off, 1 = On | |
| BI | 10603 | Diagnostic: Discharge Air High Temperature Detected | When a discharge air high temperature diagnostic is present | Read | 0 = No, 1 = Yes | |
| BI | 10605 | Diagnostic: Loss of Charge Lockout Ckt1 | When a loss of charge lockout diagnostic exists for DX circuit 1 | Read | 0 = No, 1 = Yes | |
| BI | 10606 | Diagnostic: Loss of Charge Lockout Ckt2 | When a loss of charge lockout diagnostic exists for DX circuit 2 | Read | 0 = No, 1 = Yes | |
| BI | 10608 | Diagnostic: Morning Warmup Mode Exceeded 120 Minutes | When the morning warmup mode has exceeded 120 consectutive minutes | Read | 0 = No, 1 = Yes | |
| BI | 10609 | Diagnostic: Pre Cool Mode Exceeded 120 Minutes | When the pre-cool mode has exceeded 120 consective minutes | Read | 0 = No, 1 = Yes | |
| BI | 10611 | Diagnostic: Return Air High Temperature Detected | When a return air high temperature diagnostic is present | Read | 0 = No, 1 = Yes | |
| BI | 10614 | Diagnostic: Condensate Overflow Lockout | When a condensate overflow lockout diagnostic is present | Read | 0 = No, 1 = Yes | |
| BI | 10615 | Diagnostic: High Condensate Level Detected | When a high condensate level is detected | Read | 0 = No, 1 = Yes | |
| BI | 10616 | Supply Fan Speed Control Enabled | Supply fan speed is controlled via Supply Fan Speed Setpoint | Read | 0 = Disabled, 1 = Enabled | |
| BI | 10617 | Supply Fan Speed Limited | Read | 0 = Not Limited, 1 = Limited | ||
| BI | 10618 | Exhaust Fan Speed Control Enabled | Exhaust fan speed is controlled via Exhaust Fan Speed Setpoint | Read | 0 = Disabled, 1 = Enabled | |
| BI | 10619 | Diagnostic Shutdown Present | Unit is shut down due to diagnostics | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10620 | Diagnostic: Local Manual Reset Required | Diagnostic Reset required [Local only] | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10622 | Exhaust Fan Bypass Status | Status of the exhaust fan bypass from the variable frequency drive (VFD) | Read | 0 = Inactive, 1 = Active | |
| BI | 10623 | Return Fan Bypass Status | Status of the return fan bypass from the variable frequency drive (VFD) | Read | 0 = Inactive, 1 = Active | |
| BI | 10624 | Heating Capacity Control Enabled | Status of heating capacity enabled | Read | 0 = Disabled, 1 = Enabled | |
| BI | 10625 | Outdoor Air Damper Control Enabled | Status of ourdoor air damper enabled | Read | 0 = Disabled, 1 = Enabled | |
| BI | 10626 | Return Fan Speed Control Enabled | Status of return fan speed enabled | Read | 0 = Disabled, 1 = Enabled | |
| BI | 10627 | Cooling Capacity Control Enabled | Status of cooling capacity enabled | Read | 0 = Disabled, 1 = Enabled | |
| BI | 10628 | Final Filter Differential Press Setpoint Exceeded | When the Final Filter Differential Pressure Setpoint has been exceeded | Read | 0 = Inactive, 1 = Active | |
| BI | 10629 | Pre Evap Filter Differential Pressure Setpoint Exceeded | When the Pre Evaporator Filter Differential Pressure Setpoint has been exceeded | Read | 0 = Inactive, 1 = Active | |
| BI | 10630 | Energy Wheel Filter Differential Pressure Setpoint Exceeded | When the Energy Wheel Filter Differential Pressure Setpoint has been exceeded | Read | 0 = Inactive, 1 = Active | |
| BI | 10631 | Refrigerant Mitigation Active | Unit is in active mitigation mode | Read | 0 = Inactive, 1 = Active | |
