- Home
- BACnet points lists
- Neptronic
- SKDESC-xB
Steam humidifier valve controller · BACnet points list
Neptronic SKDESC-xB BACnet points list
Updated 28 October 2026
The SKDESC-xB is the electronic controller used on Neptronic steam injection humidifier valves. It communicates over BACnet MS/TP only and exposes setpoints, room and duct RH, PI tuning, high limit, network fallback settings, inputs and relay states.
This page lists 87 BACnet objects for the Neptronic SKDESC-xB — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Neptronic’s own free documentation, linked below.
- Manufacturer
- Neptronic
- Model
- SKDESC-xB
- Equipment
- Steam humidifier valve controller
- Equipment type
- Humidifiers
- BACnet objects
- 87 (30 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 153000 + MAC address (153000 by default, MAC 0)
- Also known as
- SKDESC, SKDESCxB, ESCJx, ESCMx, Electronic Steam Controller
Reference only, provided as-is: verify against Neptronic’s current documentation and the live device before use. Not official Neptronic information. Terms of use.
BMS integration notes: Neptronic SKDESC-xB
Set MSV 2 Control Mode to Network to drive the valve from the BMS, or feed room RH to AV 2 (after turning on BV 14 NetworkRoomRH) with the internal setpoint AV 1. Configure the network fallback timeout and fallback setpoint, and switch the system with BV 1.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | PowerStatus | System power on/off | Write |
| MV 2 | ControlMode | Control mode: External, Internal or Network | Write |
| AV 1 | InternalStpnt | Internal RH setpoint | Write |
| AV 2 | RoomRH | Room RH (writable when BV 14 = On) | Write |
| AV 4 | SystemDemand | Humidity demand the controller is acting on | Read |
| BV 20 | AlarmRelayState | Alarm relay output; on when the controller signals an alarm | Read |
Enable & remote start
BV 1 PowerStatus (0 = Off, 1 = On) is writable; MSV 2 ControlMode selects External, Internal or Network control.
Heartbeat & communication loss
Network fallback is configured with AV 30 FallbackTimeout (0-900 s), AV 31 FallbackStpnt (0-100 %) and the AV 32 FallbackDownCntr countdown; the guide lists these objects but does not spell out the fallback sequence, so test it on site.
Sensors & values from the BMS
Room RH is written to AV 2 only while BV 14 NetworkRoomRH = On; duct RH is written to AV 3 only while MSV 3 HiLimitSensorSrc = Network. BV 15 enables an external RH setpoint.
Network setup
- MS/TP MAC defaults to 000 (000-254; 128-254 are non-token-passing slaves), baud auto-detects (Auto, 9600, 19200, 38400, 76800), Max_Master 127.
- Device instance defaults to 153000 + MAC and can be changed from the menu (password 637) or via Device Object_Identifier.
- Reinitialize Device over BACnet uses the password 'nep'.
Watch out for
- Out_of_Service automatically returns to False after 15 minutes by default (adjustable 0-120 min via a proprietary device property).
- A Copy Config can be run over BACnet, but the BACnet schedule is not copied.
- The controller does not send BACnet event notifications; poll alarm objects.
