Variable frequency drive BACnet MS/TP option card · BACnet points list
Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives) BACnet points list
Updated 29 October 2026
The SI-B3 is a plug-in card that puts Yaskawa 1000-series and FP605/iQpump605 drives on BACnet MS/TP. Its fixed object list mirrors the drive's Modbus registers: analog and digital I/O, run/fault/reset commands, frequency and PID setpoint references, output monitors, fault and status flags, and later energy, run-time and fault-code objects. AV29/AV30 give generic access to any drive parameter.
This page lists 121 BACnet objects for the Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Yaskawa’s own free documentation, linked below.
- Manufacturer
- Yaskawa
- Model
- SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)
- Equipment
- Variable frequency drive BACnet MS/TP option card
- Equipment type
- VFDs & pumps
- BACnet objects
- 121 (32 writable)
- Transport
- BACnet MS/TP
- Firmware
- Option software VST800265+ for AV31-AV34, VST800266+ for AV35-AV42 and BI28-BI29
- Default device instance
- 1
- Also known as
- SI-B3, SI-B3/V, A1000 BACnet, P1000 BACnet, iQpump1000 BACnet, U1000 BACnet, FP605 BACnet, iQpump605 BACnet, TOEPYAICOM22
Reference only, provided as-is: verify against Yaskawa’s current documentation and the live device before use. Not official Yaskawa information. Terms of use.
BMS integration notes: Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)
Fit the SI-B3, set the MS/TP address in F6-45, the baud rate in F6-46 and the device instance in F6-48/F6-49, and power-cycle. Set b1-01 = 3 and b1-02 = 3 (Option PCB) so BACnet supplies the frequency reference and run command. Write BV1 RUN FWD and AV2 Frequency Command, read BV13/BV16 and AV10/AV12/AV13, and reset faults with BV4.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | RUN FWD | Start/stop from the BMS (drive) | Command |
| AV 2 | Frequency Command | Frequency reference, units per o1-03 | Command |
| BV 4 | FAULT RESET | Reset a tripped drive | Command |
| BV 13 | RUN-STOP | Running status | Read |
| BV 15 | READY | Drive ready to run | Read |
| AV 10 | Output Frequency | Output frequency, units per o1-03 | Read |
| AV 12 | Output Current | Motor amps | Read |
| AV 13 | Output Power | Drive power in kW | Read |
| BV 16 | FAULT | Any active drive fault | Read |
| AV 40 | Last Drive Fault | Most recent fault code | Read |
Enable & remote start
b1-01 Frequency Reference Selection 1 = 3 (Option PCB) and b1-02 Run Command Selection 1 = 3 (Option PCB). The defaults differ by drive model. BV5 COM NET and BV6 COM CNTRL (COM/LOCAL) are also provided.
Heartbeat & communication loss
When the drive loses the option link it raises bUS (Option Communication Error) and acts per F6-01: 0 ramp to stop, 1 coast, 2 fast stop, 3 alarm only, 4 alarm and run at d1-04, 5 alarm and ramp stop (4 and 5 only on some drives). F6-04 sets the bUS detection delay and F7-16 a communication-loss timeout in tenths of a second (both need option software VST800265+). F6-14 = 1 resets the bUS fault automatically when communication returns.
Sensors & values from the BMS
AV3 PID Setpoint lets the BMS write the PID setpoint; BO4 Ref Sel: PID Setpoint (or AV5 bit 1) selects it.
Network setup
- F6-45 sets the MS/TP MAC address (0-127, default 1).
- F6-46 sets the baud rate, 1200 to 115200 bps (default setting 3 = 9600 bps).
- Device instance = F6-48 (low word) + F6-49 (high word), in hex; default 1. Example: 1234 is F6-48 = 4D2H, F6-49 = 0.
- F6-47 sets the drive transmit wait time (5-65 ms).
- Up to 127 drives per MS/TP segment; an EPICS file is available from Yaskawa.
Watch out for
- F6-01 settings 3 and 4 keep the drive running after a communication fault.
- BV56 Parameter Enter writes EEPROM; don't use it cyclically.