| BV | 10103 | Heat Lockout Command | Command the unit to prevent heating operation (Trane external heat option) | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10104 | Supply Fan Configuration Command | Command the unit supply fan configuration as either cycling or continuous | Write | 0 = Cycling, 1 = Continuous | |
| BV | 10106 | Dehumidification Enable Command | Disable unit dehumidification | Write | 0 = Disable, 1 = Auto | |
| BV | 10110 | Reset Diagnostic | Initiate a request to reset any remote controller diagnostics | Write | 0 = Normal, 1 = Reset | |
| BV | 10111 | Daytime Warmup Enable Command | Enable daytime warmup | Write | 0 = Disable, 1 = Enable | |
| BV | 10112 | Morning Warmup Enable Command | Enable morning warmup | Write | 0 = Disable, 1 = Enable | |
| BV | 10113 | Occupancy Input BAS | Provide the requested occupancy state to the unit | Write | 0 = Occupied, 1 =Unoccupied | |
| BV | 10115 | Cooling Lockout BAS | Normally used by the BAS as a command to | Write | 0 = Normal, 1 = Locked Out | |
| BV | 10116 | Demand Limit Request BAS | Write | 0 = Not Limited, 1 = Limited | ||
| BV | 10117 | Energy Consumption Reset | Reset the energy consumption accumulated total | Write | 0 = Accumulating, 1 = Reset | |
| BV | 10118 | Pre Cool Enable Command | Enable pre- cool | Write | 0 = Disabled, 1 = Enabled | |
| BV | 10119 | Supply Air Tempering Enable | Enable the supply (discharge) air tempering feature of the unit | Write | 0 = Disable, 1 = Enable | |
| BV | 10120 | Rapid Restart Enable | Enables/Disables rapid restart operation | Write | 0 = Disable, 1 = Enable | |
| BV | 10121 | Rapid Restart Economizer Enable | Enables/Disables economizer evaluation during rapid restart operation | Write | 0 = Disable, 1 = Enable | |
| BV | 10122 | Supply Fan Speed Setpoint Enable | Enables Supply Fan Speed Setpoint control | Write | 0 = Disable, 1 = Enable | |
| BV | 10123 | Exhaust Fan Speed Setpoint Enable | Enables Exhaust Fan Speed Setpoint control | Write | 0 = Disable, 1 = Enable | |
| BV | 10124 | Supply Fan Compensation | Write | 0 = Disable, 1 = Enable | ||
| BV | 10125 | Energy Consumption Reset Meter 2 | Reset the energy consumption accumulated total for second power meter | Write | 0 = Accumulating, 1 = Reset | |
| BV | 10126 | Heating Capacity Setpoint Enable External | Enables Heating Capacity Setpoint control | Write | 0 = Disable, 1 = Enable | |
| BV | 10127 | Outdoor Air Damper Position Setpoint Enable External | Enables Outdoor Air Damper Position Setpoint control | Write | 0 = Disable, 1 = Enable | |
| BV | 10128 | Exhaust Fan Speed Setpoint Enable External | Enables Exhust Fan Speed Setpoint control | Write | 0 = Disable, 1 = Enable | |
| BV | 10129 | Return Fan Speed Setpoint Enable External | Enables Return Fan Speed Setpoint control | Write | 0 = Disable, 1 = Enable | |
| BV | 10130 | Supply Fan Speed Setpoint Enable External | Enables Supply Fan Speed Setpoint control | Write | 0 = Disable, 1 = Enable | |
| BV | 10131 | Cooling Capacity Setpoint Enable External | Enables Cooling Capacity Setpoint control | Write | 0 = Disable, 1 = Enable | |
| MI | 10101 | Heat Cool Mode Status | Current heat cool mode of the controller | Read | 1 = Auto, 2 = Heat, 3 = Morning Warm- up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate | |
