Air-cooled chiller controller · BACnet points list
Trane Symbio 800 Ascend ACR Series C BACnet points list
Updated 28 October 2026
Ascend ACR Series C chillers with Symbio 800 publish about 770 BACnet objects; roughly 550 are diagnostic binary inputs. AIs cover water temperatures and pressures, refrigerant circuits, compressor drives, free cooling and power metering. The BAS writes chilled water setpoint, demand limit, pump speed or flow setpoints, mode, lockouts and auto/stop.
This page lists 772 BACnet objects for the Trane Symbio 800 Ascend ACR Series C — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 Ascend ACR Series C
- Equipment
- Air-cooled chiller controller
- Equipment type
- Chillers
- BACnet objects
- 772 (15 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 Ascend ACR Series C
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10108 | Chiller Auto Stop Command BAS | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10103 | Chiller Running State | Chiller on/off status | Read |
| BI 10101 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10104 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10180 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10116 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10108 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10124 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10100 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10106 Chiller Setpoint Source shows BAS, External or Front Panel.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
- The document says BAS setpoint values go through the controller's arbitration logic, so a written value may not be the one in use.
Trane Symbio 800 Ascend ACR Series C BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Chilled Water Setpoint | Value of the active Chilled Water Setpoint actively being | Temperature | Read | |
| AI | 10101 | Active Demand Limit Setpoint | With Ice Building not Installed | Percentage | Read | |
| AI | 10103 | Evaporator Entering Water Temperature | Current temperature of the water entering the evaporator | Temperature | Read | |
| AImin | 10104 | Evaporator Leaving Water Temperature | Current temperature of the water leaving the evaporator | Temperature | Read | |
| AI | 10106 | Unit Power Consumption | Measurement of the power being consumed by the Chiller | Power, Electrical | Read | |
| AI | 10107 | Outdoor Air Temperature | Current temperature of the outdoor air | Temperature | Read | |
| AI | 10110 | Evaporator Refrigerant Pressure Circuit 1 | Current pressure of the refrigerant in the evaporator on circuit 1 | Pressure, Fluidic | Read | |
| AI | 10111 | Condenser Refrigerant Pressure Circuit 1 | Current pressure of the refrigerant in the condenser on circuit 1 | Pressure, Fluidic | Read | |
| AI | 10112 | Differential Refrigerant Pressure Circuit 1 | Pressure difference between the suction and discharge lines on circuit 1 | Pressure, Fluidic | Read | |
| AI | 10113 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Saturated refrigerant temperature of the evaporator on circuit 1 | Temperature | Read | |
| AI | 10114 | Condenser Saturated Refrigerant Temperature Circuit 1 | Saturated refrigerant temperature of the condenser on circuit 1 | Temperature | Read | |
| AI | 10115 | Evaporator Refrigerant Pressure Circuit 2 | Current pressure of the refrigerant in the evaporator on circuit 2 | Pressure, Fluidic | Read | |
| AI | 10116 | Condenser Refrigerant Pressure Circuit 2 | Current pressure of the refrigerant in the condenser on circuit 2 | Pressure, Fluidic | Read | |
| AI | 10117 | Differential Refrigerant Pressure Circuit 2 | Pressure difference between the suction and discharge lines on circuit 2 | Pressure, Fluidic | Read | |
| AI | 10118 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Saturated refrigerant temperature of the evaporator on circuit 2 | Temperature | Read | |
| AI | 10119 | Condenser Saturated Refrigerant Temperature Circuit 2 | Saturated refrigerant temperature of the condenser on circuit 2 | Temperature | Read | |
| AI | 10120 | Refrigerant Discharge Temperature - Compressor 1A | Current temperature of the refrigerant being discharged from Compressor 1A | Temperature | Read | |
| AI | 10121 | High Side Oil Pressure - Compressor 1A | Pressure of the oil on the high pressure side of Compressor 1A | Pressure, Fluidic | Read | |
| AI | 10122 | Refrigerant Discharge Temperature - Compressor 2A | Current temperature of the refrigerant being discharged from Compressor 2A | Temperature | Read | |
| AI | 10123 | High Side Oil Pressure - Compressor 2A | Pressure of the oil on the high pressure side of Compressor 2A | Pressure, Fluidic | Read | |
| AI | 10124 | Air Flow Percentage Circuit 1 | Approximate air flow percentage of Circuit 1 | Percentage | Read | |
| AI | 10125 | Air Flow Percentage Circuit 2 | Approximate air flow percentage of Circuit 2 | Percentage | Read | |
| AI | 10126 | Drive Motor Average Voltage Circuit 1 | Average voltage line to line at AFD for Compressor 1A | Voltage | Read | |
| AI | 10127 | Drive Motor Current U Circuit 1 | Current | Read | ||
| AI | 10128 | Drive Motor Current V Circuit 1 | Current | Read | ||
| AI | 10129 | Drive Motor Current W Circuit 1 | Current | Read | ||
| AI | 10130 | Drive Motor Current U RLA Circuit 1 | Percentage | Read | ||
| AI | 10131 | Drive Motor Current V RLA Circuit 1 | Percentage | Read | ||
| AI | 10132 | Drive Motor Current W RLA Circuit 1 | Percentage | Read | ||
| AI | 10133 | Drive Motor Average Current RLA Circuit 1 | Average current at AFD for Compressor 1A in terms of % RLA | Percentage | Read | |
| AI | 10134 | Drive DC Bus Voltage Circuit 1 | Voltage of the DC Bus from the AFD for Compressor 1A | Voltage | Read | |
| AI | 10135 | Drive Output Power Circuit 1 | Power output from the AFD for Compressor 1A | Power, Electrical | Read | |
| AI | 10136 | AFD Transistor Temperature Circuit 1 | Temperature of the transistor for the AFD for Compressor 1A | Temperature | Read | |
| AI | 10137 | Motor Winding Temperature 1 Circuit 1 | First temperaure sensor of the windings on motor 1A | Temperature | Read | |
| AI | 10138 | Motor Winding Temperature 2 Circuit 1 | Second temperaure sensor of the windings on motor 1A | Temperature | Read | |
| AI | 10139 | Drive Motor Average Voltage Circuit 2 | Average voltage line to line at AFD for Compressor 2A | Voltage | Read | |
| AI | 10140 | Drive Motor Current U Circuit 2 | Current | Read | ||
| AI | 10141 | Drive Motor Current V Circuit 2 | Current | Read | ||
| AI | 10142 | Drive Motor Current W Circuit 2 | Current | Read | ||
| AI | 10143 | Drive Motor Current U RLA Circuit 2 | Percentage | Read | ||
| AI | 10144 | Drive Motor Current V RLA Circuit 2 | Percentage | Read | ||
| AI | 10145 | Drive Motor Current W RLA Circuit 2 | Percentage | Read | ||
| AI | 10146 | Drive Motor Average Current RLA Circuit 2 | Average current at AFD for Compressor 2A in terms of % RLA | Percentage | Read | |
| AI | 10147 | Drive DC Bus Voltage Circuit 2 | Voltage of the DC Bus from the AFD for Compressor 2A | Voltage | Read | |
| AI | 10148 | Drive Output Power Circuit 2 | Power output from the AFD for Compressor 2A | Power, Electrical | Read | |
| AI | 10149 | AFD Transistor Temperature Circuit 2 | Temperature of the transidtor for the AFD for Compressor 2A | Temperature | Read | |
| AI | 10150 | Motor Winding Temperature 1 Circuit 2 | First temperaure sensor of the windings on motor 2A | Temperature | Read | |
| AI | 10151 | Motor Winding Temperature 2 Circuit 2 | Second temperaure sensor of the windings on motor 2A | Temperature | Read | |
| AI | 10152 | Sub Cooled Liquid Temperature Circuit 1 | Sub cooled liquid temperature of circuit 1 | Temperature | Read | |
| AI | 10153 | Sub Cooled Liquid Temperature Circuit 2 | Sub cooled liquid temperature of circuit 2 | Temperature | Read | |
| AI | 10154 | Evaporator Differential Water Pressure | Differential water pressure of the evaporator; with Variable Primary Flow | Temperature | Read | |
| AI | 10155 | System Chilled Water Differential Pressure | Differential water pressure of the chilled water system | Pressure, Fluidic | Read | |
| AI | 10158 | Phase AB Voltage - Compressor 1B | Measurement of voltage in Phase AB for Compressor 1B | Voltage | Read | |
| AI | 10159 | Line 1 Current - Compressor 1B | Measurement of Line 1 current for Compressor 1B in terms of Amps | Current | Read | |
| AI | 10160 | Line 2 Current - Compressor 1B | Measurement of Line 2 current for Compressor 1B in terms of Amps | Current | Read | |
| AI | 10161 | Line 3 Current - Compressor 1B | Measurement of Line 3 current for Compressor 1B in terms of Amps | Current | Read | |
| AI | 10162 | Line 1 Current RLA - Compressor 1B | Percentage | Read | ||
| AI | 10163 | Line 2 Current RLA - Compressor 1B | Percentage | Read | ||
| AI | 10164 | Line 3 Current RLA - Compressor 1B | Percentage | Read | ||
| AI | 10165 | Phase AB Voltage - Compressor 2B | Measurement of voltage in Phase AB for Compressor 2B | Voltage | Read | |
| AI | 10166 | Line 1 Current - Compressor 2B | Measurement of Line 1 current for Compressor 2B in terms of Amps | Current | Read | |
| AI | 10167 | Line 2 Current - Compressor 2B | Measurement of Line 2 current for Compressor 2B in terms of Amps | Current | Read | |
| AI | 10168 | Line 3 Current - Compressor 2B | Measurement of Line 3 current for Compressor 2B in terms of Amps | Current | Read | |
| AI | 10169 | Line 1 Current RLA - Compressor 2B | Percentage | Read | ||
| AI | 10170 | Line 2 Current RLA - Compressor 2B | Percentage | Read | ||
| AI | 10171 | Line 3 Current RLA - Compressor 2B | Percentage | Read | ||
| AI | 10173 | Refrigerant Discharge Temperature - Compressor 1B | Current temperature of the refrigerant being discharged from Compressor 1B | Temperature | Read | |
| AI | 10174 | High Side Oil Pressure - Compressor 1B | Pressure of the oil on the high pressure side of Compressor 1B | Pressure, Fluidic | Read | |
| AI | 10175 | Refrigerant Discharge Temperature - Compressor 2B | Current temperature of the refrigerant being discharged from Compressor 2B | Temperature | Read | |
| AI | 10176 | High Side Oil Pressure - Compressor 2B | Pressure of the oil on the high pressure side of Compressor 2B | Pressure, Fluidic | Read | |
| AI | 10177 | Number of Circuits | Number of refrigeration circuits in the chiller | Read | ||
| AI | 10178 | Number of Compressors Circuit 1 | Number of compressors on circuit 1 of the chiller | Read | ||
| AI | 10179 | Number of Compressors Circuit 2 | Number of compressors on circuit 2 of the chiller | Read | ||
| AImin | 10180 | Actual Running Capacity | Measurement of the power being consumed by the Chiller | Percentage | Read | |
| AI | 10181 | Free Cooling Capacity Status | % capacity of the free cooling being used | Percentage | Read | |
| AI | 10182 | Free Cooling Entering Water Temperature Active | Entering water temperature of the free cooling circuit | Temperature | Read | |
| AI | 10185 | Evaporator Differential Water Pressure Setpoint Status | Setpoint status of the evaporator differential water pressure | Pressure, Fluidic | Read | |
| AI | 10186 | Energy Consumption Lifetime | Total energy consumption of the chiller (for the lifetime of the chiller) | Energy, Electrical | Read | |
| AI | 10187 | Energy Consumption | Total energy consumption of the chiller (since last accumulation reset) | Energy, Electrical | Read | |
| AI | 10188 | Starts - Compressor 1A | Number of starts of Compressor 1A | Read | ||
| AI | 10189 | Run Time - Compressor 1A | Run time of Compressor 1A in seconds | Read | ||
| AI | 10190 | Starts - Compressor 2A | Number of starts of Compressor 2A | Read | ||
| AI | 10191 | Run Time - Compressor 2A | Run time of Compressor 2A in seconds | Read | ||
| AI | 10192 | Starts - Compressor 1B | Number of starts of Compressor 1B | Read | ||
| AI | 10193 | Run Time - Compressor 1B | Run time of Compressor 1B in seconds | Read | ||
| AI | 10194 | Starts - Compressor 2B | Number of starts of Compressor 2B | Read | ||
| AI | 10195 | Run Time - Compressor 2B | Run time of Compressor 2B in seconds | Read | ||
| AI | 10196 | Chiller Design Capacity | Design capacity of chilller | Power, Cooling | Read | |
| AI | 10198 | Chilled Water Setpoint Status | Chilled water setpoint temperature | Temperature | Read | |
| AI | 10199 | Demand Limit Setpoint Status | % capacity of the demand limit being used | Percentage | Read | |
| AI | 10200 | Unit Source ID | Last diagnostic of the chiller | Read | ||
| AI | 10201 | Drive Input Voltage Calculated 1A | Input voltage at the AFD for Compressor 1A | Voltage | Read | |
| AI | 10202 | Drive Input Voltage Calculated 2A | Input voltage at the AFD for Compressor 2A | Voltage | Read | |
| AI | 10203 | Active Cool/Heat Setpoint Temperature | Value of the active Chilled Water Setpoint actively being | Temperature | Read | |
| AI | 10204 | Phase BC Voltage - Compressor 1B | Measurement of voltage in Phase BC for Compressor 1B | Voltage | Read | |
| AI | 10205 | Phase CA Voltage - Compressor 1B | Measurement of voltage in Phase CA for Compressor 1B | Voltage | Read | |
| AI | 10206 | Phase BC Voltage - Compressor 2B | Measurement of voltage in Phase BC for Compressor 2B | Voltage | Read | |
| AI | 10207 | Phase CA Voltage - Compressor 2B | Measurement of voltage in Phase CA for Compressor 2B | Voltage | Read | |
| AI | 10208 | Average Line Current Circuit 1 | Average current, reported in Circuit 1 | Current | Read | |
| AI | 10209 | Average Line Current Circuit 2 | Average current, reported in Circuit 2 | Current | Read | |
| AI | 10210 | Average Line Voltage Circuit 1 | Average voltage, line-to-line reported in Circuit 1 | Voltage | Read | |
| AI | 10211 | Average Line Voltage Circuit 2 | Average voltage, line-to-line reported in Circuit 2 | Voltage | Read | |
| AI | 10212 | Line Current L1 Circuit 1 | Current for line/leg 1 of Circuit 1 | Current | Read | |
| AI | 10213 | Line Current L2 Circuit 1 | Current for line/leg 2 of Circuit 1 | Current | Read | |
| AI | 10214 | Line Current L3 Circuit 1 | Current for line/leg 3 of Circuit 1 | Current | Read | |
| AI | 10215 | Line Current L1 Circuit 2 | Current for line/leg 1 of Circuit 2 | Current | Read | |
