- Home
- BACnet points lists
- Trane
- Symbio 700 Precedent / Axiom
Rooftop unit controller · BACnet points list
Trane Symbio 700 Precedent / Axiom BACnet points list
Updated 6 November 2026
Symbio 700 is the factory unit controller on Precedent rooftops and Axiom rooftop water-source heat pumps. It exposes several hundred BACnet objects with 5-digit instances (AI-10101, AV-11403...) grouped by object type. Most writable objects are BAS or Setpoint values feeding Trane's arbitration logic, and several have heartbeat timeouts, so a BAS must keep refreshing them.
This page lists 639 BACnet objects for the Trane Symbio 700 Precedent / Axiom — 232 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 700 Precedent / Axiom
- Equipment
- Rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 639 (232 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- V9.00.0007
- Also known as
- Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 700 Precedent / Axiom
Leave MV 11100 Arbitration Method Request at 'Enable External/BAS Control'. Then schedule the unit with MV 10106 Occupancy Request and write space setpoints to the commandable setpoint BAS points (AV 10127, or AV 10159/10160) at a priority above 14. If the BMS supplies sensor values such as space temperature, rewrite the '... BAS' points at least every 15 minutes, or the controller drops back to its own sensors.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 10106 | Occupancy Request | Occupancy command (occupied/unoccupied/standby) | Write |
| BV 11113 | Unit Stop Command | BMS stop/auto of the whole unit | Write |
| AV 10159 | Occupied Cooling Setpoint BAS | Occupied cooling setpoint (dual-setpoint units) | Command |
| AV 10160 | Occupied Heating Setpoint BAS | Occupied heating setpoint (dual-setpoint units) | Command |
| AV 10127 | Space Temperature Setpoint BAS | Single-setpoint alternative to the two setpoints above | Command |
| MI 10101 | Heat Cool Mode Status | Current heat/cool operating mode | Read |
| MV 11123 | Occupancy Status | Confirms the occupancy the unit is running in | Read |
| BI 10226 | Supply Fan Status | Supply fan on/off status | Read |
| AV 11178 | Space Temperature Active | Space temperature the unit is actually controlling to | Read |
| BV 11100 | Alarm Indicator Status | Unit alarm output; on when the controller is in alarm | Read |
Enable & remote start
MV 11100 Arbitration Method Request picks the control type. 'Enable External/BAS Control' is the factory default: the controller weighs BAS, Air-Fi and wired sources and uses the BAS value while it is valid. 'Standalone Control' ignores all BAS input. BV 11113 Unit Stop Command (Auto/Stop) stops the unit from the BMS.
Heartbeat & communication loss
The sensor BAS points (space temp, OA temp, humidity, CO2, return air, and entering water temp on Axiom WSHPs) have a 900 s heartbeat in the points list: per the integration guide, a value that is not rewritten at least every 15 minutes fails, its priority-12 entry drops out of the Arbitrator and the controller falls back to the next source (Air-Fi, wired, then default). BV 10113 Occupancy Input BAS has the same 15-minute heartbeat. The space setpoint BAS points (AV 10127, AV 10159/10160) and MV 10106 Occupancy Request are commandable and have no heartbeat.
Sensors & values from the BMS
Write the value to the matching '... BAS' AV (e.g. AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS) and keep refreshing it. It shows on the '... Arbitrator' object at priority 12, above Air-Fi (14) and wired (15). The '... Active' object reports the value in use. Space setpoints go to AV 10127 Space Temperature Setpoint BAS (single setpoint) or AV 10159/10160 Occupied Cooling/Heating Setpoint BAS (dual setpoint).
Network setup
- The rotary address (001-127) sets the BACnet MS/TP MAC and also the Device ID; changing it takes effect without a power cycle.
- A software Device ID (1-4194302) can be set in the Symbio Service and Installation mobile app (Bluetooth) or on the onboard display.
- MS/TP default baud is 76,800 bps; MS/TP wiring lands on connector J17.
- For BACnet IP set the IP address first, then the protocol, Device ID and UDP port; tick BBMD only if this is the only BACnet IP device on the subnet.
- Communicated units can be switched between IP and SI in the mobile app or onboard display; display units are separate.
Watch out for
- Space setpoint BAS points are commandable: the wired setpoint sits at priority 15 and Air-Fi at 14, so the BMS must write at a priority above 14 or the value is ignored.
- Setpoints changed from the onboard display or mobile app go to the relinquish default, not the priority array; that value is only used when no other valid source exists.
- Use either BV 10113 Occupancy Input BAS (needs heartbeat) or MV 10106 Occupancy Request (no heartbeat), not both.
- Arbitrator objects are for reading only, even though they show as writable.
- 'Command' points may be persisted once written, so don't write them cyclically.
Trane Symbio 700 Precedent / Axiom BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10101 | Cooling Capacity Status | Actual operating unit cooling capacity, in percent | % | Read | |
| AI | 10102 | Heating Capacity Primary Status | Unit (primary) heating capacity, in percent | % | Read | |
| AI | 10104 | Outdoor Air Relative Humidity Local | OA humidity value from sensor connected to the controller | % | Read | |
| AI | 10110 | Return Air Humidity Local | Return air humidity value from sensor connected to the controller | % | Read | |
| AI | 10111 | Outdoor Air Damper Position | OA Damper Actuator feedback signal | % | Read | |
| AI | 10116 | Space Humidity Active | Active space relative humidity being used by the controller | % | Read | |
| AI | 10117 | Outdoor Air Dew Point | The outdoor air dewpoint value being utilized by the unit | °F | Read | |
| AI | 10118 | Outdoor Air Temperature Active | Active OA temperature currently being used by the controller | °F | Read | |
| AI | 10120 | Outdoor Air Humidity Active | Active outdoor air humidity value used by the controller | % | Read | |
| AI | 10124 | Discharge Air Temperature Local | Discharge air temperature value from a sensor connected to the controller | °F | Read | |
| AI | 10126 | Return Air Temperature Input | Actual return air temperature being used by the controller | °F | Read | |
| AI | 10155 | Duct Static Pressure Local | Duct static pressure value from a sensor connected to the controller | In. of water | Read | |
| AI | 10156 | Outdoor Air Temperature Local | OA temp value from a sensor connected to the controller | °F | Read | |
| AI | 10182 | Duct Static Pressure Active | Duct static pressure active value for communication to SC graphics | In. of water | Read | |
| AI | 10218 | Space Temperature Input | Space temp from a wired sensor | °F | Read | |
| AI | 10226 | Space Dew Point | Calculated Space Dewpoint | °F | Read | |
| AI | 11100 | Coil Temperature Sensor 1 | Outdoor Coil Temperature Sensor for Circuit 1 on HP units | °F | Read | |
| AI | 11103 | Space CO2 Concentration Input | Space CO2 concentration from a sensor hardwired to the controller | PPM | Read | |
| AI | 11104 | Space Humidity Input | Space relative humidity from a sensor wired to the controller | % | Read | |
| AI | 11106 | Supply Fan Speed Command Status | Unit commanded supply fan speed output | % | Read | |
| AI | 11109 | Modulating Heat Command Status | Unit commanded modulating heat output | % | Read | |
| AI | 11111 | Outdoor Air Damper Command | Unit commanded outside air damper position | % | Read | |
| AI | 11132 | On-Board I/O Firmware Major Version | Software Major Version for On-Board I/O Module | Read | ||
| AI | 11133 | On-Board I/O Firmware Minor Version | On-Board I/O Module Software build number | Read | ||
| AI | 11134 | Indoor Options Module Firmware Major Version | Software Major Version for Indoor Options Module | Read | ||
| AI | 11135 | Indoor Options Module Firmware Minor Version | Indoor Options Module Software build number | Read | ||
| AI | 11136 | Fresh Air Options Module Firmware Major Version | Software Major Version for Fresh Air Options Module | Read | ||
| AI | 11137 | Fresh Air Options Module Firmware Minor Version | Fresh Air Options Module Software build number | Read | ||
| AI | 11140 | Customer Options Module Firmware Major Version | Software Major Version for Customer Connection Options Module | Read | ||
| AI | 11141 | Customer Options Module Firmware Minor Version | Customer Options Module Software build number | Read | ||
| AI | 11142 | IGN Module 1 Firmware Major Version | Software Major Version for Gas Heat Ignition Module 1 | Read | ||
| AI | 11143 | IGN Module 1 Firmware Minor Version | Software Minor Version for Gas Heat Ignition Module 1 | Read | ||
| AI | 11148 | Remote Minimum Position | Hardwired remote minimum position for OA damper control | % | Read | |
| AI | 11149 | Return Air Temperature Active | Return Air Temperature being used for control | °F | Read | |
| AI | 11150 | Sensor Battery Status Air-Fi | Status percentage of connected AirFi sensor(s) | % | Read | |
| AI | 11151 | Space CO2 Concentration Air- Fi | Space CO2 concentration from a wireless sensor connected to the controller | PPM | Read | |
| AI | 11152 | Space Humidity Air-Fi | Space relative humidity from a connected wireless sensor | % | Read | |
| AI | 11154 | Space Temperature Air-Fi | Space temp from a connected wireless (AirFi) sensor | °F | Read | |
| AI | 11155 | Space Temperature Cooling Setpoint Air-Fi | (occupied) cooling setpoint from the connected wireless space sensor | °F | Read | |
| AI | 11156 | Space Temperature Heating Setpoint Air-Fi | (occupied) heating setpoint from the connected wireless space sensor | °F | Read | |
| AI | 11157 | Space Temperature Setpoint Air-Fi | Space Temperature Setpoint from a connected wireless sensor | °F | Read | |
| AI | 11159 | Space Temperature Cooling Setpoint Input | (occupied) cooling setpoint from the connected wired space sensor | °F | Read | |
| AI | 11160 | Space Temperature Heating Setpoint Input | (occupied) heating setpoint from the connected wired space sensor | °F | Read | |
| AI | 11161 | Space Temperature Setpoint Input | Space Temperature Setpoint from a connected wired sensor | °F | Read | |
| AI | 11164 | Reheat Valve 1 Step Status | Reheat Valve 1 Status in steps from Stepper Motor Module | Read | ||
| AI | 11166 | Evaporator Entering Refrigerant Temperature | °F | Read | ||
| AI | 11167 | Stepper Motor Module Firmware Major Version | Software Major Version for Stepper Motor Module | Read | ||
| AI | 11168 | Stepper Motor Module Firmware Minor Version | Stepper Motor Module Software build number | Read | ||
| AI | 11169 | Saturated Discharge Temperature | Saturated Discharge Temperature sensor used in Ultra High Efficiency | °F | Read | |
| AI | 11170 | Supply Fan Entering Air Temperature | Air temp entering the supply fan | °F | Read | |
| AI | 11171 | Entering Water Temperature Active | Active Entering Water temperature currently being used by the controller | °F | Read | |
| AI | 11172 | Entering Water Temperature Local | Entering Water temperature value from a sensor connected to the controller | °F | Read | |
| AI | 11173 | Outdoor Air Damper Feedback | OA Damper Actuator feedback signal | % | Read | |
| AV | 10103 | Outdoor Air Temperature Arbitrator | OA temp determined by arbitration | °F | Write | |
| AV | 10104 | Outdoor Air Humidity Arbitrator | Actual outdoor air humidity being used by the controller | % | Write | |
| AV | 10106 | Space Temperature Arbitrator | Space temp determined by arbitration | °F | Write | |
| AV | 10108 | Space CO2 Concentration Arbitrator | Space CO2 concentration being used by the controller | PPM | Write | |
| AV | 10109 | Space Humidity Arbitrator | Space relative humidity, determined by the arbitration | % | Write | |
| AV | 10113 | Outdoor Air Temperature BAS | Send the outdoor air temperature sensor value | °F | Write | |
| AV | 10114 | Space Temperature BAS | Send the space temperature value | °F | Write | |
| AV | 10116 | Outdoor Air Humidity BAS | Send the outdoor air humidity sensor value | % | Write | |
| AV | 10118 | Space CO2 Concentration BAS | Send the space CO2 concentration value | PPM | Write | |
| AV | 10119 | Space Humidity BAS | Send the space relative humidity value | % | Write | |
| AV | 10121 | Discharge Air Cooling Setpoint BAS | Request the discharge air temp cooling setpoint value | °F | Command | |
| AV | 10122 | Discharge Air Heating Setpoint BAS | Request the discharge air temperature heating setpoint value | °F | Command | |
| AV | 10123 | Unoccupied Cooling Setpoint | Define the cooling temp setpoint used for control in unoccupied mode | °F | Write | |
| AV | 10124 | Unoccupied Heating Setpoint | Define the heating temp setpoint used for control in unoccupied mode | °F | Write | |
| AVmin | 10127 | Space Temperature Setpoint BAS | BAS-supplied space temperature setpoint value | °F | Command | |
| AV | 10130 | Occupied Offset | Difference between the occupied cool and heat setpts | ∆°F | Write | |
| AV | 10134 | Discharge Air Reheat Setpoint BAS | Request the discharge air temperature reheat setpoint value, for dehumidification control | °F | Command | |
| AV | 10138 | Filter Runtime Hours Setpoint | The setpoint value used by the filter run hours calculation | Command | ||
| AV | 10139 | Cooling Capacity Enable | Limit the cooling capacity of the unit; 0% = no cooling possible | % | Command | |
| AV | 10140 | Heat Primary Enable BAS | Demand limit the heating capacity; 0% = No Heating Possible | % | Command | |
| AV | 10141 | Morning Warmup Setpoint BAS | Defines the space temp below which MWU is enabled | °F | Command | |
| AV | 10142 | Occupied Standby Offset | Difference between the occupied standby cool and heat setpts | ∆°F | Write | |
| AV | 10143 | Duct Static Pressure Setpoint BAS | Request the duct static pressure setpoint value | In. of water | Command | |
| AV | 10144 | Economizer Minimum Position Setpoint BAS | Request the ecominizer minimum position setpoint | % | Command | |
| AV | 10149 | Daytime Warmup Setpoint BAS | Defines the space temp below which daytime warmup will be enabled | °F | Command | |
