Water-cooled centrifugal chiller controller · BACnet points list
Trane Symbio 800 Agility (HDWA / HDDA) BACnet points list
Updated 28 October 2026
The standard Symbio 800 list for Agility chillers has about 425 BACnet objects with 5-digit instance numbers (AI 10100 and up). AIs cover water temperatures, flows and pressures, refrigerant, AFD drive, bearing and motor data for one or two circuits. The BAS writes chilled and hot water setpoints, demand limit, base loading, differentials to start/stop, auto/stop, pump requests, circuit lockouts and mode. Most binary inputs are per-condition diagnostic and comm-loss flags.
This page lists 424 BACnet objects for the Trane Symbio 800 Agility (HDWA / HDDA) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 Agility (HDWA / HDDA)
- Equipment
- Water-cooled centrifugal chiller controller
- Equipment type
- Chillers
- BACnet objects
- 424 (17 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 Agility (HDWA / HDDA)
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10102 | Chiller Auto Stop Command BAS | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10109 | Chiller Running State | Chiller on/off status | Read |
| BI 10118 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10136 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10153 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10100 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10102 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10124 External Auto Stop Input Status reports the hardwired external auto/stop input, BI 10123 the front-panel auto/stop, and BI 10121 Run Enabled shows whether the chiller is enabled to run. The document doesn't say how these combine or how to hand setpoint control to the BAS; BI 10118 Local Setpoint Control shows when the chiller is using local setpoints, and MI 10103 Chiller Setpoint Source shows BAS, External or Front Panel.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
Trane Symbio 800 Agility (HDWA / HDDA) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Chilled Water Setpoint | Temperature | Read | ||
| AI | 10101 | Active Base Loading Setpoint | Percentage | Read | ||
| AI | 10102 | Active Cool/Heat Setpoint Temperature | Temperature | Read | ||
| AI | 10103 | Active Hot Water Setpoint | Temperature | Read | ||
| AI | 10104 | Active Demand Limit Setpoint | Percentage | Read | ||
| AI | 10105 | Demand Limit Setpoint Status | Percentage | Read | ||
| AI | 10106 | Chilled Water Setpoint Status | Temperature | Read | ||
| AI | 10107 | Drive Motor Average Current RLA Circuit 1 | Percentage | Read | ||
| AI | 10108 | Drive Motor Voltage | Voltage | Read | ||
| AI | 10109 | Drive DC Bus Voltage Circuit 1 | Voltage | Read | ||
| AI | 10110 | AFD Frequency Circuit 1 | Read | |||
| AI | 10111 | AFD Transistor Temperature Circuit 1 | Temperature | Read | ||
| AI | 10112 | Drive Motor Current U Circuit 1 | Current | Read | ||
| AI | 10113 | Drive Motor Current U RLA Circuit 1 | Percentage | Read | ||
| AI | 10114 | Drive Motor Current V Circuit 1 | Current | Read | ||
| AI | 10115 | Drive Motor Current V RLA Circuit 1 | Percentage | Read | ||
| AI | 10116 | Drive Motor Current W Circuit 1 | Current | Read | ||
| AI | 10117 | Drive Motor Current W RLA Circuit 1 | Percentage | Read | ||
| AI | 10118 | Drive Output Power Circuit 1 | Power, Electrical | Read | ||
| AI | 10119 | Drive Speed Status Percent | Percentage | Read | ||
| AI | 10120 | Condenser Water Flow Rate | Flow, Fluidic | Read | ||
| AI | 10121 | Evaporator Water Flow Rate | Flow, Fluidic | Read | ||
| AI | 10122 | Calculated Chiller Capacity | Power, Cooling | Read | ||
| AI | 10123 | Compressor Bearing Temperature 1 - Compressor 1A | Temperature | Read | ||
| AI | 10124 | Compressor Bearing Temperature 2 - Compressor 1A | Temperature | Read | ||
| AI | 10125 | Refrigerant Discharge Temperature - Compressor 1A | Temperature | Read | ||
| AI | 10126 | Run Time - Compressor 1A (in seconds) | Read | |||
| AI | 10127 | Starts - Compressor 1A | Read | |||
| AI | 10128 | Condenser Differential Water Pressure | Pressure, Fluidic | Read | ||
| AI | 10129 | Condenser Entering Water Temperature | Temperature | Read | ||
| AI | 10130 | Condenser Leaving Water Temperature | Temperature | Read | ||
| AI | 10131 | Condenser Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10132 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature | Read | ||
| AI | 10133 | Differential Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10134 | Evaporator Differential Water Pressure | Pressure, Fluidic | Read | ||
| AI | 10135 | Evaporator Entering Water Temperature | Temperature | Read | ||
| AImin | 10136 | Evaporator Leaving Water Temperature | Temperature | Read | ||
| AI | 10137 | Evaporator Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10138 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature | Read | ||
| AI | 10139 | Entering Condenser Water Pressure | Pressure, Fluidic | Read | ||
| AI | 10140 | Leaving Condenser Water Pressure | Pressure, Fluidic | Read | ||
| AI | 10141 | Entering Evaporator Water Pressure | Pressure, Fluidic | Read | ||
| AI | 10142 | Leaving Evaporator Water Pressure | Pressure, Fluidic | Read | ||
| AI | 10143 | Inlet Guide Vane 1 Percent Open Circuit 1 | Percentage | Read | ||
| AI | 10144 | Motor Winding Temperature 1 Circuit 1 | Temperature | Read | ||
| AI | 10145 | Motor Winding Temperature 2 Circuit 1 | Temperature | Read | ||
| AI | 10146 | Motor Winding Temperature 3 Circuit 1 | Temperature | Read | ||
| AI | 10147 | Number of Circuits | Read | |||
| AI | 10148 | Number of Compressors Circuit 1 | Read | |||
| AI | 10149 | Number of Compressors Circuit 2 | Read | |||
| AI | 10150 | Refrigerant Monitor | PPM | Read | ||
| AI | 10151 | Unit Power Consumption | Power, Electrical | Read | ||
| AI | 10152 | Drive Input Voltage Calculated 1A | Voltage | Read | ||
| AImin | 10153 | Actual Running Capacity | Percentage | Read | ||
| AI | 10154 | Unit Source ID | Read | |||
| AI | 10155 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10156 | Outdoor Air Temperature | Temperature | Read | ||
| AI | 10157 | Energy Consumption Lifetime | Energy, Electrical | Read | ||
| AI | 10158 | Energy Consumption | Energy, Electrical | Read | ||
| AI | 10159 | Unit Power Demand | Power, Electrical | Read | ||
| AI | 10160 | Voltage L1-L2 | Voltage | Read | ||
| AI | 10161 | Voltage L2-L3 | Voltage | Read | ||
| AI | 10162 | Voltage L1-L3 | Voltage | Read | ||
| AI | 10163 | Current L1 | Current | Read | ||
| AI | 10164 | Current L2 | Current | Read | ||
| AI | 10165 | Current L3 | Current | Read | ||
| AI | 10166 | Line Frequency | Read | |||
| AI | 10167 | Power Factor | Read | |||
| AI | 10168 | Condenser Control Output | Percentage | Read | ||
| AI | 10169 | Average Voltage L-L | Voltage | Read | ||
| AI | 10170 | Average Current | Current | Read | ||