- Several objects only exist with newer option software (VST800265 / VST800266).
- AV39 Drive HOA Status does not work on iQpump1000, FP605 or iQpump605.
Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Analog Input 1 Level | Analog input 1 level; Modbus 004EH | % | Read | |
| AI | 2 | Analog Input 2 Level | Analog input 2 level; Modbus 004FH | % | Read | |
| AI | 6 | Display Format o1-03 | Display units setting o1-03; Modbus 0502H | Read | ||
| AI | 7 | Scale Format b5-20 | PI scaling format b5-20; Modbus 01E2H | Read | ||
| AI | 8 | Inverter Model o2-04 | Drive model code o2-04; Modbus 0508H | Read | ||
| AI | 9 | Rated Current n9-01 | Drive rated current n9-01; Modbus 05D0H | A | Read | |
| AO | 1 | Analog Output 1 Level | Analog output 1 level, written by the network; Modbus 0007H | % | Command | |
| AO | 2 | Analog Output 2 Level | Analog output 2 level, written by the network; Modbus 0008H | % | Command | |
| AV | 1 | Operation Cmd (Bitmapped) | Packed run/fault/MF-input command word; Modbus 0001H | Command | ||
| AVmin | 2 | Frequency Command | Frequency reference from the network; Modbus 0002H | Hz (display units per o1-03) | Command | |
| AV | 3 | PID Setpoint | PI setpoint from the network; Modbus 0006H | % | Command | |
| AV | 4 | MF Output Cmd (Bitmapped) | Packed relay output command word; Modbus 0009H | Command | ||
| AV | 5 | Reference Select Cmd | Packed reference-select command word; Modbus 000FH | Command | ||
| AV | 6 | Drive Status (Bitmapped) | Packed drive status: run, reverse, ready, fault, outputs; Modbus 0020H | Read | ||
| AV | 7 | Fault Details (Bitmapped) | Packed fault flags; Modbus 0021H | Read | ||
| AV | 8 | Data Link Status (Bitmapped) | Packed data-link status; Modbus 0022H | Read | ||
| AV | 9 | Frequency Reference | Active frequency reference; Modbus 0040H | Hz (display units per o1-03) | Read | |
| AVmin | 10 | Output Frequency | Output frequency; Modbus 0041H | Hz (display units per o1-03) | Read | |
| AV | 11 | Output Voltage | Output voltage; Modbus 0045H | V | Read | |
| AVmin | 12 | Output Current | Output (motor) current; Modbus 0026H | A | Read | |
| AVmin | 13 | Output Power | Output power; Modbus 0047H | kW | Read | |
| AV | 14 | Torque Reference | Torque reference; Modbus 0048H | % | Read | |
| AV | 15 | MF Input Status | Modbus 002BH | Read | ||
| AV | 16 | Drive Status 2 | Modbus 002CH | Read | ||
| AV | 17 | MF Output Status | Modbus 002DH | Read | ||
| AV | 18 | DC Bus Voltage | DC bus voltage; Modbus 0031H | V | Read | |
| AV | 19 | PID Feedback Level | PI feedback level; Modbus 0038H | % | Read | |
| AV | 20 | PID Input Level | PI input level; Modbus 0039H | % | Read | |
| AV | 21 | PID Output Level | PI output level; Modbus 003AH | % | Read | |
| AV | 22 | CPU Software | Drive software number; Modbus 004DH | Read | ||
| AV | 23 | Flash Number | Flash ID number; Modbus 005BH | Read | ||
| AV | 24 | Comm Error Detail | Modbus 003DH | Read | ||
| AV | 25 | kVA Setting | Drive kVA setting; Modbus 0508H | Read | ||
| AV | 26 | Control Method | Control method; Modbus 0102H | Read | ||
