Air-cooled chiller controller · BACnet points list
Trane Symbio 800 ACRB Small (UC800) BACnet points list
Updated 28 October 2026
This Symbio 800 list for ACRB Small chillers has about 470 BACnet objects; about 290 are diagnostic binary inputs. AIs cover water temperatures and pressures, compressor drive (AFD) data, free cooling and power metering. The BAS writes chilled water setpoint, demand limit, pump setpoints, mode, lockouts and auto/stop.
This page lists 468 BACnet objects for the Trane Symbio 800 ACRB Small (UC800) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 ACRB Small (UC800)
- Equipment
- Air-cooled chiller controller
- Equipment type
- Chillers
- BACnet objects
- 468 (13 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 ACRB Small (UC800)
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10102 | Chiller Auto Stop Command BAS | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10103 | Chiller Running State | Chiller on/off status | Read |
| BI 10101 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10102 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10185 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10109 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10102 Chiller Auto Stop Command BAS (Stop/Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10120 External Auto Stop Status reports the hardwired external auto/stop input, and BI 10100 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
- The BV and status BI tables give no state texts; check the active/inactive meaning on the unit.
Trane Symbio 800 ACRB Small (UC800) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Chilled Water Setpoint | Temperature | Read | ||
| AI | 10101 | Evaporator Entering Water Temperature | Temperature | Read | ||
| AImin | 10102 | Evaporator Leaving Water Temperature | Temperature | Read | ||
| AI | 10103 | Calculated Chiller Capacity | Power, Cooling | Read | ||
| AI | 10104 | Active Demand Limit Setpoint | Percentage | Read | ||
| AI | 10105 | Unit Power Consumption | Power, Electrical | Read | ||
| AI | 10106 | Outdoor Air Temperature | Temperature | Read | ||
| AI | 10107 | Evaporator Refrigerant Gauge Pressure Circuit 1 | Evaporator Refrigerant Gauge Pressure Ckt1 | Pressure, Fluidic | Read | |
| AI | 10108 | Condenser Refrigerant Gauge Pressure Circuit 1 | Condenser Refrigerant Gauge Pressure Ckt1 | Pressure, Fluidic | Read | |
| AI | 10109 | Differential Refrigerant Pressure Circuit 1 | Differential Refrigerant Pressure Ckt1 | Pressure, Fluidic | Read | |
| AI | 10110 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Evaporator Saturated Rfgt Temp Ckt1 | Temperature | Read | |
| AI | 10111 | Condenser Saturated Refrigerant Temperature Circuit 1 | Condenser Saturated Rfgt Temp Ckt1 | Temperature | Read | |
| AI | 10112 | Evaporator Refrigerant Gauge Pressure Circuit 2 | Evaporator Refrigerant Gauge Pressure Ckt2 | Pressure, Fluidic | Read | |
| AI | 10113 | Condenser Refrigerant Gauge Pressure Circuit 2 | Condenser Refrigerant Gauge Pressure Ckt2 | Pressure, Fluidic | Read | |
| AI | 10114 | Differential Refrigerant Pressure Circuit 2 | Differential Refrigerant Pressure Ckt2 | Pressure, Fluidic | Read | |
| AI | 10115 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Evaporator Saturated Rfgt Temp Ckt2 | Temperature | Read | |
| AI | 10116 | Condenser Saturated Refrigerant Temperature Circuit 2 | Condenser Saturated Rfgt Temp Ckt2 | Temperature | Read | |
| AI | 10117 | Refrigerant Discharge Temperature - Compressor 1A | Discharge Temperature Cprsr1A | Temperature | Read | |
| AI | 10118 | Oil Gauge Pressure - Compressor 1A | Pressure, Fluidic | Read | ||
| AI | 10119 | Refrigerant Discharge Temperature - Compressor 2A | Discharge Temperature Cprsr2A | Temperature | Read | |
| AI | 10120 | Oil Gauge Pressure - Compressor 2A | Oil Gauge Pressure Cprsr2A | Pressure, Fluidic | Read | |
| AI | 10121 | Air Flow Percentage Circuit 1 | Air Flow Ckt1 | Percentage | Read | |
| AI | 10122 | Air Flow Percentage Circuit 2 | Air Flow Ckt2 | Percentage | Read | |
| AI | 10123 | Starts - Compressor 1A | Starts Cprsr1A | Read | ||
| AI | 10124 | Run Time - Compressor 1A | Running Time Cprsr1A | Read | ||
| AI | 10125 | Compressor 1A Speed Status | Percent Speed Cprsr1A | Percentage | Read | |
| AI | 10126 | Motor Winding Temperature 1 Circuit 1 | Winding Temp #1 Motor 1A | Temperature | Read | |
| AI | 10127 | Motor Winding Temperature 2 Circuit 1 | Winding Temp #2 Motor 1A | Temperature | Read | |
| AI | 10128 | Drive Motor Current U RLA Compressor 1A | Motor Current U % RLA AFD 1A | Percentage | Read | |
| AI | 10129 | Drive Motor Current V RLA Compressor 1A | Motor Current V % RLA AFD 1A | Percentage | Read | |
| AI | 10130 | Drive Motor Current W RLA Compressor 1A | Motor Current W % RLA AFD 1A | Percentage | Read | |
| AI | 10131 | Drive Motor Average Current RLA Compressor 1A | Average Motor Current % RLA AFD 1A | Percentage | Read | |
| AI | 10132 | Drive Motor Current U Compressor 1A | Motor Current U AFD 1A | Current | Read | |
| AI | 10133 | Drive Motor Current V Compressor 1A | Motor Current V AFD 1A | Current | Read | |
| AI | 10134 | Drive Motor Current W Compressor 1A | Motor Current W AFD 1A | Current | Read | |
| AI | 10135 | Drive Motor Voltage UV Circuit 1 | Motor Voltage UV AFD 1A | Voltage | Read | |
| AI | 10136 | Drive Motor Voltage VW Circuit 1 | Motor Voltage VW AFD 1A | Voltage | Read | |
| AI | 10137 | Drive Motor Voltage WU Circuit 1 | Motor Voltage WU AFD 1A | Voltage | Read | |
| AI | 10138 | Drive Motor Average Voltage Circuit 1 | Average Motor Voltage AFD 1A | Voltage | Read | |
| AI | 10139 | Drive DC Bus Voltage Circuit 1 | DC Bus Voltage AFD 1A | Voltage | Read | |
| AI | 10140 | Drive Output Power Circuit 1 | Output Power AFD 1A | Power, Electrical | Read | |
| AI | 10141 | Drive Input Power Circuit 1 | Input Power AFD 1A | Power, Electrical | Read | |
| AI | 10142 | Drive Line Average Voltage Circuit 1 | Average Input Voltage AFD 1A | Voltage | Read | |
| AI | 10143 | Drive Average Line Current Circuit 1 | Average Input Current AFD 1A | Current | Read | |
| AI | 10144 | Drive Line Frequency Circuit 1 | Estimated Input Frequency AFD 1A | Read | ||
| AI | 10145 | AFD Frequency Circuit 1 | Stator Frequency AFD 1A | Read | ||
| AI | 10146 | AFD Transistor Temperature Circuit 1 | Transistor Temperature AFD 1A | Temperature | Read | |
| AI | 10147 | Drive Inverter Base Temperature Circuit 1 | Inverter Base Temperature AFD 1A | Temperature | Read | |
| AI | 10148 | Drive Rectifier Base Temperature Circuit 1 | Rectifier Base Temperature AFD 1A | Temperature | Read | |
| AI | 10149 | Starts - Compressor 2A | Starts Cprsr2A | Read | ||
| AI | 10150 | Run Time - Compressor 2A | Running Time Cprsr2A | Read | ||
| AI | 10151 | Compressor 2A Speed Status | Percent Speed Cprsr2A | Percentage | Read | |
| AI | 10152 | Motor Winding Temperature 1 Circuit 2 | Winding Temp #1 Motor 2A | Temperature | Read | |
| AI | 10153 | Motor Winding Temperature 2 Circuit 2 | Winding Temp #2 Motor 2A | Temperature | Read | |
| AI | 10154 | Drive Motor Current U RLA Compressor 2A | Motor Current U % RLA AFD 2A | Percentage | Read | |
| AI | 10155 | Drive Motor Current V RLA Compressor 2A | Motor Current V % RLA AFD 2A | Percentage | Read | |
| AI | 10156 | Drive Motor Current W RLA Compressor 2A | Motor Current W % RLA AFD 2A | Percentage | Read | |
| AI | 10157 | Drive Motor Average Current RLA Compressor 2A | Average Motor Current % RLA AFD 2A | Percentage | Read | |
| AI | 10158 | Drive Motor Current U Compressor 2A | Motor Current U AFD 2A | Current | Read | |
| AI | 10159 | Drive Motor Current V Compressor 2A | Motor Current V AFD 2A | Current | Read | |
| AI | 10160 | Drive Motor Current W Compressor 2A | Motor Current W AFD 2A | Current | Read | |
| AI | 10161 | Drive Motor Voltage UV Circuit 2 | Motor Voltage UV AFD 2A | Voltage | Read | |
| AI | 10162 | Drive Motor Voltage VW Circuit 2 | Motor Voltage VW AFD 2A | Voltage | Read | |
| AI | 10163 | Drive Motor Voltage WU Circuit 2 | Motor Voltage WU AFD 2A | Voltage | Read | |
| AI | 10164 | Drive Motor Average Voltage Circuit 2 | Average Motor Voltage AFD 2A | Voltage | Read | |
