- Home
- BACnet points lists
- Yaskawa
- Z1000 HVAC drive (embedded BACnet MS/TP)
Variable frequency drive (HVAC) · BACnet points list
Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP) BACnet points list
Updated 29 October 2026
The Z1000 has BACnet MS/TP built into its RS-485 terminals; set H5-08 = 3 to select it. The fixed object list covers analog and digital I/O, run/fault/reset commands, the frequency and PI setpoint references, output monitors and a long set of fault and status flags. AV29/AV30 give indirect access to any drive parameter by Modbus register number.
This page lists 107 BACnet objects for the Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Yaskawa’s own free documentation, linked below.
- Manufacturer
- Yaskawa
- Model
- Z1000 HVAC drive (embedded BACnet MS/TP)
- Equipment
- Variable frequency drive (HVAC)
- Equipment type
- VFDs & pumps
- BACnet objects
- 107 (32 writable)
- Transport
- BACnet MS/TP
- Firmware
- PICS lists application software 1.3, firmware VSE90101X
- Default device instance
- 1
- Also known as
- Z1000, CIMR-ZU, CIMR-ZUA, Z1000 AC Drive for HVAC Fan and Pump, SIEP C710616 45
Reference only, provided as-is: verify against Yaskawa’s current documentation and the live device before use. Not official Yaskawa information. Terms of use.
BMS integration notes: Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP)
Set H5-08 = 3 (BACnet), the MS/TP address in H5-01, the baud rate in H5-02 and the device instance in H5-14/H5-15, then cycle power. Set b1-01 = 2 and b1-02 = 2 so the network supplies the frequency reference and run command. Write BV1 RUN FWD and AV2 Frequency Command, read BV13/BV16 and AV10/AV12/AV13, and reset faults with BV4.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | RUN FWD | Start/stop from the BMS (drive) | Command |
| AV 2 | Frequency Command | Frequency reference, units per o1-03 | Command |
| BV 4 | FAULT RESET | Reset a tripped drive | Command |
| BV 13 | RUN-STOP | Running status | Read |
| BV 15 | READY | Drive ready to run | Read |
| AV 10 | Output Frequency | Output frequency, units per o1-03 | Read |
| AV 12 | Output Current | Motor amps | Read |
| AV 13 | Output Power | Drive power in kW | Read |
| BV 16 | FAULT | Any active drive fault | Read |
| AV 7 | Fault Details (Bitmapped) | Bit-coded active fault flags | Read |
Enable & remote start
Table B.1: set b1-01 Frequency Reference Selection 1 = 2 and b1-02 Run Command Selection 1 = 2 (serial communication); b1-15/b1-16 = 2 do the same for External Reference 2. With H5-12 = 0 (default) BV1 runs forward and BV2 runs reverse; with H5-12 = 1 bit 0 is run/stop and bit 1 sets direction. Monitoring, parameter access, fault set/reset and the multi-function inputs work at any time, whatever b1-01/b1-02 are set to.
Heartbeat & communication loss
H5-05 = 1 (default) turns on CE detection: if the drive gets no data from the master for H5-09 (0.0-10.0 s, default 2.0 s) it raises a CE fault and acts per H5-04 (0 ramp to stop, 1 coast, 2 fast stop, 3 alarm only and keep running (default), 4 run at d1-04).
Sensors & values from the BMS
AV3 PI Setpoint lets the BMS write the PI setpoint; BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it. The object list has no writable PI feedback.
Network setup
- H5-08 = 3 selects BACnet; H5-01 is the MS/TP address (0-FFH, default 1FH) and must be unique.
- H5-02 sets the baud rate, 1200 to 76800 bps (BACnet default is setting 3 = 9600 bps); 115200 bps gives an oPE29 error.
- H5-03 sets parity (default none); data is 8 bits with 1 stop bit.
- Device instance = H5-14 (low word) + H5-15 (high word), in hex; default 1. Example: 1234 is H5-14 = 4D2H, H5-15 = 0.
- H5 settings and the device instance take effect after a power cycle.
- Up to 127 drives per MS/TP segment.
