- IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
VRF BACnet IP gateway (up to 64 or 128 indoor units) · BACnet points list
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) BACnet points list
Updated 12 November 2026Unofficial source
An older IntesisBox BACnet IP server that connects to one Panasonic CZ-CFUNC2 adaptor and publishes gateway-wide commands plus a fixed block of objects for each indoor unit, up to 64 or 128 units depending on model. Indoor unit instances are (unit number x 256) + offset, so unit 1 uses 256-289. Setup is done with the LinkBoxBACnet tool.
This page lists 36 BACnet objects for the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Intesis’s documentation hosted by Chipkin Automation Systems, not by Intesis itself, so treat it as unofficial.
- Manufacturer
- Intesis
- Model
- IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
- Equipment
- VRF BACnet IP gateway (up to 64 or 128 indoor units)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 36 (19 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 246
- Also known as
- IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
- Source document
- IntesisBox BACnet/IP - Panasonic AC User Manual r2.1 (PA-AC-BAC-64/128) · rev. r2.1 (unofficial copy, hosted by Chipkin Automation Systems)
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Connect the IntesisBox to the CZ-CFUNC2 adaptor and the BACnet IP LAN, configure the indoor units in LinkBoxBACnet, then map each unit's _command and _status objects from its (unit x 256) block. Instances 18-29 act on all units at once.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 258 | IUxxx_OnOff_command | Start/stop indoor unit | Write |
| MO 260 | IUxxx_Mode_command | Mode command | Write |
| AO 262 | IUxxx_SetPoint_command | Setpoint command | Write |
| MO 265 | IUxxx_FanSpeed_command | Fan speed command (4 = auto) | Write |
| BI 257 | IUxxx_OnOff_status | Run status | Read |
| AI 261 | IUxxx_SetPoint_status | Setpoint in use | Read |
| AI 263 | IUxxx_Room_Temperature | Room temperature | Read |
| BI 256 | IUxxx_IU_Exist | Unit found on the adaptor | Read |
| MI 270 | IUxxx_ErrorCode | Fault code | Read |
Enable & remote start
No enable point is documented. Remote-controller functions can be locked per unit (MV 271) or for all units (MO 22).
Network setup
- Default device instance 246; device instance, name and IP are set with LinkBoxBACnet.
- One IntesisBox integrates one CZ-CFUNC2 adaptor (bought separately from Panasonic), which has two links of up to 30 outdoor and 64 indoor units each.
Watch out for
- OnOff_All, Mode_All, SetPoint_All, FanSpeed_All and the occupancy objects (instances 18-29) act on every indoor unit.
- Outputs only use Priority_Array slot 16; slots 1-15 stay NULL.
- State_Text cannot be read as a whole array; read one array index at a time.
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | 246 | Panasonic AC Gateway | Gateway device object (instance configurable) | Read | ||
| MI | 16 | AdaptorLink1_ErrorCode | CZ-CFUNC2 link 1 error code | Read | 1-259 = Panasonic error codes (A01...); see manual | |
| MI | 17 | AdaptorLink2_ErrorCode | CZ-CFUNC2 link 2 error code | Read | 1-259 = Panasonic error codes (A01...); see manual | |
| BO | 18 | OnOff_All | On/off for all indoor units | Write | ||
| MO | 19 | Mode_All | Mode for all indoor units | Write | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AO | 20 | SetPoint_All | Setpoint for all indoor units, -15 to 60 °C | °C / °F | Write | |
| MO | 21 | FanSpeed_All | Fan speed for all indoor units | Write | 1=Low, 2=Medium, 3=High, 4=Auto | |
| MO | 22 | RemoteControl_Lock_All | Remote controller lock for all units | Write | 1-32 = combinations of locked functions (OO on/off, OM mode, SP setpoint, AD air direction, FS fan speed); see manual table | |