| AV | 27 | Accel Time | Acceleration time; Modbus 0200H | s | Write | |
| AV | 28 | Decel Time | Deceleration time; Modbus 0201H | s | Write | |
| AV | 29 | Param Number | Modbus register number for indirect parameter access | Write | ||
| AV | 30 | Param Data | Value of the register selected in AV29 | Write | ||
| AV | 33 | Drive kWh | Drive energy (kWh) on A1000/P1000/iQpump/FP605; U1000 reports kWh consumed; option software VST800265+ | kWh | Read | |
| AV | 34 | Drive kWh Produced | kWh produced; U1000 only (Not Used AV34 on other drives); VST800265+ | kWh | Read | |
| AV | 35 | Drive Run Time | option software VST800266+; Modbus 004CH | h | Read | |
| AV | 36 | Out Freq in % | option software VST800266+; Modbus 003FH | % | Read | |
| AV | 37 | Out Freq in RPM | option software VST800266+; Modbus 003EH | RPM | Read | |
| AV | 38 | Torque Iq (U6-01) | option software VST800266+; Modbus 0051H | % | Read | |
| AV | 39 | Drive HOA Status | Drive HOA status (A1000/FP605/iQpump605); Drive Control Status on U1000/P1000/iQpump1000; VST800266+ | Read | ||
| AVmin | 40 | Last Drive Fault | Last drive fault code; option software VST800266+; Modbus 0081H | Read | ||
| AV | 42 | Current Sys Fault | Current system fault code; option software VST800266+; Modbus 0080H | Read | ||
| BI | 1 | Drive Input Terminal 1 | Digital input terminal S1 status; Modbus 002B: bit 0 | Read | Active: ON, Inactive: OFF | |
| BI | 2 | Drive Input Terminal 2 | Digital input terminal S2 status; Modbus 002B: bit 1 | Read | Active: ON, Inactive: OFF | |
| BI | 3 | Drive Input Terminal 3 | Digital input terminal S3 status; Modbus 002B: bit 2 | Read | Active: ON, Inactive: OFF | |
| BI | 4 | Drive Input Terminal 4 | Digital input terminal S4 status; Modbus 002B: bit 3 | Read | Active: ON, Inactive: OFF | |
| BI | 5 | Drive Input Terminal 5 | Digital input terminal S5 status; Modbus 002B: bit 4 | Read | Active: ON, Inactive: OFF | |
| BI | 6 | Drive Input Terminal 6 | Digital input terminal S6 status; Modbus 002B: bit 5 | Read | Active: ON, Inactive: OFF | |
| BI | 7 | Drive Input Terminal 7 | Digital input terminal S7 status; Modbus 002B: bit 6 | Read | Active: ON, Inactive: OFF | |
| BI | 8 | Drive Multi-Function Out 1 | Multi-function output 1 status; Modbus 0020: bit 5 | Read | Active: ON, Inactive: OFF | |
| BI | 9 | Drive Multi-Function Out 2 | Multi-function output 2 status; Modbus 0020: bit 6 | Read | Active: ON, Inactive: OFF | |
| BI | 28 | Drive Fault Status | option software VST800266+; Modbus 004B: bit 7 | Read | Active: ON, Inactive: OFF | |
| BI | 29 | Drive Alarm Status | option software VST800266+; Modbus 004B: bit 6 | Read | Active: ON, Inactive: OFF | |
| BO | 1 | MF Output M1-M2 | Relay output M1-M2 command; Modbus 0009: bit 0 | Command | Active: ON, Inactive: OFF | |
| BO | 2 | MF Output M3-M4 | Relay output M3-M4 command; Modbus 0009: bit 1 | Command | Active: ON, Inactive: OFF | |
| BO | 3 | MF Output M5-M6 | Relay output M5-M6 command; Modbus 0009: bit 2 | Command | Active: ON, Inactive: OFF | |