Neptronic SKDESC-xB BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | SeparatorTempSig (ESCJx, ESCMx) | Separator temperature sensor signal (TS1) value | mV | Read | |
| AI | 2 | Jacket1TempSig (ESCJx) | Temperature sensor signal (TS2) value of jacket 1 | mV | Read | |
| AI | 3 | Jacket2TempSig (ESCJx) | Temperature sensor signal (TS3) value of jacket 2 | mV | Read | |
| AI | 4 | Jacket3TempSig (ESCJx) | Temperature sensor signal (TS4) value of jacket 3 | mV | Read | |
| AI | 5 | Jacket4TempSig (ESCJx) | Temperature sensor signal (TS5) value of jacket 4 | mV | Read | |
| AI | 6 | PCRTempSig (PCR Option) | Temperature sensor signal of PCR | Read | ||
| AI | 7 | ExternalSig | External input signal (AI1) | mV | Read | |
| AI | 8 | RoomRHSig | Room's relative humidity sensor signal (AI2) | mV | Read | |
| AI | 9 | DuctRHSig | Duct's relative humidity sensor signal | mV | Read | |
| AI | 10 | PCRWaterLevelSig | Water level signal of PCR | Read | ||
| AVmin | 1 | InternalStpnt | Internal setpoint value | % | Write | |
| AVmin | 2 | RoomRH | Relative humidity reading value of the room | % | Write | |
| AV | 3 | DuctRH | Relative humidity reading value of the duct | % | Write | |
| AVmin | 4 | SystemDemand | System demand value | Read | ||
| AV | 5 | SystemOutput | System output value | Read | ||
| AV | 6 | SeparatorTemp (ESCJx, ESCMx) | Separator temperature reading | °F or °C | Read | |
| AV | 7 | Jacket1Temp (ESCJx) | Temperature reading of jacket 1 | °F or °C | Read | |
| AV | 8 | Jacket2Temp (ESCJx) | Temperature reading of jacket 2 | °F or °C | Read | |
| AV | 9 | Jacket3Temp (ESCJx) | Temperature reading of jacket 3 | °F or °C | Read | |
| AV | 10 | Jacket4Temp (ESCJx) | Temperature reading of jacket 4 | Read | ||
| AV | 11 | PCRTemp (PCR Option) | Temperature reading of PCR | Read | ||
| AV | 12 | WorkingCapacity | Percentage value in full capacity | % | Write | |
| AV | 13 | SeparatorTempOffset (ESCJx, ESCMx) | Temperature sensor offset value of separator | °F or °C | Write | |
| AV | 14 | Jacket1TempOffset (ESCJx) | Temperature sensor offset value of jacket 1 | °F or °C | Write | |
| AV | 15 | Jacket2TempOffset (ESCJx) | Temperature sensor offset value of jacket 2 | °F or °C | Write | |
| AV | 16 | Jacket3TempOffset (ESCJx) | Temperature sensor offset value of jacket 3 | °F or °C | Write | |
| AV | 17 | Jacket4TempOffset (ESCJx) | Temperature sensor offset value of jacket 4 | °F or °C | Write | |
| AV | 18 | PCRTempOffset (PCR Option) | Temperature sensor offset value of PCR | Read | ||
| AV | 19 | RoomRHOffset | Relative humidity sensor offset value of the room | %RH | Write | |
| AV | 20 | CntrlDeadBand | Control deadband value | %RH | Write | |
| AV | 21 | CntrlPropRamp | Control proportional ramp value | %RH | Write | |
| AV | 22 | CntrlIntgrlTime | Control integral ramp value | %RH | Write | |
| AV | 23 | HiLimitStpnt | High limit setpoint value | %RH | Write | |
| AV | 24 | HiLimitPropRamp | High limit proportional ramp value | %RH | Write | |
| AV | 25 | DuctRHOffset | Relative humidity offset value of the duct | Read | ||
| AV | 26 | HiLimitMaxDemand | High limit maximum demand value | % | Read | |
| AV | 27 | EndOfSeasonDelay | End of season delay | h | Write | |
| AV | 28 | ServiceDelay | Delay in hours before a Service has to be performed | h | Write | |
| AV | 29 | ServiceRunTime | Service runtime counter | h | Read | |
| AV | 30 | FallbackTimeout | Network fallback timeout | s | Write | |
| AV | 31 | FallbackStpnt | Network fallback setpoint | % | Write | |
