Reverse osmosis water treatment unit · BACnet points list
Condair RO-E BACnet points list
Updated 28 October 2026
The Condair RO-E makes demineralised water for humidifiers. Its Integrated Controller exposes BACnet IP and MS/TP on-board with status, maintenance and disinfection countdowns, inlet/tank/membrane pressures, permeate quality and flow, valve states and writable tank pressure start/stop limits.
This page lists 24 BACnet objects for the Condair RO-E — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.
- Manufacturer
- Condair
- Model
- Condair RO-E
- Equipment
- Reverse osmosis water treatment unit
- Equipment type
- Humidifiers
- BACnet objects
- 24 (4 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1001
- Also known as
- Condair RO-E+, RO-E reverse osmosis
Reference only, provided as-is: verify against Condair’s current documentation and the live device before use. Not official Condair information. Terms of use.
BMS integration notes: Condair RO-E
The RO-E is monitoring-focused: enable BACnet in its Integrated Controller and read status, service status, error code, pressures and permeate quality. The only writable items are the tank pressure start/stop limits and an error/warning reset.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 30002 | Error/Warning Reset | Clears active errors and warnings | Write |
| MI 121 | RO Device Status | RO operating status | Read |
| AI 10144 | RO Permeate Conductivity | Permeate conductivity (water quality) | Read |
| AI 10142 | RO Tank Pressure | Product water tank pressure | Read |
| AI 10210 | RO Next Disinfection | Days to next disinfection | Read |
| MI 122 | RO Service Status | Maintenance/warning/error status | Read |
| AI 10020 | ErrorWarning Code | Active error or warning code | Read |
Network setup
- BACnet settings are under Menu > password 8808 > Network > BACnet Settings; the BACnet Protocol parameter ships Off (options MS/TP Master, MS/TP Slave, BACnet/IP) and the controller restarts after changing it.
- Node ID (device instance) defaults to 1001 (range 1-4194303); BACnet IP port defaults to 47808.
- IP addressing defaults to DHCP; if no DHCP server answers the controller falls back to an APIPA 169.254.x.x address.
- Foreign Device registration to a BBMD is Off by default; BBMD port 47808 and re-register time 10 are the factory values.
Watch out for
- Permeate conductivity and drain valve are optional on RO-E and standard on RO-E+; the permeate valve is RO-E+ only.
- AV 10127/10128 set the tank refill start/stop pressures.
- Pressure, temperature and flow units follow the Metric/Imperial setting.
Condair RO-E BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | 1001 | Condair Controller | Water treatment | Read | ||
| Other | 1 | Network Port IPv4 | Network-Port for BACnet IPv4 Communication | Write | ||
| MI | 88 | RO Type | RO Type | Read | 1=RO-E, 2=RO-E+ | |
| MImin | 121 | RO Device Status | RO Status | Read | 1=Initializing, 2=Diagnostic, 3=Stopped, 4=Hold, 5=Filling, 6=Standby, 7=Flushing, 8=Draining | |
| MImin | 122 | RO Service Status | UO Maintenance status | Read | 1=No Info, 2=Warning, 3=Warning Sys, 4=Warning Commissioning, 5=Warning Activation, 6=Error, 7=Warning Disinfection | |
| MI | 134 | RO Capacity | UO Capacity | Read | 1=20 l/h 5.3 gal/hr, 2=40 l/h 10.6 gal/hr, 3=100 l/h 26.4 gal/hr, 4=200 l/h 52.8 gal/hr, 5=300 l/h 79.3 gal/hr | |
| AImin | 10020 | ErrorWarning Code | Error Warning Code | Read | 0=No Error | |
| AImin | 10210 | RO Next Disinfection | Next Disinfection | days | Read | |
| AI | 10141 | RO Inlet Pressure | Inlet pressure | bar or psi | Read | |
| AImin | 10142 | RO Tank Pressure | Tank pressure | bar or psi | Read | |
| AI | 10143 | RO Membrane Pressure | Membrane pressure | bar or psi | Read | |
| AImin | 10144 | RO Permeate Conductivity | Permeate conductivity | µS/cm | Read | |
| AI | 10145 | RO Water Temperature | Permeate temperature (optional) | °C or °F | Read | |
| AI | 10146 | RO Permeate Volume Flow | Permeat flow (optional) | l/h or gal/h | Read | |
| AI | 10150 | RO Next Maintenance | Next maintenance | h | Read | |
| AI | 10238 | RO Operating Hours | Operating hours | h | Read | |
| BI | 78 | RO Inlet Valve | Y11 Inlet valve | Read | 0=Closed, 1=Open | |
| BI | 79 | RO Drain Valve | Y12 Drain valve | Read | 0=Open, 1=Closed | |
| BI | 80 | RO Outlet Valve | Y13 Outlet valve (optional) | Read | 0=Open, 1=Closed | |
| BI | 81 | RO Permeate Valve | Y15 Permeate valve | Read | 0=Drain, 1=Tank | |
| BI | 82 | RO Concentrate Valve | Y16 Concentrate valve (optional) | Read | 0=Closed, 1=Open | |
| AV | 10127 | RO Start Tank Pressure | Minimum tank pressure | bar or psi | Write | |
| AV | 10128 | RO End Tank Pressure | Maximum tank pressure | bar or psi | Write | |
| AVmin | 30002 | Error/Warning Reset | Error/Warning Reset | Write |
No points match these filters.