| AI | 10216 | Line Current L2 Circuit 2 | Current for line/leg 2 of Circuit 2 | Current | Read | |
| AI | 10217 | Line Current L3 Circuit 2 | Current for line/leg 3 of Circuit 2 | Current | Read | |
| AI | 10218 | Voltage L1-L2 Circuit 1 | Voltage between line/leg L1 and L2 of Circuit 1 | Voltage | Read | |
| AI | 10219 | Voltage L2-L3 Circuit 1 | Voltage between line/leg L2 and L3 of Circuit 1 | Voltage | Read | |
| AI | 10220 | Voltage L1-L3 Circuit 1 | Voltage between line/leg L1 and L3 of Circuit 1 | Voltage | Read | |
| AI | 10221 | Voltage L1-L2 Circuit 2 | Voltage between line/leg L1 and L2 of Circuit 2 | Voltage | Read | |
| AI | 10222 | Voltage L2-L1 Circuit 2 | Voltage between line/leg L2 and L3 of Circuit 2 | Voltage | Read | |
| AI | 10223 | Voltage L1-L3 Circuit 2 | Voltage between line/leg L1 and L3 of Circuit 2 | Voltage | Read | |
| AI | 10224 | Total Real Power | Total real power reported | Power, Electrical | Read | |
| AI | 10225 | Line Frequency Circuit 1 | Estimated input frequency for Circuit 1 | Read | ||
| AI | 10226 | Line Frequency Circuit 2 | Estimated input frequency for Circuit 2 | Read | ||
| AI | 10227 | Power Factor Circuit 1 | Reported power factor for Circuit 1 | Read | ||
| AI | 10228 | Power Factor Circuit 2 | Reported power factor for Circuit 2 | Read | ||
| AI | 10229 | Power Demand Circuit 1 | Reported power demand for Circuit 1 | Power, Electrical | Read | |
| AI | 10230 | Power Demand Circuit 2 | Reported power demand for Circuit 2 | Power, Electrical | Read | |
| AI | 10231 | Evaporator Approach Temperature Circuit 1 | Evaporator approach temperature for circuit 1 | Temperature, Delta | Read | |
| AI | 10232 | Evaporator Approach Temperature Circuit 2 | Evaporator approach temperature for circuit 2 | Temperature, Delta | Read | |
| AI | 10233 | Discharge Superheat Compressor 1A | Discharge superheat for compressor 1A | Temperature, Delta | Read | |
| AI | 10234 | Discharge Superheat Compressor 1B | Discharge superheat for compressor 1B | Temperature, Delta | Read | |
| AI | 10235 | Discharge Superheat Compressor 2A | Discharge superheat for compressor 2A | Temperature, Delta | Read | |
| AI | 10236 | Discharge Superheat Compressor 2B | Discharge superheat for compressor 2B | Temperature, Delta | Read | |
| AI | 10237 | Evaporator Water Flow Rate | Approximate evaporator water flow rate | Flow, Fluidic | Read | |
| AI | 10238 | Evaporator Differential Water Pressure | With Evap Water Flow Measurement Differential Pressure or Dual Pressure Sensors | Pressure, Fluidic | Read | |
| AI | 10239 | Entering Evaporator Water Pressure | Evaporator entering water pressure | Pressure, Fluidic | Read | |
| AI | 10240 | Leaving Evaporator Water Pressure | Evaporator leaving water pressure | Pressure, Fluidic | Read | |
| AI | 10241 | Power Factor | Unit power factor | Read | ||
| AI | 10242 | Current L1 | Current for line/leg 1 | Current | Read | |
| AI | 10243 | Current L2 | Current for line/leg 2 | Current | Read | |
| AI | 10244 | Current L3 | Current for line/leg 3 | Current | Read | |
| AI | 10245 | Average Current | Average current reported | Current | Read | |
| AI | 10246 | Voltage L1-L2 | Voltage between line/leg L1 and L2 | Voltage | Read | |
| AI | 10247 | Voltage L2-L3 | Voltage between line/leg L2 and L3 | Voltage | Read | |
| AI | 10248 | Voltage L1-L3 | Voltage between line/leg L1 and L3 | Voltage | Read | |
| AI | 10249 | Average Voltage L-L | Average voltage, line-to-line | Voltage | Read | |
| AI | 10250 | Line Frequency | Chiller line frequency | Read | ||
| AI | 10251 | AFD Coolant Supply Temperature Compressor 1A | AFD cooling supply temperature for circuit 1 | Temperature | Read | |
| AI | 10253 | AFD Coolant Supply Temperature Compressor 2A | AFD cooling supply temperature for circuit 2 | Temperature | Read | |
| AI | 10254 | Evaporator Water Pump Speed Command | Percentage | Read | ||
| AI | 10255 | Evaporator Water Pump Speed Feedback | Percentage | Read | ||
| AI | 10256 | Evaporator Water Pump Speed Setpoint Active | T the active evaporator water pump speed setpoint | Percentage | Read | |
| AI | 10257 | Evaporator Water Pump Flow Rate Setpoint Active | T the active evaporator water pump flow rate setpoint | Flow, Fluidic | Read | |
| AI | 10258 | Free Cooling Dedicated Fans Airflow | Free cooling dedicated fan air flow | Percentage | Read | |
| AI | 10259 | Drive Heat Sink Temperature Compressor 1A | Heatsink temperature for the circuit 1A AFD | Temperature | Read | |
| AI | 10260 | Drive Heat Sink Temperature Compressor 2A | Heatsink temperature for the circuit 2A AFD | Temperature | Read | |
| AI | 10261 | Compressor 1A Speed Status | Percent speed status for compressor 1A | Percentage | Read | |
| AI | 10262 | Compressor 2A Speed Status | Percent speed status for compressor 2A | Percentage | Read | |
| AI | 10263 | Calculated Chiller Capacity | Power, Cooling | Read | ||
| AI | 10264 | Free Cooling Target Offset | Temperature, Delta | Read | ||
| AI | 10265 | Free Cooling Valve Position Status | Free cooling valve percent open position | Percentage | Read | |
| AI | 10266 | Active Demand Limit Setpoint | With Ice Building | Percentage | Read | |
| AI | 10267 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Current absolute pressure of the refrigerant in the evaporator on circuit 1 | Pressure, Fluidic | Read | |
| AI | 10268 | Condenser Refrigerant Absolute Pressure Circuit 1 | Current absolute pressure of the refrigerant in the condenser on circuit 1 | Pressure, Fluidic | Read | |
| AI | 10269 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Current absolute pressure of the refrigerant in the evaporator on circuit 2 | Pressure, Fluidic | Read | |
| AI | 10270 | Condenser Refrigerant Absolute Pressure Circuit 2 | Current absolute pressure of the refrigerant in the condenser on circuit 2 | Pressure, Fluidic | Read | |
| AI | 10271 | High Side Oil Absolute Pressure - Compressor 1A | Pressure, Fluidic | Read | ||
| AI | 10272 | High Side Oil Absolute Pressure - Compressor 2A | Pressure, Fluidic | Read | ||
| AI | 10273 | High Side Oil Absolute Pressure - Compressor 1B | Pressure, Fluidic | Read | ||
| AI | 10274 | High Side Oil Absolute Pressure - Compressor 2B | Pressure, Fluidic | Read | ||
| AI | 10275 | Entering Evaporator Water Absolute Pressure | Absolute pressure of the entering evaporator water | Pressure, Fluidic | Read | |
| AI | 10276 | Leaving Evaporator Water Absolute Pressure | Absolute pressure of the leaving evaporator water | Pressure, Fluidic | Read | |
| AVmin | 10100 | Chilled Water Setpoint | Written by the BAS; goes through arbitration before use | Temperature | Write | |
| AVmin | 10101 | Demand Limit Setpoint | Written by the BAS; goes through arbitration before use | Percentage | Write | |
| AV | 10102 | Evaporator Water Pump Flow Rate Setpt BAS | BAS Evap Water Flow Rate Setpt | Flow, Fluidic | Write | |
| AV | 10103 | Evaporator Water Pump Speed Setpt BAS | BAS Evap Water Pump Speed Setpt | Percentage | Write | |
| BI | 10100 | Run Enable | That chiller is available to run or is currently running | Read | 0 = Run Not Enabled, 1 = Run Enabled | |
| BImin | 10101 | Local Setpoint Control | Which setpoint is used for control purposes, Remote (BAS) or Local | Read | 0 = Remote Control, 1 = Local Control | |
| BI | 10102 | Limit Mode Relay Status | Status of the chiller limit relay | Read | 0 = Off, 1 = On | |
| BImin | 10103 | Chiller Running State | The chiller is on | Read | 0 = Off, 1 = On | |
| BI | 10104 | Maximum Capacity | Status of the maximum capacity relay | Read | 0 = Off, 1 = On | |
| BI | 10106 | Manual Override Exists | D a manual override is present | Read | 0 = Off, 1 = On | |
| BI | 10107 | Compressor 1A Status | Running state of Compressor 1A | Read | 0 = Off, 1 = Running | |
| BI | 10108 | Compressor 2A Status | Running state of Compressor 2A | Read | 0 = Off, 1 = Running | |
| BI | 10109 | Emergency Stop | Status of the emergency stop function of the chiller | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | |
| BI | 10110 | Evaporator Water Pump Request | Request from the chiller to turn on the Evaporator Water Pump | Read | 0 = Off, 1 = On | |
| BI | 10111 | Evaporator Water Flow Status | Flow of water through evaporator | Read | 0 = No Flow, 1 = Flow | |
| BI | 10112 | Compressor 1B Status | Running state of Compressor 1B | Read | 0 = Off, 1 = Running | |
| BI | 10113 | Compressor 2B Status | Running state of Compressor 2B | Read | 0 = Off, 1 = Running | |
| BI | 10114 | Free Cooling Active | D the free cooling mode is active | Read | 0 = Inactive, 1 = Active | |
| BImin | 10116 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10117 | Diagnostic Shutdown Present | Chiller is shut down due to diagnostics | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10118 | Diagnostic: Manual Reset Required | When a diagnostic exists that requires manual reset | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10119 | Diagnostic: Local Manual Reset Required | When a diagnostic exists that requires manual reset [Local only] | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10120 | Diagnostic Present: Information | Diagnostic present with Information Category | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10121 | Diagnostic Present: Advisory | Diagnostic present with Warning Category | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10122 | Diagnostic Present: Critical | Diagnostic present with Critical Category | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10123 | Diagnostic Present: Service Required | Diagnostic present with Service Required Category | Read | 0 = Normal, 1 = In Alarm | |
| BI | 10124 | External Auto Stop Input Status | Status of the externally-wired auto/stop input | Read | 0 = Stop, 1 = Auto | |
| BI | 10125 | Front Panel Auto Stop | Auto/stop status of the Front Panel | Read | 0 = Stop, 1 = Auto | |
| BI | 10126 | Noise Reduction Request Active | Wherther Noise Reduction active | Read | 0 = Off, 1 = On | |
| BI | 10127 | Circuit 1 Lockout Front Panel | Lockout state of Circuit 1 Comprosser from Front Panel | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10128 | Circuit 2 Lockout Front Panel | Lockout state of Circuit 2 Comprosser from Front Panel | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10129 | Circuit 1 Lockout External | Lockout state of Circuit 1 Comprosser from External | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10130 | Circuit 2 Lockout External | Lockout state of Circuit 2 Comprosser from External | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10131 | Circuit 1 Lockout Active | Lockout state of Circuit 1 | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10132 | Circuit 2 Lockout Active | Lockout state of Circuit 2 | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10133 | Circuit 1 Available | Circuit 1 is available to start | Read | 0 = Unavailable, 1 = Available | |
| BI | 10134 | Circuit 2 Available | Circuit 2 is available to start | Read | 0 = Unavailable, 1 = Available | |
| BI | 10135 | Oil Sensor Circuit 1 | Status of the circuit 1 oil sensor | Read | 0 = Dry, 1 = Wet | |
| BI | 10136 | Oil Sensor Circuit 2 | Status of the circuit 2 oil sensor | Read | 0 = Dry, 1 = Wet | |
| BI | 10137 | Evaporator Water Pump 1 Inverter Running Status | Running status of the evaporator water pump 1 inverter | Read | 0 = Off, 1 = On | |
| BI | 10138 | Evaporator Water Pump 1 Fault Status | Fault status of the evaporator water pump 1 inverter | Read | 0 = Fault, 1 = No Fault | |
| BI | 10139 | Compressor 1B Lockout Active | Lockout state of Compressor 1B | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10140 | Compressor 2B Lockout Active | Lockout state of Compressor 2B | Read | 0 = Normal, 1 = Locked Out | |
| BI | 10141 | Free Cooling Front Panel Command Status | Status of the front panel free cooling command | Read | 0 = Off, 1 = Auto | |
| BI | 11000 | Diagnostic: AFD 1A Bus Over Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Diagnostic: AFD 1A Bus Under Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Diagnostic: AFD 1A Comm Loss: Main Processor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Diagnostic: AFD 1A Customized Protection Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Diagnostic: AFD 1A Gate Kill Active | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Diagnostic: AFD 1A General Failure (PF755) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Diagnostic: AFD 1A General Failure (TR200) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Diagnostic: AFD 1A Ground Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Diagnostic: AFD 1A Input Phase Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Diagnostic: AFD 1A Input Transf or Filter Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Diagnostic: AFD 1A Loss Of Motor Control | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Diagnostic: AFD 1A Low Rotor Flux Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Diagnostic: AFD 1A Motor Current Overload | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Diagnostic: AFD 1A Motor Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Diagnostic: AFD 1A Motor Shorted | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Diagnostic: AFD 1A Over Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Diagnostic: AFD 1A Precharge Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Diagnostic: AFD 2A Bus Over Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Diagnostic: AFD 2A Bus Under Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Diagnostic: AFD 2A Comm Loss: Main Processor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Diagnostic: AFD 2A Customized Protection Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Diagnostic: AFD 2A Gate Kill Active | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Diagnostic: AFD 2A General Failure (PF755) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Diagnostic: AFD 2A General Failure (TR200) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Diagnostic: AFD 2A Ground Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Diagnostic: AFD 2A Input Phase Loss | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Diagnostic: AFD 2A Input Transf or Filter Over Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Diagnostic: AFD 2A Loss Of Motor Control | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Diagnostic: AFD 2A Low Rotor Flux Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Diagnostic: AFD 2A Motor Current Overload | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Diagnostic: AFD 2A Motor Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Diagnostic: AFD 2A Motor Shorted | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Diagnostic: AFD 2A Over Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Diagnostic: AFD 2A Precharge Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Diagnostic: AFD Bus Over Voltage - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Diagnostic: AFD Bus Over Voltage - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11036 | Diagnostic: AFD Bus Under Voltage - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11037 | Diagnostic: AFD Bus Under Voltage - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Diagnostic: AFD Comm Loss – 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Diagnostic: AFD Comm Loss – 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Diagnostic: AFD Comm Loss: Main Processor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Diagnostic: AFD Comm Loss: Main Processor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Diagnostic: AFD Failure to Arm or Start - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Diagnostic: AFD Failure to Arm or Start - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Diagnostic: AFD Fault Mains - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Diagnostic: AFD Fault Mains - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Diagnostic: AFD General Fault - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Diagnostic: AFD General Fault - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Diagnostic: AFD Ground Fault - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Diagnostic: AFD Ground Fault - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Diagnostic: AFD Harmonic Filter Over Temperature - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Diagnostic: AFD Harmonic Filter Over Temperature - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Diagnostic: AFD High Pressure Cutout - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Diagnostic: AFD High Pressure Cutout - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Diagnostic: AFD High Torque - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Diagnostic: AFD High Torque - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Diagnostic: AFD Initialized - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Diagnostic: AFD Initialized - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Diagnostic: AFD Internal Fault - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Diagnostic: AFD Internal Fault - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Diagnostic: AFD Interrupt Failure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Diagnostic: AFD Interrupt Failure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Diagnostic: AFD Interrupt Failure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Diagnostic: AFD Interrupt Failure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Diagnostic: AFD Inverter Heatsink Over Temperature - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Diagnostic: AFD Inverter Heatsink Over Temperature - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Diagnostic: AFD Locked Rotor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Diagnostic: AFD Locked Rotor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Diagnostic: AFD Mains Phase Loss - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Diagnostic: AFD Mains Phase Loss - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Diagnostic: AFD Missing Motor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Diagnostic: AFD Missing Motor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Diagnostic: AFD Motor Current Overload - 1A (TR200) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Diagnostic: AFD Motor Current Overload - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Diagnostic: AFD Motor Current Overload - 2A (TR200) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Diagnostic: AFD Motor Current Overload - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Diagnostic: AFD Motor Fault - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Diagnostic: AFD Motor Fault - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Diagnostic: AFD New Spare Parts - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Diagnostic: AFD New Spare Parts - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Diagnostic: AFD Option Configuration Change - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Diagnostic: AFD Option Configuration Change - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Diagnostic: AFD Output Phase U Loss - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Diagnostic: AFD Output Phase U Loss - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Diagnostic: AFD Output Phase V Loss - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Diagnostic: AFD Output Phase V Loss - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Diagnostic: AFD Output Phase W Loss - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Diagnostic: AFD Output Phase W Loss - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Diagnostic: AFD Over Temperature - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Diagnostic: AFD Over Temperature - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Diagnostic: AFD Short Circuit - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Diagnostic: AFD Short Circuit - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Diagnostic: AFD Unexpected Shutdown - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Diagnostic: AFD Unexpected Shutdown - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11096 | Diagnostic: Check Clock | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Diagnostic: Chiller Service Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Comm Loss: %RLA Indication Output(Vdc) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Comm Loss: AFD Fault Input 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Comm Loss: AFD Fault Input 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Comm Loss: AFD Fault Input 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Comm Loss: AFD Fault Input 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss: Auxiliary Setpoint Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Comm Loss: Cond Fan Enbl Shared Ckt 1&2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Comm Loss: Cond Rfgt Tank Valve Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Comm Loss: Cond Rfgt Tank Valve Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Comm Loss: Condenser Fan Enable Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Comm Loss: Condenser Fan Enable Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11109 | Comm Loss: Condenser Rfgt Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11110 | Comm Loss: Condenser Rfgt Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11111 | Comm Loss: Cprsr Disch Rfgt Temp - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Comm Loss: Cprsr Disch Rfgt Temp - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: Cprsr Disch Rfgt Temp - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: Cprsr Disch Rfgt Temp - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Comm Loss: Drive Cooling Bypass Valve 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Comm Loss: Drive Cooling Bypass Valve 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Comm Loss: Drive Cooling Supply Temp 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Comm Loss: Drive Cooling Supply Temp 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Comm Loss: Economizer Disch Press - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: Economizer Disch Press - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Comm Loss: Economizer Disch Press - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Economizer Disch Press - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Comm Loss: Economizer Disch Temp - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Comm Loss: Economizer Disch Temp - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Comm Loss: Economizer Disch Temp - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Comm Loss: Economizer Disch Temp - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Comm Loss: Economizer Valve - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Comm Loss: Economizer Valve - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Comm Loss: Economizer Valve - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Comm Loss: Economizer Valve - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Electronic Expansion Valve 1 Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Electronic Expansion Valve 1 Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Comm Loss: Electronic Expansion Valve 2 Compressor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Comm Loss: Electronic Expansion Valve 2 Compressor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Comm Loss: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Energy Meter 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Energy Meter 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Comm Loss: Evap Diff Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: Evap Iso Valve Close Switch Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Comm Loss: Evap Iso Valve Close Switch Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Comm Loss: Evap Iso Valve Open Switch Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Evap Iso Valve Open Switch Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Evap Isolation Valve Relay Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Comm Loss: Evap Isolation Valve Relay Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Comm Loss: Evap Pump Inv1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Comm Loss: Evap Pump Inv1 Run Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Comm Loss: Evap Rfgt Pool Temp Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Comm Loss: Evap Rfgt Pool Temp Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Comm Loss: Evap Water Pump Inv Freq Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Comm Loss: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Comm Loss: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Comm Loss: Evaporator Oil Return Purge Valve - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Comm Loss: Evaporator Oil Return Purge Valve - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Comm Loss: Evaporator Pump 1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Comm Loss: Evaporator Pump 2 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Comm Loss: Evaporator Pump Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Comm Loss: Evaporator Pump Inverter Running Status | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Comm Loss: Evaporator Pump Speed Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Comm Loss: Evaporator Pump Speed Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Comm Loss: Evaporator Water Pump 1 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Comm Loss: Evaporator Water Pump 2 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Comm Loss: Evaporator Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Comm Loss: Ext Chilled Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Comm Loss: Ext Noise Reduction Request | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Comm Loss: External Ckt Lockout Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Comm Loss: External Ckt Lockout Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Comm Loss: External Heat Recovery Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Comm Loss: External Heat Recovery Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Comm Loss: Fan Board 1 Relay 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Comm Loss: Fan Board 1 Relay 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Comm Loss: Fan Board 1 Relay 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Comm Loss: Fan Board 1 Relay 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Comm Loss: Fan Board 1 Relay 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Comm Loss: Fan Board 1 Relay 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Comm Loss: Fan Board 1 Relay 4 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Comm Loss: Fan Board 1 Relay 4 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Comm Loss: Fan Board 2 Relay 1 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Comm Loss: Fan Board 2 Relay 1 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Comm Loss: Fan Board 2 Relay 2 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Comm Loss: Fan Board 2 Relay 2 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Comm Loss: Fan Board 2 Relay 3 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Comm Loss: Fan Board 2 Relay 3 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Comm Loss: Fan Board 2 Relay 4 Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Comm Loss: Fan Board 2 Relay 4 Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1 & 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Comm Loss: Fan Inverter Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Comm Loss: Fan Inverter Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Comm Loss: Fan Inverter Speed Command Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Comm Loss: Fan Inverter Speed Command Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Comm Loss: FC Entering Glycol Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Comm Loss: FC Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Comm Loss: FC Leaving Glycol Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Comm Loss: Free Cooling Bypass Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Comm Loss: Free Cooling Dedicated Fan Enable | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Comm Loss: Free Cooling Dedicated Fan Inverter Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Comm Loss: Free Cooling Dedicated Fan Inverter