- INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
VRF BACnet gateway (up to 16 or 64 indoor units) · BACnet points list
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server) BACnet points list
Updated 28 October 2026
An Intesis BACnet server that connects to the Hitachi H-Link bus at the outdoor unit and publishes every configured indoor and outdoor unit as BACnet IP and BACnet MS/TP objects. Each indoor unit gets the same block of objects at a base instance of (unit index x 100); outdoor units get (address x 25) + 1000. Configuration is done with the Intesis MAPS tool.
This page lists 51 BACnet objects for the Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
- Equipment
- VRF BACnet gateway (up to 16 or 64 indoor units)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 51 (16 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246
- Also known as
- Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF
- Brands covered
- Hitachi
Instance calculator. This list prints one unit; the other units follow a formula. Intesis INBACHIT016O000 / 064O000 (Hitachi H-Link) instance calculator →
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Wire the gateway's Port A to the H-Link TB2 terminals, scan or enter the indoor/outdoor units in Intesis MAPS, send the configuration, then map each unit's _C command and _S status objects from its instance block. The 'all units' objects at instances 0-2 command every unit at once.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | OxxUxxOn/Off_C | Start/stop indoor unit | Command |
| MO 100 | OxxUxxMode_C | Mode command | Command |
| AO 100 | OxxUxxSetpoint_C | Setpoint command | Command |
| MO 101 | OxxUxxFanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | OxxUxxOn/Off_S | Run status | Read |
| AI 100 | OxxUxxSetpoint_S | Setpoint in use | Read |
| AI 102 | OxxUxxInlet Temp. | Return air temperature | Read |
| BI 102 | OxxUxxCommunication Status | Unit present on H-Link | Read |
| AI 106 | OxxUxxUnit Error code | Fault code | Read |
Enable & remote start
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 102-105).
Network setup
- Default device instance 246; it can be changed in Intesis MAPS.
- BACnet IP: default IP 192.168.100.246, DHCP enabled by default; BACnet MS/TP on Port B (B1 -, B2 +, B3 SNGD).
- Indoor unit index (xxx) is the unit's index in Intesis MAPS, which is not necessarily its H-Link address.
- After any change in MAPS the configuration must be sent to the gateway, which then reboots.
Watch out for
- Instance numbers follow the MAPS unit index, so changing a unit's index changes every instance number of that unit.
- On/Off, Mode, FanSpeed, Vane and Setpoint at instances 0-2 (BO 0, MO 0-2, AO 0) act on all units at once.
- Communication Status (BI 102) shows 0 when the address does not exist on the H-Link bus.
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 0 | On/Off (all units) | On/Off (all units) | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode (all units) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MO | 1 | FanSpeed (all units) | FanSpeed (all units) | Command | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ | |
| MO | 2 | Vane Position swing (all units) | Vane Position swing (all units) | Command | 1=Auto, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Pos6, 8=Pos7 | |
| AO | 0 | Temperature Setpoint (all units) | Temperature Setpoint (all units) | °C | Command | |
| AI | 1000 | OUxx_Outdoor Air Temp. | Outdoor Air temperature | °C | Read | |
| AI | 1001 | OUXX_Comp.Top Temp. | CompressorTop temperature | °C | Read | |
| AI | 1002 | OUXX_Total Real Comp. Freq. | Total Real Compressor Freq. | Hz | Read | |
| AI | 1003 | OUXX_Total Comp. Current | Total Compressor Current | A | Read | |
| AI | 1004 | OUXX_Out Exp. Valve 1 Open | Out Exp. Valve 1 Open | % | Read | |
| AI | 1005 | OUXX_Discharge Pressure | Discharge Pressure | MPa | Read | |