| AV | 10150 | Economizer Outdoor Air Enable Setpoint BAS | Temperature setpoint below which economizing can be used | °F | Command | |
| AV | 10154 | Space Cooling Setpoint High Limit BAS | °F | Write | ||
| AV | 10155 | Space Cooling Setpoint Low Limit BAS | °F | Write | ||
| AV | 10157 | Space Heating Setpoint High Limit BAS | °F | Write | ||
| AV | 10158 | Space Heating Setpoint Low Limit BAS | °F | Write | ||
| AVmin | 10159 | Occupied Cooling Setpoint BAS | Define the occupied cooling setpt | °F | Command | |
| AVmin | 10160 | Occupied Heating Setpoint BAS | Define the occupied heating setpt | °F | Command | |
| AV | 10161 | Occupied Standby Cooling Setpoint BAS | Defines the occupied standby cooling setpt when both heat/cool setpoints are provided | °F | Command | |
| AV | 10162 | Occupied Standby Heating Setpoint BAS | Defines the occupied standby heating setpt when both heat/cool setpoints are provided | °F | Command | |
| AV | 10167 | Discharge Air Temperature Minimum Cool Limit | Define the discharge air temperature minimum cool limit | °F | Command | |
| AV | 10168 | Relief Enable Position Setpoint | The OA damper position above which the Relief sequence is enabled | % | Command | |
| AV | 10169 | Occupied Bypass Time | Configure the occupied bypass time (occupancy override) | Write | ||
| AV | 10170 | Economizer Outdoor Air Enthalpy Enable Setpoint BAS | Determine the outdoor air enthalpy below which economizing is enabled | BTUs/pound | Command | |
| AV | 10175 | Space CO2 High Limit | Define the CO2 high limit, for ventilation purposes | PPM | Command | |
| AV | 10176 | Space CO2 Low Limit | Define the CO2 low limit | PPM | Command | |
| AV | 10214 | Space Dehumidification Unoccupied Setpoint Active | Active value for Space Dehumidification Setpoint BAS point being used for control | % | Read | |
| AV | 10228 | Space Dew Point Unoccupied Setpoint Active | Unoccupied Space Dew Point Setpoint actively being used for dehumidification control | °F | Read | |
| AV | 10281 | Discharge Air Temperature Setpoint Active | Discharge air temp setpoint actively being used for control | °F | Read | |
| AV | 11103 | Return Air Humidity BAS | BAS Source for Return Air Humidity | % | Write | |
| AV | 11108 | Cabinet Style | Cabinet style of the unit | Read | ||
| AV | 11110 | Supply Fan Speed Command | Remote supply fan speed request | % | Command | |
| AV | 11112 | Cooling Capacity Setpoint BAS | Remote cooling capacity request | % | Command | |
| AV | 11113 | Space Dehumidification Setpoint Offset BAS - Active | The active value for the offset applied to the Space Dehumidification Setpoint | % | Read | |
| AV | 11115 | Exhaust Or Return Fan Type | Identifies the product exhaust or return fan type | Read | ||
| AV | 11116 | Filter Runtime Hours | Number of hours air has flowed through the filter | Read | ||
| AV | 11117 | Outdoor Air Enthalpy Active | The outdoor air enthalpy value being utilized by the unit | BTUs/pound | Read | |
| AV | 11118 | Return Air Temperature Arbitrator | Arbitrator for Return Air Temperature | °F | Write | |
| AV | 11119 | Return Air Temperature BAS | BAS source for Return Air Temperature | °F | Write | |
| AV | 11120 | Heating Demand Limit Capacity Enable Setpoint | % | Command | ||
| AV | 11121 | Discharge Air Temperature Maximum Cool Limit | Maximum discharge air temperature allowed during space temperature cooling mode of operation | °F | Command | |
| AV | 11122 | Run Time - Condenser Fan 1 (Hours) | Condenser Fan 1 Runtime | Read | ||
| AV | 11123 | Run Time - Condenser Fan 2 (Hours) | Condenser Fan 2 Runtime | Read | ||
| AV | 11124 | Run Time - Relief Fan (Hours) | Relief Fan Runtime | Read | ||
| AV | 11125 | Run Time - Electric Heat Stage 1 (Hours) | Electric Heat Stage 1 Runtime | Read | ||
| AV | 11126 | Run Time - Electric Heat Stage 2 (Hours) | Electric Heat Stage 2 Runtime | Read | ||
| AV | 11127 | Run Time - Supply Fan (Hours) | Supply Fan Runtime | Read | ||
| AV | 11128 | Space Temp Cooling Setpoint Status | Space cooling setpoint, being used by the controller | °F | Read | |
| AV | 11129 | Space Temp Heating Setpoint Status | Space heating setpoint, being used by the controller | °F | Read | |
| AV | 11130 | Design Minimum OA Damper Position at Full Fan Capacity | % | Command | ||
| AV | 11131 | Design Minimum OA Damper Position at Mid Fan Capacity | % | Command | ||
| AV | 11132 | Design Minimum OA Damper Position at Min Fan Capacity | % | Command | ||
| AV | 11133 | DCV Minimum OA Damper Position at Full Fan Capacity | % | Command | ||
| AV | 11134 | DCV Minimum OA Damper Position at Mid Fan Capacity | % | Command | ||
| AV | 11135 | DCV Minimum OA Damper Position at Min Fan Capacity | % | Command | ||
| AV | 11136 | Space Dehumidification Setpoint BAS - Active | The active value for the Space Dehumidification Setpoint for Relative Humidity control | % | Read | |
| AV | 11137 | Discharge Air Heating Setpoint High Limit | Discharge Air Heating Setpoint High Limit (deg F) | °F | Command | |
| AV | 11138 | Discharge Air Heating Setpoint (Target) | °F | Command | ||
| AV | 11140 | Discharge Air Cooling Setpoint (Target) | °F | Command | ||
| AV | 11147 | Economizer Dry Bulb Enable Offset | Outdoor air temperature offset below dry bulb economizer enable setpoint | ∆°F | Write | |
| AV | 11148 | Duct Static Pressure P-Gain (%/IWC) | Proportional gain for fan speed on duct static pressure control (%/IWC) | % | Write | |
| AV | 11149 | Duct Static Pressure Deadband BAS | Supply Air Pressure Setpoint Deadband | In. of water | Command | |
| AV | 11150 | Cooling Reset Start Temp | Discharge air cooling reset start temperature | °F | Write | |
| AV | 11151 | Cooling Reset End Temp | Discharge air cooling reset end temperature | °F | Write | |
| AV | 11152 | Cooling Reset Amount | Discharge air cooling amount to reset between start and end temperatures | ∆°F | Write | |
| AV | 11153 | Service Test Timeout (Minutes) | Timer (minutes) to indicate when the unit should cease service test | Write | ||
| AV | 11154 | Economizer Cooling Reference Enthalpy Offset | BTUs/pound | Write | ||
| AV | 11155 | Starts - Condenser Fan 1 | Condenser Fan 1 Starts | Read | ||
| AV | 11156 | Starts - Condenser Fan 2 | Condenser Fan 2 Starts | Read | ||
| AV | 11157 | Starts - Relief Fan | Relief Fan Starts | Read | ||
| AV | 11158 | Starts - Electric Heat Stage 1 | Electric Heat Stage 1 Starts | Read | ||
| AV | 11159 | Starts - Electric Heat Stage 2 | Electric Heat Stage 2 Starts | Read | ||
| AV | 11160 | Starts - Supply Fan | Counter for Supply Fan Starts | Read | ||
| AV | 11161 | Supply Fan Type | Unit supply fan type | Read | ||
| AV | 11163 | Supply Fan Speed Status | Estimated supply fan speed being utilized | % | Read | |
| AV | 11164 | Heating Capacity Setpoint BAS | Setpoint to command the unit to a given heating capacity output | % | Command | |
| AV | 11167 | Demand Shed Offset Setpoint | ∆°F | Command | ||
| AV | 11168 | Cooling Demand Limit Capacity Enable Setpoint | % | Command | ||
| AV | 11169 | Run Time - Compressor 1 (Hours) | Compressor 1 Runtime | Read | ||
| AV | 11170 | Run Time - Compressor 2 (Hours) | Compressor 2 Runtime | Read | ||
| AV | 11173 | Supply Fan Minimum Speed Setpoint | Minimum supply fan speed command | % | Command | |
| AV | 11174 | Supply Fan Maximum Speed Setpoint | Maximum supply fan speed command | % | Command | |
| AVmin | 11178 | Space Temperature Active | Active space temperature being used by the controller | °F | Read | |
| AV | 11180 | Space Temperature Heating Setpoint Input Active | Active heating space temperature input setpoint | °F | Read | |
| AV | 11181 | Space Temperature Setpoint Active | Active space temperature setpoint being used by the controller | °F | Read | |
| AV | 11183 | Starts - Compressor 1 | Compressor 1 Starts | Read | ||
| AV | 11184 | Starts - Compressor 2 | Compressor 2 Starts | Read | ||
| AV | 11185 | Cooling Capacity Enable - Active | Active value for Cooling Capacity Enable point being used for control | % | Read | |
| AV | 11186 | Daytime Warmup Setpoint BAS - Active | Active value for Daytime Warmup Setpoint BAS point being used for control | °F | Read | |
| AV | 11187 | Supply Fan Speed Command - Active | Active value for Supply Fan Speed Command point being used for control | % | Read | |
| AV | 11189 | Cooling Capacity Setpoint BAS - Active | Active value for Cooling Capacity Setpoint BAS point being used for control | % | Read | |
| AV | 11190 | Discharge Air Cooling Setpoint BAS - Active | °F | Read | ||
| AV | 11191 | Discharge Air Heating Setpoint BAS - Active | °F | Read | ||
| AV | 11192 | Discharge Air Reheat Setpoint BAS - Active | °F | Read | ||
| AV | 11193 | Discharge Air Temperature Minimum Cool Limit - Active | °F | Read | ||
| AV | 11195 | Economizer Minimum Position Setpoint BAS - Active | % | Read | ||
| AV | 11196 | Economizer Outdoor Air Enthalpy Enable Setpoint BAS - Active | BTUs/pound | Read | ||
| AV | 11197 | Economizer Outdoor Air Enable Setpoint BAS - Active | °F | Read | ||
| AV | 11198 | Relief Enable Position Setpoint - Active | Active value for Relief Enable Position Setpoint point being used for control | % | Read | |
| AV | 11199 | Heating Demand Limit Capacity Enable Setpoint - Active | % | Read | ||
| AV | 11200 | Discharge Air Temperature Maximum Cool Limit - Active | °F | Read | ||
| AV | 11202 | Cool Type | Describes the type of cooling in the unit | Read | ||
| AV | 11204 | DCV Minimum OA Damper Position at Full Fan Capacity - Active | % | Read | ||
| AV | 11205 | DCV Minimum OA Damper Position at Mid Fan Capacity - Active | % | Read | ||
| AV | 11206 | DCV Minimum OA Damper Position at Min Fan Capacity - Active | % | Read | ||
| AV | 11209 | Demand Shed Offset Setpoint - Active | Active value for Demand Shed Offset Setpoint point being used for control | ∆°F | Read | |
| AV | 11211 | Design Minimum OA Damper Position at Full Fan Capacity - Active | % | Read | ||
| AV | 11212 | Design Minimum OA Damper Position at Mid Fan Capacity - Active | % | Read | ||
| AV | 11213 | Design Minimum OA Damper Position at Min Fan Capacity - Active | % | Read | ||
| AV | 11214 | Economizer Dry Bulb Disable Return Air Offset | Differential dry bulb economizer disable offset | ∆°F | Write | |
| AV | 11217 | Filter Runtime Hours Setpoint - Active | Active value for Filter Runtime Hours Setpoint point being used for control | Read | ||
| AV | 11218 | Heat Primary Enable BAS - Active | Active value for Heat Primary Enable BAS point being used for control | % | Read | |
| AV | 11219 | Heating Capacity Setpoint BAS - Active | Active value for Heating Capacity Setpoint BAS point being used for control | % | Read | |
| AV | 11220 | Morning Warmup Setpoint BAS - Active | Active value for Morning Warmup Setpoint BAS point being used for control | °F | Read | |
| AV | 11226 | Space CO2 High Limit - Active | Active value for Space CO2 High Limit point being used for control | PPM | Read | |
| AV | 11227 | Space CO2 Low Limit - Active | Active value for Space CO2 Low Limit point being used for control | PPM | Read | |
| AV | 11236 | Discharge Air Cooling Setpoint (Target) - Active | Active value for Discharge Air Cooling Setpoint | °F | Read | |
| AV | 11237 | Discharge Air Heating Setpoint High Limit - Active | °F | Read | ||
| AV | 11238 | Duct Static Pressure Reset Time (seconds) | Reset time for fan speed on duct static pressure control (seconds) | Write | ||
| AV | 11240 | Duct Static Pressure Deadband Active | In. of water | Read | ||
| AV | 11241 | Heating Reset Start Temp | Discharge air heating reset start temperature | °F | Write | |
| AV | 11242 | Heating Reset End Temp | Discharge air heating reset end temperature | °F | Write | |
| AV | 11243 | Supply Fan Maximum Speed Setpoint - Active | % | Read | ||
| AV | 11245 | Supply Fan Minimum Speed Setpoint - Active | % | Read | ||
| AV | 11247 | Cooling Demand Limit Capacity Enable Setpoint - Active | % | Read | ||
| AV | 11248 | Economizer Minimum Position Setpoint Active | Economizer min position setpoint value resulting from arbitration | % | Read | |
| AV | 11249 | Heating Capacity Secondary Status | Unit secondary heating capacity being utilized | % | Read | |
| AV | 11250 | Occupied Standby Cooling Setpoint BAS - Active | Active value for Occupied Standby Cooling Setpoint BAS | °F | Read | |
| AV | 11251 | Occupied Standby Heating Setpoint BAS - Active | Active value for Occupied Standby Heating Setpoint BAS | °F | Read | |
| AV | 11252 | Preheat Type | Identifies the product preheat type | Read | ||
| AV | 11253 | Reheat Type | Identifies the product reheat type | Read | ||
| AV | 11254 | Space CO2 Concentration Active | Active space CO2 concentration being used by the controller | PPM | Read | |
| AV | 11256 | Compressor Cooling P-Gain (%/F) | Proportional gain for single loop Compressor Cooling PI controller (%/F) | % | Write | |
| AV | 11257 | Compressor Cooling Reset Time (seconds) | Reset time for single loop compressor Cooling PI controller (second) | Write | ||
| AV | 11258 | Economizer Cooling P-Gain - 1 (%/F) | Proportional gain for 1st loop Econ PI controller (%/F), for CVZT/VVZT systems | % | Write | |
| AV | 11259 | Economizer Cooling Reset Time - 1 (Seconds) | Reset time for 1st loop Econ PI controller (seconds), for CVZT/VVZT systems | Write | ||
| AV | 11264 | Compressor Heating P-Gain (%/F) | Proportional gain for single loop Heat Pump Heating PI controller (%/F) | % | Write | |
| AV | 11265 | Compressor Heating Reset Time (seconds) | Reset time for single loop Heat Pump Heating PI controller (seconds) | Write | ||
| AV | 11266 | Auxiliary Heating P-Gain (%/F) | Proportional gain for Electric single loop PI controller (%/F) | % | Write | |
| AV | 11267 | Auxiliary Heating Reset Time (seconds) | Reset time for Electric single loop PI controller (in seconds) | Write | ||
| AV | 11268 | Compressor Cooling P-Gain - 1 (%/F) | Proportional gain for 1st loop Cooling PI controller (%/F) | % | Write | |
| AV | 11269 | Compressor Cooling Reset Time - 1 (seconds) | Reset time for 1st loop Cooling PI controller (second) | Write | ||
| AV | 11270 | Compressor Cooling P-Gain - 2 (%/F) | Proportional gain for 2nd loop compressor cooling PI controller (%/F) | % | Write | |
