- Home
- BACnet points lists
- Trane
- Symbio 800 RTAC (CH530)
Air-cooled screw chiller controller · BACnet points list
Trane Symbio 800 RTAC (CH530) BACnet points list
Updated 28 October 2026
A short Symbio 800 list of about 85 objects for RTAC chillers marked CH530, with small instance numbers (AI 1 to AI 98). AIs cover water temperatures, refrigerant and oil pressures, compressor starts, run times and motor currents. The BAS writes chilled water setpoint and current limit (AO), auto/stop and diagnostic reset (BO) and mode (MO).
This page lists 86 BACnet objects for the Trane Symbio 800 RTAC (CH530) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 RTAC (CH530)
- Equipment
- Air-cooled screw chiller controller
- Equipment type
- Chillers
- BACnet objects
- 86 (5 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 RTAC (CH530)
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, current limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. The alarm-present flag gives a single summary alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | Chiller Auto Stop Command | BMS auto/stop (enable) command | Write |
| MO 1 | Chiller Mode Command | Cool/heat/ice mode command | Write |
| AO 1 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AO 2 | Current Limit Setpoint | Current (capacity) limit from the BMS, % | Write |
| BI 4 | Chiller Running State | Chiller on/off status | Read |
| BI 2 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 45 | Evaporator Leaving Water Temp | Leaving chilled water temperature | Read |
| AI 5 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 23 | Alarm Present | Any active alarm on the chiller | Read |
Enable & remote start
BO 1 Chiller Auto Stop Command (Inactive = Stop, Active = Auto) is the BMS auto/stop; its relinquish default is True (Auto). BI 1 Run Enabled shows whether the chiller is available to run. The document doesn't say how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- This list has no read/write column; writability of the command and setpoint objects is inferred from their object type and relinquish defaults.
- Relinquish defaults: AO 1 44 °F (6.7 °C), AO 2 100 %, BO 1 Auto, BO 2 no reset, MO 1 Cool. Releasing BO 1 leaves the chiller in Auto.
- MI 3 MP Communication Status is marked 'Do Not Use This Point' in the document.
Trane Symbio 800 RTAC (CH530) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Active Cool/Heat Setpoint Temperature | Active chiller water or hot water setpoint | Temperature | Read | |
| AI | 2 | Active Current Limit Setpoint | Active capacity current limit setpoint | Percent | Read | |
| AImin | 5 | Actual Running Capacity | Level of capacity that the chiller is currently running at | Percent | Read | |
| AI | 6 | Evaporator Refrigerant Pressure- Ckt1 | Circuit 1 evaporator refrigerant pressure | Pressure | Read | |
| AI | 9 | Evaporator Refrigerant Pressure- Ckt 2 | Circuit 2 evaporator refrigerant pressure | Pressure | Read | |
| AI | 12 | Evaporator Saturated Refrigerant Temperature- Ckt 1 | Circuit 2 evaporator refrigerant temperature | Temperature | Read | |
| AI | 14 | Evaporator Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 evaporator refrigerant temperature | Temperature | Read | |
| AI | 16 | Condenser Refrigerant Pressure- Ckt 1 | Circuit 1 condenser refrigerant pressure | Pressure | Read | |
| AI | 18 | Condenser Refrigerant Pressure- Ckt 2 | Circuit 2 condenser refrigerant pressure | Pressure | Read | |
| AI | 20 | Condenser Saturated Refrigerant Temperature- Ckt 1 | Circuit 1 condenser refrigerant temperature | Temperature | Read | |
| AI | 22 | Condenser Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 condenser refrigerant temperature | Temperature | Read | |
