- Home
- BACnet points lists
- Condair
- Condair ME
Evaporative humidifier / cooler · BACnet points list
Condair ME BACnet points list
Updated 28 October 2026
The Condair ME is a multi-stage evaporative humidifier and adiabatic cooler. The Integrated Controller exposes BACnet IP and MS/TP on-board. Points include operating and error status, per-stage capacity and pump speeds, tank level, water quality, separate humidity and cooling PI loops, and writable humidity/demand and temperature inputs.
This page lists 61 BACnet objects for the Condair ME — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.
- Manufacturer
- Condair
- Model
- Condair ME
- Equipment
- Evaporative humidifier / cooler
- Equipment type
- Humidifiers
- BACnet objects
- 61 (12 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1001
- Also known as
- Condair ME II, ME evaporative humidifier
Reference only, provided as-is: verify against Condair’s current documentation and the live device before use. Not official Condair information. Terms of use.
BMS integration notes: Condair ME
Enable BACnet in the Integrated Controller, set the signal source to BACnet, and write humidity demand (or measured RH) to AO 15044 within the signal timeout. When the ME runs as an evaporative cooler in system mode, also write the temperature to AO 15045. Monitor status, error status and the error code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 15044 | RH or Demand | Demand or measured RH from the BMS | Command |
| AV 15054 | Setpoint Humidifying | Humidity setpoint used in RH P/PI mode | Write |
| AO 15045 | Temperature | Air temperature from the BMS (cooling system mode) | Command |
| AV 30002 | Error/Warning Reset | Reset errors and warnings (1 = reset) | Write |
| MI 5050 | Device Status | Operating status | Read |
| AI 15112 | Actual Stages | Number of stages running | Read |
| MI 5051 | Error Status | Maintenance/error status | Read |
| AI 10020 | Error/Warning Code | Active error or warning code | Read |
Enable & remote start
Set Menu > password 8808 > Controls > Signal Settings > Source to BACnet and pick the Control Mode (Demand, RH P or RH PI; On/Off also exists). With Source left at Analog the unit ignores BACnet control values.
Heartbeat & communication loss
When the signal source is not Analog, the demand/humidity value written over BACnet must be refreshed within the Signal Timeout (1-300 s, default 300 s). If it is not, warning W35 Signal Timeout is raised and the unit stops until a new value arrives, so the BMS must keep rewriting the AO.
Sensors & values from the BMS
In Demand mode the BMS writes the required output (0-100 %) to the RH/Demand AO. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used. For cooling, AO 15045 carries the air temperature (relinquish default 20 °C) and is only active when the ME is operated in system mode.
Network setup
- BACnet settings are under Menu > password 8808 > Network > BACnet Settings; the BACnet Protocol parameter ships Off (options MS/TP Master, MS/TP Slave, BACnet/IP) and the controller restarts after changing it.
- Node ID (device instance) defaults to 1001 (range 1-4194303); BACnet IP port defaults to 47808.
- IP addressing defaults to DHCP; if no DHCP server answers the controller falls back to an APIPA 169.254.x.x address.
- Foreign Device registration to a BBMD is Off by default; BBMD port 47808 and re-register time 10 are the factory values.
- MS/TP: MAC defaults to 127 (0-127 master, 0-254 slave), baud 9600 (up to 115200); fit jumper JP6 only on the first and last device, remove JP8, and tie GND between all devices.
Watch out for
- AO 15044 relinquishes to 0 % demand.
- Draining and Matrix Wash Over AVs: write 1 to start, 0 to stop; a read of 100 means off.
- Optional sensors (UV, conductivity, water/air temperature, tank levels) only report when fitted.
- Temperature and capacity units follow the Metric/Imperial setting.