| AI | 10165 | Drive DC Bus Voltage Circuit 2 | DC Bus Voltage AFD 2A | Voltage | Read | |
| AI | 10166 | Drive Output Power Circuit 2 | Output Power AFD 2A | Power, Electrical | Read | |
| AI | 10167 | Drive Input Power Circuit 2 | Input Power AFD 2A | Power, Electrical | Read | |
| AI | 10168 | Drive Line Average Voltage Circuit 2 | Average Input Voltage AFD 2A | Voltage | Read | |
| AI | 10169 | Drive Average Line Current Circuit 2 | Average Input Current AFD 2A | Current | Read | |
| AI | 10170 | Drive Line Frequency Circuit 2 | Estimated Input Frequency AFD 2A | Read | ||
| AI | 10171 | AFD Frequency Circuit 2 | Stator Frequency AFD 2A | Read | ||
| AI | 10172 | AFD Transistor Temperature Circuit 2 | Transistor Temperature AFD 2A | Temperature | Read | |
| AI | 10173 | Drive Inverter Base Temperature Circuit 2 | Inverter Base Temperature AFD 2A | Temperature | Read | |
| AI | 10174 | Drive Rectifier Base Temperature Circuit 2 | Rectifier Base Temperature AFD 2A | Temperature | Read | |
| AI | 10175 | Number Of Circuits | Read | |||
| AI | 10176 | Number Of Compressors Circuit 1 | Read | |||
| AI | 10177 | Number Of Compressors Circuit 2 | Read | |||
| AI | 10178 | Free Cooling Capacity Status | Free Cooling Capacity | Percentage | Read | |
| AI | 10179 | Free Cooling Entering Water Temperature | Temperature | Read | ||
| AI | 10180 | Energy Consumption Lifetime | Energy, Electrical | Read | ||
| AI | 10181 | Energy Consumption | Energy, Electrical | Read | ||
| AI | 10182 | Unit Source ID | Last Logged Diagnostic Spec BAS | Read | ||
| AI | 10183 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10184 | Active Cool/Heat Setpoint Temperature | Active Chilled Water Setpoint | Temperature | Read | |
| AImin | 10185 | Actual Running Capacity | Chiller Power | Percentage | Read | |
| AI | 10186 | Evaporator Water Flow Rate | Approximate Evaporator Water Flow | Flow, Fluidic | Read | |
| AI | 10187 | Evaporator Differential Water Pressure | Pressure, Fluidic | Read | ||
| AI | 10188 | Entering Evaporator Water Gauge Pressure | Evaporator Entering Water Gauge Pressure | Pressure, Fluidic | Read | |
| AI | 10189 | Leaving Evaporator Water Gauge Pressure | Evaporator Leaving Water Gauge Pressure | Pressure, Fluidic | Read | |
| AI | 10190 | Evaporator Water Pump Speed Command | Percentage | Read | ||
| AI | 10191 | Evaporator Water Pump Speed Feedback | Percentage | Read | ||
| AI | 10192 | Evaporator Water Pump Speed Setpoint Active | Active Evap Water Pump Speed Setpt | Percentage | Read | |
| AI | 10193 | Evaporator Water Pump Flow Rate Setpt Active | Active Evap Water Flow Rate Setpt | Flow, Fluidic | Read | |
| AI | 10194 | Discharge Superheat Compressor 1A | Discharge Superheat Cprsr 1A | Temperature, Delta | Read | |
| AI | 10195 | Discharge Superheat Compressor 2A | Discharge Superheat Cprsr 2A | Temperature, Delta | Read | |
| AI | 10196 | Current L1 | Meter Line Current L1 | Current | Read | |
| AI | 10197 | Current L2 | Meter Line Current L2 | Current | Read | |
| AI | 10198 | Current L3 | Meter Line Current L3 | Current | Read | |
| AI | 10199 | Average Current | Meter Average Line Current | Current | Read | |
| AI | 10200 | Voltage L1-L2 | Meter Line Voltage L1-L2 | Voltage | Read | |
| AI | 10201 | Voltage L2-L3 | Meter Line Voltage L2-L3 | Voltage | Read | |
| AI | 10202 | Voltage L1-L3 | Meter Line Voltage L1-L3 | Voltage | Read | |
| AI | 10203 | Average Voltage L-L | Meter Average Line Voltage | Voltage | Read | |
| AI | 10204 | Line Frequency | Unit Line Frequency | Read | ||
| AI | 10205 | Power Factor | Unit Power Factor | Read | ||
| AI | 10206 | Unit Power Demand | Chiller Power Demand | Power, Electrical | Read | |
| AI | 10207 | Free Cooling Entering Glycol Temperature | Temperature | Read | ||
| AI | 10208 | Free Cooling Leaving Glycol Temperature | Temperature | Read | ||
| AI | 10209 | Free Cooling Glycol Pressure | Pressure, Fluidic | Read | ||
| AI | 10210 | Free Cooling Valve Position Status | Free Cooling Valve Percent Open | Percentage | Read | |
| AI | 10211 | Free Cooling Bypass Valve Position Status | Free Cooling Bypass Valve Percent Open | Percentage | Read | |
| AI | 10212 | Free Cooling Pump Override Time Remaining | Read | |||
| AI | 10213 | Free Cooling Target Offset | Temperature, Delta | Read | ||
| AI | 10214 | Free Cooling Dedicated Fans Airflow | Free Cooling Dedicated Fan Air Flow | Percentage | Read | |
| AI | 10215 | Free Cooling Waterside Bypass Valve Status | Free Cooling Waterside Byp Vlv Pct Open | Percentage | Read | |
| AI | 10216 | Evaporator Refrigerant Pressure Circuit 1 | Evaporator Refrigerant Absolute Pressure Ckt1 | Pressure, Fluidic | Read | |
| AI | 10217 | Condenser Refrigerant Pressure Circuit 1 | Condenser Refrigerant Absolute Pressure Ckt1 | Pressure, Fluidic | Read | |
| AI | 10218 | Evaporator Refrigerant Pressure Circuit 2 | Evaporator Refrigerant Absolute Pressure Ckt2 | Pressure, Fluidic | Read | |
| AI | 10219 | Condenser Refrigerant Pressure Circuit 2 | Condenser Refrigerant Absolute Pressure Ckt2 | Pressure, Fluidic | Read | |
| AI | 10220 | Oil Pressure - Compressor 1A | Oil Absolute Pressure - Compressor 1A | Pressure, Fluidic | Read | |
| AI | 10221 | Oil Pressure - Compressor 2A | Oil Absolute Pressure Cprsr2A | Pressure, Fluidic | Read | |
| AI | 10222 | Entering Evaporator Water Pressure | Evaporator Entering Water Absolute Pressure | Pressure, Fluidic | Read | |
| AI | 10223 | Leaving Evaporator Water Pressure | Evaporator Leaving Water Absolute Pressure | Pressure, Fluidic | Read | |
| AI | 10224 | AFD Coolant Supply Temperature Compressor 1A | Drive Cooling Supply Temperature Ckt1 | Temperature | Read | |
| AI | 10225 | AFD Coolant Supply Temperature Compressor 2A | Drive Cooling Supply Temperature Ckt2 | Temperature | Read | |
| AI | 10226 | Evaporator Approach Temperature Circuit 1 | Evaporator Approach Temperature Ckt1 | Temperature, Delta | Read | |
| AI | 10227 | Evaporator Approach Temperature Circuit 2 | Evaporator Approach Temperature Ckt2 | Temperature, Delta | Read | |
| AVmin | 10100 | Chilled Water Setpoint | Temperature | Write | ||
| AVmin | 10101 | Demand Limit Setpoint | Percentage | Write | ||
| AV | 10102 | Evaporator Water Pump Flow Rate Setpt BAS | BAS Evap Water Flow Rate Setpt | Flow, Fluidic | Write | |
| AV | 10103 | Evaporator Water Pump Speed Setpt BAS | BAS Evap Water Pump Speed Setpt | Percentage | Write | |
| BI | 10100 | Run Enable | Read | |||
| BImin | 10101 | Local Setpoint Control | Read | |||
| BI | 10102 | Limit Mode Relay Status | Read | |||
| BImin | 10103 | Chiller Running State | Read | |||
| BI | 10104 | Maximum Capacity | Maximum Capacity Relay | Read | ||
| BI | 10105 | Evaporator Water Pump Command | Read | |||
| BI | 10106 | Evaporator Water Flow Status | Read | |||
| BI | 10107 | Manual Override Exists | Read | |||
| BI | 10108 | Emergency Stop | Read | |||
| BImin | 10109 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10110 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10111 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10112 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10113 | Diagnostic Present: Information | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10114 | Diagnostic Present: Advisory | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10115 | Diagnostic Present: Critical | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10116 | Diagnostic Present: Service Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10117 | Compressor 1A Running Status | Running Status Cprsr1A | Read | ||
| BI | 10118 | Compressor 2A Running Status | Running Status Cprsr2A | Read | ||
| BI | 10119 | Free Cooling Active | Read | |||
| BI | 10120 | External Auto Stop Status | External Auto Stop | Read | ||
| BI | 10121 | Front Panel Auto Stop Status | Front Panel Auto/Stop | Read | ||
| BI | 10122 | Noise Reduction Request Active | Read | |||
| BI | 10123 | Evaporator Water Pump 1 Inverter Running Status | Evap Water Pump 1 Inverter Running Status | Read | ||
| BI | 10124 | Evaporator Water Pump 1 Fault Status | Read | |||
| BI | 10125 | Circuit 1 Cooling Available | Circuit is available to start | Read | ||