| AI | 10171 | Condenser Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10172 | Evaporator Approach Temperature Circuit 1 | Temperature, Delta | Read | ||
| AI | 10173 | Condenser Refrigerant Gauge Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10174 | Entering Condenser Water Gauge Pressure | Pressure, Fluidic | Read | ||
| AI | 10175 | Entering Evaporator Water Gauge Pressure | Pressure, Fluidic | Read | ||
| AI | 10176 | Evaporator Refrigerant Gauge Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10177 | Leaving Condenser Water Gauge Pressure | Pressure, Fluidic | Read | ||
| AI | 10178 | Leaving Evaporator Water Gauge Pressure | Pressure, Fluidic | Read | ||
| AI | 10179 | Drive Motor Average Current RLA Circuit 2 | Percentage | Read | ||
| AI | 10180 | Drive Motor Voltage Circuit 2 | Voltage | Read | ||
| AI | 10181 | Drive DC Bus Voltage Circuit 2 | Voltage | Read | ||
| AI | 10182 | AFD Frequency Circuit 2 | Read | |||
| AI | 10183 | AFD Transistor Temperature Circuit 2 | Temperature | Read | ||
| AI | 10184 | Drive Motor Current U Circuit 2 | Current | Read | ||
| AI | 10185 | Drive Motor Current U RLA Circuit 2 | Percentage | Read | ||
| AI | 10186 | Drive Motor Current V Circuit 2 | Current | Read | ||
| AI | 10187 | Drive Motor Current V RLA Circuit 2 | Percentage | Read | ||
| AI | 10188 | Drive Motor Current W Circuit 2 | Current | Read | ||
| AI | 10189 | Drive Motor Current W RLA Circuit 2 | Percentage | Read | ||
| AI | 10190 | Drive Output Power Circuit 2 | Power, Electrical | Read | ||
| AI | 10191 | Drive Speed Status Percent Circuit 2 | Percentage | Read | ||
| AI | 10192 | Compressor Bearing Temperature 1 - Compressor 2A | Temperature | Read | ||
| AI | 10193 | Compressor Bearing Temperature 2 - Compressor 2A | Temperature | Read | ||
| AI | 10194 | Refrigerant Discharge Temperature - Compressor 2A | Temperature | Read | ||
| AI | 10195 | Run Time - Compressor 2A | Read | |||
| AI | 10196 | Starts - Compressor 2A | Read | |||
| AI | 10197 | Condenser Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10198 | Condenser Saturated Refrigerant Temperature Circuit 2 | Temperature | Read | ||
| AI | 10199 | Differential Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10200 | Evaporator Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10201 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Temperature | Read | ||
| AI | 10202 | Inlet Guide Vane 1 Percent Open Circuit 2 | Percentage | Read | ||
| AI | 10203 | Motor Winding Temperature 1 Circuit 2 | Temperature | Read | ||
| AI | 10204 | Motor Winding Temperature 2 Circuit 2 | Temperature | Read | ||
| AI | 10205 | Motor Winding Temperature 3 Circuit 2 | Temperature | Read | ||
| AI | 10206 | Drive Input Voltage Calculated 2A | Voltage | Read | ||
| AI | 10215 | Condenser Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10216 | Evaporator Approach Temperature Circuit 2 | Temperature, Delta | Read | ||
| AI | 10217 | Condenser Refrigerant Gauge Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10218 | Evaporator Refrigerant Gauge Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10319 | Active Cooling Differential to Start | Temperature, Delta | Read | ||
| AI | 10320 | Active Cooling Differential to Stop | Temperature, Delta | Read | ||
| AI | 10321 | Active Heating Differential to Start | Temperature, Delta | Read | ||
| AI | 10322 | Active Heating Differential to Stop | Temperature, Delta | Read | ||
| AI | 10323 | Discharge Superheat Compressor 1A | Temperature, Delta | Read | ||
| AI | 10324 | Discharge Superheat Compressor 2A | Temperature, Delta | Read | ||
| AVmin | 10100 | Chilled Water Setpoint | Temperature | Write | ||
| AVmin | 10101 | Demand Limit Setpoint | Percentage | Write | ||
| AV | 10102 | Hot Water Setpoint | Temperature | Write | ||
| AV | 10103 | Base Loading Setpoint | Percentage | Write | ||
| AV | 10104 | BAS Cooling Differential to Start | Temperature, Delta | Write | ||
| AV | 10105 | BAS Cooling Differential to Stop | Temperature, Delta | Write | ||
| AV | 10106 | BAS Heating Differential to Start | Temperature, Delta | Write | ||
| AV | 10107 | BAS Heating Differential to Stop | Temperature, Delta | Write | ||
| BImin | 10100 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10101 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10102 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10103 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10104 | Diagnostic Present: Information | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10105 | Diagnostic Present: Advisory | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10106 | Diagnostic Present: Critical | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10107 | Diagnostic Present: Service Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10108 | Base Loading Active | Read | 0 = Inactive, 1 = Active | ||
| BImin | 10109 | Chiller Running State | Read | 0 = Off, 1 = On | ||
| BI | 10110 | Condenser Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BI | 10111 | Condenser Water Pump Request | Read | 0 = Off, 1 = On | ||
| BI | 10112 | Emergency Stop | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | ||
| BI | 10113 | Evaporator Water Flow Status | Read | 0 = No Flow, 1 = Flow | ||
| BI | 10114 | Evaporator Water Pump Request | Read | 0 = Off, 1 = On | ||
| BI | 10115 | Base Loading Request Active | Read | 0 = Off, 1 = On | ||
| BI | 10116 | Head Relief Request | Read | 0 = Off, 1 = On | ||
| BI | 10117 | Limit Mode Relay Status | Read | 0 = Off, 1 = On | ||
| BImin | 10118 | Local Setpoint Control | Read | 0 = Remote Control, 1 = Local Control | ||
| BI | 10119 | Manual Override Exists | Read | 0 = Off, 1 = On | ||
| BI | 10120 | Maximum Capacity | Read | 0 = Off, 1 = On | ||
| BI | 10121 | Run Enabled | Read | 0 = Run Not Enabled, 1 = Run Enabled | ||
| BI | 10122 | Compressor 1A Status | Read | 0 = Off, 1 = Running | ||
| BI | 10123 | Front Panel Auto Stop | Read | 0 = Stop, 1 = Auto | ||
| BI | 10124 | External Auto Stop Input Status | Read | 0 = Stop, 1 = Auto | ||
| BI | 10125 | Compressor 2A Status | Read | 0 = Off, 1 = Running | ||