| MI | 10102 | Ventilation Override Status | Which of the 5 preprogrammed ventilation override modes is operational, when applicable | Read | 1 = Inactive, 2 = Mode A Active, 3 = Mode B Active, 4 = Mode C Active, 5 = Mode D Active, 6 = Mode E Active | |
| MImin | 10103 | Occupancy Status | Active occupancy mode of the controller | Read | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MI | 10105 | Cooling Reset Type Status | Type of cooling reset used by the controller | Read | 1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air | |
| MI | 10106 | Heating Reset Type Status | Type of heating reset used, when applicable | Read | 1 = None, 2 = Outdoor Air, 3 = Zone | |
| MI | 10107 | Trane Unit Type | Equipment type according to the manufacturer's classification | Read | 6 = Rooftop | |
| MI | 10108 | Economizer Type | General description of the type of economizer system | Read | 1 = None, 3 = Modulation Economizer, 8 = Airside Economizer and TRAQ Damper/ Sensor | |
| MI | 10109 | Condenser Type | General description of the equipment condenser system | Read | 2 = Air Cooled Condenser | |
| MI | 10117 | Refrigerant Type | Type of refrigerant used in the equipment | Read | 7 = R-410A, 17 = R-454B | |
| MI | 10118 | System Mode Switch Local | Status of the system mode switch connected to the controller | Read | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat | |
| MImin | 10119 | Arbitration Method | Read | 1 = Full (Auto) Source, 2 = Local Source, 3 = Default Source | ||
| MI | 10120 | Timed Override Request Active | Status of the timed override request (see above) | Read | 1 = Idle, 2 = On, 3 = Cancel | |
| MI | 10121 | Electrical Service Type | Electrical service type used for the unit | Read | 1 = A+N, 2 = A+B, 3 = A+B+N, 4 = A+B+C, 5 = A+B+C+N | |
| MI | 10132 | Economizer Decision Method | Method of enabling airside economizing | Read | 1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy | |
| MI | 10144 | Economizer System Status | Status of enabling economizing | Read | 1 = Disabled, 2 = Enabled, 3 = Not Present | |
| MI | 10145 | Model Information [GEN2] | Type of equipment | Read | 27 = IPAK | |
| MI | 10146 | Electrical Service Type Meter 2 | Electrical service type used for the second power connection on the unit | Read | 1 = A+N, 2 = A+B, 3 = A+B+N, 4 = A+B+C, 5 = A+B+C+N | |
| MI | 10147 | Emergency Override BAS - Active | Status of emergency override | Read | 1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire | |
| MV | 10102 | Emergency Override BAS | Command the unit into an emergency mode of operation | Write | 1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire | |
| MV | 10103 | Economizer Airside Enable BAS | Enable airside economizing | Write | 1 = Disabled, 2 = Enabled, 3 = Auto | |
| MVmin | 10104 | Heat Cool Mode Request | Command the unit into a heat/cool mode, including additional possible control modes | Write | 1 = Auto, 2 = Heat, 3 = Morning Warm- up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate | |
| MVmin | 10106 | Occupancy Request | Command the unit into an occupancy mode | Write | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MV | 10110 | Timed Override Request | Request a temporary timed override during unoccupied | Write | 1 = Idle, 2 = On, 3 = Cancel | |
| MV | 10111 | Dehumidification Method | Select how the unit determines when to dehumidify | Write | 1 = Relative Humidity, 2 = Dew Point |
No points match these filters.
