- IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
VRF BACnet gateway (multiple indoor units, Midea) · BACnet points list
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet points list
Updated 6 November 2026
Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP on a Midea commercial/VRF system. It publishes gateway-wide commands, outdoor-unit error objects at (OU x 10000) and one block per indoor unit at (unit index x 100): on/off, mode, setpoint, standard and extended fan speed, swing and vane positions, room temperature, error codes, remote and per-mode locks, operating-mode force and energy consumption.
This page lists 51 BACnet objects for the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
- Equipment
- VRF BACnet gateway (multiple indoor units, Midea)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 51 (23 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea
- Brands covered
- Midea
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Connect the Midea bus to the gateway, pick BACnet IP or BACnet MS/TP in Intesis MAPS, configure the units, send the project, then map each indoor unit's _C commands and _S status objects from its (index x 100) block.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | UXX_On/Off_C | Start/stop indoor unit | Command |
| MO 100 | UXX_Mode_C | Mode command | Command |
| AO 100 | UXX_Setpoint_C | Setpoint command | Command |
| MO 101 | UXX_FanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | UXX_On/Off_S | Run status | Read |
| AI 100 | UXX_Setpoint_S | Setpoint in use | Read |
| AI 101 | UXX_Room Temperature | Indoor unit room temperature, °C | Read |
| BI 102 | UXX_Communication Error IU | Unit offline on the Midea bus | Read |
| AI 102 | UXX_Unit Error Code | Fault code (0 = no error) | Read |
Enable & remote start
No enable point is documented. UXX_Remote control lock_C (BO 102) locks the remote controller of that unit.
Network setup
- Units are indexed in Intesis MAPS; the index (not the Midea address) sets the instance block.
- Send the project to the gateway after changes in MAPS.
Watch out for
- Global objects (BO 0-3, MO 0-4, AO 0) act on all units at once.
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 0 | On/Off (all units) | Start/stop every unit | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode for every unit | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MO | 1 | FanSpeed (all units) | Fan speed for every unit | Command | 1=Auto, 2=Low, 3=Med, 4=High | |
| MO | 2 | FanSpeed extended (all units) | Extended fan speed for every unit | Command | 1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7 | |
| MO | 3 | Vane Position LEFT/RIGHT (all units) | Left/right vane for every unit | Command | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| MO | 4 | Vane Position UP/DOWN (all units) | Up/down vane for every unit | Command | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| BO | 1 | Vane Position Swing (all units) | Swing for every unit | Command | 0=Swing Off, 1=Swing On | |
| AO | 0 | Temperature Setpoint (all units) | Setpoint for every unit (17-30 °C) | °C | Command | |
| BO | 2 | Operating mode force (all Units) | Operating mode force for every unit | Command | 0=No force, 1=Force | |
| BO | 3 | Remote control lock (all units) | Lock remotes of every unit | Command | 0=Unlock, 1=Lock | |
| AI | 10000 | OUXX_Unit Error Code | Outdoor unit error code | Read | 0=No error, 1..260=Error | |
| BI | 10000 | OUXX_Communication Error OU | Outdoor unit communication error | Read | 0=No error, 1=Error | |
| BImin | 100 | UXX_On/Off_S | On/off status | Read | 0=Off, 1=On | |
| BOmin | 100 | UXX_On/Off_C | Start/stop the indoor unit | Command | 0=Off, 1=On | |
