- INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units) · BACnet points list
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet points list
Updated 28 October 2026
An Intesis BACnet server on the Samsung NASA R1/R2 bus that serves BACnet IP and BACnet MS/TP. It publishes outdoor-unit communication alarms, gateway-wide commands and one block of objects per indoor unit at (identifier x 100). The manual also defines different object sets for hot-water (HE/HT/EHS), AHU, ERV/ERV+ and chiller unit types; this file shows the standard indoor unit (IU) set.
This page lists 54 BACnet objects for the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
- Equipment
- VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 54 (20 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246
- Also known as
- Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA
- Brands covered
- Samsung
Instance calculator. This list prints one unit; the other units follow a formula. Intesis INBACSAM004O000-064O000 (Samsung NASA) instance calculator →
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Connect the NASA R1/R2 bus to Port A (A3 R1/+, A4 R2/-), scan the bus in Intesis MAPS, assign each unit an identifier and send the project; then map each indoor unit's objects from its (identifier x 100) block. Gateway-wide objects at low instances command all units.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | OxxUxx_On/Off_C | Start/stop indoor unit | Command |
| MO 100 | OxxUxx_Mode IU/AHU_C | Mode command | Command |
| AO 100 | OxxUxx_Setpoint_C | Setpoint command | Command |
| MO 101 | OxxUxx_FanSpeed_C | Fan speed command (4 = auto) | Command |
| BI 100 | OxxUxx_On/Off_S | Run status | Read |
| AI 100 | OxxUxx_Setpoint_S | Setpoint in use | Read |
| AI 101 | OxxUxx_Room_Temperature | Indoor unit room temperature, °C | Read |
| MI 102 | OxxUxx_Communication Status | Link flags; EXST = unit found on the NASA bus | Read |
| AI 105 | OxxUxx_Unit Error code | Fault code | Read |
Enable & remote start
No enable point is documented. OxxUxx_RC Restriction_C (BO 103) restricts the unit's remote controller.
Network setup
- Default device instance 246, configurable in MAPS.
- BACnet IP: default IP 192.168.100.246, DHCP enabled by default.
- Indoor units are addressed 0-63 and outdoor units 0-15 on the NASA bus; the identifier xxx (1-64) used in instance numbers is assigned in MAPS.
Watch out for
- Mode state numbering is Samsung's: 1=Heat, 2=Dry, 3=Fan, 4=Cool, 5=Auto (not the usual Intesis order).
- Check the Unit type object (MI 103) before mapping: other unit types use different objects in the same block.
- Manual addressing may be needed on the outdoor units if BI 16 OU Addressing Error is active.
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 0 | OU00_Communication Error OU | Outdoor unit00 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 1 | OU01_Communication Error OU | Outdoor unit01 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 2 | OU02_Communication Error OU | Outdoor unit02 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 3 | OU03_Communication Error OU | Outdoor unit03 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 4 | OU04_Communication Error OU | Outdoor unit04 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 5 | OU05_Communication Error OU | Outdoor unit05 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 6 | OU06_Communication Error OU | Outdoor unit06 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 7 | OU07_Communication Error OU | Outdoor unit07 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 8 | OU08_Communication Error OU | Outdoor unit08 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 9 | OU09_Communication Error OU | Outdoor unit09 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 10 | OU10_Communication Error OU | Outdoor unit10 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 11 | OU11_Communication Error OU | Outdoor unit11 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 12 | OU12_Communication Error OU | Outdoor unit12 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 13 | OU13_Communication Error OU | Outdoor unit13 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 14 | OU14_Communication Error OU | Outdoor unit14 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 15 | OU15_Communication Error OU | Outdoor unit15 Communication Error outdoor unit | Read | 0=No Error, 1=Error | |