Object ID lookup: Trane Symbio 800 IntelliPak point IDs by name
AI10101Cooling Capacity StatusAI10102Heating Capacity Primary StatusAI10104Outdoor Air Relative Humidity LocalAI10105Outdoor Air Flow LocalAI10107Space Static Pressure LocalAI10110Return Air Humidity LocalAI10111Outdoor Air Damper PositionAI10112Exhaust Damper PositionAI10113Return Plenum Static PressureAI10114Outdoor Air Minimum Flow Setpoint ActiveAI10116Space Humidity ActiveAI10117Outdoor Air Dew PointAI10118Outdoor Air Temperature ActiveAI10120Outdoor Air Humidity ActiveAI10121Discharge Air Cooling Setpoint ActiveAI10122Discharge Air Heating Setpoint ActiveAI10123Duct Static Pressure Setpoint ActiveAI10124Discharge Air TemperatureAI10125Mixed Air Temperature LocalAI10126Return Air TemperatureAI10128Space Static Pressure Setpoint ActiveAI10135Space Dehumidification Setpoint ActiveAI10152Exhaust Fan Speed StatusAI10153Return Fan Speed StatusAI10154Economizer Minimum Position Setpoint ActiveAI10155Duct Static Pressure LocalAI10156Outdoor Air Temperature LocalAI10157Dehumidification Control StatusAI10161Condenser CapacityAI10166Energy Recovery Leaving Exhaust Temperatue StatusAI10167Energy Recovery Outdoor Air Bypass Damper StatusAI10168Energy Recovery Exhaust Air Bypass Damper PositionAI10172Reheat Capacity StatusAI10173Supply Fan Speed StatusAI10181Discharge Air Temperature LocalAI10182Duct Static Pressure ActiveAI10183Outdoor Air Enthalpy ActiveAI10185Outdoor Air Flow ActiveAI10186Space Temperature ActiveAI10187Space Static Pressure ActiveAI10188Space CO2 Concentration ActiveAI10190Space Temperature Cooling Setpoint InputAI10191Space Temperature Heating Setpoint InputAI10197Heat TypeAI10198Cabinet StyleAI10199Cool TypeAI10200Preheat TypeAI10201Reheat TypeAI10202Supply Fan TypeAI10203Exhaust Or Return Fan TypeAI10204Exhaust Fan Speed Setpoint ActiveAI10206Number of CircuitsAI10207Number of Compressors Circuit 1AI10208Number of Compressors Circuit 2AI10210Return Isolation Damper InputAI10213Space CO2 Concentration InputAI10214Space Dehumidification Unoccupied Setpoint ActiveAI10215Space Humidity InputAI10216Space Temp Cooling Setpoint StatusAI10217Space Temp Heating Setpoint StatusAI10218Space Temperature InputAI10221Space Temperature Setpoint ActiveAI10222Supply Isolation Damper InputAI10224Average CurrentAI10227Run Time - Compressor 1AAI10228Starts - Compressor 1AAI10229Run Time - Compressor 1BAI10230Starts - Compressor 1BAI10231Run Time - Compressor 1CAI10232Starts - Compressor 1CAI10233Run Time - Compressor 2AAI10234Starts - Compressor 2AAI10235Run Time - Compressor 2BAI10236Starts - Compressor 2BAI10237Run Time - Compressor 2CAI10238Starts - Compressor 2CAI10239Current L1AI10240Current L2AI10241Current L3AI10242Current NeutralAI10243Discharge Air Cooling Setpoint StatusAI10244Discharge Air Heating Setpoint StatusAI10246Discharge Gauge Pressure Circuit 1AI10247Discharge Gauge Pressure Circuit 2AI10249Energy Consumption LifetimeAI10250Evaporator Leaving Air TemperatureAI10251Evaporator Leaving Air Temperature Evap AAI10252Evaporator Leaving Air Temperature Evap BAI10253Evaporator Leaving Air Temperature Setpoint ActiveAI10254Final Filter Differential Pressure LocalAI10255Line FrequencyAI10256Mixed Air Temperature Evap AAI10257Mixed Air Temperature Evap BAI10258Power FactorAI10259Prefilter Differential Pressure LocalAI10262Suction Gauge Pressure Circuit 1AI10263Suction Gauge Pressure Circuit 2AI10268Total Apparent EnergyAI10269Energy