| MO | 23 | Occupancy_All | Occupancy function for all units | Write | 1=Occupied, 2=Unoccupied, 3=Disabled | |
| AV | 24 | Occ_Cool_SetPoint | Occupied cooling setpoint | °C / °F | Write | |
| AV | 25 | Occ_Heat_SetPoint | Occupied heating setpoint | °C / °F | Write | |
| AV | 26 | Unocc_Cool_SetPoint | Unoccupied cooling setpoint | °C / °F | Write | |
| AV | 27 | Unocc_Heat_SetPoint | Unoccupied heating setpoint | °C / °F | Write | |
| BO | 28 | Occ_ContinuousCheck | Keep checking setpoint and occupancy continuously | Write | ||
| BO | 29 | Unocc_DeadbandAction | Action when unoccupied and inside the deadband | Write | ||
| BO | 34 | Consumption_Reset | Reset consumption counters | Write | ||
| BImin | 256 | IUxxx_IU_Exist | Indoor unit present | Read | ||
| BImin | 257 | IUxxx_OnOff_status | Run status | Read | ||
| BOmin | 258 | IUxxx_OnOff_command | Start/stop command | Write | ||
| MI | 259 | IUxxx_Mode_status | Operating mode | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=AutoHeat, 6=AutoCool | |
| MOmin | 260 | IUxxx_Mode_command | Mode command | Write | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 261 | IUxxx_SetPoint_status | Setpoint in use | °C / °F | Read | |
| AOmin | 262 | IUxxx_SetPoint_command | Setpoint command, -15 to 60 °C | °C / °F | Write | |
| AImin | 263 | IUxxx_Room_Temperature | Room temperature at the indoor unit sensor | °C / °F | Read | |
| MI | 264 | IUxxx_FanSpeed_status | Fan speed | Read | 1=Low, 2=Medium, 3=High, 4=Auto | |
| MOmin | 265 | IUxxx_FanSpeed_command | Fan speed command | Write | 1=Low, 2=Medium, 3=High, 4=Auto | |
| MI | 266 | IUxxx_AirDirection_status | Air direction (louver) | Read | 1=Horizontal, 2=Pos2, 3=Pos3, 4=Pos4, 5=Vertical, 6=Swing, 7=Off/Auto | |
| MO | 267 | IUxxx_AirDirection_command | Air direction command | Write | 1=Horizontal, 2=Pos2, 3=Pos3, 4=Pos4, 5=Vertical, 6=Swing, 7=Off/Auto | |
| BI | 268 | IUxxx_FilterSign_status | Filter sign | Read | ||
| BO | 269 | IUxxx_FilterSign_Reset_command | Filter sign reset | Write | ||
| MImin | 270 | IUxxx_ErrorCode | Indoor unit error code | Read | 1-259 = Panasonic error codes (A01...); see manual | |
| MV | 271 | IUxxx_RemoteControl_Lock | Remote controller lock for this unit | Read | 1-32 = combinations of locked functions (OO on/off, OM mode, SP setpoint, AD air direction, FS fan speed); see manual table | |
| MV | 286 | IUxxx_Occupancy | Occupancy function for this unit | Read | 1=Occupied, 2=Unoccupied, 3=Disabled | |
| AI | 287 | IUxxx_Consumption_Yesterday | Consumption yesterday | kW (as printed) | Read | |
| AI | 288 | IUxxx_Consumption_Today | Consumption today | kW (as printed) | Read | |
| AI | 289 | IUxxx_Consumption_Total | Total consumption | kW (as printed) | Read |
No points match these filters.
Object ID lookup: Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 point IDs by name
MI16AdaptorLink1_ErrorCodeMI17AdaptorLink2_ErrorCodeBO18OnOff_AllMO19Mode_AllAO20SetPoint_AllMO21FanSpeed_AllMO22RemoteControl_Lock_AllMO23Occupancy_AllAV24Occ_Cool_SetPointAV25Occ_Heat_SetPointAV26Unocc_Cool_SetPointAV27Unocc_Heat_SetPointBO28Occ_ContinuousCheckBO29Unocc_DeadbandActionBO34Consumption_ResetBI256IUxxx_IU_ExistBI257IUxxx_OnOff_statusBO258IUxxx_OnOff_commandMI259IUxxx_Mode_statusMO260IUxxx_Mode_commandAI261IUxxx_SetPoint_statusAO262IUxxx_SetPoint_commandAI263IUxxx_Room_TemperatureMI264IUxxx_FanSpeed_statusMO265IUxxx_FanSpeed_commandMI266IUxxx_AirDirection_statusMO267IUxxx_AirDirection_commandBI268IUxxx_FilterSign_statusBO269IUxxx_FilterSign_Reset_commandMI270IUxxx_ErrorCodeMV271IUxxx_RemoteControl_LockMV286IUxxx_OccupancyAI287IUxxx_Consumption_YesterdayAI288IUxxx_Consumption_TodayAI289IUxxx_Consumption_Total
Integration notes
- Indoor unit objects are shown for unit 1 only. Instance = (xxx x 256) + offset, xxx = indoor unit number 1-128. Object names start with IUxxx; the description text carries the link, outdoor and indoor address (K-OA-IA).