Watch out for
- H5-04 defaults to Alarm Only, so the drive keeps running when BACnet traffic stops.
- BV56 Parameter Enter writes EEPROM (rated about 100,000 writes); don't use it cyclically.
- Don't mix the packed words (AV1, AV4, AV5) with the single-bit BV/BO objects they duplicate.
- Terminal inputs and BACnet multi-function inputs are ORed together.
- Frequency objects use the o1-03 display units, which are not always Hz.
Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Analog Input 1 Level | Analog input 1 level; Modbus 004EH | % | Read | |
| AI | 2 | Analog Input 2 Level | Analog input 2 level; Modbus 004FH | % | Read | |
| AI | 6 | Display Format o1-03 | Display units setting o1-03; Modbus 0502H | Read | ||
| AI | 7 | Scale Format b5-20 | PI scaling format b5-20; Modbus 01E2H | Read | ||
| AI | 8 | Inverter Model o2-04 | Drive model code o2-04; Modbus 0508F | Read | ||
| AI | 9 | Rated Current n9-01 | Drive rated current n9-01; Modbus 05D0H | A | Read | |
| AO | 1 | Analog Output 1 Level | Analog output 1 level, written by the network; Modbus 0007H | % | Command | |
| AO | 2 | Analog Output 2 Level | Analog output 2 level, written by the network; Modbus 0008H | % | Command | |
| AV | 1 | Operation Cmd (Bitmapped) | Packed run/fault/MF-input command word; Modbus 0x0001 | Command | ||
| AVmin | 2 | Frequency Command | Frequency reference from the network; Modbus 0002H | Hz (display units per o1-03) | Command | |
| AV | 3 | PI Setpoint | PI setpoint from the network; Modbus 0006H | % | Command | |
| AV | 4 | MF Output Cmd (Bitmapped) | Packed relay output command word; Modbus 0x0009 | Command | ||
| AV | 5 | Reference Select Cmd (Bitmapped) | Packed reference-select command word; Modbus 0x000F | Command | ||
| AV | 6 | Drive Status (Bitmapped) | Packed drive status: run, reverse, ready, fault, outputs; Modbus 0x0020 | Read | ||
| AVmin | 7 | Fault Details (Bitmapped) | Packed fault flags; Modbus 0x0021 | Read | ||
| AV | 8 | Data Link Status (Bitmapped) | Packed data-link status; Modbus 0x0022 | Read | ||
| AV | 9 | Frequency Reference | Active frequency reference; Modbus 0040H | Hz (display units per o1-03) | Read | |
| AVmin | 10 | Output Frequency | Output frequency; Modbus 0041H | Hz (display units per o1-03) | Read | |
| AV | 11 | Output Voltage | Output voltage; Modbus 0045H | V | Read | |
| AVmin | 12 | Output Current | Output (motor) current; Modbus 0026H | A | Read | |
| AVmin | 13 | Output Power | Output power; Modbus 0047H | kW | Read | |
| AV | 14 | Torque Reference | Torque reference; Modbus 0048H | % | Read | |
| AV | 18 | DC Bus Voltage | DC bus voltage; Modbus 0031H | V | Read | |
| AV | 19 | PI Feedback Level | PI feedback level; Modbus 0038H | % | Read | |
| AV | 20 | PI Input Level | PI input level; Modbus 0039H | % | Read | |
| AV | 21 | PI Output Level | PI output level; Modbus 003AH | % | Read | |
| AV | 22 | CPU Software | Drive software number; Modbus 005BH | Read | ||
| AV | 23 | Flash Number | Flash ID number; Modbus 004DH | Read | ||
| AV | 25 | kVA Setting | Drive kVA setting; Modbus 0508H | Read | ||
