- Humidifiers
Equipment type
Humidifiers BACnet points lists
Updated 12 November 2026
37 humidifiers BACnet points lists from 7 manufacturers — Armstrong International, CAREL, Condair, Devatec, DriSteem, Neptronic, Pure Humidifier. Each one has the full object table, the minimum points an integrator needs, enable and heartbeat notes, and CSV/EDE downloads. Click a column heading to sort.
37 of 37 shown
Unit type
| Type | Download | ||||
|---|---|---|---|---|---|
| Armstrong International | Armstrong International HumidiClean HC-6000 series (HC-6100/6300/6500/6700)Armstrong HumidiClean HC-6100, HC-6300, HC-6500 and HC-6700 ionic bed electric steam humidifiers with the FieldServer ProtoNode BACnet gateway. · 539D-EN V2.1 Also known as: HumidiClean, HC-6000, HC-6100, HC-6300, HC-6500, HC-6700, Armstrong HumidiClean, 539D-EN, ionic bed humidifier | Steam | 59 | 33 | CSVEDE |
| CAREL | CAREL gaSteam (UG) gas-fired humidifierCAREL gaSteam UG gas-fired isothermal steam humidifiers (indoor and outdoor versions, single unit or Main/Secondary pairs). · +0300122EN rel. 1.4 Also known as: gaSteam, UG, UG045, UG090, UG180, CAREL gas-fired steam humidifier, +0300122EN | Steam | 350 | 350 | CSVEDE |
| CAREL | CAREL heaterSteam 4 (UR) process / titaniumCAREL heaterSteam UR electric heater steam humidifiers (process and titanium versions) with the c.pHC-based controller, manual +0300087EN. · +0300087EN rel. 1.7 Also known as: heaterSteam, heaterSteam 4, heaterSteam process, heaterSteam titanium, UR, URH, CAREL electric resistance humidifier, +0300087EN | Steam | 248 | 123 | CSVEDE |
| CAREL | CAREL heaterSteam UR (2018 manual, before heaterSteam 4)CAREL heaterSteam UR electric heater steam humidifiers of the generation before heaterSteam 4, as covered by manual +0300080EN rel. 1.4 (2018). · +0300080EN rel. 1.4 Also known as: heaterSteam, heaterSteam UR, UR002, UR080, CAREL resistance steam humidifier, +0300080EN | Steam | 188 | 76 | CSVEDE |
| CAREL | CAREL humiFog direct (UA) high-pressure atomising humidifierCAREL humiFog direct UA pumping stations with c.pHC controller, one or two humidification zones in the room. · +0300073EN rel. 1.4 Also known as: humiFog direct, humiFog Direct, UA, c.pHC, CAREL humiFog, +0300073EN | High-pressure | 61 | 12 | CSVEDE |
| CAREL | CAREL humiFog Multizone / Multizone Touch / Touch Oil-free - zone controllerZone controllers (zone cabinets) of CAREL humiFog Multizone, Multizone Touch and Touch Oil-free systems, each supervised as its own device. · +0300116EN rel. 1.3 Also known as: humiFog Multizone zone, humiFog zone cabinet, humiFog Multizone Touch zone, humiFog zone controller BACnet, +0300116EN, +0300115EN, +0300127EN | High-pressure | 117 | 48 | CSVEDE |
| CAREL | CAREL humiFog Multizone / Multizone Touch / Touch Oil-free high-pressure humidifier - pumping stationCAREL humiFog Multizone, Multizone Touch and Touch Oil-free high-pressure water atomising humidifier pumping stations (c.pCO), which supervise up to 12 zones. · +0300116EN rel. 1.3 Also known as: humiFog Multizone, humiFog Multizone Touch, humiFog Touch Oil-free, humiFog multizone pumping station, UA multizone, c.pCO humiFog, +0300116EN, +0300115EN, +0300127EN | High-pressure | 325 | 129 | CSVEDE |
| Condair | Condair DLCondair DL / DL II hybrid in-duct humidifiers with the Integrated Controller. · 2603582-F Also known as: Condair DL II, DL hybrid humidifier, Integrated Controller DL | EvaporativeHybrid | 41 | 9 | CSVEDE |
| Condair | Condair DL (BACnet gateway board)Condair DL hybrid humidifiers (Integrated Controller 5.9.x.x) fitted with the optional BACnet/LonWorks gateway board. · 2585293-L Also known as: Virtual_BCU_DL, DL ProtoCessor gateway, BMS DL BACnet | HybridBACnet gateway | 39 | 7 | CSVEDE |
| Condair | Condair GS IICondair GS II gas-fired steam humidifiers with the Integrated Controller (software 5.10.1.14 or later). · 2595492-C Also known as: Condair GS, Nortec GS II, GS gas-fired humidifier | Steam | 30 | 9 | CSVEDE |
