Trane Symbio 800 Ascend ACS / ACX BACnet points list
Updated 28 October 2026
Ascend ACS/ACX chillers expose about 400 BACnet objects through the Symbio 800. Status values are AI/BI/MI, and the BAS writes a small set of AV/BV/MV objects for chilled and hot water setpoints, demand limit, mode, circuit lockouts and auto/stop. Most binary inputs are individual diagnostic flags.
This page lists 397 BACnet objects for the Trane Symbio 800 Ascend ACS / ACX — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Trane’s own free documentation, linked below.
- Manufacturer
- Trane
- Model
- Symbio 800 Ascend ACS / ACX
- Equipment
- Air-cooled chiller controller
- Equipment type
- Chillers
- BACnet objects
- 397 (16 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Symbio 800 Ascend, BAS-PTS011
Reference only, provided as-is: verify against Trane’s current documentation and the live device before use. Not official Trane information. Terms of use.
BMS integration notes: Trane Symbio 800 Ascend ACS / ACX
Put the chiller on the network (BACnet MS/TP or IP), then write the auto/stop command, chilled water setpoint, demand limit and mode. Read back running state, leaving water temperature and capacity. Check the local-setpoint flag to confirm the BAS setpoints are actually in use. Most remaining objects are read-only status and per-alarm diagnostic flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10107 | BAS Chiller Auto Stop Command | BMS auto/stop (enable) command | Write |
| MV 10100 | Chiller Mode Command BAS | Cool/heat/ice/free-cooling mode command | Write |
| AV 10100 | Chilled Water Setpoint | Chilled water setpoint from the BMS | Write |
| AV 10101 | Demand Limit Setpoint | Capacity (demand) limit from the BMS | Write |
| BI 10110 | Chiller Running State | Chiller on/off status | Read |
| BI 10104 | Local Setpoint Control | Shows if local setpoints override BAS setpoints | Read |
| AI 10101 | Evaporator Leaving Water Temperature | Leaving chilled water temperature | Read |
| AI 10116 | Actual Running Capacity | Actual running capacity in percent | Read |
| BI 10126 | Diagnostic Present | Any active diagnostic (alarm) on the chiller | Read |
Enable & remote start
BV 10107 BAS Chiller Auto Stop Command (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10130 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
Network setup
- With no protocol specified at order, the controller ships as BACnet MS/TP at 76,800 bps with the rotary address at 000, and MS/TP is disabled at 000. Set a rotary address of 001-127 to bring it online.
- The rotary address sets the MS/TP MAC and the Device ID and takes effect without a power cycle. A software Device ID (1-4194302) can be set in the web UI, Tracer SC+ or Tracer TU.
- The web UI is reached only over USB at http://198.80.18.1/; the Ethernet ports do not serve it.
- BACnet IP uses Ethernet port 1 (or the optional USB Wi-Fi adapter); the default UDP port is 47808. Enable BBMD only if this is the only BACnet IP device on the subnet, then fill in the BDT.
- MS/TP wiring lands on the P1 link; P2 and P3 are for factory devices only, and Ethernet port 2 is only for the touch-screen display.
Watch out for
- Communicated units (I-P or SI) are fixed at the factory; changing them in the field needs a Trane representative. Web UI display units do not change the BACnet values.
- Points that don't apply to the unit's configuration are absent, and a technician can 'recycle' (remove) factory points from the interface, so a missing object may have been recycled.
- The chiller lists have no read/write column; writability of the AV/BV/MV objects is inferred from Trane's naming convention.
- Diagnostic BIs are one object per alarm condition and only exist for the options fitted.
Trane Symbio 800 Ascend ACS / ACX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 10100 | Active Cool/Heat Setpoint Temperature | Temperature | Read | ||
| AImin | 10101 | Evaporator Leaving Water Temperature | Temperature | Read | ||
| AI | 10102 | Evaporator Entering Water Temperature | Temperature | Read | ||
| AI | 10103 | Active Demand Limit Setpoint | Percentage | Read | ||
| AI | 10104 | Unit Power Consumption | Power, Electrical | Read | ||
| AI | 10105 | Outdoor Air Temperature | Temperature | Read | ||
| AI | 10106 | Evaporator Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10107 | Condenser Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10108 | Differential Refrigerant Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10109 | Evaporator Saturated Rfgt Temp Circuit 1 | Temperature | Read | ||
| AI | 10110 | Condenser Saturated Rfgt Temp Circuit 1 | Temperature | Read | ||
| AI | 10111 | Evaporator Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10112 | Condenser Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10113 | Differential Refrigerant Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10114 | Evaporator Saturated Rfgt Temp Circuit 2 | Temperature | Read | ||
| AI | 10115 | Condenser Saturated Rfgt Temp Circuit 2 | Temperature | Read | ||
| AImin | 10116 | Actual Running Capacity | Percentage | Read | ||
| AI | 10117 | Active Heat Recovery Setpoint | Temperature | Read | ||
| AI | 10118 | Active Hot Water Setpoint | Temperature | Read | ||
| AI | 10119 | Air Flow Circuit 1 | Percentage | Read | ||
| AI | 10120 | Air Flow Circuit 2 | Percentage | Read | ||
| AI | 10121 | Starts Cprsr1A | Read | |||
| AI | 10122 | Running Time Cprsr1A | Read | |||
| AI | 10123 | Starts Cprsr2A | Read | |||
| AI | 10124 | Running Time Cprsr2A | Read | |||
| AI | 10125 | Heat Recovery Entering Water Temp | Temperature | Read | ||
| AI | 10126 | Heat Recovery Leaving Water Temp | Temperature | Read | ||
| AI | 10127 | Chiller Design Capacity | Power, Cooling | Read | ||
| AI | 10128 | Starts Cprsr1B | Read | |||
| AI | 10129 | Running Time Cprsr1B | Read | |||
| AI | 10130 | Starts Cprsr2B | Read | |||
| AI | 10131 | Running Time Cprsr2B | Read | |||
| AI | 10132 | Number Of Circuits | Read | |||
| AI | 10133 | Number of Compressors for Circuit 1 | Read | |||
| AI | 10134 | Number of Compressors for Circuit 2 | Read | |||
| AI | 10135 | Free Cooling Capacity | Percentage | Read | ||
| AI | 10136 | Free Cooling Entering Water Temperature | Temperature | Read | ||
| AI | 10137 | Free Cooling Entering Glycol Temperature | Temperature | Read | ||
| AI | 10138 | Free Cooling Leaving Glycol Temperature | Temperature | Read | ||
| AI | 10139 | Energy Consumption NonReset | Power, Electrical | Read | ||
| AI | 10140 | Energy Consumption Resettable | Power, Electrical | Read | ||
| AI | 10141 | Starts Cprsr1C | Read | |||
| AI | 10142 | Running Time Cprsr1C | Read | |||
| AI | 10143 | Starts Cprsr2C | Read | |||
| AI | 10144 | Running Time Cprsr2C | Read | |||
| AI | 10145 | Estimated Discharge Temperature Circuit 1 | Temperature | Read | ||
| AI | 10146 | Estimated Discharge Temperature Circuit 2 | Temperature | Read | ||
| AI | 10147 | Compressor Discharge Temperature Circuit 1 | Temperature | Read | ||
| AI | 10148 | Compressor Discharge Temperature Circuit 2 | Temperature | Read | ||
| AI | 10149 | Free Cooling Glycol Pressure | Pressure, Fluidic | Read | ||
| AI | 10150 | Last Logged Diagnostic | Read | |||
| AI | 10151 | Unit Load Command | Percentage | Read | ||
| AI | 10152 | Average Line Current | Current | Read | ||
| AI | 10153 | Average Line Voltage | Voltage | Read | ||
| AI | 10154 | Current L1 | Current | Read | ||
| AI | 10155 | Current L2 | Current | Read | ||
| AI | 10156 | Current L3 | Current | Read | ||
| AI | 10157 | Voltage L1-L2 | Voltage | Read | ||
| AI | 10158 | Voltage L2-L3 | Voltage | Read | ||
| AI | 10159 | Voltage L1-L3 | Voltage | Read | ||
| AI | 10160 | Total Real Power | Power, Electrical | Read | ||
| AI | 10161 | Line Frequency | Read | |||
| AI | 10162 | Power Factor | Read | |||
| AI | 10163 | Heat Recovery Valve Position | Percentage | Read | ||
| AI | 10164 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10165 | Condenser Refrigerant Absolute Pressure Circuit 1 | Pressure, Fluidic | Read | ||
| AI | 10166 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10167 | Condenser Refrigerant Absolute Pressure Circuit 2 | Pressure, Fluidic | Read | ||
| AI | 10168 | Free Cooling Glycol Absolute Pressure | Pressure, Fluidic | Read | ||
| AI | 10169 | Supplemental Heater Status | Percentage | Read | ||
| AI | 10170 | Evaporator Approach Temperature Circuit 1 (Cooling Mode Only) | Temperature | Read | ||
| AI | 10171 | Evaporator Approach Temperature Circuit 2 (Cooling Mode Only) | Temperature | Read | ||
| AI | 10172 | Condenser Approach Temperature Circuit 1 (Heating Mode Only) | Temperature | Read | ||
| AI | 10173 | Condenser Approach Temperature Circuit 2 (Heating Mode Only) | Temperature | Read | ||
| AI | 10174 | Active Chilled Water Setpoint | Temperature | Read | ||
| AI | 10175 | Chilled Water Setpoint Status | Temperature | Read | ||
| AI | 10176 | Hot Water Setpoint Status | Temperature | Read | ||
| AI | 10177 | Demand Limit Setpoint Status | Percentage | Read | ||
| AI | 10178 | Active Demand Limit Setpoint | Percentage | Read | ||
| AVmin | 10100 | Chilled Water Setpoint | Temperature | Write | ||
| AVmin | 10101 | Demand Limit Setpoint | Percentage | Write | ||
| AV | 10102 | BAS Hot Water Setpoint | Temperature | Write | ||
| AV | 10103 | BAS Heat Recovery Setpoint | Temperature | Write | ||
| AV | 10104 | Evaporator Water Pump Speed Setpoint | Percentage | Write | ||
| BI | 10100 | Limit Mode Relay Status | Read | 0 = Auto, 1 = On | ||
| BI | 10101 | Emergency Stop | Read | 0 = Auto, 1 = Emergency Stop - Manual Reset Required | ||
| BI | 10102 | Manual Override Exists | Read | 0 = Off, 1 = On | ||
| BI | 10103 | Run Enable | Read | 0 = Run Not Enabled, 1 = Run Enabled | ||