| AI | 1006 | OUXX_Suction Pressure | Suction Pressure | MPa | Read | |
| BI | 1000 | OUXX_Communication Status | Communication Status | Read | 0=Not Exist, 1=Exist | |
| BImin | 100 | OxxUxxOn/Off_S | On/Off (status) | Read | 0=Off, 1=On | |
| BOmin | 100 | OxxUxxOn/Off_C | On/Off (command) | Command | 0=Off, 1=On | |
| MI | 100 | OxxUxxMode_S | Mode (status) | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MOmin | 100 | OxxUxxMode_C | Mode (command) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | OxxUxxSetpoint_S | Setpoint (status) | °C | Read | |
| AOmin | 100 | OxxUxxSetpoint_C | Setpoint (command) | °C | Command | |
| MI | 101 | OxxUxxFanSpeed_S | FanSpeed (status) | Read | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ | |
| MOmin | 101 | OxxUxxFanSpeed_C | FanSpeed (command) | Command | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ | |
| MI | 102 | OxxUxxVane Position_S | Vane Position (status) | Read | 1=Auto, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Pos6, 8=Pos7 | |
| MO | 102 | OxxUxxVane Position_C | Vane Position (command) | Command | 1=Auto, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4, 6=Pos5, 7=Pos6, 8=Pos7 | |
| AI | 101 | OxxUxxRemote Sensor Temp. | Remote Sensor temperature | °C | Read | |
| AImin | 102 | OxxUxxInlet Temp. | Inlet temperature | °C | Read | |
| AI | 103 | OxxUxxOutlet Temp. | Outlet temperature | °C | Read | |
| AI | 104 | OxxUxxGasPipe Temp. | GasPipe temperature | °C | Read | |
| AI | 105 | OxxUxxLiquidPipe Temp. | LiquidPipe temperature | °C | Read | |
| AImin | 106 | OxxUxxUnit Error code | Unit Error code | Read | ||
| BI | 101 | OxxUxxFilterSign | FilterSign | Read | 0=Normal, 1=Alarm | |
| BO | 101 | OxxUxxFilterReset | FilterReset | Command | 0=No reset, 1=Reset | |
| BImin | 102 | OxxUxxCommunication Status | Communication Status | Read | 0=Not Exist, 1=Exist | |
| BI | 103 | OxxUxxAllow On/Off from RC_S | Allow On/Off from remote controller (status) | Read | 0=Allow, 1=Not allow | |
| BO | 102 | OxxUxxAllow On/Off from RC_C | Allow On/Off from remote controller (command) | Command | 0=Allow, 1=Not allow | |
| BI | 104 | OxxUxxAllow Mode from RC_S | Allow Mode from remote controller (status) | Read | 0=Allow, 1=Not allow | |
| BO | 103 | OxxUxxAllow Mode from RC_C | Allow Mode from remote controller (command) | Command | 0=Allow, 1=Not allow | |
| BI | 105 | OxxUxxAllow Setpoint from RC_S | Allow Setpoint from remote controller (status) | Read | 0=Allow, 1=Not allow | |
| BO | 104 | OxxUxxAllow Setpoint from RC_C | Allow Setpoint from remote controller (command) | Command | 0=Allow, 1=Not allow | |
| BI | 106 | OxxUxxAllow Fan from RC_S | Allow Fan from remote controller (status) | Read | 0=Allow, 1=Not allow | |
| BO | 105 | OxxUxxAllow Fan from RC_C | Allow Fan from remote controller (command) | Command | 0=Allow, 1=Not allow | |
| MI | 103 | OxxUxxUnit type | Unit type | Read | 1=Not Defined, 2=SS, 3=FC, 4=VRF, 5=IU, 6=ES | |
| AI | 107 | OxxUxxUnit Address | Unit Address (range 1..64) | Read | ||
| AI | 108 | OxxUxxSystem Address | System Address (range 1..64) | Read | ||
| BI | 107 | OxxUxxDehumidification | Dehumidification | Read | 0=Disabled, 1=Enabled | |
| MI | 104 | OxxUxxDehum. Correction_S | Dehum. Correction (status) | Read | 1=0, 2=(-1), 3=(-2) | |
| MO | 103 | OxxUxxDehum. Correction_C | Dehum. Correction (command) | Command | 1=0, 2=(-1), 3=(-2) | |
| AI | 109 | OxxUxxComp. Stop Cause | Compressor Stop Cause (range 255-Operation Off, Other-See manual) | Read | ||
| AI | 110 | OxxUxxExp. Valve Open | Exp. Valve Open (range 0..100) | Read | ||
| MI | 105 | OxxUxxOperat. Condition | Operat. Condition | Read | 1=Off, 2=Thermo Off, 3=Thermo On, 4=Alarm | |
| AI | 111 | OxxUxxRC SW Temp. | Remote controller SW temperature | °C | Read | |
| BI | 108 | OxxUxxRC SW Config | Remote controller SW Config | Read | 0=With RCS, 1=Without RCS |
No points match these filters.