Condair ME BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | 1001 | Condair Controller | Humidifier | Read | ||
| Other | 1 | Network Port IPv4 | Network-Port for BACnet IPv4 Communication | Write | ||
| MImin | 5050 | Device Status | Actual device status | Read | 1=Initializing, 2=Diagnostic, 3=Stopped, 4=Humidifying, 5=Cooling, 6=Holding, 7=Draining, 8=Refreshing, 9=Filling, 10=Standby, 11=Diluting, 12=Assisted Draining, 13=Bleeding, 14=Softstart, 15=Switched Off, 16=Remote Off, 17=Purging, 18=Drain Check | |
| MImin | 5051 | Error Status | Maintenance and error status | Read | 1=No Info, 2=Warning, 3=Maintenance, 4=WET Tank empty, 5=Replace PureFlo Cartridge, 6=Replace UV Lamp, 7=Matrix Wash Over, 8=Out of Commissioning, 9=Activation Code, 10=Error, 11=Disinfection Tank empty | |
| AI | 15176 | Water Level Tank | Water level tank | Read | 0=Level 0, 1=Level 1, 2=Level 2, 3=Level 3, 4=Level 4, 5=Level 5, 6=Level 6, 7=Level 7 | |
| AImin | 10020 | Error/Warning Code | Code of the latest pending error or warning | Read | 0=no Error | |
| AI | 10044 | Operating Hours | Total hours of operation since commissioning | h | Read | |
| AI | 10060 | Next Maintenance | Due date of next maintenance in operating hours | h | Read | |
| AI | 15171 | Next UV Lamp Exchange | Due date of next UV Lamp exchange in days (optional) | days | Read | |
| AI | 15172 | Next PureFlo Exchange | Due date of next Pure-Flo exchange in days (optional) | days | Read | |
| AI | 15047 | Humidity Control | Actual humidity or demand | % | Read | |
| AI | 15048 | Temperature Control | Actual air temperature | °C or °F | Read | |
| AI | 15019 | UV Current | Actual UV current (optional) | A | Read | |
| AImin | 15112 | Actual Stages | Number of running stages | Read | ||
| AI | 15086 | Capacity 1 | Water capacity stage 1 | kg/h or lb/h | Read | |
| AI | 15087 | Capacity 2 | Water capacity stage 2 | kg/h or lb/h | Read | |
| AI | 15088 | Capacity 3 | Water capacity stage 3 | kg/h or lb/h | Read | |
| AI | 15089 | Capacity 4 | Water capacity stage 4 | kg/h or lb/h | Read | |
| AI | 15090 | Capacity 5 | Water capacity stage 5 | kg/h or lb/h | Read | |
| AI | 15091 | Capacity 6 | Water capacity stage 6 | kg/h or lb/h | Read | |
| AI | 15092 | Capacity 7 | Water capacity stage 7 | kg/h or lb/h | Read | |
| AI | 15130 | Speed Pump 1 | Actual speed pump 1 | % | Read | |
| AI | 15131 | Speed Pump 2 | Actual speed pump 2 | % | Read | |
| AI | 15132 | Speed Pump 3 | Actual speed pump 3 | % | Read | |
| AI | 15133 | Speed Pump 4 | Actual speed pump 4 | % | Read | |
| AI | 15134 | Speed Pump 5 | Actual speed pump 5 | % | Read | |
| AI | 15135 | Speed Pump 6 | Actual speed pump 6 | % | Read | |
| AI | 15136 | Speed Pump 7 | Actual speed pump 7 | % | Read | |
| AI | 15077 | Water Conductivity | Water conductivity tank (optional) | µS/cm | Read | |
| AI | 15075 | Water Temperature | Actual water temperature (optional) | °C or °F | Read | |
| AI | 15049 | Incoming Air Temperature | Incoming air temperature (optional) | °C or °F | Read | |
| AVmin | 15054 | Setpoint Humidifying | Setpoint humidity control | % | Write | |
| AV | 15055 | P-Band Humidifying | Proportional band humidity control | % | Write | |
| AV | 15056 | I-Time Humidifying | Integral time humidity control | min | Write | |
| AV | 15057 | Setpoint Cooling | Setpoint temperature control | °C or °F | Write | |
| AV | 15058 | P-Band Cooling | Proportional band temperature control | °C or °F | Write | |
| AV | 15059 | I-Time Cooling | Integral time temperature control | min | Write | |
| AV | 30507 | Draining | Remote draining | % | Write | Read: 100=Off, 0 - 99=Progress draining in %, Write: 0=Stop draining, 1=Start draining |
| AV | 30505 | Matrix Wash Over | Remote matrix wash over | % | Write | Read: 100=Off, 0 - 99=Progress matrix wash over in %, Write: 0=Stop matrix wash over, 1=Start matrix wash over |