ConsumptionAI10270Total Reactive EnergyAI10271Total Real PowerAI10272Total Apparent PowerAI10273Total Reactive PowerAI10274Unit Source IDAI10275Voltage L1-L2AI10276Voltage L1-L3AI10277Voltage L1-NAI10278Voltage L2-L3AI10279Voltage L2-NAI10280Voltage L3-NAI10281Discharge Air Temperature Setpoint ActiveAI10282Air Flow Percentage Circuit 1AI10283Air Flow Percentage Circuit 2AI10284Discharge Saturated Refrigeration Temperature Circuit 1AI10285Discharge Saturated Refrigeration Temperature Circuit 2AI10286Suction Saturated Refrigerant Temperature Circuit 1AI10287Suction Saturated Refrigerant Temperature Circuit 2AI10288Suction Temperature Evap 1AAI10289Suction Temperature Evap 1BAI10290Suction Temperature Evap 2AAI10291Suction Temperature Evap 2BAI10292Occupied Cooling SetpointAI10293Occupied Heating SetpointAI10294Occupied Standby Cooling SetpointAI10295Occupied Standby Heating SetpointAI10296Supply Fan Speed Setpoint ActiveAI10297Discharge Air Temperature Maximum Cool Limit ActiveAI10298Discharge Air Temperature Minimum Heat Limit ActiveAI10299Discharge Air Temperature Minimum Cool Limit ActiveAI10300Discharge Air Temperature Maximum Heat Limit ActiveAI10303Energy Recovery Wheel Filter Differential PressureAI10304Average Current Meter 2AI10305Current L1 Meter 2AI10306Current L2 Meter 2AI10307Current L3 Meter 2AI10308Current Neutral Meter 2AI10309Energy Consumption Meter 2AI10310Energy Consumption Lifetime Meter 2AI10311Line Frequency Meter 2AI10312Power Factor Meter 2AI10313Total Apparent Energy Meter 2AI10314Total Apparent Power Meter 2AI10315Total Reactive Energy Meter 2AI10316Total Reactive Power Meter 2AI10317Total Real Power Meter 2AI10318Voltage L1-L2 Meter 2AI10319Voltage L1-L3 Meter 2AI10320Voltage L1-N Meter 2AI10321Voltage L2-L3 Meter 2AI10322Voltage L2-N Meter 2AI10323Voltage L3-N Meter 2AI10324Run Time - Compressor 1A (Hours)AI10325Run Time - Compressor 1B (Hours)AI10326Run Time - Compressor 1C (Hours)AI10327Run Time - Compressor 2A (Hours)AI10328Run Time - Compressor 2B (Hours)AI10329Run Time - Compressor 2C (Hours)AI10330Discharge Pressure Circuit 1AI10331Discharge Pressure Circuit 2AI10332Suction Pressure Circuit 1AI10333Suction Pressure Circuit 2AI10334Space Dew PointAI10335Space Dew Point Setpoint ActiveAI10336Space Dew Point Unocc Setpoint ActiveAI10337Heating Capacity Setpoint ActiveAI10338Outdoor Air Damper Position Setpoint ActiveAI10339Return Fan Speed Setpoint ActiveAI10340Cooling Capacity Setpoint ActiveAI10341Rfgt LFL Conc Alarm Threshold Sensor AAI10342Rfgt LFL Conc Alarm Threshold Sensor BAI10343Refrigerant LFL Concentration Sensor AAI10344Refrigerant LFL Concentration Sensor BAI10345Rfgt LFL Conc Alarm Threshold Sensor CAI10346Rfgt LFL Conc Alarm Threshold Sensor DAI10347Refrigerant LFL Concentration Sensor CAI10348Refrigerant LFL Concentration Sensor DAI10349Exhaust Fan 1 VFD PowerAI10350Exhaust Fan 2 VFD PowerAI10351Exhaust Fan 3 VFD PowerAI10352Supply Fan 1 VFD PowerAI10353Supply Fan 2 VFD PowerAI10354Return Fan VFD PowerAI10355Return Air Enthalpy ActiveAI10356Return Plenum Static Pressure Setpoint (Target)AV10101Discharge Air Temperature ArbitratorAV10103Outdoor Air Temperature ArbitratorAV10104Outdoor Air Humidity ArbitratorAV10105Outdoor Air Flow ArbitratorAV10106Space Temperature ArbitratorAV10107Space Static Pressure ArbitratorAV10108Space CO2 Concentration ArbitratorAV10109Space Humidity ArbitratorAV10111Discharge Air Temperature BASAV10113Outdoor Air Temperature