| AV | 11271 | Compressor Cooling Reset Time - 2 (seconds) | Reset time for 2nd loop compressor cooling PI controller (second) | Write | ||
| AV | 11272 | Economizer Discharge Air Setpoint | °F | Command | ||
| AV | 11273 | Economizer Discharge Air Setpoint - Active | °F | Read | ||
| AV | 11274 | Heat Pump Heating Lockout Setpoint | °F | Command | ||
| AV | 11275 | Heat Pump Heating Lockout Setpoint - Active | °F | Read | ||
| AV | 11276 | Space Temperature Setpoint Input Active | Active space temperature input setpoint | °F | Read | |
| AV | 11277 | Space Temperature Cooling Setpoint Input Active | Active cooling space temperature input setpoint | °F | Read | |
| AV | 11278 | Supply Fan Power | Supply Fan Drive Output Power | kW | Read | |
| AV | 11280 | Duct Static Pressure Setpoint Active | Duct static pressure control setpoint value resulting from arbitration | In. of water | Read | |
| AV | 11281 | Dehumidification Control Status | Status of the unit dehumidification capacity | % | Read | |
| AV | 11282 | Supply Fan 1 Maximum RPM Status | Read | |||
| AV | 11283 | Supply Fan Minimum RPM Status | Read | |||
| AV | 11284 | Run Time - Supply Fan 2 (Hours) | Supply Fan 2 Runtime | Read | ||
| AV | 11285 | Starts - Supply Fan 2 | Counter for Supply Fan 2 Starts | Read | ||
| AV | 11286 | Motorized Damper Position Setpoint | % | Command | ||
| AV | 11287 | Motorized Damper Position Setpoint - Active | Active value for Motorized Damper Position Setpoint | % | Read | |
| AV | 11288 | Standby Minimum OA Damper Position at Full Fan Capacity | % | Command | ||
| AV | 11289 | Standby Minimum OA Damper Position at Full Fan Capacity - Active | % | Read | ||
| AV | 11290 | Standby Minimum OA Damper Position at Mid Fan Capacity | % | Command | ||
| AV | 11291 | Standby Minimum OA Damper Position at Mid Fan Capacity - Active | % | Read | ||
| AV | 11292 | Standby Minimum OA Damper Position at Min Fan Capacity | % | Command | ||
| AV | 11293 | Standby Minimum OA Damper Position at Min Fan Capacity - Active | % | Read | ||
| AV | 11294 | Supply Fan 2 Power | Supply Fan 2 Output Power | kW | Read | |
| AV | 11295 | Run Time - Gas Heat Stage 1 (Hours) | Gas heat Stage 1 Runtime | Read | ||
| AV | 11296 | Starts - Gas Heat Stage 1 | Gas heat Stage 1 Starts | Read | ||
| AV | 11297 | Run Time - Gas Heat Stage 2 (Hours) | Gas heat Stage 2 Runtime | Read | ||
| AV | 11298 | Starts - Gas Heat Stage 2 | Gas heat Stage 2 Starts | Read | ||
| AV | 11299 | Return Air Humidity Active | Active Return Air Humidity sensor used for control | % | Read | |
| AV | 11300 | Return Air Humidity Arbitrator | Arbitrator for Return Air Humidity | % | Write | |
| AV | 11301 | Return Air Enthalpy Active | The return air enthalpy value being utilized by the unit | BTUs/pound | Read | |
| AV | 11302 | Relief Enable Position Setpoint Status | Outdoor air damper position to enable Relief sequence | % | Read | |
| AV | 11304 | Supply Fan RPM | Supply Fan 1 RPM | Read | ||
| AV | 11305 | Supply Fan 2 RPM | Read | |||
| AV | 11306 | Supply Fan 2 Maximum RPM Status | Read | |||
| AV | 11307 | Discharge Air Heating Setpoint (Target) - Active | Active value for Discharge Air Heating Setpoint | °F | Read | |
| AV | 11308 | Duct Static Pressure Setpoint High Limit Setpoint BAS | In. of water | Command | ||
| AV | 11309 | Duct Static Pressure Setpoint High Limit Setpoint BAS - Active | In. of water | Read | ||
| AV | 11314 | Comfort Purge Interval (minutes) | Write | |||
| AV | 11315 | Reheat Purge Interval (minutes) | Write | |||
| AV | 11316 | Reheat P-Gain 1 | Proportional gain for 1st loop Reheat PI controller (%/F) | % | Write | |
| AV | 11317 | Reheat Reset Time - 1 | Reset time for 1st loop Reheat PI controller (second) | Write | ||
| AV | 11318 | Reheat P-Gain 2 | Proportional gain for 2nd loop Reheat PI controller (%/F) | % | Write | |
| AV | 11319 | Reheat Reset Time - 2 | Reset time for discharge air Reheat PI controller (second) | Write | ||
| AV | 11320 | Space Dew Point Setpoint BAS | °F | Write | ||
| AV | 11321 | Dew Point Setpoint Offset BAS | °F | Write | ||
| AV | 11323 | Outdoor Air Dew Point Setpoint BAS | °F | Write | ||
| AV | 11326 | Space Dehumidification Setpoint Offset BAS | % | Write | ||
| AV | 11327 | Space Dehumidification Setpoint BAS | Setting for unit to use to control dehumidification | % | Write | |
| AV | 11329 | Space Dehumidification Unoccupied Setpoint BAS | Define the (occupied) space dehumidification setpoint | % | Command | |
| AV | 11330 | Space Dew Point Unoccupied Setpoint BAS | °F | Write | ||
| AV | 11331 | Compressor Dehumid P-Gain 2 | Proportional Gain for 2nd loop Compressor Dehumid PI controller (%/deg F) | °F | Write | |
| AV | 11332 | Compressor Dehumid P-Gain 1 | Proportional gain for 1st loop Compressor Dehumid PI controller (%/F) | °F | Write | |
| AV | 11333 | Compressor Dehumid Reset Time - 2 (seconds) | Reset time for 2nd loop compressor Dehumid PI controller (second) | Write | ||
| AV | 11334 | Compressor Dehumid Reset Time - 1 (seconds) | Reset time for 1st loop Dehumid PI controller (second) | Write | ||
| AV | 11335 | Pre Cool Setpoint BAS | Defines the space temp above which Pre Cool is enabled | °F | Command | |
| AV | 11336 | Pre Cool Setpoint BAS - Active | Active value for Pre Cool Setpoint BAS point being used for control | °F | Read | |
| AV | 11337 | Refrigerant Target Setpoint Active | Refrigerant target setpoint actively being used for dehumidification control | °F | Read | |
| AV | 11338 | Space Dew Point Setpoint Active | Occupied Space Dew Point Setpoint actively being used for dehumidification control | °F | Read | |
| AV | 11340 | Dew Point Setpoint Offset BAS - Active | Dew Point Setpoint Offset actively being used for dehumidification control | °F | Read | |
| AV | 11341 | Outdoor Air Dew Point Setpoint BAS - Active | Outdoor Air Dew Point Setpoint Offset actively being used for dehumidification control | °F | Read | |
| AV | 11342 | Unoccupied Dehumidification Timer | Write | |||
| AV | 11343 | Heating Reset Amount | Discharge air heating amount to reset between start and end temperatures | ∆°F | Write | |
| AV | 11344 | VAV Box Stroke Timer | Write | |||
| AV | 11346 | Economizer Cooling P-Gain (%/F) | Proportional gain for VVDA systems Econ PI controller (%/F) | % | Write | |
| AV | 11347 | Economizer Cooling Reset Time (Seconds) | Reset time for VVDA systems Econ PI controller (in seconds) | Write | ||
| AV | 11348 | Economizer Cooling P-Gain - 2 (%/F) | Proportional gain for 2nd loop Econ PI controller (%/F), for CVZT/VVZT systems | % | Write | |
| AV | 11349 | Economizer Cooling Reset Time - 2 (Seconds) | Reset time for 2nd loop Econ PI controller (seconds), for CVZT/VVZT systems | Write | ||
| AV | 11350 | Auxiliary Heating P-Gain - 1 (%/F) | Space control proportional gain for 1st loop Heating PI controller (%/F) | % | Write | |
| AV | 11351 | Auxiliary Heating Reset Time - 1 (seconds) | Space control reset Time for 1st loop Auxiliary Heating PI Controller | Write | ||
| AV | 11352 | Auxiliary Heating P-Gain - 2 (%/F) | Space control proportional gain for 2nd loop Heating PI controller (%/F) | % | Write | |
| AV | 11353 | Auxiliary Heating Reset Time - 2 (seconds) | Space control reset Time for 2nd loop Auxiliary Heating PI Controller | Write | ||
| AV | 11354 | Discharge Air Heating Setpoint Low Limit | Discharge Air Heating Setpoint Low Limit (deg F) | °F | Command | |
| AV | 11355 | Discharge Air Heating Setpoint Low Limit - Active | °F | Read | ||
| AV | 11356 | Discharge Air Cooling Setpoint Status | Actual discharge air cooling setpoint value being used for control | °F | Read | |
| AV | 11357 | Discharge Air Heating Setpoint Status | Actual discharge air heating setpoint value being used for control | °F | Read | |
| AV | 11358 | Discharge Air Reheating Setpoint High Limit - Active | °F | Read | ||
| AV | 11359 | Discharge Air Reheating Setpoint Low Limit - Active | °F | Read | ||
| AV | 11360 | Discharge Air Reheating Setpoint High Limit | Discharge Air Reheating Setpoint High Limit (deg F) | °F | Command | |
| AV | 11361 | Discharge Air Reheating Setpoint Low Limit | Discharge Air Reheating Setpoint Low Limit (deg F) | °F | Command | |
| AV | 11362 | Run Time - Gas Heat Manifold 1 Burner 1 (Hours) | Gas heat runtime | Read | ||
| AV | 11363 | Starts - Gas Heat Manifold 1 Burner 1 | Gas heat starts | Read | ||
| AV | 11364 | Run Time - Gas Heat Manifold 1 Burner 2 (Hours) | Gas heat runtime | Read | ||
| AV | 11365 | Starts - Gas Heat Manifold 1 Burner 2 | Gas heat starts | Read | ||
| AV | 11368 | Auxiliary Heating P-Gain Modulating Gas Staging (%/F) | Proportional gain for 2nd loop- Staging control for Modulating Gas Heating | % | Write | |
| AV | 11369 | Auxiliary Heating Reset Time Modulating Gas Staging (seconds) | Reset Time for 2nd loop- Staging control for Modulating Gas Heating | Write | ||
| AV | 11375 | Run Time - Circuit 1 Condenser Defrost (Hours) | Circuit 1 Condenser Defrost Run Time | Read | ||
| AV | 11376 | Starts - Circuit 1 Condenser Defrost | Circuit 1 Condenser Defrost Starts | Read | ||
| AV | 11383 | Condenser Fan Capacity | Status of the total unit condenser fan capacity | % | Read | |
| AV | 11384 | Compressor Cooling Modulating P-Gain - 2 (%/F) | Proportional gain for 2nd loop modulating compressor cooling PI controller (%/F) | % | Write | |
| AV | 11385 | Compressor Cooling Modulating Reset Time - 2 (seconds) | Reset time for 2nd loop modulating compressor cooling PI controller (second) | Write | ||
| AV | 11386 | Compressor Cooling Modulating P-Gain (%/F) | Proportional gain for discharge air control - modulating compressor cooling PI controller | % | Write | |
| AV | 11387 | Compressor Cooling Modulating Reset Time (seconds) | Reset time for discharge air controls - modulating compressor cooling PI controller | Write | ||
| AV | 11388 | Control State | Control State Status | Read | ||
| AV | 11389 | Demand Defrost Initiate Delta Temperature | ∆°F | Read | ||
| AV | 11392 | Discharge Air Cooling Setpoint Y1 | Request discharge air temp cooling setpoint value | °F | Command | |
| AV | 11393 | Discharge Air Cooling Setpoint Y1 - Active | °F | Read | ||
| AV | 11394 | Discharge Air Cooling Setpoint Y2 | Request discharge air temp cooling setpoint value | °F | Command | |
| AV | 11395 | Discharge Air Cooling Setpoint Y2 - Active | °F | Read | ||
| AV | 11398 | Dehumidification Disable Space Temperature Setpoint | Value used to disable Dehumidification when compared to the Space Temperature | °F | Write | |
| AV | 11399 | Supply Fan Maximum Speed Setpoint Heating | Maximum supply fan speed command Heating | % | Write | |
| AV | 11400 | Low Saturated Suction Refrig Temp Abnormal Deviation Offset | ∆°F | Write | ||
| AV | 11401 | Low Saturated Suction Refrig Temp Coefficient 1 | Write | |||
| AV | 11402 | Low Saturated Suction Refrig Temp Coefficient 2 | Write | |||
| AV | 11403 | Entering Water Temperature Arbitrator | Entering Water temperature determined by arbitration | °F | Write | |
| AV | 11404 | Entering Water Temperature BAS | Send the Entering Water temperature sensor value | °F | Write | |
| AV | 11405 | Heat Pump Heating Changeover Delay (Minutes) | Time at full heat pump capacity before secondary heat is added | Write | ||
| AV | 11406 | Heat Pump Heating Changeover Offset | Heat Pump Changeover Offset is the temperature difference | °F | Write | |
| AV | 11407 | Heat Pump Heating Space Recovery Delta | Heat Pump Heating Space Recovery Delta is | Write | ||
| AV | 11408 | Run Time - Circuit 1 Heat Pump (Hours) | Circuit 1 Heat Pump Run Time | Read | ||
| AV | 11410 | Heating Capacity Primary Limit | Setpoint to Demand Limit heating capacity for the Primary Heat Source | % | Command | |
| AV | 11411 | Heating Capacity Primary Limit - Active | % | Read | ||
| AV | 11412 | Heating Capacity Secondary Limit | Setpoint to Demand Limit heating capacity for the Secondary Heat Source | % | Command | |
| AV | 11413 | Heating Capacity Secondary Limit - Active | % | Read | ||
| AV | 11414 | Supply Air Tempering Enable Setpoint | Units with Supply Air Tempering configured as installed | °F | Write | |
| AV | 11415 | Supply Air Tempering Disable Setpoint | Units with Supply Air Tempering configured as installed | °F | Write | |
| AV | 11416 | Supply Air Tempering Delay (Seconds) | Thermostat controlled units with Supply Air Tempering configured as installed | Write | ||
| AV | 11417 | Secondary Heating Lockout Setpoint | Setpoint at which to disable secondary heating based on outdoor air temperature | °F | Command | |
| AV | 11418 | Secondary Heating Lockout Setpoint - Active | Setpoint at which to disable secondary heating based on outdoor air temperature | °F | Read | |
| AV | 11419 | Auxiliary Heating P-Gain Modulating Electric Staging (%/F) | Proportional gain for 2nd loop- Staging control for Modulating Electric Heating | % | Write | |
| AV | 11420 | Auxiliary Heating Reset Time Modulating Electric Staging (seconds) | Reset Time for 2nd loop- Staging control for Modulating Electric Heating | Write | ||
| AV | 11421 | Design Air Flow | Setting For Units Design Air Flow | CFM | Write | |
| AV | 11422 | Hydronic Heating Standby Freeze Avoidance Position | Hydronic Heating Standby Freeze Avoid Position | % | Command | |
| AV | 11423 | Hydronic Heating Standby Freeze Avoidance Position - Active | % | Read | ||
| AV | 11424 | Run Time - Electric Heat 1 Command Status (Hours) | Electric Heat 1 Command Runtime | Read | ||
| AV | 11425 | Run Time - Electric Heat 2 Command Status (Hours) | Electric Heat 2 Command Runtime | Read | ||
| AV | 11426 | Run Time - Electric Heat 3 Command Status (Hours) | Electric Heat 3 Command Runtime | Read | ||
| AV | 11427 | Starts - Electric Heat 1 Command Status | Electric Heat 1 Command Starts | Read | ||
| AV | 11428 | Starts - Electric Heat 2 Command Status | Electric Heat 2 Command Starts | Read | ||
| AV | 11429 | Starts - Electric Heat 3 Command Status | Electric Heat 3 Command Starts | Read | ||
| AV | 11430 | Hydronic Freeze Avoidance Setpoint | Freeze Avoidance Setpoint | °F | Command | |
| AV | 11431 | Hydronic Freeze Avoidance Setpoint - Active | °F | Read | ||
| AV | 11432 | Heating Primary Capacity Setpoint BAS | Setpoint to command the unit to a given Primary heating capacity output | % | Command | |