| AVmin | 30002 | Error/Warning Reset | Remote Error/Warning Reset | Write | 0=Off, 1=On | |
| AOmin | 15044 | RH or Demand | Actual humidity or demand via BACnet | % | Command | |
| AOmin | 15045 | Temperature | Actual temperature via BACnet | °C or °F | Command | |
| BI | 5002 | Safety Loop | Safety loop | Read | 0=Open, 1=Closed (ok) | |
| BI | 5034 | Drain Valve | Drain valve | Read | 0=Open, 1=Closed | |
| BI | 5033 | Inlet Valve | Inlet valve | Read | 0=Closed, 1=Open | |
| BI | 5091 | Drain Pump | Drain pump | Read | 0=Off, 1=On | |
| BI | 5111 | Pump 1 Error | Fault pump 1 | Read | 0=Fault, 1=Ok | |
| BI | 5112 | Pump 2 Error | Fault pump 2 | Read | 0=Fault, 1=Ok | |
| BI | 5113 | Pump 3 Error | Fault pump 3 | Read | 0=Fault, 1=Ok | |
| BI | 5114 | Pump 4 Error | Fault pump 4 | Read | 0=Fault, 1=Ok | |
| BI | 5115 | Pump 5 Error | Fault pump 5 | Read | 0=Fault, 1=Ok | |
| BI | 5116 | Pump 6 Error | Fault pump 6 | Read | 0=Fault, 1=Ok | |
| BI | 5117 | Pump 7 Error | Fault pump 7 | Read | 0=Fault, 1=Ok | |
| BI | 5118 | Water Inlet Error | Fault water inlet | Read | 0=Fault, 1=Ok | |
| BI | 5119 | Water Outlet Error | Fault water outlet | Read | 0=Fault, 1=Ok | |
| BI | 5120 | Water Temperature Error | Fault water temperature (optional) | Read | 0=Fault, 1=Ok | |
| BI | 5122 | Level Sensor Error | Fault level sensor | Read | 0=Fault, 1=Ok | |
| BI | 5121 | Water Conductivity Error | Fault water conductivity (optional) | Read | 0=Fault, 1=Ok | |
| BI | 5009 | Leak Monitoring | Leakage sensor (optional) | Read | 0=Leak, 1=Ok | |
| BI | 5007 | WET Tank Level | WET tank level (optional) | Read | 0=Empty, 1=Ok | |
| BI | 5008 | Disinfection Tank Level | Disinfection tank level (optional) | Read | 0=Empty, 1=Ok |
No points match these filters.
Object ID lookup: Condair ME (on-board BACnet) point IDs by name
MI5050Device StatusMI5051Error StatusAI15176Water Level TankAI10020Error/Warning CodeAI10044Operating HoursAI10060Next MaintenanceAI15171Next UV Lamp ExchangeAI15172Next PureFlo ExchangeAI15047Humidity ControlAI15048Temperature ControlAI15019UV CurrentAI15112Actual StagesAI15086Capacity 1AI15087Capacity 2AI15088Capacity 3AI15089Capacity 4AI15090Capacity 5AI15091Capacity 6AI15092Capacity 7AI15130Speed Pump 1AI15131Speed Pump 2AI15132Speed Pump 3AI15133Speed Pump 4AI15134Speed Pump 5AI15135Speed Pump 6AI15136Speed Pump 7AI15077Water ConductivityAI15075Water TemperatureAI15049Incoming Air TemperatureAV15054Setpoint HumidifyingAV15055P-Band HumidifyingAV15056I-Time HumidifyingAV15057Setpoint CoolingAV15058P-Band CoolingAV15059I-Time CoolingAV30507DrainingAV30505Matrix Wash OverAV30002Error/Warning ResetAO15044RH or DemandAO15045TemperatureBI5002Safety LoopBI5034Drain ValveBI5033Inlet ValveBI5091Drain PumpBI5111Pump 1 ErrorBI5112Pump 2 ErrorBI5113Pump 3 ErrorBI5114Pump 4 ErrorBI5115Pump 5 ErrorBI5116Pump 6 ErrorBI5117Pump 7 ErrorBI5118Water Inlet ErrorBI5119Water Outlet ErrorBI5120Water Temperature ErrorBI5122Level Sensor ErrorBI5121Water Conductivity ErrorBI5009Leak MonitoringBI5007WET Tank LevelBI5008Disinfection Tank Level
Integration notes
- BACnet is built into the Integrated Controller (RJ45 for BACnet IP, RS485 for MS/TP master or slave); it ships with the BACnet protocol set to Off.
- Factory Node ID (device instance) is 1001 and the MS/TP MAC is 127; BACnet IP uses UDP 47808 and supports registering with a BBMD.
- To command the unit over BACnet set Controls > Signal Settings > Source to BACnet; the demand/humidity AO must then be rewritten within the Signal Timeout (default 300 s) or the unit stops with warning W35.
- Points marked optional only report when that option is fitted; capacity, pressure and temperature units follow the controller's Metric/Imperial setting.