| AI | 25 | Local Atmospheric Pressure | Pressure | Read | ||
| AI | 26 | Starts- Compressor 1A | Number of starts for compressor 1A | Read | ||
| AI | 27 | Starts- Compressor 1B | Number of starts for compressor 1B | Read | ||
| AI | 28 | Starts- Compressor 2A | Number of starts for compressor 2A | Read | ||
| AI | 29 | Starts- Compressor 2B | Number of starts for compressor 2B | Read | ||
| AI | 34 | Run Time- Compressor 1A | Total run time of compressor 1A | Time | Read | |
| AI | 35 | Run Time- Compressor 1B | Total run time of compressor 1B | Time | Read | |
| AI | 36 | Run Time- Compressor 2A | Total run time of compressor 2A | Time | Read | |
| AI | 42 | Airflow Percentage- Circuit 1 | Approximate airflow percentage of circuit 1 | Percent | Read | |
| AI | 43 | Airflow Percentage- Circuit 2 | Approximate airflow percentage of circuit 2 | Percent | Read | |
| AI | 44 | Evaporator Entering Water Temp | Temperature of the water entering the evaporator | Temperature | Read | |
| AImin | 45 | Evaporator Leaving Water Temp | Temperature of the water leaving the evaporator | Temperature | Read | |
| AI | 48 | High Side Oil Pressure- Compressor 1A | Pressure of the oil at the high side of compressor 1A | Pressure | Read | |
| AI | 49 | High Side Oil Pressure- Compressor 1B | Pressure of the oil at the high side of compressor 1B | Pressure | Read | |
| AI | 50 | High Side Oil Pressure- Compressor 2A | Pressure of the oil at the high side of compressor 2A | Pressure | Read | |
| AI | 51 | High Side Oil Pressure- Compressor 2B | Pressure of the oil at the high side of compressor 2B | Pressure | Read | |
| AI | 52 | Oil Temp- Compressor 1A | Temperature of the oil in compressor 1A | Temperature | Read | |
| AI | 54 | Oil Temp- Compressor 2A | Temperature of the oil in compressor 2A | Temperature | Read | |
| AI | 55 | Oil Temp- Compressor 2B | Temperature of the oil in compressor 2B | Temperature | Read | |
| AI | 57 | Outdoor Air Temperature | Temperature | Read | ||
| AI | 59 | Phase AB Voltage- Compressor 1A | Phase AB voltage, compressor 1A | Voltage | Read | |
| AI | 71 | Line 1 Current (in Amps)- Compressor 1A | Current | Read | ||
| AI | 72 | Line 2 Current (in Amps)- Compressor 1A | Current | Read | ||
| AI | 73 | Line 3 Current (in Amps)- Compressor 1A | Current | Read | ||
| AI | 74 | Line 1 Current (in Amps)- Compressor 1B | Current | Read | ||
| AI | 75 | Line 2 Current (in Amps)- Compressor 1B | Current | Read | ||
| AI | 76 | Line 3 Current (in Amps)- Compressor 1B | Current | Read | ||
| AI | 77 | Line 1 Current (in Amps)- Compressor 2A | Current | Read | ||
| AI | 78 | Line 2 Current (in Amps)- Compressor 2A | Current | Read | ||
| AI | 79 | Line 3 Current (in Amps)- Compressor 2A | Current | Read | ||
| AI | 80 | Line 1 Current (in Amps)- Compressor 2B | Current | Read | ||
| AI | 81 | Line 2 Current (in Amps)- Compressor 2B | Current | Read | ||
| AI | 82 | Line 3 Current (in Amps)- Compressor 2B | Current | Read | ||
| AI | 83 | Line 1 Current (%RLA)- Compressor 1A | Percent | Read | ||
| AI | 84 | Line 2 Current (%RLA)- Compressor 1A | Percent | Read | ||
| AI | 85 | Line 3 Current (%RLA)- Compressor 1A | Percent | Read | ||
| AI | 86 | Line 1 Current (%RLA)- Compressor 1B | Percent | Read | ||
| AI | 87 | Line 2 Current (%RLA)- Compressor 1B | Percent | Read | ||
| AI | 88 | Line 3 Current (%RLA)- Compressor 1B | Percent | Read | ||
| AI | 89 | Line 1 Current (%RLA)- Compressor 2A | Percent | Read | ||
| AI | 90 | Line 2 Current (%RLA)- Compressor 2A | Percent | Read | ||
| AI | 91 | Line 3 Current (%RLA)- Compressor 2A | Percent | Read | ||
| AI | 92 | Line 1 Current (%RLA)- Compressor 2B | Percent | Read | ||
| AI | 93 | Line 2 Current (%RLA)- Compressor 2B | Percent | Read | ||