| BI | 10126 | Circuit 2 Cooling Available | Circuit is available to start | Read | ||
| BI | 10127 | Oil Sensor Circuit 1 | Oil Loss Level Sensor Ckt1 | Read | ||
| BI | 10128 | Oil Sensor Circuit 2 | Oil Loss Level Sensor Ckt2 | Read | ||
| BI | 10129 | Free Cooling Pump Command Status | Free Cooling Pump Command | Read | ||
| BI | 10130 | Free Cooling Front Panel Command Status | Front Panel Free Cooling Command | Read | ||
| BI | 10131 | Free Cooling Glycol Flow Status | Read | |||
| BI | 11000 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Diagnostic: Check Clock | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Diagnostic: Software Error 1001: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Diagnostic: Software Error 1002: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Diagnostic: Software Error 1003: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Comm Loss: Energy Meter | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Diagnostic: Energy Meter Write Command Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Comm Loss: Condenser Rfgt Pressure - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Comm Loss: Condenser Rfgt Pressure - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Comm Loss: Suction Rfgt Pressure, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Comm Loss: Suction Rfgt Pressure, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Diagnostic: Pumpdown Terminated - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Diagnostic: Pumpdown Terminated - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Diagnostic: Condenser Rfgt Pressure Transducer - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Diagnostic: Condenser Rfgt Pressure Transducer - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Diagnostic: Suction Pressure Rfgt Transducer - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Diagnostic: Suction Pressure Rfgt Transducer - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Diagnostic: Evap Spillover Liquid Level Sensor - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Diagnostic: Evap Spillover Liquid Level Sensor - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Comm Loss: Evap Rfgt Liquid Level - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Comm Loss: Evap Rfgt Liquid Level - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Comm Loss: External Ckt Lockout - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Comm Loss: External Ckt Lockout - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Comm Loss: Evap Rfgt Pool Temp, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Comm Loss: Evap Rfgt Pool Temp, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Diagnostic: Drive Cooling Supply Temp Sensor Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Diagnostic: Drive Cooling Supply Temp Sensor Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Comm Loss: Drive Cooling Supply Temp Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11036 | Comm Loss: Drive Cooling Supply Temp Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11037 | Comm Loss: Drive Cooling Bypass Valve Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Comm Loss: Drive Cooling Bypass Valve Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Comm Loss: Drive Cooling Inline Valve Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Comm Loss: Drive Cooling Inline Valve Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Comm Loss: Evaporator Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Comm Loss: Off-cycle Freeze Prot Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Comm Loss: Evaporator Pump Speed Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Comm Loss: Evaporator Pump Speed Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Comm Loss: Evaporator Pump Inverter Running Status | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Comm Loss: Evaporator Pump Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Diagnostic: Evaporator Water Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Diagnostic: Evaporator Water Pump Speed Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Comm Loss: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Diagnostic: Emergency Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Comm Loss: Op Status Programmable Relays | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Comm Loss: Chiller % Capacity Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Comm Loss: Ext Noise Reduction Request | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Diagnostic: Low Evaporator Rfgt Temperature - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Diagnostic: Low Evaporator Rfgt Temperature - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Diagnostic: Low Evaporator Rfgt Pressure - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Diagnostic: Low Evaporator Rfgt Pressure - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Diagnostic: High Differential Rfgt Pressure - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Diagnostic: High Differential Rfgt Pressure - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Diagnostic: High Refrigerant Pressure Ratio - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Diagnostic: High Refrigerant Pressure Ratio - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Diagnostic: Low Evaporator Temp (Unit Off) - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Diagnostic: Low Evaporator Temp (Unit Off) - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Diagnostic: Evaporator Approach Error - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Diagnostic: Evaporator Approach Error - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Diagnostic: Low Drive Cooling Supply Temperature - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Diagnostic: Low Drive Cooling Supply Temperature - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Diagnostic: High Evaporator Refrigerant Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Diagnostic: High Pressure Cutout - Cprsr 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Diagnostic: High Pressure Cutout - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Diagnostic: Excessive Condenser Pressure - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Diagnostic: Excessive Condenser Pressure - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Comm Loss: Ice Building Status Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Diagnostic: Low Evaporator Water Temp (Unit On) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Diagnostic: Evap Water Flow (Entering Water Temp) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: Evap Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Diagnostic: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Diagnostic: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11096 | Comm Loss: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Comm Loss: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Diagnostic: Low Evaporator Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Diagnostic: Low Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Diagnostic: Low Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Diagnostic: Low Oil Return or AFD Cooling - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Diagnostic: Low Oil Return or AFD Cooling - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss: Fan Inverter Fault, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Comm Loss: Fan Inverter Fault, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Comm Loss: Fan Inverter Speed Command, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Comm Loss: Fan Inverter Speed Command, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Diagnostic: Condenser Fan Inverter Fault - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Diagnostic: Condenser Fan Inverter Fault - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11109 | Comm Loss: Condenser Fan Enable, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11110 | Comm Loss: Condenser Fan Enable, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11111 | Comm Loss: Fan Inv Spd Cmd, Shrd Ckt1&2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Comm Loss: Cond