- Home
- BACnet points lists
- Trane
- Symbio 800 CenTraVac (Simplex)
Centrifugal chiller controller · BACnet points list
Trane Symbio 800 CenTraVac (Simplex) BACnet points list
Updated 28 October 2026
Simplex CenTraVac chillers controlled by a Symbio 800 publish their operating data as AI/BI/MI objects, plus a short list of AV/BV/MV objects for setpoints and commands (chilled water setpoint, demand limit, auto/stop, mode). Most of the list is diagnostic binary inputs, one per alarm condition. Many points depend on options such as base loading, heat recovery or a unit-mounted drive.
This page lists 546 BACnet objects for the Trane Symbio 800 CenTraVac (Simplex) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 CenTraVac (Simplex)
- Equipment
- Centrifugal chiller controller
- Equipment type
- Chillers
- BACnet objects
- 546 (15 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 CenTraVac (Simplex)
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10104 | Chiller Auto Stop Command BAS | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10113 | Chiller Running State | Chiller on/off status | Read |
| BI 10105 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10107 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10158 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10118 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10128 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10104 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10105 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
Trane Symbio 800 CenTraVac (Simplex) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Chilled Water Setpoint | Temperature | Read | ||
| AI | 10101 | Chilled Water Setpoint Status | Temperature | Read | ||
| AI | 10102 | Active Base Loading Setpoint | Percent | Read | ||
| AI | 10103 | Active Hot Water Setpoint | Temperature | Read | ||
| AI | 10104 | Calculated Chiller Capacity | Power, Cooling | Read | ||
| AI | 10105 | Total Demand Distortion | Percent | Read | ||
| AI | 10106 | Active Cool/Heat Setpoint Temperature | Temperature | Read | ||
| AImin | 10107 | Evaporator Leaving Water Temperature | Temperature | Read | ||
| AI | 10108 | Evaporator Entering Water Temperature | Temperature | Read | ||
| AI | 10109 | Condenser Entering Water Temperature | Temperature | Read | ||
| AI | 10110 | Condenser Leaving Water Temperature | Temperature | Read | ||
| AI | 10111 | Evaporator Water Flow Rate | Flow, water | Read | ||
| AI | 10112 | Evaporator Differential Water Pressure | Differential Pressure | Read | ||
| AI | 10113 | Condenser Water Flow Rate | Flow, water | Read | ||
| AI | 10114 | Condenser Differential Water Pressure | Differential Pressure | Read | ||
| AI | 10115 | Heat Recovery Entering Water Temperature | Temperature | Read | ||
| AI | 10116 | Heat Recovery Leaving Water Temperature | Temperature | Read | ||
| AI | 10117 | AFD Last Diagnostic Code Ckt1 | Read | |||
| AI | 10118 | Unit Source ID (Last Diagnostic Code) | Read | |||
| AI | 10119 | Drive Input Voltage Calculated | Voltage | Read | ||
| AI | 10120 | Number of Circuits | Read | |||
| AI | 10121 | Number of Compressors Circuit 1 | Read | |||
| AI | 10122 | Number of Compressors Circuit 2 | Read | |||
| AI | 10123 | Refrigerant Monitor | Concentration | Read | ||
| AI | 10124 | Evaporator Refrigerant Pressure Circuit 1 | Pressure | Read | ||
| AI | 10125 | Condenser Refrigerant Pressure Circuit 1 | Pressure | Read | ||
| AI | 10126 | Differential Refrigerant Pressure Circuit 1 | Differential Pressure | Read | ||
| AI | 10127 | Low Side Oil Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10128 | High Side Oil Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10129 | Oil Differential Pressure Circuit 1 | Differential Pressure | Read | ||
| AI | 10130 | Oil Temperature - Compressor 1A | Temperature | Read | ||
| AI | 10131 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature | Read | ||
| AI | 10132 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature | Read | ||
| AI | 10133 | Refrigerant Discharge Temperature - Compressor 1A | Temperature | Read | ||
| AI | 10134 | Inlet Guide Vane 1 Percent Open Circuit 1 | Percent | Read | ||
| AI | 10135 | Inlet Guide Vane 2 Percent Open Circuit 1 | Percent | Read | ||
| AI | 10136 | Purge Carbon Tank Temperature Circuit 1 | Temperature | Read | ||
| AI | 10137 | Purge Liquid Temperature Circuit 1 | Temperature | Read | ||
| AI | 10138 | Purge Refrigerant Compressor Suction Temperature Circuit 1 | Temperature | Read | ||
| AI | 10139 | Time Until Next Purge Run Circuit 1 (in seconds) | Read | |||
| AI | 10140 | Purge Pumpout Chiller On % (7 Days) Circuit 1 | Percent | Read | ||
| AI | 10141 | Purge Pumpout Chiller Off % (7 Days) Circuit 1 | Percent | Read | ||
| AI | 10142 | Purge 24 Hour Pumpout Circuit 1 (in seconds) | Read | |||
| AI | 10143 | Purge Pumpout - Life Circuit 1 (in seconds) | Read | |||
| AI | 10144 | Refrigeration - Life Circuit 1 (in seconds) | Read | |||
| AI | 10145 | Starts - Compressor 1A | Read | |||
| AI | 10146 | Run Time - Compressor 1A (in seconds) | Read | |||
| AI | 10147 | Phase AB Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10148 | Phase BC Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10149 | Phase CA Voltage - Compressor 1A | Voltage | Read | ||
| AI | 10150 | Starter Average Phase Volt Circuit 1 | Voltage | Read | ||
| AI | 10151 | Line 1 Current - Compressor 1A | Current | Read | ||
| AI | 10152 | Line 2 Current - Compressor 1A | Current | Read | ||
| AI | 10153 | Line 3 Current - Compressor 1A | Current | Read | ||
| AI | 10154 | Average Line Current Circuit 1 | Current | Read | ||
| AI | 10155 | Line 1 Current RLA - Compressor 1A | Percent | Read | ||
| AI | 10156 | Line 2 Current RLA - Compressor 1A | Percent | Read | ||
| AI | 10157 | Line 3 Current RLA - Compressor 1A | Percent | Read | ||
| AImin | 10158 | Actual Running Capacity | Percent | Read | ||
| AI | 10159 | Unit Power Consumption | Power, Electrical | Read | ||
| AI | 10160 | Starter Load Power Factor - Compressor 1A | Read | |||
| AI | 10161 | Inboard Bearing Temperature Circuit 1 | Temperature | Read | ||
| AI | 10162 | Outboard Bearing Temperature Circuit 1 | Temperature | Read | ||
| AI | 10163 | Motor Winding Temperature 1 Circuit 1 | Temperature | Read | ||
| AI | 10164 | Motor Winding Temperature 2 Circuit 1 | Temperature | Read | ||
| AI | 10165 | Motor Winding Temperature 3 Circuit 1 | Temperature | Read | ||
| AI | 10166 | AFD Frequency Circuit 1 | Read | |||
| AI | 10167 | AFD Transistor Temperature Circuit 1 | Temperature | Read | ||
| AI | 10168 | Drive Average Line Current Circuit 1 | Current | Read | ||
| AI | 10169 | Drive Current Line 1 Circuit 1 | Current | Read | ||
| AI | 10170 | Drive Current Line 2 Circuit 1 | Current | Read | ||
| AI | 10171 | Drive Current Line 3 Circuit 1 | Current | Read | ||
| AI | 10172 | Drive Line Frequency Circuit 1 | Read | |||
| AI | 10173 | Drive Frequency Status | Read | |||
| AI | 10174 | Drive Inverter Base Temperature Circuit 1 | Temperature | Read | ||
| AI | 10175 | Drive Rectifier Base Temperature Circuit 1 | Temperature | Read | ||
| AI | 10176 | Drive Output Power Circuit 1 | Current | Read | ||
| AI | 10177 | Drive Motor Current U RLA Circuit 1 | Percent | Read | ||
| AI | 10178 | Drive Motor Current V RLA Circuit 1 | Percent | Read | ||
| AI | 10179 | Drive Motor Current W RLA Circuit 1 | Percent | Read | ||
| AI | 10180 | Drive Motor Current U Circuit 1 | Current | Read | ||
| AI | 10181 | Drive Motor Current V Circuit 1 | Current | Read | ||
| AI | 10182 | Drive Motor Current W Circuit 1 | Current | Read | ||
| AI | 10183 | Drive Motor Voltage UV Circuit 1 | Voltage | Read | ||
| AI | 10184 | Drive Motor Voltage VW Circuit 1 | Voltage | Read | ||
| AI | 10185 | Drive Motor Voltage WU Circuit 1 | Voltage | Read | ||
| AI | 10186 | Drive Motor Average Voltage Circuit 1 | Voltage | Read | ||
| AI | 10187 | Drive Motor Average Current RLA Circuit 1 | Percent | Read | ||
| AI | 10188 | Lube Differential Pressure | Differential Pressure | Read | ||
| AI | 10189 | Lube Pump Suction Pressure | Pressure | Read | ||
| AI | 10190 | Lube Pump Discharge Pressure | Pressure | Read | ||
| AI | 10191 | Motor Coolant Temperature | Temperature | Read | ||
| AI | 10192 | AFD % RLA Ripple | Percent | Read | ||
| AI | 10193 | AFD Inverter Module Temperature U | Temperature | Read | ||
| AI | 10194 | AFD Inverter Module Temperature V | Temperature | Read | ||
| AI | 10195 | AFD Inverter Module Temperature W | Temperature | Read | ||
| AI | 10196 | Outboard Bearing Pad Temperature #1 Ckt1 | Temperature | Read | ||
| AI | 10197 | Outboard Bearing Pad Temperature #2 Ckt1 | Temperature | Read | ||
| AI | 10198 | Outboard Bearing Pad Temperature #3 Ckt1 | Temperature | Read | ||