| BImin | 10104 | Local Setpoint Control | Read | 0 = Remote control, 1 = Local control | ||
| BI | 10105 | Maximum Capacity Relay | Read | 0 = Off, 1 = On | ||
| BI | 10106 | Running Status Cprsr1A | Read | 0 = Off, 1 = Running | ||
| BI | 10107 | Running Status Cprsr2A | Read | 0 = Off, 1 = Running | ||
| BI | 10108 | Running Status Cprsr1B | Read | 0 = Off, 1 = Running | ||
| BI | 10109 | Running Status Cprsr2B | Read | 0 = Off, 1 = Running | ||
| BImin | 10110 | Chiller Running State | Read | 0 = Off, 1 = On | ||
| BI | 10111 | Running Status Cprsr1C | Read | 0 = Off, 1 = Running | ||
| BI | 10112 | Running Status Cprsr2C | Read | 0 = Off, 1 = Running | ||
| BI | 10113 | Free Cooling Active | Read | 0 = Inactive, 1 = Active | ||
| BI | 10114 | Heat Recovery Active | Read | 0 = Inactive, 1 = Active | ||
| BI | 10115 | Front Panel Auto/Stop | Read | 0 = Stop, 1 = Auto | ||
| BI | 10116 | Circuit Manual Reset Indicator (CMR) Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10117 | Circuit Manual Reset Indicator (CMR) Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10118 | Circuit Auto Reset Indicator (CAR) Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10119 | Circuit Auto Reset Indicator (CAR) Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10120 | Evaporator Water Pump Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10121 | Evaporator Water Flow Status | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10122 | Diagnostic Present: Information | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10123 | Diagnostic Present: Advisory | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10124 | Diagnostic Present: Critical | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10125 | Diagnostic Present: Service Required | Read | 0 = Normal, 1 = In Alarm | ||
| BImin | 10126 | Diagnostic Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10127 | Diagnostic Shutdown Present | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10128 | Diagnostic: Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10129 | Diagnostic: Local Manual Reset Required | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 10130 | External Auto Stop | Read | 0 = Stop, 1 = Auto | ||
| BI | 10131 | Noise Reduction Request Active | Read | 0 = Off, 1 = On | ||
| BI | 10132 | Heat Recovery Request Active | Read | 0 = Off, 1 = On | ||
| BI | 10133 | Evaporator Water Pump Status | Read | 0 = Off, 1 = On | ||
| BI | 10134 | Circuit 1 Defrost Delay Status | Read | 0 = Off, 1 = On | ||
| BI | 10135 | Circuit 2 Defrost Delay Status | Read | 0 = Off, 1 = On | ||
| BI | 10136 | In Defrost | Read | 0 = Not in Defrost, 1 = Defrost | ||
| BI | 10137 | Circuit 1 Defrost Status | Read | 0 = Inactive, 1 = Active | ||
| BI | 10138 | Circuit 2 Defrost Status | Read | 0 = Inactive, 1 = Active | ||
| BI | 10139 | Circuit 1 Running Status | Read | 0 = Off, 1 = On | ||
| BI | 10140 | Circuit 2 Running Status | Read | 0 = Off, 1 = On | ||
| BI | 10141 | Low Ambient Lockout Status | Read | 0 = No Lockout, 1 = Lockout Present | ||
| BI | 10142 | Circuit 1 Lockout Front Panel | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10143 | Circuit 2 Lockout Front Panel | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10144 | Circuit 1 Lockout External | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10145 | Circuit 2 Lockout External | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10146 | Circuit 1 Lockout Active | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 10147 | Circuit 2 Lockout Active | Read | 0 = Normal, 1 = Locked Out | ||
| BI | 11000 | Comm Loss: Percent Capacity Output | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11001 | Comm Loss: Supplemental Heater Relay 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11002 | Comm Loss: Supplemental Heater Relay 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11003 | Comm Loss: Supplemental Heater Relay 3 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11004 | Comm Loss: Supplemental Heater Relay 4 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11005 | Comm Loss: Energy Meter | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11006 | Comm Loss: Outdoor Air Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11007 | Comm Loss: Phase Protection Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11008 | Diagnostic: Energy Meter Write Command Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11009 | Diagnostic: Outdoor Air Temperature Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11010 | Diagnostic: Phase Protection Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11011 | Diagnostic: Software Error 1003: Call Trane Service | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11012 | Diagnostic: Pumpdown Terminated By Time - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11013 | Diagnostic: Pumpdown Terminated By Time - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11014 | Comm Loss: Discharge Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11015 | Comm Loss: Discharge Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11016 | Comm Loss: Discharge Temperature Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11017 | Comm Loss: Discharge Temperature Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11018 | Comm Loss: External Circuit 2 Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11019 | Comm Loss: External Circuit 1 Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11020 | Comm Loss: Reversing Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11021 | Comm Loss: Reversing Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11022 | Comm Loss: Suction Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11023 | Comm Loss: Suction Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11024 | Comm Loss: Suction Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11025 | Comm Loss: Suction Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11026 | Diagnostic: Discharge Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11027 | Diagnostic: Discharge Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11028 | Diagnostic: Discharge Temperature Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11029 | Diagnostic: Discharge Temperature Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11030 | Diagnostic: Suction Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11031 | Diagnostic: Suction Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11032 | Diagnostic: Suction Temperature Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11033 | Diagnostic: Suction Temperature Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11034 | Comm Loss: Sump Heater - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11035 | Comm Loss: Sump Heater - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11036 | Diagnostic: High Compressor Pressure Differential - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11037 | Diagnostic: High Compressor Pressure Differential - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11038 | Diagnostic: High Discharge Refrigerant Pressure - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11039 | Diagnostic: High Discharge Refrigerant Pressure - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11040 | Diagnostic: High Discharge Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11041 | Diagnostic: High Discharge Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11042 | Diagnostic: High Discharge Temperature Lockout - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11043 | Diagnostic: High Discharge Temperature Lockout - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11044 | Diagnostic: Loss of Charge - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11045 | Diagnostic: Loss of Charge - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11046 | Diagnostic: Low Discharge Saturated Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11047 | Diagnostic: Low Discharge Saturated Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11048 | Diagnostic: Low Refrigerant Pressure Ratio - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11049 | Diagnostic: Low Refrigerant Pressure Ratio - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11050 | Diagnostic: Low Refrigerant Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11051 | Diagnostic: Low Refrigerant Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11052 | Diagnostic: Low Suction Refrigerant Pressure - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11053 | Diagnostic: Low Suction Refrigerant Pressure - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11054 | Diagnostic: Low Suction Superheat - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11055 | Diagnostic: Low Suction Superheat - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11056 | Diagnostic: Suction Temperature Too High - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11057 | Diagnostic: Suction Temperature Too High - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11058 | Diagnostic: Very Low Suction Pressure - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11059 | Diagnostic: Very Low Suction Pressure - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11060 | Comm Loss: Compressor 1C Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11061 | Comm Loss: Compressor 1B Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11062 | Comm Loss: Compressor 1A Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11063 | Diagnostic: Compressor 1A Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11064 | Diagnostic: Compressor 1B Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11065 | Diagnostic: Compressor 1C Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11066 | Diagnostic: Compressor 1C Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11067 | Diagnostic: Compressor 1B Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11068 | Diagnostic: Compressor 1A Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11069 | Diagnostic: Starts/Hours Modified 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11070 | Diagnostic: Starts/Hours Modified 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11071 | Diagnostic: Starts/Hours Modified 1C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11072 | Comm Loss: Compressor 2C Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11073 | Comm Loss: Compressor 2B Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11074 | Comm Loss: Compressor 2A Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11075 | Diagnostic: Compressor 2A Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11076 | Diagnostic: Compressor 2B Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11077 | Diagnostic: Compressor 2C Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11078 | Diagnostic: Compressor 2C Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11079 | Diagnostic: Compressor 2B Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11080 | Diagnostic: Compressor 2A Fault Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11081 | Diagnostic: Starts/Hours Modified 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11082 | Diagnostic: Starts/Hours Modified 2C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11083 | Diagnostic: Starts/Hours Modified 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11084 | Comm Loss: High Pressure Cutout Switch - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11085 | Comm Loss: High Pressure Cutout Switch - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11086 | Diagnostic: High Pressure Cutout - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11087 | Diagnostic: High Pressure Cutout - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11088 | Comm Loss: Shared V Coil Isolating Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11089 | Comm Loss: Shared V Coil Isolating Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11090 | Comm Loss: Dynamic Receiver Fill Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11091 | Comm Loss: Dynamic Receiver Fill Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11092 | Comm Loss: Hot Gas Bypass Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11093 | Comm Loss: Hot Gas Bypass Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11094 | Comm Loss: Liquid Line Pressure - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11095 | Comm Loss: Liquid Line Pressure - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11096 | Comm Loss: Liquid Line Temperature - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11097 | Comm Loss: Liquid Line Temperature - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11098 | Diagnostic: Liquid Line Pressure Transducer - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11099 | Diagnostic: Liquid Line Pressure Transducer - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11100 | Diagnostic: Liquid Line Temperature Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11101 | Diagnostic: Liquid Line Temperature Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11102 | Comm Loss:Evaporator Antifreeze Heater | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11103 | Comm Loss:Heat Recovery Antifreeze Heater | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11104 | Diagnostic: Evaporator Water Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11105 | Diagnostic: Evaporator Water Flow Lost Lockout | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11106 | Diagnostic: Evaporator Water Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11107 | Diagnostic: High Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11108 | Diagnostic: High Suction Rfgt Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11109 | Diagnostic: Inverted Evaporator Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11110 | Diagnostic: Inverted Water Temp (Heating) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11111 | Diagnostic: Low Evaporator Water Temp (Unit On) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11112 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11113 | Comm Loss: Evap Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11114 | Comm Loss: Evap Leaving Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11115 | Comm Loss: Evaporator Water Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11116 | Diagnostic: Evaporator Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11117 | Diagnostic: Evaporator Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11118 | Comm Loss: Cooling EXV - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11119 | Comm Loss: Cooling EXV - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11120 | Comm Loss: Electronic Expansion Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11121 | Comm Loss: Electronic Expansion Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11122 | Comm Loss: Heating EXV - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11123 | Comm Loss: Heating EXV - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11124 | Comm Loss: Auxiliary Setpoint Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11125 | Comm Loss: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11126 | Comm Loss: Ext Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11127 | Comm Loss: Ext Noise Reduction Request | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11128 | Comm Loss: External Auto/Stop | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11129 | Comm Loss: Ext Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11130 | Comm Loss: External Hot Water Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11131 | Comm Loss: Programmable Relay Board 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11132 | Comm Loss: Programmable Relay Board 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11133 | Diagnostic: Emergency Stop Feedback Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11134 | Diagnostic: External Chilled/Hot Water Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11135 | Diagnostic: External Demand Limit Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11136 | Comm Loss: Condenser Fan Enable - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11137 | Comm Loss: Condenser Fan Enable - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11138 | Comm Loss: Cond Fan Enbl Shared Ckt 1&2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11139 | Comm Loss: Condenser Fan Fault - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11140 | Comm Loss: Condenser Fan Fault - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11141 | Comm Loss: Fan Board 1 Relay 1 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11142 | Comm Loss: Fan Board 1 Relay 1 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11143 | Comm Loss: Fan Board 1 Relay 2 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11144 | Comm Loss: Fan Board 1 Relay 2 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11145 | Comm Loss: Fan Board 1 Relay 3 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11146 | Comm Loss: Fan Board 1 Relay 3 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11147 | Comm Loss: Fan Board 1 Relay 4 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11148 | Comm Loss: Fan Board 1 Relay 4 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11149 | Comm Loss: Fan Board 2 Relay 1 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11150 | Comm Loss: Fan Board 2 Relay 1 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11151 | Comm Loss: Fan Board 2 Relay 2 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11152 | Comm Loss: Fan Board 2 Relay 2 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11153 | Comm Loss: Fan Board 2 Relay 3 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11154 | Comm Loss: Fan Board 2 Relay 3 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11155 | Comm Loss: Fan Board 2 Relay 4 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11156 | Comm Loss: Fan Board 2 Relay 4 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11157 | Comm Loss: Fan Inverter Speed Command - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11158 | Comm Loss: Fan Inverter Speed Command - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11159 | Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1&2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11160 | Comm Loss: Fan Speed Select Board Relay 1 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11161 | Comm Loss: Fan Speed Select Board Relay 2 - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11162 | Comm Loss: Fan Speed Select Board Relay 3 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11163 | Comm Loss: Fan Speed Select Board Relay 4 - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11164 | Diagnostic: Condenser Fan Fault - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11165 | Diagnostic: Condenser Fan Fault - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11166 | Comm Loss: FC Entering Glycol Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11167 | Comm Loss: FC Entering Water Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11168 | Comm Loss: FC Leaving Glycol Temp | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11169 | Comm Loss: Free Cooling Glycol Flow Switch | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11170 | Comm Loss: Free Cooling Glycol Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11171 | Comm Loss: Free Cooling Glycol Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11172 | Comm Loss: Free Cooling Pump | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11173 | Comm Loss: Free Cooling Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11174 | Diagnostic: Free Cooling Entering Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11175 | Diagnostic: Free Cooling Entering Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11176 | Diagnostic: Free Cooling Glycol Flow Lost | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11177 | Diagnostic: Free Cooling Glycol Flow Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11178 | Diagnostic: Free Cooling Glycol Pressure | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11179 | Diagnostic: Free Cooling Glycol Temperature Equalization Overdue | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11180 | Diagnostic: Free Cooling Leaving Glycol Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11181 | Diagnostic: Free Cooling Glycol Pump Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11182 | Diagnostic: Low Glycol Pressure Free Cooling | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11183 | Diagnostic: Low Glycol Temp Free Cooling | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11184 | Comm Loss: External Heat Recovery Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11185 | Comm Loss: External Heat Recovery Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11186 | Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11187 | Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11188 | Comm Loss: HR Entering Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11189 | Comm Loss: HR Leaving Water Temperature | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11190 | Comm Loss: Heat Recovery Three Way Valve | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11191 | Diagnostic: External Heat Recovery Setpoint | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11192 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11193 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11194 | Diagnostic: No Heat Recovery | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11195 | Comm Loss: External Ice Building Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11196 | Diagnostic: Restart Inhibit Invoked - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11197 | Diagnostic: Restart Inhibit Invoked - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11198 | Diagnostic: Restart Inhibit Invoked - 1C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11199 | Diagnostic: Restart Inhibit Invoked - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11200 | Diagnostic: Restart Inhibit Invoked - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11201 | Diagnostic: Restart Inhibit Invoked - 2C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11202 | Comm Loss: Energy Meter Pulse Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11203 | Comm Loss: Run Command Compressor 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11204 | Comm Loss: Run Command Compressor 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11205 | Comm Loss: Run Command Compressor 1C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11206 | Comm Loss: Run Command Compressor 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11207 | Comm Loss: Run Command Compressor 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11208 | Comm Loss: Run Command Compressor 2C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11209 | Diagnostic: MP: Invalid Configuration | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11210 | Diagnostic: MP: Reset Has Occurred | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11211 | Comm Loss: Evap Pump Inv1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11212 | Comm Loss: Evap Pump Inv1 Freq Feedback | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11213 | Comm Loss: Evap Pump Inv1 Run Command | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11214 | Comm Loss: Evaporator Pump 2 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11215 | Comm Loss: Evaporator Water Pump 1 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11216 | Comm Loss: Evaporator Water Pump 2 Relay | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11217 | Comm Loss: Evaporator Pump 1 Fault Input | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11218 | Diagnostic: Evap Pump 1 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11219 | Diagnostic: Evap Pump 2 Starts Run time Written | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11220 | Diagnostic: Evaporator Pump 1 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11221 | Diagnostic: Evaporator Pump 2 Fault | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11222 | Diagnostic: Evaporator Water Flow Lost - Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11223 | Diagnostic: Evaporator Water Flow Lost - Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11224 | Diagnostic: Evaporator Water Flow Overdue - Pump1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11225 | Diagnostic: Evaporator Water Flow Overdue - Pump2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11226 | Comm Loss: SLHX Entering Refrigerant Temp - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11227 | Comm Loss: SLHX Entering Refrigerant Temp - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11228 | Comm Loss: SLHX Valve - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11229 | Comm Loss: SLHX Valve - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11230 | Diagnostic: SLHX Entering Temp Sensor - Circuit 1 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11231 | Diagnostic: SLHX Entering Temp Sensor - Circuit 2 | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11232 | Diagnostic: Chiller Service Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11233 | Diagnostic: Evap Water Pump 1 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11234 | Diagnostic: Evap Water Pump 2 Svc Recommended | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11235 | Diagnostic: Mfr Maintenance Recommended - 1A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11236 | Diagnostic: Mfr Maintenance Recommended - 1B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11237 | Diagnostic: Mfr Maintenance Recommended - 1C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11238 | Diagnostic: Mfr Maintenance Recommended - 2A | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11239 | Diagnostic: Mfr Maintenance Recommended - 2B | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11240 | Diagnostic: Mfr Maintenance Recommended - 2C | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11241 | Diagnostic: Evaporator Water Flow Too Low | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11242 | Comm Loss: Evap Water Pump Inverter Speed | Read | 0 = Normal, 1 = In Alarm | ||
| BI | 11243 | Energy Meter Write Value Failure | Read | 0 = Normal, 1 = In Alarm | ||
| BV | 10100 | Reset Diagnostic | Write | 0 = Normal, 1 = Reset | ||
| BV | 10101 | BAS Noise Reduction Request | Write | 0 = Normal, 1 = Reduce Noise | ||
| BV | 10102 | BAS Heat Recovery Command | Write | 0 = Off, 1 = On | ||
| BV | 10103 | Energy Consumption Reset | Write | 0 = Accumulating, 1 = Reset | ||
| BV | 10104 | BAS Circuit 1 Lockout | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10105 | BAS Circuit 2 Lockout | Write | 0 = Normal, 1 = Locked Out | ||
| BV | 10106 | BAS Free Cooling Auto Stop Command | Write | 0 = Stop, 1 = Auto | ||
| BVmin | 10107 | BAS Chiller Auto Stop Command | Write | 0 = Stop, 1 = Auto | ||
| BV | 10108 | Evaporator Water Pump Request BAS | Write | 0 = Auto, 1 = On | ||
| BV | 10109 | Defrost Delay Request BAS | Write | 0 = Off, 1 = On | ||
| MI | 10100 | Running Mode | Read | 1 = Chiller Off, 2 = Chiller In Start Mode, 3 = Chiller In Run Mode, 4 = Chiller In Pre-Shutdown Mode, 5 = Chiller In Service Mode | ||
| MI | 10101 | Operating Mode | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | ||
| MI | 10102 | Chiller Setpoint Source | Read | 1 = BAS, 2 = External, 3 = Front Panel | ||
| MI | 10103 | Refrigerant Type | Read | 1 = R-11, 2 = R-12, 3= R-22, 4= R-123, 5 = R-134a, 6 = R-407C, 7 = R-410A, 8 = R-113, 9 = R-114, 10 = R-500, 11 = R-502, 12 = R-404A, 13 = R-513A, 14 = R-1233zd(E), 15 = R-514A, 16 = R-1234z(E), 17 = R-454B, 18 = R-515B | ||
| MI | 10104 | Cooling Type | Read | 1 = Water Cooled, 2 = Air Cooled | ||
| MI | 10105 | Manufacture Location | Read | 1 = Field Applied, 2= La Crosse, 3 = Pueblo, 4 = Charmes, 5 = Rushville, 6 = Macon, 7 = Waco, 8 = Lexington, 9 = Forsyth, 10 = Clarksville, 11 = Ft. Smith, 12 = Penang, 13 = Colchester, 14 = Curitiba, 15 = Taicang, 16 = Taiwan, 17 = Epinal, 18 = Golbey | ||
| MI | 10107 | Front Panel Chiller Mode Command | Read | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling | ||
| MI | 10108 | Model Information [GEN2] | Read | 1 = CVHF, 2 = CVGF, 3= CVHS, 4= RTAE, 5 = RTAF, 6 = RTHA, 7 = RTHB, 8 = RTHC, 9 = RTHD, 10 = RTW, 11 = CTVD, 12 = CVR, 13 = CVHH, 14 = CDHH, 15 = VMAX, 16 = GVAF, 17 = RTWF, 18 = RTHF, 19 = RTAC, 20 = CVHM, 21 = RTAG, 22 = CGAF, 23 = RTXG, 24 = GVWF, 25 = HDWA, 26 = CMAC, 27 = IPAK, 28 = CXAF, 29 = ACSA, 30 = RTSF, 31 = HSWA, 32 = ACRA, 33 = RTEG, 34 = ACXA, 35 = CMAF, 36 = ACRB (375 to 550 tons), 37 = ACRB (150 to 300 tons) | ||
| MI | 10109 | Circuit 1 Status | Read | 1 = Available, 2 = Heat Recovery, 3 = Cooling, 4 = Heating, 5 = Defrost, 6 = Not Available | ||
| MI | 10110 | Circuit 2 Status | Read | 1 = Available, 2 = Heat Recovery, 3 = Cooling, 4 = Heating, 5 = Defrost, 6 = Not Available | ||
| MVmin | 10100 | Chiller Mode Command BAS | BAS Chiller Mode Command | Write | 1 = Cool, 2 = Heat, 3 = Ice Making, 4 = Free Cooling |
No points match these filters.