Fan Enbl Shared Ckt 1&2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: Expansion Valve, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: Expansion Valve, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Diagnostic: Oil Analysis Recommended - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Diagnostic: Oil Analysis Recommended - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Diagnostic: Oil Filter Change Recommended - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Diagnostic: Oil Filter Change Recommended - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Diagnostic: Starts or Hours Modified - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: Var Vi Valve - Cprsr 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Diagnostic: Starts or Hours Modified - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Var Vi Valve - Cprsr 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Diagnostic: No Differential Rfgt Pressure - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Diagnostic: No Differential Rfgt Pressure - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Diagnostic: Low Differential Rfgt Pressure - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Diagnostic: Low Differential Rfgt Pressure - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Diagnostic: Oil Flow Protection Fault - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Diagnostic: Oil Flow Protection Fault - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Diagnostic: Low Oil Flow - Cprsr 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Diagnostic: Low Oil Flow - Cprsr 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Cprsr Discharge Rfgt Temp, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Cprsr Discharge Rfgt Temp, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Diagnostic: Discharge Rfgt Temp Sensor - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Diagnostic: Discharge Rfgt Temp Sensor - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Comm Loss: Oil Pressure, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Oil Pressure, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Diagnostic: Oil Pressure Transducer - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Diagnostic: Oil Pressure Transducer - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Diagnostic: Low Discharge Superheat - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Diagnostic: Low Discharge Superheat - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Diagnostic: Very Low Evaporator Rfgt Pressure - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Diagnostic: Very Low Evaporator Rfgt Pressure - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Oil Loss Level Sensor Input, Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Oil Loss Level Sensor Input, Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Diagnostic: Loss of Oil (Stopped) - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Diagnostic: Loss of Oil (Stopped) - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Diagnostic: Loss of Oil (Running) - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Diagnostic: Loss of Oil (Running) - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Diagnostic: High Discharge Temperature - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Diagnostic: High Discharge Temperature - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Diagnostic: High Motor Winding Temperature - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Diagnostic: High Motor Winding Temperature - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Comm Loss: Winding Temp 1, Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Comm Loss: Winding Temp 1, Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Comm Loss: Winding Temp 2, Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Comm Loss: Winding Temp 2, Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Diagnostic: Motor Winding Temp Sensor - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Diagnostic: Motor Winding Temp Sensor - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Diagnostic: Failure to Arm or Start - AFD 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Diagnostic: Failure to Arm or Start - AFD 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Comm Loss: AFD 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Comm Loss: AFD 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Diagnostic: Unexpected Shutdown - AFD1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Diagnostic: Unexpected Shutdown - AFD2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Diagnostic: Interrupt Failure - AFD1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Diagnostic: Interrupt Failure - AFD2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Diagnostic: AFD 1A DSP Board Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Diagnostic: AFD 2A DSP Board Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Diagnostic: AFD 1A DSP Board Initialization Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Diagnostic: AFD 2A DSP Board Initialization Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Diagnostic: AFD 1A DSP Board ID Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Diagnostic: AFD 2A DSP Board ID Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Diagnostic: AFD 1A Non-Volatile Memory Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Diagnostic: AFD 2A Non-Volatile Memory Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Diagnostic: AFD 1A A/D Calibration Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Diagnostic: AFD 2A A/D Calibration Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Diagnostic: AFD 1A Voltage Transient Protection Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Diagnostic: AFD 2A Voltage Transient Protection Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Diagnostic: AFD 1A Watchdog Timer Overflow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Diagnostic: AFD 2A Watchdog Timer Overflow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Diagnostic: AFD 1A Comm Loss: Main Processor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Diagnostic: AFD 2A Comm Loss: Main Processor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Diagnostic: AFD 1A General Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Diagnostic: AFD 2A General Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Diagnostic: AFD 1A Gate Drive Module Comm Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Diagnostic: AFD 2A Gate Drive Module Comm Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Diagnostic: AFD 1A Gate Drive Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Diagnostic: AFD 2A Gate Drive Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: AFD 1A Over Speed | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: AFD 2A Over Speed | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Diagnostic: AFD 1A Motor Current Overload | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Diagnostic: AFD 2A Motor Current Overload | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: AFD 1A Ground Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: AFD 2A Ground Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: AFD 1A Output Phase Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: AFD 2A Output Phase Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: AFD 1A Low Rotor Flux Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Diagnostic: AFD 2A Low Rotor Flux Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Diagnostic: AFD 1A Bump Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Diagnostic: AFD 2A Bump Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Diagnostic: AFD 1A Compressor Start Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11205 | Diagnostic: AFD 2A Compressor Start Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Diagnostic: AFD 1A Instantaneous Current Overload | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Diagnostic: AFD 2A Instantaneous Current Overload | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Diagnostic: AFD 1A Desaturation Detected | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Diagnostic: AFD 2A