Speed Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Comm Loss: Free Cooling Glycol Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Comm Loss: Free Cooling Glycol Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11205 | Comm Loss: Free Cooling Glycol Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Comm Loss: Free Cooling Pump | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Comm Loss: Free Cooling Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Comm Loss: Heat Recovery Mode Valve Command - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Comm Loss: Heat Recovery Mode Valve Command - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Comm Loss: Heat Recovery Water Flow Cmd | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Comm Loss: Heat Recovery Water Pump Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Comm Loss: Heat Recovery Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Comm Loss: High Pressure Cutout Sw - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Comm Loss: High Pressure Cutout Sw - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Comm Loss: High Pressure Cutout Sw - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Comm Loss: High Pressure Cutout Sw - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Comm Loss: Hot Gas Oil Return Valve - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Comm Loss: Hot Gas Oil Return Valve - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11219 | Comm Loss: HR Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11220 | Comm Loss: HR Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Comm Loss: Liquid Line Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Comm Loss: Liquid Line Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Comm Loss: Liquid Line Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Comm Loss: Liquid Line Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Comm Loss: Motor Winding Tstat Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11226 | Comm Loss: Motor Winding Tstat Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11227 | Comm Loss: Off-cycle Freeze Prot Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11228 | Comm Loss: Oil Loss Level Sensor Input Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11229 | Comm Loss: Oil Loss Level Sensor Input Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Comm Loss: Oil Pressure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Comm Loss: Oil Pressure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Comm Loss: Oil Pressure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Comm Loss: Oil Pressure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Comm Loss: Oil Return Solenoid Valve - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Comm Loss: Oil Return Solenoid Valve - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Comm Loss: Oil Return Valve - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Comm Loss: Oil Return Valve - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Comm Loss: Oil Supply Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Comm Loss: Oil Supply Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Comm Loss: Oil Temperature - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Comm Loss: Oil Temperature - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Comm Loss: Oil Temperature - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Comm Loss: Oil Temperature - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11244 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11245 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11246 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11247 | Comm Loss: Slide Valve Load - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11248 | Comm Loss: Slide Valve Load - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11249 | Comm Loss: Slide Valve Load - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11250 | Comm Loss: Slide Valve Load - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11251 | Comm Loss: Slide Valve Unload - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11252 | Comm Loss: Slide Valve Unload - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11253 | Comm Loss: Slide Valve Unload - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11254 | Comm Loss: Slide Valve Unload - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11255 | Comm Loss: Starter 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11256 | Comm Loss: Starter 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11257 | Comm Loss: Starter 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11258 | Comm Loss: Starter 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11259 | Comm Loss: Step Load - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11260 | Comm Loss: Step Load - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11261 | Comm Loss: Step Load - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11262 | Comm Loss: Step Load - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11263 | Comm Loss: Suction Rfgt Pressure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11264 | Comm Loss: Suction Rfgt Pressure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11265 | Comm Loss: Suction Rfgt Pressure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11266 | Comm Loss: Suction Rfgt Pressure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11267 | Comm Loss: Var Vi Valve – Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11268 | Comm Loss: Var Vi Valve – Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11269 | Comm Loss: Winding Temp 1, Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11270 | Comm Loss: Winding Temp 1, Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11271 | Comm Loss: Winding Temp 2, Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11272 | Comm Loss: Winding Temp 2, Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11273 | Diagnostic: Condenser Rfgt Pressure Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11274 | Diagnostic: Condenser Rfgt Pressure Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11275 | Diagnostic: Cprsr Did Not Accel: Shutdown - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11276 | Diagnostic: Cprsr Did Not Accel: Shutdown - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11277 | Diagnostic: Cprsr Did Not Accel: Shutdown - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11278 | Diagnostic: Cprsr Did Not Accel: Shutdown - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11279 | Diagnostic: Cprsr Did Not Accel: Transition - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11280 | Diagnostic: Cprsr Did Not Accel: Transition - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11281 | Diagnostic: Cprsr Did Not Accel: Transition - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11282 | Diagnostic: Cprsr Did Not Accel: Transition - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11283 | Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11284 | Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11285 | Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11286 | Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11287 | Diagnostic: Drive Cooling Supply Temp Sensor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11288 | Diagnostic: Drive Cooling Supply Temp Sensor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11289 | Diagnostic: Economizer Disch Press Sensor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11290 | Diagnostic: Economizer Disch Press Sensor - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11291 | Diagnostic: Economizer Disch Press Sensor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11292 | Diagnostic: Economizer Disch Press Sensor - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11293 | Diagnostic: Economizer Disch Temp Sensor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11294 | Diagnostic: Economizer Disch Temp Sensor - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11295 | Diagnostic: Economizer Disch Temp Sensor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11296 | Diagnostic: Economizer Disch Temp Sensor - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11297 | Diagnostic: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11298 | Diagnostic: Evap Iso Valve Illegal Switch State Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11299 | Diagnostic: Evap Iso Valve Illegal Switch State Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11300 | Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11301 | Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11302 | Diagnostic: Evap Isolation Valve Failed To Close Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11303 | Diagnostic: Evap Isolation Valve Failed To Close Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11304 | Diagnostic: Evap Isolation Valve Failed To Open Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11305 | Diagnostic: Evap Isolation Valve Failed To Open Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11306 | Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11307 | Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11308 | Diagnostic: Evap Pump 1 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11309 | Diagnostic: Evap Pump 2 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11310 | Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11311 | Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11312 | Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11313 | Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11314 | Diagnostic: Evap Water Pump 1 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11315 | Diagnostic: Evap Water Pump 2 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11316 | Diagnostic: Evaporator Approach Error Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11317 | Diagnostic: Evaporator Approach Error Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11318 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11319 | Diagnostic: Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11320 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11321 | Diagnostic: Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11322 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11323 | Diagnostic: Evaporator Pump 1 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11324 | Diagnostic: Evaporator Pump 2 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11325 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11326 | Diagnostic: Evaporator Water Flow Lost - Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11327 | Diagnostic: Evaporator Water Flow Lost - Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11328 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11329 | Diagnostic: Evaporator Water Flow Overdue - Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11330 | Diagnostic: Evaporator Water Flow Overdue - Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11331 | Diagnostic: Evaporator Water Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11332 | Diagnostic: Evaporator Water Pump Speed Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11333 | Diagnostic: Excessive Condenser Pressure Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11334 | Diagnostic: Excessive Condenser Pressure Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11335 | Diagnostic: External Chilled Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11336 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11337 | Diagnostic: External Heat Recovery Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11338 | Diagnostic: Fan Inverter Fault Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11339 | Diagnostic: Fan Inverter Fault Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11340 | Diagnostic: Free Cooling Dedicated Fan Inverter Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11341 | Diagnostic: Free Cooling Entering Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11342 | Diagnostic: Free Cooling Entering Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11343 | Diagnostic: Free Cooling Glycol Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11344 | Diagnostic: Free Cooling Glycol Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11345 | Diagnostic: Free Cooling Glycol Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11346 | Diagnostic: Free Cooling Glycol Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11347 | Diagnostic: Free Cooling Glycol Temperature Equalization Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11348 | Diagnostic: Free Cooling Leaving Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11349 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11350 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11351 | Diagnostic: Heat Recovery Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11352 | Diagnostic: Heat Recovery Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11353 | Diagnostic: High Cprsr Rfgt Discharge Temp - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11354 | Diagnostic: High Cprsr Rfgt Discharge Temp - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11355 | Diagnostic: High Cprsr Rfgt Discharge Temp - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11356 | Diagnostic: High Cprsr Rfgt Discharge Temp - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11357 | Diagnostic: High Differential Rfgt Pressure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11358 | Diagnostic: High Differential Rfgt Pressure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11359 | Diagnostic: High Differential Rfgt Pressure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11360 | Diagnostic: High Differential Rfgt Pressure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11361 | Diagnostic: High Evaporator Refrigerant Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11362 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11363 | Diagnostic: High Motor Winding Temperature - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11364 | Diagnostic: High Motor Winding Temperature - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11365 | Diagnostic: High Oil Temperature - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11366 | Diagnostic: High Oil Temperature - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11367 | Diagnostic: High Oil Temperature - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11368 | Diagnostic: High Oil Temperature - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11369 | Diagnostic: High Pressure Cutout - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11370 | Diagnostic: High Pressure Cutout - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11371 | Diagnostic: High Pressure Cutout - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11372 | Diagnostic: High Pressure Cutout - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11373 | Diagnostic: High Refrigerant Pressure Ratio - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11374 | Diagnostic: High Refrigerant Pressure Ratio - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11375 | Diagnostic: High Refrigerant Pressure Ratio - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11376 | Diagnostic: High Refrigerant Pressure Ratio - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11377 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11378 | Diagnostic: Liquid Line Pressure Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11379 | Diagnostic: Liquid Line Pressure Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11380 | Diagnostic: Liquid Line Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11381 | Diagnostic: Liquid Line Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11382 | Diagnostic: Loss of Oil for Compressor (Running) Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11383 | Diagnostic: Loss of Oil for Compressor (Running) Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11384 | Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11385 | Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11386 | Diagnostic: Low Differential Rfgt Pressure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11387 | Diagnostic: Low Differential Rfgt Pressure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11388 | Diagnostic: Low Differential Rfgt Pressure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11389 | Diagnostic: Low Differential Rfgt Pressure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11390 | Diagnostic: Low Discharge Superheat - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11391 | Diagnostic: Low Discharge Superheat - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11392 | Diagnostic: Low Discharge Superheat - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11393 | Diagnostic: Low Discharge Superheat - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11394 | Diagnostic: Low Drive Cooling Supply Temperature - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11395 | Diagnostic: Low Drive Cooling Supply Temperature - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11396 | Diagnostic: Low Evaporator Entering Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11397 | Diagnostic: Low Evaporator Leaving Water Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11398 | Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11399 | Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit Off | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11400 | Diagnostic: Low Evaporator Water Flow | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11401 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11402 | Diagnostic: Low Evaporator Water Temp (Unit On) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11403 | Diagnostic: Low Glycol Pressure Free Cooling | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11404 | Diagnostic: Low Glycol Temp Free Cooling | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11405 | Diagnostic: Low Oil Flow - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11406 | Diagnostic: Low Oil Flow - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11407 | Diagnostic: Low Oil Flow - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11408 | Diagnostic: Low Oil Flow - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11409 | Diagnostic: Low Refrigerant Temperature Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11410 | Diagnostic: Low Refrigerant Temperature Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11411 | Diagnostic: Low Suction Refrigerant Pressure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11412 | Diagnostic: Low Suction Refrigerant Pressure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11413 | Diagnostic: Low Suction Refrigerant Pressure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11414 | Diagnostic: Low Suction Refrigerant Pressure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11415 | Diagnostic: Mfr Maintenance Recommended - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11416 | Diagnostic: Mfr Maintenance Recommended - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11417 | Diagnostic: Mfr Maintenance Recommended - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11418 | Diagnostic: Mfr Maintenance Recommended - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11419 | Diagnostic: Momentary Power Loss Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11420 | Diagnostic: Momentary Power Loss Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11421 | Diagnostic: Motor Current Overload - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11422 | Diagnostic: Motor Current Overload - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11423 | Diagnostic: Motor Current Overload - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11424 | Diagnostic: Motor Current Overload - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11425 | Diagnostic: Motor Winding Temp Sensor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11426 | Diagnostic: Motor Winding Temp Sensor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11427 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11428 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11429 | Diagnostic: No Differential Rfgt Pressure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11430 | Diagnostic: No Differential Rfgt Pressure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11431 | Diagnostic: No Differential Rfgt Pressure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11432 | Diagnostic: No Differential Rfgt Pressure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11433 | Diagnostic: Oil Filter Change Recommended - Cprsr1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11434 | Diagnostic: Oil Filter Change Recommended - Cprsr2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11435 | Diagnostic: Oil Flow Protection Fault - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11436 | Diagnostic: Oil Flow Protection Fault - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11437 | Diagnostic: Oil Flow Protection Fault - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11438 | Diagnostic: Oil Flow Protection Fault - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11439 | Diagnostic: Oil Pressure Sensor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11440 | Diagnostic: Oil Pressure Sensor - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11441 | Diagnostic: Oil Pressure Sensor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11442 | Diagnostic: Oil Pressure Sensor - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11443 | Diagnostic: Oil Supply Temp Sensor Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11444 | Diagnostic: Oil Supply Temp Sensor Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11445 | Diagnostic: Oil Temperature Sensor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11446 | Diagnostic: Oil Temperature Sensor - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11447 | Diagnostic: Oil Temperature Sensor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11448 | Diagnostic: Oil Temperature Sensor - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11449 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11450 | Diagnostic: Over Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11451 | Diagnostic: Phase Loss - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11452 | Diagnostic: Phase Loss - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11453 | Diagnostic: Phase Loss - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11454 | Diagnostic: Phase Loss - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11455 | Diagnostic: Phase Reversal - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11456 | Diagnostic: Phase Reversal - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11457 | Diagnostic: Phase Reversal - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11458 | Diagnostic: Phase Reversal - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11459 | Diagnostic: Power Loss - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11460 | Diagnostic: Power Loss - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11461 | Diagnostic: Power Loss - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11462 | Diagnostic: Power Loss - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11463 | Diagnostic: Pumpdown Terminated By Time Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11464 | Diagnostic: Pumpdown Terminated By Time Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11465 | Diagnostic: Restart Inhibit Invoked - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11466 | Diagnostic: Restart Inhibit Invoked - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11467 | Diagnostic: Restart Inhibit Invoked - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11468 | Diagnostic: Restart Inhibit Invoked - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11469 | Diagnostic: Severe Current Imbalance - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11470 | Diagnostic: Severe Current Imbalance - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11471 | Diagnostic: Severe Current Imbalance - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11472 | Diagnostic: Severe Current Imbalance - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11473 | Diagnostic: Software Error 1001: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11474 | Diagnostic: Software Error 1002: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11475 | Diagnostic: Software Error 1003: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11476 | Diagnostic: Starter Comm Loss: Main Processor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11477 | Diagnostic: Starter Comm Loss: Main Processor - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11478 | Diagnostic: Starter Comm Loss: Main Processor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11479 | Diagnostic: Starter Comm Loss: Main Processor - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11480 | Diagnostic: Starter Contactor Interrupt Failure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11481 | Diagnostic: Starter Contactor Interrupt Failure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11482 | Diagnostic: Starter Contactor Interrupt Failure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11483 | Diagnostic: Starter Contactor Interrupt Failure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11484 | Diagnostic: Starter Did Not Fully Accelerate | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11485 | Diagnostic: Starter Did Not Transition - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11486 | Diagnostic: Starter Did Not Transition - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11487 | Diagnostic: Starter Did Not Transition - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11488 | Diagnostic: Starter Did Not Fully Accelerate Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11489 | Diagnostic: Starter Did Not Transition - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11490 | Diagnostic: Starter Dry Run Test - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11491 | Diagnostic: Starter Dry Run Test - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11492 | Diagnostic: Starter Dry Run Test - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11493 | Diagnostic: Starter Dry Run Test - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11494 | Diagnostic: Starter Failed to Arm/Start - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11495 | Diagnostic: Starter Failed to Arm/Start - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11496 | Diagnostic: Starter Failed to Arm/Start - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11497 | Diagnostic: Starter Failed to Arm/Start - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11498 | Diagnostic: Starter Fault Type I - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11499 | Diagnostic: Starter Fault Type I - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11500 | Diagnostic: Starter Fault Type I - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11501 | Diagnostic: Starter Fault Type I - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11502 | Diagnostic: Starter Fault Type II - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11503 | Diagnostic: Starter Fault Type II - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11504 | Diagnostic: Starter Fault Type II - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11505 | Diagnostic: Starter Fault Type II - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11506 | Diagnostic: Starter Fault Type III - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11507 | Diagnostic: Starter Fault Type III - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11508 | Diagnostic: Starter Fault Type III - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11509 | Diagnostic: Starter Fault Type III - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11510 | Diagnostic: Starter Module Memory Error Type 1 - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11511 | Diagnostic: Starter Module Memory Error Type 1 - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11512 | Diagnostic: Starter Module Memory Error Type 1 - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11513 | Diagnostic: Starter Module Memory Error Type 1 - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11514 | Diagnostic: Starter Module Memory Error Type 2 - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11515 | Diagnostic: Starter Module Memory Error Type 2 - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11516 | Diagnostic: Starter Module Memory Error Type 2 - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11517 | Diagnostic: Starter Module Memory Error Type 2 - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11518 | Diagnostic: Starts/Hours Modified 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11519 | Diagnostic: Starts/Hours Modified 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11520 | Diagnostic: Starts/Hours Modified 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11521 | Diagnostic: Starts/Hours Modified 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11522 | Diagnostic: Suction Refrigerant Pressure Sensor - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11523 | Diagnostic: Suction Refrigerant Pressure Sensor - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11524 | Diagnostic: Suction Refrigerant Pressure Sensor - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11525 | Diagnostic: Suction Refrigerant Pressure Sensor - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11526 | Diagnostic: Transition Complete Input Opened - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11527 | Diagnostic: Transition Complete Input Opened - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11528 | Diagnostic: Transition Complete Input Opened - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11529 | Diagnostic: Transition Complete Input Opened - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11530 | Diagnostic: Transition Complete Input Shorted - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11531 | Diagnostic: Transition Complete Input Shorted - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11532 | Diagnostic: Transition Complete Input Shorted - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11533 | Diagnostic: Transition Complete Input Shorted - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11534 | Diagnostic: Under Voltage | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11535 | Diagnostic: Unexpected Starter Shutdown - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11536 | Diagnostic: Unexpected Starter Shutdown - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11537 | Diagnostic: Unexpected Starter Shutdown - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11538 | Diagnostic: Unexpected Starter Shutdown - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11539 | Diagnostic: Very Low Evap Rfgt Pressure - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11540 | Diagnostic: Very Low Evap Rfgt Pressure - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11541 | Diagnostic: Very Low Evap Rfgt Pressure - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11542 | Diagnostic: Very Low Evap Rfgt Pressure - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11543 | Diagnostic: Write Command Failure Energy Meter 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11544 | Diagnostic: Write Command Failure Energy Meter 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11545 | Comm Loss: Ice Building Status Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BV | 10100 | Reset Diagnostic | BAS Diagnostic Reset | Write | 0 = Normal, 1 = Reset | |
| BV | 10101 | Noise Reduction Request BAS | BAS Noise Reduction Command | Write | 0 = Normal, 1 = Reduce Noise | |
| BV | 10102 | Circuit 1 Lockout BAS | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10103 | Circuit 2 Lockout BAS | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10107 | Energy Consumption Reset | Write | 0 = Accumulating, 1 = Reset | ||
| BVmin | 10108 | Chiller Auto Stop Command BAS | Write | 0 = Stop, 1 = Auto | ||
| BV | 10109 | Free Cooling Auto Stop Command BAS | Write | 0 = Stop, 1 = Auto | ||
| BV | 10110 | Free Cooling Compressor Lockout | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10111 | Compressor 1B Lockout BAS | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10112 | Compressor 2B Lockout BAS | Write | 0 = Normal, 1 = Locked Out | ||
| MI | 10100 | Running Mode | Running state of the chiller | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | |
| MI | 10101 | Operating Mode | Operating mode of the chiller | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | |
| MI | 10102 | Refrigerant Type | Chiller refrigerant type | Read | 1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234ze(E) | |
| MI | 10103 | Cooling Type | Cooling Type of chiller | Read | 1 = Water Cooled, 2 = Air Cooled | |
| MI | 10104 | Manufacture Location | Location that the chiller was manufactured | Read | 1 = Field Applied, 2 = La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey | |
| MI | 10105 | Model Information [GEN2] | Model information of chiller | Read | 1 = CVHF, 2 = CVGF, 3 = CVHS, 4 = RTAE, 5 = RTAF, 6 = RTHA, 7 = RTHB, 8 = RTHC, 9 = RTHD, 10 = RTWE, 11 = CTVD, 12 = CVR, 13 = CVHH, 14 = CDHH, 15 = VMAX, 16 = GVAF, 17 = RTWF, 18 = RTHF, 19 = RTAC, 20 = CVHM, 21 = RTAG, 22 = CGAF, 23 = RTXG, 24 = GVWF, 25 = HDWA, 26 = CMAC, 27 = IPAK, 28 = CXAF, 29 = ACSA, 30 = RTSF, 31 = HSWA, 32 = ACRA, 33 = RTEG, 34 = ACXA, 35 = CMAF, 36 = ACRB Large, 37 = ACRB Small, 38 = CVHE, 39 = CVHG, 40 = CVHL, 41 = RTWF XSE, 42 = CGWF, 43 = CDHG, 44 = ACCA, 45 = RTWD, 46 = RTUD, 47 = CXWF, 48 = CCUF, 49 = RTHG, 50 = CGAM, 51 = CXAM, 52 = CGAX, 53 = CXAX, 54 = EIC, 55 = EIH, 56 = RTXG, 57 = RTMG, 58 = ACRC, 59 = HSWB | |
| MI | 10106 | Chiller Setpoint Source | Selected setpoint source for control purpose | Read | 1 = BAS, 2 = External, 3 = Front Panel | |
| MVmin | 10100 | Chiller Mode Command BAS | Command the chiller Mode | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Object ID lookup: Trane Symbio 800 Ascend ACR Series C point IDs by name
AI10100Active Chilled Water SetpointAI10101Active Demand Limit SetpointAI10103Evaporator Entering Water TemperatureAI10104Evaporator Leaving Water TemperatureAI10106Unit Power ConsumptionAI10107Outdoor Air TemperatureAI10110Evaporator Refrigerant Pressure Circuit 1AI10111Condenser Refrigerant Pressure Circuit 1AI10112Differential Refrigerant Pressure Circuit 1AI10113Evaporator Saturated Refrigerant Temperature Circuit 1AI10114Condenser Saturated Refrigerant Temperature Circuit 1AI10115Evaporator Refrigerant Pressure Circuit 2AI10116Condenser Refrigerant Pressure Circuit 2AI10117Differential Refrigerant Pressure Circuit 2AI10118Evaporator Saturated Refrigerant Temperature Circuit 2AI10119Condenser Saturated Refrigerant Temperature Circuit 2AI10120Refrigerant Discharge Temperature - Compressor 1AAI10121High Side Oil Pressure - Compressor 1AAI10122Refrigerant Discharge Temperature - Compressor 2AAI10123High Side Oil Pressure - Compressor 2AAI10124Air Flow Percentage Circuit 1AI10125Air Flow Percentage Circuit 2AI10126Drive Motor Average Voltage Circuit 1AI10127Drive Motor Current U Circuit 1AI10128Drive Motor Current V Circuit 1AI10129Drive Motor Current W Circuit 1AI10130Drive Motor Current U RLA Circuit 1AI10131Drive Motor Current V RLA Circuit 1AI10132Drive Motor Current W RLA Circuit 1AI10133Drive Motor Average Current RLA Circuit 1AI10134Drive DC Bus Voltage Circuit 1AI10135Drive Output Power Circuit 1AI10136AFD Transistor Temperature Circuit 1AI10137Motor Winding Temperature 1 Circuit 1AI10138Motor Winding Temperature 2 Circuit 1AI10139Drive Motor Average Voltage Circuit 2AI10140Drive Motor Current U Circuit 2AI10141Drive Motor Current V Circuit 2AI10142Drive Motor Current W Circuit 2AI10143Drive Motor Current U RLA Circuit 2AI10144Drive Motor Current V RLA Circuit 2AI10145Drive Motor Current W RLA Circuit 2AI10146Drive Motor Average Current RLA Circuit 2AI10147Drive DC Bus Voltage Circuit 2AI10148Drive Output Power Circuit 2AI10149AFD Transistor Temperature Circuit 2AI10150Motor Winding Temperature 1 Circuit 2AI10151Motor Winding Temperature 2 Circuit 2AI10152Sub Cooled Liquid Temperature Circuit 1AI10153Sub Cooled Liquid Temperature Circuit 2AI10154Evaporator Differential Water PressureAI10155System Chilled Water Differential PressureAI10158Phase AB Voltage - Compressor 1BAI10159Line 1 Current - Compressor 1BAI10160Line 2 Current - Compressor 1BAI10161Line 3 Current - Compressor 1BAI10162Line 1 Current RLA - Compressor 1BAI10163Line 2 Current RLA - Compressor 1BAI10164Line 3 Current RLA - Compressor 1BAI10165Phase AB Voltage - Compressor 2BAI10166Line 1 Current - Compressor 2BAI10167Line 2 Current - Compressor 2BAI10168Line 3 Current - Compressor 2BAI10169Line 1 Current RLA - Compressor 2BAI10170Line 2 Current RLA - Compressor 2BAI10171Line 3 Current RLA - Compressor 2BAI10173Refrigerant Discharge Temperature - Compressor 1BAI10174High Side Oil Pressure - Compressor 1BAI10175Refrigerant Discharge Temperature - Compressor 2BAI10176High Side Oil Pressure - Compressor 2BAI10177Number of CircuitsAI10178Number of Compressors Circuit 1AI10179Number of Compressors Circuit 2AI10180Actual Running CapacityAI10181Free Cooling Capacity StatusAI10182Free Cooling Entering Water Temperature ActiveAI10185Evaporator Differential Water Pressure Setpoint StatusAI10186Energy Consumption LifetimeAI10187Energy ConsumptionAI10188Starts - Compressor 1AAI10189Run Time - Compressor 1AAI10190Starts - Compressor 2AAI10191Run Time - Compressor 2AAI10192Starts - Compressor 1BAI10193Run Time - Compressor 1BAI10194Starts - Compressor 2BAI10195Run Time - Compressor 2BAI10196Chiller Design CapacityAI10198Chilled Water Setpoint StatusAI10199Demand Limit Setpoint StatusAI10200Unit Source IDAI10201Drive Input Voltage Calculated 1AAI10202Drive Input Voltage Calculated 2AAI10203Active Cool/Heat Setpoint TemperatureAI10204Phase BC Voltage - Compressor 1BAI10205Phase CA Voltage - Compressor 1BAI10206Phase BC Voltage - Compressor 2BAI10207Phase CA Voltage - Compressor 2BAI10208Average Line Current Circuit 1AI10209Average Line Current Circuit 2AI10210Average Line Voltage Circuit 1AI10211Average Line Voltage Circuit 2AI10212Line Current L1 Circuit 1AI10213Line Current L2 Circuit 1AI10214Line Current L3 Circuit 1AI10215Line Current L1 Circuit 2AI10216Line Current L2 Circuit 2AI10217Line Current L3 Circuit 2AI10218Voltage L1-L2 Circuit 1AI10219Voltage L2-L3 Circuit 1AI10220Voltage L1-L3 Circuit 1AI10221Voltage L1-L2 Circuit 2AI10222Voltage L2-L1 Circuit 2AI10223Voltage L1-L3 Circuit 2AI10224Total Real PowerAI10225Line Frequency Circuit 1AI10226Line Frequency Circuit 2AI10227Power Factor Circuit 1AI10228Power Factor Circuit 2AI10229Power Demand Circuit 1AI10230Power Demand Circuit 2AI10231Evaporator Approach Temperature Circuit 1AI10232Evaporator Approach Temperature Circuit 2AI10233Discharge Superheat Compressor 1AAI10234Discharge Superheat Compressor 1BAI10235Discharge Superheat Compressor 2AAI10236Discharge Superheat Compressor 2BAI10237Evaporator Water Flow RateAI10238Evaporator Differential Water PressureAI10239Entering Evaporator Water PressureAI10240Leaving Evaporator Water PressureAI10241Power FactorAI10242Current L1AI10243Current L2AI10244Current L3AI10245Average CurrentAI10246Voltage L1-L2AI10247Voltage L2-L3AI10248Voltage L1-L3AI10249Average Voltage L-LAI10250Line FrequencyAI10251AFD Coolant Supply Temperature Compressor 1AAI10253AFD Coolant Supply Temperature Compressor 2AAI10254Evaporator Water Pump Speed CommandAI10255Evaporator Water Pump Speed FeedbackAI10256Evaporator Water Pump Speed Setpoint ActiveAI10257Evaporator Water Pump Flow Rate Setpoint ActiveAI10258Free Cooling Dedicated Fans AirflowAI10259Drive Heat Sink Temperature Compressor 1AAI10260Drive Heat Sink Temperature Compressor 2AAI10261Compressor 1A Speed StatusAI10262Compressor 2A Speed StatusAI10263Calculated Chiller CapacityAI10264Free Cooling Target OffsetAI10265Free Cooling Valve Position StatusAI10266Active Demand Limit SetpointAI10267Evaporator Refrigerant Absolute Pressure Circuit 1AI10268Condenser Refrigerant Absolute Pressure Circuit 1AI10269Evaporator Refrigerant Absolute Pressure Circuit 2AI10270Condenser Refrigerant Absolute Pressure Circuit 2AI10271High Side Oil Absolute Pressure - Compressor 1AAI10272High Side Oil Absolute Pressure - Compressor 2AAI10273High Side Oil Absolute Pressure - Compressor 1BAI10274High Side Oil Absolute Pressure - Compressor 2BAI10275Entering Evaporator Water Absolute PressureAI10276Leaving Evaporator Water Absolute PressureAV10100Chilled Water SetpointAV10101Demand Limit SetpointAV10102Evaporator Water Pump Flow Rate Setpt BASAV10103Evaporator Water Pump Speed Setpt BASBI10100Run EnableBI10101Local Setpoint ControlBI10102Limit Mode Relay StatusBI10103Chiller Running StateBI10104Maximum CapacityBI10106Manual Override ExistsBI10107Compressor 1A StatusBI10108Compressor 2A StatusBI10109Emergency StopBI10110Evaporator Water Pump RequestBI10111Evaporator Water Flow StatusBI10112Compressor 1B StatusBI10113Compressor 2B StatusBI10114Free Cooling ActiveBI10116Diagnostic PresentBI10117Diagnostic Shutdown PresentBI10118Diagnostic: Manual Reset RequiredBI10119Diagnostic: Local Manual Reset RequiredBI10120Diagnostic Present: InformationBI10121Diagnostic Present: AdvisoryBI10122Diagnostic Present: CriticalBI10123Diagnostic Present: Service RequiredBI10124External Auto Stop Input StatusBI10125Front Panel Auto StopBI10126Noise Reduction Request ActiveBI10127Circuit 1 Lockout Front PanelBI10128Circuit 2 Lockout Front PanelBI10129Circuit 1 Lockout ExternalBI10130Circuit 2 Lockout ExternalBI10131Circuit 1 Lockout ActiveBI10132Circuit 2 Lockout ActiveBI10133Circuit 1 AvailableBI10134Circuit 2 AvailableBI10135Oil Sensor Circuit 1BI10136Oil Sensor Circuit 2BI10137Evaporator Water Pump 1 Inverter Running StatusBI10138Evaporator Water Pump 1 Fault StatusBI10139Compressor 1B Lockout ActiveBI10140Compressor 2B Lockout ActiveBI10141Free Cooling Front Panel Command StatusBI11000Diagnostic: AFD 1A Bus Over VoltageBI11001Diagnostic: AFD 1A Bus Under VoltageBI11002Diagnostic: AFD 1A Comm Loss: Main ProcessorBI11003Diagnostic: AFD 1A Customized Protection FaultBI11004Diagnostic: AFD 1A Gate Kill ActiveBI11005Diagnostic: AFD 1A General Failure (PF755)BI11006Diagnostic: AFD 1A General Failure (TR200)BI11007Diagnostic: AFD 1A Ground FaultBI11008Diagnostic: AFD 1A Input Phase LossBI11009Diagnostic: AFD 1A Input Transf or Filter Over TempBI11010Diagnostic: AFD 1A Loss Of Motor ControlBI11011Diagnostic: AFD 1A Low Rotor Flux