| AI | 10199 | Condenser Control Output | Percent | Read | ||
| AI | 10200 | Restart Inhibit Time Remaining | Read | |||
| AI | 10201 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10202 | Entering Condenser Water Pressure | Pressure | Read | ||
| AI | 10203 | Entering Evaporator Water Pressure | Pressure | Read | ||
| AI | 10204 | Leaving Condenser Water Pressure | Pressure | Read | ||
| AI | 10205 | Leaving Evaporator Water Pressure | Pressure | Read | ||
| AI | 10206 | Condenser Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10207 | Evaporator Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10208 | Drive DC Bus Voltage Circuit 1 | Voltage | Read | ||
| AI | 10209 | Active Demand Limit Setpoint | Percent | Read | ||
| AI | 10210 | Demand Limit Setpoint Status | Percent | Read | ||
| AI | 10211 | Drive Heatsink Temperature Compressor 1A | Temperature | Read | ||
| AI | 10212 | Heat Recovery Differential Water Pressure | Differential Pressure | Read | ||
| AI | 10213 | Heat Recovery Water Flow Rate | Flow, water | Read | ||
| AI | 10214 | Heat Recovery Calculated Capacity | Power, Heating | Read | ||
| AI | 10215 | Heat Recovery Entering Water Pressure | Pressure | Read | ||
| AI | 10216 | Heat Recovery Leaving Water Pressure | Pressure | Read | ||
| AI | 10217 | Voltage L1-L2 | Voltage | Read | ||
| AI | 10218 | Voltage L2-L3 | Voltage | Read | ||
| AI | 10219 | Voltage L1-L3 | Voltage | Read | ||
| AI | 10220 | Chiller Average Line Voltage | Voltage | Read | ||
| AI | 10221 | Current L1 | Current | Read | ||
| AI | 10222 | Current L2 | Current | Read | ||
| AI | 10223 | Current L3 | Current | Read | ||
| AI | 10224 | Unit Average Line Current | Current | Read | ||
| AI | 10225 | Line Frequency | Read | |||
| AI | 10226 | Power Factor | Read | |||
| AI | 10227 | Unit Power Demand | Read | |||
| AI | 10228 | Energy Consumption | Energy, Electrical | Read | ||
| AI | 10229 | Energy Consumption Lifetime | Energy, Electrical | Read | ||
| AI | 10230 | Outdoor Air Temperature Local | Temperature | Read | ||
| AI | 10231 | Heat Recovery Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10232 | High Side Oil Gauge Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10233 | Low Side Oil Gauge Pressure - Compressor 1A | Pressure | Read | ||
| AI | 10234 | Condenser Refrigerant Gauge Pressure Circuit 1 | Pressure | Read | ||
| AI | 10235 | Entering Condenser Water Gauge Pressure | Pressure | Read | ||
| AI | 10236 | Entering Evaporator Water Gauge Pressure | Pressure | Read | ||
| AI | 10237 | Evaporator Refrigerant Gauge Pressure Circuit 1 | Pressure | Read | ||
| AI | 10238 | Heat Recovery Entering Water Gauge Pressure | Pressure | Read | ||
| AI | 10239 | Heat Recovery Leaving Water Gauge Pressure | Pressure | Read | ||
| AI | 10240 | Leaving Condenser Water Gauge Pressure | Pressure | Read | ||
| AI | 10241 | Leaving Evaporator Water Gauge Pressure | Pressure | Read | ||
| AI | 10242 | Lube Pump Suction Gauge Pressure | Pressure | Read | ||
| AI | 10243 | Lube Pump Discharge Gauge Pressure | Pressure | Read | ||
| AI | 10244 | Active Cooling Differential to Start | Temperature, Delta | Read | ||
| AI | 10245 | Active Cooling Differential to Stop | Temperature, Delta | Read | ||
| AI | 10246 | Active Heating Differential to Start | Temperature, Delta | Read | ||
| AI | 10247 | Active Heating Differential to Stop | Temperature, Delta | Read | ||
| AI | 10248 | Calculated Heating Capacity | Power, Heating | Read | ||
| AI | 10249 | Discharge Superheat Compressor 1A | Temperature, Delta | Read | ||
| AVmin | 10100 | Chilled Water Setpoint | Temperature | Write | ||
| AVmin | 10101 | Demand Limit Setpoint | Percent | Write | ||
| AV | 10102 | Hot Water Setpoint | Temperature | Write | ||
| AV | 10103 | Base Loading Setpoint | Percent | Write | ||
| AV | 10104 | BAS Cooling Differential to Start | Temperature, Delta | Write | ||
| AV | 10105 | BAS Cooling Differential to Stop | Temperature, Delta | Write | ||
| AV | 10106 | BAS Heating Differential to Start | Temperature, Delta | Write | ||
| AV | 10107 | BAS Heating Differential to Stop | Temperature, Delta | Write | ||
| BI | 10100 | Base Loading Request Active | Read | 0 = Off, 1 = On | ||
| BI | 10101 | Emergency Stop | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | ||
| BI | 10102 | Manual Override Exists | Read | 0 = Off, 1 = On | ||
| BI | 10103 | Base Loading Active | Read | 0 = Inactive, 1 = Active | ||
| BI | 10104 | Run Enabled | Read | 0 = Run Not Enabled, 1 = Run Enabled | ||
| BImin | 10105 | Local Setpoint Control | Read | 0 = Remote Control, 1 = Local Control | ||
| BI | 10106 | Maximum Capacity | Read | 0 = Off, 1 = On | ||
| BI | 10107 | Evaporator Leaving Water Temperature | Read | 0 = Not Limited, 1 = Limited | ||
| BI | 10108 | Head Relief Request | Read | 0 = Off, 1 = On | ||
| BI | 10109 | Hot Gas Bypass Active | Read | 0 = Inactive, 1 = Active | ||
| BI | 10110 | Purge Compressor Relay Circuit 1 | Read | 0 = Off, 1 = On | ||
| BI | 10111 | Pump Out Relay Circuit 1 | Read | 0 = Off, 1 = On | ||
| BI | 10112 | Purge Regenerating Valve Solenoid Circuit 1 | Read | 0 = Off, 1 = On | ||
| BImin | 10113 | Chiller Running State | Read | 0 = Off, 1 = On | ||
| BI | 10114 | Evaporator Water Pump Request | Read | 0 = Off, 1 = On | ||
| BI | 10115 | Evaporator Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BI | 10116 | Condenser Water Pump Request | Read | 0 = Off, 1 = On | ||
| BI | 10117 | Condenser Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BImin | 10118 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10119 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10120 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10121 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10122 | Diagnostic Present: Information | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10123 | Diagnostic Present: Advisory | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10124 | Diagnostic Present: Critical | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10125 | Diagnostic Present: Service Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10126 | Compressor 1A Status | Read | 0 = Off, 1 = Running | ||
| BI | 10127 | Front Panel Auto Stop | Read | 0 = Stop, 1 = Auto | ||
| BI | 10128 | External Auto Stop Input Status | Read | 0 = Stop, 1 = Auto | ||
| BI | 10129 | Heat Recovery Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BI | 10130 | AFD Shutdown Diagnostic Present Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11000 | Diagnostic: AFD AD Calibration Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Diagnostic: AFD AHD Frequency Out of Range Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Diagnostic: AFD AHD Sync Signal Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Diagnostic: AFD Bump Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Diagnostic: AFD Bus Over Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Diagnostic: AFD Bus Ripple Too High Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Diagnostic: AFD Bus Under Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Evaporator Leaving Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Diagnostic: AFD Comm Loss: Main Processor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Diagnostic: AFD Current Sensor Self Test Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Diagnostic: AFD Desaturation Detected Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Diagnostic: AFD DPI Communication Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Diagnostic: AFD Drive Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Diagnostic: AFD DSP Board ID Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Diagnostic: AFD DSP Board Initialization Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Diagnostic: AFD DSP Board Low Voltage Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Diagnostic: AFD DSP Board Over Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Diagnostic: AFD Emergency Stop Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Diagnostic: AFD Estimated Junction Over Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Diagnostic: AFD Excessive AHD Inhibit Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Diagnostic: AFD External Fault Input Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Diagnostic: AFD Fatal Software Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Diagnostic: AFD Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Diagnostic: AFD Gate Drive Board Over Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Diagnostic: AFD Gate Drive Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Diagnostic: AFD Gate Drive Low Voltage Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Diagnostic: AFD Gate Drive Module Comm Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Diagnostic: AFD Gate Kill Active Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Diagnostic: AFD General Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Diagnostic: AFD General Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Diagnostic: AFD Ground Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Diagnostic: AFD Ground Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Diagnostic: AFD High Bus Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Diagnostic: AFD High Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Diagnostic: AFD I/O Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11036 | Diagnostic: AFD IGBT Self Test Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11037 | Diagnostic: AFD IMC 24V Detection Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Diagnostic: AFD Input Transformer or Filter High Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Diagnostic: AFD Instantaneous Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Diagnostic: AFD Interrupt Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Diagnostic: AFD Invalid Drive Command Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Diagnostic: AFD Loss of AHD Sync Signal Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Diagnostic: AFD Low Rotor Flux Feedback Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Diagnostic: AFD Mains Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Diagnostic: AFD Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Diagnostic: AFD Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Diagnostic: AFD Motor Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Diagnostic: AFD Motor Short Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Diagnostic: AFD Non-Volatile Memory Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Diagnostic: AFD Output Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Diagnostic: AFD Over Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Diagnostic: AFD Overspeed Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Diagnostic: AFD Panel Interlock Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Diagnostic: AFD Panel Interlock Warning Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Diagnostic: AFD Power Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Diagnostic: AFD Power Structure Board Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Diagnostic: AFD Precharge Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Diagnostic: AFD Rectifier Heatsink Over Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Diagnostic: AFD Safe Stop Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Diagnostic: AFD Short Circuit Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Diagnostic: AFD Speed Configuration Mismatch Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Diagnostic: AFD Start Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Diagnostic: AFD Temperature Sensor Warning Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Diagnostic: AFD Watchdog Timer Overflow Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Diagnostic: At Speed Input Opened Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Diagnostic: At Speed Input Shorted Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Diagnostic: Bearing Lube Flow First Stage Sensor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Diagnostic: Bearing Lube Flow Second Stage Sensor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Diagnostic: Brg Lube Flow Overdue First Stage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Diagnostic: Brg Lube Flow Overdue Second Stage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Diagnostic: Check Lube Filter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Diagnostic: Check Oil Filter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Diagnostic: Check Oil Heater Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Comm Loss: Adaptive Frequency Drive Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Comm Loss: AFD Speed Signal VDC Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Comm Loss: Bearing Lube Flow First Stage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Comm Loss: Bearing Lube Flow Second Stage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Comm Loss: Compressor Motor % RLA Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Comm Loss: Cond Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Comm Loss: Cond Head Press Cntrl Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: Cond High Pressure Cutout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Comm Loss: Cond Lubrication Source Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Comm Loss: Cond Refrigerant Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Comm Loss: Cond Rfgt Pressure Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Comm Loss: Cond Saturated Rfgt Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Comm Loss: Condenser Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Comm Loss: Condenser Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: Condenser Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Comm Loss: Condenser Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Comm Loss: Condenser Liquid Level Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11096 | Comm Loss: Condenser Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Comm Loss: Condenser Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Comm Loss: Cprsr Discharge Rfgt Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Comm Loss: Economizer Bypass Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Comm Loss: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss: Energy Meter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Comm Loss: Evap Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Comm Loss: Evap Lube Source Valve Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Comm Loss: Evap Saturated Rfgt Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11109 | Comm Loss: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11110 | Comm Loss: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11111 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Comm Loss: Evaporator Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: Ext Base Loading Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: Ext Base Loading Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Comm Loss: External Free Cooling Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Comm Loss: External Hot Water Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Comm Loss: Free Cool Actrs Closed Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Free Cool Gas Line Actr Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Comm Loss: Free Cool Liq Line Actr Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Comm Loss: Free Cooling Auxiliary Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Comm Loss: Generator Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Comm Loss: Generator Speed Signal Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Comm Loss: Generator Start/Stop Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Comm Loss: Generator Up To Speed Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Comm Loss: Heat Recovery Differential Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Comm Loss: Heat Recovery Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Heat Recovery Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Heat Recovery Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Comm Loss: Heat Recovery Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Comm Loss: Heat Recovery Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Comm Loss: High Lift Unload Valve Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Hot Gas Bypass Actr Closed In | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Hot Gas Bypass Load Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Comm Loss: Hot Gas Bypass Unload Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Ice Building Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: IGV First Stage Actuator Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Comm Loss: IGV Second Stage Actuator Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Comm Loss: Inboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Lube Pump Discharge Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Lube Pump Suction Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Comm Loss: Lube/Refrigerant Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Comm Loss: Motor Coolant Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Comm Loss: Motor Temp/Overload | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Comm Loss: Motor Temperature Cutout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Comm Loss: Motor Winding Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Comm Loss: Motor