| BO | 4 | Ref Sel: PID Setpoint | Select the network PI setpoint; Modbus 000F: bit 1 | Command | Active: ON, Inactive: OFF | |
| BO | 5 | Ref Sel: Term S5 IN | Reference-select bit for terminal S5 input; Modbus 0001: bit 8 | Command | Active: ON, Inactive: OFF | |
| BO | 6 | Ref Sel: Term S6 IN | Reference-select bit for terminal S6 input; Modbus 0001: bit 9 | Command | Active: ON, Inactive: OFF | |
| BO | 7 | Refl Sel: Term S7 IN | Reference-select bit for terminal S7 input; Modbus 0001: bit 10 | Command | Active: ON, Inactive: OFF | |
| BVmin | 1 | RUN FWD | Run forward command; Modbus 0001: bit 0 | Command | Active: RUN, Inactive: OFF | |
| BV | 2 | RUN REV | Run reverse command; Modbus 0001: bit 1 | Command | Active: REV, Inactive: OFF | |
| BV | 3 | EXT FAULT | External fault (EF0) command; Modbus 0001: bit 2 | Command | Active: FAULT, Inactive: OFF | |
| BVmin | 4 | FAULT RESET | Fault reset command; Modbus 0001: bit 3 | Command | Active: RESET, Inactive: OFF | |
| BV | 5 | COM NET | Com Net command, COM or LOCAL (internal to option) | Command | Active: COM, Inactive: LOCAL | |
| BV | 6 | COM CNTRL | Com Cntrl command, COM or LOCAL (internal to option) | Command | Active: COM, Inactive: LOCAL | |
| BV | 7 | MF Input 3 Cmd | Multi-function input 3 via network; Modbus 0001: bit 6 | Command | Active: ON, Inactive: OFF | |
| BV | 8 | MF Input 4 Cmd | Multi-function input 4 via network; Modbus 0001: bit 7 | Command | Active: ON, Inactive: OFF | |
| BV | 9 | MF Input 5 Cmd | Multi-function input 5 via network; Modbus 0001: bit 8 | Command | Active: ON, Inactive: OFF | |
| BV | 10 | MF Input 6 Cmd | Multi-function input 6 via network; Modbus 0001: bit 9 | Command | Active: ON, Inactive: OFF | |
| BV | 11 | MF Input 7 Cmd | Multi-function input 7 via network; Modbus 0001: bit 10 | Command | Active: ON, Inactive: OFF | |
| BV | 12 | Set Fault Contact Cmd | Enables network control of the fault relay; Modbus 0009: bit 6 | Command | Active: ENABLE, Inactive: OFF | |
| BVmin | 13 | RUN-STOP | Drive running; Modbus 0020: bit 0 | Read | Active: RUN, Inactive: OFF | |
| BV | 14 | REV-FWD | Rotation direction; Modbus 0020: bit 1 | Read | Active: REV, Inactive: FWD | |
| BVmin | 15 | READY | Drive ready; Modbus 0020: bit 2 | Read | Active: READY, Inactive: OFF | |
| BVmin | 16 | FAULT | Drive faulted; Modbus 0020: bit 3 | Read | Active: FAULTED, Inactive: OFF | |
| BV | 17 | Data Set Error | Data setting error; Modbus 0020: bit 4 | Read | Active: ERROR, Inactive: OFF | |
| BV | 18 | Overcurrent - Ground Fault | Modbus 0021: bit 0 | Read | Active: OC-GF, Inactive: OFF | |
| BV | 19 | Main Circuit Overvoltage | Modbus 0021: bit 1 | Read | Active: OV, Inactive: OFF | |
| BV | 20 | Drive Overload | Modbus 0021: bit 2 | Read | Active: OL2, Inactive: OFF | |
| BV | 21 | Drive Overheat | Modbus 0021: bit 3 | Read | Active: OH1-OH2, Inactive: OFF | |
| BV | 22 | Fuse Blown | Modbus 0021: bit 5 | Read | Active: PUF, Inactive: OFF | |
| BV | 23 | PID Feedback Loss | Modbus 0021: bit 6 | Read | Active: FBL, Inactive: OFF | |