Object ID lookup: Intesis Hitachi VRF Gateway INBACHIT064O000 point IDs by name
BO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)MO2Vane Position swing (all units)AO0Temperature Setpoint (all units)AI1000OUxx_Outdoor Air Temp.AI1001OUXX_Comp.Top Temp.AI1002OUXX_Total Real Comp. Freq.AI1003OUXX_Total Comp. CurrentAI1004OUXX_Out Exp. Valve 1 OpenAI1005OUXX_Discharge PressureAI1006OUXX_Suction PressureBI1000OUXX_Communication StatusBI100OxxUxxOn/Off_SBO100OxxUxxOn/Off_CMI100OxxUxxMode_SMO100OxxUxxMode_CAI100OxxUxxSetpoint_SAO100OxxUxxSetpoint_CMI101OxxUxxFanSpeed_SMO101OxxUxxFanSpeed_CMI102OxxUxxVane Position_SMO102OxxUxxVane Position_CAI101OxxUxxRemote Sensor Temp.AI102OxxUxxInlet Temp.AI103OxxUxxOutlet Temp.AI104OxxUxxGasPipe Temp.AI105OxxUxxLiquidPipe Temp.AI106OxxUxxUnit Error codeBI101OxxUxxFilterSignBO101OxxUxxFilterResetBI102OxxUxxCommunication StatusBI103OxxUxxAllow On/Off from RC_SBO102OxxUxxAllow On/Off from RC_CBI104OxxUxxAllow Mode from RC_SBO103OxxUxxAllow Mode from RC_CBI105OxxUxxAllow Setpoint from RC_SBO104OxxUxxAllow Setpoint from RC_CBI106OxxUxxAllow Fan from RC_SBO105OxxUxxAllow Fan from RC_CMI103OxxUxxUnit typeAI107OxxUxxUnit AddressAI108OxxUxxSystem AddressBI107OxxUxxDehumidificationMI104OxxUxxDehum. Correction_SMO103OxxUxxDehum. Correction_CAI109OxxUxxComp. Stop CauseAI110OxxUxxExp. Valve OpenMI105OxxUxxOperat. ConditionAI111OxxUxxRC SW Temp.BI108OxxUxxRC SW Config
Integration notes
- Points are shown for the gateway-wide 'all units' commands, outdoor unit address 0 and indoor unit index 1 only.
- Indoor unit instance = (xxx x 100) + offset, where xxx is the unit index in Intesis MAPS (index 1 gives 100-111 here).
- Outdoor unit instance = (xx x 25) + 1000 + offset, where xx is the outdoor unit address (address 0 shown, 1000-1006).
- Object names carry the Oxx/Uxx (or OUxx) address prefix, replaced by the real addresses on site.
- Vane and Operat. Condition state lists are taken from the object-detail pages (the summary table abbreviates them).
- FanSpeed High+ (5) appears in the summary table but not in the object-detail state table, and RC SW Config's detail page prints its states reversed (0=Without RCS, 1=With RCS); verify on site.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
How many BACnet points does the Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server) have?
This list has 51 BACnet objects: 19 analog inputs, 2 analog outputs, 10 binary inputs, 7 binary outputs, 6 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server) BACnet points are writable?
16 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server) BACnet documentation?
The source is Intesis BACnet Server - Hitachi VRF User's Manual, revision 2022/06 r1.2, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbachitxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)?
Start with BO 100 OxxUxxOn/Off_C (Start/stop indoor unit); MO 100 OxxUxxMode_C (Mode command); AO 100 OxxUxxSetpoint_C (Setpoint command); MO 101 OxxUxxFanSpeed_C (Fan speed command (1 = auto)); BI 100 OxxUxxOn/Off_S (Run status); AI 100 OxxUxxSetpoint_S (Setpoint in use); AI 102 OxxUxxInlet Temp. (Return air temperature); BI 102 OxxUxxCommunication Status (Unit present on H-Link); AI 106 OxxUxxUnit Error code (Fault code).
How do I enable BMS control of the Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)?
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 102-105).
How do I check these points on the real INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - VRF BACnet gateway (Fujitsu, multi-unit)
Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
Fujitsu VRF systems (outdoor units 0-11, indoor units 1-64) integrated through the Intesis 700 Series Air gateway IN775FGL***O000.
Also known as: IN775FGL, IN775FGLO000, IN775FGL***O000, 700 Series Air Fujitsu, Intesis Fujitsu VRF BACnet gateway, HMS Intesis Fujitsu VRF, Fujitsu Airstage VRF BACnet - VRF BACnet gateway (Mitsubishi Heavy Industries, multi-unit)
Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
Mitsubishi Heavy Industries VRF systems (up to 128 indoor units, or 80 with up to 12 monitored outdoor units on the large license) through the Intesis 700 Series Air gateway IN776MHI***O000.
Also known as: IN776MHI, IN776MHIO000, IN776MHI***O000, IN776MHI00LO000, 700 Series Air MHI, Intesis MHI VRF BACnet gateway, Mitsubishi Heavy Industries VRF BACnet, MHI KX VRF BACnet - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: Intesis BACnet Server - Hitachi VRF User's Manual · rev. 2022/06 r1.2. Object names, instances and units are reproduced as published; descriptions are our own.