| BI | 11000 | Comm Loss: Ext Base Loading Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Comm Loss: Ext Base Loading Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Diagnostic: External Base Loading Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Comm Loss: Energy Meter | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Diagnostic: Energy Meter Write Command Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Diagnostic: Software Error 1001: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Diagnostic: Software Error 1002: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Diagnostic: Software Error 1003: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Comm Loss: Condenser Liquid Level Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Comm Loss: Condenser Rfgt Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Comm Loss: Drive Cooling Supply Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Comm Loss: Drive Cooling Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Comm Loss: Evaporator Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Diagnostic: Condenser Liquid Level Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Diagnostic: Condenser Refrigerant Pressure Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Diagnostic: Drive Cooling Supply Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Diagnostic: Evaporator Refrigerant Pressure Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Diagnostic: High Condenser Liquid Level Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Diagnostic: Low Condenser Liquid Level Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Diagnostic: Inverted Condenser Approach Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Diagnostic: Inverted Evaporator Approach Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Diagnostic: Loss of Drive Cooling Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Diagnostic: Loss of Evaporator EXV Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Comm Loss: Economizer Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Comm Loss: Economizer Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Comm Loss: Economizer Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Comm Loss: IGV First Stage Actuator Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Comm Loss: Interstage Bypass Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Diagnostic: Compressor Refrigerant Discharge Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Diagnostic: Economizer Pressure Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Diagnostic: Economizer Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Diagnostic: Extended Compressor Surge Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11036 | Diagnostic: Condenser Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11037 | Diagnostic: Condenser Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Diagnostic: High Condenser Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Comm Loss: Condenser Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Comm Loss: Condenser Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Comm Loss: Condenser Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Comm Loss: Condenser Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Comm Loss: Condenser Water Flow Measurement Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Comm Loss: Condenser Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Comm Loss: Condenser Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Diagnostic: Condenser Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Diagnostic: Condenser Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Diagnostic: Condenser Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Diagnostic: Condenser Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Diagnostic: Condenser Water Flow Measurement Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Diagnostic: Inverted Condenser Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Diagnostic: High Evaporator Refrigerant Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Diagnostic: Low Evaporator Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Comm Loss: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Comm Loss: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Comm Loss: Evaporator Water Flow Measurement Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Comm Loss: Evaporator Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Diagnostic: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Diagnostic: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Diagnostic: Evaporator Water Flow Measurement Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Diagnostic: Low Evap Leaving Water Temp: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Diagnostic: Low Evap Leaving Water Temp: Unit On | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Comm Loss: Evaporator EXV Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Comm Loss: Chiller % Capacity Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Comm Loss: Condenser Rfgt Pressure Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Comm Loss: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Comm Loss: External Hot Water Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Diagnostic: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: Refrigerant Monitor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Diagnostic: Refrigerant Monitor Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Comm Loss: Ice Building Status Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Diagnostic: MBC Bearing Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Diagnostic: MBC Bearing Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Diagnostic: MBC Failed Centering Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: MBC Cooling Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Comm Loss: Magnetic Bearing Controller Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Comm Loss: UPS Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Diagnostic: Loss of MBC Cooling Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11096 | Diagnostic: MBC Not Centered Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Diagnostic: MBC Not Ready To Rotate Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Diagnostic: MBC Over Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Diagnostic: MBC Parameter Table Not Set Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Diagnostic: MBC Rotor Elongation Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Diagnostic: MBC Rotor Unbalance Alarm Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Diagnostic: MBC: Shutdown Request Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Diagnostic: MBC Under Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Diagnostic: MBC Overspeed Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Diagnostic: MBC PCB Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Diagnostic: MBC Rotation Detected Without Levitation Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Diagnostic: MBC Speed Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Diagnostic: UPS Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11109 | Comm Loss: Motor Cooling Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11110 | Comm Loss: Motor Winding Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11111 | Comm Loss: Motor Winding Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Comm Loss: Motor Winding Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Diagnostic: High Compressor Refrigerant Discharge Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Diagnostic: High Motor Winding Temperature 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Diagnostic: High Motor Winding Temperature 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Diagnostic: High Motor Winding Temperature 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Diagnostic: High Vacuum Lockout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Diagnostic: Loss of Motor Cooling Control Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Diagnostic: AFD Comm Loss: Main Processor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Diagnostic: AFD Failure to Arm or Start Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Diagnostic: AFD Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Diagnostic: AFD Ground Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Diagnostic: AFD Interrupt Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Diagnostic: AFD Mains Failure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Diagnostic: AFD Motor Current Overload Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Diagnostic: AFD Safe Stop Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Diagnostic: AFD Short Circuit Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Diagnostic: AFD Speed Configuration Mismatch Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Comm Loss: Adaptive Frequency Drive Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Diagnostic: Unexpected Starter Shutdown Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Diagnostic: Software Error 1005: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Starter Panel High Temp Limit Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Diagnostic: Starter Panel High Temp Limit Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Subcooled Liquid Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: External Ckt Lockout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Diagnostic: Subcooled Liquid Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Diagnostic: Evaporator Saturated Refrigerant Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Evap Saturated Rfgt Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Diagnostic: Low Suction Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Diagnostic: High Differential Refrigerant Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Diagnostic: High Refrigerant Pressure Ratio Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Diagnostic: Starts/Hours Modified Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Diagnostic: Starts/Hours Modified Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Comm Loss: Off-cycle Freeze Protection Relay Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Comm Loss: Condenser Head Pressure Cntrl Output Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Comm Loss: Ext Noise Reduction Request Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Diagnostic: MBC Failed Clearance Check Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Diagnostic: Check Clock | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Diagnostic: MP: Non-Volatile Block Test Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Diagnostic: Under Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Diagnostic: Over Voltage Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Compressor 2A Status | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Comm Loss: Condenser Liquid Level Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Comm Loss: Condenser Rfgt Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Comm Loss: Drive Cooling Supply Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Comm Loss: Drive Cooling Supply Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Comm Loss: Drive Cooling Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Comm Loss: Evaporator Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Diagnostic: Condenser Liquid Level Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Diagnostic: Condenser Refrigerant Pressure Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Diagnostic: Drive Cooling Supply Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Diagnostic: Evaporator Refrigerant Pressure Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Diagnostic: High Condenser Liquid Level Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Diagnostic: Low Condenser Liquid Level Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Diagnostic: Loss of Drive Cooling Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Diagnostic: Loss of Evaporator EXV Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Comm Loss: Economizer Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Comm Loss: Economizer Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Comm Loss: Economizer Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Comm Loss: IGV First Stage Actuator Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Comm Loss: Interstage Bypass Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Diagnostic: Compressor Refrigerant Discharge Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Diagnostic: Economizer Pressure Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Diagnostic: Economizer Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Diagnostic: Extended Compressor Surge Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Diagnostic: High Condenser Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Comm Loss: Evaporator EXV Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Diagnostic: MBC Bearing Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Diagnostic: MBC Bearing Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Diagnostic: MBC Failed Centering Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Comm Loss: MBC Cooling Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Comm Loss: Magnetic Bearing Controller Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Comm Loss: UPS Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: Loss of MBC Cooling Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: MBC Not Centered Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Diagnostic: MBC Not Ready To Rotate Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Diagnostic: MBC Over Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: MBC Parameter Table Not Set Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: MBC Rotor Elongation Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: MBC Rotor Unbalance Alarm Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: MBC: Shutdown Request Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: MBC Under Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Diagnostic: MBC Overspeed Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Diagnostic: MBC PCB Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Diagnostic: MBC Rotation Detected Without Levitation Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Diagnostic: MBC Speed Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11205 | Diagnostic: UPS Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Comm Loss: Motor Cooling Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Comm Loss: Motor Winding Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Comm