- Home
- BACnet points lists
- Intesis
- IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
VRF BACnet gateway (multiple indoor units, H-Link) · BACnet points list
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) BACnet points list
Updated 6 November 2026
Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP on a Hitachi or Hisense H-Link bus. It publishes gateway-wide commands, a block of outdoor-unit objects at (OU address x 25) + 20000 and a block of indoor-unit objects at (IU address x 100): on/off, mode, setpoint, fan, louver, coil and air temperatures, error code, filter, remote-controller permissions, dehumidification and energy consumption.
This page lists 60 BACnet objects for the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
- Equipment
- VRF BACnet gateway (multiple indoor units, H-Link)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 60 (16 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Wire the H-Link (TB2) bus to Port A (A1/A2), pick BACnet IP or BACnet MS/TP in Intesis MAPS, scan or add the units, send the project, then map each indoor unit's _C commands and _S status objects from its (IU address x 100) block. Instances 0-2 command every unit at once.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | OXXUXX_On/Off_C | Start/stop indoor unit | Command |
| MO 100 | OXXUXX_Mode_C | Mode command | Command |
| AO 100 | OXXUXX_Setpoint_C | Setpoint command | Command |
| MO 101 | OXXUXX_FanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | OXXUXX_On/Off_S | Run status | Read |
| AI 100 | OXXUXX_Setpoint_S | Setpoint in use | Read |
| AI 102 | OXXUXX_Inlet Temp. | Return air temperature | Read |
| BI 102 | OXXUXX_Communication Status | Unit present on H-Link | Read |
| AI 106 | OXXUXX_Unit Error code | Fault code | Read |
Enable & remote start
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 102-105).
Network setup
- BACnet IP: DHCP for 30 seconds at first start-up, then the default IP 192.168.100.246.
- BACnet MS/TP uses the gateway's EIA-485 port.
- Units are found with the scan function in Intesis MAPS; send the project to the gateway after changes.
- With a Hitachi CSNET Manager on the bus the fan speed list shrinks to Low/Mid/High.
Watch out for
- On/Off, Mode, FanSpeed, Vane and Setpoint at instances 0-2 (BO 0, MO 0-2, AO 0) act on all units at once.
- Instance numbers follow the IU/OU address, so readdressing a unit changes its instances.
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 0 | On/Off (all units) | On/Off (all units) | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode (all units) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MO | 1 | FanSpeed (all units) | FanSpeed (all units) | Command | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ (with a CSNET Manager: 1=Low, 2=Mid, 3=High) | |
| MO | 2 | Vane Position (all units) | Vane Position (all units) | Command | 1=Auto, 2..8=Pos1..Pos7 | |
| AO | 0 | Temperature Setpoint (all units) | Temperature Setpoint (all units) | °C | Command | |
| AI | 20000 | OUXX_Outdoor Air Temp. | Outdoor Air Temp. | °C | Read | |
| AI | 20001 | OUXX_Comp.Top Temp. | Comp.Top Temp. | °C | Read | |
| AI | 20002 | OUXX_Total Real Comp. Freq. | Total Real Comp. Freq. | Hz | Read | |