| MI | 100 | UXX_Mode_S | Operating mode in use | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool, 8=AutoDry, 9=AutoFan | |
| MOmin | 100 | UXX_Mode_C | Operating mode command | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | UXX_Setpoint_S | Setpoint in use (17-30 °C) | °C | Read | |
| AOmin | 100 | UXX_Setpoint_C | Setpoint command (17-30 °C) | °C | Command | |
| MI | 101 | UXX_FanSpeed_S | Fan speed status | Read | 1=Auto, 2=Low, 3=Med, 4=High | |
| MOmin | 101 | UXX_FanSpeed_C | Fan speed command | Command | 1=Auto, 2=Low, 3=Med, 4=High | |
| MI | 102 | UXX_FanSpeed Extended_S | Extended fan speed status | Read | 1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7 | |
| MO | 102 | UXX_FanSpeed Extended_C | Extended fan speed command | Command | 1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7 | |
| BI | 101 | UXX_Vane position swing_S | Swing status | Read | 0=Swing Off, 1=Swing On | |
| BO | 101 | UXX_Vane position swing_C | Swing command | Command | 0=Swing Off, 1=Swing On | |
| MI | 103 | UXX_Vane Position Left/Right_S | Left/right vane status | Read | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| MO | 103 | UXX_Vane Position Left/Right_C | Left/right vane command | Command | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| MI | 104 | UXX_Vane Position Up/Down_S | Up/down vane status | Read | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| MO | 104 | UXX_Vane Position Up/Down_C | Up/down vane command | Command | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| AImin | 101 | UXX_Room Temperature | Room temperature | °C | Read | |
| AImin | 102 | UXX_Unit Error Code | Unit error code | Read | 0=No error, 1..255=Error | |
| AI | 112 | UXX_Unit Error Code Extended | Extended unit error code | Read | 0=No error, 1..260=Error | |
| BImin | 102 | UXX_Communication Error IU | Indoor unit communication error | Read | 0=No error, 1=Error | |
| BI | 103 | UXX_Remote control lock_S | Remote lock status | Read | 0=Unlock, 1=Lock | |
| BO | 102 | UXX_Remote control lock_C | Remote lock command | Command | 0=Unlock, 1=Lock | |
| BI | 107 | UXX_Control lock_Mode Heat_S | Heat mode lock status | Read | 0=Unlock, 1=Lock | |
| BO | 106 | UXX_Control lock_Mode Heat_C | Heat mode lock command | Command | 0=Unlock, 1=Lock | |
| BI | 108 | UXX_Control lock_Mode Cool_S | Cool mode lock status | Read | 0=Unlock, 1=Lock | |
| BO | 107 | UXX_Control lock_Mode Cool_C | Cool mode lock command | Command | 0=Unlock, 1=Lock | |
| BI | 109 | UXX_Control lock_Mode Fan_S | Fan mode lock status | Read | 0=Unlock, 1=Lock | |
| BO | 108 | UXX_Control lock_Mode Fan_C | Fan mode lock command | Command | 0=Unlock, 1=Lock | |
| BI | 104 | UXX_Operating mode force_S | Operating mode force status | Read | 0=No force, 1=Force | |
| BO | 103 | UXX_Operating mode force_C | Operating mode force command | Command | 0=No force, 1=Force | |
| AI | 103 | UXX_Consumption_Yesterday_S | Energy consumption, yesterday | Wh/kWh | Read | |
| AI | 104 | UXX_Consumption_Today_S | Energy consumption, today | Wh/kWh | Read | |
| AI | 105 | UXX_Consumption_Total_S | Energy consumption, total | Wh/kWh | Read | |
| AI | 106 | UXX_Consumption_Yesterday_Heat_S | Energy consumption, yesterday heat | Wh/kWh | Read | |
| AI | 107 | UXX_Consumption_Today_Heat_S | Energy consumption, today heat | Wh/kWh | Read | |
| AI | 108 | UXX_Consumption_Total_Heat_S | Energy consumption, total heat | Wh/kWh | Read | |
| AI | 109 | UXX_Consumption_Yesterday_Cool_S | Energy consumption, yesterday cool | Wh/kWh | Read | |
| AI | 110 | UXX_Consumption_Today_Cool_S | Energy consumption, today cool | Wh/kWh | Read | |
| AI | 111 | UXX_Consumption_Total_Cool_S | Energy consumption, total cool | Wh/kWh | Read |
No points match these filters.