BASAV10114Space Temperature BASAV10115Outdoor Air Flow BASAV10116Outdoor Air Humidity BASAV10118Space CO2 Concentration BASAV10119Space Humidity BASAV10121Discharge Air Cooling Setpoint BASAV10122Discharge Air Heating Setpoint BASAV10123Unoccupied Cooling SetpointAV10124Unoccupied Heating SetpointAV10125Outdoor Air Minimum Flow Setpoint BASAV10127Space Temperature Setpoint BASAV10128Space Static Pressure Setpoint BASAV10130Occupied OffsetAV10134Discharge Air Reheat Setpoint BASAV10135Space Dehumidification Setpoint BASAV10136Supply Fan Speed SetpointAV10137Exhaust Fan Speed SetpointAV10139Cooling Capacity EnableAV10140Heat Primary Enable BASAV10141Morning Warmup Setpoint BASAV10142Occupied Standby OffsetAV10143Duct Static Pressure Setpoint BASAV10144Economizer Minimum Position Setpoint BASAV10147Cooling Setpoint High LimitAV10148Cooling Setpoint Low LimitAV10149Daytime Warmup Setpoint BASAV10150Economizer Outdoor Air Enable Setpoint BASAV10152Heating Setpoint High LimitAV10153Heating Setpoint Low LimitAV10156Space Dehumidification Unoccupied Setpoint BASAV10159Occupied Cooling Setpoint BASAV10160Occupied Heating Setpoint BASAV10161Occupied Standby Cooling Setpoint BASAV10162Occupied Standby Heating Setpoint BASAV10163Demand Limit SetpointAV10164Evaporator Leaving Air Temperature SetpointAV10165Pre Cool SetpointAV10166Discharge Air Temperature Maximum Heat LimitAV10167Discharge Air Temperature Minimum Cool LimitAV10168Exhaust Enable Position SetpointAV10169Occupied Bypass TimeAV10170Economizer Outdoor Air Enthalpy Enable Setpoint BASAV10175Space CO2 High LimitAV10176Space CO2 Low LimitAV10177Supply Fan Speed Setpoint External HeatAV10178Discharge Air Temperature Maximum Cool LimitAV10179Discharge Air Temperature Minimum Heat LimitAV10180Space Dew Point Setpoint BASAV10181Space Dew Point Unocc Setpoint BASAV10182Heating Capacity Setpoint ExternalAV10183Outdoor Air Damper Position Setpoint ExternalAV10184Exhaust Fan Speed Setpoint ExternalAV10185Return Fan Speed Setpoint ExternalAV10186Supply Fan Speed Setpoint ExternalAV10187Cooling Capacity Setpoint ExternalBI10001microSDBI10002USB Port 1BI10003USB Port 2BI10004USB Port 3BI10005USB Port 4BI10105FDD: Unit Economizing When It Should NotBI10106FDD: Unit Not Economizing When it Should BeBI10107FDD: Excessive Outdoor AirBI10108FDD: Outdoor Air Damper Not ModulatingBI10111Compressor 1A StatusBI10112Compressor 1B StatusBI10113Compressor 1C StatusBI10114Compressor 2A StatusBI10115Compressor 2B StatusBI10116Compressor 2C StatusBI10132FDD: Outdoor Air Temperature Sensor FailureBI10140Unit Running StateBI10143VAV Box CommandBI10144Alarm Relay Output StatusBI10149Return Fan Output StatusBI10154Supply Fan Configuration StatusBI10155Rapid Restart StatusBI10161Morning Warmup ActiveBI10162Daytime Warmup ActiveBI10164Coil Frost Protection Status Circuit 1BI10165Coil Frost Protection Status Circuit 2BI10166Energy Recovery StatusBI10167Energy Recovery Preheat StatusBI10168Energy Recovery Frost Avoidance StatusBI10170Condensate Overflow InputBI10172Occupancy InputBI10173Precool ActiveBI10174Supply Air Tempering StatusBI10175Timed Override Timer Is ActiveBI10176Diagnostic PresentBI10201Changeover InputBI10202Condenser Fan Circuit 1 Relay 1 StatusBI10203Condenser Fan Circuit 1 Relay 2 StatusBI10204Condenser Fan Circuit 1 Relay 3 StatusBI10205Condenser Fan Circuit 1 Relay 4 StatusBI10206Condenser Fan Circuit 2 Relay 1 StatusBI10207Condenser Fan Circuit 2 Relay 2 