Winding Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Comm Loss: Motor Winding Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Comm Loss: Oil Cooler Solenoid Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Comm Loss: Oil Diff Pressure Switch Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Comm Loss: Oil Pressure Status Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Comm Loss: Oil Pump Discharge Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Comm Loss: Oil Tank Heater Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Comm Loss: Oil Tank Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Comm Loss: Oil Tank Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Comm Loss: Oil Vent Line Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Comm Loss: Oil/Refrigerant Pump Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Comm Loss: Outboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Comm Loss: Purge Alarm Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Comm Loss: Purge Carbon Tank Heater Rly Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Comm Loss: Purge Carbon Tank Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Comm Loss: Purge Condensing Unit Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Comm Loss: Purge Exhaust Solenoid Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Comm Loss: Purge Liquid Level Switch Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Comm Loss: Purge Pumpout Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Comm Loss: Purge Pumpout Solenoid Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Comm Loss: Purge Regen Solenoid Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Comm Loss: Refrigerant Monitor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Comm Loss: Starter Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Comm Loss: Starter Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Comm Loss: Vibration Sensor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Diagnostic: Compressor Did Not Accelerate: Shutdown Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Diagnostic: Cond Saturated Refrigerant Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Diagnostic: Condenser Diff Water Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Diagnostic: Condenser Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Diagnostic: Condenser Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Diagnostic: Condenser High Pressure Cutout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Diagnostic: Condenser Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Diagnostic: Condenser Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: Condenser Liquid Level Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: Condenser Refrigerant Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Diagnostic: Condenser Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: Condenser Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: Cprsr Did Not Accelerate: Transition | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: Differential Lube Pressure Overdue Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: Differential Oil Pressure Overdue Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Diagnostic: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Diagnostic: Evap Rfgt Temp Deviate From Selection | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Diagnostic: Evap Saturated Refrigerant Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11205 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Diagnostic: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Diagnostic: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Diagnostic: Excessive Loss of Communication | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Diagnostic: Extended Compressor Surge Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Diagnostic: External Base Loading Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Diagnostic: Free Cooling Actrs Not Open During FC | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: Free Cooling Actuators Not Closed | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11219 | Diagnostic: Free Cooling Actuators Not Open | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11220 | Diagnostic: Free Cooling Actuators Unexpectedly Open | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: Generator Fault Relay Open | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: Generator Ready Signal Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: Heat Recovery Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: Heat Recovery Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11226 | Diagnostic: Heat Recovery Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11227 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11228 | Diagnostic: High Condenser Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11229 | Diagnostic: High Cprsr Rfgt Discharge Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: High Differential Refrigerant Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Diagnostic: High Evaporator Refrigerant Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Diagnostic: High Inboard Bearing Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Diagnostic: High Motor Coolant Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: High Motor Winding Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: High Motor Winding Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Diagnostic: High Motor Winding Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: High Oil Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Diagnostic: High Outboard Bearing Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Diagnostic: High Vacuum Lockout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11244 | Diagnostic: Hot Gas Bypass Valve Closure Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11245 | Diagnostic: Hot Gas Bypass Valve Opening Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11246 | Diagnostic: Hot Gas Bypass Valve Unexpectedly Open | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11247 | Diagnostic: HPC/High AFD Heat Sink Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11248 | Diagnostic: Inboard Bearing Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11249 | Diagnostic: Inverted Condenser Approach Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11250 | Diagnostic: Inverted Condenser Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11251 | Diagnostic: Inverted Evaporator Approach Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11252 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11253 | Diagnostic: Loss of Economizer Bypass Valve Control | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11254 | Diagnostic: Low Bearing Lube Flow First Stage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11255 | Diagnostic: Low Bearing Lube Flow Second Stage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11256 | Diagnostic: Low Brg Lube Flow Lockout First Stage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11257 | Diagnostic: Low Brg Lube Flow Lockout Second Stage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11258 | Diagnostic: Low Differential Lube Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11259 | Diagnostic: Low Differential Oil Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11260 | Diagnostic: Low Evap Leaving Water Temp: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11261 | Diagnostic: Low Evap Leaving Water Temp: Unit On | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11262 | Diagnostic: Low Evaporator Refrigerant Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11263 | Diagnostic: Low Evaporator Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11264 | Diagnostic: Low Oil Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11265 | Diagnostic: Lube Pressure Sensor Calibration Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11266 | Diagnostic: Lube Pump Disch Pressure Xdcr Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11267 | Diagnostic: Lube Pump Override: Low Diff Press Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11268 | Diagnostic: Lube Pump Override: Low Flow 1st Stage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11269 | Diagnostic: Lube Pump Override: Low Flow 2nd Stage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11270 | Diagnostic: Lube Pump Suction Pressure Xdcr Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11271 | Diagnostic: Momentary Power Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11272 | Diagnostic: Motor Coolant Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11273 | Diagnostic: Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11274 | Diagnostic: Motor Temperature Cutout Tripped Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11275 