| AV | 11433 | Heating Primary Capacity Setpoint BAS - Active | % | Read | ||
| AV | 11434 | Heating Secondary Capacity Setpoint BAS | Setpoint to command the unit to a given Secondary heating capacity output | % | Command | |
| AV | 11435 | Heating Secondary Capacity Setpoint BAS - Active | % | Read | ||
| AV | 11448 | Compressor Heating P-Gain - 2 (%/F) | Proportional gain for discharge air control - compressor Heating PI controller (%/F) | % | Write | |
| AV | 11449 | Compressor Heating Reset Time - 2 (seconds) | Reset time for discharge air controls - compressor Heating PI controller (seconds) | Write | ||
| BI | 10105 | FDD: Unit Economizing When It Should Not | Diagnostic: Unit Economizing When It Should Not | Read | false = Inactive, true = Active | |
| BI | 10106 | FDD: Unit Not Economizing When It Should | Diagnostic: Unit Not Economizing When It Should | Read | false = Inactive, true = Active | |
| BI | 10107 | FDD: Excessive Outdoor Air | Diagnostic: Excessive Air | Read | false = Inactive, true = Active | |
| BI | 10108 | FDD: Outdoor Air Damper Not Modulating | Diagnostic: Damper NOT Modulating | Read | false = Inactive, true = Active | |
| BI | 10121 | Relief Fan Output Status | Status of the Relief fan output on the controller | Read | false = Off, true = On | |
| BI | 10143 | VAV Box Command | The associated VAV boxes should be AUTO or forced open | Read | false = Off, true = On | |
| BI | 10170 | Condensate Overflow Input | Status of the condensate overflow input | Read | false = Open, true = Closed | |
| BI | 10172 | Occupancy Input | Status of the wired occupancy input | Read | false = Occupied, true = Unoccupied | |
| BI | 10210 | Equipment Shutdown Input Status | Status of the equipment shutdown function of the unit | Read | false = Equipment Run, true = Equipment Shutdown | |
| BI | 10211 | External Auto Stop Input Status | Status of the externally-wired auto/stop input | Read | false = Stop, true = Auto | |
| BI | 10219 | Economizer Airside Status | Status of airside economizing | Read | false = Inactive, true = Active | |
| BImin | 10226 | Supply Fan Status | Status of the supply fan output of the controller | Read | false = Off, true = On | |
| BI | 11100 | Compressor 1 Command Status | Compressor 1 Run Command Status | Read | false = Off, true = On | |
| BI | 11101 | Circuit 1 LPC Status | Circuit 1 LPC Input Status | Read | false = Open, true = Closed | |
| BI | 11102 | Compressor 1 Proving Status | Status of input for monitoring Compressor 1 proof of operation circuit | Read | false = Not Proved, true = Proved | |
| BI | 11103 | Compressor 2 Command Status | Compressor 2 Run Command Status | Read | false = Off, true = On | |
| BI | 11105 | Compressor 2 Proving Status | Status of input for monitoring Compressor 2 proof of operation circuit | Read | false = Not Proved, true = Proved | |
| BI | 11109 | Compressor 1 Unloader Command Status | Read | false = Off, true = On | ||
| BI | 11111 | Compressor 2 Unloader Command Status | Read | false = Off, true = On | ||
| BI | 11113 | Demand Limit Input | Configurable, hardwired input to command Demand Limit | Read | false = Not Limited, true = Limited | |
| BI | 11114 | Demand Shed Input | Configurable, hardwired input to command Demand Shed | Read | false = Off, true = On | |
| BI | 11115 | Phase Monitor Status | Status of local Phase Monitor Input | Read | false = Tripped, true = Okay | |
| BI | 11116 | Condenser Fan 1 Command Status | Condenser Fan 1 Run Command Status | Read | false = Off, true = On | |
| BI | 11117 | Condenser Fan 2 Command Status | Condenser Fan 2 Run Command Status | Read | false = Off, true = On | |
| BI | 11118 | Switchover Valve 1 Command Status | Status of Switchover Valve Command for HP Circuit 1 | Read | false = Off, true = On | |
| BI | 11120 | Thermostat G Input | Thermostat Fan Request | Read | false = Open, true = Closed | |
| BI | 11121 | Thermostat W1/O Input | Thermostat Heat Stage 1 Request or Thermostat Heat/Cool Mode Request for HP | Read | false = Open, true = Closed | |
| BI | 11122 | Thermostat W2 Input | Thermostat Heat Stage 2 Request (or Emergency Heat) | Read | false = Open, true = Closed | |
| BI | 11123 | Thermostat X2 Input | Thermostat Emergency Heat Request | Read | false = Open, true = Closed | |
| BI | 11124 | Thermostat Y1 Input | Thermostat Compressor Stage 1 Request | Read | false = Open, true = Closed | |
| BI | 11125 | Thermostat Y2 Input | Thermostat Compressor Stage 2 Request | Read | false = Open, true = Closed | |
| BI | 11126 | Supply Fan Proving Input Status | Status of the supply fan proving input on the controller | Read | false = Not Proved, true = Proved | |
| BI | 11127 | FroStat Input | Status of Hardwired Frostat Input | Read | false = Inactive, true = Active | |
| BI | 11128 | Electric Heat Stage 1 Status | Status of Electric Heat Stage 1 command | Read | false = Off, true = On | |
| BI | 11129 | Electric Heat Stage 2 Status | Status of Electric Heat Stage 2 command | Read | false = Off, true = On | |
| BI | 11130 | Clogged Filter Input | Status of Hardwired Clogged Filter Input | Read | false = Clean, true = Dirty Filter | |
| BI | 11133 | Ventilation Override Exhaust Status | Hardwired input VOM Exhaust | Read | false = Open, true = Closed | |
| BI | 11134 | Ventilation Override Pressurize Status | Hardwired input VOM Pressurize | Read | false = Open, true = Closed | |
| BI | 11135 | Ventilation Override Purge Status | Hardwired input VOM Purge | Read | false = Open, true = Closed | |
| BI | 11143 | Reheat Humidistat Input | Hardwired input to support dehumidification requests on hot gas reheat units | Read | false = Open, true = Closed | |
| BI | 11149 | Fan Mode - Air-Fi | Supply Fan Mode as set | Read | false = Cycling, true = Continuous | |
| BI | 11150 | Occupancy Input - Air-Fi | Read | false = Occupied, true = Unoccupied | ||
| BI | 11151 | Fan Mode Input | Supply Fan Mode as set | Read | false = Cycling, true = Continuous | |
| BI | 11152 | Supply Air Smoke Detector Status | Status of Hardwired Supply Air Smoke Detector Input | Read | false = Open, true = Closed | |
| BI | 11153 | Return Air Smoke Detector Status | Status of Hardwired Return Air Smoke Detector Input | Read | false = Open, true = Closed | |
| BI | 11154 | Gas Heat Stage 1 Status | Status of gas heat Stage 1 | Read | false = Off, true = On | |
| BI | 11155 | Gas Heat Stage 2 Status | Status of gas heat Stage 2 | Read | false = Off, true = On | |
| BI | 11156 | Diagnostic: ERM Supply Fan Locked Motor - 1 | Read | false = Inactive, true = Active | ||
| BI | 11157 | Diagnostic: ERM Supply Fan Locked Motor - 2 | Read | false = Inactive, true = Active | ||
| BI | 11158 | Diagnostic: ERM Supply Fan Motor Overheated - 1 | Read | false = Inactive, true = Active | ||
| BI | 11159 | Diagnostic: ERM Supply Fan Motor Overheated - 2 | Read | false = Inactive, true = Active | ||
| BI | 11160 | Diagnostic: ERM Supply Fan Power Mod Overheated - 1 | Read | false = Inactive, true = Active | ||
| BI | 11161 | Diagnostic: ERM Supply Fan Power Mod Overheated - 2 | Read | false = Inactive, true = Active | ||
| BI | 11162 | Diagnostic: ERM Fault Supply Fan - 1 | Read | false = Inactive, true = Active | ||
| BI | 11163 | Diagnostic: ERM Fault Supply Fan - 2 | Read | false = Inactive, true = Active | ||
| BI | 11164 | Diagnostic: IGN1 Module Lockout | Read | false = Inactive, true = Active | ||
| BI | 11165 | Diagnostic: IGN1 Heating High Temp Limit Open | Read | false = Inactive, true = Active | ||
| BI | 11166 | Diagnostic: IGN1 Flame Rollout Switch Open | Read | false = Inactive, true = Active | ||
| BI | 11167 | Diagnostic: IGN1 Inducer Proving Switch Fail Closed | Read | false = Inactive, true = Active | ||
| BI | 11168 | Diagnostic: IGN1 Inducer Proving Switch Fail Open | Read | false = Inactive, true = Active | ||
| BI | 11169 | Diagnostic: IGN1 No Flame Sensed on Ignition | Read | false = Inactive, true = Active | ||
| BI | 11170 | Diagnostic: IGN1 Flame Sensed w/Gas Valve Off | Read | false = Inactive, true = Active | ||
| BI | 11171 | Diagnostic: IGN1 Hardware Configuration Error | Read | false = Inactive, true = Active | ||
| BI | 11172 | Diagnostic: IGN1 Weak Flame | Read | false = Inactive, true = Active | ||
| BI | 11173 | Diagnostic: IGN1 Gas Valve Error | Read | false = Inactive, true = Active | ||
| BI | 11174 | Diagnostic: IGN1 Module Failure | Read | false = Inactive, true = Active | ||
| BI | 11175 | Diagnostic: ERM Supply Fan Phase Failure - 1 | Diagnostic:ERM Supply Fan Phase Failure -1 | Read | false = Inactive, true = Active | |
| BI | 11176 | Diagnostic: ERM Supply Fan Phase Failure - 2 | Read | false = Inactive, true = Active | ||
| BI | 11177 | Diagnostic: ERM Supply Fan Internal Comm Failure - 1 | Read | false = Inactive, true = Active | ||
| BI | 11178 | Diagnostic: ERM Supply Fan Internal Comm Failure - 2 | Read | false = Inactive, true = Active | ||
| BI | 11179 | Diagnostic: ERM Supply Fan Hall Sensor Error - 1 | Diagnostic: ERM Supply Fan Hall Sensor Error -1 | Read | false = Inactive, true = Active | |
| BI | 11180 | Diagnostic: ERM Supply Fan Hall Sensor Error - 2 | Diagnostic: ERM Supply Fan Hall Sensor Error -2 | Read | false = Inactive, true = Active | |
| BI | 11181 | Diagnostic: ERM Supply Fan Speed Limit Exceeded - 1 | Read | false = Inactive, true = Active | ||
| BI | 11182 | Diagnostic: ERM Supply Fan Speed Limit Exceeded - 2 | Read | false = Inactive, true = Active | ||
| BI | 11183 | Diagnostic: ERM Supply Fan Rotor Calibration - 1 | Read | false = Inactive, true = Active | ||
| BI | 11184 | Diagnostic: ERM Supply Fan Rotor Calibration - 2 | Read | false = Inactive, true = Active | ||
| BI | 11185 | Diagnostic: ERM Supply Fan DC link Undervoltage - 1 | Diagnostic: ERM Supply Fan DC-link Undervoltage - 1 | Read | false = Inactive, true = Active | |
| BI | 11186 | Diagnostic: ERM Supply Fan DC link Undervoltage - 2 | Diagnostic: ERM Supply Fan DC-link Undervoltage - 2 | Read | false = Inactive, true = Active | |
| BI | 11187 | Reheat Pumpout Solenoid Status | Reheat Pumpout Solenoid IMC Command Status | Read | false = Off, true = On | |
| BI | 11189 | Reheat Valve 1 Fault Status | Read | false = Inactive, true = Active | ||
| BI | 11190 | Reheat Valve 1 Calibration Status | Reheat Valve 1 Calibration Status from Stepper Motor Module | Read | false = Inactive, true = Active | |
| BI | 11192 | VAV Changeover Input | VAV Changeover Request | Read | false = Open, true = Closed | |
| BI | 11193 | Crankcase Heater Command | Crankcase Heater status for VSPD Compressor | Read | false = Off, true = On | |
| BI | 11195 | Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 1 | Read | false = Inactive, true = Active | ||
| BI | 11196 | Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 2 | Read | false = Inactive, true = Active | ||
| BI | 11197 | Diagnostic: Modulating Gas Invalid ID Plug Manifold 1 | Gas heat ignition controller detected an invalid or failed ID Plug | Read | false = Inactive, true = Active | |
| BI | 11198 | Diagnostic: Modulating Gas Heat Configuration Invalid | Read | false = Inactive, true = Active | ||
| BI | 11199 | Diagnostic: Gas Heat Weak Flame Manif 1 Burner 1 | Weak flame or aged flame rod detected on burner 1 | Read | false = Inactive, true = Active | |
| BI | 11200 | Diagnostic: Gas Heat Weak Flame Manif 1 Burner 2 | Weak flame or aged flame rod detected on burner 2 | Read | false = Inactive, true = Active | |
| BI | 11201 | Diagnostic: Gas Heat Insufficient Combustion Air | Gas heat is being derated/reduced due to insufficient combustion air | Read | false = Inactive, true = Active | |
| BI | 11202 | Diagnostic: Modulating Gas Primary Limit Open Manifold 1 | Gas heat failure, primary limit detected open | Read | false = Inactive, true = Active | |
| BI | 11203 | Diagnostic: Modulating Gas Heat Open Fuse Manifold 1 | Gas heat failure, fuse detected open | Read | false = Inactive, true = Active | |
| BI | 11204 | Diagnostic: Gas Heat Failed Ignition Manifold 1 | Read | false = Inactive, true = Active | ||
| BI | 11205 | Diagnostic: Modulating Gas Valve Failure Manifold 1 | Modulating gas valve did not reach park or full On position | Read | false = Inactive, true = Active | |
| BI | 11206 | Diagnostic: Modulating Gas Control Board Failure Manifold 1 | Ignition control board failure during startup self test | Read | false = Inactive, true = Active | |
| BI | 11231 | Diagnostic: Gas Heat Lockout Manifold 1 | Modulating gas heat ignition controller operation is locked out | Read | false = Inactive, true = Active | |
| BI | 11235 | Diagnostic: Gas Heat Failed Ignition Manifold 1 Burner 2 | Modulating gas heat ignition controller burner 2 operation failed ignition | Read | false = Inactive, true = Active | |
| BI | 11237 | Diagnostic: VFD Cprsr Current Overload - Cprsr 1 | Read | false = Inactive, true = Active | ||
| BI | 11238 | Diagnostic: VFD Compressor Ground Fault - Cprsr 1 | Read | false = Inactive, true = Active | ||
| BI | 11239 | Diagnostic: VFD Compressor Short Circuit - Cprsr 1 | Read | false = Inactive, true = Active | ||
| BI | 11240 | Diagnostic: VFD Compressor In Hand Mode - Cprsr 1 | Read | false = Inactive, true = Active | ||
| BI | 11241 | Diagnostic: Gas Heat Air Pressure Sensor Reading Low | Modulating gas heat ignition controller, air pressure sensor is reading low | Read | false = Inactive, true = Active | |
| BI | 11242 | Diagnostic: Gas Heat Air Pressure Sensor Reading High | Read | false = Inactive, true = Active | ||
| BI | 11243 | Diagnostic: Gas Heat Loss of Inducer Motor Control | Modulating gas heat ignition controller, loss of inducer motor control | Read | false = Inactive, true = Active | |
| BI | 11244 | Diagnostic: Gas Heat Air Sensor Null Pressure Check | Read | false = Inactive, true = Active | ||
| BI | 11245 | Diagnostic: Gas Heat Limited Low Fire | Read | false = Inactive, true = Active | ||
| BI | 11246 | Heating Output Operational Limit | Heating capacity is being limited due to heat rise across gas furnace | Read | false = Inactive, true = Active | |
| BI | 11247 | Diagnostic: Refrigerant Concentration Sensor A | Diagnostic point that is be active | Read | false = Inactive, true = Active | |