Loss: Motor Winding Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Comm Loss: Motor Winding Temperature 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: High Compressor Refrigerant Discharge Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Diagnostic: High Motor Winding Temperature 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Diagnostic: High Motor Winding Temperature 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Diagnostic: High Motor Winding Temperature 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Diagnostic: High Vacuum Lockout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Diagnostic: Loss of Motor Cooling Control Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11219 | Diagnostic: AFD Comm Loss: Main Processor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11220 | Diagnostic: AFD Failure to Arm or Start Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: AFD Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: AFD Ground Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: AFD Interrupt Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: AFD Mains Failure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: AFD Motor Current Overload Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11226 | Diagnostic: AFD Safe Stop Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11227 | Diagnostic: AFD Short Circuit Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11228 | Diagnostic: AFD Speed Configuration Mismatch Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11229 | Comm Loss: Adaptive Frequency Drive Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: Unexpected Starter Shutdown Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Comm Loss: Starter Panel High Temp Limit Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: Starter Panel High Temp Limit Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Comm Loss: Subcooled Liquid Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Comm Loss: External Ckt Lockout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: Subcooled Liquid Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: Evaporator Saturated Refrigerant Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Comm Loss: Evap Saturated Rfgt Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: Low Suction Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: High Differential Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: High Refrigerant Pressure Ratio Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Comm Loss: Off-cycle Freeze Protection Relay Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Comm Loss: Condenser Head Pressure Cntrl Output Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11244 | Comm Loss: Ext Noise Reduction Request Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11245 | Diagnostic: MBC Failed Clearance Check Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11246 | Diagnostic: Under Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11247 | Diagnostic: Over Voltage Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11248 | Comm Loss: IGV Second Stage Actuator Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11249 | Comm Loss: IGV Second Stage Actuator Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11250 | Comm Loss: Condenser Liquid Line Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11251 | Diagnostic: Condenser Liquid Line Temperature Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11252 | Comm Loss: Condenser Liquid Line Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11253 | Diagnostic: Condenser Liquid Line Temperature Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11254 | Diagnostic: High Evaporator Refrigerant Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11255 | Diagnostic: Inverted Condenser Approach Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11256 | Diagnostic: Inverted Evaporator Approach Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BV | 10100 | Base Loading Request | Write | 0 = Off, 1 = On | ||
| BV | 10101 | Reset Diagnostic | Write | 0 = Normal, 1 = Reset | ||
| BVmin | 10102 | Chiller Auto Stop Command BAS | Write | 0 = Stop, 1 = Auto | ||
| BV | 10103 | Energy Consumption Reset | Write | 0 = Accumulating, 1 = Reset | ||
| BV | 10104 | Evaporator Water Pump Request BAS | Write | 1 = Auto, 1 = On | ||
| BV | 10105 | Condenser Water Pump Request BAS | Write | 1 = Auto, 1 = On | ||
| BV | 10106 | Circuit 1 Lockout BAS | Write | 1 = Auto, 1 = On | ||
| BV | 10107 | Circuit 2 Lockout BAS | Write | 1 = Auto, 1 = On | ||
| MI | 10100 | Operating Mode | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | ||
| MI | 10101 | Running Mode | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | ||
| MI | 10102 | Manufacturing Location | Read | 2 = La Crosse | ||
| MI | 10103 | Chiller Setpoint Source | Read | 1 = BAS, 2 = External, 3 = Front Panel | ||
| MI | 10104 | Refrigerant Type | Read | 5 = R-134a, 13 = R-513A, 16 = R-1234ze(E), 18 = R-515B | ||
| MI | 10105 | Cooling Type | Read | 1 = Water Cooled | ||
| MI | 10106 | Model Information [GEN2] | Read | 25 = HDWA, 66 = HDDA | ||
| MVmin | 10100 | Chiller Mode Command BAS | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Object ID lookup: Trane Symbio 800 Agility point IDs by name
AI10100Active Chilled Water SetpointAI10101Active Base Loading SetpointAI10102Active Cool/Heat Setpoint TemperatureAI10103Active Hot Water SetpointAI10104Active Demand Limit SetpointAI10105Demand Limit Setpoint StatusAI10106Chilled Water Setpoint StatusAI10107Drive Motor Average Current RLA Circuit 1AI10108Drive Motor VoltageAI10109Drive DC Bus Voltage Circuit 1AI10110AFD Frequency Circuit 1AI10111AFD Transistor Temperature Circuit 1AI10112Drive Motor Current U Circuit 1AI10113Drive Motor Current U RLA Circuit 1AI10114Drive Motor Current V Circuit 1AI10115Drive Motor Current V RLA Circuit 1AI10116Drive Motor Current W Circuit 1AI10117Drive Motor Current W RLA Circuit 1AI10118Drive Output Power Circuit 1AI10119Drive Speed Status PercentAI10120Condenser Water Flow RateAI10121Evaporator Water Flow RateAI10122Calculated Chiller CapacityAI10123Compressor Bearing Temperature 1 - Compressor 1AAI10124Compressor Bearing Temperature 2 - Compressor 1AAI10125Refrigerant Discharge Temperature - Compressor 1AAI10126Run Time - Compressor 1A (in seconds)AI10127Starts - Compressor 1AAI10128Condenser Differential Water PressureAI10129Condenser Entering Water TemperatureAI10130Condenser Leaving Water TemperatureAI10131Condenser Refrigerant Pressure Circuit 1AI10132Condenser Saturated Refrigerant Temperature Circuit 1AI10133Differential Refrigerant Pressure Circuit 1AI10134Evaporator Differential Water PressureAI10135Evaporator Entering Water TemperatureAI10136Evaporator Leaving Water TemperatureAI10137Evaporator Refrigerant Pressure Circuit 1AI10138Evaporator Saturated Refrigerant Temperature Circuit 1AI10139Entering