| AV | 26 | Control Method | Control method; Modbus 0043H | Read | ||
| AV | 27 | Accel Time | Acceleration time; Modbus 0200H | s | Write | |
| AV | 28 | Decel Time | Deceleration time; Modbus 0201H | s | Write | |
| AV | 29 | Param Number | Modbus register number for indirect parameter access | Write | ||
| AV | 30 | Param Data | Value of the register selected in AV29 | Write | ||
| BI | 1 | Input Terminal 1 | Digital input terminal S1 status; Modbus 002BH:bit 0 | Read | Active: ON, Inactive: OFF | |
| BI | 2 | Input Terminal 2 | Digital input terminal S2 status; Modbus 002BH:bit 1 | Read | Active: ON, Inactive: OFF | |
| BI | 3 | Input Terminal 3 | Digital input terminal S3 status; Modbus 002BH:bit 2 | Read | Active: ON, Inactive: OFF | |
| BI | 4 | Input Terminal 4 | Digital input terminal S4 status; Modbus 002BH:bit 3 | Read | Active: ON, Inactive: OFF | |
| BI | 5 | Input Terminal 5 | Digital input terminal S5 status; Modbus 002BH:bit 4 | Read | Active: ON, Inactive: OFF | |
| BI | 6 | Input Terminal 6 | Digital input terminal S6 status; Modbus 002BH:bit 5 | Read | Active: ON, Inactive: OFF | |
| BI | 7 | Input Terminal 7 | Digital input terminal S7 status; Modbus 002BH:bit 6 | Read | Active: ON, Inactive: OFF | |
| BI | 8 | Multi-Function Out 1 | Multi-function output 1 status; Modbus 0020H:bit 5 | Read | Active: ON, Inactive: OFF | |
| BI | 9 | Multi-Function Out 2 | Multi-function output 2 status; Modbus 0020H:bit 6 | Read | Active: ON, Inactive: OFF | |
| BO | 1 | MF Output M1-M2 | Relay output M1-M2 command; Modbus 0009H:bit 0 | Command | Active: ON, Inactive: OFF | |
| BO | 2 | MF Output M3-M4 | Relay output M3-M4 command; Modbus 0009H:bit 1 | Command | Active: ON, Inactive: OFF | |
| BO | 3 | MF Output MA-MC | Relay output MA-MC command; Modbus 0009H:bit 2 | Command | Active: ON, Inactive: OFF | |
| BO | 4 | Ref Sel: PI Setpoint | Select the network PI setpoint; Modbus 000FH:bit 1 | Command | Active: ON, Inactive: OFF | |
| BO | 5 | Ref Sel: Term S5 IN | Reference-select bit for terminal S5 input; Modbus 000FH:bit 8 | Command | Active: ON, Inactive: OFF | |
| BO | 6 | Ref Sel: Term S6 IN | Reference-select bit for terminal S6 input; Modbus 000FH:bit 9 | Command | Active: ON, Inactive: OFF | |
| BO | 7 | Refl Sel: Term S7 IN | Reference-select bit for terminal S7 input; Modbus 000FH:bit 10 | Command | Active: ON, Inactive: OFF | |
| BVmin | 1 | RUN FWD | Run forward command; Modbus 0001H:bit 0 | Command | Active: RUN, Inactive: OFF | |
| BV | 2 | RUN REV | Run reverse command; Modbus 0001H:bit 1 | Command | Active: REV, Inactive: OFF | |
| BV | 3 | EXT FAULT | External fault (EF0) command; Modbus 0001H:bit 2 | Command | Active: FAULT, Inactive: OFF | |
| BVmin | 4 | FAULT RESET | Fault reset command; Modbus 0001H:bit 3 | Command | Active: RESET, Inactive: OFF | |
| BV | 5 | COM NET | MF input 1; ComRef when H1-01 = 40; Modbus 0001H:bit 4 | Command | Active: COM, Inactive: LOCAL | |
| BV | 6 | COM CNTRL | MF input 2; ComCtrl when H1-02 = 41; Modbus 0001H:bit 5 | Command | Active: COM, Inactive: LOCAL | |
| BV | 7 | MF Input 3 Cmd | Multi-function input 3 via network; Modbus 0001H:bit 6 | Command | Active: ON, Inactive: OFF | |