| BI | 16 | OU Addressing Error | Outdoor unit Addressing Error | Read | 0=OU Addressing OK, 1=Manual Addr in OU required | |
| BO | 0 | On/Off (all units) | On/Off (all units) | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode (all units) | Command | 1=Heat, 2=Dry, 3=Fan, 4=Cool, 5=Auto, 6=Cool Storage, 7=Hot Water | |
| MO | 1 | FanSpeed (all units) | FanSpeed (all units) | Command | 1=Low, 2=Mid, 3=High, 4=Auto | |
| BO | 1 | Vane position swing (all units) | Vane position swing (all units) | Command | 0=Swing Off, 1=Swing On | |
| AO | 0 | Temperature Setpoint (all units) | Temperature Setpoint (all units) | °C | Command | |
| BO | 2 | Vent. On/Off (all units) | Vent. On/Off (all units) | Command | 0=Off, 1=On | |
| BO | 3 | Hot Water On/Off (all units) | Hot Water On/Off (all units) | Command | 0=Off, 1=On | |
| BImin | 100 | OxxUxx_On/Off_S | On/Off (status) | Read | 0=Off, 1=On | |
| BOmin | 100 | OxxUxx_On/Off_C | On/Off (command) | Command | 0=Off, 1=On | |
| MI | 100 | OxxUxx_Mode IU/AHU_S | Mode indoor unit/AHU (status) | Read | 1=Heat, 2=Dry, 3=Fan, 4=Cool, 5=Auto, 6=Not Valid, 7=Not Valid | |
| MOmin | 100 | OxxUxx_Mode IU/AHU_C | Mode indoor unit/AHU (command) | Command | 1=Heat, 2=Dry, 3=Fan, 4=Cool, 5=Auto, 6=Not Valid, 7=Not Valid | |
| AImin | 100 | OxxUxx_Setpoint_S | Setpoint (status) | °C | Read | |
| AOmin | 100 | OxxUxx_Setpoint_C | Setpoint (command) | °C | Command | |
| MI | 101 | OxxUxx_FanSpeed_S | FanSpeed (status) | Read | 1=Low, 2=Mid, 3=High, 4=Auto | |
| MOmin | 101 | OxxUxx_FanSpeed_C | FanSpeed (command) | Command | 1=Low, 2=Mid, 3=High, 4=Auto | |
| BI | 101 | OxxUxx_Vane position swing_S | Vane position swing (status) | Read | 0=Off, 1=On | |
| BO | 101 | OxxUxx_Vane position swing_C | Vane position swing (command) | Command | 0=Off, 1=On | |
| AImin | 101 | OxxUxx_Room_Temperature | Room Temperature | °C | Read | |
| AI | 102 | OxxUxx_Disch.Setpoint Cool IU_S | Discharge Setpoint Cool indoor unit (status) | °C | Read | |
| AO | 101 | OxxUxx_Disch.Setpoint Cool IU_C | Discharge Setpoint Cool indoor unit (command) | °C | Command | |
| AI | 103 | OxxUxx_Disch.Setpoint Heat IU_S | Discharge Setpoint Heat indoor unit (status) | °C | Read | |
| AO | 102 | OxxUxx_Disch.Setpoint Heat IU_C | Discharge Setpoint Heat indoor unit (command) | °C | Command | |
| AI | 104 | OxxUxx_Disch. Current Temp. | Discharge Current temperature | °C | Read | |
| AImin | 105 | OxxUxx_Unit Error code | Unit Error code | Read | ||
| BI | 102 | OxxUxx_FilterSign | FilterSign | Read | 0=Normal, 1=Alarm | |
| BO | 102 | OxxUxx_FilterReset | FilterReset | Command | 0=No reset, 1=Reset | |
| MImin | 102 | OxxUxx_Communication Status | Communication Status | Read | 1=-/-/-/-, 2=-/-/-/EXST, 3=-/-/RDY/-, 4=-/-/RDY/EXST, 5=-/DTUP/-/-, 6=-/DTUP/-/EXST, 7=-/DTUP/RDY/-, 8=-/DTUP/RDY/EXST, 9=TPOK/-/-/-, 10=TPOK/-/-/EXST, 11=TPOK/-/RDY/-, 12=TPOK/-/RDY/EXST, 13=TPOK/DTUP/-/-, 14=TPOK/DTUP/-/EXST, 15=TPOK/DTUP/RDY/-, 16=TPOK/DTUP/RDY/EXST | |
| BI | 103 | OxxUxx_RC Restriction_S | Remote controller Restriction (status) | Read | 0=No restriction, 1=Restriction | |
| BO | 103 | OxxUxx_RC Restriction_C | Remote controller Restriction (command) | Command | 0=No restriction, 1=Restriction | |
| BO | 104 | OxxUxx_Buzzer Sound | Buzzer Sound | Command | 0=Buzzer On, 1=Buzzer Off | |
| MI | 103 | OxxUxx_Unit type | Unit type | Read | 1=Not Defined, 2=IU, 3=HE, 4=HT, 5=AHU, 6=ERV, 7=ERV+, 8=EHS, 9=CHILLER | |
| BI | 106 | OXXUXX_WindFree_S | WindFree (status) | Read | 0=Disable, 1=Enable | |
| BO | 107 | OXXUXX_WindFree_C | WindFree (command) | Command | 0=Disable, 1=Enable | |
| BI | 107 | OXXUXX_Air Clean_S | Air Clean (status) | Read | 0=Disable, 1=Enable | |
| BO | 108 | OXXUXX_Air Clean_C | Air Clean (command) | Command | 0=Disable, 1=Enable | |
| MI | 107 | OXXUXX_360 CST Air Flow_S | 360 CST Air Flow (status) | Read | 1=Spot, 2=Mid, 3=Wide, 4=Swing | |
| MO | 105 | OXXUXX_360 CST Air Flow_C | 360 CST Air Flow (command) | Command | 1=Spot, 2=Mid, 3=Wide, 4=Swing |
No points match these filters.