StatusBI10208Condenser Fan Circuit 2 Relay 3 StatusBI10209Condenser Fan Circuit 2 Relay 4 StatusBI10210Emergency StopBI10211Equipment Stop StatusBI10212Supply Fan Bypass StatusBI10213Ventilation Mode A LocalBI10214Ventilation Mode B LocalBI10215Ventilation Mode C LocalBI10216Ventilation Mode D LocalBI10217Ventilation Mode E LocalBI10218Diagnostic: Manual Reset RequiredBI10219Economizer Airside StatusBI10221Exhaust Fan Output StatusBI10222Heat Output 1 StatusBI10223Heat Output 2 StatusBI10224Heat Output 3 StatusBI10225Heat Output 4 StatusBI10226Supply Fan Output StatusBI10603Diagnostic: Discharge Air High Temperature DetectedBI10605Diagnostic: Loss of Charge Lockout Ckt1BI10606Diagnostic: Loss of Charge Lockout Ckt2BI10608Diagnostic: Morning Warmup Mode Exceeded 120 MinutesBI10609Diagnostic: Pre Cool Mode Exceeded 120 MinutesBI10611Diagnostic: Return Air High Temperature DetectedBI10614Diagnostic: Condensate Overflow LockoutBI10615Diagnostic: High Condensate Level DetectedBI10616Supply Fan Speed Control EnabledBI10617Supply Fan Speed LimitedBI10618Exhaust Fan Speed Control EnabledBI10619Diagnostic Shutdown PresentBI10620Diagnostic: Local Manual Reset RequiredBI10622Exhaust Fan Bypass StatusBI10623Return Fan Bypass StatusBI10624Heating Capacity Control EnabledBI10625Outdoor Air Damper Control EnabledBI10626Return Fan Speed Control EnabledBI10627Cooling Capacity Control EnabledBI10628Final Filter Differential Press Setpoint ExceededBI10629Pre Evap Filter Differential Pressure Setpoint ExceededBI10630Energy Wheel Filter Differential Pressure Setpoint ExceededBI10631Refrigerant Mitigation ActiveBV10103Heat Lockout CommandBV10104Supply Fan Configuration CommandBV10106Dehumidification Enable CommandBV10110Reset DiagnosticBV10111Daytime Warmup Enable CommandBV10112Morning Warmup Enable CommandBV10113Occupancy Input BASBV10115Cooling Lockout BASBV10116Demand Limit Request BASBV10117Energy Consumption ResetBV10118Pre Cool Enable CommandBV10119Supply Air Tempering EnableBV10120Rapid Restart EnableBV10121Rapid Restart Economizer EnableBV10122Supply Fan Speed Setpoint EnableBV10123Exhaust Fan Speed Setpoint EnableBV10124Supply Fan CompensationBV10125Energy Consumption Reset Meter 2BV10126Heating Capacity Setpoint Enable ExternalBV10127Outdoor Air Damper Position Setpoint Enable ExternalBV10128Exhaust Fan Speed Setpoint Enable ExternalBV10129Return Fan Speed Setpoint Enable ExternalBV10130Supply Fan Speed Setpoint Enable ExternalBV10131Cooling Capacity Setpoint Enable ExternalMI10101Heat Cool Mode StatusMI10102Ventilation Override StatusMI10103Occupancy StatusMI10105Cooling Reset Type StatusMI10106Heating Reset Type StatusMI10107Trane Unit TypeMI10108Economizer TypeMI10109Condenser TypeMI10117Refrigerant TypeMI10118System Mode Switch LocalMI10119Arbitration MethodMI10120Timed Override Request ActiveMI10121Electrical Service TypeMI10132Economizer Decision MethodMI10144Economizer System StatusMI10145Model Information [GEN2]MI10146Electrical Service Type Meter 2MI10147Emergency Override BAS - ActiveMV10102Emergency Override BASMV10103Economizer Airside Enable BASMV10104Heat Cool Mode RequestMV10106Occupancy RequestMV10110Timed Override RequestMV10111Dehumidification Method
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- Name suffixes carry meaning: Status/Local/Active/Input are read-only, BAS/Command/Request/Setpoint value objects are the ones a BAS writes, and Arbitrator objects show which source is winning.