| AV | 32 | FallbackDownCntr | Network fallback downcounter | s | Write | |
| AV | 33 | TotalRunTime | Total system runtime | h | Read | |
| AV | 34 | CntrlOutputSig | Control valve output signal | mV | Read | |
| AV | 35 | MicroCntrlTemp | Microcontroller temperature reading | °F or °C | Read | |
| AV | 36 | BoardTemp | Temperature reading of the PC board | °F or °C | Read | |
| AV | 37 | CntrlDerivativeTime | Control derivative time | Read | ||
| AV | 38 | DuctStpntMin | Minimum setpoint value of duct | Read | ||
| AV | 39 | DuctStpntMax | Maximum setpoint value of duct | Read | ||
| AV | 41 | DuctPropRamp | Proportional ramp value of duct | Read | ||
| AV | 42 | DuctIntgrlTime | Integral time value of duct | Read | ||
| AV | 43 | DuctDerivativeTime | Derivative time value of duct | Read | ||
| AV | 44 | ControlDemand | Control demand value | Read | ||
| AV | 45 | DynamicDuctStpnt | Dynamic duct setpoint value | Read | ||
| AV | 46 | DuctDemand | Duct demand value | Read | ||
| AV | 47 | PCRSupplySig (PCR Option) | Supply signal value of PCR | Read | ||
| AV | 48 | PCRSupply (PCR Option) | Supply value of PCR | Read | ||
| BI | 1 | ExternalDemandInputState | Digital external demand input state | Read | 0=OFF, 1=ON | |
| BI | 2 | AirflowInputState | Airflow input state | Read | 0=OFF, 1=ON | |
| BI | 3 | HiLimitInputState | High limit input state | Read | 0=OFF, 1=ON | |
| BI | 4 | InterlockInputState | Interlock input state | Read | 0=OFF, 1=ON | |
| BVmin | 1 | PowerStatus | System's power status | Write | 0=OFF, 1=ON | |
| BV | 2 | ServiceWarning | Service warning | Read | 0=OFF, 1=ON | |
| BV | 3 | ServiceAlarm | Service alarm | Read | 0=OFF, 1=ON | |
| BV | 4 | AirFlowCutout | Air flow cutout state | Read | 0=OFF, 1=ON | |
| BV | 5 | HiLimitCutout | High limit cutout state | Read | 0=OFF, 1=ON | |
| BV | 6 | InterlockCutout | Interlock cutout state | Read | 0=OFF, 1=ON | |
| BV | 7 | TempSensorDefect | Temperature sensor defect | Read | 0=OFF, 1=ON | |
| BV | 8 | RoomRHSensorDefect | Room relative humidity sensor defect | Read | 0=OFF, 1=ON | |
| BV | 9 | DuctRHSensorDefect | Duct relative humidity sensor defect | Read | 0=OFF, 1=ON | |
| BV | 10 | FloodedSteamTrap | Flooded steam trap | Read | 0=OFF, 1=ON | |
| BV | 11 | DisplayUnits | Display units | Write | 0=Metric, 1=Imperial | |
| BV | 12 | EconoMode | Economic mode | Write | 0=OFF, 1=ON | |
| BV | 13 | ExternalSigRange | External input signal range | Write | 0=2 to 10V, 1=0 to 10V | |
| BV | 14 | NetworkRoomRH | Network room relative humidity | Write | 0=OFF, 1=ON | |
| BV | 15 | ExternalRHStpnt | External relative humidity setpoint | Write | 0=OFF, 1=ON | |
| BV | 16 | ExternalRHStpnt | Read | |||
| BV | 17 | HiLimitRHSigRange | High limit relative humidity signal range | Write | 0=OFF, 1=ON | |
| BV | 18 | RunsWhenServiceAlarm | Runs when service alarm is active | Write | 0=OFF, 1=ON | |
| BV | 19 | IsoValveOutState | Isolating valve output state | Read | 0=OFF, 1=ON | |
| BVmin | 20 | AlarmRelayState | Alarm relay output state | Read | 0=OFF, 1=ON | |
| BV | 21 | SteamRelayState | Steam relay output state | Read | 0=OFF, 1=ON | |
| BV | 22 | PCRReliefValveOutState (PCR Option) | Relief valve output state of PCR option | Read | ||
| MV | 1 | Language | Sytem language | Write | 1=ENG | |
| MVmin | 2 | ControlMode | Control mode | Write | 1=External, 2=Internal, 3=Network | |
| MV | 3 | DuctSensorSrc | Duct sensor source | Read | ||
| MV | 4 | PCRWaterLevel (PCR Option) | PCR water level | Read | 1=Above High, 2=Above Low, 3=Below Low, 4=Error |
No points match these filters.