| BI | 11248 | Refrigerant Leak Detection System Input | Read | false = Inactive, true = Active | ||
| BI | 11249 | Diagnostic: Refrigerant Leak Sensor Failure Sensor A | Diagnostic point that shall be active | Read | false = Inactive, true = Active | |
| BI | 11250 | Diagnostic: IGN1 Low Ambient Lockout | Diagnostic: IGN1 Low NOx Heat Furnace Low Ambient Lockout | Read | false = Inactive, true = Active | |
| BI | 11251 | Diagnostic: Low Saturated Suction Refrig Protection | Read | false = Inactive, true = Active | ||
| BI | 11252 | Diagnostic: Low Saturated Suction Refrig Protection Disabled | Read | false = Inactive, true = Active | ||
| BI | 11253 | Electric Heat 1 Command Status | Status of Electric Heat 1 command | Read | false = Off, true = On | |
| BI | 11254 | Electric Heat 2 Command Status | Status of Electric Heat 2 command | Read | false = Off, true = On | |
| BI | 11255 | Electric Heat 3 Command Status | Status of Electric Heat 3 command | Read | false = Off, true = On | |
| BI | 11256 | Diagnostic: Freeze Protection | Diagnostic created when Hydronic Heat Freezestat status is in alarm position | Read | false = Inactive, true = Active | |
| BI | 11257 | Diagnostic: Freeze Avoidance Mode | Diagnostic created to notify user Freeze avoidance measure are in place | Read | false = Inactive, true = Active | |
| BI | 11258 | Freezestat Input | Status of Hardwired Freezestat Input | Read | false = Tripped, true = Okay | |
| BV | 10103 | Heat Lockout Command | Command the unit to prevent heating operation | Command | false = Normal, true = Locked out | |
| BV | 10104 | Supply Fan Configuration Command | Command the supply fan configuration as either cycling or continuous | Write | false = Cycling, true = Continuous | |
| BV | 10106 | Dehumidification Enable Command | Disable unit dehumidification | Command | false = Disabled, true = Auto | |
| BV | 10109 | Filter Timer Reset | Command the unit to reset the accumulated filter run hours | Write | false = Accumulating, true = Reset | |
| BV | 10110 | Reset Diagnostic | Initiate a request to reset any controller diagnostics | Write | false = Normal, true = Reset | |
| BV | 10111 | Daytime Warmup Enable Command | Enable daytime warmup | Command | false = Disabled, true = Enabled | |
| BV | 10112 | Morning Warmup Enable Command | Enable morning warmup | Command | false = Disabled, true = Enabled | |
| BV | 10113 | Occupancy Input BAS | Provide the requested occupancy state to the unit | Write | false = Occupied, true = Unoccupied | |
| BV | 10115 | Cooling Lockout BAS | Prevent all mechanical cooling | Command | false = Normal, true = Locked out | |
| BV | 10119 | Supply Air Tempering Enable | Enable the supply (discharge) air tempering feature of the unit | Command | false = Disable, true = Enable | |
| BVmin | 11100 | Alarm Indicator Status | State of the alarm output command from the controller | Read | false = Off, true = On | |
| BV | 11101 | Supply Fan High Speed Command Status | Supply Fan High Speed Command for 2- Speed Fan Relay Controlled Equipment | Read | false = Off, true = On | |
| BV | 11112 | Condenser Defrost Status | Status point to indicate | Read | false = Inactive, true = Active | |
| BVmin | 11113 | Unit Stop Command | Point used to force the unit into an immediate stop condition | Write | false = Auto, true = Stop | |
| BV | 11114 | Supply Fan Speed Command Enable | Command | false = Disabled, true = Enabled | ||
| BV | 11115 | Cooling Capacity Setpoint Enable BAS | Command | false = Disabled, true = Enabled | ||
| BV | 11116 | Heating Capacity Setpoint Enable BAS | Command | false = Disabled, true = Enabled | ||
| BV | 11119 | Supply Fan Compensation | Command | false = Disabled, true = Enabled | ||
| BV | 11121 | Compressor 1 Run Time Reset | Compressor 1 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11122 | Compressor 1 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11123 | Compressor 2 Run Time Reset | Compressor 2 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11124 | Compressor 2 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11127 | Condenser Fan 1 Run Time Reset | Condenser Fan 1 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11128 | Condenser Fan 1 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11129 | Condenser Fan 2 Run Time Reset | Condenser Fan 2 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11130 | Condenser Fan 2 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11133 | Relief Fan Run Time Reset | Relief Fan Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11134 | Relief Fan Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11135 | Electric Heat Stage 1 Run Time Reset | Electric Heat Stage 1 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11136 | Electric Heat Stage 1 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11137 | Electric Heat Stage 2 Run Time Reset | Electric Heat Stage 2 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11138 | Electric Heat Stage 2 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11139 | Supply Fan Run Time Reset | Supply Fan Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11140 | Supply Fan Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11142 | Diagnostic: Heat Failure | Read | false = Inactive, true = Active | ||
| BV | 11143 | Diagnostic: Duct Static Pressure Limit Trip | Read | false = Inactive, true = Active | ||
| BV | 11144 | Diagnostic: Filter Change Required | Diagnostic: Dirty Filter | Read | false = Inactive, true = Active | |
| BV | 11145 | Diagnostic: Condensate Overflow Lockout | Condensate Drain Pan Overflow Lockout | Read | false = Inactive, true = Active | |
| BV | 11146 | Diagnostic: FroStat Trip | Read | false = Inactive, true = Active | ||
| BV | 11155 | Diagnostic: Comp 1 Proving Trip | Read | false = Inactive, true = Active | ||
| BV | 11156 | Diagnostic: Comp 2 Proving Trip | Read | false = Inactive, true = Active | ||
| BV | 11158 | Diagnostic: Circuit 1 LPC Trip | Read | false = Inactive, true = Active | ||
| BV | 11161 | Diagnostic: Compressor 1 Contactor Failure | Diagnostic: Compressor 1 Contactor Fail Lockout | Read | false = Inactive, true = Active | |
| BV | 11162 | Diagnostic: Circuit 1 LPC Lockout | Read | false = Inactive, true = Active | ||
| BV | 11166 | VVZT DAT Control Mode | Command | false = Auto, true = Manual | ||
| BV | 11172 | Diagnostic: Compressor 1 Proving Lockout | Read | false = Inactive, true = Active | ||
| BV | 11173 | Occupancy Input Active | Occupancy Input being actively used for status determination | Read | false = Occupied, true = Unoccupied | |
| BV | 11174 | Diagnostic: Compressor 2 Contactor Failure | Diagnostic: Compressor 2 Contactor Fail Lockout | Read | false = Inactive, true = Active | |
| BV | 11176 | Diagnostic: Compressor 2 Proving Lockout | Read | false = Inactive, true = Active | ||
| BV | 11177 | Diagnostic: Demand Defrost Disabled | Read | false = Inactive, true = Active | ||
| BV | 11180 | Diagnostic: Demand Defrost Fault A | Read | false = Inactive, true = Active | ||
| BV | 11183 | Diagnostic: Demand Defrost Fault B | Read | false = Inactive, true = Active | ||
| BV | 11186 | Diagnostic: Demand Defrost Fault C | Read | false = Inactive, true = Active | ||
| BV | 11189 | Diagnostic: Demand Defrost Fault D | Read | false = Inactive, true = Active | ||
| BV | 11190 | Diagnostic: Maintenance Required | Read | false = Inactive, true = Active | ||
| BV | 11192 | Diagnostic: Unit Communications Failure | Read | false = Inactive, true = Active | ||
| BV | 11199 | Supply Fan Configuration Status | Supply fan configuration | Read | false = Cycling, true = Continuous | |
| BV | 11200 | Timed Override Timer Is Active | Or not the timed override timer is active | Read | false = Inactive, true = Active | |
| BV | 11201 | Supply Fan Speed Command Enable - Active | Read | false = Disabled, true = Enabled | ||
| BV | 11202 | Cooling Capacity Setpoint Enable BAS - Active | Read | false = Disabled, true = Enabled | ||
| BV | 11203 | Cooling Lockout BAS - Active | Active value for Cooling Lockout BAS point being used for control | Read | false = Normal, true = Locked out | |
| BV | 11204 | Heating Capacity Setpoint Enable BAS - Active | Active value for Heating Capacity Setpoint Enable point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11205 | Daytime Warmup Enable Command - Active | Active value for Daytime Warmup Enable Command point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11208 | Supply Fan Compensation - Active | Active value for Supply Fan Compensation point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11209 | Dehumidification Enable Command - Active | Active value for Dehumidification Enable Command point being used for control | Read | false = Disabled, true = Auto | |
| BV | 11211 | VVZT DAT Control Mode - Active | Active value for VVZT DAT Control Mode point being used for control | Read | false = Auto, true = Manual | |
| BV | 11216 | Heat Lockout Command - Active | Active value for Heat Lockout Command point being used for control | Read | false = Normal, true = Locked out | |
| BV | 11217 | Morning Warmup Enable Command - Active | Active value for Morning Warmup Enable Command point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11221 | Supply Air Tempering Status | Status of the Supply Air Tempering function | Read | false = Disable, true = Enable | |
| BV | 11222 | Supply Air Tempering Enable - Active | Active value for Supply Air Tempering Enable point being used for control | Read | false = Disable, true = Enable | |
| BV | 11224 | Occupancy Input Arbitrator | Status of the arbitrated occupancy inputs | Write | false = Occupied, true = Unoccupied | |
| BV | 11226 | Demand Limit Request BAS | Demand limit the unit remotely | Write | false = Not Limited, true = Limited | |
| BV | 11227 | Demand Limit Request - Active | Active Demand Limit Request value used by the equipment | Read | false = Not Limited, true = Limited | |
| BV | 11230 | Diagnostic: VFD Compressor Fault - Cprsr 1 | Diagnostic that becomes active anytime a drive fault is Active | Read | false = Inactive, true = Active | |
| BV | 11231 | Daytime Warmup Active | Daytime warmup is currently active | Read | false = Inactive, true = Active | |
| BV | 11232 | Morning Warmup Active | Morning warmup is active | Read | false = Inactive, true = Active | |
| BV | 11233 | Supply Fan 2 Run Time Reset | Supply Fan 2 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11234 | Supply Fan 2 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11235 | Occupied Standby Supply Fan Configuration Command | Select the Occupied Standby Fan Mode setting | Command | false = Cycling, true = Continuous | |
| BV | 11236 | Occupied Standby Supply Fan Configuration Command - Active | Occupied Standby Fan Mode setting | Read | false = Cycling, true = Continuous | |
| BV | 11239 | Gas Heat Stage 1 Run Time Reset | Gas heat Stage 1 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11240 | Gas Heat Stage 1 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11241 | Gas Heat Stage 2 Run Time Reset | Gas heat Stage 2 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11242 | Gas Heat Stage 2 Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11243 | Diagnostic: ERM Supply Fan 1 Failure | Read | false = Inactive, true = Active | ||
| BV | 11244 | Diagnostic: ERM Supply Fan 2 Failure | Read | false = Inactive, true = Active | ||
| BV | 11245 | Diagnostic: Supply Fan Proving Failure | Read | false = Inactive, true = Active | ||
| BV | 11248 | Diagnostic: High Condensate Level Detected | Read | false = Inactive, true = Active | ||
| BV | 11249 | Diagnostic: Morning Warmup Mode Exceeded 120 Minutes | Read | false = Inactive, true = Active | ||
| BV | 11250 | Diagnostic: Pre Cool Mode Exceeded 120 Minutes | Diagnostic: Precool Mode Exceeded 120 Minutes | Read | false = Inactive, true = Active | |
| BV | 11251 | Diagnostic: Night Purge Mode Exceeded 120 Minutes | Read | false = Inactive, true = Active | ||
| BV | 11253 | Heat Pump Heating Lockout Setpoint Enable | Enable the Heat pump Heating Lockout Setpoint | Command | false = Disable, true = Enable | |
| BV | 11254 | Heat Pump Heating Lockout Setpoint Enable - Active | Active value for the Heat pump Heating Lockout Setpoint Enable | Read | false = Inactive, true = Active | |
| BV | 11255 | Dehumidification Status | Active state showing whether dehumidification is active or inactive | Read | false = Inactive, true = Active | |
| BV | 11256 | Pre Cool Enable Command | Enable pre Cool | Command | false = Disabled, true = Enabled | |
| BV | 11257 | Pre Cool Enable Command - Active | Active value for Pre Cool Enable Command point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11258 | Pre Cool Active | Pre Cool is active | Read | false = Inactive, true = Active | |
| BV | 11259 | Occupied Dehumidification Enable BAS | Setting for unit to use "Enable" or "Disable" for Occupied Dehumidification Control | Write | false = Disabled, true = Enabled | |
| BV | 11260 | Occupied Dehumidification Enable BAS - Active | Active value for Dehumidification Enable BAS point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11261 | Unoccupied Dehumidification Enable BAS | Setting for unit to use "Enable" or "Disable" for Occupied Dehumidification Control | Write | false = Disabled, true = Enabled | |
| BV | 11262 | Unoccupied Dehumidification Enable BAS - Active | Active value for Dehumidification Enable BAS point being used for control | Read | false = Disabled, true = Enabled | |
| BV | 11263 | Diagnostic: Duct Static Pressure Limit Lockout | Read | false = Inactive, true = Active | ||
| BV | 11264 | Diagnostic: Duct Static Pressure Local Trip | Read | false = Inactive, true = Active | ||
| BV | 11265 | Diagnostic: Duct Static Pressure Local Lockout | Read | false = Inactive, true = Active | ||
| BV | 11266 | Gas Heat Manifold 1 Burner 1 Run Time Reset | Gas heat runtime reset | Write | false = Accumulating, true = Reset | |
| BV | 11267 | Gas Heat Manifold 1 Burner 1 Starts Reset | Gas heat starts counter reset | Write | false = Accumulating, true = Reset | |
| BV | 11268 | Gas Heat Manifold 1 Burner 2 Run Time Reset | Gas heat runtime reset | Write | false = Accumulating, true = Reset | |