| AI | 20003 | OUXX_Total Comp. Current | Total Comp. Current | A | Read | |
| AI | 20004 | OUXX_Out Exp. Valve 1 Open | Out Exp. Valve 1 Open | % | Read | |
| AI | 20005 | OUXX_Discharge Pressure | Discharge Pressure | MPa | Read | |
| AI | 20006 | OUXX_Suction Pressure | Suction Pressure | MPa | Read | |
| BI | 20000 | OUXX_Communication Status | Communication Status | Read | 0=Not Exist, 1=Exist | |
| BImin | 100 | OXXUXX_On/Off_S | On/Off (status) | Read | 0=Off, 1=On | |
| BOmin | 100 | OXXUXX_On/Off_C | On/Off (command) | Command | 0=Off, 1=On | |
| MI | 100 | OXXUXX_Mode_S | Mode (status) | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MOmin | 100 | OXXUXX_Mode_C | Mode (command) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | OXXUXX_Setpoint_S | Setpoint (status) | °C | Read | |
| AOmin | 100 | OXXUXX_Setpoint_C | Setpoint (command) | °C | Command | |
| MI | 101 | OXXUXX_FanSpeed_S | FanSpeed (status) | Read | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ (with a CSNET Manager: 1=Low, 2=Mid, 3=High) | |
| MOmin | 101 | OXXUXX_FanSpeed_C | FanSpeed (command) | Command | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ (with a CSNET Manager: 1=Low, 2=Mid, 3=High) | |
| MI | 102 | OXXUXX_Vane Position_S | Vane Position (status) | Read | 1=Auto, 2..8=Pos1..Pos7 | |
| MO | 102 | OXXUXX_Vane Position_C | Vane Position (command) | Command | 1=Auto, 2..8=Pos1..Pos7 | |
| AI | 101 | OXXUXX_Remote Sensor Temp. | Remote Sensor Temp. | °C | Read | |
| AImin | 102 | OXXUXX_Inlet Temp. | Inlet Temp. | °C | Read | |
| AI | 103 | OXXUXX_Outlet Temp. | Outlet Temp. | °C | Read | |
| AI | 104 | OXXUXX_GasPipe Temp. | GasPipe Temp. | °C | Read | |
| AI | 105 | OXXUXX_LiquidPipe Temp. | LiquidPipe Temp. | °C | Read | |
| AImin | 106 | OXXUXX_Unit Error code | Unit error code | Read | ||
| BI | 101 | OXXUXX_FilterSign | FilterSign | Read | 0=Normal, 1=Alarm | |
| BO | 101 | OXXUXX_FilterReset | FilterReset | Command | 1=Reset | |
| BImin | 102 | OXXUXX_Communication Status | Communication Status | Read | 0=Not Exist, 1=Exist | |
| BI | 103 | OXXUXX_Allow On/Off from RC_S | Allow On/Off from RC (status) | Read | 0=Allowed, 1=Not allowed | |
| BO | 102 | OXXUXX_Allow On/Off from RC_C | Allow On/Off from RC (command) | Command | 0=Allowed, 1=Not allowed | |
| BI | 104 | OXXUXX_Allow Mode from RC_S | Allow Mode from RC (status) | Read | 0=Allowed, 1=Not allowed | |
| BO | 103 | OXXUXX_Allow Mode from RC_C | Allow Mode from RC (command) | Command | 0=Allowed, 1=Not allowed | |
| BI | 105 | OXXUXX_Allow Setpoint from RC_S | Allow Setpoint from RC (status) | Read | 0=Allowed, 1=Not allowed | |
| BO | 104 | OXXUXX_Allow Setpoint from RC_C | Allow Setpoint from RC (command) | Command | 0=Allowed, 1=Not allowed | |
| BI | 106 | OXXUXX_Allow Fan from RC_S | Allow Fan from RC (status) | Read | 0=Allowed, 1=Not allowed | |
| BO | 105 | OXXUXX_Allow Fan from RC_C | Allow Fan from RC (command) | Command | 0=Allowed, 1=Not allowed | |
| MI | 103 | OXXUXX_Unit type | Unit type | Read | 1=Not Defined, 2=SS, 3=FC, 4=VRF, 5=IU, 6=ES | |
| AI | 107 | OXXUXX_Unit Address | Unit Address (0-63) | Read | ||
| AI | 108 | OXXUXX_System Address | System Address (0-63) | Read | ||
| BI | 107 | OXXUXX_Dehumidification | Dehumidification | Read | 0=Disabled, 1=Enabled | |