| BV | 8 | MF Input 4 Cmd | Multi-function input 4 via network; Modbus 0001H:bit 7 | Command | Active: ON, Inactive: OFF | |
| BV | 9 | MF Input 5 Cmd | Multi-function input 5 via network; Modbus 0001H:bit 8 | Command | Active: ON, Inactive: OFF | |
| BV | 10 | MF Input 6 Cmd | Multi-function input 6 via network; Modbus 0001H:bit 9 | Command | Active: ON, Inactive: OFF | |
| BV | 11 | MF Input 7 Cmd | Multi-function input 7 via network; Modbus 0001H:bit 10 | Command | Active: ON, Inactive: OFF | |
| BV | 12 | Set Fault Contact Cmd | Enables network control of the fault relay; Modbus 0009H:bit 6 | Command | Active: ENABLE, Inactive: OFF | |
| BVmin | 13 | RUN-STOP | Drive running; Modbus 0020H:bit 0 | Read | Active: RUN, Inactive: OFF | |
| BV | 14 | REV-FWD | Rotation direction; Modbus 0020H:bit 1 | Read | Active: REV, Inactive: FWD | |
| BVmin | 15 | READY | Drive ready; Modbus 0020H:bit 2 | Read | Active: READY, Inactive: OFF | |
| BVmin | 16 | FAULT | Drive faulted; Modbus 0020H:bit 3 | Read | Active: FAULTED, Inactive: OFF | |
| BV | 17 | Data Set Error | Data setting error; Modbus 0020H:bit 4 | Read | Active: ERROR, Inactive: OFF | |
| BV | 18 | Overcurrent – Ground Fault | Modbus 0021H:bit 0 | Read | Active: OC-GF, Inactive: OFF | |
| BV | 19 | Main Circuit Overvoltage | Modbus 0021H:bit 1 | Read | Active: OV, Inactive: OFF | |
| BV | 20 | Drive Overload | Modbus 0021H:bit 2 | Read | Active: OL2, Inactive: OFF | |
| BV | 21 | Drive Overheat | Modbus 0021H:bit 3 | Read | Active: OH1-OH2, Inactive: OFF | |
| BV | 22 | Fuse Blown | Modbus 0021H:bit 5 | Read | Active: PUF, Inactive: OFF | |
| BV | 23 | PI Feedback Loss | Modbus 0021H:bit 6 | Read | Active: FBL, Inactive: OFF | |
| BV | 24 | External Fault | Modbus 0021H:bit 7 | Read | Active: EF0-EF, Inactive: OFF | |
| BV | 25 | Hardware Error | Modbus 0021H:bit 8 | Read | Active: CPF, Inactive: OFF | |
| BV | 26 | Mtr Ovrld-OvrTorque | Modbus 0021H:bit 9 | Read | Active: OL1-OL3, Inactive: OFF | |
| BV | 27 | Overspeed | Modbus 0021H:bit 10 | Read | Active: OS-DEV, Inactive: OFF | |
| BV | 28 | Main CKT Undervoltage | Modbus 0021H:bit 11 | Read | Active: UV, Inactive: OFF | |
| BV | 29 | MCU, Cntl Pwr Sy Err | Modbus 0021H:bit 12 | Read | Active: UV1-2-3, Inactive: OFF | |
| BV | 30 | Output Phase Loss | Modbus 0021H:bit 13 | Read | Active: LF, Inactive: OFF | |
| BV | 31 | Communication Error | Modbus 0021H:bit 14 | Read | Active: CE, Inactive: OFF | |
| BV | 32 | Operator Disconnect | Modbus 0021H:bit 15 | Read | Active: OPR, Inactive: OFF | |
| BV | 33 | Operating | Modbus 002CH:bit 0 | Read | Active: OPERATING, Inactive: OFF | |
| BV | 34 | Aero Speed | Modbus 002CH:bit 1 | Read | Active: ON, Inactive: OFF | |
| BV | 35 | Frequency Agree | Modbus 002CH:bit 2 | Read | Active: ON, Inactive: OFF | |
| BV | 36 | Desired Frequency Agree | Modbus 002CH:bit 3 | Read | Active: ON, Inactive: OFF | |
| BV | 37 | Frequency Detect 1 | Modbus 002CH:bit 4 | Read | Active: ON, Inactive: OFF | |
| BV | 38 | Frequency Detect 2 | Modbus 002CH:bit 5 | Read | Active: ON, Inactive: OFF | |