- The temperature AO (15045) is only used when the ME runs in cooling/system mode.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair ME and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Condair ME
How many BACnet points does the Condair ME have?
This list has 61 BACnet objects: 27 analog inputs, 2 analog outputs, 9 analog values, 19 binary inputs, 1 device, 2 multi-state inputs, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Condair ME BACnet points are writable?
12 of the 61 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Condair ME BACnet documentation?
The source is BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) (2603582-F), revision 2026-07, published free by Condair at https://www.condair.co.uk/consense/bms-communication-ic-2.0/am_bms_interface_bacnet_on_board_2603582_en.pdf.
What are the minimum BACnet points to integrate the Condair ME?
Start with AO 15044 RH or Demand (Demand or measured RH from the BMS); AV 15054 Setpoint Humidifying (Humidity setpoint used in RH P/PI mode); AO 15045 Temperature (Air temperature from the BMS (cooling system mode)); AV 30002 Error/Warning Reset (Reset errors and warnings (1 = reset)); MI 5050 Device Status (Operating status); AI 15112 Actual Stages (Number of stages running); MI 5051 Error Status (Maintenance/error status); AI 10020 Error/Warning Code (Active error or warning code).
How do I enable BMS control of the Condair ME?
Set Menu > password 8808 > Controls > Signal Settings > Source to BACnet and pick the Control Mode (Demand, RH P or RH PI; On/Off also exists). With Source left at Analog the unit ignores BACnet control values.
Does the Condair ME need a BACnet heartbeat or have a communication timeout?
When the signal source is not Analog, the demand/humidity value written over BACnet must be refreshed within the Signal Timeout (1-300 s, default 300 s). If it is not, warning W35 Signal Timeout is raised and the unit stops until a new value arrives, so the BMS must keep rewriting the AO.
Can the BMS supply sensor values to the Condair ME?
In Demand mode the BMS writes the required output (0-100 %) to the RH/Demand AO. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used. For cooling, AO 15045 carries the air temperature (relinquish default 20 °C) and is only active when the ME is operated in system mode.
How do I check these points on the real Condair ME?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Condair BACnet points lists
- Hybrid (spray + evaporative) humidifier
Condair DL
Condair DL / DL II hybrid in-duct humidifiers with the Integrated Controller.
Also known as: Condair DL II, DL hybrid humidifier, Integrated Controller DL - Hybrid humidifier BACnet gateway
Condair DL (BACnet gateway board)
Condair DL hybrid humidifiers (Integrated Controller 5.9.x.x) fitted with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_DL, DL ProtoCessor gateway, BMS DL BACnet - Gas-fired steam humidifier
Condair GS II
Condair GS II gas-fired steam humidifiers with the Integrated Controller (software 5.10.1.14 or later).
Also known as: Condair GS, Nortec GS II, GS gas-fired humidifier - Evaporative humidifier BACnet gateway
Condair ME (BACnet gateway board)
Condair ME evaporative humidifiers (Integrated Controller 5.9.x.x and 5.10.x.x) with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_ME, ME ProtoCessor gateway - Reverse osmosis water treatment unit
Condair RO-A
Condair RO-A reverse osmosis units connected through the Integrated Controller.
Also known as: RO-A reverse osmosis - Reverse osmosis water treatment unit
Condair RO-E
Condair RO-E and RO-E+ reverse osmosis water treatment units for humidifier feed water.
Also known as: Condair RO-E+, RO-E reverse osmosis - Reverse osmosis water treatment unit BACnet gateway
Condair RO-E (BACnet gateway board)
Condair RO-E and RO-E+ reverse osmosis water treatment units with the optional BACnet IP (2611780) or BACnet MS/TP (2611783) gateway board.
Also known as: Virtual_BCU_ROE, RO-E ProtoCessor gateway, RO-E+ gateway board, 2611780, 2611783 - Electric resistive steam humidifier
Condair RS
Condair RS / RS II single and dual cylinder (A/B) resistive steam humidifiers.
Also known as: Condair RS II, RS resistive steam humidifier, Nortec RS - Resistive steam humidifier BACnet gateway
Condair RS (BACnet gateway board)
Condair RS resistive steam humidifiers (Integrated Controller 5.9.x.x) with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_RS, RS ProtoCessor gateway - High-pressure nozzle humidification system
Condair Vita
Condair Vita high-pressure nozzle humidification systems with up to 50 areas.
Also known as: Condair Vita high-pressure, Vita System Master
Source: BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.