| BV | 11269 | Gas Heat Manifold 1 Burner 2 Starts Reset | Gas heat starts counter reset | Write | false = Accumulating, true = Reset | |
| BV | 11272 | Circuit 1 Condenser Defrost Run Time Reset | Circuit 1 Condenser Defrost Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11273 | Circuit 1 Condenser Defrost Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11277 | Diagnostic: Reheat Valve 1 Fault | Read | false = Inactive, true = Active | ||
| BV | 11283 | Refrigerant Mitigation Active | Read | false = Inactive, true = Active | ||
| BV | 11284 | Thermostat Control Method Request | Determines Auto or Conventional mode for enhanced thermostat applications | Write | false = Conventional, true = Enhanced | |
| BV | 11285 | Thermostat Control Method Status | Active value for Thermostat Control Method being used for control | Read | false = Conventional, true = Enhanced | |
| BV | 11288 | Heating Capacity Control Type Override BAS | Used on units leveraging remote capacity control | Write | false = Disable, true = Enable | |
| BV | 11289 | Circuit 1 Heat Pump Run Time Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11291 | Diagnostic: Primary Heat Installed but Locked Out by Application | Read | false = Inactive, true = Active | ||
| BV | 11292 | Diagnostic: Secondary Heat Installed but Locked Out by Application | Read | false = Inactive, true = Active | ||
| BV | 11293 | Secondary Heating Lockout Setpoint Enable | Enable the Secondary Heating Lockout Setpoint | Command | false = Disable, true = Enable | |
| BV | 11294 | Secondary Heating Lockout Setpoint Enable - Active | Active value for the Secondary Heating Lockout Setpoint Enable | Read | false = Inactive, true = Active | |
| BV | 11295 | Hydronic Heat Valve Direct/Reverse Acting | Direction of actuator stroke | Write | false = Direct, true = Reverse | |
| BV | 11296 | Freeze Avoidance Enable | Command | false = Disabled, true = Enabled | ||
| BV | 11297 | Freeze Avoidance Enable - Active | Active Value for Freeze Avoidance Enable, for freeze avoidance control | Read | false = Disabled, true = Enabled | |
| BV | 11300 | Electric Heat 1 Command Status Run Time Reset | Electric Heat 1 Command Status Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11301 | Electric Heat 2 Command Status Run Time Reset | Electric Heat 2 Command Status Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11302 | Electric Heat 3 Command Status Run Time Reset | Electric Heat 3 Command Status Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11303 | Electric Heat 1 Command Status Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11304 | Electric Heat 2 Command Status Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11305 | Electric Heat 3 Command Status Starts Reset | Write | false = Accumulating, true = Reset | ||
| BV | 11306 | Relief Fan 2 Run Time Reset | Relief Fan 2 Runtime Reset | Write | false = Accumulating, true = Reset | |
| BV | 11307 | Relief Fan 2 Starts Reset | Write | false = Accumulating, true = Reset | ||
| MImin | 10101 | Heat Cool Mode Status | Current heat cool mode of the controller | Read | 1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate | |
| MI | 10144 | Economizer System Status | Operating state of the airside economizer system | Read | 1 = Disabled, 2 = Enabled, 3 = Not Present | |
| MI | 11100 | System Mode Switch Air-Fi | Status of the wireless system mode switch connected to the controller | Read | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat | |
| MI | 11101 | Timed Override Air-Fi | Status of the Timed Override wireless input | Read | 1 = Idle, 2 = On, 3 = Cancel | |
| MI | 11102 | System Mode Switch Input | Status of the wired system mode switch connected to the controller | Read | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat | |
| MI | 11103 | Timed Override Input | Status of the Timed Override wired input | Read | 1 = Idle, 2 = On, 3 = Cancel | |
| MI | 11104 | Supply Fan 1 ERM Information Alarm Status | Informational alarm status from the ERM supply fan 1 | Read | 1 = Normal, 2 = Current Limitation in Action, 3 = Line Impedance Too High, 4 = Power Limiter in Action, 5 = Output Stage Temperature High, 6 = Motor Temperature High, 7 = Temperature Inside Electronics High, 8 = DC Link Voltage High, 9 = Braking Mode, 10 = Calibration of Rotor Position, 11 = Actual Speed is Lower Than Run Monitoring Speed Limit, 12 = Cable Break at Analog or PWM Input For Analog Set Value, 13 = DC Link Voltage Low, 14 = Line Voltage High, 15 = Shedding Function Active | |
| MI | 11105 | Supply Fan 2 ERM Information Alarm Status | Informational alarm status from the ERM supply fan 2 | Read | 1 = Normal, 2 = Current Limitation in Action, 3 = Line Impedance Too High, 4 = Power Limiter in Action, 5 = Output Stage Temperature High, 6 = Motor Temperature High, 7 = Temperature Inside Electronics High, 8 = DC Link Voltage High, 9 = Braking Mode, 10 = Calibration of Rotor Position, 11 = Actual Speed is Lower Than Run Monitoring Speed Limit, 12 = Cable Break at Analog or PWM Input For Analog Set Value, 13 = DC Link Voltage Low, 14 = Line Voltage High, 15 = Shedding Function Active | |
| MV | 10101 | Cooling Reset Type Status | Type of cooling reset used by the controller | Read | 1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air | |
| MV | 10102 | Emergency Override BAS | Command the unit into an emergency mode of operation | Command | 1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire | |
| MV | 10103 | Economizer Airside Enable BAS | Enable airside economizing | Command | 1 = Disabled, 2 = Enabled, 3 = Auto | |
| MV | 10104 | Heat Cool Mode Request | Command the unit into a heat/cool mode | Command | 1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate | |
| MVmin | 10106 | Occupancy Request | Command the unit into an occupancy mode | Write | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MV | 10110 | Timed Override Request | Request a temporary timed override during unoccupied | Write | 1 = Idle, 2 = On, 3 = Cancel | |
| MV | 11100 | Arbitration Method Request | Write | 1 = Enable External/BAS Control, 2 = Standalone Control | ||
| MV | 11101 | Customer Options Module Communication Status | Communication Status of the Customer Options Module | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11102 | Economizer Type | General description of the type of economizer system | Read | 1 = None, 2 = 2 Position Ventilation, 3 = Modulation Economizer, 4 = 2 Position Ventilation/Waterside Economizer, 5 = Waterside Economizer, 6 = Airside/Waterside Economizer, 7 = TRAQ Damper, 8 = Airside Economizer and TRAQ Damper/Sensor, 9 = Waterside Economizer and TRAQ Damper/Sensor, 10 = Airside/Waterside Economizer and TRAQ Damper/Sensor | |
| MV | 11103 | Fresh Air Options Module Communication Status | Communication Status of the Fresh Air Options Module | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11105 | Indoor Options Module Communication Status | Communication Status of the Indoor Options Module | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11106 | On-Board I/O Communication Status | Communication Status of the On-Board Inputs and Outputs | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11110 | Service Test State Request | Point to request the unit into a service test step | Write | *See (a), 1 = Inactive, 2 = Fan On Econ Open, 3 = High Fan Speed Econ Open, 4 = Ventilation Low Fan Speed, 5 = Ventilation Mid Fan Speed, 6 = Ventilation High Fan Speed, 7 = Cool 1, 8 = Cool 2, 9 = Cool 3, 10 = Cool 4, 11 = Cool 5, 12 = Reheat, 13 = Heat 1, 14 = Heat 2, 15 = Heat 3, 16 = Heat 4, 17 = Aux Heat 1, 18 = Aux Heat 2, 19 = Defrost, 20 = Emergency Heat, 21 = Open Reheat Valve 1, 22 = Close Reheat Valve 1, 23 = Refrigerant Recovery | |
| MV | 11111 | Cooling Reset Type | Write | 1 = None, 2 = Outdoor Air, 3 = Zone, 4 = Return Air | ||
| MV | 11112 | System Mode Switch Local | Read | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat, 5 = Emergency Heat | ||
| MV | 11113 | Timed Override Status | Status of the timed override request | Read | 1 = Idle, 2 = On, 3 = Cancel | |
| MV | 11114 | Trane Unit Type | Equipment type according to the manufacturer's classification | Read | 1 = 1 Heat/1 Cool, 2 = Heat Pump, 3 = Blower Coil, 4 = Unit Ventilator, 5 = Fan Coil, 6 = Rooftop, 7 = Air Handler, 8 = Vertical Self Contained, 9 = Unitary, 10 = VAV Box | |
| MV | 11115 | Unit Stop Source | Source of the stop command that turned off the equipment | Read | 1 = None, 2 = Emergency Stop, 3 = Drain Pan Overflow, 4 = Local HI, 5 = Remote HI, 6 = External Auto Stop, 7 = Phase Monitor, 8 = Emergency Override, 9 = Supply Fan Fault, 10 = Equipment Shutdown Input, 11 = Smoke Detector, 12 = Equipment Limit, 13 = Sensor Failure | |
| MV | 11116 | Emergency Override BAS - Active | Active value for Emergency Override BAS point being used for control | Read | 1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire | |
| MV | 11118 | Economizer Decision Method | Indicate the method of enabling airside economizing | Read | 1 = Absolute Temperature, 2 = Relative Temperature, 3 = Absolute Enthalpy, 4 = Comparative Enthalpy, 5 = Differential Dry Bulb | |
| MV | 11119 | Refrigerant Type | Type of refrigerant used in the equipment | Read | 1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E), 17 = R-454B | |
| MV | 11120 | Economizer Airside Enable BAS - Active | Active value for Economizer Airside Enable BAS point being used for control | Read | 1 = Disabled, 2 = Enabled, 3 = Auto | |
| MV | 11121 | Heat Cool Mode Request - Active | Active value for Heat Cool Mode Request point being used for control | Read | 1 = Auto, 2 = Heat, 3 = Morning Warm-up, 4 = Cool, 5 = Night Purge, 6 = Pre Cool, 7 = Off, 8 = Test, 9 = Emergency Heat, 10 = Fan Only, 11 = Free Cool, 12 = Ice-Making, 13 = Max Heat, 14 = Economizer, 15 = Dehumidify, 16 = Calibrate | |
| MVmin | 11123 | Occupancy Status | Active occupancy mode of the controller | Read | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MV | 11125 | Occupancy Request Active | Active Occupancy mode being requested of the unit | Read | 1 = Occupied, 2 = Unoccupied, 3 = Occupied Bypass, 4 = Occupied Standby, 5 = Auto | |
| MV | 11126 | Supply Fan 1 Communication Status | Communication Status of the Modbus Supply Fan 1 | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11127 | Supply Fan 2 Communication Status | Communication Status of the Modbus Supply Fan 2 | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11128 | Gas Heat Ignition Module 1 Communication Status | Communication Status of the Modbus Gas Heat Ignition Module 1 | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11130 | Emergency Override Status | Active Emergency Override mode in control of the equipment | Read | 1 = Normal, 2 = Pressurize, 3 = Depressurize, 4 = Purge, 5 = Shutdown, 6 = Fire | |
| MV | 11133 | Stepper Motor Communication Status | Communication Status of the Stepper Motor Inputs and Outputs | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11136 | Heating Reset Type | Write | 1 = None, 2 = Outdoor air, 3 = Zone, 4 = Return Air | ||
| MV | 11137 | Heating Reset Type Status | Discharge air heating reset type status | Read | 1 = None, 2 = Outdoor air, 3 = Zone, 4 = Return Air | |
| MV | 11138 | Compressor 1 VFD Communication Status | Communication Status of the Modbus Compressor VFD | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured | |
| MV | 11139 | Refrigerant Leak Sensor Communication Status Sensor A | Communication status of the Modbus communicating refrigerant detection system | Read | 1 = Not Configured, 2 = Not Communicating, 3 = Communicating, 4 = Communicating - Not Configured |
No points match these filters.
Object ID lookup: Trane Symbio 700 Precedent / Axiom point IDs by name
AI10101Cooling Capacity StatusAI10102Heating Capacity Primary StatusAI10104Outdoor Air Relative Humidity LocalAI10110Return Air Humidity LocalAI10111Outdoor Air Damper PositionAI10116Space Humidity ActiveAI10117Outdoor Air Dew PointAI10118Outdoor Air Temperature ActiveAI10120Outdoor Air Humidity ActiveAI10124Discharge Air Temperature LocalAI10126Return Air Temperature InputAI10155Duct Static Pressure LocalAI10156Outdoor Air Temperature LocalAI10182Duct Static Pressure ActiveAI10218Space Temperature InputAI10226Space Dew PointAI11100Coil Temperature Sensor 1AI11103Space CO2 Concentration InputAI11104Space Humidity InputAI11106Supply Fan Speed Command StatusAI11109Modulating Heat Command StatusAI11111Outdoor Air Damper CommandAI11132On-Board I/O Firmware Major VersionAI11133On-Board I/O Firmware Minor VersionAI11134Indoor Options Module Firmware Major VersionAI11135Indoor Options Module Firmware Minor VersionAI11136Fresh Air Options Module Firmware Major VersionAI11137Fresh Air Options Module Firmware Minor VersionAI11140Customer Options Module Firmware Major VersionAI11141Customer Options Module Firmware Minor VersionAI11142IGN Module 1 Firmware Major VersionAI11143IGN Module 1 Firmware Minor VersionAI11148Remote Minimum PositionAI11149Return Air Temperature ActiveAI11150Sensor Battery Status Air-FiAI11151Space CO2 Concentration Air- FiAI11152Space Humidity Air-FiAI11154Space Temperature Air-FiAI11155Space Temperature Cooling Setpoint Air-FiAI11156Space Temperature Heating Setpoint Air-FiAI11157Space Temperature Setpoint Air-FiAI11159Space Temperature Cooling Setpoint InputAI11160Space Temperature Heating Setpoint InputAI11161Space Temperature Setpoint InputAI11164Reheat Valve 1 Step StatusAI11166Evaporator Entering Refrigerant TemperatureAI11167Stepper Motor Module Firmware Major VersionAI11168Stepper Motor Module Firmware Minor VersionAI11169Saturated Discharge TemperatureAI11170Supply Fan Entering Air TemperatureAI11171Entering Water Temperature ActiveAI11172Entering Water Temperature LocalAI11173Outdoor Air Damper FeedbackAV10103Outdoor Air Temperature ArbitratorAV10104Outdoor Air Humidity ArbitratorAV10106Space Temperature ArbitratorAV10108Space CO2 Concentration ArbitratorAV10109Space Humidity ArbitratorAV10113Outdoor Air Temperature BASAV10114Space Temperature BASAV10116Outdoor Air Humidity BASAV10118Space CO2 Concentration BASAV10119Space Humidity BASAV10121Discharge Air Cooling Setpoint BASAV10122Discharge Air Heating Setpoint BASAV10123Unoccupied