| AI | 94 | Line 3 Current (%RLA)- Compressor 2B | Percent | Read | ||
| AI | 95 | Number of Circuits | Read | |||
| AI | 96 | Number of Compressors, Ckt 1 | Read | |||
| AI | 97 | Number of Compressors, Ckt 2 | Read | |||
| AI | 98 | Chiller Design Capacity | Design Capacity of the Chiller | Read | ||
| AOmin | 1 | Chilled Water Setpoint | Desired leaving water temperature if chiller is in cooling mode | Temperature | Write | |
| AOmin | 2 | Current Limit Setpoint | Sets the maximum capacity that the chiller can use | Percent | Write | |
| BI | 1 | Run Enabled | The chiller is available to run or is currently running | Read | Inactive = Stop, Active = Auto | |
| BImin | 2 | Local Setpoint Control | The chiller is being controlled by local setpoints instead of BAS setpoints | Read | Inactive = Remote Control, Active = Local Control | |
| BI | 3 | Capacity Limited | Conditions may exist that prevent the chiller from reaching setpoint | Read | Inactive = Not Limited, Active = Limited | |
| BImin | 4 | Chiller Running State | The chiller is running or stopped | Read | Inactive = Off, Active = On | |
| BI | 6 | Maximum Capacity | All available chiller capacity is being used | Read | Inactive = Off, Active = On | |
| BI | 9 | Compressor 1A Running | Compressor 1A is running | Read | Inactive = Off, Active = Running | |
| BI | 10 | Compressor 1B Running | Compressor 1B is running | Read | Inactive = Off, Active = Running | |
| BI | 11 | Compressor 2A Running | Compressor 2A is running | Read | Inactive = Off, Active = Running | |
| BI | 12 | Compressor 2B Running | Compressor 2B is running | Read | Inactive = Off, Active = Running | |
| BI | 17 | Evaporator Water Pump Request | Request from the chiller to turn on the evaporator water pump | Read | Inactive = Off, Active = On | |
| BI | 22 | Evaporator Water Flow Status | Water is flowing through the evaporator | Read | Inactive = No Flow, Active = Flow | |
| BImin | 23 | Alarm Present | An alarm is active | Read | Inactive = No Alarm, Active = Alarm | |
| BI | 24 | Shutdown Alarm Present | A shutdown alarm is active | Read | Inactive = No Alarm, Active = None | |
| BI | 25 | Last Diagnostic | Last diagnostic for the chiller | Read | Inactive = Off, Active = On | |
| BOmin | 1 | Chiller Auto Stop Command | Allows the chiller to run if conditions for running are met | Write | Inactive = Stop, Active = Auto | |
| BO | 2 | Remote Diagnostic Reset Command | Resets remotely diagnostics that can be reset | Write | Inactive = No Reset Request, Active = Reset Request | |
| MI | 1 | Running Mode | Primary running mode of the chiller | Read | 1 = Chiller Off, 2 = Chiller in Start Mode, 3 = Chiller in Run Mode, 4 = Chiller in Pre-shutdown Mode, 5 = Chiller in Service Mode | |
| MI | 2 | Operating Mode | Primary operating mode of the chiller | Read | 1 = HVAC_Cool, 2 = HVAC_Heat, 3 = HVAC_Ice (a), 4 = Not Used | |
| MI | 3 | MP Communication Status | Do Not Use This Point | Read | ||
| MI | 4 | Refrigerant Type | Read | 1 = R-11, 2 = R-12, 3 = R-22, 4 = R-123, 5 = R-134A, 6 = R407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A | ||
| MI | 5 | Model Information | Model type of the chiller | Read | 1 = RTA, 2 = CVH, 3 = CVG, 4 = CVR, 5 = CDH, 6 = RTH, 7 = CGW, 8 = CGA, 9 = CCA, 10 = RTW, 11 = RTX, 12 = RTU, 13 = CCU, 14 = CXA, 15 = CGC, 16 = RAU | |
| MI | 6 | Cooling Type | Cooling type of the condenser | Read | 1 = Water Cooled, 2 = Air Cooled | |
| MI | 7 | Manufacturing Location | Location where chiller was manufactured | Read | 1 = Field Applied, 2 = La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey | |
| MOmin | 1 | Chiller Mode Command | Mode of operation of the chiller | Write | 1 = HVAC_Cool, 2 = HVAC_Heat, 3 = HVAC_Ice (a), 4 = Not Used |
No points match these filters.