| BV | 24 | External Fault | Modbus 0021: bit 7 | Read | Active: EF0-EF, Inactive: OFF | |
| BV | 25 | Hardware Error | Modbus 0021: bit 8 | Read | Active: CPF, Inactive: OFF | |
| BV | 26 | Mtr Ovrld-OvrTorque | Modbus 0021: bit 9 | Read | Active: OL1-OL3, Inactive: OFF | |
| BV | 27 | Overspeed | Modbus 0021: bit 10 | Read | Active: OS-DEV, Inactive: OFF | |
| BV | 28 | Main CKT Undervoltage | Modbus 0021: bit 11 | Read | Active: UV, Inactive: OFF | |
| BV | 29 | MCU, Cntl Pwr Sy Err | Modbus 0021: bit 12 | Read | Active: UV1-2-3, Inactive: OFF | |
| BV | 30 | Output Phase Loss | Modbus 0021: bit 13 | Read | Active: LF, Inactive: OFF | |
| BV | 31 | Communication Error | Modbus 0021: bit 14 | Read | Active: CE, Inactive: OFF | |
| BV | 32 | Operator Disconnect | Modbus 0021: bit 15 | Read | Active: OPR, Inactive: OFF | |
| BV | 33 | Operating | Modbus 002C: bit 0 | Read | Active: OPERATING, Inactive: OFF | |
| BV | 34 | Zero Speed | Modbus 002C: bit 1 | Read | Active: ON, Inactive: OFF | |
| BV | 35 | Frequency Agree | Modbus 002C: bit 2 | Read | Active: ON, Inactive: OFF | |
| BV | 36 | Desired Frequency Agree | Modbus 002C: bit 3 | Read | Active: ON, Inactive: OFF | |
| BV | 37 | Frequency Detect 1 | Modbus 002C: bit 4 | Read | Active: ON, Inactive: OFF | |
| BV | 38 | Frequency Detect 2 | Modbus 002C: bit 5 | Read | Active: ON, Inactive: OFF | |
| BV | 39 | Drive Startup Complete | Modbus 002C: bit 6 | Read | Active: ON, Inactive: OFF | |
| BV | 40 | Low Voltage Detect | Modbus 002C: bit 7 | Read | Active: ON, Inactive: OFF | |
| BV | 41 | Base Block | Modbus 002C: bit 8 | Read | Active: ON, Inactive: OFF | |
| BV | 42 | Frequency Reference Mode | Modbus 002C: bit 9 | Read | Active: LOCAL, Inactive: COM | |
| BV | 43 | Run Command Mode | Modbus 002C: bit 10 | Read | Active: LOCAL, Inactive: COM | |
| BV | 44 | Overtorque Detect | Modbus 002C: bit 11 | Read | Active: ON, Inactive: OFF | |
| BV | 45 | Frequency Refer Lost | Modbus 002C: bit 12 | Read | Active: ON, Inactive: OFF | |
| BV | 46 | Retry Error | Modbus 002C: bit 13 | Read | Active: ON, Inactive: OFF | |
| BV | 47 | Modbus Comms Error | Modbus 002C: bit 14 | Read | Active: ON, Inactive: OFF | |
| BV | 48 | Modbus Timeout Error | Modbus 002C: bit 15 | Read | Active: ON, Inactive: OFF | |
| BV | 49 | CRC Error | Modbus 003D: bit 0 | Read | Active: ON, Inactive: OFF | |
| BV | 50 | Invalid Data Length | Modbus 003D: bit 1 | Read | Active: ON, Inactive: OFF | |
| BV | 51 | Parity Error | Modbus 003D: bit 3 | Read | Active: ON, Inactive: OFF | |
| BV | 52 | Overrun Error | Modbus 003D: bit 4 | Read | Active: ON, Inactive: OFF | |
| BV | 53 | Framing Error | Modbus 003D: bit 5 | Read | Active: ON, Inactive: OFF | |
| BV | 54 | Timeout Error | Modbus 003D: bit 6 | Read | Active: ON, Inactive: OFF | |
| BV | 55 | Parameter Accept | ON = accept parameter writes into RAM; not on FP605/iQpump605 | Write | Active: ON, Inactive: OFF | |
| BV | 56 | Parameter Enter | ON = enter parameter writes and save to EEPROM | Write | Active: ON, Inactive: OFF |
No points match these filters.