- BI-11000 to BI-11999 are reserved for user-created diagnostic points made in Tracer TU; they are not listed.
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 IntelliPak and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 IntelliPak
How many BACnet points does the Trane Symbio 800 IntelliPak have?
This list has 380 BACnet objects: 184 analog inputs, 65 analog values, 83 binary inputs, 24 binary values, 18 multi-state inputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 IntelliPak BACnet points are writable?
95 of the 380 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Trane Symbio 800 IntelliPak BACnet documentation?
The source is Symbio 800 Integration Points List BACnet/Modbus - IntelliPak (BAS-PTS003C-EN), revision 12/17/2025, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS003C-EN_12172025.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 IntelliPak?
Start with MV 10106 Occupancy Request (Occupancy command from the BMS schedule); MV 10104 Heat Cool Mode Request (Mode command from the BMS); AV 10127 Space Temperature Setpoint BAS (Space setpoint from the BMS); AV 10121 Discharge Air Cooling Setpoint BAS (Supply air cooling setpoint from the BMS); AV 10143 Duct Static Pressure Setpoint BAS (Duct static setpoint on VAV units); MI 10119 Arbitration Method (Must read Full (Auto) for BAS values to be used); MI 10103 Occupancy Status (Confirms the occupancy in effect); BI 10226 Supply Fan Output Status (Supply fan running (1 = on)); AI 10124 Discharge Air Temperature (Supply air temperature in use (BAS or local sensor)); BI 10176 Diagnostic Present (Summary alarm).
How do I enable BMS control of the Trane Symbio 800 IntelliPak?
The integration guide describes an arbitration method: with 'full/auto' the BMS value is used ahead of local or default values, and with 'local' BMS values are ignored. MI 10119 Arbitration Method (read-only) shows which is active; the documents don't name a BACnet point to change it. BI 10211 Equipment Stop Status reports stop/auto; no BAS start/stop command is listed.
Does the Trane Symbio 800 IntelliPak need a BACnet heartbeat or have a communication timeout?
The points list gives a 900 s heartbeat for the sensor BAS values (AV 10111, 10113-10116, 10118, 10119) and the External setpoints (AV 10183-10187). The Symbio 800 integration guide doesn't describe what happens when it expires.
Can the BMS supply sensor values to the Trane Symbio 800 IntelliPak?
Write BMS values to the '... BAS' AVs (AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS, AV 10119 Space Humidity BAS, AV 10118 Space CO2 Concentration BAS, AV 10111 Discharge Air Temperature BAS). The '... Arbitrator' AVs show all sources in their priority array; the guide notes the default for sensor arbitrators is invalid, so the value must come from the BMS or a local sensor. Direct capacity/fan/damper control uses the 'Setpoint External' AVs together with their 'Setpoint Enable External' BVs (e.g. AV 10187 with BV 10131).
How do I check these points on the real Symbio 800 IntelliPak?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet/Modbus - IntelliPak · BAS-PTS003C-EN · rev. 12/17/2025. Object names, instances and units are reproduced as published; descriptions are our own.