Desaturation Detected | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: AFD 1A Current Sensor Self Test Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Diagnostic: AFD 2A Current Sensor Self Test Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Diagnostic: AFD 1A IGBT Self Test Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Diagnostic: AFD 2A IGBT Self Test Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Diagnostic: AFD 1A Gate Kill Active | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Diagnostic: AFD 2A Gate Kill Active | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Diagnostic: AFD 1A Load Inductor High Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Diagnostic: AFD 2A Load Inductor High Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: AFD 1A 12-Pulse or Auto Transf High Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11219 | Diagnostic: AFD 2A 12-Pulse or Auto Transf High Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11220 | Diagnostic: AFD 1A Inverter Heatsink Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: AFD 2A Inverter Heatsink Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: AFD 1A Rectifier Heatsink Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: AFD 2A Rectifier Heatsink Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: AFD 1A Estimated Junction Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: AFD 2A Estimated Junction Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11226 | Diagnostic: AFD 1A Gate Drive Board Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11227 | Diagnostic: AFD 2A Gate Drive Board Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11228 | Diagnostic: AFD 1A Bus Over Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11229 | Diagnostic: AFD 2A Bus Over Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: AFD 1A Bus Under Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Diagnostic: AFD 2A Bus Under Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: AFD 1A IMC 24V Low Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Diagnostic: AFD 2A IMC 24V Low Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Diagnostic: AFD 1A AHD Frequency Out of Range | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: AFD 2A AHD Frequency Out of Range | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: AFD 1A Bus Voltage Ripple Too High | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Diagnostic: AFD 2A Bus Voltage Ripple Too High | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: AFD 1A DSP Board Low Voltage Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: AFD 2A DSP Board Low Voltage Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: Failure to Arm or Hold - AFD 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: Failure to Arm or Hold - AFD 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Diagnostic: AFD 1A Loss of AHD Sync Signal | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Diagnostic: AFD 2A Loss of AHD Sync Signal | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11244 | Diagnostic: AFD 1A AHD Sync Signal Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11245 | Diagnostic: AFD 2A AHD Sync Signal Error | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11246 | Diagnostic: AFD 1A Excessive AHD Inhibit | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11247 | Diagnostic: AFD 2A Excessive AHD Inhibit | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11248 | Diagnostic: AFD 1A Gate Drive Low Voltage Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11249 | Diagnostic: AFD 2A Gate Drive Low Voltage Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11250 | Diagnostic: AFD 1A Temperature Sensor Warning | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11251 | Diagnostic: AFD 2A Temperature Sensor Warning | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11252 | Diagnostic: AFD 1A Motor Shorted | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11253 | Diagnostic: AFD 2A Motor Shorted | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11254 | Diagnostic: AFD 1A Over Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11255 | Diagnostic: AFD 2A Over Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11256 | Diagnostic: AFD 1A Precharge Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11257 | Diagnostic: AFD 2A Precharge Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11258 | Diagnostic: AFD 1A Input Phase Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11259 | Diagnostic: AFD 2A Input Phase Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11260 | Diagnostic: AFD 1A Motor Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11261 | Diagnostic: AFD 2A Motor Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11262 | Diagnostic: AFD 1A Customized Protection Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11263 | Diagnostic: AFD 2A Customized Protection Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11264 | Diagnostic: AFD 1A Input Transf or Filter Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11265 | Diagnostic: AFD 2A Input Transf or Filter Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11266 | Diagnostic: AFD 1A Loss Of Motor Control | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11267 | Diagnostic: AFD 2A Loss Of Motor Control | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11268 | Comm Loss: Free Cooling Entering Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11269 | Diagnostic: Free Cooling Entering Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11270 | Comm Loss: Free Cooling Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11271 | Comm Loss: Free Cooling Bypass Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11272 | Comm Loss: Free Cooling Entering Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11273 | Diagnostic: Free Cooling Entering Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11274 | Comm Loss: Free Cooling Leaving Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11275 | Diagnostic: Free Cooling Leaving Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11276 | Comm Loss: Free Cooling Pump | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11277 | Diagnostic: Low Glycol Temp Free Cooling | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11278 | Diagnostic: Free Cooling Glycol Temperature Equalization Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11279 | Diagnostic: Free Cooling Glycol Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11280 | Comm Loss: Free Cooling Glycol Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11281 | Comm Loss: Free Cooling Glycol Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11282 | Diagnostic: Free Cooling Glycol Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11283 | Diagnostic: Low Glycol Pressure Free Cooling | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11284 | Comm Loss: Free Cooling Glycol Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11285 | Diagnostic: Free Cooling Glycol Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11286 | Diagnostic: Free Cooling Glycol Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11287 | Comm Loss: Free Cooling Waterside Bypass Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11288 | Comm Loss: Free Cooling Dedicated Fan Enable | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11289 | Comm Loss: Free Cooling Dedicated Fan Inverter Speed Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11290 | Comm Loss: Free Cooling Dedicated Fan Inverter Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11291 | Diagnostic: Free Cooling Dedicated Fan Inverter Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11292 | Diagnostic: Energy Meter Write Value Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BV | 10100 | Reset Diagnostic | Write | |||
| BV | 10101 | Noise Reduction Request BAS | Write | |||
| BVmin | 10102 | Chiller Auto Stop Command BAS | Write | |||
| BV | 10103 | Free Cooling Auto Stop Command BAS | Write | |||
| BV | 10104 | Free Cooling Compressor Lockout | Write | |||
| BV | 10105 | Circuit 1 Lockout BAS | BAS Lockout of Circuit 1 | Write | ||