Condenser Water PressureAI10140Leaving Condenser Water PressureAI10141Entering Evaporator Water PressureAI10142Leaving Evaporator Water PressureAI10143Inlet Guide Vane 1 Percent Open Circuit 1AI10144Motor Winding Temperature 1 Circuit 1AI10145Motor Winding Temperature 2 Circuit 1AI10146Motor Winding Temperature 3 Circuit 1AI10147Number of CircuitsAI10148Number of Compressors Circuit 1AI10149Number of Compressors Circuit 2AI10150Refrigerant MonitorAI10151Unit Power ConsumptionAI10152Drive Input Voltage Calculated 1AAI10153Actual Running CapacityAI10154Unit Source IDAI10155Chiller Design CapacityAI10156Outdoor Air TemperatureAI10157Energy Consumption LifetimeAI10158Energy ConsumptionAI10159Unit Power DemandAI10160Voltage L1-L2AI10161Voltage L2-L3AI10162Voltage L1-L3AI10163Current L1AI10164Current L2AI10165Current L3AI10166Line FrequencyAI10167Power FactorAI10168Condenser Control OutputAI10169Average Voltage L-LAI10170Average CurrentAI10171Condenser Approach Temperature Circuit 1AI10172Evaporator Approach Temperature Circuit 1AI10173Condenser Refrigerant Gauge Pressure Circuit 1AI10174Entering Condenser Water Gauge PressureAI10175Entering Evaporator Water Gauge PressureAI10176Evaporator Refrigerant Gauge Pressure Circuit 1AI10177Leaving Condenser Water Gauge PressureAI10178Leaving Evaporator Water Gauge PressureAI10179Drive Motor Average Current RLA Circuit 2AI10180Drive Motor Voltage Circuit 2AI10181Drive DC Bus Voltage Circuit 2AI10182AFD Frequency Circuit 2AI10183AFD Transistor Temperature Circuit 2AI10184Drive Motor Current U Circuit 2AI10185Drive Motor Current U RLA Circuit 2AI10186Drive Motor Current V Circuit 2AI10187Drive Motor Current V RLA Circuit 2AI10188Drive Motor Current W Circuit 2AI10189Drive Motor Current W RLA Circuit 2AI10190Drive Output Power Circuit 2AI10191Drive Speed Status Percent Circuit 2AI10192Compressor Bearing Temperature 1 - Compressor 2AAI10193Compressor Bearing Temperature 2 - Compressor 2AAI10194Refrigerant Discharge Temperature - Compressor 2AAI10195Run Time - Compressor 2AAI10196Starts - Compressor 2AAI10197Condenser Refrigerant Pressure Circuit 2AI10198Condenser Saturated Refrigerant Temperature Circuit 2AI10199Differential Refrigerant Pressure Circuit 2AI10200Evaporator Refrigerant Pressure Circuit 2AI10201Evaporator Saturated Refrigerant Temperature Circuit 2AI10202Inlet Guide Vane 1 Percent Open Circuit 2AI10203Motor Winding Temperature 1 Circuit 2AI10204Motor Winding Temperature 2 Circuit 2AI10205Motor Winding Temperature 3 Circuit 2AI10206Drive Input Voltage Calculated 2AAI10215Condenser Approach Temperature Circuit 2AI10216Evaporator Approach Temperature Circuit 2AI10217Condenser Refrigerant Gauge Pressure Circuit 2AI10218Evaporator Refrigerant Gauge Pressure Circuit 2AI10319Active Cooling Differential to StartAI10320Active Cooling Differential to StopAI10321Active Heating Differential to StartAI10322Active Heating Differential to StopAI10323Discharge Superheat Compressor 1AAI10324Discharge Superheat Compressor 2AAV10100Chilled Water SetpointAV10101Demand Limit SetpointAV10102Hot Water SetpointAV10103Base Loading SetpointAV10104BAS Cooling Differential to StartAV10105BAS Cooling Differential to StopAV10106BAS Heating Differential to StartAV10107BAS Heating Differential to StopBI10100Diagnostic PresentBI10101Diagnostic Shutdown PresentBI10102Diagnostic: Manual Reset RequiredBI10103Diagnostic: Local Manual Reset RequiredBI10104Diagnostic Present: InformationBI10105Diagnostic Present: AdvisoryBI10106Diagnostic Present: CriticalBI10107Diagnostic Present: Service RequiredBI10108Base Loading ActiveBI10109Chiller Running StateBI10110Condenser Water Flow StatusBI10111Condenser Water Pump RequestBI10112Emergency StopBI10113Evaporator Water Flow StatusBI10114Evaporator Water Pump RequestBI10115Base Loading Request ActiveBI10116Head Relief RequestBI10117Limit Mode Relay StatusBI10118Local Setpoint ControlBI10119Manual Override ExistsBI10120Maximum CapacityBI10121Run EnabledBI10122Compressor 1A StatusBI10123Front Panel Auto StopBI10124External Auto Stop Input StatusBI10125Compressor 2A StatusBI11000Comm Loss: Ext Base Loading CommandBI11001Comm Loss: Ext Base Loading SetpointBI11002Diagnostic: External Base Loading SetpointBI11003Comm Loss: Energy MeterBI11004Comm Loss: Outdoor Air TemperatureBI11005Diagnostic: Energy Meter Write Command FailureBI11006Diagnostic: Outdoor Air Temperature SensorBI11007Diagnostic: Software Error 1001: Call Trane ServiceBI11008Diagnostic: Software Error 1002: Call Trane ServiceBI11009Diagnostic: Software Error 1003: Call Trane ServiceBI11010Comm Loss: Condenser Liquid Level Sensor Circuit 1BI11011Comm Loss: Condenser Rfgt Pressure Circuit 1BI11012Comm Loss: Drive Cooling Supply Temperature Circuit 1BI11013Comm Loss: Drive Cooling Valve Circuit 1BI11014Comm Loss: Evaporator Refrigerant Pressure Circuit 1BI11015Diagnostic: Condenser Liquid Level Sensor Circuit 1BI11016Diagnostic: Condenser Refrigerant Pressure Sensor Circuit 1BI11017Diagnostic: Drive Cooling Supply Temperature Sensor Circuit 1BI11018Diagnostic: Evaporator Refrigerant Pressure Sensor Circuit 1BI11019Diagnostic: High Condenser Liquid Level Circuit 1BI11020Diagnostic: Low Condenser Liquid Level Circuit 1BI11021Diagnostic: Inverted Condenser Approach TemperatureBI11022Diagnostic: Inverted Evaporator Approach TemperatureBI11023Diagnostic: Loss of Drive Cooling Control Circuit 1BI11024Diagnostic: Loss of Evaporator EXV Control Circuit 1BI11025Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1BI11026Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1BI11027Comm Loss: Economizer Valve Circuit 1BI11028Comm Loss: Economizer Pressure Circuit 1BI11029Comm Loss: Economizer Temperature Circuit 1BI11030Comm Loss: IGV First Stage Actuator Circuit 1BI11031Comm Loss: Interstage Bypass Valve Circuit 1BI11032Diagnostic: Compressor Refrigerant Discharge Temperature Sensor Circuit 1BI11033Diagnostic: Economizer Pressure Sensor Circuit 1BI11034Diagnostic: Economizer Temperature Sensor Circuit 1BI11035Diagnostic: Extended Compressor Surge Circuit 1BI11036Diagnostic: Condenser Water Flow LostBI11037Diagnostic: Condenser Water Flow OverdueBI11038Diagnostic: High Condenser Pressure Circuit 1BI11039Comm Loss: Condenser Entering Water PressureBI11040Comm Loss: Condenser Entering Water TempBI11041Comm Loss: Condenser Leaving Water PressureBI11042Comm Loss: Condenser Leaving Water TempBI11043Comm Loss: Condenser Water Flow Measurement SensorBI11044Comm Loss: Condenser Water Flow SwitchBI11045Comm Loss: Condenser Water Pump RelayBI11046Diagnostic: Condenser Entering Water PressureBI11047Diagnostic: Condenser Entering Water Temp SensorBI11048Diagnostic: Condenser Leaving Water PressureBI11049Diagnostic: Condenser Leaving Water Temp SensorBI11050Diagnostic: Condenser Water Flow Measurement SensorBI11051Diagnostic: Inverted Condenser Water TemperatureBI11052Diagnostic: Evaporator Water Flow LostBI11053Diagnostic: Evaporator Water