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11276 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11277 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11278 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11279 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11280 | Diagnostic: Oil Pressure Sensor Calibration Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11281 | Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11282 | Diagnostic: Oil Tank Pressure Transducer Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11283 | Diagnostic: Oil Tank Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11284 | Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11285 | Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11286 | Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11287 | Diagnostic: Outboard Bearing Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11288 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11289 | Diagnostic: Over Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11290 | Diagnostic: Phase Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11291 | Diagnostic: Phase Reversal Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11292 | Diagnostic: Power Loss Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11293 | Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11294 | Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11295 | Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11296 | Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11297 | Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11298 | Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11299 | Diagnostic: Purge Liquid Level Too High Continuously Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11300 | Diagnostic: Purge Liquid Level Too High Warning Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11301 | Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11302 | Diagnostic: Refrigerant Monitor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11303 | Diagnostic: Restart Inhibit | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11304 | Diagnostic: Severe Current Unbalance Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11305 | Diagnostic: Software Error 1001: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11306 | Diagnostic: Software Error 1004: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11307 | Diagnostic: Starter Comm Loss: Main Processor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11308 | Diagnostic: Starter Contactor Interrupt Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11309 | Diagnostic: Starter Did Not Fully Accelerate Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11310 | Diagnostic: Starter Did Not Transition Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11311 | Diagnostic: Starter Dry Run Test Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11312 | Diagnostic: Starter Failed to Arm/Start Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11313 | Diagnostic: Starter Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11314 | Diagnostic: Starter Fault Type I Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11315 | Diagnostic: Starter Fault Type II Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11316 | Diagnostic: Starter Fault Type III Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11317 | Diagnostic: Starter Module Memory Error Type 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11318 | Diagnostic: Starter Module Memory Error Type 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11319 | Diagnostic: Transition Complete Input Opened Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11320 | Diagnostic: Transition Complete Input Shorted Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11321 | Diagnostic: Under Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11322 | Diagnostic: Unexpected Differential Lube Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11323 | Diagnostic: Unexpected Differential Oil Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11324 | Diagnostic: Unexpected Starter Shutdown Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11325 | Diagnostic: Vibration Sensor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11326 | Comm Loss: Evap Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11327 | Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11328 | Diagnostic: Inverted Heat Recovery Approach Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11329 | Comm Loss: Sporlan Automatic Econ Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11330 | Comm Loss: Sporlan Automatic Cond Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11331 | Comm Loss: Trane IGV Cond Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11332 | Comm Loss: Trane IGV Econ Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11333 | Diagnostic: External Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11334 | Diagnostic: External Chilled Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11335 | Comm Loss: External Hot Wtr Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11336 | Comm Loss: External Chilled Wtr Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11337 | Comm Loss: Motor Cooling Vent Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11338 | Diagnostic: Motor Cooling Vent Valve Position Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11339 | Comm Loss: Oil Heat Exchanger Vent Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11340 | Diagnostic: Oil Heat Exchanger Vent Valve Position Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11341 | Diagnostic: High Evaporator Refrigerant Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11342 | Diagnostic: Low Condenser Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11343 | Diagnostic: Low Heat Recovery Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11344 | Comm Loss: External Diagnostic Reset | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11345 | Diagnostic: Economizer Refrigerant Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11346 | Diagnostic: Motor Cooling Pressure Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11347 | Comm Loss: Motor Cooling Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11348 | Comm Loss: Motor Cooling Pressure Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BV | 10100 | Base Loading Request | Write | 0 = Off, 1 = On | ||
| BV | 10101 | Reset Diagnostic | Write | 0 = Normal, 1 = Reset | ||
| BV | 10102 | Evaporator Water Pump Request BAS | Write | 0 = Auto, 1 = On | ||
| BV | 10103 | Condenser Water Pump Request BAS | Write | 0 = Auto, 1 = On | ||
| BVmin | 10104 | Chiller Auto Stop Command BAS | Write | 0 = Stop, 1 = Auto | ||
| BV | 10105 | Energy Consumption Reset | Write | 0 = Accumulating, 1 = Reset | ||
| MI | 10100 | Running Mode | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | ||
| MI | 10101 | Operating Mode | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | ||
| MI | 10102 | Chiller Setpoint Source | Read | 1 = BAS, 2 = External, 3 = Front Panel | ||
| MI | 10103 | Model Information [GEN2] | Read | 1 = CVHF, 2 = CVGF, 3 = CVHS, 11 = CDHF, 12 = CVR, 13 = CVHH, 14 = CDHH, 20 = CVHM, 38 = CVHE, 39 = CVHG, 40 = CVHL, 43 = CDHG, 72 =CVZA, 73 =CVXA | ||
| MI | 10104 | Cooling Type | Read | 1 = Water Cooled | ||
| MI | 10105 | Refrigerant Type | Read | 1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A | ||
| MI | 10106 | Manufacturing Location | Read | 1 = Field Applied, 2 = La Crosse, 15 = Taicang | ||
| MVmin | 10100 | Chiller Mode Command BAS | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Object ID lookup: Trane Symbio 800 CenTraVac (Simplex) point IDs by name