| BV | 10106 | Circuit 2 Lockout BAS | BAS Lockout of Circuit 2 | Write | ||
| BV | 10107 | Energy Consumption Reset | Write | |||
| MI | 10100 | Running Mode | Chiller Running Status | Read | Chiller Off, Chiller In Start Mode, Chiller In Run Mode, Chiller In Pre-Shutdown Mode, Chiller In Service Mode | |
| MI | 10101 | Operating Mode | Read | Cool, Heat, Ice Making, Free Cooling | ||
| MI | 10102 | Chiller Setpoint Source | Setpoint Source | Read | BAS, External, Front Panel | |
| MI | 10103 | Refrigerant Type | Read | R-11, R-12, R-22, R-123, R-134a, R-407C, R-410A, R-113, R-114, R-500, R-502, R-404A, R-513A, R-1233zd(E), R-514A, R-1234ze(E) | ||
| MI | 10104 | Cooling Type | Read | Water Cooled, Air Cooled | ||
| MI | 10105 | Manufacture Location | Read | Field Applied, La Crosse, Pueblo, Charmes, Rushville, Macon, Waco, Lexington, Forsyth, Clarksville, Ft. Smith, Penang, Colchester, Curitiba, Taicang, Taiwan, Epinal, Golbey | ||
| MI | 10106 | Model Information [GEN2] | Model Information | Read | CVHF, CVGF, CVHS, RTAE, RTAF, RTHA, RTHB, RTHC, RTHD, RTWE, CTVD, CVR, CVHH, CDHH, VMAX, GVAF, RTWF, RTHF, RTAC, CVHM, RTAG, CGAF, RTXG, GVWF, HDWA, CMAC, IPAK, CXAF, ACSA, RTSF, HSWA, ACRA, RTEG, ACXA, CMAF, ACRB Large, ACRB Small | |
| MVmin | 10100 | Chiller Mode Command BAS | Write | Cool, Heat, Ice Making, Free Cooling |
No points match these filters.
Object ID lookup: Trane Symbio 800 ACRB Small point IDs by name
AI10100Active Chilled Water SetpointAI10101Evaporator Entering Water TemperatureAI10102Evaporator Leaving Water TemperatureAI10103Calculated Chiller CapacityAI10104Active Demand Limit SetpointAI10105Unit Power ConsumptionAI10106Outdoor Air TemperatureAI10107Evaporator Refrigerant Gauge Pressure Circuit 1AI10108Condenser Refrigerant Gauge Pressure Circuit 1AI10109Differential Refrigerant Pressure Circuit 1AI10110Evaporator Saturated Refrigerant Temperature Circuit 1AI10111Condenser Saturated Refrigerant Temperature Circuit 1AI10112Evaporator Refrigerant Gauge Pressure Circuit 2AI10113Condenser Refrigerant Gauge Pressure Circuit 2AI10114Differential Refrigerant Pressure Circuit 2AI10115Evaporator Saturated Refrigerant Temperature Circuit 2AI10116Condenser Saturated Refrigerant Temperature Circuit 2AI10117Refrigerant Discharge Temperature - Compressor 1AAI10118Oil Gauge Pressure - Compressor 1AAI10119Refrigerant Discharge Temperature - Compressor 2AAI10120Oil Gauge Pressure - Compressor 2AAI10121Air Flow Percentage Circuit 1AI10122Air Flow Percentage Circuit 2AI10123Starts - Compressor 1AAI10124Run Time - Compressor 1AAI10125Compressor 1A Speed StatusAI10126Motor Winding Temperature 1 Circuit 1AI10127Motor Winding Temperature 2 Circuit 1AI10128Drive Motor Current U RLA Compressor 1AAI10129Drive Motor Current V RLA Compressor 1AAI10130Drive Motor Current W RLA Compressor 1AAI10131Drive Motor Average Current RLA Compressor 1AAI10132Drive Motor Current U Compressor 1AAI10133Drive Motor Current V Compressor 1AAI10134Drive Motor Current W Compressor 1AAI10135Drive Motor Voltage UV Circuit 1AI10136Drive Motor Voltage VW Circuit 1AI10137Drive Motor Voltage WU Circuit 1AI10138Drive Motor Average Voltage Circuit 1AI10139Drive DC Bus Voltage Circuit 1AI10140Drive Output Power Circuit 1AI10141Drive Input Power Circuit 1AI10142Drive Line Average Voltage Circuit 1AI10143Drive Average Line Current Circuit 1AI10144Drive Line Frequency Circuit 1AI10145AFD Frequency Circuit 1AI10146AFD Transistor Temperature Circuit 1AI10147Drive Inverter Base Temperature Circuit 1AI10148Drive Rectifier Base Temperature Circuit 1AI10149Starts - Compressor 2AAI10150Run Time - Compressor 2AAI10151Compressor 2A Speed StatusAI10152Motor Winding Temperature 1 Circuit 2AI10153Motor Winding Temperature 2 Circuit 2AI10154Drive Motor Current U RLA Compressor 2AAI10155Drive Motor Current V RLA Compressor 2AAI10156Drive Motor Current W RLA Compressor 2AAI10157Drive Motor Average Current RLA Compressor 2AAI10158Drive Motor Current U Compressor 2AAI10159Drive Motor Current V Compressor 2AAI10160Drive Motor Current W Compressor 2AAI10161Drive Motor Voltage UV Circuit 2AI10162Drive Motor Voltage VW Circuit 2AI10163Drive Motor Voltage WU Circuit 2AI10164Drive Motor Average Voltage Circuit 2AI10165Drive DC Bus Voltage Circuit 2AI10166Drive Output Power Circuit 2AI10167Drive Input Power Circuit 2AI10168Drive Line Average Voltage Circuit 2AI10169Drive Average Line Current Circuit 2AI10170Drive Line Frequency Circuit 2AI10171AFD Frequency Circuit 2AI10172AFD Transistor Temperature Circuit 2AI10173Drive Inverter Base Temperature Circuit 2AI10174Drive Rectifier Base Temperature Circuit 2AI10175Number Of CircuitsAI10176Number Of Compressors Circuit 1AI10177Number Of Compressors Circuit 2AI10178Free Cooling Capacity StatusAI10179Free Cooling Entering Water TemperatureAI10180Energy Consumption LifetimeAI10181Energy ConsumptionAI10182Unit Source IDAI10183Chiller Design CapacityAI10184Active Cool/Heat Setpoint TemperatureAI10185Actual Running CapacityAI10186Evaporator Water Flow RateAI10187Evaporator Differential Water PressureAI10188Entering Evaporator Water Gauge PressureAI10189Leaving Evaporator Water Gauge PressureAI10190Evaporator Water Pump Speed CommandAI10191Evaporator Water Pump Speed FeedbackAI10192Evaporator Water Pump Speed Setpoint ActiveAI10193Evaporator Water Pump Flow Rate Setpt ActiveAI10194Discharge Superheat Compressor 1AAI10195Discharge Superheat Compressor 2AAI10196Current L1AI10197Current L2AI10198Current L3AI10199Average CurrentAI10200Voltage L1-L2AI10201Voltage L2-L3AI10202Voltage L1-L3AI10203Average Voltage L-LAI10204Line FrequencyAI10205Power FactorAI10206Unit Power DemandAI10207Free Cooling Entering Glycol TemperatureAI10208Free Cooling Leaving Glycol TemperatureAI10209Free Cooling Glycol PressureAI10210Free Cooling Valve Position StatusAI10211Free Cooling Bypass Valve Position StatusAI10212Free Cooling Pump Override Time RemainingAI10213Free Cooling Target OffsetAI10214Free Cooling Dedicated Fans AirflowAI10215Free Cooling Waterside Bypass Valve StatusAI10216Evaporator Refrigerant Pressure Circuit 1AI10217Condenser Refrigerant Pressure Circuit 1AI10218Evaporator Refrigerant Pressure Circuit 2AI10219Condenser Refrigerant Pressure Circuit 2AI10220Oil Pressure - Compressor 1AAI10221Oil Pressure - Compressor 2AAI10222Entering Evaporator Water PressureAI10223Leaving Evaporator Water PressureAI10224AFD Coolant Supply Temperature Compressor 1AAI10225AFD Coolant Supply Temperature Compressor 2AAI10226Evaporator Approach Temperature Circuit 1AI10227Evaporator Approach Temperature Circuit 2AV10100Chilled Water SetpointAV10101Demand Limit SetpointAV10102Evaporator Water Pump Flow Rate Setpt BASAV10103Evaporator Water Pump Speed Setpt BASBI10100Run EnableBI10101Local Setpoint ControlBI10102Limit Mode Relay StatusBI10103Chiller Running StateBI10104Maximum CapacityBI10105Evaporator Water Pump CommandBI10106Evaporator Water Flow StatusBI10107Manual Override ExistsBI10108Emergency StopBI10109Diagnostic PresentBI10110Diagnostic Shutdown PresentBI10111Diagnostic: Manual Reset RequiredBI10112Diagnostic: Local Manual Reset RequiredBI10113Diagnostic Present: InformationBI10114Diagnostic Present: AdvisoryBI10115Diagnostic Present: CriticalBI10116Diagnostic Present: Service RequiredBI10117Compressor 1A Running StatusBI10118Compressor 2A Running StatusBI10119Free Cooling ActiveBI10120External Auto Stop StatusBI10121Front Panel Auto Stop StatusBI10122Noise Reduction Request ActiveBI10123Evaporator Water Pump 1 Inverter Running StatusBI10124Evaporator Water Pump 1 Fault StatusBI10125Circuit 1 Cooling AvailableBI10126Circuit 2 Cooling AvailableBI10127Oil Sensor Circuit 1BI10128Oil Sensor Circuit 2BI10129Free Cooling Pump Command StatusBI10130Free Cooling Front Panel Command StatusBI10131Free Cooling Glycol Flow StatusBI11000Diagnostic: MP: Invalid ConfigurationBI11001Diagnostic: Check ClockBI11002Diagnostic: MP: Reset Has OccurredBI11003Comm Loss: Outdoor Air TemperatureBI11004Diagnostic: Outdoor Air Temperature SensorBI11005Diagnostic: Software Error 1001: Call Trane ServiceBI11006Diagnostic: Software Error 1002: Call Trane ServiceBI11007Diagnostic: Software Error 1003: Call Trane ServiceBI11009Comm Loss: Energy MeterBI11010Diagnostic: Energy Meter