FeedbackBI11012Diagnostic: AFD 1A Motor Current OverloadBI11013Diagnostic: AFD 1A Motor FaultBI11014Diagnostic: AFD 1A Motor ShortedBI11015Diagnostic: AFD 1A Over TemperatureBI11016Diagnostic: AFD 1A Precharge FaultBI11017Diagnostic: AFD 2A Bus Over VoltageBI11018Diagnostic: AFD 2A Bus Under VoltageBI11019Diagnostic: AFD 2A Comm Loss: Main ProcessorBI11020Diagnostic: AFD 2A Customized Protection FaultBI11021Diagnostic: AFD 2A Gate Kill ActiveBI11022Diagnostic: AFD 2A General Failure (PF755)BI11023Diagnostic: AFD 2A General Failure (TR200)BI11024Diagnostic: AFD 2A Ground FaultBI11025Diagnostic: AFD 2A Input Phase LossBI11026Diagnostic: AFD 2A Input Transf or Filter Over TempBI11027Diagnostic: AFD 2A Loss Of Motor ControlBI11028Diagnostic: AFD 2A Low Rotor Flux FeedbackBI11029Diagnostic: AFD 2A Motor Current OverloadBI11030Diagnostic: AFD 2A Motor FaultBI11031Diagnostic: AFD 2A Motor ShortedBI11032Diagnostic: AFD 2A Over TemperatureBI11033Diagnostic: AFD 2A Precharge FaultBI11034Diagnostic: AFD Bus Over Voltage - 1ABI11035Diagnostic: AFD Bus Over Voltage - 2ABI11036Diagnostic: AFD Bus Under Voltage - 1ABI11037Diagnostic: AFD Bus Under Voltage - 2ABI11038Diagnostic: AFD Comm Loss – 1ABI11039Diagnostic: AFD Comm Loss – 2ABI11040Diagnostic: AFD Comm Loss: Main Processor - 1ABI11041Diagnostic: AFD Comm Loss: Main Processor - 2ABI11042Diagnostic: AFD Failure to Arm or Start - 1ABI11043Diagnostic: AFD Failure to Arm or Start - 2ABI11044Diagnostic: AFD Fault Mains - 1ABI11045Diagnostic: AFD Fault Mains - 2ABI11046Diagnostic: AFD General Fault - 1ABI11047Diagnostic: AFD General Fault - 2ABI11048Diagnostic: AFD Ground Fault - 1ABI11049Diagnostic: AFD Ground Fault - 2ABI11050Diagnostic: AFD Harmonic Filter Over Temperature - 1ABI11051Diagnostic: AFD Harmonic Filter Over Temperature - 2ABI11052Diagnostic: AFD High Pressure Cutout - 1ABI11053Diagnostic: AFD High Pressure Cutout - 2ABI11054Diagnostic: AFD High Torque - 1ABI11055Diagnostic: AFD High Torque - 2ABI11056Diagnostic: AFD Initialized - 1ABI11057Diagnostic: AFD Initialized - 2ABI11058Diagnostic: AFD Internal Fault - 1ABI11059Diagnostic: AFD Internal Fault - 2ABI11060Diagnostic: AFD Interrupt Failure - 1ABI11061Diagnostic: AFD Interrupt Failure - 1BBI11062Diagnostic: AFD Interrupt Failure - 2ABI11063Diagnostic: AFD Interrupt Failure - 2BBI11064Diagnostic: AFD Inverter Heatsink Over Temperature - 1ABI11065Diagnostic: AFD Inverter Heatsink Over Temperature - 2ABI11066Diagnostic: AFD Locked Rotor - 1ABI11067Diagnostic: AFD Locked Rotor - 2ABI11068Diagnostic: AFD Mains Phase Loss - 1ABI11069Diagnostic: AFD Mains Phase Loss - 2ABI11070Diagnostic: AFD Missing Motor - 1ABI11071Diagnostic: AFD Missing Motor - 2ABI11073Diagnostic: AFD Motor Current Overload - 1A (TR200)BI11074Diagnostic: AFD Motor Current Overload - 1BBI11076Diagnostic: AFD Motor Current Overload - 2A (TR200)BI11077Diagnostic: AFD Motor Current Overload - 2BBI11078Diagnostic: AFD Motor Fault - 1ABI11079Diagnostic: AFD Motor Fault - 2ABI11080Diagnostic: AFD New Spare Parts - 1ABI11081Diagnostic: AFD New Spare Parts - 2ABI11082Diagnostic: AFD Option Configuration Change - 1ABI11083Diagnostic: AFD Option Configuration Change - 2ABI11084Diagnostic: AFD Output Phase U Loss - 1ABI11085Diagnostic: AFD Output Phase U Loss - 2ABI11086Diagnostic: AFD Output Phase V Loss - 1ABI11087Diagnostic: AFD Output Phase V Loss - 2ABI11088Diagnostic: AFD Output Phase W Loss - 1ABI11089Diagnostic: AFD Output Phase W Loss - 2ABI11090Diagnostic: AFD Over Temperature - 1ABI11091Diagnostic: AFD Over Temperature - 2ABI11092Diagnostic: AFD Short Circuit - 1ABI11093Diagnostic: AFD Short Circuit - 2ABI11094Diagnostic: AFD Unexpected Shutdown - 1ABI11095Diagnostic: AFD Unexpected Shutdown - 2ABI11096Diagnostic: Check ClockBI11097Diagnostic: Chiller Service RecommendedBI11098Comm Loss: %RLA Indication Output(Vdc)BI11099Comm Loss: AFD Fault Input 1ABI11100Comm Loss: AFD Fault Input 1BBI11101Comm Loss: AFD Fault Input 2ABI11102Comm Loss: AFD Fault Input 2BBI11103Comm Loss: Auxiliary Setpoint CommandBI11104Comm Loss: Cond Fan Enbl Shared Ckt 1&2BI11105Comm Loss: Cond Rfgt Tank Valve Ckt1BI11106Comm Loss: Cond Rfgt Tank Valve Ckt2BI11107Comm Loss: Condenser Fan Enable Circuit 1BI11108Comm Loss: Condenser Fan Enable Circuit 2BI11109Comm Loss: Condenser Rfgt Pressure Circuit 1BI11110Comm Loss: Condenser Rfgt Pressure Circuit 2BI11111Comm Loss: Cprsr Disch Rfgt Temp - 1ABI11112Comm Loss: Cprsr Disch Rfgt Temp - 1BBI11113Comm Loss: Cprsr Disch Rfgt Temp - 2ABI11114Comm Loss: Cprsr Disch Rfgt Temp - 2BBI11115Comm Loss: Drive Cooling Bypass Valve 1ABI11116Comm Loss: Drive Cooling Bypass Valve 2ABI11117Comm Loss: Drive Cooling Supply Temp 1ABI11118Comm Loss: Drive Cooling Supply Temp 2ABI11119Comm Loss: Economizer Disch Press - 1ABI11120Comm Loss: Economizer Disch Press - 1BBI11121Comm Loss: Economizer Disch Press - 2ABI11122Comm Loss: Economizer Disch Press - 2BBI11123Comm Loss: Economizer Disch Temp - 1ABI11124Comm Loss: Economizer Disch Temp - 1BBI11125Comm Loss: Economizer Disch Temp - 2ABI11126Comm Loss: Economizer Disch Temp - 2BBI11127Comm Loss: Economizer Valve - 1ABI11128Comm Loss: Economizer Valve - 1BBI11129Comm Loss: Economizer Valve - 2ABI11130Comm Loss: Economizer Valve - 2BBI11131Comm Loss: Electronic Expansion Valve 1 Compressor 1ABI11132Comm Loss: Electronic Expansion Valve 1 Compressor 2ABI11133Comm Loss: Electronic Expansion Valve 2 Compressor 1BBI11134Comm Loss: Electronic Expansion Valve 2 Compressor 2BBI11135Comm Loss: Emergency Stop Feedback InputBI11136Comm Loss: Energy Meter 1BI11137Comm Loss: Energy Meter 2BI11138Comm Loss: Evap Diff Water PressureBI11139Comm Loss: Evap Entering Water TempBI11140Comm Loss: Evap Iso Valve Close Switch Compressor 1ABI11141Comm Loss: Evap Iso Valve Close Switch Compressor 2ABI11142Comm Loss: Evap Iso Valve Open Switch Compressor 1ABI11143Comm Loss: Evap Iso Valve Open Switch Compressor 2ABI11144Comm Loss: Evap Isolation Valve Relay Compressor 1ABI11145Comm Loss: Evap Isolation Valve Relay Compressor 2ABI11146Comm Loss: Evap Leaving Water TempBI11147Comm Loss: Evap Pump Inv1 Fault InputBI11148Comm Loss: Evap Pump Inv1 Run CommandBI11149Comm Loss: Evap Rfgt Pool Temp Circuit 1BI11150Comm Loss: Evap Rfgt Pool Temp Circuit 2BI11151Comm Loss: Evap Water Pump Inv Freq InputBI11152Comm Loss: Evaporator Entering Water PressureBI11153Comm Loss: Evaporator Leaving Water PressureBI11154Comm Loss: Evaporator Oil Return Purge Valve - 1ABI11155Comm Loss: Evaporator Oil Return Purge Valve - 2ABI11156Comm Loss: Evaporator Pump 1 Fault InputBI11157Comm Loss: Evaporator Pump 2 Fault InputBI11158Comm Loss: Evaporator Pump Fault InputBI11159Comm Loss: Evaporator Pump Inverter Running StatusBI11160Comm Loss: Evaporator Pump Speed CommandBI11161Comm Loss: Evaporator Pump Speed FeedbackBI11162Comm Loss: Evaporator Water Flow SwitchBI11163Comm Loss: Evaporator Water Pump 1 RelayBI11164Comm Loss: Evaporator Water Pump 2 RelayBI11165Comm Loss: Evaporator Water Pump RelayBI11166Comm Loss: Ext Chilled Water SetpointBI11167Comm Loss: Ext Demand Limit SetpointBI11168Comm Loss: Ext Noise Reduction RequestBI11169Comm Loss: External Auto/StopBI11170Comm Loss: External Ckt Lockout Circuit 1BI11171Comm Loss: External Ckt Lockout Circuit 2BI11172Comm Loss: External Heat Recovery CommandBI11173Comm Loss: External Heat Recovery SetpointBI11174Comm Loss: External Ice Building CommandBI11175Comm Loss: Fan Board 1 Relay 1 Circuit 1BI11176Comm Loss: Fan Board 1 Relay 1 Circuit 2BI11177Comm Loss: Fan Board 1 Relay 2 Circuit 1BI11178Comm Loss: Fan Board 1 Relay 2 Circuit 2BI11179Comm Loss: Fan Board 1 Relay 3 Circuit 1BI11180Comm Loss: Fan Board 1 Relay 3 Circuit 2BI11181Comm Loss: Fan Board 1 Relay 4 Circuit 1BI11182Comm Loss: Fan Board 1 Relay 4 Circuit 2BI11183Comm Loss: Fan Board 2 Relay 1 Circuit 1BI11184Comm Loss: Fan Board 2 Relay 1 Circuit 2BI11185Comm Loss: Fan Board 2 Relay 2 Circuit 1BI11186Comm Loss: Fan Board 2 Relay 2 Circuit 2BI11187Comm Loss: Fan Board 2 Relay 3 Circuit 1BI11188Comm Loss: Fan Board 2 Relay 3 Circuit 2BI11189Comm Loss: Fan Board 2 Relay 4 Circuit 1BI11190Comm Loss: Fan Board 2 Relay 4 Circuit 2BI11191Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1 & 2BI11192Comm Loss: Fan Inverter Fault Circuit 1BI11193Comm Loss: Fan Inverter Fault Circuit 2BI11194Comm Loss: Fan Inverter Speed Command Circuit 1BI11195Comm Loss: Fan Inverter Speed Command Circuit 2BI11196Comm Loss: FC Entering Glycol TempBI11197Comm Loss: FC Entering Water TempBI11198Comm Loss: FC Leaving Glycol TempBI11199Comm Loss: Free Cooling Bypass ValveBI11200Comm Loss: Free Cooling Dedicated Fan EnableBI11201Comm Loss: Free Cooling Dedicated Fan Inverter FaultBI11202Comm Loss: Free Cooling Dedicated Fan Inverter Speed CommandBI11203Comm Loss: Free Cooling Glycol Flow SwitchBI11204Comm Loss: Free Cooling Glycol PressureBI11205Comm Loss: Free Cooling Glycol Pump FaultBI11206Comm Loss: Free Cooling PumpBI11207Comm Loss: Free Cooling ValveBI11208Comm Loss: Heat Recovery Mode Valve Command - Ckt1BI11209Comm Loss: Heat Recovery Mode Valve Command - Ckt2BI11210Comm Loss: Heat Recovery Water Flow CmdBI11211Comm Loss: Heat Recovery Water Pump RelayBI11212Comm Loss: Heat Recovery Water Flow SwitchBI11213Comm Loss: High Pressure Cutout Sw - 1ABI11214Comm Loss: High Pressure Cutout Sw - 1BBI11215Comm Loss: High Pressure Cutout Sw - 2ABI11216Comm Loss: High Pressure Cutout Sw - 2BBI11217Comm Loss: Hot Gas Oil Return Valve - 1ABI11218Comm Loss: Hot Gas Oil Return Valve - 2ABI11219Comm Loss: HR Entering Water Temp SensorBI11220Comm Loss: HR Leaving Water Temp SensorBI11221Comm Loss: Liquid Line Pressure Circuit 1BI11222Comm Loss: Liquid Line Pressure Circuit 2BI11223Comm Loss: Liquid Line Temperature Circuit 1BI11224Comm Loss: Liquid Line Temperature Circuit 2BI11225Comm Loss: Motor Winding Tstat Cprsr1ABI11226Comm Loss: Motor Winding Tstat Cprsr2ABI11227Comm Loss: Off-cycle Freeze Prot RelayBI11228Comm Loss: Oil Loss Level Sensor Input Circuit 1BI11229Comm Loss: Oil Loss Level Sensor Input Circuit 2BI11230Comm Loss: Oil Pressure - 1ABI11231Comm Loss: Oil Pressure - 1BBI11232Comm Loss: Oil Pressure - 2ABI11233Comm Loss: Oil Pressure - 2BBI11234Comm Loss: Oil Return Solenoid Valve - 1BBI11235Comm Loss: Oil Return Solenoid Valve - 2BBI11236Comm Loss: Oil Return Valve - 1ABI11237Comm Loss: Oil Return Valve - 2ABI11238Comm Loss: Oil Supply TemperatureBI11239Comm Loss: Oil Supply TemperatureBI11240Comm Loss: Oil Temperature - 1ABI11241Comm Loss: Oil Temperature - 1BBI11242Comm Loss: Oil Temperature - 2ABI11243Comm Loss: Oil Temperature - 2BBI11244Comm Loss: Outdoor Air TemperatureBI11245Comm Loss: Programmable Relay Board 1BI11246Comm Loss: Programmable Relay Board 2BI11247Comm Loss: Slide Valve Load - 1ABI11248Comm Loss: Slide Valve Load - 1BBI11249Comm Loss: Slide Valve Load - 2ABI11250Comm Loss: Slide Valve Load - 2BBI11251Comm Loss: Slide Valve Unload - 1ABI11252Comm Loss: Slide Valve Unload - 1BBI11253Comm Loss: Slide Valve Unload - 2ABI11254Comm Loss: Slide Valve Unload - 2BBI11255Comm Loss: Starter 1ABI11256Comm Loss: Starter 1BBI11257Comm Loss: Starter 2ABI11258Comm Loss: Starter 2BBI11259Comm Loss: Step Load - 1ABI11260Comm Loss: Step Load - 1BBI11261Comm Loss: Step Load - 2ABI11262Comm Loss: Step Load - 2BBI11263Comm Loss: Suction Rfgt Pressure - 1ABI11264Comm Loss: Suction Rfgt Pressure - 1BBI11265Comm Loss: Suction Rfgt Pressure - 2ABI11266Comm Loss: Suction Rfgt Pressure - 2BBI11267Comm Loss: Var Vi Valve – Cprsr1ABI11268Comm Loss: Var Vi Valve – Cprsr2ABI11269Comm Loss: Winding Temp 1, Cprsr1ABI11270Comm Loss: Winding Temp 1, Cprsr2ABI11271Comm Loss: Winding Temp 2, Cprsr1ABI11272Comm Loss: Winding Temp 2, Cprsr2ABI11273Diagnostic: Condenser Rfgt Pressure Sensor Circuit 1BI11274Diagnostic: Condenser Rfgt Pressure Sensor Circuit 2BI11275Diagnostic: Cprsr Did Not Accel: Shutdown - 1ABI11276Diagnostic: Cprsr Did Not Accel: Shutdown - 1BBI11277Diagnostic: Cprsr Did Not Accel: Shutdown - 2ABI11278Diagnostic: Cprsr Did Not Accel: Shutdown - 2BBI11279Diagnostic: Cprsr Did Not Accel: Transition - 1ABI11280Diagnostic: Cprsr Did Not Accel: Transition - 1BBI11281Diagnostic: Cprsr Did Not Accel: Transition - 2ABI11282Diagnostic: Cprsr Did Not Accel: Transition - 2BBI11283Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1ABI11284Diagnostic: Cprsr Disch Rfgt Temp Sensor - 1BBI11285Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2ABI11286Diagnostic: Cprsr Disch Rfgt Temp Sensor - 2BBI11287Diagnostic: Drive Cooling Supply Temp Sensor - 1ABI11288Diagnostic: Drive Cooling Supply Temp Sensor - 2ABI11289Diagnostic: Economizer Disch Press Sensor - 1ABI11290Diagnostic: Economizer Disch Press Sensor - 1BBI11291Diagnostic: Economizer Disch Press Sensor - 2ABI11292Diagnostic: Economizer Disch Press Sensor - 2BBI11293Diagnostic: Economizer Disch Temp Sensor - 1ABI11294Diagnostic: Economizer Disch Temp Sensor - 1BBI11295Diagnostic: Economizer Disch Temp Sensor - 2ABI11296Diagnostic: Economizer Disch Temp Sensor - 2BBI11297Diagnostic: Emergency Stop Feedback InputBI11298Diagnostic: Evap Iso Valve Illegal Switch State Compressor 1ABI11299Diagnostic: Evap Iso Valve Illegal Switch State Compressor 2ABI11300Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 1ABI11301Diagnostic: Evap Isolation Valve Closed Switch Failure Compressor 2ABI11302Diagnostic: Evap Isolation Valve Failed To Close Compressor 1ABI11303Diagnostic: Evap Isolation Valve Failed To Close Compressor 2ABI11304Diagnostic: Evap Isolation Valve Failed To Open Compressor 1ABI11305Diagnostic: Evap Isolation Valve Failed To Open Compressor 2ABI11306Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 1ABI11307Diagnostic: Evap Isolation Valve Open Switch Failure Compressor 2ABI11308Diagnostic: Evap Pump 1 Starts Run time WrittenBI11309Diagnostic: Evap Pump 2 Starts Run time WrittenBI11310Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 1BI11311Diagnostic: Evap Rfgt Pool Temp Sensor Circuit 2BI11312Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt1BI11313Diagnostic: Evap Rfgt Pool Temp Sensor Error - Ckt2BI11314Diagnostic: Evap Water Pump 1 Svc RecommendedBI11315Diagnostic: Evap Water Pump 2 Svc RecommendedBI11316Diagnostic: Evaporator Approach Error Circuit 1BI11317Diagnostic: Evaporator Approach Error Circuit 2BI11318Diagnostic: Evaporator Diff Water Pressure