| Condair | Condair MECondair ME / ME II in-duct evaporative humidifiers and evaporative coolers. · 2603582-F Also known as: Condair ME II, ME evaporative humidifier | Evaporative | 61 | 12 | CSVEDE |
| Condair | Condair ME (BACnet gateway board)Condair ME evaporative humidifiers (Integrated Controller 5.9.x.x and 5.10.x.x) with the optional BACnet/LonWorks gateway board. · 2585293-L Also known as: Virtual_BCU_ME, ME ProtoCessor gateway | EvaporativeBACnet gateway | 59 | 10 | CSVEDE |
| Condair | Condair RO-ACondair RO-A reverse osmosis units connected through the Integrated Controller. · 2595492-C Also known as: RO-A reverse osmosis | Water treatment | 13 | 0 | CSVEDE |
| Condair | Condair RO-ECondair RO-E and RO-E+ reverse osmosis water treatment units for humidifier feed water. · 2603582-F Also known as: Condair RO-E+, RO-E reverse osmosis | Water treatment | 24 | 4 | CSVEDE |
| Condair | Condair RO-E (BACnet gateway board)Condair RO-E and RO-E+ reverse osmosis water treatment units with the optional BACnet IP (2611780) or BACnet MS/TP (2611783) gateway board. · 2603584-F Also known as: Virtual_BCU_ROE, RO-E ProtoCessor gateway, RO-E+ gateway board, 2611780, 2611783 | BACnet gatewayWater treatment | 23 | 3 | CSVEDE |
| Condair | Condair RSCondair RS / RS II single and dual cylinder (A/B) resistive steam humidifiers. · 2603582-F Also known as: Condair RS II, RS resistive steam humidifier, Nortec RS | Steam | 62 | 13 | CSVEDE |
| Condair | Condair RS (BACnet gateway board)Condair RS resistive steam humidifiers (Integrated Controller 5.9.x.x) with the optional BACnet/LonWorks gateway board. · 2585293-L Also known as: Virtual_BCU_RS, RS ProtoCessor gateway | SteamBACnet gateway | 61 | 10 | CSVEDE |
| Condair | Condair VitaCondair Vita high-pressure nozzle humidification systems with up to 50 areas. · 2603582-F Also known as: Condair Vita high-pressure, Vita System Master | High-pressure | 214 | 50 | CSVEDE |
| Devatec | Devatec ElectroVap ERS / RTH resistive steam humidifier (V3 controller)Devatec ElectroVap ERS, ERS-LC, RTH-HC and RTH-LC electric resistive steam humidifiers with the V3 controller and RS485 port. · DT_ERS-V3_EN REV B.3 Also known as: ERS, ERS-HC, ERS-LC, RTH-HC, RTH-LC, ElectroVap ERS, ElectroVap RTH, Devatec ERS, Devatec RTH, Armstrong Motherboard | Steam | 66 | 15 | CSVEDE |
| Devatec | Devatec ElectroVap MC (ELMC) electrode steam humidifier (V3 controller)Devatec ElectroVap ELMC electrode steam humidifiers with the V3 controller; the same table is printed for the EHU-750, KIT MC and SB steam-bath generator. · DT_ELMC-V3-EN REV B.1 Also known as: ELMC, ElectroVap MC, ElectroVap ELMC, EHU-750, EHU 750, KIT MC, CMC, Steam Bath SB, Devatec ELMC | Steam | 32 | 10 | CSVEDE |
| DriSteem | DriSteem TRI2 BACnet humidistatDriSteem model TRI2 room or duct humidistat with BACnet, controlling a DriSteem modulating humidifier (analog output) or a DriSteem dehumidifier (digital output). · TCI-IOM-EN-REVF-0125 Also known as: TRI2, DriSteem TRI2, TCI humidistat, DriSteem BACnet humidistat, X2 controller, AEX-BAC | 39 | 21 | CSVEDE | |
| DriSteem | DriSteem Vapor-logic 4DriSteem Vapor-logic version 4 humidifier controllers (older generation before Vapor-logic 6) on GTS, STS, XT, Vaporstream, HPS and similar humidifiers. · VL4-IOM-0312 Also known as: Vapor-logic4, Vapor-logic version 4, VL4, Vaporlogic 4, DriSteem humidifier controller (legacy) | 100 | 69 | CSVEDE | |
| DriSteem | DriSteem Vapor-logic 5DriSteem Vapor-logic version 5 humidifier controllers (older generation before Vapor-logic 6) on GTS, STS, XT, Vaporstream, HPS and similar humidifiers. · VL5-IOM-0914 Also known as: Vapor-logic5, Vapor-logic version 5, VL5, Vaporlogic 5, DriSteem humidifier controller (legacy) | 107 | 72 | CSVEDE | |