| MI | 104 | OXXUXX_Dehum. Correction_S | Dehum. Correction (status) | Read | 1=0, 2=(-1), 3=(-2) | |
| MO | 103 | OXXUXX_Dehum. Correction_C | Dehum. Correction (command) | Command | 1=0, 2=(-1), 3=(-2) | |
| AI | 109 | OXXUXX_Comp. Stop Cause | Comp. Stop Cause | Read | 255=Operation Off; other values per the Hitachi manual | |
| AI | 110 | OXXUXX_Exp. Valve Open | Exp. Valve Open | % | Read | |
| MI | 105 | OXXUXX_Operat. Condition | Operat. Condition | Read | 1=Off, 2=Thermo Off, 3=Thermo On, 4=Alarm | |
| AI | 111 | OXXUXX_RC SW Temp. | RC SW Temp. | °C | Read | |
| BI | 108 | OXXUXX_RC SW Config | RC SW Config | Read | 0=Without RCS, 1=With RCS | |
| AI | 112 | OXXUXX_Consumption Yesterday_S | Consumption Yesterday (status) | Wh/kWh | Read | |
| AI | 113 | OXXUXX_Consumption Today_S | Consumption Today (status) | Wh/kWh | Read | |
| AI | 114 | OXXUXX_Consumption Total_S | Consumption Total (status) | Wh/kWh | Read | |
| AI | 115 | OXXUXX_Consumption Yesterday_S Heat | Consumption Yesterday, heat (status) | Wh/kWh | Read | |
| AI | 116 | OXXUXX_Consumption Today_S Heat | Consumption Today, heat (status) | Wh/kWh | Read | |
| AI | 117 | OXXUXX_Consumption Total_S Heat | Consumption Total, heat (status) | Wh/kWh | Read | |
| AI | 118 | OXXUXX_Consumption Yesterday_S Cool | Consumption Yesterday, cool (status) | Wh/kWh | Read | |
| AI | 119 | OXXUXX_Consumption Today_S Cool | Consumption Today, cool (status) | Wh/kWh | Read | |
| AI | 120 | OXXUXX_Consumption Total_S Cool | Consumption Total, cool (status) | Wh/kWh | Read |
No points match these filters.
Object ID lookup: Intesis Hitachi/Hisense VRF Gateway IN770 point IDs by name
BO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)MO2Vane Position (all units)AO0Temperature Setpoint (all units)AI20000OUXX_Outdoor Air Temp.AI20001OUXX_Comp.Top Temp.AI20002OUXX_Total Real Comp. Freq.AI20003OUXX_Total Comp. CurrentAI20004OUXX_Out Exp. Valve 1 OpenAI20005OUXX_Discharge PressureAI20006OUXX_Suction PressureBI20000OUXX_Communication StatusBI100OXXUXX_On/Off_SBO100OXXUXX_On/Off_CMI100OXXUXX_Mode_SMO100OXXUXX_Mode_CAI100OXXUXX_Setpoint_SAO100OXXUXX_Setpoint_CMI101OXXUXX_FanSpeed_SMO101OXXUXX_FanSpeed_CMI102OXXUXX_Vane Position_SMO102OXXUXX_Vane Position_CAI101OXXUXX_Remote Sensor Temp.AI102OXXUXX_Inlet Temp.AI103OXXUXX_Outlet Temp.AI104OXXUXX_GasPipe Temp.AI105OXXUXX_LiquidPipe Temp.AI106OXXUXX_Unit Error codeBI101OXXUXX_FilterSignBO101OXXUXX_FilterResetBI102OXXUXX_Communication StatusBI103OXXUXX_Allow On/Off from RC_SBO102OXXUXX_Allow On/Off from RC_CBI104OXXUXX_Allow Mode from RC_SBO103OXXUXX_Allow Mode from RC_CBI105OXXUXX_Allow Setpoint from RC_SBO104OXXUXX_Allow Setpoint from RC_CBI106OXXUXX_Allow Fan from RC_SBO105OXXUXX_Allow Fan from RC_CMI103OXXUXX_Unit typeAI107OXXUXX_Unit AddressAI108OXXUXX_System AddressBI107OXXUXX_DehumidificationMI104OXXUXX_Dehum. Correction_SMO103OXXUXX_Dehum. Correction_CAI109OXXUXX_Comp. Stop CauseAI110OXXUXX_Exp. Valve OpenMI105OXXUXX_Operat. ConditionAI111OXXUXX_RC SW Temp.BI108OXXUXX_RC SW ConfigAI112OXXUXX_Consumption Yesterday_SAI113OXXUXX_Consumption Today_SAI114OXXUXX_Consumption Total_SAI115OXXUXX_Consumption Yesterday_S HeatAI116OXXUXX_Consumption Today_S HeatAI117OXXUXX_Consumption Total_S HeatAI118OXXUXX_Consumption Yesterday_S CoolAI119OXXUXX_Consumption Today_S CoolAI120OXXUXX_Consumption Total_S Cool