Object ID lookup: Neptronic SKDESC-xB point IDs by name
AI1SeparatorTempSig (ESCJx, ESCMx)AI2Jacket1TempSig (ESCJx)AI3Jacket2TempSig (ESCJx)AI4Jacket3TempSig (ESCJx)AI5Jacket4TempSig (ESCJx)AI6PCRTempSig (PCR Option)AI7ExternalSigAI8RoomRHSigAI9DuctRHSigAI10PCRWaterLevelSigAV1InternalStpntAV2RoomRHAV3DuctRHAV4SystemDemandAV5SystemOutputAV6SeparatorTemp (ESCJx, ESCMx)AV7Jacket1Temp (ESCJx)AV8Jacket2Temp (ESCJx)AV9Jacket3Temp (ESCJx)AV10Jacket4Temp (ESCJx)AV11PCRTemp (PCR Option)AV12WorkingCapacityAV13SeparatorTempOffset (ESCJx, ESCMx)AV14Jacket1TempOffset (ESCJx)AV15Jacket2TempOffset (ESCJx)AV16Jacket3TempOffset (ESCJx)AV17Jacket4TempOffset (ESCJx)AV18PCRTempOffset (PCR Option)AV19RoomRHOffsetAV20CntrlDeadBandAV21CntrlPropRampAV22CntrlIntgrlTimeAV23HiLimitStpntAV24HiLimitPropRampAV25DuctRHOffsetAV26HiLimitMaxDemandAV27EndOfSeasonDelayAV28ServiceDelayAV29ServiceRunTimeAV30FallbackTimeoutAV31FallbackStpntAV32FallbackDownCntrAV33TotalRunTimeAV34CntrlOutputSigAV35MicroCntrlTempAV36BoardTempAV37CntrlDerivativeTimeAV38DuctStpntMinAV39DuctStpntMaxAV41DuctPropRampAV42DuctIntgrlTimeAV43DuctDerivativeTimeAV44ControlDemandAV45DynamicDuctStpntAV46DuctDemandAV47PCRSupplySig (PCR Option)AV48PCRSupply (PCR Option)BI1ExternalDemandInputStateBI2AirflowInputStateBI3HiLimitInputStateBI4InterlockInputStateBV1PowerStatusBV2ServiceWarningBV3ServiceAlarmBV4AirFlowCutoutBV5HiLimitCutoutBV6InterlockCutoutBV7TempSensorDefectBV8RoomRHSensorDefectBV9DuctRHSensorDefectBV10FloodedSteamTrapBV11DisplayUnitsBV12EconoModeBV13ExternalSigRangeBV14NetworkRoomRHBV15ExternalRHStpntBV16ExternalRHStpntBV17HiLimitRHSigRangeBV18RunsWhenServiceAlarmBV19IsoValveOutStateBV20AlarmRelayStateBV21SteamRelayStateBV22PCRReliefValveOutState (PCR Option)MV1LanguageMV2ControlModeMV3DuctSensorSrcMV4PCRWaterLevel (PCR Option)
Integration notes
- Points marked 'object available as per system configuration' depend on the unit options.
- Empty 'W?' entries in the guide are treated as read-only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SKDESC-xB and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Neptronic SKDESC-xB
How many BACnet points does the Neptronic SKDESC-xB have?
This list has 87 BACnet objects: 10 analog inputs, 47 analog values, 4 binary inputs, 22 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Neptronic SKDESC-xB BACnet points are writable?
30 of the 87 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Neptronic SKDESC-xB BACnet documentation?
The source is SKDESC-xB Series Electronic Steam Controller BACnet Communication Module User Guide (SKDESCXB-BACnet-250905-EUA), revision 2025-09-05, published free by Neptronic at https://www.neptronic.com/Humidifiers/PDF/2025/SKDESCXB-BACnet-250905-EUA.pdf.
What are the minimum BACnet points to integrate the Neptronic SKDESC-xB?
Start with BV 1 PowerStatus (System power on/off); MV 2 ControlMode (Control mode: External, Internal or Network); AV 1 InternalStpnt (Internal RH setpoint); AV 2 RoomRH (Room RH (writable when BV 14 = On)); AV 4 SystemDemand (Humidity demand the controller is acting on); BV 20 AlarmRelayState (Alarm relay output; on when the controller signals an alarm).
How do I enable BMS control of the Neptronic SKDESC-xB?
BV 1 PowerStatus (0 = Off, 1 = On) is writable; MSV 2 ControlMode selects External, Internal or Network control.