Flow OverdueBI11054Diagnostic: High Evaporator Refrigerant PressureBI11055Diagnostic: High Evaporator Water TemperatureBI11056Diagnostic: Low Evaporator Water FlowBI11057Comm Loss: Evap Entering Water TempBI11058Comm Loss: Evap Leaving Water TempBI11059Comm Loss: Evaporator Entering Water PressureBI11060Comm Loss: Evaporator Leaving Water PressureBI11061Comm Loss: Evaporator Water Flow Measurement SensorBI11062Comm Loss: Evaporator Water Flow SwitchBI11063Comm Loss: Evaporator Water Pump RelayBI11064Diagnostic: Evaporator Entering Water PressureBI11065Diagnostic: Evaporator Entering Water Temp SensorBI11066Diagnostic: Evaporator Leaving Water PressureBI11067Diagnostic: Evaporator Leaving Water Temp SensorBI11068Diagnostic: Evaporator Water Flow Measurement SensorBI11069Diagnostic: Inverted Evaporator Water TemperatureBI11070Diagnostic: Low Evap Leaving Water Temp: Unit OffBI11071Diagnostic: Low Evap Leaving Water Temp: Unit OnBI11072Comm Loss: Evaporator EXV Circuit 1BI11073Comm Loss: Chiller % Capacity OutputBI11074Comm Loss: Condenser Rfgt Pressure OutputBI11075Comm Loss: Emergency StopBI11076Comm Loss: Ext Chilled/Hot Water SetpointBI11077Comm Loss: Ext Demand Limit SetpointBI11078Comm Loss: External Auto/StopBI11079Comm Loss: External Hot Water CommandBI11080Comm Loss: Programmable Relay Board 1BI11081Comm Loss: Programmable Relay Board 2BI11082Diagnostic: Emergency StopBI11083Diagnostic: External Chilled/Hot Water SetpointBI11084Diagnostic: External Demand Limit SetpointBI11085Comm Loss: Refrigerant Monitor InputBI11086Diagnostic: Refrigerant Monitor InputBI11087Comm Loss: External Ice Building CommandBI11088Comm Loss: Ice Building Status RelayBI11089Diagnostic: MBC Bearing Temperature 1 Circuit 1BI11090Diagnostic: MBC Bearing Temperature 2 Circuit 1BI11091Diagnostic: MBC Failed Centering Circuit 1BI11092Comm Loss: MBC Cooling Valve Circuit 1BI11093Comm Loss: Magnetic Bearing Controller Circuit 1BI11094Comm Loss: UPS Fault Circuit 1BI11095Diagnostic: Loss of MBC Cooling Control Circuit 1BI11096Diagnostic: MBC Not Centered Circuit 1BI11097Diagnostic: MBC Not Ready To Rotate Circuit 1BI11098Diagnostic: MBC Over Voltage Circuit 1BI11099Diagnostic: MBC Parameter Table Not Set Circuit 1BI11100Diagnostic: MBC Rotor Elongation Circuit 1BI11101Diagnostic: MBC Rotor Unbalance Alarm Circuit 1BI11102Diagnostic: MBC: Shutdown Request Circuit 1BI11103Diagnostic: MBC Under Voltage Circuit 1BI11104Diagnostic: MBC Overspeed Circuit 1BI11105Diagnostic: MBC PCB Temperature Circuit 1BI11106Diagnostic: MBC Rotation Detected Without Levitation Circuit 1BI11107Diagnostic: MBC Speed Sensor Circuit 1BI11108Diagnostic: UPS Fault Circuit 1BI11109Comm Loss: Motor Cooling Valve Circuit 1BI11110Comm Loss: Motor Winding Temperature 1 Circuit 1BI11111Comm Loss: Motor Winding Temperature 2 Circuit 1BI11112Comm Loss: Motor Winding Temperature 3 Circuit 1BI11113Diagnostic: High Compressor Refrigerant Discharge Temperature Circuit 1BI11114Diagnostic: High Motor Winding Temperature 1 Circuit 1BI11115Diagnostic: High Motor Winding Temperature 2 Circuit 1BI11116Diagnostic: High Motor Winding Temperature 3 Circuit 1BI11117Diagnostic: High Vacuum Lockout Circuit 1BI11118Diagnostic: Loss of Motor Cooling Control Circuit 1BI11119Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1BI11120Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1BI11121Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1BI11122Diagnostic: MP: Invalid ConfigurationBI11123Diagnostic: MP: Reset Has OccurredBI11124Diagnostic: AFD Comm Loss: Main Processor Circuit 1BI11125Diagnostic: AFD Failure to Arm or Start Circuit 1BI11126Diagnostic: AFD Fault Circuit 1BI11127Diagnostic: AFD Ground Fault Circuit 1BI11128Diagnostic: AFD Interrupt Failure Circuit 1BI11129Diagnostic: AFD Mains Failure Circuit 1BI11130Diagnostic: AFD Motor Current Overload Circuit 1BI11131Diagnostic: AFD Safe Stop Circuit 1BI11132Diagnostic: AFD Short Circuit Circuit 1BI11133Diagnostic: AFD Speed Configuration Mismatch Circuit 1BI11134Comm Loss: Adaptive Frequency Drive Circuit 1BI11135Diagnostic: Unexpected Starter Shutdown Circuit 1BI11136Diagnostic: Software Error 1005: Call Trane ServiceBI11137Comm Loss: Starter Panel High Temp Limit Compressor 1ABI11138Diagnostic: Starter Panel High Temp Limit Compressor 1ABI11139Comm Loss: Subcooled Liquid Temp Circuit 1BI11140Comm Loss: External Ckt Lockout Circuit 1BI11141Diagnostic: Subcooled Liquid Temperature Sensor Circuit 1BI11142Diagnostic: Evaporator Saturated Refrigerant Temp Sensor Circuit 1BI11143Comm Loss: Evap Saturated Rfgt Temp Circuit 1BI11144Diagnostic: Low Suction Refrigerant Pressure Circuit 1BI11145Diagnostic: High Differential Refrigerant Pressure Circuit 1BI11146Diagnostic: High Refrigerant Pressure Ratio Circuit 1BI11147Diagnostic: Starts/Hours Modified Compressor 1ABI11148Diagnostic: Starts/Hours Modified Compressor 2ABI11149Diagnostic: High Evaporator Refrigerant Temperature Circuit 1BI11150Comm Loss: Off-cycle Freeze Protection Relay Circuit 1BI11151Comm Loss: Condenser Head Pressure Cntrl Output Circuit 1BI11152Comm Loss: Ext Noise Reduction Request Circuit 1BI11153Diagnostic: MBC Failed Clearance Check Circuit 1BI11154Diagnostic: Check ClockBI11155Diagnostic: MP: Non-Volatile Block Test ErrorBI11156Diagnostic: Under Voltage Circuit 1BI11157Diagnostic: Over Voltage Circuit 1BI11158Compressor 2A StatusBI11159Comm Loss: Condenser Liquid Level Sensor Circuit 2BI11160Comm Loss: Condenser Rfgt Pressure Circuit 2BI11161Comm Loss: Drive Cooling Supply Temperature Circuit 2BI11162Comm Loss: Drive Cooling Supply Temperature Circuit 2BI11163Comm Loss: Drive Cooling Valve Circuit 2BI11164Comm Loss: Evaporator Refrigerant Pressure Circuit 2BI11165Diagnostic: Condenser Liquid Level Sensor Circuit 2BI11166Diagnostic: Condenser Refrigerant Pressure Sensor Circuit 2BI11167Diagnostic: Drive Cooling Supply Temperature Sensor Circuit 2BI11168Diagnostic: Evaporator Refrigerant Pressure Sensor Circuit 2BI11169Diagnostic: High Condenser Liquid Level Circuit 2BI11170Diagnostic: Low Condenser Liquid Level Circuit 2BI11171Diagnostic: Loss of Drive Cooling Control Circuit 2BI11172Diagnostic: Loss of Evaporator EXV Control Circuit 2BI11173Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2BI11174Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2BI11175Comm Loss: Economizer Valve Circuit 2BI11176Comm Loss: Economizer Pressure Circuit 2BI11177Comm Loss: Economizer Temperature Circuit 2BI11178Comm Loss: IGV First Stage Actuator Circuit 2BI11179Comm Loss: Interstage Bypass Valve Circuit 2BI11180Diagnostic: Compressor Refrigerant Discharge Temperature Sensor Circuit 2BI11181Diagnostic: Economizer Pressure Sensor Circuit 2BI11182Diagnostic: Economizer Temperature Sensor Circuit 2BI11183Diagnostic: Extended Compressor Surge Circuit 2BI11184Diagnostic: High Condenser Pressure Circuit 2BI11185Comm Loss: Evaporator EXV Circuit 2BI11186Diagnostic: MBC Bearing Temperature 1 Circuit 