AI10100Active Chilled Water SetpointAI10101Chilled Water Setpoint StatusAI10102Active Base Loading SetpointAI10103Active Hot Water SetpointAI10104Calculated Chiller CapacityAI10105Total Demand DistortionAI10106Active Cool/Heat Setpoint TemperatureAI10107Evaporator Leaving Water TemperatureAI10108Evaporator Entering Water TemperatureAI10109Condenser Entering Water TemperatureAI10110Condenser Leaving Water TemperatureAI10111Evaporator Water Flow RateAI10112Evaporator Differential Water PressureAI10113Condenser Water Flow RateAI10114Condenser Differential Water PressureAI10115Heat Recovery Entering Water TemperatureAI10116Heat Recovery Leaving Water TemperatureAI10117AFD Last Diagnostic Code Ckt1AI10118Unit Source ID (Last Diagnostic Code)AI10119Drive Input Voltage CalculatedAI10120Number of CircuitsAI10121Number of Compressors Circuit 1AI10122Number of Compressors Circuit 2AI10123Refrigerant MonitorAI10124Evaporator Refrigerant Pressure Circuit 1AI10125Condenser Refrigerant Pressure Circuit 1AI10126Differential Refrigerant Pressure Circuit 1AI10127Low Side Oil Pressure - Compressor 1AAI10128High Side Oil Pressure - Compressor 1AAI10129Oil Differential Pressure Circuit 1AI10130Oil Temperature - Compressor 1AAI10131Evaporator Saturated Refrigerant Temperature Circuit 1AI10132Condenser Saturated Refrigerant Temperature Circuit 1AI10133Refrigerant Discharge Temperature - Compressor 1AAI10134Inlet Guide Vane 1 Percent Open Circuit 1AI10135Inlet Guide Vane 2 Percent Open Circuit 1AI10136Purge Carbon Tank Temperature Circuit 1AI10137Purge Liquid Temperature Circuit 1AI10138Purge Refrigerant Compressor Suction Temperature Circuit 1AI10139Time Until Next Purge Run Circuit 1 (in seconds)AI10140Purge Pumpout Chiller On % (7 Days) Circuit 1AI10141Purge Pumpout Chiller Off % (7 Days) Circuit 1AI10142Purge 24 Hour Pumpout Circuit 1 (in seconds)AI10143Purge Pumpout - Life Circuit 1 (in seconds)AI10144Refrigeration - Life Circuit 1 (in seconds)AI10145Starts - Compressor 1AAI10146Run Time - Compressor 1A (in seconds)AI10147Phase AB Voltage - Compressor 1AAI10148Phase BC Voltage - Compressor 1AAI10149Phase CA Voltage - Compressor 1AAI10150Starter Average Phase Volt Circuit 1AI10151Line 1 Current - Compressor 1AAI10152Line 2 Current - Compressor 1AAI10153Line 3 Current - Compressor 1AAI10154Average Line Current Circuit 1AI10155Line 1 Current RLA - Compressor 1AAI10156Line 2 Current RLA - Compressor 1AAI10157Line 3 Current RLA - Compressor 1AAI10158Actual Running CapacityAI10159Unit Power ConsumptionAI10160Starter Load Power Factor - Compressor 1AAI10161Inboard Bearing Temperature Circuit 1AI10162Outboard Bearing Temperature Circuit 1AI10163Motor Winding Temperature 1 Circuit 1AI10164Motor Winding Temperature 2 Circuit 1AI10165Motor Winding Temperature 3 Circuit 1AI10166AFD Frequency Circuit 1AI10167AFD Transistor Temperature Circuit 1AI10168Drive Average Line Current Circuit 1AI10169Drive Current Line 1 Circuit 1AI10170Drive Current Line 2 Circuit 1AI10171Drive Current Line 3 Circuit 1AI10172Drive Line Frequency Circuit 1AI10173Drive Frequency StatusAI10174Drive Inverter Base Temperature Circuit 1AI10175Drive Rectifier Base Temperature Circuit 1AI10176Drive Output Power Circuit 1AI10177Drive Motor Current U RLA Circuit 1AI10178Drive Motor Current V RLA Circuit 1AI10179Drive Motor Current W RLA Circuit 1AI10180Drive Motor Current U Circuit 1AI10181Drive Motor Current V Circuit 1AI10182Drive Motor Current W Circuit 1AI10183Drive Motor Voltage UV Circuit 1AI10184Drive Motor Voltage VW Circuit 1AI10185Drive Motor Voltage WU Circuit 1AI10186Drive Motor Average Voltage Circuit 1AI10187Drive Motor Average Current RLA Circuit 1AI10188Lube Differential PressureAI10189Lube Pump Suction PressureAI10190Lube Pump Discharge PressureAI10191Motor Coolant TemperatureAI10192AFD % RLA RippleAI10193AFD Inverter Module Temperature UAI10194AFD Inverter Module Temperature VAI10195AFD Inverter Module Temperature WAI10196Outboard Bearing Pad Temperature #1 Ckt1AI10197Outboard Bearing Pad Temperature #2 Ckt1AI10198Outboard Bearing Pad Temperature #3 Ckt1AI10199Condenser Control OutputAI10200Restart Inhibit Time RemainingAI10201Chiller Design CapacityAI10202Entering Condenser Water PressureAI10203Entering Evaporator Water PressureAI10204Leaving Condenser Water PressureAI10205Leaving Evaporator Water PressureAI10206Condenser Approach Temperature Circuit 1AI10207Evaporator Approach Temperature Circuit 1AI10208Drive DC Bus Voltage Circuit 1AI10209Active Demand Limit SetpointAI10210Demand Limit Setpoint StatusAI10211Drive Heatsink Temperature Compressor 1AAI10212Heat Recovery Differential Water PressureAI10213Heat Recovery Water Flow RateAI10214Heat Recovery Calculated CapacityAI10215Heat Recovery Entering Water PressureAI10216Heat Recovery Leaving Water PressureAI10217Voltage L1-L2AI10218Voltage L2-L3AI10219Voltage L1-L3AI10220Chiller Average Line VoltageAI10221Current L1AI10222Current L2AI10223Current L3AI10224Unit Average Line CurrentAI10225Line FrequencyAI10226Power FactorAI10227Unit Power DemandAI10228Energy ConsumptionAI10229Energy Consumption LifetimeAI10230Outdoor Air Temperature LocalAI10231Heat Recovery Approach Temperature Circuit 1AI10232High Side Oil Gauge Pressure - Compressor 1AAI10233Low Side Oil Gauge Pressure - Compressor 1AAI10234Condenser Refrigerant Gauge Pressure Circuit 1AI10235Entering Condenser Water Gauge PressureAI10236Entering Evaporator Water Gauge PressureAI10237Evaporator Refrigerant Gauge Pressure Circuit 1AI10238Heat Recovery Entering Water Gauge PressureAI10239Heat Recovery Leaving Water Gauge PressureAI10240Leaving Condenser Water Gauge PressureAI10241Leaving Evaporator Water Gauge PressureAI10242Lube Pump Suction Gauge PressureAI10243Lube Pump Discharge Gauge PressureAI10244Active Cooling Differential to StartAI10245Active Cooling Differential to StopAI10246Active Heating Differential to StartAI10247Active Heating Differential to StopAI10248Calculated Heating CapacityAI10249Discharge Superheat Compressor 1AAV10100Chilled Water SetpointAV10101Demand Limit SetpointAV10102Hot Water SetpointAV10103Base Loading SetpointAV10104BAS Cooling Differential to StartAV10105BAS Cooling Differential to StopAV10106BAS Heating Differential to StartAV10107BAS Heating Differential to StopBI10100Base Loading Request ActiveBI10101Emergency StopBI10102Manual Override ExistsBI10103Base Loading ActiveBI10104Run EnabledBI10105Local Setpoint ControlBI10106Maximum CapacityBI10107Evaporator Leaving Water TemperatureBI10108Head Relief RequestBI10109Hot Gas Bypass ActiveBI10110Purge Compressor Relay Circuit 1BI10111Pump Out Relay Circuit 1BI10112Purge Regenerating Valve Solenoid Circuit 1BI10113Chiller Running StateBI10114Evaporator Water Pump RequestBI10115Evaporator Water Flow StatusBI10116Condenser Water Pump RequestBI10117Condenser Water Flow StatusBI10118Diagnostic PresentBI10119Diagnostic Shutdown PresentBI10120Diagnostic: Manual Reset RequiredBI10121Diagnostic: Local Manual Reset RequiredBI10122Diagnostic Present: InformationBI10123Diagnostic Present: AdvisoryBI10124Diagnostic Present: CriticalBI10125Diagnostic Present: Service RequiredBI10126Compressor 1A StatusBI10127Front Panel Auto StopBI10128External Auto Stop Input StatusBI10129Heat Recovery Water Flow StatusBI10130AFD Shutdown Diagnostic Present Circuit 1BI11000Diagnostic: AFD AD Calibration Error Circuit 1BI11001Diagnostic: AFD AHD Frequency Out of Range Circuit 1BI11002Diagnostic: AFD AHD Sync Signal Error Circuit 1BI11003Diagnostic: AFD Bump Failure Circuit 1BI11004Diagnostic: AFD Bus Over Voltage Circuit 1BI11005Diagnostic: AFD Bus Ripple Too High Circuit 1BI11006Diagnostic: AFD Bus Under Voltage Circuit 1BI11007Evaporator Leaving Water TemperatureBI11008Diagnostic: AFD Comm Loss: Main Processor Circuit 1BI11009Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1BI11010Diagnostic: AFD Current Sensor Self Test Failure Circuit 1BI11011Diagnostic: AFD Desaturation Detected Circuit 1BI11012Diagnostic: AFD DPI Communication Failure Circuit 1BI11013Diagnostic: AFD Drive Fault Circuit 1BI11014Diagnostic: AFD DSP Board ID Error Circuit 1BI11015Diagnostic: AFD DSP Board Initialization Failure Circuit 1BI11016Diagnostic: AFD DSP Board Low Voltage Failure Circuit 1BI11017Diagnostic: AFD DSP Board Over Temp Circuit 1BI11018Diagnostic: AFD Emergency Stop Fault Circuit 1BI11019Diagnostic: AFD Estimated Junction Over Temp Circuit 1BI11020Diagnostic: AFD Excessive AHD Inhibit Circuit 1BI11021Diagnostic: AFD External Fault Input Circuit 1BI11022Diagnostic: AFD Fatal Software Error Circuit 1BI11023Diagnostic: AFD Fault Circuit 1BI11024Diagnostic: AFD Gate Drive Board Over Temp Circuit 1BI11025Diagnostic: AFD Gate Drive Fault Circuit 1BI11026Diagnostic: AFD Gate Drive Low Voltage Failure Circuit 1BI11027Diagnostic: AFD Gate Drive Module Comm Loss Circuit 1BI11028Diagnostic: AFD Gate Kill Active Circuit 1BI11029Diagnostic: AFD General Failure Circuit 1BI11030Diagnostic: AFD General Failure Circuit 1BI11031Diagnostic: AFD Ground Fault Circuit 1BI11032Diagnostic: AFD Ground Fault Circuit 1BI11033Diagnostic: AFD High Bus Voltage Circuit 1BI11034Diagnostic: AFD High Temperature Circuit 1BI11035Diagnostic: AFD I/O Board Failure Circuit 1BI11036Diagnostic: AFD IGBT Self Test Failure Circuit 1BI11037Diagnostic: AFD IMC 24V Detection Failure Circuit 1BI11038Diagnostic: AFD Input Transformer or Filter High Temp Circuit 1BI11039Diagnostic: AFD Instantaneous Current Overload Circuit 1BI11040Diagnostic: AFD Interrupt Failure Circuit 1BI11041Diagnostic: AFD Invalid Drive Command Circuit 1BI11042Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1BI11043Diagnostic: AFD Loss of AHD Sync Signal Circuit 1BI11044Diagnostic: AFD Low Rotor Flux Feedback Circuit 1BI11045Diagnostic: AFD Mains Phase Loss Circuit 1BI11046Diagnostic: AFD Motor Current Overload Circuit 1BI11047Diagnostic: AFD Motor Current Overload Circuit 1BI11048Diagnostic: AFD Motor Fault Circuit 1BI11049Diagnostic: AFD Motor Short Circuit 