Cooling SetpointAV10124Unoccupied Heating SetpointAV10127Space Temperature Setpoint BASAV10130Occupied OffsetAV10134Discharge Air Reheat Setpoint BASAV10138Filter Runtime Hours SetpointAV10139Cooling Capacity EnableAV10140Heat Primary Enable BASAV10141Morning Warmup Setpoint BASAV10142Occupied Standby OffsetAV10143Duct Static Pressure Setpoint BASAV10144Economizer Minimum Position Setpoint BASAV10149Daytime Warmup Setpoint BASAV10150Economizer Outdoor Air Enable Setpoint BASAV10154Space Cooling Setpoint High Limit BASAV10155Space Cooling Setpoint Low Limit BASAV10157Space Heating Setpoint High Limit BASAV10158Space Heating Setpoint Low Limit BASAV10159Occupied Cooling Setpoint BASAV10160Occupied Heating Setpoint BASAV10161Occupied Standby Cooling Setpoint BASAV10162Occupied Standby Heating Setpoint BASAV10167Discharge Air Temperature Minimum Cool LimitAV10168Relief Enable Position SetpointAV10169Occupied Bypass TimeAV10170Economizer Outdoor Air Enthalpy Enable Setpoint BASAV10175Space CO2 High LimitAV10176Space CO2 Low LimitAV10214Space Dehumidification Unoccupied Setpoint ActiveAV10228Space Dew Point Unoccupied Setpoint ActiveAV10281Discharge Air Temperature Setpoint ActiveAV11103Return Air Humidity BASAV11108Cabinet StyleAV11110Supply Fan Speed CommandAV11112Cooling Capacity Setpoint BASAV11113Space Dehumidification Setpoint Offset BAS - ActiveAV11115Exhaust Or Return Fan TypeAV11116Filter Runtime HoursAV11117Outdoor Air Enthalpy ActiveAV11118Return Air Temperature ArbitratorAV11119Return Air Temperature BASAV11120Heating Demand Limit Capacity Enable SetpointAV11121Discharge Air Temperature Maximum Cool LimitAV11122Run Time - Condenser Fan 1 (Hours)AV11123Run Time - Condenser Fan 2 (Hours)AV11124Run Time - Relief Fan (Hours)AV11125Run Time - Electric Heat Stage 1 (Hours)AV11126Run Time - Electric Heat Stage 2 (Hours)AV11127Run Time - Supply Fan (Hours)AV11128Space Temp Cooling Setpoint StatusAV11129Space Temp Heating Setpoint StatusAV11130Design Minimum OA Damper Position at Full Fan CapacityAV11131Design Minimum OA Damper Position at Mid Fan CapacityAV11132Design Minimum OA Damper Position at Min Fan CapacityAV11133DCV Minimum OA Damper Position at Full Fan CapacityAV11134DCV Minimum OA Damper Position at Mid Fan CapacityAV11135DCV Minimum OA Damper Position at Min Fan CapacityAV11136Space Dehumidification Setpoint BAS - ActiveAV11137Discharge Air Heating Setpoint High LimitAV11138Discharge Air Heating Setpoint (Target)AV11140Discharge Air Cooling Setpoint (Target)AV11147Economizer Dry Bulb Enable OffsetAV11148Duct Static Pressure P-Gain (%/IWC)AV11149Duct Static Pressure Deadband BASAV11150Cooling Reset Start TempAV11151Cooling Reset End TempAV11152Cooling Reset AmountAV11153Service Test Timeout (Minutes)AV11154Economizer Cooling Reference Enthalpy OffsetAV11155Starts - Condenser Fan 1AV11156Starts - Condenser Fan 2AV11157Starts - Relief FanAV11158Starts - Electric Heat Stage 1AV11159Starts - Electric Heat Stage 2AV11160Starts - Supply FanAV11161Supply Fan TypeAV11163Supply Fan Speed StatusAV11164Heating Capacity Setpoint BASAV11167Demand Shed Offset SetpointAV11168Cooling Demand Limit Capacity Enable SetpointAV11169Run Time - Compressor 1 (Hours)AV11170Run Time - Compressor 2 (Hours)AV11173Supply Fan Minimum Speed SetpointAV11174Supply Fan Maximum Speed SetpointAV11178Space Temperature ActiveAV11180Space Temperature Heating Setpoint Input ActiveAV11181Space Temperature Setpoint ActiveAV11183Starts - Compressor 1AV11184Starts - Compressor 2AV11185Cooling Capacity Enable - ActiveAV11186Daytime Warmup Setpoint BAS - ActiveAV11187Supply Fan Speed Command - ActiveAV11189Cooling Capacity Setpoint BAS - ActiveAV11190Discharge Air Cooling Setpoint BAS - ActiveAV11191Discharge Air Heating Setpoint BAS - ActiveAV11192Discharge Air Reheat Setpoint BAS - ActiveAV11193Discharge Air Temperature Minimum Cool Limit - ActiveAV11195Economizer Minimum Position Setpoint BAS - ActiveAV11196Economizer Outdoor Air Enthalpy Enable Setpoint BAS - ActiveAV11197Economizer Outdoor Air Enable Setpoint BAS - ActiveAV11198Relief Enable Position Setpoint - ActiveAV11199Heating Demand Limit Capacity Enable Setpoint - ActiveAV11200Discharge Air Temperature Maximum Cool Limit - ActiveAV11202Cool TypeAV11204DCV Minimum OA Damper Position at Full Fan Capacity - ActiveAV11205DCV Minimum OA Damper Position at Mid Fan Capacity - ActiveAV11206DCV Minimum OA Damper Position at Min Fan Capacity - ActiveAV11209Demand Shed Offset Setpoint - ActiveAV11211Design Minimum OA Damper Position at Full Fan Capacity - ActiveAV11212Design Minimum OA Damper Position at Mid Fan Capacity - ActiveAV11213Design Minimum OA Damper Position at Min Fan Capacity - ActiveAV11214Economizer Dry Bulb Disable Return Air OffsetAV11217Filter Runtime Hours Setpoint - ActiveAV11218Heat Primary Enable BAS - ActiveAV11219Heating Capacity Setpoint BAS - ActiveAV11220Morning Warmup Setpoint BAS - ActiveAV11226Space CO2 High Limit - ActiveAV11227Space CO2 Low Limit - ActiveAV11236Discharge Air Cooling Setpoint (Target) - ActiveAV11237Discharge Air Heating Setpoint High Limit - ActiveAV11238Duct Static Pressure Reset Time (seconds)AV11240Duct Static Pressure Deadband ActiveAV11241Heating Reset Start TempAV11242Heating Reset End TempAV11243Supply Fan Maximum Speed Setpoint - ActiveAV11245Supply Fan Minimum Speed Setpoint - ActiveAV11247Cooling Demand Limit Capacity Enable Setpoint - ActiveAV11248Economizer Minimum Position Setpoint ActiveAV11249Heating Capacity Secondary StatusAV11250Occupied Standby Cooling Setpoint BAS - ActiveAV11251Occupied Standby Heating Setpoint BAS - ActiveAV11252Preheat TypeAV11253Reheat TypeAV11254Space CO2 Concentration ActiveAV11256Compressor Cooling P-Gain (%/F)AV11257Compressor Cooling Reset Time (seconds)AV11258Economizer Cooling P-Gain - 1 (%/F)AV11259Economizer Cooling Reset Time - 1 (Seconds)AV11264Compressor Heating P-Gain (%/F)AV11265Compressor Heating Reset Time (seconds)AV11266Auxiliary Heating P-Gain (%/F)AV11267Auxiliary Heating Reset Time (seconds)AV11268Compressor Cooling P-Gain - 1 (%/F)AV11269Compressor Cooling Reset Time - 1 (seconds)AV11270Compressor Cooling P-Gain - 2 (%/F)AV11271Compressor Cooling Reset Time - 2 (seconds)AV11272Economizer Discharge Air SetpointAV11273Economizer Discharge Air Setpoint - ActiveAV11274Heat Pump Heating Lockout SetpointAV11275Heat Pump Heating Lockout Setpoint - ActiveAV11276Space Temperature Setpoint Input ActiveAV11277Space Temperature Cooling Setpoint Input ActiveAV11278Supply Fan PowerAV11280Duct Static Pressure Setpoint ActiveAV11281Dehumidification Control StatusAV11282Supply Fan 1 Maximum RPM StatusAV11283Supply Fan Minimum RPM StatusAV11284Run Time - Supply Fan 2 (Hours)AV11285Starts - Supply Fan 2AV11286Motorized Damper Position SetpointAV11287Motorized Damper Position Setpoint - ActiveAV11288Standby Minimum OA Damper Position at Full Fan CapacityAV11289Standby Minimum OA Damper Position at Full Fan Capacity - ActiveAV11290Standby Minimum OA Damper Position at Mid Fan CapacityAV11291Standby Minimum OA Damper Position at Mid Fan Capacity - ActiveAV11292Standby Minimum OA Damper Position at Min Fan CapacityAV11293Standby Minimum OA Damper Position at Min Fan Capacity - ActiveAV11294Supply Fan 2 PowerAV11295Run Time - Gas Heat Stage 1 (Hours)AV11296Starts - Gas Heat Stage 1AV11297Run Time - Gas Heat Stage 2 (Hours)AV11298Starts - Gas Heat Stage 2AV11299Return Air Humidity ActiveAV11300Return Air Humidity ArbitratorAV11301Return Air Enthalpy ActiveAV11302Relief Enable Position Setpoint StatusAV11304Supply Fan RPMAV11305Supply Fan 2 RPMAV11306Supply Fan 2 Maximum RPM StatusAV11307Discharge Air Heating Setpoint (Target) - ActiveAV11308Duct Static Pressure Setpoint High Limit Setpoint BASAV11309Duct Static Pressure Setpoint High Limit Setpoint BAS - ActiveAV11314Comfort Purge Interval (minutes)AV11315Reheat Purge Interval (minutes)AV11316Reheat P-Gain 1AV11317Reheat Reset Time - 1AV11318Reheat P-Gain 2AV11319Reheat Reset Time - 2AV11320Space Dew Point Setpoint BASAV11321Dew Point Setpoint Offset BASAV11323Outdoor Air Dew Point Setpoint BASAV11326Space Dehumidification Setpoint Offset BASAV11327Space Dehumidification Setpoint BASAV11329Space Dehumidification Unoccupied Setpoint BASAV11330Space Dew Point Unoccupied Setpoint BASAV11331Compressor Dehumid P-Gain 2AV11332Compressor Dehumid P-Gain 1AV11333Compressor Dehumid Reset Time - 2 (seconds)AV11334Compressor Dehumid Reset Time - 1 (seconds)AV11335Pre Cool Setpoint BASAV11336Pre Cool Setpoint BAS - ActiveAV11337Refrigerant Target Setpoint ActiveAV11338Space Dew Point Setpoint ActiveAV11340Dew Point Setpoint Offset BAS - ActiveAV11341Outdoor Air Dew Point Setpoint BAS - ActiveAV11342Unoccupied Dehumidification TimerAV11343Heating Reset AmountAV11344VAV Box Stroke TimerAV11346Economizer Cooling P-Gain (%/F)AV11347Economizer Cooling Reset Time (Seconds)AV11348Economizer Cooling P-Gain - 2 (%/F)AV11349Economizer Cooling Reset Time - 2 (Seconds)AV11350Auxiliary Heating P-Gain - 1 (%/F)AV11351Auxiliary Heating Reset Time - 1 (seconds)AV11352Auxiliary Heating P-Gain - 2 (%/F)AV11353Auxiliary Heating Reset Time - 2 (seconds)AV11354Discharge Air Heating Setpoint Low LimitAV11355Discharge Air Heating Setpoint Low Limit - ActiveAV11356Discharge Air Cooling Setpoint StatusAV11357Discharge Air Heating Setpoint StatusAV11358Discharge Air Reheating Setpoint High Limit - ActiveAV11359Discharge Air Reheating Setpoint Low Limit - ActiveAV11360Discharge Air Reheating Setpoint High LimitAV11361Discharge Air Reheating Setpoint Low LimitAV11362Run Time - Gas Heat Manifold 1 Burner 1 (Hours)AV11363Starts - Gas Heat Manifold 1 Burner 1AV11364Run Time - Gas Heat Manifold 1 Burner 2 (Hours)AV11365Starts - Gas Heat Manifold 1 Burner 2AV11368Auxiliary Heating P-Gain Modulating Gas Staging (%/F)AV11369Auxiliary Heating Reset Time Modulating Gas Staging (seconds)AV11375Run Time - Circuit 1 Condenser Defrost (Hours)AV11376Starts - Circuit 1 Condenser DefrostAV11383Condenser Fan CapacityAV11384Compressor Cooling Modulating P-Gain - 2 (%/F)AV11385Compressor Cooling Modulating Reset Time - 2 (seconds)AV11386Compressor Cooling Modulating P-Gain (%/F)AV11387Compressor Cooling Modulating Reset Time (seconds)AV11388Control StateAV11389Demand Defrost Initiate Delta TemperatureAV11392Discharge Air Cooling Setpoint Y1AV11393Discharge Air Cooling Setpoint Y1 - ActiveAV11394Discharge Air Cooling Setpoint Y2AV11395Discharge Air Cooling Setpoint Y2 - ActiveAV11398Dehumidification Disable Space Temperature SetpointAV11399Supply Fan Maximum Speed Setpoint HeatingAV11400Low Saturated Suction Refrig Temp Abnormal Deviation OffsetAV11401Low Saturated Suction Refrig Temp Coefficient 1AV11402Low Saturated Suction Refrig Temp Coefficient 2AV11403Entering Water Temperature ArbitratorAV11404Entering Water Temperature BASAV11405Heat Pump Heating Changeover Delay (Minutes)AV11406Heat Pump Heating Changeover OffsetAV11407Heat Pump Heating Space Recovery DeltaAV11408Run Time - Circuit 1 Heat Pump (Hours)AV11410Heating Capacity Primary LimitAV11411Heating Capacity Primary Limit - ActiveAV11412Heating Capacity Secondary LimitAV11413Heating Capacity Secondary Limit - ActiveAV11414Supply Air Tempering Enable SetpointAV11415Supply Air Tempering Disable SetpointAV11416Supply Air Tempering Delay (Seconds)AV11417Secondary Heating Lockout SetpointAV11418Secondary Heating Lockout Setpoint - ActiveAV11419Auxiliary Heating P-Gain Modulating Electric Staging (%/F)AV11420Auxiliary Heating Reset Time Modulating Electric Staging (seconds)AV11421Design Air FlowAV11422Hydronic Heating Standby Freeze Avoidance PositionAV11423Hydronic Heating Standby Freeze Avoidance Position - ActiveAV11424Run Time - Electric Heat 1 Command Status (Hours)AV11425Run Time - Electric Heat 2 Command Status (Hours)AV11426Run Time - Electric Heat 3 Command Status (Hours)AV11427Starts - Electric Heat 1 Command StatusAV11428Starts - Electric Heat 2 Command StatusAV11429Starts - Electric Heat 3 Command StatusAV11430Hydronic Freeze Avoidance SetpointAV11431Hydronic Freeze Avoidance Setpoint - ActiveAV11432Heating Primary Capacity Setpoint BASAV11433Heating Primary Capacity Setpoint BAS - ActiveAV11434Heating Secondary Capacity Setpoint BASAV11435Heating Secondary Capacity Setpoint BAS - ActiveAV11448Compressor Heating P-Gain - 2 (%/F)AV11449Compressor Heating Reset Time - 2 (seconds)BI10105FDD: Unit Economizing When It Should NotBI10106FDD: Unit Not Economizing When It ShouldBI10107FDD: Excessive Outdoor AirBI10108FDD: Outdoor Air Damper Not ModulatingBI10121Relief Fan Output StatusBI10143VAV Box CommandBI10170Condensate Overflow InputBI10172Occupancy InputBI10210Equipment Shutdown Input StatusBI10211External Auto Stop Input StatusBI10219Economizer Airside StatusBI10226Supply Fan StatusBI11100Compressor 1 Command StatusBI11101Circuit 1 LPC StatusBI11102Compressor 1 Proving StatusBI11103Compressor 2 Command StatusBI11105Compressor 2 Proving StatusBI11109Compressor 1 Unloader Command StatusBI11111Compressor 2 Unloader Command StatusBI11113Demand Limit InputBI11114Demand Shed InputBI11115Phase Monitor StatusBI11116Condenser Fan 1 Command StatusBI11117Condenser Fan 2 Command StatusBI11118Switchover Valve 1 Command StatusBI11120Thermostat G InputBI11121Thermostat W1/O InputBI11122Thermostat W2 InputBI11123Thermostat X2 InputBI11124Thermostat Y1 InputBI11125Thermostat Y2 InputBI11126Supply Fan Proving Input StatusBI11127FroStat InputBI11128Electric Heat Stage 1 StatusBI11129Electric Heat Stage 2 StatusBI11130Clogged Filter InputBI11133Ventilation Override Exhaust StatusBI11134Ventilation Override Pressurize StatusBI11135Ventilation Override Purge StatusBI11143Reheat Humidistat InputBI11149Fan Mode - Air-FiBI11150Occupancy Input - Air-FiBI11151Fan Mode InputBI11152Supply Air Smoke Detector StatusBI11153Return Air Smoke Detector StatusBI11154Gas Heat Stage 1 StatusBI11155Gas Heat Stage 2 StatusBI11156Diagnostic: ERM Supply Fan Locked Motor - 1BI11157Diagnostic: ERM Supply Fan Locked Motor - 2BI11158Diagnostic: ERM Supply Fan Motor Overheated - 1BI11159Diagnostic: ERM Supply Fan Motor Overheated - 2BI11160Diagnostic: ERM Supply Fan Power Mod Overheated - 1BI11161Diagnostic: ERM Supply Fan Power Mod Overheated - 2BI11162Diagnostic: ERM Fault Supply Fan - 1BI11163Diagnostic: ERM Fault Supply Fan - 