XdcrBI11319Diagnostic: Evaporator Entering Water PressureBI11320Diagnostic: Evaporator Entering Water Temp SensorBI11321Diagnostic: Evaporator Leaving Water PressureBI11322Diagnostic: Evaporator Leaving Water Temp SensorBI11323Diagnostic: Evaporator Pump 1 FaultBI11324Diagnostic: Evaporator Pump 2 FaultBI11325Diagnostic: Evaporator Water Flow LostBI11326Diagnostic: Evaporator Water Flow Lost - Pump1BI11327Diagnostic: Evaporator Water Flow Lost - Pump2BI11328Diagnostic: Evaporator Water Flow OverdueBI11329Diagnostic: Evaporator Water Flow Overdue - Pump1BI11330Diagnostic: Evaporator Water Flow Overdue - Pump2BI11331Diagnostic: Evaporator Water Pump FaultBI11332Diagnostic: Evaporator Water Pump Speed FeedbackBI11333Diagnostic: Excessive Condenser Pressure Circuit 1BI11334Diagnostic: Excessive Condenser Pressure Circuit 2BI11335Diagnostic: External Chilled Water SetpointBI11336Diagnostic: External Demand Limit SetpointBI11337Diagnostic: External Heat Recovery SetpointBI11338Diagnostic: Fan Inverter Fault Circuit 1BI11339Diagnostic: Fan Inverter Fault Circuit 2BI11340Diagnostic: Free Cooling Dedicated Fan Inverter FaultBI11341Diagnostic: Free Cooling Entering Glycol TemperatureBI11342Diagnostic: Free Cooling Entering Water TemperatureBI11343Diagnostic: Free Cooling Glycol Flow LostBI11344Diagnostic: Free Cooling Glycol Flow OverdueBI11345Diagnostic: Free Cooling Glycol PressureBI11346Diagnostic: Free Cooling Glycol Pump FaultBI11347Diagnostic: Free Cooling Glycol Temperature Equalization OverdueBI11348Diagnostic: Free Cooling Leaving Glycol TemperatureBI11349Diagnostic: Heat Recovery Entering Water Temp SensorBI11350Diagnostic: Heat Recovery Leaving Water Temp SensorBI11351Diagnostic: Heat Recovery Water Flow LostBI11352Diagnostic: Heat Recovery Water Flow OverdueBI11353Diagnostic: High Cprsr Rfgt Discharge Temp - 1ABI11354Diagnostic: High Cprsr Rfgt Discharge Temp - 1BBI11355Diagnostic: High Cprsr Rfgt Discharge Temp - 2ABI11356Diagnostic: High Cprsr Rfgt Discharge Temp - 2BBI11357Diagnostic: High Differential Rfgt Pressure - 1ABI11358Diagnostic: High Differential Rfgt Pressure - 1BBI11359Diagnostic: High Differential Rfgt Pressure - 2ABI11360Diagnostic: High Differential Rfgt Pressure - 2BBI11361Diagnostic: High Evaporator Refrigerant PressureBI11362Diagnostic: High Evaporator Water TemperatureBI11363Diagnostic: High Motor Winding Temperature - 1ABI11364Diagnostic: High Motor Winding Temperature - 2ABI11365Diagnostic: High Oil Temperature - 1ABI11366Diagnostic: High Oil Temperature - 1BBI11367Diagnostic: High Oil Temperature - 2ABI11368Diagnostic: High Oil Temperature - 2BBI11369Diagnostic: High Pressure Cutout - 1ABI11370Diagnostic: High Pressure Cutout - 1BBI11371Diagnostic: High Pressure Cutout - 2ABI11372Diagnostic: High Pressure Cutout - 2BBI11373Diagnostic: High Refrigerant Pressure Ratio - 1ABI11374Diagnostic: High Refrigerant Pressure Ratio - 1BBI11375Diagnostic: High Refrigerant Pressure Ratio - 2ABI11376Diagnostic: High Refrigerant Pressure Ratio - 2BBI11377Diagnostic: Inverted Evaporator Water TemperatureBI11378Diagnostic: Liquid Line Pressure Sensor Circuit 1BI11379Diagnostic: Liquid Line Pressure Sensor Circuit 2BI11380Diagnostic: Liquid Line Temp Sensor Circuit 1BI11381Diagnostic: Liquid Line Temp Sensor Circuit 2BI11382Diagnostic: Loss of Oil for Compressor (Running) Compressor 1ABI11383Diagnostic: Loss of Oil for Compressor (Running) Compressor 2ABI11384Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 1ABI11385Diagnostic: Loss of Oil for Compressor (Stopped) Compressor 2ABI11386Diagnostic: Low Differential Rfgt Pressure - 1ABI11387Diagnostic: Low Differential Rfgt Pressure - 1BBI11388Diagnostic: Low Differential Rfgt Pressure - 2ABI11389Diagnostic: Low Differential Rfgt Pressure - 2BBI11390Diagnostic: Low Discharge Superheat - 1ABI11391Diagnostic: Low Discharge Superheat - 1BBI11392Diagnostic: Low Discharge Superheat - 2ABI11393Diagnostic: Low Discharge Superheat - 2BBI11394Diagnostic: Low Drive Cooling Supply Temperature - 1ABI11395Diagnostic: Low Drive Cooling Supply Temperature - 2ABI11396Diagnostic: Low Evaporator Entering Water PressureBI11397Diagnostic: Low Evaporator Leaving Water PressureBI11398Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit OffBI11399Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit OffBI11400Diagnostic: Low Evaporator Water FlowBI11401Diagnostic: Low Evaporator Water Temp (Unit Off)BI11402Diagnostic: Low Evaporator Water Temp (Unit On)BI11403Diagnostic: Low Glycol Pressure Free CoolingBI11404Diagnostic: Low Glycol Temp Free CoolingBI11405Diagnostic: Low Oil Flow - 1ABI11406Diagnostic: Low Oil Flow - 1BBI11407Diagnostic: Low Oil Flow - 2ABI11408Diagnostic: Low Oil Flow - 2BBI11409Diagnostic: Low Refrigerant Temperature Circuit 1BI11410Diagnostic: Low Refrigerant Temperature Circuit 2BI11411Diagnostic: Low Suction Refrigerant Pressure - 1ABI11412Diagnostic: Low Suction Refrigerant Pressure - 1BBI11413Diagnostic: Low Suction Refrigerant Pressure - 2ABI11414Diagnostic: Low Suction Refrigerant Pressure - 2BBI11415Diagnostic: Mfr Maintenance Recommended - 1ABI11416Diagnostic: Mfr Maintenance Recommended - 1BBI11417Diagnostic: Mfr Maintenance Recommended - 2ABI11418Diagnostic: Mfr Maintenance Recommended - 2BBI11419Diagnostic: Momentary Power Loss Compressor 1ABI11420Diagnostic: Momentary Power Loss Compressor 2ABI11421Diagnostic: Motor Current Overload - 1ABI11422Diagnostic: Motor Current Overload - 1BBI11423Diagnostic: Motor Current Overload - 2ABI11424Diagnostic: Motor Current Overload - 2BBI11425Diagnostic: Motor Winding Temp Sensor - 1ABI11426Diagnostic: Motor Winding Temp Sensor - 2ABI11427Diagnostic: MP: Invalid ConfigurationBI11428Diagnostic: MP: Reset Has OccurredBI11429Diagnostic: No Differential Rfgt Pressure - 1ABI11430Diagnostic: No Differential Rfgt Pressure - 1BBI11431Diagnostic: No Differential Rfgt Pressure - 2ABI11432Diagnostic: No Differential Rfgt Pressure - 2BBI11433Diagnostic: Oil Filter Change Recommended - Cprsr1ABI11434Diagnostic: Oil Filter Change Recommended - Cprsr2ABI11435Diagnostic: Oil Flow Protection Fault - 1ABI11436Diagnostic: Oil Flow Protection Fault - 1BBI11437Diagnostic: Oil Flow Protection Fault - 2ABI11438Diagnostic: Oil Flow Protection Fault - 2BBI11439Diagnostic: Oil Pressure Sensor - 1ABI11440Diagnostic: Oil Pressure Sensor - 1BBI11441Diagnostic: Oil Pressure Sensor - 2ABI11442Diagnostic: Oil Pressure Sensor - 2BBI11443Diagnostic: Oil Supply Temp Sensor Circuit 1BI11444Diagnostic: Oil Supply Temp Sensor Circuit 2BI11445Diagnostic: Oil Temperature Sensor - 1ABI11446Diagnostic: Oil Temperature Sensor - 1BBI11447Diagnostic: Oil Temperature Sensor - 2ABI11448Diagnostic: Oil Temperature Sensor - 2BBI11449Diagnostic: Outdoor Air Temperature SensorBI11450Diagnostic: Over VoltageBI11451Diagnostic: Phase Loss - 1ABI11452Diagnostic: Phase Loss - 1BBI11453Diagnostic: Phase Loss - 2ABI11454Diagnostic: Phase Loss - 2BBI11455Diagnostic: Phase Reversal - 1ABI11456Diagnostic: Phase Reversal - 1BBI11457Diagnostic: Phase Reversal - 2ABI11458Diagnostic: Phase Reversal - 2BBI11459Diagnostic: Power Loss - 1ABI11460Diagnostic: Power Loss - 1BBI11461Diagnostic: Power Loss - 2ABI11462Diagnostic: Power Loss - 2BBI11463Diagnostic: Pumpdown Terminated By Time Circuit 1BI11464Diagnostic: Pumpdown Terminated By Time Circuit 2BI11465Diagnostic: Restart Inhibit Invoked - 1ABI11466Diagnostic: Restart Inhibit Invoked - 1BBI11467Diagnostic: Restart Inhibit Invoked - 2ABI11468Diagnostic: Restart Inhibit Invoked - 2BBI11469Diagnostic: Severe Current Imbalance - 1ABI11470Diagnostic: Severe Current Imbalance - 1BBI11471Diagnostic: Severe Current Imbalance - 2ABI11472Diagnostic: Severe Current Imbalance - 2BBI11473Diagnostic: Software Error 1001: Call Trane ServiceBI11474Diagnostic: Software Error 1002: Call Trane ServiceBI11475Diagnostic: Software Error 1003: Call Trane ServiceBI11476Diagnostic: Starter Comm Loss: Main Processor - 1ABI11477Diagnostic: Starter Comm Loss: Main Processor - 1BBI11478Diagnostic: Starter Comm Loss: Main Processor - 2ABI11479Diagnostic: Starter Comm Loss: Main Processor - 2BBI11480Diagnostic: Starter Contactor Interrupt Failure - 1ABI11481Diagnostic: Starter Contactor Interrupt Failure - 1BBI11482Diagnostic: Starter Contactor Interrupt Failure - 2ABI11483Diagnostic: Starter Contactor Interrupt Failure - 2BBI11484Diagnostic: Starter Did Not Fully AccelerateBI11485Diagnostic: Starter Did Not Transition - 1ABI11486Diagnostic: Starter Did Not Transition - 1BBI11487Diagnostic: Starter Did Not Transition - 2ABI11488Diagnostic: Starter Did Not Fully Accelerate Compressor 2ABI11489Diagnostic: Starter Did Not Transition - 2BBI11490Diagnostic: Starter Dry Run Test - 1ABI11491Diagnostic: Starter Dry Run Test - 1BBI11492Diagnostic: Starter Dry Run Test - 2ABI11493Diagnostic: Starter Dry Run Test - 2BBI11494Diagnostic: Starter Failed to Arm/Start - 1ABI11495Diagnostic: Starter Failed to Arm/Start - 1BBI11496Diagnostic: Starter Failed to Arm/Start - 2ABI11497Diagnostic: Starter Failed to Arm/Start - 2BBI11498Diagnostic: Starter Fault Type I - 1ABI11499Diagnostic: Starter Fault Type I - 1BBI11500Diagnostic: Starter Fault Type I - 2ABI11501Diagnostic: Starter Fault Type I - 2BBI11502Diagnostic: Starter Fault Type II - 1ABI11503Diagnostic: Starter Fault Type II - 1BBI11504Diagnostic: Starter Fault Type II - 2ABI11505Diagnostic: Starter Fault Type II - 2BBI11506Diagnostic: Starter Fault Type III - 1ABI11507Diagnostic: Starter Fault Type III - 1BBI11508Diagnostic: Starter Fault Type III - 2ABI11509Diagnostic: Starter Fault Type III - 2BBI11510Diagnostic: Starter Module Memory Error Type 1 - 1ABI11511Diagnostic: Starter Module Memory Error Type 1 - 1BBI11512Diagnostic: Starter Module Memory Error Type 1 - 2ABI11513Diagnostic: Starter Module Memory Error Type 1 - 2BBI11514Diagnostic: Starter Module Memory Error Type 2 - 1ABI11515Diagnostic: Starter Module Memory Error Type 2 - 1BBI11516Diagnostic: Starter Module Memory Error Type 2 - 2ABI11517Diagnostic: Starter Module Memory Error Type 2 - 2BBI11518Diagnostic: Starts/Hours Modified 1ABI11519Diagnostic: Starts/Hours Modified 1BBI11520Diagnostic: Starts/Hours Modified 2ABI11521Diagnostic: Starts/Hours Modified 2BBI11522Diagnostic: Suction Refrigerant Pressure Sensor - 1ABI11523Diagnostic: Suction Refrigerant Pressure Sensor - 1BBI11524Diagnostic: Suction Refrigerant Pressure Sensor - 2ABI11525Diagnostic: Suction Refrigerant Pressure Sensor - 2BBI11526Diagnostic: Transition Complete Input Opened - 1ABI11527Diagnostic: Transition Complete Input Opened - 1BBI11528Diagnostic: Transition Complete Input Opened - 2ABI11529Diagnostic: Transition Complete Input Opened - 2BBI11530Diagnostic: Transition Complete Input Shorted - 1ABI11531Diagnostic: Transition Complete Input Shorted - 1BBI11532Diagnostic: Transition Complete Input Shorted - 2ABI11533Diagnostic: Transition Complete Input Shorted - 2BBI11534Diagnostic: Under VoltageBI11535Diagnostic: Unexpected Starter Shutdown - 1ABI11536Diagnostic: Unexpected Starter Shutdown - 1BBI11537Diagnostic: Unexpected Starter Shutdown - 2ABI11538Diagnostic: Unexpected Starter Shutdown - 2BBI11539Diagnostic: Very Low Evap Rfgt Pressure - 1ABI11540Diagnostic: Very Low Evap Rfgt Pressure - 1BBI11541Diagnostic: Very Low Evap Rfgt Pressure - 2ABI11542Diagnostic: Very Low Evap Rfgt Pressure - 2BBI11543Diagnostic: Write Command Failure Energy Meter 1BI11544Diagnostic: Write Command Failure Energy Meter 2BI11545Comm Loss: Ice Building Status RelayBV10100Reset DiagnosticBV10101Noise Reduction Request BASBV10102Circuit 1 Lockout BASBV10103Circuit 2 Lockout BASBV10107Energy Consumption ResetBV10108Chiller Auto Stop Command BASBV10109Free Cooling Auto Stop Command BASBV10110Free Cooling Compressor LockoutBV10111Compressor 1B Lockout BASBV10112Compressor 2B Lockout BASMI10100Running ModeMI10101Operating ModeMI10102Refrigerant TypeMI10103Cooling TypeMI10104Manufacture LocationMI10105Model Information [GEN2]MI10106Chiller Setpoint SourceMV10100Chiller Mode Command BAS
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the communicated engineering unit follows the factory-configured unit system (I-P or SI), not the web UI display setting.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
- The document ends with a table of numeric diagnostic codes and their names; AI 10200 Unit Source ID reports the last diagnostic as a number.
- Trane also publishes a list for Ascend ACS/ACX chillers (BAS-PTS011) with different instance numbers.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Ascend ACR Series C and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 Ascend ACR Series C
How many BACnet points does the Trane Symbio 800 Ascend ACR Series C have?
This list has 772 BACnet objects: 166 analog inputs, 4 analog values, 584 binary inputs, 10 binary values, 7 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 Ascend ACR Series C BACnet points are writable?
15 of the 772 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 Ascend ACR Series C BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - Ascend Model ACR Series C (BAS-PTS021A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS021A-EN_11152024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 Ascend ACR Series C?
Start with BV 10108 Chiller Auto Stop Command BAS (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10103 Chiller Running State (Chiller on/off status); BI 10101 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10104 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10180 Actual Running Capacity (Actual running capacity in percent); BI 10116 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 Ascend ACR Series C?
BV 10108 Chiller Auto Stop Command BAS (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10124 External Auto Stop Input Status reports the hardwired external auto/stop input, and BI 10100 Run Enable shows whether the chiller is enabled to run. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10101 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10106 Chiller Setpoint Source shows BAS, External or Front Panel.
How do I check these points on the real Symbio 800 Ascend ACR Series C?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet - Ascend Model ACR Series C · BAS-PTS021A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.