| BV | 39 | Drive Startup Complete | Modbus 002CH:bit 6 | Read | Active: ON, Inactive: OFF | |
| BV | 40 | Low Voltage Detect | Modbus 002CH:bit 7 | Read | Active: ON, Inactive: OFF | |
| BV | 41 | Base Block | Modbus 002CH:bit 8 | Read | Active: ON, Inactive: OFF | |
| BV | 42 | Frequency Reference Mode | Modbus 002CH:bit 9 | Read | Active: COM, Inactive: LOCAL | |
| BV | 43 | Run Command Mode | Modbus 002CH:bit 10 | Read | Active: COM, Inactive: LOCAL | |
| BV | 44 | Overtorque Detect | Modbus 002CH:bit 11 | Read | Active: ON, Inactive: OFF | |
| BV | 45 | Frequency Refer Lost | Modbus 002CH:bit 12 | Read | Active: ON, Inactive: OFF | |
| BV | 46 | Retry Error | Modbus 002CH:bit 13 | Read | Active: ON, Inactive: OFF | |
| BV | 47 | Modbus Comms Error | Modbus 002CH:bit 14 | Read | Active: ON, Inactive: OFF | |
| BV | 48 | Modbus Timeout Error | Modbus 002CH:bit 15 | Read | Active: ON, Inactive: OFF | |
| BV | 49 | CRC Error | Modbus 003DH:bit 0 | Read | Active: ON, Inactive: OFF | |
| BV | 50 | Invalid Data Length | Modbus 003DH:bit 1 | Read | Active: ON, Inactive: OFF | |
| BV | 51 | Parity Error | Modbus 003DH:bit 3 | Read | Active: ON, Inactive: OFF | |
| BV | 52 | Overrun Error | Modbus 003DH:bit 4 | Read | Active: ON, Inactive: OFF | |
| BV | 53 | Framing Error | Modbus 003DH:bit 5 | Read | Active: ON, Inactive: OFF | |
| BV | 54 | Timeout Error | Modbus 003DH:bit 6 | Read | Active: ON, Inactive: OFF | |
| BV | 55 | Parameter Accept | ON = accept parameter writes into RAM; Modbus 0910H:bit 0 | Write | Active: ON, Inactive: OFF | |
| BV | 56 | Parameter Enter | ON = enter parameter writes and save to EEPROM; Modbus 0900H:bit 0 | Write | Active: ON, Inactive: OFF | |
| BV | 57 | Drive Comm Error | Drive communication error | Read | Active: ON, Inactive: OFF |
No points match these filters.
Object ID lookup: Yaskawa Z1000 HVAC drive point IDs by name
AI1Analog Input 1 LevelAI2Analog Input 2 LevelAI6Display Format o1-03AI7Scale Format b5-20AI8Inverter Model o2-04AI9Rated Current n9-01AO1Analog Output 1 LevelAO2Analog Output 2 LevelAV1Operation Cmd (Bitmapped)AV2Frequency CommandAV3PI SetpointAV4MF Output Cmd (Bitmapped)AV5Reference Select Cmd (Bitmapped)AV6Drive Status (Bitmapped)AV7Fault Details (Bitmapped)AV8Data Link Status (Bitmapped)AV9Frequency ReferenceAV10Output FrequencyAV11Output VoltageAV12Output CurrentAV13Output PowerAV14Torque ReferenceAV18DC Bus VoltageAV19PI Feedback LevelAV20PI Input LevelAV21PI Output LevelAV22CPU SoftwareAV23Flash NumberAV25kVA SettingAV26Control MethodAV27Accel TimeAV28Decel TimeAV29Param NumberAV30Param DataBI1Input Terminal 1BI2Input Terminal 2BI3Input Terminal 3BI4Input Terminal 4BI5Input Terminal 5BI6Input Terminal 6BI7Input Terminal 7BI8Multi-Function Out 1BI9Multi-Function Out 2BO1MF Output M1-M2BO2MF Output M3-M4BO3MF Output MA-MCBO4Ref Sel: PI SetpointBO5Ref Sel: Term S5 INBO6Ref Sel: Term S6 INBO7Refl Sel: Term S7 INBV1RUN FWDBV2RUN REVBV3EXT FAULTBV4FAULT RESETBV5COM NETBV6COM CNTRLBV7MF Input 3 CmdBV8MF Input 4 CmdBV9MF Input 5 CmdBV10MF Input 6 CmdBV11MF Input 7 CmdBV12Set Fault