Write Command FailureBI11011Comm Loss: Condenser Rfgt Pressure - Ckt1BI11012Comm Loss: Condenser Rfgt Pressure - Ckt2BI11013Comm Loss: Suction Rfgt Pressure, Ckt1BI11014Comm Loss: Suction Rfgt Pressure, Ckt2BI11015Diagnostic: Pumpdown Terminated - Ckt1BI11016Diagnostic: Pumpdown Terminated - Ckt2BI11017Diagnostic: Condenser Rfgt Pressure Transducer - Ckt1BI11018Diagnostic: Condenser Rfgt Pressure Transducer - Ckt2BI11019Diagnostic: Suction Pressure Rfgt Transducer - Cprsr1ABI11020Diagnostic: Suction Pressure Rfgt Transducer - Cprsr2ABI11021Diagnostic: Evap Spillover Liquid Level Sensor - Ckt1BI11022Diagnostic: Evap Spillover Liquid Level Sensor - Ckt2BI11023Comm Loss: Evap Rfgt Liquid Level - Ckt1BI11024Comm Loss: Evap Rfgt Liquid Level - Ckt2BI11025Comm Loss: External Ckt Lockout - Ckt1BI11026Comm Loss: External Ckt Lockout - Ckt2BI11027Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt1BI11028Diagnostic: Evap Rfgt Pool Temp Sensor - Ckt2BI11029Comm Loss: Evap Rfgt Pool Temp, Ckt1BI11030Comm Loss: Evap Rfgt Pool Temp, Ckt2BI11031Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1BI11032Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2BI11033Diagnostic: Drive Cooling Supply Temp Sensor Ckt1BI11034Diagnostic: Drive Cooling Supply Temp Sensor Ckt2BI11035Comm Loss: Drive Cooling Supply Temp Ckt1BI11036Comm Loss: Drive Cooling Supply Temp Ckt2BI11037Comm Loss: Drive Cooling Bypass Valve Ckt1BI11038Comm Loss: Drive Cooling Bypass Valve Ckt2BI11039Comm Loss: Drive Cooling Inline Valve Ckt1BI11040Comm Loss: Drive Cooling Inline Valve Ckt2BI11041Comm Loss: Evaporator Water Pump RelayBI11042Comm Loss: Evaporator Water Flow SwitchBI11043Comm Loss: Off-cycle Freeze Prot RelayBI11044Comm Loss: Evaporator Pump Speed CommandBI11045Comm Loss: Evaporator Pump Speed FeedbackBI11046Comm Loss: Evaporator Pump Inverter Running StatusBI11047Comm Loss: Evaporator Pump Fault InputBI11048Diagnostic: Evaporator Water Pump FaultBI11049Diagnostic: Evaporator Water Pump Speed FeedbackBI11050Comm Loss: External Auto/StopBI11051Comm Loss: Emergency StopBI11052Diagnostic: Emergency StopBI11053Diagnostic: External Chilled/Hot Water SetpointBI11054Comm Loss: Ext Chilled/Hot Water SetpointBI11055Comm Loss: Op Status Programmable RelaysBI11056Diagnostic: External Demand Limit SetpointBI11057Comm Loss: Ext Demand Limit SetpointBI11059Comm Loss: Chiller % Capacity OutputBI11060Comm Loss: Ext Noise Reduction RequestBI11061Diagnostic: Low Evaporator Rfgt Temperature - Ckt1BI11062Diagnostic: Low Evaporator Rfgt Temperature - Ckt2BI11063Diagnostic: Low Evaporator Rfgt Pressure - Ckt1BI11064Diagnostic: Low Evaporator Rfgt Pressure - Ckt2BI11065Diagnostic: High Differential Rfgt Pressure - Ckt1BI11066Diagnostic: High Differential Rfgt Pressure - Ckt2BI11067Diagnostic: High Refrigerant Pressure Ratio - Ckt1BI11068Diagnostic: High Refrigerant Pressure Ratio - Ckt2BI11069Diagnostic: Low Evaporator Temp (Unit Off) - Ckt1BI11070Diagnostic: Low Evaporator Temp (Unit Off) - Ckt2BI11071Diagnostic: Evaporator Approach Error - Ckt1BI11072Diagnostic: Evaporator Approach Error - Ckt2BI11073Diagnostic: Low Drive Cooling Supply Temperature - Ckt1BI11074Diagnostic: Low Drive Cooling Supply Temperature - Ckt2BI11075Diagnostic: High Evaporator Refrigerant PressureBI11076Diagnostic: High Evaporator Water TemperatureBI11077Diagnostic: Evaporator Water Flow OverdueBI11078Diagnostic: Evaporator Water Flow LostBI11079Diagnostic: High Pressure Cutout - Cprsr 1ABI11080Diagnostic: High Pressure Cutout - Cprsr2ABI11081Diagnostic: Excessive Condenser Pressure - Ckt1BI11082Diagnostic: Excessive Condenser Pressure - Ckt2BI11083Comm Loss: External Ice Building CommandBI11084Comm Loss: Ice Building Status RelayBI11085Comm Loss: Evap Entering Water TempBI11086Diagnostic: Evaporator Entering Water Temp SensorBI11087Comm Loss: Evap Leaving Water TempBI11088Diagnostic: Evaporator Leaving Water Temp SensorBI11089Diagnostic: Low Evaporator Water Temp (Unit On)BI11090Diagnostic: Low Evaporator Water Temp (Unit Off)BI11091Diagnostic: Evap Water Flow (Entering Water Temp)BI11092Comm Loss: Evap Diff Water PressureBI11093Diagnostic: Evaporator Diff Water Pressure XdcrBI11094Diagnostic: Evaporator Entering Water PressureBI11095Diagnostic: Evaporator Leaving Water PressureBI11096Comm Loss: Evaporator Entering Water PressureBI11097Comm Loss: Evaporator Leaving Water PressureBI11098Diagnostic: Low Evaporator Water FlowBI11099Diagnostic: Low Evaporator Entering Water PressureBI11100Diagnostic: Low Evaporator Leaving Water PressureBI11101Diagnostic: Low Oil Return or AFD Cooling - Ckt1BI11102Diagnostic: Low Oil Return or AFD Cooling - Ckt2BI11103Comm Loss: Fan Inverter Fault, Ckt1BI11104Comm Loss: Fan Inverter Fault, Ckt2BI11105Comm Loss: Fan Inverter Speed Command, Ckt1BI11106Comm Loss: Fan Inverter Speed Command, Ckt2BI11107Diagnostic: Condenser Fan Inverter Fault - Ckt1BI11108Diagnostic: Condenser Fan Inverter Fault - Ckt2BI11109Comm Loss: Condenser Fan Enable, Ckt1BI11110Comm Loss: Condenser Fan Enable, Ckt2BI11111Comm Loss: Fan Inv Spd Cmd, Shrd Ckt1&2BI11112Comm Loss: Cond Fan Enbl Shared Ckt 1&2BI11113Comm Loss: Expansion Valve, Ckt1BI11114Comm Loss: Expansion Valve, Ckt2BI11115Diagnostic: Oil Analysis Recommended - Ckt1BI11116Diagnostic: Oil Analysis Recommended - Ckt2BI11117Diagnostic: Oil Filter Change Recommended - Cprsr1ABI11118Diagnostic: Oil Filter Change Recommended - Cprsr2ABI11119Diagnostic: Starts or Hours Modified - Cprsr1ABI11120Comm Loss: Var Vi Valve - Cprsr 1ABI11121Diagnostic: Starts or Hours Modified - Cprsr2ABI11122Comm Loss: Var Vi Valve - Cprsr 2ABI11123Diagnostic: No Differential Rfgt Pressure - Ckt1BI11124Diagnostic: No Differential Rfgt Pressure - Ckt2BI11125Diagnostic: Low Differential Rfgt Pressure - Ckt1BI11126Diagnostic: Low Differential Rfgt Pressure - Ckt2BI11127Diagnostic: Oil Flow Protection Fault - Ckt1BI11128Diagnostic: Oil Flow Protection Fault - Ckt2BI11129Diagnostic: Low Oil Flow - Cprsr 1ABI11130Diagnostic: Low Oil Flow - Cprsr 2ABI11131Comm Loss: Cprsr Discharge Rfgt Temp, Ckt1BI11132Comm Loss: Cprsr Discharge Rfgt Temp, Ckt2BI11133Diagnostic: Discharge Rfgt Temp Sensor - Cprsr1ABI11134Diagnostic: Discharge Rfgt Temp Sensor - Cprsr2ABI11135Comm Loss: Oil Pressure, Ckt1BI11136Comm Loss: Oil Pressure, Ckt2BI11137Diagnostic: Oil Pressure Transducer - Cprsr1ABI11138Diagnostic: Oil Pressure Transducer - Cprsr2ABI11139Diagnostic: Low Discharge Superheat - Ckt1BI11140Diagnostic: Low Discharge Superheat - Ckt2BI11141Diagnostic: Very Low Evaporator Rfgt Pressure - Ckt1BI11142Diagnostic: Very Low Evaporator Rfgt Pressure - Ckt2BI11143Comm Loss: Oil Loss Level Sensor Input, Ckt1BI11144Comm Loss: Oil Loss Level Sensor Input, Ckt2BI11145Diagnostic: Loss of Oil (Stopped) - Cprsr1ABI11146Diagnostic: Loss of Oil (Stopped) - Cprsr2ABI11147Diagnostic: Loss of Oil (Running) - Cprsr1ABI11148Diagnostic: Loss of Oil (Running) - Cprsr2ABI11149Diagnostic: High Discharge Temperature - Cprsr1ABI11150Diagnostic: High Discharge Temperature - Cprsr2ABI11151Diagnostic: High Motor Winding Temperature - Cprsr1ABI11152Diagnostic: High Motor Winding Temperature - Cprsr2ABI11153Comm Loss: Winding Temp 1, Cprsr1ABI11154Comm Loss: Winding Temp 1, Cprsr2ABI11155Comm Loss: Winding Temp 2, Cprsr1ABI11156Comm Loss: Winding Temp 2, Cprsr2ABI11157Diagnostic: Motor Winding Temp Sensor - Cprsr1ABI11158Diagnostic: Motor Winding Temp Sensor - Cprsr2ABI11159Diagnostic: Failure to Arm or Start - AFD 1ABI11160Diagnostic: Failure to Arm or Start - AFD 2ABI11161Comm Loss: AFD 1ABI11162Comm Loss: AFD 2ABI11163Diagnostic: Unexpected Shutdown - AFD1ABI11164Diagnostic: Unexpected Shutdown - AFD2ABI11165Diagnostic: Interrupt Failure - AFD1ABI11166Diagnostic: Interrupt Failure - AFD2ABI11168Diagnostic: AFD 1A DSP Board Over TempBI11169Diagnostic: AFD 2A DSP Board Over TempBI11170Diagnostic: AFD 1A DSP Board Initialization FailureBI11171Diagnostic: AFD 2A DSP Board Initialization FailureBI11172Diagnostic: AFD 1A DSP Board ID ErrorBI11173Diagnostic: AFD 2A DSP Board ID ErrorBI11174Diagnostic: AFD 1A Non-Volatile Memory FailureBI11175Diagnostic: AFD 2A Non-Volatile Memory FailureBI11176Diagnostic: AFD 1A A/D Calibration ErrorBI11177Diagnostic: AFD 2A