Object ID lookup: Intesis Samsung NASA Gateway INBACSAM064O000 point IDs by name
BI0OU00_Communication Error OUBI1OU01_Communication Error OUBI2OU02_Communication Error OUBI3OU03_Communication Error OUBI4OU04_Communication Error OUBI5OU05_Communication Error OUBI6OU06_Communication Error OUBI7OU07_Communication Error OUBI8OU08_Communication Error OUBI9OU09_Communication Error OUBI10OU10_Communication Error OUBI11OU11_Communication Error OUBI12OU12_Communication Error OUBI13OU13_Communication Error OUBI14OU14_Communication Error OUBI15OU15_Communication Error OUBI16OU Addressing ErrorBO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)BO1Vane position swing (all units)AO0Temperature Setpoint (all units)BO2Vent. On/Off (all units)BO3Hot Water On/Off (all units)BI100OxxUxx_On/Off_SBO100OxxUxx_On/Off_CMI100OxxUxx_Mode IU/AHU_SMO100OxxUxx_Mode IU/AHU_CAI100OxxUxx_Setpoint_SAO100OxxUxx_Setpoint_CMI101OxxUxx_FanSpeed_SMO101OxxUxx_FanSpeed_CBI101OxxUxx_Vane position swing_SBO101OxxUxx_Vane position swing_CAI101OxxUxx_Room_TemperatureAI102OxxUxx_Disch.Setpoint Cool IU_SAO101OxxUxx_Disch.Setpoint Cool IU_CAI103OxxUxx_Disch.Setpoint Heat IU_SAO102OxxUxx_Disch.Setpoint Heat IU_CAI104OxxUxx_Disch. Current Temp.AI105OxxUxx_Unit Error codeBI102OxxUxx_FilterSignBO102OxxUxx_FilterResetMI102OxxUxx_Communication StatusBI103OxxUxx_RC Restriction_SBO103OxxUxx_RC Restriction_CBO104OxxUxx_Buzzer SoundMI103OxxUxx_Unit typeBI106OXXUXX_WindFree_SBO107OXXUXX_WindFree_CBI107OXXUXX_Air Clean_SBO108OXXUXX_Air Clean_CMI107OXXUXX_360 CST Air Flow_SMO105OXXUXX_360 CST Air Flow_C
Integration notes
- Indoor unit instance = (xxx x 100) + offset, xxx = indoor unit identifier 1-64 (identifier 1 shown, 100-108).
- Outdoor communication-error objects are BI 0-15 for outdoor addresses 00-15; BI 16 flags an addressing problem.
- Hot-water, AHU, ERV, ERV+ and chiller units reuse the same instance block with a different object set (see manual).
- WindFree, Air Clean and 360 CST Air Flow objects apply only to indoor units that support them.
- Communication Status (MI) states combine NASA flags such as RDY, EXST and DTUP.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
How many BACnet points does the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) have?
This list has 54 BACnet objects: 6 analog inputs, 4 analog outputs, 23 binary inputs, 11 binary outputs, 5 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet points are writable?
20 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server) BACnet documentation?
The source is Intesis BACnet Server - Samsung NASA AC User's Manual, revision 01/2022 r1.3, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbacsamxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)?
Start with BO 100 OxxUxx_On/Off_C (Start/stop indoor unit); MO 100 OxxUxx_Mode IU/AHU_C (Mode command); AO 100 OxxUxx_Setpoint_C (Setpoint command); MO 101 OxxUxx_FanSpeed_C (Fan speed command (4 = auto)); BI 100 OxxUxx_On/Off_S (Run status); AI 100 OxxUxx_Setpoint_S (Setpoint in use); AI 101 OxxUxx_Room_Temperature (Indoor unit room temperature, °C); MI 102 OxxUxx_Communication Status (Link flags; EXST = unit found on the NASA bus); AI 105 OxxUxx_Unit Error code (Fault code).
How do I enable BMS control of the Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)?
No enable point is documented. OxxUxx_RC Restriction_C (BO 103) restricts the unit's remote controller.
How do I check these points on the real INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - VRF BACnet gateway (Fujitsu, multi-unit)
Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
Fujitsu VRF systems (outdoor units 0-11, indoor units 1-64) integrated through the Intesis 700 Series Air gateway IN775FGL***O000.
Also known as: IN775FGL, IN775FGLO000, IN775FGL***O000, 700 Series Air Fujitsu, Intesis Fujitsu VRF BACnet gateway, HMS Intesis Fujitsu VRF, Fujitsu Airstage VRF BACnet - VRF BACnet gateway (Mitsubishi Heavy Industries, multi-unit)
Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
Mitsubishi Heavy Industries VRF systems (up to 128 indoor units, or 80 with up to 12 monitored outdoor units on the large license) through the Intesis 700 Series Air gateway IN776MHI***O000.
Also known as: IN776MHI, IN776MHIO000, IN776MHI***O000, IN776MHI00LO000, 700 Series Air MHI, Intesis MHI VRF BACnet gateway, Mitsubishi Heavy Industries VRF BACnet, MHI KX VRF BACnet - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: Intesis BACnet Server - Samsung NASA AC User's Manual · rev. 01/2022 r1.3. Object names, instances and units are reproduced as published; descriptions are our own.