Object ID lookup: Trane Symbio 800 Ascend ACS / ACX point IDs by name
AI10100Active Cool/Heat Setpoint TemperatureAI10101Evaporator Leaving Water TemperatureAI10102Evaporator Entering Water TemperatureAI10103Active Demand Limit SetpointAI10104Unit Power ConsumptionAI10105Outdoor Air TemperatureAI10106Evaporator Refrigerant Pressure Circuit 1AI10107Condenser Refrigerant Pressure Circuit 1AI10108Differential Refrigerant Pressure Circuit 1AI10109Evaporator Saturated Rfgt Temp Circuit 1AI10110Condenser Saturated Rfgt Temp Circuit 1AI10111Evaporator Refrigerant Pressure Circuit 2AI10112Condenser Refrigerant Pressure Circuit 2AI10113Differential Refrigerant Pressure Circuit 2AI10114Evaporator Saturated Rfgt Temp Circuit 2AI10115Condenser Saturated Rfgt Temp Circuit 2AI10116Actual Running CapacityAI10117Active Heat Recovery SetpointAI10118Active Hot Water SetpointAI10119Air Flow Circuit 1AI10120Air Flow Circuit 2AI10121Starts Cprsr1AAI10122Running Time Cprsr1AAI10123Starts Cprsr2AAI10124Running Time Cprsr2AAI10125Heat Recovery Entering Water TempAI10126Heat Recovery Leaving Water TempAI10127Chiller Design CapacityAI10128Starts Cprsr1BAI10129Running Time Cprsr1BAI10130Starts Cprsr2BAI10131Running Time Cprsr2BAI10132Number Of CircuitsAI10133Number of Compressors for Circuit 1AI10134Number of Compressors for Circuit 2AI10135Free Cooling CapacityAI10136Free Cooling Entering Water TemperatureAI10137Free Cooling Entering Glycol TemperatureAI10138Free Cooling Leaving Glycol TemperatureAI10139Energy Consumption NonResetAI10140Energy Consumption ResettableAI10141Starts Cprsr1CAI10142Running Time Cprsr1CAI10143Starts Cprsr2CAI10144Running Time Cprsr2CAI10145Estimated Discharge Temperature Circuit 1AI10146Estimated Discharge Temperature Circuit 2AI10147Compressor Discharge Temperature Circuit 1AI10148Compressor Discharge Temperature Circuit 2AI10149Free Cooling Glycol PressureAI10150Last Logged DiagnosticAI10151Unit Load CommandAI10152Average Line CurrentAI10153Average Line VoltageAI10154Current L1AI10155Current L2AI10156Current L3AI10157Voltage L1-L2AI10158Voltage L2-L3AI10159Voltage L1-L3AI10160Total Real PowerAI10161Line FrequencyAI10162Power FactorAI10163Heat Recovery Valve PositionAI10164Evaporator Refrigerant Absolute Pressure Circuit 1AI10165Condenser Refrigerant Absolute Pressure Circuit 1AI10166Evaporator Refrigerant Absolute Pressure Circuit 2AI10167Condenser Refrigerant Absolute Pressure Circuit 2AI10168Free Cooling Glycol Absolute PressureAI10169Supplemental Heater StatusAI10170Evaporator Approach Temperature Circuit 1 (Cooling Mode Only)AI10171Evaporator Approach Temperature Circuit 2 (Cooling Mode Only)AI10172Condenser Approach Temperature Circuit 1 (Heating Mode Only)AI10173Condenser Approach Temperature Circuit 2 (Heating Mode Only)AI10174Active Chilled Water SetpointAI10175Chilled Water Setpoint StatusAI10176Hot Water Setpoint StatusAI10177Demand Limit Setpoint StatusAI10178Active Demand Limit SetpointAV10100Chilled Water SetpointAV10101Demand Limit SetpointAV10102BAS Hot Water SetpointAV10103BAS Heat Recovery SetpointAV10104Evaporator Water Pump Speed SetpointBI10100Limit Mode Relay StatusBI10101Emergency StopBI10102Manual Override ExistsBI10103Run EnableBI10104Local Setpoint ControlBI10105Maximum Capacity RelayBI10106Running Status Cprsr1ABI10107Running Status Cprsr2ABI10108Running Status Cprsr1BBI10109Running Status Cprsr2BBI10110Chiller Running StateBI10111Running Status Cprsr1CBI10112Running Status Cprsr2CBI10113Free Cooling ActiveBI10114Heat Recovery ActiveBI10115Front Panel Auto/StopBI10116Circuit Manual Reset Indicator (CMR) Circuit 1BI10117Circuit Manual Reset Indicator (CMR) Circuit 2BI10118Circuit Auto Reset Indicator (CAR) Circuit 1BI10119Circuit Auto Reset Indicator (CAR) Circuit 2BI10120Evaporator Water Pump CommandBI10121Evaporator Water Flow StatusBI10122Diagnostic Present: InformationBI10123Diagnostic Present: AdvisoryBI10124Diagnostic Present: CriticalBI10125Diagnostic Present: Service RequiredBI10126Diagnostic PresentBI10127Diagnostic Shutdown PresentBI10128Diagnostic: Manual Reset RequiredBI10129Diagnostic: Local Manual Reset RequiredBI10130External Auto StopBI10131Noise Reduction Request ActiveBI10132Heat Recovery Request ActiveBI10133Evaporator Water Pump StatusBI10134Circuit 1 Defrost Delay StatusBI10135Circuit 2 Defrost Delay StatusBI10136In DefrostBI10137Circuit 1 Defrost StatusBI10138Circuit 2 Defrost StatusBI10139Circuit 1 Running StatusBI10140Circuit 2 Running StatusBI10141Low Ambient Lockout StatusBI10142Circuit 1 Lockout Front PanelBI10143Circuit 2 Lockout Front PanelBI10144Circuit 1 Lockout ExternalBI10145Circuit 2 Lockout ExternalBI10146Circuit 1 Lockout ActiveBI10147Circuit 2 Lockout ActiveBI11000Comm Loss: Percent Capacity OutputBI11001Comm Loss: Supplemental Heater Relay 1BI11002Comm Loss: Supplemental Heater Relay 2BI11003Comm Loss: Supplemental Heater Relay 3BI11004Comm Loss: Supplemental Heater Relay 4BI11005Comm Loss: Energy MeterBI11006Comm Loss: Outdoor Air TemperatureBI11007Comm Loss: Phase Protection Fault InputBI11008Diagnostic: Energy Meter Write Command FailureBI11009Diagnostic: Outdoor Air Temperature SensorBI11010Diagnostic: Phase Protection FaultBI11011Diagnostic: Software Error 1003: Call Trane ServiceBI11012Diagnostic: Pumpdown Terminated By Time - Circuit 2BI11013Diagnostic: Pumpdown Terminated By Time - Circuit 1BI11014Comm Loss: Discharge Pressure Transducer - Circuit 2BI11015Comm Loss: Discharge Pressure Transducer - Circuit 1BI11016Comm Loss: Discharge Temperature Sensor - Circuit 2BI11017Comm Loss: Discharge Temperature Sensor - Circuit 1BI11018Comm Loss: External Circuit 2 LockoutBI11019Comm Loss: External Circuit 1 LockoutBI11020Comm Loss: Reversing Valve - Circuit 1BI11021Comm Loss: Reversing Valve - Circuit 2BI11022Comm Loss: Suction Pressure Transducer - Circuit 2BI11023Comm Loss: Suction Pressure Transducer - Circuit 1BI11024Comm Loss: Suction Temperature - Circuit 2BI11025Comm Loss: Suction Temperature - Circuit 1BI11026Diagnostic: Discharge Pressure Transducer - Circuit 2BI11027Diagnostic: Discharge Pressure Transducer - Circuit 1BI11028Diagnostic: Discharge Temperature Sensor - Circuit 1BI11029Diagnostic: Discharge Temperature Sensor - Circuit 2BI11030Diagnostic: Suction Pressure Transducer - Circuit 2BI11031Diagnostic: Suction Pressure Transducer - Circuit 1BI11032Diagnostic: Suction Temperature Sensor - Circuit 2BI11033Diagnostic: Suction Temperature Sensor - Circuit 1BI11034Comm Loss: Sump Heater - Circuit 1BI11035Comm Loss: Sump Heater - Circuit 2BI11036Diagnostic: High Compressor Pressure Differential - Circuit 2BI11037Diagnostic: High Compressor Pressure Differential - Circuit 1BI11038Diagnostic: High Discharge Refrigerant Pressure - Circuit 2BI11039Diagnostic: High Discharge Refrigerant Pressure - Circuit 1BI11040Diagnostic: High Discharge Temperature - Circuit 2BI11041Diagnostic: High Discharge Temperature - Circuit 1BI11042Diagnostic: High Discharge Temperature Lockout - Circuit 2BI11043Diagnostic: High Discharge Temperature Lockout - Circuit 1BI11044Diagnostic: Loss of Charge - Circuit 2BI11045Diagnostic: Loss of Charge - Circuit 1BI11046Diagnostic: Low Discharge Saturated Temperature - Circuit 2BI11047Diagnostic: Low Discharge Saturated Temperature - Circuit 1BI11048Diagnostic: Low Refrigerant Pressure Ratio - Circuit 1BI11049Diagnostic: Low Refrigerant Pressure Ratio - Circuit 2BI11050Diagnostic: Low Refrigerant Temperature - Circuit 2BI11051Diagnostic: Low Refrigerant Temperature - Circuit 1BI11052Diagnostic: Low Suction Refrigerant Pressure - Circuit 2BI11053Diagnostic: Low Suction Refrigerant Pressure - Circuit 1BI11054Diagnostic: Low