A/D Calibration ErrorBI11178Diagnostic: AFD 1A Voltage Transient Protection LossBI11179Diagnostic: AFD 2A Voltage Transient Protection LossBI11180Diagnostic: AFD 1A Watchdog Timer OverflowBI11181Diagnostic: AFD 2A Watchdog Timer OverflowBI11184Diagnostic: AFD 1A Comm Loss: Main ProcessorBI11185Diagnostic: AFD 2A Comm Loss: Main ProcessorBI11186Diagnostic: AFD 1A General FailureBI11187Diagnostic: AFD 2A General FailureBI11188Diagnostic: AFD 1A Gate Drive Module Comm LossBI11189Diagnostic: AFD 2A Gate Drive Module Comm LossBI11190Diagnostic: AFD 1A Gate Drive FaultBI11191Diagnostic: AFD 2A Gate Drive FaultBI11192Diagnostic: AFD 1A Over SpeedBI11193Diagnostic: AFD 2A Over SpeedBI11194Diagnostic: AFD 1A Motor Current OverloadBI11195Diagnostic: AFD 2A Motor Current OverloadBI11196Diagnostic: AFD 1A Ground FaultBI11197Diagnostic: AFD 2A Ground FaultBI11198Diagnostic: AFD 1A Output Phase LossBI11199Diagnostic: AFD 2A Output Phase LossBI11200Diagnostic: AFD 1A Low Rotor Flux FeedbackBI11201Diagnostic: AFD 2A Low Rotor Flux FeedbackBI11202Diagnostic: AFD 1A Bump FailureBI11203Diagnostic: AFD 2A Bump FailureBI11204Diagnostic: AFD 1A Compressor Start FailureBI11205Diagnostic: AFD 2A Compressor Start FailureBI11206Diagnostic: AFD 1A Instantaneous Current OverloadBI11207Diagnostic: AFD 2A Instantaneous Current OverloadBI11208Diagnostic: AFD 1A Desaturation DetectedBI11209Diagnostic: AFD 2A Desaturation DetectedBI11210Diagnostic: AFD 1A Current Sensor Self Test FailureBI11211Diagnostic: AFD 2A Current Sensor Self Test FailureBI11212Diagnostic: AFD 1A IGBT Self Test FailureBI11213Diagnostic: AFD 2A IGBT Self Test FailureBI11214Diagnostic: AFD 1A Gate Kill ActiveBI11215Diagnostic: AFD 2A Gate Kill ActiveBI11216Diagnostic: AFD 1A Load Inductor High TemperatureBI11217Diagnostic: AFD 2A Load Inductor High TemperatureBI11218Diagnostic: AFD 1A 12-Pulse or Auto Transf High TempBI11219Diagnostic: AFD 2A 12-Pulse or Auto Transf High TempBI11220Diagnostic: AFD 1A Inverter Heatsink Over TempBI11221Diagnostic: AFD 2A Inverter Heatsink Over TempBI11222Diagnostic: AFD 1A Rectifier Heatsink Over TempBI11223Diagnostic: AFD 2A Rectifier Heatsink Over TempBI11224Diagnostic: AFD 1A Estimated Junction Over TempBI11225Diagnostic: AFD 2A Estimated Junction Over TempBI11226Diagnostic: AFD 1A Gate Drive Board Over TempBI11227Diagnostic: AFD 2A Gate Drive Board Over TempBI11228Diagnostic: AFD 1A Bus Over VoltageBI11229Diagnostic: AFD 2A Bus Over VoltageBI11230Diagnostic: AFD 1A Bus Under VoltageBI11231Diagnostic: AFD 2A Bus Under VoltageBI11232Diagnostic: AFD 1A IMC 24V Low VoltageBI11233Diagnostic: AFD 2A IMC 24V Low VoltageBI11234Diagnostic: AFD 1A AHD Frequency Out of RangeBI11235Diagnostic: AFD 2A AHD Frequency Out of RangeBI11236Diagnostic: AFD 1A Bus Voltage Ripple Too HighBI11237Diagnostic: AFD 2A Bus Voltage Ripple Too HighBI11238Diagnostic: AFD 1A DSP Board Low Voltage FailureBI11239Diagnostic: AFD 2A DSP Board Low Voltage FailureBI11240Diagnostic: Failure to Arm or Hold - AFD 1ABI11241Diagnostic: Failure to Arm or Hold - AFD 2ABI11242Diagnostic: AFD 1A Loss of AHD Sync SignalBI11243Diagnostic: AFD 2A Loss of AHD Sync SignalBI11244Diagnostic: AFD 1A AHD Sync Signal ErrorBI11245Diagnostic: AFD 2A AHD Sync Signal ErrorBI11246Diagnostic: AFD 1A Excessive AHD InhibitBI11247Diagnostic: AFD 2A Excessive AHD InhibitBI11248Diagnostic: AFD 1A Gate Drive Low Voltage FailureBI11249Diagnostic: AFD 2A Gate Drive Low Voltage FailureBI11250Diagnostic: AFD 1A Temperature Sensor WarningBI11251Diagnostic: AFD 2A Temperature Sensor WarningBI11252Diagnostic: AFD 1A Motor ShortedBI11253Diagnostic: AFD 2A Motor ShortedBI11254Diagnostic: AFD 1A Over TemperatureBI11255Diagnostic: AFD 2A Over TemperatureBI11256Diagnostic: AFD 1A Precharge FaultBI11257Diagnostic: AFD 2A Precharge FaultBI11258Diagnostic: AFD 1A Input Phase LossBI11259Diagnostic: AFD 2A Input Phase LossBI11260Diagnostic: AFD 1A Motor FaultBI11261Diagnostic: AFD 2A Motor FaultBI11262Diagnostic: AFD 1A Customized Protection FaultBI11263Diagnostic: AFD 2A Customized Protection FaultBI11264Diagnostic: AFD 1A Input Transf or Filter Over TempBI11265Diagnostic: AFD 2A Input Transf or Filter Over TempBI11266Diagnostic: AFD 1A Loss Of Motor ControlBI11267Diagnostic: AFD 2A Loss Of Motor ControlBI11268Comm Loss: Free Cooling Entering Water TemperatureBI11269Diagnostic: Free Cooling Entering Water TemperatureBI11270Comm Loss: Free Cooling ValveBI11271Comm Loss: Free Cooling Bypass ValveBI11272Comm Loss: Free Cooling Entering Glycol TemperatureBI11273Diagnostic: Free Cooling Entering Glycol TemperatureBI11274Comm Loss: Free Cooling Leaving Glycol TemperatureBI11275Diagnostic: Free Cooling Leaving Glycol TemperatureBI11276Comm Loss: Free Cooling PumpBI11277Diagnostic: Low Glycol Temp Free CoolingBI11278Diagnostic: Free Cooling Glycol Temperature Equalization OverdueBI11279Diagnostic: Free Cooling Glycol Flow OverdueBI11280Comm Loss: Free Cooling Glycol Flow SwitchBI11281Comm Loss: Free Cooling Glycol PressureBI11282Diagnostic: Free Cooling Glycol PressureBI11283Diagnostic: Low Glycol Pressure Free CoolingBI11284Comm Loss: Free Cooling Glycol Pump FaultBI11285Diagnostic: Free Cooling Glycol Pump FaultBI11286Diagnostic: Free Cooling Glycol Flow LostBI11287Comm Loss: Free Cooling Waterside Bypass ValveBI11288Comm Loss: Free Cooling Dedicated Fan EnableBI11289Comm Loss: Free Cooling Dedicated Fan Inverter Speed CommandBI11290Comm Loss: Free Cooling Dedicated Fan Inverter FaultBI11291Diagnostic: Free Cooling Dedicated Fan Inverter FaultBI11292Diagnostic: Energy Meter Write Value FailureBV10100Reset DiagnosticBV10101Noise Reduction Request BASBV10102Chiller Auto Stop Command BASBV10103Free Cooling Auto Stop Command BASBV10104Free Cooling Compressor LockoutBV10105Circuit 1 Lockout BASBV10106Circuit 2 Lockout BASBV10107Energy Consumption ResetMI10100Running ModeMI10101Operating ModeMI10102Chiller Setpoint SourceMI10103Refrigerant TypeMI10104Cooling TypeMI10105Manufacture LocationMI10106Model Information [GEN2]MV10100Chiller Mode Command BAS
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Trane titles this list 'ACRB Small (UC800)' and does not explain the suffix in the document. Unlike the other (UC800)/(CH530) lists, this one uses the same 5-digit instances (AI 10100...) as the standard Symbio 800 lists.
- Units are printed as BACnet unit names (TEMPERATURE, PRESSURE_FLUIDIC...); the communicated unit system (I-P or SI) is set at the factory.
- Multistate state texts are printed without numbers; they are listed here in the doc's order.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 ACRB Small (UC800) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 ACRB Small (UC800)
How many BACnet points does the Trane Symbio 800 ACRB Small (UC800) have?
This list has 468 BACnet objects: 128 analog inputs, 4 analog values, 320 binary inputs, 8 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 ACRB Small (UC800) BACnet points are writable?
13 of the 468 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 ACRB Small (UC800) BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - ACRB Small (UC800) (BAS-PTS025A-EN), revision 12/06/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS025A-EN_12062024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 ACRB Small (UC800)?
Start with BV 10102 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10103 Chiller Running State (Chiller on/off status); BI 10101 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10102 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10185 Actual Running Capacity (Actual running capacity in percent); BI 10109 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 ACRB Small (UC800)?
BV 10102 Chiller Auto Stop Command BAS (Stop/Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10120 External Auto Stop Status reports the hardwired external auto/stop input, and BI 10100 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
How do I check these points on the real Symbio 800 ACRB Small (UC800)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet - ACRB Small (UC800) · BAS-PTS025A-EN · rev. 12/06/2024. Object names, instances and units are reproduced as published; descriptions are our own.