Does the Neptronic SKDESC-xB need a BACnet heartbeat or have a communication timeout?
Network fallback is configured with AV 30 FallbackTimeout (0-900 s), AV 31 FallbackStpnt (0-100 %) and the AV 32 FallbackDownCntr countdown; the guide lists these objects but does not spell out the fallback sequence, so test it on site.
Can the BMS supply sensor values to the Neptronic SKDESC-xB?
Room RH is written to AV 2 only while BV 14 NetworkRoomRH = On; duct RH is written to AV 3 only while MSV 3 HiLimitSensorSrc = Network. BV 15 enables an external RH setpoint.
How do I check these points on the real SKDESC-xB?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Neptronic BACnet points lists
- Room / indoor air quality controller (temperature, humidity, CO2, VOC)
Neptronic AROB universal room / IAQ controller
Neptronic AROB room controllers measuring temperature, humidity, CO2 and VOC, with 2 analog and 2 binary outputs.
Also known as: AROB, AROB24, Neptronic AROB, IAQ controller - Make-up air unit (electric heat)
Neptronic CMU Compact Make-up Air Unit
Neptronic CMU compact make-up air units with electric heating, EC fan, damper and optional exhaust fan outputs.
Also known as: CMU, Neptronic CMU - Fan coil unit controller
Neptronic EFCB Series Fan Coil Controller
Neptronic EFCB fan coil controllers (24, 120 or 240 Vac, 2 or 4 relays) for 2-pipe and 4-pipe fan coils with TFL/TDF room sensors.
Also known as: EFCB, EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4 - Fan coil unit controller
Neptronic EFCB-OE1 Series Fan Coil Controller
Neptronic EFCB-OE1 fan coil controllers (24 or 240 Vac, 0, 2 or 4 relays), an OEM variant of the EFCB series.
Also known as: EFCB-OE1, EFCB10T-OE1, EFCB12T-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1 - VAV terminal unit controller
Neptronic EVCB14N Series VAV Controller
Neptronic EVCB14N networkable VAV controllers with integrated damper actuator, pressure-independent or pressure-dependent, with 0-4 triac outputs.
Also known as: EVCB14N, EVCB14NIT0S, EVCB14NIT2S, EVCB14NIT4S, EVCB14NDT4S, EVCB14NIT0SF, EVCB14NIT4SF - VAV terminal unit controller
Neptronic EVCB14NxT4X VAV Controller (external motor)
Neptronic EVCB14N VAV controllers with four triac outputs that drive an external damper motor, pressure independent (IT4X) or dependent (DT4X).
Also known as: EVCB14NxT4X, EVCB14NIT4X, EVCB14NDT4X - VAV terminal unit controller
Neptronic EVCB44N Series VAV Controller
Neptronic EVCB44N VAV controllers without triac outputs, pressure independent (IT0S) or pressure dependent (DT0S).
Also known as: EVCB44N, EVCB44NIT0S, EVCB44NDT0S - Dual duct VAV terminal controller
Neptronic EVCBM Dual Duct VAV Controller
Neptronic EVCBM master controller used on dual duct terminals, with a second (slave) airflow channel for the other duct.
Also known as: EVCBM, EVCBM Dual Duct, EVCB dual duct - Electric duct heater / terminal reheat controller
Neptronic HECB electric duct heater controller
Neptronic electric duct heaters fitted with the HECB intelligent controller (staged and SSR, with optional EAS airflow sensing).
Also known as: HECB, HEC, Neptronic HECB, electric duct heater controller - Electric steam humidifier
Neptronic SK300 / SKE (legacy) Steam Humidifier with NEPIC BACnet module
Legacy Neptronic SK300 and SKE electric steam humidifiers fitted with the NEPIC BACnet MS/TP communication module.
Also known as: SK300, SKE, Neptronic SK300, Neptronic SKE, NEPIC, SK300-BACNET, SKE-BACNET - Electric steam humidifier
Neptronic SKE4
Neptronic SKE4 electric (heating element) steam humidifiers, indoor and outdoor versions.
Also known as: SKE4 electric steam humidifier, SKE4-N, SKE4-E, SKE4 BACnet - Gas-fired steam humidifier
Neptronic SKG (legacy, pre-SKG4) gas-fired humidifier with NEPICSKG BACnet module
Older Neptronic SKG gas-fired steam humidifiers (before the SKG4) with the NEPICSKG BACnet MS/TP module, one to four tanks.