Object ID lookup: Yaskawa SI-B3 BACnet MS/TP option point IDs by name
AI1Analog Input 1 LevelAI2Analog Input 2 LevelAI6Display Format o1-03AI7Scale Format b5-20AI8Inverter Model o2-04AI9Rated Current n9-01AO1Analog Output 1 LevelAO2Analog Output 2 LevelAV1Operation Cmd (Bitmapped)AV2Frequency CommandAV3PID SetpointAV4MF Output Cmd (Bitmapped)AV5Reference Select CmdAV6Drive Status (Bitmapped)AV7Fault Details (Bitmapped)AV8Data Link Status (Bitmapped)AV9Frequency ReferenceAV10Output FrequencyAV11Output VoltageAV12Output CurrentAV13Output PowerAV14Torque ReferenceAV15MF Input StatusAV16Drive Status 2AV17MF Output StatusAV18DC Bus VoltageAV19PID Feedback LevelAV20PID Input LevelAV21PID Output LevelAV22CPU SoftwareAV23Flash NumberAV24Comm Error DetailAV25kVA SettingAV26Control MethodAV27Accel TimeAV28Decel TimeAV29Param NumberAV30Param DataAV33Drive kWhAV34Drive kWh ProducedAV35Drive Run TimeAV36Out Freq in %AV37Out Freq in RPMAV38Torque Iq (U6-01)AV39Drive HOA StatusAV40Last Drive FaultAV42Current Sys FaultBI1Drive Input Terminal 1BI2Drive Input Terminal 2BI3Drive Input Terminal 3BI4Drive Input Terminal 4BI5Drive Input Terminal 5BI6Drive Input Terminal 6BI7Drive Input Terminal 7BI8Drive Multi-Function Out 1BI9Drive Multi-Function Out 2BI28Drive Fault StatusBI29Drive Alarm StatusBO1MF Output M1-M2BO2MF Output M3-M4BO3MF Output M5-M6BO4Ref Sel: PID SetpointBO5Ref Sel: Term S5 INBO6Ref Sel: Term S6 INBO7Refl Sel: Term S7 INBV1RUN FWDBV2RUN REVBV3EXT FAULTBV4FAULT RESETBV5COM NETBV6COM CNTRLBV7MF Input 3 CmdBV8MF Input 4 CmdBV9MF Input 5 CmdBV10MF Input 6 CmdBV11MF Input 7 CmdBV12Set Fault Contact CmdBV13RUN-STOPBV14REV-FWDBV15READYBV16FAULTBV17Data Set ErrorBV18Overcurrent - Ground FaultBV19Main Circuit OvervoltageBV20Drive OverloadBV21Drive OverheatBV22Fuse BlownBV23PID Feedback LossBV24External FaultBV25Hardware ErrorBV26Mtr Ovrld-OvrTorqueBV27OverspeedBV28Main CKT UndervoltageBV29MCU, Cntl Pwr Sy ErrBV30Output Phase LossBV31Communication ErrorBV32Operator DisconnectBV33OperatingBV34Zero SpeedBV35Frequency AgreeBV36Desired Frequency AgreeBV37Frequency Detect 1BV38Frequency Detect 2BV39Drive Startup CompleteBV40Low Voltage DetectBV41Base BlockBV42Frequency Reference ModeBV43Run Command ModeBV44Overtorque DetectBV45Frequency Refer LostBV46Retry ErrorBV47Modbus Comms ErrorBV48Modbus Timeout ErrorBV49CRC ErrorBV50Invalid Data LengthBV51Parity ErrorBV52Overrun ErrorBV53Framing ErrorBV54Timeout ErrorBV55Parameter AcceptBV56Parameter Enter
Integration notes
- Objects named Not Used (AI3-AI5, AV31, AV32, AV41, BI10-BI27, BI30) are left out.
- Drive-dependent object names: AV33 is Drive kWh on A1000, P1000, iQpump1000, FP605 and iQpump605 but Drive kWh Consumed on U1000; AV34 is Drive kWh Produced on U1000 and Not Used AV34 on the other drives; AV39 is Drive HOA Status on A1000, FP605 and iQpump605 but Drive Control Status on U1000, P1000 and iQpump1000. The names listed here are the A1000-family names except AV34 (U1000 only).
- AV1, AV4 and AV5 are packed command words; don't combine them with the single-bit objects they duplicate.