| DriSteem | DriSteem Vapor-logic 6Vapor-logic version 6 controller used on DriSteem GTS, STS, XT, Vaporstream, HPS, LMH, Ultra-sorb XV and evaporative (WM) humidification systems. · VL6-IOM-EN-REVH-0225 Also known as: Vapor-logic, Vapor-logic version 6, VL6, Vaporlogic, DriSteem humidifier controller | 136 | 85 | CSVEDE | |
| Neptronic | Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet moduleLegacy Neptronic SK300 and SKE electric steam humidifiers fitted with the NEPIC BACnet MS/TP communication module. · SK300-BACNET Also known as: SK300, SKE, Neptronic SK300, Neptronic SKE, NEPIC, SK300-BACNET, SKE-BACNET | Steam | 83 | 61 | CSVEDE |
| Neptronic | Neptronic SKDESC-xBNeptronic SKDESC-xB electronic controllers for steam-to-steam / direct steam injection humidifier valves (ESCJx jacketed, ESCMx models). · SKDESCXB-BACnet-250905-EUA Also known as: SKDESC, SKDESCxB, ESCJx, ESCMx, Electronic Steam Controller | Steam | 87 | 30 | CSVEDE |
| Neptronic | Neptronic SKE4Neptronic SKE4 electric (heating element) steam humidifiers, indoor and outdoor versions. · SKE4-BACnet Guide-230616 (V2.07) Also known as: SKE4 electric steam humidifier, SKE4-N, SKE4-E, SKE4 BACnet | Steam | 187 | 131 | CSVEDE |
| Neptronic | Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet moduleOlder Neptronic SKG gas-fired steam humidifiers (before the SKG4) with the NEPICSKG BACnet MS/TP module, one to four tanks. · SKG-BACNET Also known as: SKG, SKG3, Neptronic SKG, NEPICSKG, SKG-BACNET, SKG gas fired humidifier | Steam | 199 | 115 | CSVEDE |
| Neptronic | Neptronic SKG4Neptronic SKG4 gas-fired steam humidifiers with up to four humidifier modules. · SKG4-BACnet Guide-250609 (V2.06) Also known as: SKG4 gas fired humidifier, SKG4-N, SKG4-E, SKG4 BACnet | Steam | 303 | 175 | CSVEDE |
| Neptronic | Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controllerEZC zone controllers of older Neptronic SKH high pressure atomising humidifiers, before the SKH4; each zone is its own BACnet device. · SKH-BACnet Guide-210104 Also known as: SKH EZC, EZC, Neptronic SKH zone controller, SKH-BACnet Guide-210104 | High-pressure | 121 | 84 | CSVEDE |
| Neptronic | Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump stationThe SKH pump station (master board) of older Neptronic SKH high pressure atomising humidifiers, before the SKH4. · SKH-BACnet Guide-210104 Also known as: SKH, Neptronic SKH, SKH high pressure atomiser, SKH-BACnet Guide-210104 | High-pressure | 68 | 20 | CSVEDE |
| Neptronic | Neptronic SKH4Neptronic SKH4 high-pressure water atomizing humidifiers and evaporative coolers with up to six zones (A-F). · SKH4-BACnet Guide-240126 (V1.00) Also known as: SKH4 high-pressure atomizer, SKH4 BACnet | High-pressure | 325 | 238 | CSVEDE |
| Neptronic | Neptronic SKRONeptronic SKRO reverse osmosis water treatment units feeding humidifiers. · SKRO-BACnet Guide-250913 (V1.0) Also known as: SKRO reverse osmosis, SKRO BACnet | Water treatment | 87 | 50 | CSVEDE |
| Neptronic | Neptronic SKS4Neptronic SKS4 steam-to-steam (boiler steam heated) humidifiers. · SKS4-BACnet Guide-220509 (V2.03) Also known as: SKS4 steam to steam humidifier, SKS4 BACnet | Steam | 180 | 122 | CSVEDE |
| Neptronic | Neptronic SKVNeptronic SKV evaporative (media) humidifiers with up to four modules. Also known as: SKV evaporative humidifier, SKV BACnet | Evaporative | 277 | 242 | CSVEDE |
| Neptronic | Neptronic SKVFNeptronic SKVF series evaporative coolers (also used for humidification). · SKVF-BACnet Guide (v1.08)-250212 Also known as: SKVF evaporative cooler, SKVF Series, SKVF BACnet | Evaporative | 201 | 151 | CSVEDE |
| Pure Humidifier | Pure Humidifier Intac controller via ProtoNode FPC-N34 / FPC-N35Pure Humidifier steam humidifiers with the Intac controller, connected over Modbus RTU to a ProtoNode gateway. Also known as: Pure Humidifier Intac, Intac controller BACnet, ProtoNode FPC-N34 Pure Humidifier, FPC-N35 Pure Humidifier, Pure Humidifier BACnet | BACnet gateway | 90 | 68 | CSVEDE |