Suction Superheat - Circuit 2BI11055Diagnostic: Low Suction Superheat - Circuit 1BI11056Diagnostic: Suction Temperature Too High - Circuit 2BI11057Diagnostic: Suction Temperature Too High - Circuit 1BI11058Diagnostic: Very Low Suction Pressure - Circuit 1BI11059Diagnostic: Very Low Suction Pressure - Circuit 2BI11060Comm Loss: Compressor 1C Fault InputBI11061Comm Loss: Compressor 1B Fault InputBI11062Comm Loss: Compressor 1A Fault InputBI11063Diagnostic: Compressor 1A FaultBI11064Diagnostic: Compressor 1B FaultBI11065Diagnostic: Compressor 1C FaultBI11066Diagnostic: Compressor 1C Fault LockoutBI11067Diagnostic: Compressor 1B Fault LockoutBI11068Diagnostic: Compressor 1A Fault LockoutBI11069Diagnostic: Starts/Hours Modified 1ABI11070Diagnostic: Starts/Hours Modified 1BBI11071Diagnostic: Starts/Hours Modified 1CBI11072Comm Loss: Compressor 2C Fault InputBI11073Comm Loss: Compressor 2B Fault InputBI11074Comm Loss: Compressor 2A Fault InputBI11075Diagnostic: Compressor 2A FaultBI11076Diagnostic: Compressor 2B FaultBI11077Diagnostic: Compressor 2C FaultBI11078Diagnostic: Compressor 2C Fault LockoutBI11079Diagnostic: Compressor 2B Fault LockoutBI11080Diagnostic: Compressor 2A Fault LockoutBI11081Diagnostic: Starts/Hours Modified 2BBI11082Diagnostic: Starts/Hours Modified 2CBI11083Diagnostic: Starts/Hours Modified 2ABI11084Comm Loss: High Pressure Cutout Switch - Circuit 2BI11085Comm Loss: High Pressure Cutout Switch - Circuit 1BI11086Diagnostic: High Pressure Cutout - Circuit 2BI11087Diagnostic: High Pressure Cutout - Circuit 1BI11088Comm Loss: Shared V Coil Isolating Valve - Circuit 1BI11089Comm Loss: Shared V Coil Isolating Valve - Circuit 2BI11090Comm Loss: Dynamic Receiver Fill Valve - Circuit 1BI11091Comm Loss: Dynamic Receiver Fill Valve - Circuit 2BI11092Comm Loss: Hot Gas Bypass Valve - Circuit 1BI11093Comm Loss: Hot Gas Bypass Valve - Circuit 2BI11094Comm Loss: Liquid Line Pressure - Circuit 1BI11095Comm Loss: Liquid Line Pressure - Circuit 2BI11096Comm Loss: Liquid Line Temperature - Circuit 1BI11097Comm Loss: Liquid Line Temperature - Circuit 2BI11098Diagnostic: Liquid Line Pressure Transducer - Circuit 1BI11099Diagnostic: Liquid Line Pressure Transducer - Circuit 2BI11100Diagnostic: Liquid Line Temperature Sensor - Circuit 1BI11101Diagnostic: Liquid Line Temperature Sensor - Circuit 2BI11102Comm Loss:Evaporator Antifreeze HeaterBI11103Comm Loss:Heat Recovery Antifreeze HeaterBI11104Diagnostic: Evaporator Water Flow LostBI11105Diagnostic: Evaporator Water Flow Lost LockoutBI11106Diagnostic: Evaporator Water Flow OverdueBI11107Diagnostic: High Evaporator Water TemperatureBI11108Diagnostic: High Suction Rfgt PressureBI11109Diagnostic: Inverted Evaporator Water TemperatureBI11110Diagnostic: Inverted Water Temp (Heating)BI11111Diagnostic: Low Evaporator Water Temp (Unit On)BI11112Diagnostic: Low Evaporator Water Temp (Unit Off)BI11113Comm Loss: Evap Entering Water TempBI11114Comm Loss: Evap Leaving Water TempBI11115Comm Loss: Evaporator Water Flow SwitchBI11116Diagnostic: Evaporator Entering Water Temp SensorBI11117Diagnostic: Evaporator Leaving Water Temp SensorBI11118Comm Loss: Cooling EXV - Circuit 1BI11119Comm Loss: Cooling EXV - Circuit 2BI11120Comm Loss: Electronic Expansion Valve - Circuit 2BI11121Comm Loss: Electronic Expansion Valve - Circuit 1BI11122Comm Loss: Heating EXV - Circuit 1BI11123Comm Loss: Heating EXV - Circuit 2BI11124Comm Loss: Auxiliary Setpoint CommandBI11125Comm Loss: Emergency Stop Feedback InputBI11126Comm Loss: Ext Chilled/Hot Water SetpointBI11127Comm Loss: Ext Noise Reduction RequestBI11128Comm Loss: External Auto/StopBI11129Comm Loss: Ext Demand Limit SetpointBI11130Comm Loss: External Hot Water CommandBI11131Comm Loss: Programmable Relay Board 1BI11132Comm Loss: Programmable Relay Board 2BI11133Diagnostic: Emergency Stop Feedback InputBI11134Diagnostic: External Chilled/Hot Water SetpointBI11135Diagnostic: External Demand Limit SetpointBI11136Comm Loss: Condenser Fan Enable - Circuit 2BI11137Comm Loss: Condenser Fan Enable - Circuit 1BI11138Comm Loss: Cond Fan Enbl Shared Ckt 1&2BI11139Comm Loss: Condenser Fan Fault - Circuit 1BI11140Comm Loss: Condenser Fan Fault - Circuit 2BI11141Comm Loss: Fan Board 1 Relay 1 - Circuit 1BI11142Comm Loss: Fan Board 1 Relay 1 - Circuit 2BI11143Comm Loss: Fan Board 1 Relay 2 - Circuit 1BI11144Comm Loss: Fan Board 1 Relay 2 - Circuit 2BI11145Comm Loss: Fan Board 1 Relay 3 - Circuit 1BI11146Comm Loss: Fan Board 1 Relay 3 - Circuit 2BI11147Comm Loss: Fan Board 1 Relay 4 - Circuit 1BI11148Comm Loss: Fan Board 1 Relay 4 - Circuit 2BI11149Comm Loss: Fan Board 2 Relay 1 - Circuit 1BI11150Comm Loss: Fan Board 2 Relay 1 - Circuit 2BI11151Comm Loss: Fan Board 2 Relay 2 - Circuit 1BI11152Comm Loss: Fan Board 2 Relay 2 - Circuit 2BI11153Comm Loss: Fan Board 2 Relay 3 - Circuit 2BI11154Comm Loss: Fan Board 2 Relay 3 - Circuit 1BI11155Comm Loss: Fan Board 2 Relay 4 - Circuit 2BI11156Comm Loss: Fan Board 2 Relay 4 - Circuit 1BI11157Comm Loss: Fan Inverter Speed Command - Circuit 2BI11158Comm Loss: Fan Inverter Speed Command - Circuit 1BI11159Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1&2BI11160Comm Loss: Fan Speed Select Board Relay 1 - Circuit 1BI11161Comm Loss: Fan Speed Select Board Relay 2 - Circuit 1BI11162Comm Loss: Fan Speed Select Board Relay 3 - Circuit 2BI11163Comm Loss: Fan Speed Select Board Relay 4 - Circuit 2BI11164Diagnostic: Condenser Fan Fault - Circuit 1BI11165Diagnostic: Condenser Fan Fault - Circuit 2BI11166Comm Loss: FC Entering Glycol TempBI11167Comm Loss: FC Entering Water TempBI11168Comm Loss: FC Leaving Glycol TempBI11169Comm Loss: Free Cooling Glycol Flow SwitchBI11170Comm Loss: Free Cooling Glycol PressureBI11171Comm Loss: Free Cooling Glycol Pump FaultBI11172Comm Loss: Free Cooling PumpBI11173Comm Loss: Free Cooling ValveBI11174Diagnostic: Free Cooling Entering Glycol TemperatureBI11175Diagnostic: Free Cooling Entering Water TemperatureBI11176Diagnostic: Free Cooling Glycol Flow LostBI11177Diagnostic: Free Cooling Glycol Flow OverdueBI11178Diagnostic: Free Cooling Glycol PressureBI11179Diagnostic: Free Cooling Glycol Temperature Equalization OverdueBI11180Diagnostic: Free Cooling Leaving Glycol TemperatureBI11181Diagnostic: Free Cooling Glycol Pump FaultBI11182Diagnostic: Low Glycol Pressure Free CoolingBI11183Diagnostic: Low Glycol Temp Free CoolingBI11184Comm Loss: External Heat Recovery CommandBI11185Comm Loss: External Heat Recovery SetpointBI11186Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 1BI11187Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 2BI11188Comm Loss: HR Entering Water TemperatureBI11189Comm Loss: HR Leaving Water TemperatureBI11190Comm Loss: Heat Recovery Three Way ValveBI11191Diagnostic: External Heat Recovery SetpointBI11192Diagnostic: Heat Recovery Entering Water Temp SensorBI11193Diagnostic: Heat Recovery Leaving Water Temp SensorBI11194Diagnostic: No Heat RecoveryBI11195Comm Loss: External Ice Building CommandBI11196Diagnostic: Restart Inhibit Invoked - 1ABI11197Diagnostic: Restart Inhibit Invoked - 1BBI11198Diagnostic: Restart Inhibit Invoked - 1CBI11199Diagnostic: Restart Inhibit Invoked - 2ABI11200Diagnostic: Restart Inhibit Invoked - 2BBI11201Diagnostic: Restart Inhibit Invoked - 2CBI11202Comm Loss: Energy Meter Pulse InputBI11203Comm Loss: Run Command Compressor 1ABI11204Comm Loss: Run Command Compressor 1BBI11205Comm Loss: Run Command Compressor 1CBI11206Comm Loss: Run Command Compressor 2ABI11207Comm Loss: Run Command Compressor 2BBI11208Comm Loss: Run Command Compressor 2CBI11209Diagnostic: MP: Invalid ConfigurationBI11210Diagnostic: MP: Reset Has OccurredBI11211Comm Loss: Evap