Object ID lookup: Trane Symbio 800 RTAC (CH530) point IDs by name
AI1Active Cool/Heat Setpoint TemperatureAI2Active Current Limit SetpointAI5Actual Running CapacityAI6Evaporator Refrigerant Pressure- Ckt1AI9Evaporator Refrigerant Pressure- Ckt 2AI12Evaporator Saturated Refrigerant Temperature- Ckt 1AI14Evaporator Saturated Refrigerant Temperature- Ckt 2AI16Condenser Refrigerant Pressure- Ckt 1AI18Condenser Refrigerant Pressure- Ckt 2AI20Condenser Saturated Refrigerant Temperature- Ckt 1AI22Condenser Saturated Refrigerant Temperature- Ckt 2AI25Local Atmospheric PressureAI26Starts- Compressor 1AAI27Starts- Compressor 1BAI28Starts- Compressor 2AAI29Starts- Compressor 2BAI34Run Time- Compressor 1AAI35Run Time- Compressor 1BAI36Run Time- Compressor 2AAI42Airflow Percentage- Circuit 1AI43Airflow Percentage- Circuit 2AI44Evaporator Entering Water TempAI45Evaporator Leaving Water TempAI48High Side Oil Pressure- Compressor 1AAI49High Side Oil Pressure- Compressor 1BAI50High Side Oil Pressure- Compressor 2AAI51High Side Oil Pressure- Compressor 2BAI52Oil Temp- Compressor 1AAI54Oil Temp- Compressor 2AAI55Oil Temp- Compressor 2BAI57Outdoor Air TemperatureAI59Phase AB Voltage- Compressor 1AAI71Line 1 Current (in Amps)- Compressor 1AAI72Line 2 Current (in Amps)- Compressor 1AAI73Line 3 Current (in Amps)- Compressor 1AAI74Line 1 Current (in Amps)- Compressor 1BAI75Line 2 Current (in Amps)- Compressor 1BAI76Line 3 Current (in Amps)- Compressor 1BAI77Line 1 Current (in Amps)- Compressor 2AAI78Line 2 Current (in Amps)- Compressor 2AAI79Line 3 Current (in Amps)- Compressor 2AAI80Line 1 Current (in Amps)- Compressor 2BAI81Line 2 Current (in Amps)- Compressor 2BAI82Line 3 Current (in Amps)- Compressor 2BAI83Line 1 Current (%RLA)- Compressor 1AAI84Line 2 Current (%RLA)- Compressor 1AAI85Line 3 Current (%RLA)- Compressor 1AAI86Line 1 Current (%RLA)- Compressor 1BAI87Line 2 Current (%RLA)- Compressor 1BAI88Line 3 Current (%RLA)- Compressor 1BAI89Line 1 Current (%RLA)- Compressor 2AAI90Line 2 Current (%RLA)- Compressor 2AAI91Line 3 Current (%RLA)- Compressor 2AAI92Line 1 Current (%RLA)- Compressor 2BAI93Line 2 Current (%RLA)- Compressor 2BAI94Line 3 Current (%RLA)- Compressor 2BAI95Number of CircuitsAI96Number of Compressors, Ckt 1AI97Number of Compressors, Ckt 2AI98Chiller Design CapacityAO1Chilled Water SetpointAO2Current Limit SetpointBI1Run EnabledBI2Local Setpoint ControlBI3Capacity LimitedBI4Chiller Running StateBI6Maximum CapacityBI9Compressor 1A RunningBI10Compressor 1B RunningBI11Compressor 2A RunningBI12Compressor 2B RunningBI17Evaporator Water Pump RequestBI22Evaporator Water Flow StatusBI23Alarm PresentBI24Shutdown Alarm PresentBI25Last DiagnosticBO1Chiller Auto Stop CommandBO2Remote Diagnostic Reset CommandMI1Running ModeMI2Operating ModeMI3MP Communication StatusMI4Refrigerant TypeMI5Model InformationMI6Cooling TypeMI7Manufacturing LocationMO1Chiller Mode Command