- This older product talks to the CZ-CFUNC2 adaptor. The newer Intesis INBACPAN016O000/064O000/128O000 (P-Link) uses a different object set. The PA-AC-BAC-64/128 names are also used for that newer product, so check the gateway model before mapping.
- Occupancy_All instance 23 and Consumption_Reset 34 come from the object-detail pages; the member-objects table prints the instance column one row off.
- The setpoint command AOs' property tables mark Present_Value R; they are listed as writable here because they are the setpoint commands. IUxxx_RemoteControl_Lock and IUxxx_Occupancy are printed R; check on site.
- Temperature units follow the gateway setting (°C or °F). Consumption units are printed as kilowatts.
- Error code states are a long Panasonic code table (A01, C12, E23 ...) in the manual and are not reproduced here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
How many BACnet points does the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) have?
This list has 36 BACnet objects: 5 analog inputs, 2 analog outputs, 4 analog values, 3 binary inputs, 6 binary outputs, 1 device, 6 multi-state inputs, 7 multi-state outputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) BACnet points are writable?
19 of the 36 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor) BACnet documentation?
Intesis does not publish it on its own website. This list comes from IntesisBox BACnet/IP - Panasonic AC User Manual r2.1 (PA-AC-BAC-64/128), revision r2.1, a copy hosted by Chipkin Automation Systems at https://cdn.chipkin.com/assets/uploads/2018/feb/08-02-04-48_intesisbox_pa-ac-bac-64-128_user_manual_en.pdf. Ask Intesis or its representative for the current revision.
What are the minimum BACnet points to integrate the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)?
Start with BO 258 IUxxx_OnOff_command (Start/stop indoor unit); MO 260 IUxxx_Mode_command (Mode command); AO 262 IUxxx_SetPoint_command (Setpoint command); MO 265 IUxxx_FanSpeed_command (Fan speed command (4 = auto)); BI 257 IUxxx_OnOff_status (Run status); AI 261 IUxxx_SetPoint_status (Setpoint in use); AI 263 IUxxx_Room_Temperature (Room temperature); BI 256 IUxxx_IU_Exist (Unit found on the adaptor); MI 270 IUxxx_ErrorCode (Fault code).
How do I enable BMS control of the Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)?
No enable point is documented. Remote-controller functions can be locked per unit (MV 271) or for all units (MO 22).
How do I check these points on the real IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - VRF BACnet gateway (Fujitsu, multi-unit)
Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
Fujitsu VRF systems (outdoor units 0-11, indoor units 1-64) integrated through the Intesis 700 Series Air gateway IN775FGL***O000.
Also known as: IN775FGL, IN775FGLO000, IN775FGL***O000, 700 Series Air Fujitsu, Intesis Fujitsu VRF BACnet gateway, HMS Intesis Fujitsu VRF, Fujitsu Airstage VRF BACnet - VRF BACnet gateway (Mitsubishi Heavy Industries, multi-unit)
Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
Mitsubishi Heavy Industries VRF systems (up to 128 indoor units, or 80 with up to 12 monitored outdoor units on the large license) through the Intesis 700 Series Air gateway IN776MHI***O000.
Also known as: IN776MHI, IN776MHIO000, IN776MHI***O000, IN776MHI00LO000, 700 Series Air MHI, Intesis MHI VRF BACnet gateway, Mitsubishi Heavy Industries VRF BACnet, MHI KX VRF BACnet - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway
Source: IntesisBox BACnet/IP - Panasonic AC User Manual r2.1 (PA-AC-BAC-64/128) · rev. r2.1. Object names, instances and units are reproduced as published; descriptions are our own.