1BI11050Diagnostic: AFD Non-Volatile Memory Failure Circuit 1BI11051Diagnostic: AFD Output Phase Loss Circuit 1BI11052Diagnostic: AFD Over Temperature Circuit 1BI11053Diagnostic: AFD Overspeed Circuit 1BI11054Diagnostic: AFD Panel Interlock Fault Circuit 1BI11055Diagnostic: AFD Panel Interlock Warning Circuit 1BI11056Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1BI11057Diagnostic: AFD Power Loss Circuit 1BI11058Diagnostic: AFD Power Structure Board Failure Circuit 1BI11059Diagnostic: AFD Precharge Fault Circuit 1BI11060Diagnostic: AFD Rectifier Heatsink Over Temp Circuit 1BI11061Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1BI11062Diagnostic: AFD Safe Stop Circuit 1BI11063Diagnostic: AFD Short Circuit Circuit 1BI11064Diagnostic: AFD Speed Configuration Mismatch Circuit 1BI11065Diagnostic: AFD Start Failure Circuit 1BI11066Diagnostic: AFD Temperature Sensor Warning Circuit 1BI11067Diagnostic: AFD Watchdog Timer Overflow Circuit 1BI11068Diagnostic: At Speed Input Opened Circuit 1BI11069Diagnostic: At Speed Input Shorted Circuit 1BI11070Diagnostic: Bearing Lube Flow First Stage Sensor InputBI11071Diagnostic: Bearing Lube Flow Second Stage Sensor InputBI11072Diagnostic: Brg Lube Flow Overdue First Stage Circuit 1BI11073Diagnostic: Brg Lube Flow Overdue Second Stage Circuit 1BI11075Diagnostic: Check Lube Filter Circuit 1BI11076Diagnostic: Check Oil Filter Circuit 1BI11077Diagnostic: Check Oil Heater Circuit 1BI11078Comm Loss: Adaptive Frequency Drive Circuit 1BI11079Comm Loss: AFD Speed Signal VDC Output Circuit 1BI11080Comm Loss: Bearing Lube Flow First StageBI11081Comm Loss: Bearing Lube Flow Second StageBI11082Comm Loss: Compressor Motor % RLA Output Circuit 1BI11083Comm Loss: Cond Diff Water PressureBI11084Comm Loss: Cond Head Press Cntrl OutputBI11085Comm Loss: Cond High Pressure CutoutBI11086Comm Loss: Cond Lubrication Source ValveBI11087Comm Loss: Cond Refrigerant PressureBI11088Comm Loss: Cond Rfgt Pressure OutputBI11089Comm Loss: Cond Saturated Rfgt TempBI11090Comm Loss: Condenser Entering Water PressureBI11091Comm Loss: Condenser Entering Water TempBI11092Comm Loss: Condenser Leaving Water PressureBI11093Comm Loss: Condenser Leaving Water TempBI11094Comm Loss: Condenser Liquid Level SensorBI11096Comm Loss: Condenser Water Flow SwitchBI11097Comm Loss: Condenser Water Pump RelayBI11098Comm Loss: Cprsr Discharge Rfgt TempBI11099Comm Loss: Economizer Bypass ValveBI11102Comm Loss: Emergency StopBI11103Comm Loss: Energy Meter Circuit 1BI11104Comm Loss: Evap Diff Water PressureBI11105Comm Loss: Evap Entering Water TempBI11106Comm Loss: Evap Leaving Water TempBI11107Comm Loss: Evap Lube Source Valve RelayBI11108Comm Loss: Evap Saturated Rfgt TempBI11109Comm Loss: Evaporator Entering Water PressureBI11110Comm Loss: Evaporator Leaving Water PressureBI11111Comm Loss: Evaporator Water Flow SwitchBI11112Comm Loss: Evaporator Water Pump RelayBI11113Comm Loss: Ext Base Loading CommandBI11114Comm Loss: Ext Base Loading SetpointBI11115Comm Loss: Ext Chilled/Hot Water SetpointBI11116Comm Loss: Ext Demand Limit SetpointBI11117Comm Loss: External Auto/StopBI11118Comm Loss: External Free Cooling CommandBI11119Comm Loss: External Hot Water CommandBI11120Comm Loss: External Ice Building CommandBI11121Comm Loss: Free Cool Actrs Closed InputBI11122Comm Loss: Free Cool Gas Line Actr RelayBI11123Comm Loss: Free Cool Liq Line Actr RelayBI11124Comm Loss: Free Cooling Auxiliary RelayBI11125Comm Loss: Generator Fault InputBI11126Comm Loss: Generator Speed Signal OutputBI11127Comm Loss: Generator Start/Stop RelayBI11128Comm Loss: Generator Up To Speed InputBI11129Comm Loss: Heat Recovery Differential Water PressureBI11130Comm Loss: Heat Recovery Entering Water PressureBI11131Comm Loss: Heat Recovery Entering Water TempBI11132Comm Loss: Heat Recovery Leaving Water PressureBI11133Comm Loss: Heat Recovery Leaving Water TempBI11134Comm Loss: Heat Recovery Water Flow SwitchBI11135Comm Loss: High Lift Unload Valve RelayBI11136Comm Loss: Hot Gas Bypass Actr Closed InBI11137Comm Loss: Hot Gas Bypass Load RelayBI11138Comm Loss: Hot Gas Bypass Unload RelayBI11139Comm Loss: Ice Building RelayBI11140Comm Loss: IGV First Stage Actuator Circuit 1BI11141Comm Loss: IGV Second Stage Actuator Circuit 1BI11142Comm Loss: Inboard Bearing Temperature Circuit 1BI11143Comm Loss: Lube Pump Discharge PressureBI11144Comm Loss: Lube Pump Suction PressureBI11145Comm Loss: Lube/Refrigerant Pump RelayBI11146Comm Loss: Motor Coolant TemperatureBI11147Comm Loss: Motor Temp/OverloadBI11148Comm Loss: Motor Temperature CutoutBI11149Comm Loss: Motor Winding Temperature 1 Circuit 1BI11150Comm Loss: Motor Winding Temperature 2 Circuit 1BI11151Comm Loss: Motor Winding Temperature 3 Circuit 1BI11152Comm Loss: Oil Cooler Solenoid Circuit 1BI11153Comm Loss: Oil Diff Pressure Switch Circuit 1BI11154Comm Loss: Oil Pressure Status Circuit 1BI11155Comm Loss: Oil Pump Discharge Pressure Circuit 1BI11156Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1BI11157Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1BI11158Comm Loss: Oil Tank Heater Relay Circuit 1BI11159Comm Loss: Oil Tank Pressure Circuit 1BI11160Comm Loss: Oil Tank Temperature Circuit 1BI11161Comm Loss: Oil Vent Line Circuit 1BI11162Comm Loss: Oil/Refrigerant Pump Relay Circuit 1BI11163Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1BI11164Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1BI11165Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1BI11166Comm Loss: Outboard Bearing Temperature Circuit 1BI11167Comm Loss: Outdoor Air TemperatureBI11168Comm Loss: Programmable Relay Board 1BI11169Comm Loss: Programmable Relay Board 2BI11170Comm Loss: Purge Alarm Relay Circuit 1BI11171Comm Loss: Purge Carbon Tank Heater Rly Circuit 1BI11172Comm Loss: Purge Carbon Tank Temperature Circuit 1BI11173Comm Loss: Purge Condensing Unit Relay Circuit 1BI11174Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1BI11175Comm Loss: Purge Exhaust Solenoid Output Circuit 1BI11176Comm Loss: Purge Liquid Level Switch Circuit 1BI11177Comm Loss: Purge Pumpout Relay Circuit 1BI11178Comm Loss: Purge Pumpout Solenoid Output Circuit 1BI11179Comm Loss: Purge Regen Solenoid Relay Circuit 1BI11180Comm Loss: Refrigerant Monitor InputBI11181Comm Loss: Starter Circuit 1BI11182Comm Loss: Starter Fault Circuit 1BI11183Comm Loss: Vibration Sensor InputBI11184Diagnostic: Compressor Did Not Accelerate: Shutdown Compressor 1ABI11185Diagnostic: Cond Saturated Refrigerant Temp SensorBI11186Diagnostic: Condenser Diff Water Pressure XdcrBI11187Diagnostic: Condenser Entering Water PressureBI11188Diagnostic: Condenser Entering Water Temp SensorBI11189Diagnostic: Condenser High Pressure CutoutBI11190Diagnostic: Condenser Leaving Water PressureBI11191Diagnostic: Condenser Leaving Water Temp SensorBI11192Diagnostic: Condenser Liquid Level SensorBI11193Diagnostic: Condenser Refrigerant Pressure XdcrBI11195Diagnostic: Condenser Water Flow LostBI11196Diagnostic: Condenser Water Flow OverdueBI11197Diagnostic: Cprsr Did Not Accelerate: TransitionBI11198Diagnostic: Cprsr Discharge Refrigerant Temp SensorBI11199Diagnostic: Differential Lube Pressure Overdue Circuit 1BI11200Diagnostic: Differential Oil Pressure Overdue Circuit 1BI11202Diagnostic: Emergency StopBI11203Diagnostic: Evap Rfgt Temp Deviate From SelectionBI11204Diagnostic: Evap Saturated Refrigerant Temp SensorBI11205Diagnostic: Evaporator Diff Water Pressure XdcrBI11206Diagnostic: Evaporator Entering Water PressureBI11207Diagnostic: Evaporator Entering Water Temp SensorBI11208Diagnostic: Evaporator Leaving Water PressureBI11209Diagnostic: Evaporator Leaving Water Temp SensorBI11210Diagnostic: Evaporator Water Flow LostBI11211Diagnostic: Evaporator Water Flow OverdueBI11212Diagnostic: Excessive Loss of CommunicationBI11213Diagnostic: Extended Compressor Surge Compressor 1ABI11214Diagnostic: External Base Loading SetpointBI11215Diagnostic: External Chilled/Hot Water SetpointBI11216Diagnostic: External Demand Limit SetpointBI11217Diagnostic: Free Cooling Actrs Not Open During FCBI11218Diagnostic: Free Cooling Actuators Not ClosedBI11219Diagnostic: Free Cooling Actuators Not OpenBI11220Diagnostic: Free Cooling Actuators Unexpectedly OpenBI11221Diagnostic: Generator Fault Relay OpenBI11222Diagnostic: Generator Ready Signal OverdueBI11223Diagnostic: Heat Recovery Diff Water PressureBI11224Diagnostic: Heat Recovery Entering Water PressureBI11225Diagnostic: Heat Recovery Entering Water Temp SensorBI11226Diagnostic: Heat Recovery Leaving Water PressureBI11227Diagnostic: Heat Recovery Leaving Water Temp SensorBI11228Diagnostic: High Condenser PressureBI11229Diagnostic: High Cprsr Rfgt Discharge TemperatureBI11230Diagnostic: High Differential Refrigerant PressureBI11231Diagnostic: High Evaporator Refrigerant TemperatureBI11232Diagnostic: High Evaporator