2BI11164Diagnostic: IGN1 Module LockoutBI11165Diagnostic: IGN1 Heating High Temp Limit OpenBI11166Diagnostic: IGN1 Flame Rollout Switch OpenBI11167Diagnostic: IGN1 Inducer Proving Switch Fail ClosedBI11168Diagnostic: IGN1 Inducer Proving Switch Fail OpenBI11169Diagnostic: IGN1 No Flame Sensed on IgnitionBI11170Diagnostic: IGN1 Flame Sensed w/Gas Valve OffBI11171Diagnostic: IGN1 Hardware Configuration ErrorBI11172Diagnostic: IGN1 Weak FlameBI11173Diagnostic: IGN1 Gas Valve ErrorBI11174Diagnostic: IGN1 Module FailureBI11175Diagnostic: ERM Supply Fan Phase Failure - 1BI11176Diagnostic: ERM Supply Fan Phase Failure - 2BI11177Diagnostic: ERM Supply Fan Internal Comm Failure - 1BI11178Diagnostic: ERM Supply Fan Internal Comm Failure - 2BI11179Diagnostic: ERM Supply Fan Hall Sensor Error - 1BI11180Diagnostic: ERM Supply Fan Hall Sensor Error - 2BI11181Diagnostic: ERM Supply Fan Speed Limit Exceeded - 1BI11182Diagnostic: ERM Supply Fan Speed Limit Exceeded - 2BI11183Diagnostic: ERM Supply Fan Rotor Calibration - 1BI11184Diagnostic: ERM Supply Fan Rotor Calibration - 2BI11185Diagnostic: ERM Supply Fan DC link Undervoltage - 1BI11186Diagnostic: ERM Supply Fan DC link Undervoltage - 2BI11187Reheat Pumpout Solenoid StatusBI11189Reheat Valve 1 Fault StatusBI11190Reheat Valve 1 Calibration StatusBI11192VAV Changeover InputBI11193Crankcase Heater CommandBI11195Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 1BI11196Diagnostic: Gas Heat Unexpected Flame Manif 1 Burner 2BI11197Diagnostic: Modulating Gas Invalid ID Plug Manifold 1BI11198Diagnostic: Modulating Gas Heat Configuration InvalidBI11199Diagnostic: Gas Heat Weak Flame Manif 1 Burner 1BI11200Diagnostic: Gas Heat Weak Flame Manif 1 Burner 2BI11201Diagnostic: Gas Heat Insufficient Combustion AirBI11202Diagnostic: Modulating Gas Primary Limit Open Manifold 1BI11203Diagnostic: Modulating Gas Heat Open Fuse Manifold 1BI11204Diagnostic: Gas Heat Failed Ignition Manifold 1BI11205Diagnostic: Modulating Gas Valve Failure Manifold 1BI11206Diagnostic: Modulating Gas Control Board Failure Manifold 1BI11231Diagnostic: Gas Heat Lockout Manifold 1BI11235Diagnostic: Gas Heat Failed Ignition Manifold 1 Burner 2BI11237Diagnostic: VFD Cprsr Current Overload - Cprsr 1BI11238Diagnostic: VFD Compressor Ground Fault - Cprsr 1BI11239Diagnostic: VFD Compressor Short Circuit - Cprsr 1BI11240Diagnostic: VFD Compressor In Hand Mode - Cprsr 1BI11241Diagnostic: Gas Heat Air Pressure Sensor Reading LowBI11242Diagnostic: Gas Heat Air Pressure Sensor Reading HighBI11243Diagnostic: Gas Heat Loss of Inducer Motor ControlBI11244Diagnostic: Gas Heat Air Sensor Null Pressure CheckBI11245Diagnostic: Gas Heat Limited Low FireBI11246Heating Output Operational LimitBI11247Diagnostic: Refrigerant Concentration Sensor ABI11248Refrigerant Leak Detection System InputBI11249Diagnostic: Refrigerant Leak Sensor Failure Sensor ABI11250Diagnostic: IGN1 Low Ambient LockoutBI11251Diagnostic: Low Saturated Suction Refrig ProtectionBI11252Diagnostic: Low Saturated Suction Refrig Protection DisabledBI11253Electric Heat 1 Command StatusBI11254Electric Heat 2 Command StatusBI11255Electric Heat 3 Command StatusBI11256Diagnostic: Freeze ProtectionBI11257Diagnostic: Freeze Avoidance ModeBI11258Freezestat InputBV10103Heat Lockout CommandBV10104Supply Fan Configuration CommandBV10106Dehumidification Enable CommandBV10109Filter Timer ResetBV10110Reset DiagnosticBV10111Daytime Warmup Enable CommandBV10112Morning Warmup Enable CommandBV10113Occupancy Input BASBV10115Cooling Lockout BASBV10119Supply Air Tempering EnableBV11100Alarm Indicator StatusBV11101Supply Fan High Speed Command StatusBV11112Condenser Defrost StatusBV11113Unit Stop CommandBV11114Supply Fan Speed Command EnableBV11115Cooling Capacity Setpoint Enable BASBV11116Heating Capacity Setpoint Enable BASBV11119Supply Fan CompensationBV11121Compressor 1 Run Time ResetBV11122Compressor 1 Starts ResetBV11123Compressor 2 Run Time ResetBV11124Compressor 2 Starts ResetBV11127Condenser Fan 1 Run Time ResetBV11128Condenser Fan 1 Starts ResetBV11129Condenser Fan 2 Run Time ResetBV11130Condenser Fan 2 Starts ResetBV11133Relief Fan Run Time ResetBV11134Relief Fan Starts ResetBV11135Electric Heat Stage 1 Run Time ResetBV11136Electric Heat Stage 1 Starts ResetBV11137Electric Heat Stage 2 Run Time ResetBV11138Electric Heat Stage 2 Starts ResetBV11139Supply Fan Run Time ResetBV11140Supply Fan Starts ResetBV11142Diagnostic: Heat FailureBV11143Diagnostic: Duct Static Pressure Limit TripBV11144Diagnostic: Filter Change RequiredBV11145Diagnostic: Condensate Overflow LockoutBV11146Diagnostic: FroStat TripBV11155Diagnostic: Comp 1 Proving TripBV11156Diagnostic: Comp 2 Proving TripBV11158Diagnostic: Circuit 1 LPC TripBV11161Diagnostic: Compressor 1 Contactor FailureBV11162Diagnostic: Circuit 1 LPC LockoutBV11166VVZT DAT Control ModeBV11172Diagnostic: Compressor 1 Proving LockoutBV11173Occupancy Input ActiveBV11174Diagnostic: Compressor 2 Contactor FailureBV11176Diagnostic: Compressor 2 Proving LockoutBV11177Diagnostic: Demand Defrost DisabledBV11180Diagnostic: Demand Defrost Fault ABV11183Diagnostic: Demand Defrost Fault BBV11186Diagnostic: Demand Defrost Fault CBV11189Diagnostic: Demand Defrost Fault DBV11190Diagnostic: Maintenance RequiredBV11192Diagnostic: Unit Communications FailureBV11199Supply Fan Configuration StatusBV11200Timed Override Timer Is ActiveBV11201Supply Fan Speed Command Enable - ActiveBV11202Cooling Capacity Setpoint Enable BAS - ActiveBV11203Cooling Lockout BAS - ActiveBV11204Heating Capacity Setpoint Enable BAS - ActiveBV11205Daytime Warmup Enable Command - ActiveBV11208Supply Fan Compensation - ActiveBV11209Dehumidification Enable Command - ActiveBV11211VVZT DAT Control Mode - ActiveBV11216Heat Lockout Command - ActiveBV11217Morning Warmup Enable Command - ActiveBV11221Supply Air Tempering StatusBV11222Supply Air Tempering Enable - ActiveBV11224Occupancy Input ArbitratorBV11226Demand Limit Request BASBV11227Demand Limit Request - ActiveBV11230Diagnostic: VFD Compressor Fault - Cprsr 1BV11231Daytime Warmup ActiveBV11232Morning Warmup ActiveBV11233Supply Fan 2 Run Time ResetBV11234Supply Fan 2 Starts ResetBV11235Occupied Standby Supply Fan Configuration CommandBV11236Occupied Standby Supply Fan Configuration Command - ActiveBV11239Gas Heat Stage 1 Run Time ResetBV11240Gas Heat Stage 1 Starts ResetBV11241Gas Heat Stage 2 Run Time ResetBV11242Gas Heat Stage 2 Starts ResetBV11243Diagnostic: ERM Supply Fan 1 FailureBV11244Diagnostic: ERM Supply Fan 2 FailureBV11245Diagnostic: Supply Fan Proving FailureBV11248Diagnostic: High Condensate Level DetectedBV11249Diagnostic: Morning Warmup Mode Exceeded 120 MinutesBV11250Diagnostic: Pre Cool Mode Exceeded 120 MinutesBV11251Diagnostic: Night Purge Mode Exceeded 120 MinutesBV11253Heat Pump Heating Lockout Setpoint EnableBV11254Heat Pump Heating Lockout Setpoint Enable - ActiveBV11255Dehumidification StatusBV11256Pre Cool Enable CommandBV11257Pre Cool Enable Command - ActiveBV11258Pre Cool ActiveBV11259Occupied Dehumidification Enable BASBV11260Occupied Dehumidification Enable BAS - ActiveBV11261Unoccupied Dehumidification Enable BASBV11262Unoccupied Dehumidification Enable BAS - ActiveBV11263Diagnostic: Duct Static Pressure Limit LockoutBV11264Diagnostic: Duct Static Pressure Local TripBV11265Diagnostic: Duct Static Pressure Local LockoutBV11266Gas Heat Manifold 1 Burner 1 Run Time ResetBV11267Gas Heat Manifold 1 Burner 1 Starts ResetBV11268Gas Heat Manifold 1 Burner 2 Run Time ResetBV11269Gas Heat Manifold 1 Burner 2 Starts ResetBV11272Circuit 1 Condenser Defrost Run Time ResetBV11273Circuit 1 Condenser Defrost Starts ResetBV11277Diagnostic: Reheat Valve 1 FaultBV11283Refrigerant Mitigation ActiveBV11284Thermostat Control Method RequestBV11285Thermostat Control Method StatusBV11288Heating Capacity Control Type Override BASBV11289Circuit 1 Heat Pump Run Time ResetBV11291Diagnostic: Primary Heat Installed but Locked Out by ApplicationBV11292Diagnostic: Secondary Heat Installed but Locked Out by ApplicationBV11293Secondary Heating Lockout Setpoint EnableBV11294Secondary Heating Lockout Setpoint Enable - ActiveBV11295Hydronic Heat Valve Direct/Reverse ActingBV11296Freeze Avoidance EnableBV11297Freeze Avoidance Enable - ActiveBV11300Electric Heat 1 Command Status Run Time ResetBV11301Electric Heat 2 Command Status Run Time ResetBV11302Electric Heat 3 Command Status Run Time ResetBV11303Electric Heat 1 Command Status Starts ResetBV11304Electric Heat 2 Command Status Starts ResetBV11305Electric Heat 3 Command Status Starts ResetBV11306Relief Fan 2 Run Time ResetBV11307Relief Fan 2 Starts ResetMI10101Heat Cool Mode StatusMI10144Economizer System StatusMI11100System Mode Switch Air-FiMI11101Timed Override Air-FiMI11102System Mode Switch InputMI11103Timed Override InputMI11104Supply Fan 1 ERM Information Alarm StatusMI11105Supply Fan 2 ERM Information Alarm StatusMV10101Cooling Reset Type StatusMV10102Emergency Override BASMV10103Economizer Airside Enable BASMV10104Heat Cool Mode RequestMV10106Occupancy RequestMV10110Timed Override RequestMV11100Arbitration Method RequestMV11101Customer Options Module Communication StatusMV11102Economizer TypeMV11103Fresh Air Options Module Communication StatusMV11105Indoor Options Module Communication StatusMV11106On-Board I/O Communication StatusMV11110Service Test State RequestMV11111Cooling Reset TypeMV11112System Mode Switch LocalMV11113Timed Override StatusMV11114Trane Unit TypeMV11115Unit Stop SourceMV11116Emergency Override BAS - ActiveMV11118Economizer Decision MethodMV11119Refrigerant TypeMV11120Economizer Airside Enable BAS - ActiveMV11121Heat Cool Mode Request - ActiveMV11123Occupancy StatusMV11125Occupancy Request ActiveMV11126Supply Fan 1 Communication StatusMV11127Supply Fan 2 Communication StatusMV11128Gas Heat Ignition Module 1 Communication StatusMV11130Emergency Override StatusMV11133Stepper Motor Communication StatusMV11136Heating Reset TypeMV11137Heating Reset Type StatusMV11138Compressor 1 VFD Communication StatusMV11139Refrigerant Leak Sensor Communication Status Sensor A
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- Name suffixes carry meaning: Status/Local/Active/Input are read-only, BAS/Command/Request/Setpoint value objects are the ones a BAS writes, and Arbitrator objects show which source is winning.
- Access 'C' marks writable objects whose arbitration pattern the doc lists as setpoint with a priority array, plus AV 10127, AV 10159 and AV 10160, which the integration guide (BAS-SVP085B) calls commandable; other writable objects are 'W'.
- The Symbio 700 integration guide (BAS-SVP085B-EN, Nov 2024) covers BACnet IP and BACnet MS/TP; the rotary address (001-127) sets the MS/TP MAC and the default Device ID, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 700 Precedent / Axiom and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 700 Precedent / Axiom
How many BACnet points does the Trane Symbio 700 Precedent / Axiom have?
This list has 639 BACnet objects: 53 analog inputs, 294 analog values, 119 binary inputs, 131 binary values, 8 multi-state inputs, 34 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 700 Precedent / Axiom BACnet points are writable?
232 of the 639 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Trane Symbio 700 Precedent / Axiom BACnet documentation?
The source is Symbio 700 Integration Points List BACnet/Modbus - Precedent, Axiom Rooftop WSHP (BAS-PTS001C-EN), revision 08/12/2026, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS001C-EN_08172026.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 700 Precedent / Axiom?
Start with MV 10106 Occupancy Request (Occupancy command (occupied/unoccupied/standby)); BV 11113 Unit Stop Command (BMS stop/auto of the whole unit); AV 10159 Occupied Cooling Setpoint BAS (Occupied cooling setpoint (dual-setpoint units)); AV 10160 Occupied Heating Setpoint BAS (Occupied heating setpoint (dual-setpoint units)); AV 10127 Space Temperature Setpoint BAS (Single-setpoint alternative to the two setpoints above); MI 10101 Heat Cool Mode Status (Current heat/cool operating mode); MV 11123 Occupancy Status (Confirms the occupancy the unit is running in); BI 10226 Supply Fan Status (Supply fan on/off status); AV 11178 Space Temperature Active (Space temperature the unit is actually controlling to); BV 11100 Alarm Indicator Status (Unit alarm output; on when the controller is in alarm).
How do I enable BMS control of the Trane Symbio 700 Precedent / Axiom?
MV 11100 Arbitration Method Request picks the control type. 'Enable External/BAS Control' is the factory default: the controller weighs BAS, Air-Fi and wired sources and uses the BAS value while it is valid. 'Standalone Control' ignores all BAS input. BV 11113 Unit Stop Command (Auto/Stop) stops the unit from the BMS.
Does the Trane Symbio 700 Precedent / Axiom need a BACnet heartbeat or have a communication timeout?
The sensor BAS points (space temp, OA temp, humidity, CO2, return air, and entering water temp on Axiom WSHPs) have a 900 s heartbeat in the points list: per the integration guide, a value that is not rewritten at least every 15 minutes fails, its priority-12 entry drops out of the Arbitrator and the controller falls back to the next source (Air-Fi, wired, then default). BV 10113 Occupancy Input BAS has the same 15-minute heartbeat. The space setpoint BAS points (AV 10127, AV 10159/10160) and MV 10106 Occupancy Request are commandable and have no heartbeat.
Can the BMS supply sensor values to the Trane Symbio 700 Precedent / Axiom?
Write the value to the matching '... BAS' AV (e.g. AV 10114 Space Temperature BAS, AV 10113 Outdoor Air Temperature BAS) and keep refreshing it. It shows on the '... Arbitrator' object at priority 12, above Air-Fi (14) and wired (15). The '... Active' object reports the value in use. Space setpoints go to AV 10127 Space Temperature Setpoint BAS (single setpoint) or AV 10159/10160 Occupied Cooling/Heating Setpoint BAS (dual setpoint).
How do I check these points on the real Symbio 700 Precedent / Axiom?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 700 Integration Points List BACnet/Modbus - Precedent, Axiom Rooftop WSHP · BAS-PTS001C-EN · rev. 08/12/2026. Object names, instances and units are reproduced as published; descriptions are our own.