2BI11187Diagnostic: MBC Bearing Temperature 2 Circuit 2BI11188Diagnostic: MBC Failed Centering Circuit 2BI11189Comm Loss: MBC Cooling Valve Circuit 2BI11190Comm Loss: Magnetic Bearing Controller Circuit 2BI11191Comm Loss: UPS Fault Circuit 2BI11192Diagnostic: Loss of MBC Cooling Control Circuit 2BI11193Diagnostic: MBC Not Centered Circuit 2BI11194Diagnostic: MBC Not Ready To Rotate Circuit 2BI11195Diagnostic: MBC Over Voltage Circuit 2BI11196Diagnostic: MBC Parameter Table Not Set Circuit 2BI11197Diagnostic: MBC Rotor Elongation Circuit 2BI11198Diagnostic: MBC Rotor Unbalance Alarm Circuit 2BI11199Diagnostic: MBC: Shutdown Request Circuit 2BI11200Diagnostic: MBC Under Voltage Circuit 2BI11201Diagnostic: MBC Overspeed Circuit 2BI11202Diagnostic: MBC PCB Temperature Circuit 2BI11203Diagnostic: MBC Rotation Detected Without Levitation Circuit 2BI11204Diagnostic: MBC Speed Sensor Circuit 2BI11205Diagnostic: UPS Fault Circuit 2BI11206Comm Loss: Motor Cooling Valve Circuit 2BI11207Comm Loss: Motor Winding Temperature 1 Circuit 2BI11208Comm Loss: Motor Winding Temperature 2 Circuit 2BI11209Comm Loss: Motor Winding Temperature 3 Circuit 2BI11210Diagnostic: High Compressor Refrigerant Discharge Temperature Circuit 2BI11211Diagnostic: High Motor Winding Temperature 1 Circuit 2BI11212Diagnostic: High Motor Winding Temperature 2 Circuit 2BI11213Diagnostic: High Motor Winding Temperature 3 Circuit 2BI11214Diagnostic: High Vacuum Lockout Circuit 2BI11215Diagnostic: Loss of Motor Cooling Control Circuit 2BI11216Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2BI11217Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2BI11218Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2BI11219Diagnostic: AFD Comm Loss: Main Processor Circuit 2BI11220Diagnostic: AFD Failure to Arm or Start Circuit 2BI11221Diagnostic: AFD Fault Circuit 2BI11222Diagnostic: AFD Ground Fault Circuit 2BI11223Diagnostic: AFD Interrupt Failure Circuit 2BI11224Diagnostic: AFD Mains Failure Circuit 2BI11225Diagnostic: AFD Motor Current Overload Circuit 2BI11226Diagnostic: AFD Safe Stop Circuit 2BI11227Diagnostic: AFD Short Circuit Circuit 2BI11228Diagnostic: AFD Speed Configuration Mismatch Circuit 2BI11229Comm Loss: Adaptive Frequency Drive Circuit 2BI11230Diagnostic: Unexpected Starter Shutdown Circuit 2BI11231Comm Loss: Starter Panel High Temp Limit Compressor 2ABI11232Diagnostic: Starter Panel High Temp Limit Compressor 2ABI11233Comm Loss: Subcooled Liquid Temp Circuit 2BI11234Comm Loss: External Ckt Lockout Circuit 2BI11235Diagnostic: Subcooled Liquid Temperature Sensor Circuit 2BI11236Diagnostic: Evaporator Saturated Refrigerant Temp Sensor Circuit 2BI11237Comm Loss: Evap Saturated Rfgt Temp Circuit 2BI11238Diagnostic: Low Suction Refrigerant Pressure Circuit 2BI11239Diagnostic: High Differential Refrigerant Pressure Circuit 2BI11240Diagnostic: High Refrigerant Pressure Ratio Circuit 2BI11241Diagnostic: High Evaporator Refrigerant Temperature Circuit 2BI11242Comm Loss: Off-cycle Freeze Protection Relay Circuit 2BI11243Comm Loss: Condenser Head Pressure Cntrl Output Circuit 2BI11244Comm Loss: Ext Noise Reduction Request Circuit 2BI11245Diagnostic: MBC Failed Clearance Check Circuit 2BI11246Diagnostic: Under Voltage Circuit 2BI11247Diagnostic: Over Voltage Circuit 2BI11248Comm Loss: IGV Second Stage Actuator Circuit 1BI11249Comm Loss: IGV Second Stage Actuator Circuit 2BI11250Comm Loss: Condenser Liquid Line Temperature Circuit 1BI11251Diagnostic: Condenser Liquid Line Temperature Sensor Circuit 1BI11252Comm Loss: Condenser Liquid Line Temperature Circuit 2BI11253Diagnostic: Condenser Liquid Line Temperature Sensor Circuit 2BI11254Diagnostic: High Evaporator Refrigerant Pressure Circuit 2BI11255Diagnostic: Inverted Condenser Approach Temperature Circuit 2BI11256Diagnostic: Inverted Evaporator Approach Temperature Circuit 2BV10100Base Loading RequestBV10101Reset DiagnosticBV10102Chiller Auto Stop Command BASBV10103Energy Consumption ResetBV10104Evaporator Water Pump Request BASBV10105Condenser Water Pump Request BASBV10106Circuit 1 Lockout BASBV10107Circuit 2 Lockout BASMI10100Operating ModeMI10101Running ModeMI10102Manufacturing LocationMI10103Chiller Setpoint SourceMI10104Refrigerant TypeMI10105Cooling TypeMI10106Model Information [GEN2]MV10100Chiller Mode Command BAS
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point and a configuration dependency for each.
- The tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS setpoint and command objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percentage...); the communicated engineering unit follows the factory-configured unit system (I-P or SI).
- The doc prints the states of BV 10104-10107 (pump requests and circuit lockouts) as '1 = Auto, 1 = On'; kept as printed.
- This is the standard 5-digit list. Trane also publishes an 'HDWA (UC800)' list (BAS-PTS028) with short instance numbers, so check which list matches the controller on site.
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Agility (HDWA / HDDA) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 Agility (HDWA / HDDA)
How many BACnet points does the Trane Symbio 800 Agility (HDWA / HDDA) have?
This list has 424 BACnet objects: 117 analog inputs, 8 analog values, 283 binary inputs, 8 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 Agility (HDWA / HDDA) BACnet points are writable?
17 of the 424 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 Agility (HDWA / HDDA) BACnet documentation?
The source is Symbio 800 Integration Points List BACnet/Modbus - Agility Water-Cooled Chillers (BAS-PTS007C-EN), revision 6/30/2026, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS007C-EN_06302026.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 Agility (HDWA / HDDA)?
Start with BV 10102 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10109 Chiller Running State (Chiller on/off status); BI 10118 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10136 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10153 Actual Running Capacity (Actual running capacity in percent); BI 10100 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 Agility (HDWA / HDDA)?
BV 10102 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10124 External Auto Stop Input Status reports the hardwired external auto/stop input, BI 10123 the front-panel auto/stop, and BI 10121 Run Enabled shows whether the chiller is enabled to run. The document doesn't say how these combine or how to hand setpoint control to the BAS; BI 10118 Local Setpoint Control shows when the chiller is using local setpoints, and MI 10103 Chiller Setpoint Source shows BAS, External or Front Panel.
How do I check these points on the real Symbio 800 Agility (HDWA / HDDA)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet/Modbus - Agility Water-Cooled Chillers · BAS-PTS007C-EN · rev. 6/30/2026. Object names, instances and units are reproduced as published; descriptions are our own.