Object ID lookup: Intesis Midea VRF Gateway IN770 point IDs by name
BO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)MO2FanSpeed extended (all units)MO3Vane Position LEFT/RIGHT (all units)MO4Vane Position UP/DOWN (all units)BO1Vane Position Swing (all units)AO0Temperature Setpoint (all units)BO2Operating mode force (all Units)BO3Remote control lock (all units)AI10000OUXX_Unit Error CodeBI10000OUXX_Communication Error OUBI100UXX_On/Off_SBO100UXX_On/Off_CMI100UXX_Mode_SMO100UXX_Mode_CAI100UXX_Setpoint_SAO100UXX_Setpoint_CMI101UXX_FanSpeed_SMO101UXX_FanSpeed_CMI102UXX_FanSpeed Extended_SMO102UXX_FanSpeed Extended_CBI101UXX_Vane position swing_SBO101UXX_Vane position swing_CMI103UXX_Vane Position Left/Right_SMO103UXX_Vane Position Left/Right_CMI104UXX_Vane Position Up/Down_SMO104UXX_Vane Position Up/Down_CAI101UXX_Room TemperatureAI102UXX_Unit Error CodeAI112UXX_Unit Error Code ExtendedBI102UXX_Communication Error IUBI103UXX_Remote control lock_SBO102UXX_Remote control lock_CBI107UXX_Control lock_Mode Heat_SBO106UXX_Control lock_Mode Heat_CBI108UXX_Control lock_Mode Cool_SBO107UXX_Control lock_Mode Cool_CBI109UXX_Control lock_Mode Fan_SBO108UXX_Control lock_Mode Fan_CBI104UXX_Operating mode force_SBO103UXX_Operating mode force_CAI103UXX_Consumption_Yesterday_SAI104UXX_Consumption_Today_SAI105UXX_Consumption_Total_SAI106UXX_Consumption_Yesterday_Heat_SAI107UXX_Consumption_Today_Heat_SAI108UXX_Consumption_Total_Heat_SAI109UXX_Consumption_Yesterday_Cool_SAI110UXX_Consumption_Today_Cool_SAI111UXX_Consumption_Total_Cool_S
Integration notes
- Indoor unit instance = (IU x 100) + offset, IU = unit index in Intesis MAPS; index 1 is shown (100-112).
- Outdoor unit instance = (OU x 10000) + offset; OU 1 is shown (10000).
- The BACnet table has no read/write column; access is inferred from object type.
- Consumption objects report Wh or kWh as set in MAPS.
- The manual names INBACMID004I000 (listed separately) as its legacy order code.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
How many BACnet points does the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) have?
This list has 51 BACnet objects: 14 analog inputs, 2 analog outputs, 9 binary inputs, 11 binary outputs, 5 multi-state inputs, 10 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet points are writable?
23 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet documentation?
The source is 700 Series Air Gateway IN770AIR***O000 - Midea Commercial and VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2025-12-09 v1.0.22, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770midxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?
Start with BO 100 UXX_On/Off_C (Start/stop indoor unit); MO 100 UXX_Mode_C (Mode command); AO 100 UXX_Setpoint_C (Setpoint command); MO 101 UXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 UXX_On/Off_S (Run status); AI 100 UXX_Setpoint_S (Setpoint in use); AI 101 UXX_Room Temperature (Indoor unit room temperature, °C); BI 102 UXX_Communication Error IU (Unit offline on the Midea bus); AI 102 UXX_Unit Error Code (Fault code (0 = no error)).
How do I enable BMS control of the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?
No enable point is documented. UXX_Remote control lock_C (BO 102) locks the remote controller of that unit.
How do I check these points on the real IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - VRF BACnet gateway (Fujitsu, multi-unit)
Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
Fujitsu VRF systems (outdoor units 0-11, indoor units 1-64) integrated through the Intesis 700 Series Air gateway IN775FGL***O000.
Also known as: IN775FGL, IN775FGLO000, IN775FGL***O000, 700 Series Air Fujitsu, Intesis Fujitsu VRF BACnet gateway, HMS Intesis Fujitsu VRF, Fujitsu Airstage VRF BACnet - VRF BACnet gateway (Mitsubishi Heavy Industries, multi-unit)
Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
Mitsubishi Heavy Industries VRF systems (up to 128 indoor units, or 80 with up to 12 monitored outdoor units on the large license) through the Intesis 700 Series Air gateway IN776MHI***O000.
Also known as: IN776MHI, IN776MHIO000, IN776MHI***O000, IN776MHI00LO000, 700 Series Air MHI, Intesis MHI VRF BACnet gateway, Mitsubishi Heavy Industries VRF BACnet, MHI KX VRF BACnet - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway IN770AIR***O000 - Midea Commercial and VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.0.22. Object names, instances and units are reproduced as published; descriptions are our own.