Pump Inv1 Fault InputBI11212Comm Loss: Evap Pump Inv1 Freq FeedbackBI11213Comm Loss: Evap Pump Inv1 Run CommandBI11214Comm Loss: Evaporator Pump 2 Fault InputBI11215Comm Loss: Evaporator Water Pump 1 RelayBI11216Comm Loss: Evaporator Water Pump 2 RelayBI11217Comm Loss: Evaporator Pump 1 Fault InputBI11218Diagnostic: Evap Pump 1 Starts Run time WrittenBI11219Diagnostic: Evap Pump 2 Starts Run time WrittenBI11220Diagnostic: Evaporator Pump 1 FaultBI11221Diagnostic: Evaporator Pump 2 FaultBI11222Diagnostic: Evaporator Water Flow Lost - Pump1BI11223Diagnostic: Evaporator Water Flow Lost - Pump2BI11224Diagnostic: Evaporator Water Flow Overdue - Pump1BI11225Diagnostic: Evaporator Water Flow Overdue - Pump2BI11226Comm Loss: SLHX Entering Refrigerant Temp - Circuit 1BI11227Comm Loss: SLHX Entering Refrigerant Temp - Circuit 2BI11228Comm Loss: SLHX Valve - Circuit 1BI11229Comm Loss: SLHX Valve - Circuit 2BI11230Diagnostic: SLHX Entering Temp Sensor - Circuit 1BI11231Diagnostic: SLHX Entering Temp Sensor - Circuit 2BI11232Diagnostic: Chiller Service RecommendedBI11233Diagnostic: Evap Water Pump 1 Svc RecommendedBI11234Diagnostic: Evap Water Pump 2 Svc RecommendedBI11235Diagnostic: Mfr Maintenance Recommended - 1ABI11236Diagnostic: Mfr Maintenance Recommended - 1BBI11237Diagnostic: Mfr Maintenance Recommended - 1CBI11238Diagnostic: Mfr Maintenance Recommended - 2ABI11239Diagnostic: Mfr Maintenance Recommended - 2BBI11240Diagnostic: Mfr Maintenance Recommended - 2CBI11241Diagnostic: Evaporator Water Flow Too LowBI11242Comm Loss: Evap Water Pump Inverter SpeedBI11243Energy Meter Write Value FailureBV10100Reset DiagnosticBV10101BAS Noise Reduction RequestBV10102BAS Heat Recovery CommandBV10103Energy Consumption ResetBV10104BAS Circuit 1 LockoutBV10105BAS Circuit 2 LockoutBV10106BAS Free Cooling Auto Stop CommandBV10107BAS Chiller Auto Stop CommandBV10108Evaporator Water Pump Request BASBV10109Defrost Delay Request BASMI10100Running ModeMI10101Operating ModeMI10102Chiller Setpoint SourceMI10103Refrigerant TypeMI10104Cooling TypeMI10105Manufacture LocationMI10107Front Panel Chiller Mode CommandMI10108Model Information [GEN2]MI10109Circuit 1 StatusMI10110Circuit 2 StatusMV10100Chiller Mode Command BAS
Integration notes
- Only the points that apply to the unit's factory configuration show up; the doc lists every possible point.
- The chiller tables have no read/write column: AI/BI/MI are read-only, and AV/BV/MV are the BAS command and setpoint objects, marked writable here per Trane's naming convention.
- Units are listed as a quantity (Temperature, Pressure, Percent...); the actual engineering unit follows the controller's display-unit setting.
- Binary inputs named 'Diagnostic: ...' are individual alarm flags (0/false = normal, 1/true = in alarm).
- The Symbio 800 integration guide (BAS-SVP083) covers BACnet IP and BACnet MS/TP; the rotary address sets the MS/TP MAC and a default Device ID of 1-127, and a software Device ID can be set instead.
- The same document also maps every object to a Modbus register; only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Symbio 800 Ascend ACS / ACX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Trane Symbio 800 Ascend ACS / ACX
How many BACnet points does the Trane Symbio 800 Ascend ACS / ACX have?
This list has 397 BACnet objects: 79 analog inputs, 5 analog values, 292 binary inputs, 10 binary values, 10 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Trane Symbio 800 Ascend ACS / ACX BACnet points are writable?
16 of the 397 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Trane Symbio 800 Ascend ACS / ACX BACnet documentation?
The source is Symbio 800 Integration Points List BACnet - Ascend Models ACS and ACX (BAS-PTS011A-EN), revision 11/15/2024, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS011A-EN_11152024.pdf.
What are the minimum BACnet points to integrate the Trane Symbio 800 Ascend ACS / ACX?
Start with BV 10107 BAS Chiller Auto Stop Command (BMS auto/stop (enable) command); MV 10100 Chiller Mode Command BAS (Cool/heat/ice/free-cooling mode command); AV 10100 Chilled Water Setpoint (Chilled water setpoint from the BMS); AV 10101 Demand Limit Setpoint (Capacity (demand) limit from the BMS); BI 10110 Chiller Running State (Chiller on/off status); BI 10104 Local Setpoint Control (Shows if local setpoints override BAS setpoints); AI 10101 Evaporator Leaving Water Temperature (Leaving chilled water temperature); AI 10116 Actual Running Capacity (Actual running capacity in percent); BI 10126 Diagnostic Present (Any active diagnostic (alarm) on the chiller).
How do I enable BMS control of the Trane Symbio 800 Ascend ACS / ACX?
BV 10107 BAS Chiller Auto Stop Command (0 = Stop, 1 = Auto) is the BMS auto/stop; with it at Auto the chiller runs when its own run conditions are met. BI 10130 External Auto Stop reports the hardwired external auto/stop input. The documents don't say how the two combine or how to hand setpoint control to the BAS; BI 10104 Local Setpoint Control shows when the chiller is using local setpoints instead of BAS setpoints, and MI 10102 Chiller Setpoint Source shows BAS, External or Front Panel.
How do I check these points on the real Symbio 800 Ascend ACS / ACX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Trane BACnet points lists
- Water-cooled scroll chiller BACnet interface
Trane BCI2-C for CGWN / CCUN chillers (CH530)
Trane CGWN water-cooled and CCUN condenserless scroll chillers with CH530 controls, as listed in the BCI2-C integration guide.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, CGWN, CCUN, CGWN water-cooled scroll chiller, CCUN condenserless chiller, BAS-SVP055 - Water-cooled screw chiller BACnet interface
Trane BCI2-C for RTWD / RTUD chillers (CH530)
Trane Series R RTWD water-cooled and RTUD condenserless helical-rotary chillers with CH530 controls fitted with the BCI2-C BACnet interface.
Also known as: BCI2-C, BCI2C, BACnet Communication Interface for Chillers, RTWD, RTUD, Series R RTWD, RTWD CH530, BAS-SVP055 - Rooftop unit communication interface (IntelliPak)
Trane BCI2-I (IntelliPak)
Trane IntelliPak I and II rooftop units, IntelliPak air handlers and Commercial Self-Contained (CSC) units fitted with the BCI2-I BACnet card.
Also known as: BCI2-I, BCI2I, IntelliPak BACnet interface, BACnet Communication Interface for IntelliPak, BAS-SVP054, IntelliPak I, IntelliPak II, Commercial Self-Contained, Signature Series - Rooftop unit communication interface (ReliaTel)
Trane BCI2-R (ReliaTel)
Trane packaged rooftop units with ReliaTel controls (Voyager, Precedent, Odyssey) fitted with the BCI2-R BACnet card.
Also known as: BCI2-R, BCI2R, ReliaTel BACnet interface, BACnet Communication Interface for ReliaTel, BAS-SVP053, Voyager, Precedent, Odyssey - DOAS / outdoor air unit controller
Trane Horizon Outdoor Air Unit, Tracer UC600 program V12
Trane Horizon outdoor air units (cabinets OAB, OAD, OAG, OAK, OAN) with the Tracer UC600 controller running Horizon program version 12.
Also known as: Horizon OAU, Horizon DOAS, OAU-SVP002A, Tracer UC600 Horizon, OAB, OAD, OAG, OAK, OAN - Rooftop unit controller (zone sensor interaction subset)
Trane ReliaTel BCI-R - touch-screen zone sensor points
Trane Precedent, Voyager 2/3 and Odyssey single-zone units on ReliaTel controls with a BCI-R board, used with the commercial touch-screen programmable zone sensor.
Also known as: ReliaTel, BCI-R, RTRM, X13790994001, BAYSENS924, BAS-SVP080A - VAV box controller
Trane Symbio 210 VAV
Trane VAV terminal units with the Symbio 210 programmable controller running the factory VAV programs (space temperature, ventilation flow and flow tracking control).