Integration notes
- Indoor unit instance = (IU address x 100) + offset; IU address 1 is shown (100-120). Outdoor unit instance = (OU address x 25) + 20000 + offset; OU address 0 is shown (20000-20006).
- The Hitachi and Hisense manuals (both v1.1.8, 2025-12-09) print the same BACnet object table; this one entry covers both.
- With an SPX-RAMHLK adapter only part of the objects is supported (marked in the Hitachi manual).
- The BACnet table has no read/write column; access is inferred from object type (outputs commandable, inputs read-only).
- Consumption objects report Wh or kWh as set in Intesis MAPS.
- Replaces the older INBACHIT016O000/064O000 BACnet server (listed separately), which used different outdoor-unit instances.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
How many BACnet points does the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) have?
This list has 60 BACnet objects: 28 analog inputs, 2 analog outputs, 10 binary inputs, 7 binary outputs, 6 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) BACnet points are writable?
16 of the 60 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) BACnet documentation?
The source is 700 Series Air Gateway IN770AIR***O000 - Hitachi VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2025-12-09 v1.1.8, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770hitxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)?
Start with BO 100 OXXUXX_On/Off_C (Start/stop indoor unit); MO 100 OXXUXX_Mode_C (Mode command); AO 100 OXXUXX_Setpoint_C (Setpoint command); MO 101 OXXUXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 OXXUXX_On/Off_S (Run status); AI 100 OXXUXX_Setpoint_S (Setpoint in use); AI 102 OXXUXX_Inlet Temp. (Return air temperature); BI 102 OXXUXX_Communication Status (Unit present on H-Link); AI 106 OXXUXX_Unit Error code (Fault code).
How do I enable BMS control of the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)?
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 102-105).
How do I check these points on the real IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - VRF BACnet gateway (Fujitsu, multi-unit)
Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
Fujitsu VRF systems (outdoor units 0-11, indoor units 1-64) integrated through the Intesis 700 Series Air gateway IN775FGL***O000.
Also known as: IN775FGL, IN775FGLO000, IN775FGL***O000, 700 Series Air Fujitsu, Intesis Fujitsu VRF BACnet gateway, HMS Intesis Fujitsu VRF, Fujitsu Airstage VRF BACnet - VRF BACnet gateway (Mitsubishi Heavy Industries, multi-unit)
Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
Mitsubishi Heavy Industries VRF systems (up to 128 indoor units, or 80 with up to 12 monitored outdoor units on the large license) through the Intesis 700 Series Air gateway IN776MHI***O000.
Also known as: IN776MHI, IN776MHIO000, IN776MHI***O000, IN776MHI00LO000, 700 Series Air MHI, Intesis MHI VRF BACnet gateway, Mitsubishi Heavy Industries VRF BACnet, MHI KX VRF BACnet - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway IN770AIR***O000 - Hitachi VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.1.8. Object names, instances and units are reproduced as published; descriptions are our own.