Contact CmdBV13RUN-STOPBV14REV-FWDBV15READYBV16FAULTBV17Data Set ErrorBV18Overcurrent – Ground FaultBV19Main Circuit OvervoltageBV20Drive OverloadBV21Drive OverheatBV22Fuse BlownBV23PI Feedback LossBV24External FaultBV25Hardware ErrorBV26Mtr Ovrld-OvrTorqueBV27OverspeedBV28Main CKT UndervoltageBV29MCU, Cntl Pwr Sy ErrBV30Output Phase LossBV31Communication ErrorBV32Operator DisconnectBV33OperatingBV34Aero SpeedBV35Frequency AgreeBV36Desired Frequency AgreeBV37Frequency Detect 1BV38Frequency Detect 2BV39Drive Startup CompleteBV40Low Voltage DetectBV41Base BlockBV42Frequency Reference ModeBV43Run Command ModeBV44Overtorque DetectBV45Frequency Refer LostBV46Retry ErrorBV47Modbus Comms ErrorBV48Modbus Timeout ErrorBV49CRC ErrorBV50Invalid Data LengthBV51Parity ErrorBV52Overrun ErrorBV53Framing ErrorBV54Timeout ErrorBV55Parameter AcceptBV56Parameter EnterBV57Drive Comm Error
Integration notes
- Object IDs marked Not used (AI3-AI5, AV24) are left out. AV15-AV17 (MF Input Status, Drive Status 2, MF Output Status) are named in the table but have no register, units or access, so they are left out too.
- AV1, AV4 and AV5 are packed command words; the manual says not to use them together with the single-bit objects they duplicate (AV1 with BV1-BV11 or AV5, AV4 with BO1-BO3 or BV12, AV5 with AV1, BO4 or BV9-BV11).
- Frequency units follow the o1-03 display setting.
- AV29/AV30 with BV55/BV56 read and write drive parameters that are not in the object list.
- The device object name is writable from BACnet (20 characters) and takes effect after a power cycle.
- Each description gives the drive's Modbus register where the manual lists one.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Z1000 HVAC drive (embedded BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP)
How many BACnet points does the Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP) have?
This list has 107 BACnet objects: 6 analog inputs, 2 analog outputs, 26 analog values, 9 binary inputs, 7 binary outputs, 57 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP) BACnet points are writable?
32 of the 107 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP) BACnet documentation?
The source is YASKAWA AC Drive Z1000, AC Drive for HVAC Fan and Pump, Programming Manual (Appendix B, BACnet Communications) (SIEP C710616 45F), revision 2021-06, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPC71061645&cmd=documents&documentName=SIEPC71061645.pdf.
What are the minimum BACnet points to integrate the Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP)?
Start with BV 1 RUN FWD (Start/stop from the BMS (drive)); AV 2 Frequency Command (Frequency reference, units per o1-03); BV 4 FAULT RESET (Reset a tripped drive); BV 13 RUN-STOP (Running status); BV 15 READY (Drive ready to run); AV 10 Output Frequency (Output frequency, units per o1-03); AV 12 Output Current (Motor amps); AV 13 Output Power (Drive power in kW); BV 16 FAULT (Any active drive fault); AV 7 Fault Details (Bitmapped) (Bit-coded active fault flags).
How do I enable BMS control of the Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP)?