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The tables have no read/write column: AI/BI/MI are read-only, and the AO/BO/MO objects (listed with a relinquish default) are the BAS setpoints and commands, marked writable here.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the actual engineering unit is the factory-configured I-P or SI set.
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- Trane titles this list 'RTAC (CH530)' and does not explain the suffix in the document. Its objects use short instance numbers (AI 1, BI 4...) instead of the 5-digit numbering in the standard Symbio 800 RTAC list (BAS-PTS023), so check which list matches the controller on site.
- AI 52 is printed twice in the source (Oil Temp- Compressor 1A and Oil Temp- Compressor 1B); only the first is listed here. The RTAC (UC800) list numbers Oil Temp - Compressor 1B as AI 53, so the second entry is probably a misprint for AI 53.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 RTAC (CH530) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 RTAC (CH530)
How many BACnet points does the Trane Symbio 800 RTAC (CH530) have?
This list has 86 BACnet objects: 60 analog inputs, 2 analog outputs, 14 binary inputs, 2 binary outputs, 7 multi-state inputs, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 RTAC (CH530) BACnet points are writable?
5 of the 86 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 RTAC (CH530) BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - RTAC (CH530) (BAS-PTS031A-EN), revision 12/6/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS031A-EN_12062024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 RTAC (CH530)?
Start with BO 1 Chiller Auto Stop Command (BMS auto/stop (enable) command); MO 1 Chiller Mode Command (Cool/heat/ice mode command); AO 1 Chilled Water Setpoint (Chilled water setpoint from the BMS); AO 2 Current Limit Setpoint (Current (capacity) limit from the BMS, %); BI 4 Chiller Running State (Chiller on/off status); BI 2 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 45 Evaporator Leaving Water Temp (Leaving chilled water temperature); AI 5 Actual Running Capacity (Actual running capacity in percent); BI 23 Alarm Present (Any active alarm on the chiller).
How do I enable BMS control of the Trane Symbio 800 RTAC (CH530)?
BO 1 Chiller Auto Stop Command (Inactive = Stop, Active = Auto) is the BMS auto/stop; its relinquish default is True (Auto). BI 1 Run Enabled shows whether the chiller is available to run. The document doesn't say how to hand setpoint control to the BAS; BI 2 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints.
How do I check these points on the real Symbio 800 RTAC (CH530)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACS / ACX
Trane Ascend model ACS and ACX air-cooled scroll chillers with Symbio 800 controls.
Also known as: Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet - RTAC (CH530) · BAS-PTS031A-EN · rev. 12/6/2024. Object names, instances and units are reproduced as published; descriptions are our own.