Water TemperatureBI11233Diagnostic: High Inboard Bearing Temperature Circuit 1BI11234Diagnostic: High Motor Coolant Temperature Circuit 1BI11235Diagnostic: High Motor Winding Temperature 1 Circuit 1BI11236Diagnostic: High Motor Winding Temperature 2 Circuit 1BI11237Diagnostic: High Motor Winding Temperature 3 Circuit 1BI11238Diagnostic: High Oil Temperature Circuit 1BI11239Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1BI11240Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1BI11241Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1BI11242Diagnostic: High Outboard Bearing Temp Circuit 1BI11243Diagnostic: High Vacuum Lockout Circuit 1BI11244Diagnostic: Hot Gas Bypass Valve Closure OverdueBI11245Diagnostic: Hot Gas Bypass Valve Opening OverdueBI11246Diagnostic: Hot Gas Bypass Valve Unexpectedly OpenBI11247Diagnostic: HPC/High AFD Heat Sink Water PressureBI11248Diagnostic: Inboard Bearing Temp Sensor Circuit 1BI11249Diagnostic: Inverted Condenser Approach TemperatureBI11250Diagnostic: Inverted Condenser Water TemperatureBI11251Diagnostic: Inverted Evaporator Approach TemperatureBI11252Diagnostic: Inverted Evaporator Water TemperatureBI11253Diagnostic: Loss of Economizer Bypass Valve ControlBI11254Diagnostic: Low Bearing Lube Flow First Stage Circuit 1BI11255Diagnostic: Low Bearing Lube Flow Second Stage Circuit 1BI11256Diagnostic: Low Brg Lube Flow Lockout First Stage Circuit 1BI11257Diagnostic: Low Brg Lube Flow Lockout Second Stage Circuit 1BI11258Diagnostic: Low Differential Lube Pressure Circuit 1BI11259Diagnostic: Low Differential Oil Pressure Circuit 1BI11260Diagnostic: Low Evap Leaving Water Temp: Unit OffBI11261Diagnostic: Low Evap Leaving Water Temp: Unit OnBI11262Diagnostic: Low Evaporator Refrigerant TemperatureBI11263Diagnostic: Low Evaporator Water FlowBI11264Diagnostic: Low Oil Temperature Circuit 1BI11265Diagnostic: Lube Pressure Sensor Calibration Circuit 1BI11266Diagnostic: Lube Pump Disch Pressure Xdcr Circuit 1BI11267Diagnostic: Lube Pump Override: Low Diff Press Circuit 1BI11268Diagnostic: Lube Pump Override: Low Flow 1st Stage Circuit 1BI11269Diagnostic: Lube Pump Override: Low Flow 2nd Stage Circuit 1BI11270Diagnostic: Lube Pump Suction Pressure Xdcr Circuit 1BI11271Diagnostic: Momentary Power LossBI11272Diagnostic: Motor Coolant Temperature Sensor Circuit 1BI11273Diagnostic: Motor Current Overload Circuit 1BI11274Diagnostic: Motor Temperature Cutout Tripped Circuit 1BI11275Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1BI11276Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1BI11277Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1BI11278Diagnostic: MP: Invalid ConfigurationBI11279Diagnostic: MP: Reset Has OccurredBI11280Diagnostic: Oil Pressure Sensor Calibration Circuit 1BI11281Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1BI11282Diagnostic: Oil Tank Pressure Transducer Circuit 1BI11283Diagnostic: Oil Tank Temperature Sensor Circuit 1BI11284Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1BI11285Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1BI11286Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1BI11287Diagnostic: Outboard Bearing Temperature Sensor Circuit 1BI11288Diagnostic: Outdoor Air Temperature SensorBI11289Diagnostic: Over Voltage Circuit 1BI11290Diagnostic: Phase Loss Circuit 1BI11291Diagnostic: Phase Reversal Circuit 1BI11292Diagnostic: Power Loss Circuit 1BI11293Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1BI11294Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1BI11295Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1BI11296Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1BI11297Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1BI11298Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1BI11299Diagnostic: Purge Liquid Level Too High Continuously Circuit 1BI11300Diagnostic: Purge Liquid Level Too High Warning Circuit 1BI11301Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1BI11302Diagnostic: Refrigerant Monitor InputBI11303Diagnostic: Restart InhibitBI11304Diagnostic: Severe Current Unbalance Circuit 1BI11305Diagnostic: Software Error 1001: Call Trane ServiceBI11306Diagnostic: Software Error 1004: Call Trane ServiceBI11307Diagnostic: Starter Comm Loss: Main Processor Circuit 1BI11308Diagnostic: Starter Contactor Interrupt Failure Circuit 1BI11309Diagnostic: Starter Did Not Fully Accelerate Circuit 1BI11310Diagnostic: Starter Did Not Transition Circuit 1BI11311Diagnostic: Starter Dry Run Test Circuit 1BI11312Diagnostic: Starter Failed to Arm/Start Circuit 1BI11313Diagnostic: Starter Fault Circuit 1BI11314Diagnostic: Starter Fault Type I Circuit 1BI11315Diagnostic: Starter Fault Type II Circuit 1BI11316Diagnostic: Starter Fault Type III Circuit 1BI11317Diagnostic: Starter Module Memory Error Type 1 Circuit 1BI11318Diagnostic: Starter Module Memory Error Type 2 Circuit 1BI11319Diagnostic: Transition Complete Input Opened Circuit 1BI11320Diagnostic: Transition Complete Input Shorted Circuit 1BI11321Diagnostic: Under Voltage Circuit 1BI11322Diagnostic: Unexpected Differential Lube Pressure Circuit 1BI11323Diagnostic: Unexpected Differential Oil Pressure Circuit 1BI11324Diagnostic: Unexpected Starter Shutdown Circuit 1BI11325Diagnostic: Vibration Sensor InputBI11326Comm Loss: Evap Refrigerant Pressure Circuit 1BI11327Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1BI11328Diagnostic: Inverted Heat Recovery Approach Temperature Circuit 1BI11329Comm Loss: Sporlan Automatic Econ Valve Circuit 1BI11330Comm Loss: Sporlan Automatic Cond Valve Circuit 1BI11331Comm Loss: Trane IGV Cond Valve Circuit 1BI11332Comm Loss: Trane IGV Econ Valve Circuit 1BI11333Diagnostic: External Hot Water SetpointBI11334Diagnostic: External Chilled Water SetpointBI11335Comm Loss: External Hot Wtr SetpointBI11336Comm Loss: External Chilled Wtr SetpointBI11337Comm Loss: Motor Cooling Vent Valve Circuit 1BI11338Diagnostic: Motor Cooling Vent Valve Position Error Circuit 1BI11339Comm Loss: Oil Heat Exchanger Vent Valve Circuit 1BI11340Diagnostic: Oil Heat Exchanger Vent Valve Position Error Circuit 1BI11341Diagnostic: High Evaporator Refrigerant TemperatureBI11342Diagnostic: Low Condenser Water FlowBI11343Diagnostic: Low Heat Recovery Water FlowBI11344Comm Loss: External Diagnostic ResetBI11345Diagnostic: Economizer Refrigerant PressureBI11346Diagnostic: Motor Cooling Pressure Sensor Circuit 1BI11347Comm Loss: Motor Cooling Valve Circuit 1BI11348Comm Loss: Motor Cooling Pressure Sensor Circuit 1BV10100Base Loading RequestBV10101Reset DiagnosticBV10102Evaporator Water Pump Request BASBV10103Condenser Water Pump Request BASBV10104Chiller Auto Stop Command BASBV10105Energy Consumption ResetMI10100Running ModeMI10101Operating ModeMI10102Chiller Setpoint SourceMI10103Model Information [GEN2]MI10104Cooling TypeMI10105Refrigerant TypeMI10106Manufacturing LocationMV10100Chiller Mode Command BAS
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the communicated engineering unit follows the factory-configured unit system (I-P or SI), not the web UI display setting.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- The source document also has a separate table for duplex (two-compressor) CenTraVacs; see the duplex page.
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 CenTraVac (Simplex) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 CenTraVac (Simplex)
How many BACnet points does the Trane Symbio 800 CenTraVac (Simplex) have?
This list has 546 BACnet objects: 150 analog inputs, 8 analog values, 374 binary inputs, 6 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 CenTraVac (Simplex) BACnet points are writable?
15 of the 546 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 CenTraVac (Simplex) BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - CenTraVac (BAS-PTS009C-EN), revision 12/12/2025, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 CenTraVac (Simplex)?
Start with BV 10104 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10113 Chiller Running State (Chiller on/off status); BI 10105 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10107 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10158 Actual Running Capacity (Actual running capacity in percent); BI 10118 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 CenTraVac (Simplex)?
BV 10104 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10128 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10104 Run Enabled shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10105 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
How do I check these points on the real Symbio 800 CenTraVac (Simplex)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet - CenTraVac · BAS-PTS009C-EN · rev. 12/12/2025. Object names, instances and units are reproduced as published; descriptions are our own.