Object ID lookup: Condair RO-E point IDs by name
MI88RO TypeMI121RO Device StatusMI122RO Service StatusMI134RO CapacityAI10020ErrorWarning CodeAI10210RO Next DisinfectionAI10141RO Inlet PressureAI10142RO Tank PressureAI10143RO Membrane PressureAI10144RO Permeate ConductivityAI10145RO Water TemperatureAI10146RO Permeate Volume FlowAI10150RO Next MaintenanceAI10238RO Operating HoursBI78RO Inlet ValveBI79RO Drain ValveBI80RO Outlet ValveBI81RO Permeate ValveBI82RO Concentrate ValveAV10127RO Start Tank PressureAV10128RO End Tank PressureAV30002Error/Warning Reset
Integration notes
- BACnet is built into the Integrated Controller (RJ45 for BACnet IP, RS485 for MS/TP master or slave); it ships with the BACnet protocol set to Off.
- Factory Node ID (device instance) is 1001 and the MS/TP MAC is 127; BACnet IP uses UDP 47808 and supports registering with a BBMD.
- Some points are RO-E+ only or optional on the RO-E (permeate conductivity, drain valve, permeate valve).
- Pressure, temperature and flow units follow the controller's Metric/Imperial setting.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair RO-E and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Condair RO-E
How many BACnet points does the Condair RO-E have?
This list has 24 BACnet objects: 10 analog inputs, 3 analog values, 5 binary inputs, 1 device, 4 multi-state inputs, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Condair RO-E BACnet points are writable?
4 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Condair RO-E BACnet documentation?
The source is BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) (2603582-F), revision 2026-07, published free by Condair at https://www.condair.co.uk/consense/bms-communication-ic-2.0/am_bms_interface_bacnet_on_board_2603582_en.pdf.
What are the minimum BACnet points to integrate the Condair RO-E?
Start with AV 30002 Error/Warning Reset (Clears active errors and warnings); MI 121 RO Device Status (RO operating status); AI 10144 RO Permeate Conductivity (Permeate conductivity (water quality)); AI 10142 RO Tank Pressure (Product water tank pressure); AI 10210 RO Next Disinfection (Days to next disinfection); MI 122 RO Service Status (Maintenance/warning/error status); AI 10020 ErrorWarning Code (Active error or warning code).
How do I check these points on the real Condair RO-E?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Condair BACnet points lists
- Hybrid (spray + evaporative) humidifier
Condair DL
Condair DL / DL II hybrid in-duct humidifiers with the Integrated Controller.
Also known as: Condair DL II, DL hybrid humidifier, Integrated Controller DL - Hybrid humidifier BACnet gateway
Condair DL (BACnet gateway board)
Condair DL hybrid humidifiers (Integrated Controller 5.9.x.x) fitted with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_DL, DL ProtoCessor gateway, BMS DL BACnet - Gas-fired steam humidifier
Condair GS II
Condair GS II gas-fired steam humidifiers with the Integrated Controller (software 5.10.1.14 or later).
Also known as: Condair GS, Nortec GS II, GS gas-fired humidifier - Evaporative humidifier / cooler
Condair ME
Condair ME / ME II in-duct evaporative humidifiers and evaporative coolers.
Also known as: Condair ME II, ME evaporative humidifier - Evaporative humidifier BACnet gateway
Condair ME (BACnet gateway board)
Condair ME evaporative humidifiers (Integrated Controller 5.9.x.x and 5.10.x.x) with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_ME, ME ProtoCessor gateway - Reverse osmosis water treatment unit
Condair RO-A
Condair RO-A reverse osmosis units connected through the Integrated Controller.
Also known as: RO-A reverse osmosis - Reverse osmosis water treatment unit BACnet gateway
Condair RO-E (BACnet gateway board)
Condair RO-E and RO-E+ reverse osmosis water treatment units with the optional BACnet IP (2611780) or BACnet MS/TP (2611783) gateway board.
Also known as: Virtual_BCU_ROE, RO-E ProtoCessor gateway, RO-E+ gateway board, 2611780, 2611783 - Electric resistive steam humidifier
Condair RS
Condair RS / RS II single and dual cylinder (A/B) resistive steam humidifiers.
Also known as: Condair RS II, RS resistive steam humidifier, Nortec RS - Resistive steam humidifier BACnet gateway
Condair RS (BACnet gateway board)
Condair RS resistive steam humidifiers (Integrated Controller 5.9.x.x) with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_RS, RS ProtoCessor gateway - High-pressure nozzle humidification system
Condair Vita
Condair Vita high-pressure nozzle humidification systems with up to 50 areas.
Also known as: Condair Vita high-pressure, Vita System Master
Source: BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.