Also known as: Symbio 210, Symbio210, Symbio 210 VAV controller, BAS-SVP043 - Fan coil, blower coil and unit ventilator controller
Trane Symbio 400-B/500 Fan Coil, Blower Coil and Unit Ventilator
Trane fan coils, blower coils and unit ventilators controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio fan coil, Symbio blower coil, Symbio unit ventilator, BAS-SVP060A-EN - Water-source heat pump controller
Trane Symbio 400-B/500 Water-Source Heat Pump
Trane water-source heat pumps controlled by a Symbio 400-B or Symbio 500 programmable controller.
Also known as: Symbio 400-B, Symbio 400B, Symbio 500, Symbio WSHP, BAS-SVP061B-EN - Self-contained unit controller
Trane Symbio 500 Commercial Self-Contained (SWUD)
Trane commercial self-contained (SWUD) units controlled by a Symbio 500.
Also known as: Symbio 500, SWUD, Commercial Self-Contained, CSC, BAS-PTS038 - Self-contained unit controller
Trane Symbio 500 Modular Self-Contained (SCWM)
Trane modular self-contained (SCWM) units controlled by a Symbio 500.
Also known as: Symbio 500, SCWM, Modular Self-Contained, BAS-PTS037 - Split system controller
Trane Symbio 700 Odyssey
Trane Odyssey split systems controlled by a Symbio 700.
Also known as: Symbio 700, Odyssey split system, BAS-PTS005 - Rooftop unit controller
Trane Symbio 700 Precedent / Axiom
Trane Precedent packaged rooftop units and Axiom rooftop water-source heat pumps with the Symbio 700 controller.
Also known as: Symbio 700, Symbio700, Precedent rooftop, Axiom rooftop WSHP, BAS-PTS001 - Rooftop unit controller
Trane Symbio 700 Voyager 3
Trane Voyager 3 packaged rooftop air conditioners with the Symbio 700 controller.
Also known as: Voyager 3, Voyager III, Symbio 700, Symbio700, BAS-SVP066 - Rooftop unit controller (zone sensor interaction subset)
Trane Symbio 800 (SCC IntelliPak) / Symbio 700 - touch-screen zone sensor points
Trane single-zone equipment on Symbio 700 and IntelliPak units on Symbio 800 (SCC), used with the commercial touch-screen programmable zone sensor.
Also known as: Symbio 700, Symbio 800, SCC IPak, IntelliPak, X13791009001, BAYSENS800, BAS-SVP080A - Air-cooled chiller controller
Trane Symbio 800 ACRB Small (UC800)
Trane ACRB Small air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACRB, ACRB Small, ACRB UC800, Symbio 800 ACRB, BAS-PTS025 - Air-cooled chiller controller
Trane Symbio 800 ACSA (UC800)
Trane ACSA air-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: ACSA, ACSA UC800, Symbio 800 ACSA, BAS-PTS026 - Water-cooled centrifugal chiller controller
Trane Symbio 800 Agility (HDWA / HDDA)
Trane Agility water-cooled centrifugal chillers (model HDWA and HDDA per the model information point) with Symbio 800 controls.
Also known as: Agility, HDWA, HDDA, Agility water-cooled chiller, Symbio 800 Agility, BAS-PTS007 - Air-cooled chiller controller
Trane Symbio 800 Ascend ACR Series C
Trane Ascend model ACR Series C air-cooled chillers with Symbio 800 controls.
Also known as: Ascend ACR, ACR Series C, Ascend air-cooled chiller, Symbio 800 Ascend ACR, BAS-PTS021 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Duplex)
Two-compressor (duplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac Duplex, CDHH, CDHF, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac (Simplex)
Single-compressor (simplex) Trane CenTraVac water-cooled centrifugal chillers with Symbio 800 controls.
Also known as: CenTraVac, CVHE, CVHF, CVHH, Symbio 800 CenTraVac, BAS-PTS009 - Centrifugal chiller controller
Trane Symbio 800 CenTraVac Simplex (UC800)
Trane CenTraVac (CTV) simplex centrifugal chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: CenTraVac, CTV, CTV-Simplex, CenTraVac UC800, Symbio 800 CenTraVac, BAS-PTS029 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM
Trane CGAM air-cooled scroll chillers with Symbio 800 controls.
Also known as: CGAM, CGAM air-cooled chiller, Symbio 800 CGAM, BAS-PTS019 - Air-cooled scroll chiller controller
Trane Symbio 800 CGAM (CH530)
Trane CGAM air-cooled scroll chillers whose Symbio 800 points list Trane tags '(CH530)'.
Also known as: CGAM, CGAM CH530, CH530 CGAM, Symbio 800 CGAM, BAS-PTS027 - Water-cooled centrifugal chiller controller
Trane Symbio 800 HDWA (UC800)
Trane HDWA water-cooled chillers whose Symbio 800 points list Trane tags '(UC800)'.
Also known as: HDWA, Agility HDWA, HDWA UC800, Symbio 800 HDWA, BAS-PTS028 - Split system controller
Trane Symbio 800 IntelliCore Split System (RAUK)
Trane IntelliCore split systems (RAUK) controlled by a Symbio 800.
Also known as: IntelliCore, RAUK, IntelliCore split system, Symbio 800, BAS-PTS036 - Rooftop unit / air handler controller
Trane Symbio 800 IntelliPak
Trane IntelliPak large packaged rooftop units running the Symbio 800 controller.
Also known as: Symbio 800, IntelliPak rooftop, IntelliPak with Symbio 800, BAS-PTS003 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC
Trane RTAC air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTAC, Series R RTAC, RTAC air-cooled chiller, BAS-PTS023 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (CH530)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (CH530)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC CH530, CH530, BAS-PTS031 - Air-cooled screw chiller controller
Trane Symbio 800 RTAC (UC800)
Trane RTAC air-cooled helical-rotary chillers covered by Trane's 'RTAC (UC800)' Symbio 800 points list.
Also known as: RTAC, Series R RTAC, RTAC UC800, UC800, BAS-PTS032 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (CH530)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (CH530)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD CH530, CH530, BAS-PTS033 - Water-cooled screw chiller controller
Trane Symbio 800 RTHD (UC800)
Trane RTHD water-cooled helical-rotary chillers covered by Trane's 'RTHD (UC800)' Symbio 800 points list.
Also known as: RTHD, Series R RTHD, RTHD UC800, UC800, BAS-PTS034 - Water-cooled screw chiller controller
Trane Symbio 800 RTWD (CH530)
Trane RTWD water-cooled helical-rotary chillers covered by Trane's 'RTWD (CH530)' Symbio 800 points list.
Also known as: RTWD, Series R RTWD, RTWD CH530, CH530, BAS-PTS035 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTHD
Trane Series R model RTHD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTHD, Series R RTHD, RTHD water-cooled chiller, Symbio 800 RTHD, BAS-PTS015 - Water-cooled screw chiller controller
Trane Symbio 800 Series R RTWD
Trane Series R model RTWD water-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: RTWD, Series R RTWD, Series R water-cooled chiller, BAS-PTS017 - Air-cooled screw chiller controller
Trane Symbio 800 Sintesis RTAF
Trane Sintesis model RTAF air-cooled helical-rotary chillers with Symbio 800 controls.
Also known as: Sintesis RTAF, RTAF, Sintesis air-cooled chiller, Symbio 800 Sintesis, BAS-PTS013 - Dedicated outdoor air unit (DOAS) controller
Trane Tracer UC600 Packaged Outdoor Air Unit
Trane packaged outdoor air units controlled by a Tracer UC600 running the packaged outdoor air unit program.
Also known as: Tracer UC600, UC600 DOAS, Packaged Outdoor Air Unit, BAS-SVP18 - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 (FC, BC, UV, staged WSHP) - touch-screen zone sensor points
Factory-programmed Trane fan coils, blower coils, unit ventilators and staged water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B, Symbio 500, Symbio 400-B, X13790993001, SEN02587, X13790992001, BAS-SVP080A - Heat pump / fan coil controller (zone sensor interaction subset)
Trane UC400-B / Symbio 500 VS-WSHP - touch-screen zone sensor points
Factory-programmed Trane variable-speed water-source heat pumps on Tracer UC400-B or Symbio 400-B/500, used with the touch-screen programmable zone sensor.
Also known as: UC400-B VS-WSHP, Symbio 500 VS-WSHP, variable speed WSHP, X13790993001, SEN02587, BAS-SVP080A
Source: Symbio 800 Integration Points List BACnet - Ascend Models ACS and ACX · BAS-PTS011A-EN · rev. 11/15/2024. Object names, instances and units are reproduced as published; descriptions are our own.