Table B.1: set b1-01 Frequency Reference Selection 1 = 2 and b1-02 Run Command Selection 1 = 2 (serial communication); b1-15/b1-16 = 2 do the same for External Reference 2. With H5-12 = 0 (default) BV1 runs forward and BV2 runs reverse; with H5-12 = 1 bit 0 is run/stop and bit 1 sets direction. Monitoring, parameter access, fault set/reset and the multi-function inputs work at any time, whatever b1-01/b1-02 are set to.
Does the Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
H5-05 = 1 (default) turns on CE detection: if the drive gets no data from the master for H5-09 (0.0-10.0 s, default 2.0 s) it raises a CE fault and acts per H5-04 (0 ramp to stop, 1 coast, 2 fast stop, 3 alarm only and keep running (default), 4 run at d1-04).
Can the BMS supply sensor values to the Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP)?
AV3 PI Setpoint lets the BMS write the PI setpoint; BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it. The object list has no writable PI feedback.
How do I check these points on the real Z1000 HVAC drive (embedded BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Yaskawa BACnet points lists
- Variable frequency drive (HVAC)
Yaskawa HV600 HVAC drive (embedded BACnet MS/TP)
Yaskawa HV600 HVAC fan and pump drives (HV60U, 208 V and 480 V class) using the built-in RS-485 port with H5-08 set to BACnet.
Also known as: HV600, HV60U, HV600 AC drive, HV600 BACnet MS/TP, SIEPC71061732 - Variable frequency drive with bypass (HVAC)
Yaskawa HV600 Narrow & Enclosed Bypass (BACnet MS/TP)
Yaskawa HV600 Narrow and Enclosed Bypass packages (H6B models) connected to BACnet MS/TP at the bypass controller.
Also known as: HV600 Bypass, HV600 Narrow Bypass, HV600 Enclosed Bypass, H6B1, H6BP, HV600 bypass controller, SIEPYAIH6B01 - Variable frequency drive BACnet IP option card
Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
Yaskawa HV600, FP605, Z1000U, GA500, GA700 and GA800 drives and HV600/FP605 bypasses fitted with the JOHB-SMP3 card.
Also known as: JOHB-SMP3, SMP3, HV600 BACnet/IP, Z1000U BACnet/IP, FP605 BACnet/IP, GA800 BACnet/IP, SIEP C730600 0MB - Variable frequency drive BACnet MS/TP option card
Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)
Yaskawa A1000, P1000, iQpump1000, U1000, FP605 and iQpump605 drives fitted with the SI-B3 BACnet MS/TP option card.
Also known as: SI-B3, SI-B3/V, A1000 BACnet, P1000 BACnet, iQpump1000 BACnet, U1000 BACnet, FP605 BACnet, iQpump605 BACnet, TOEPYAICOM22 - Variable frequency drive BACnet MS/TP option card
Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive)
Yaskawa V1000 compact drives (CIMR-VA, software VST910120 and later) fitted with the SI-B3/V BACnet MS/TP option.
Also known as: SI-B3/V, SI-B3 V1000, V1000 BACnet, V1000 BACnet MS/TP, CIMR-VA BACnet, TOEP YAICOM 19 - Variable frequency drive with bypass (HVAC)
Yaskawa Z1000 Bypass (BACnet MS/TP)
Yaskawa Z1000 Bypass packages (Z1B1, 208 V and 480 V) connected to BACnet MS/TP at the bypass controller.
Also known as: Z1000 Bypass, Z1B1, Z1000 drive bypass, Z1000 bypass controller, SIEP YAIZ1B 01 - Variable frequency drive with bypass (HVAC)
Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP)
Yaskawa Z1000U HVAC Matrix low-harmonic drive bypass packages (Z1D1, 208 V and 480 V) connected to BACnet MS/TP at the bypass controller.
Also known as: Z1000U Bypass, Z1000U Matrix Bypass, Z1D1, Z1000U HVAC MATRIX Drive Bypass, Z1000U low harmonic bypass, SIEP YAIZ1D 01
Source: YASKAWA AC Drive Z1000, AC Drive for HVAC Fan and Pump, Programming Manual (Appendix B, BACnet Communications) · SIEP C710616 45F · rev. 2021-06. Object names, instances and units are reproduced as published; descriptions are our own.