Also known as: SKG, SKG3, Neptronic SKG, NEPICSKG, SKG-BACNET, SKG gas fired humidifier - Gas-fired steam humidifier
Neptronic SKG4
Neptronic SKG4 gas-fired steam humidifiers with up to four humidifier modules.
Also known as: SKG4 gas fired humidifier, SKG4-N, SKG4-E, SKG4 BACnet - High-pressure atomising humidifier zone controller
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH EZC zone controller
EZC zone controllers of older Neptronic SKH high pressure atomising humidifiers, before the SKH4; each zone is its own BACnet device.
Also known as: SKH EZC, EZC, Neptronic SKH zone controller, SKH-BACnet Guide-210104 - High-pressure atomising humidifier
Neptronic SKH (legacy, pre-SKH4) high pressure atomiser - SKH pump station
The SKH pump station (master board) of older Neptronic SKH high pressure atomising humidifiers, before the SKH4.
Also known as: SKH, Neptronic SKH, SKH high pressure atomiser, SKH-BACnet Guide-210104 - High-pressure atomizing humidifier / cooler
Neptronic SKH4
Neptronic SKH4 high-pressure water atomizing humidifiers and evaporative coolers with up to six zones (A-F).
Also known as: SKH4 high-pressure atomizer, SKH4 BACnet - Reverse osmosis water treatment unit
Neptronic SKRO
Neptronic SKRO reverse osmosis water treatment units feeding humidifiers.
Also known as: SKRO reverse osmosis, SKRO BACnet - Steam-to-steam humidifier
Neptronic SKS4
Neptronic SKS4 steam-to-steam (boiler steam heated) humidifiers.
Also known as: SKS4 steam to steam humidifier, SKS4 BACnet - Evaporative humidifier
Neptronic SKV
Neptronic SKV evaporative (media) humidifiers with up to four modules.
Also known as: SKV evaporative humidifier, SKV BACnet - Evaporative cooler / humidifier
Neptronic SKVF
Neptronic SKVF series evaporative coolers (also used for humidification).
Also known as: SKVF evaporative cooler, SKVF Series, SKVF BACnet - Fan coil / zone thermostat controller
Neptronic TFxB Series Thermostat Controller
Neptronic TFxB24 communicating thermostats for 2-pipe and 4-pipe fan coils and zone heating/cooling, including the humidity (TFHB) and OE variants.
Also known as: TFCB24F3XYZ1, TFCB24F3XY2, TFHB24F3XYZ1, TFHB24F3XYZ2, TFCB24P3-OE1, TFHB24P3-OE1, TFHB24P3-OE2, TFxB24 - Zone thermostat controller (VAV / fan coil)
Neptronic TROB24 thermostat controller
Neptronic TROB24 communicating thermostats with universal inputs, analog outputs and triac (on/off, pulsing or floating) outputs.
Also known as: TROB24, TROB, TROB24T4, Neptronic TROB - Fan coil / zone thermostat controller
Neptronic TSUB universal wall-mount controller
Neptronic TSUB universal wall-mount controllers for fan coils, heat pumps and zone heating/cooling.
Also known as: TSUB, TSUB24, Neptronic TSUB - Fan coil / zone thermostat controller
Neptronic TUCB / TUHB universal controller (TUxB24C6X2)
Neptronic TUCB (cooling/heating) and TUHB (with humidity) universal room controllers, model TUxB24C6X2.
Also known as: TUCB, TUHB, TUxB24C6X2, TUCB24C6X2, TUHB24C6X2 - Fan coil / zone thermostat controller
Neptronic TUUB universal wall-mount controller
Neptronic TUUB universal wall-mount controllers for fan coils, heat pumps, VFDs and zone heating/cooling.
Also known as: TUUB, TUUB24, Neptronic TUUB
Source: SKDESC-xB Series Electronic Steam Controller BACnet Communication Module User Guide · SKDESCXB-BACnet-250905-EUA · rev. 2025-09-05. Object names, instances and units are reproduced as published; descriptions are our own.