- Frequency units follow the drive's o1-03 display setting.
- Each description gives the drive Modbus register where the manual lists one.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)
How many BACnet points does the Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives) have?
This list has 121 BACnet objects: 6 analog inputs, 2 analog outputs, 39 analog values, 11 binary inputs, 7 binary outputs, 56 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives) BACnet points are writable?
32 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives) BACnet documentation?
The source is YASKAWA AC Drive Option BACnet MS/TP Installation & Technical Manual, Model SI-B3 (TOEP YAICOM 22B), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TOEPYAICOM22&cmd=documents&documentName=TOEPYAICOM22.pdf.
What are the minimum BACnet points to integrate the Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)?
Start with BV 1 RUN FWD (Start/stop from the BMS (drive)); AV 2 Frequency Command (Frequency reference, units per o1-03); BV 4 FAULT RESET (Reset a tripped drive); BV 13 RUN-STOP (Running status); BV 15 READY (Drive ready to run); AV 10 Output Frequency (Output frequency, units per o1-03); AV 12 Output Current (Motor amps); AV 13 Output Power (Drive power in kW); BV 16 FAULT (Any active drive fault); AV 40 Last Drive Fault (Most recent fault code).
How do I enable BMS control of the Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)?
b1-01 Frequency Reference Selection 1 = 3 (Option PCB) and b1-02 Run Command Selection 1 = 3 (Option PCB). The defaults differ by drive model. BV5 COM NET and BV6 COM CNTRL (COM/LOCAL) are also provided.
Does the Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives) need a BACnet heartbeat or have a communication timeout?
When the drive loses the option link it raises bUS (Option Communication Error) and acts per F6-01: 0 ramp to stop, 1 coast, 2 fast stop, 3 alarm only, 4 alarm and run at d1-04, 5 alarm and ramp stop (4 and 5 only on some drives). F6-04 sets the bUS detection delay and F7-16 a communication-loss timeout in tenths of a second (both need option software VST800265+). F6-14 = 1 resets the bUS fault automatically when communication returns.
Can the BMS supply sensor values to the Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)?
AV3 PID Setpoint lets the BMS write the PID setpoint; BO4 Ref Sel: PID Setpoint (or AV5 bit 1) selects it.
How do I check these points on the real SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Yaskawa BACnet points lists
- Variable frequency drive (HVAC)
Yaskawa HV600 HVAC drive (embedded BACnet MS/TP)
Yaskawa HV600 HVAC fan and pump drives (HV60U, 208 V and 480 V class) using the built-in RS-485 port with H5-08 set to BACnet.
Also known as: HV600, HV60U, HV600 AC drive, HV600 BACnet MS/TP, SIEPC71061732 - Variable frequency drive with bypass (HVAC)
Yaskawa HV600 Narrow & Enclosed Bypass (BACnet MS/TP)
Yaskawa HV600 Narrow and Enclosed Bypass packages (H6B models) connected to BACnet MS/TP at the bypass controller.
Also known as: HV600 Bypass, HV600 Narrow Bypass, HV600 Enclosed Bypass, H6B1, H6BP, HV600 bypass controller, SIEPYAIH6B01 - Variable frequency drive BACnet IP option card
Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
Yaskawa HV600, FP605, Z1000U, GA500, GA700 and GA800 drives and HV600/FP605 bypasses fitted with the JOHB-SMP3 card.
Also known as: JOHB-SMP3, SMP3, HV600 BACnet/IP, Z1000U BACnet/IP, FP605 BACnet/IP, GA800 BACnet/IP, SIEP C730600 0MB - Variable frequency drive BACnet MS/TP option card
Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive)
Yaskawa V1000 compact drives (CIMR-VA, software VST910120 and later) fitted with the SI-B3/V BACnet MS/TP option.
Also known as: SI-B3/V, SI-B3 V1000, V1000 BACnet, V1000 BACnet MS/TP, CIMR-VA BACnet, TOEP YAICOM 19 - Variable frequency drive with bypass (HVAC)
Yaskawa Z1000 Bypass (BACnet MS/TP)
Yaskawa Z1000 Bypass packages (Z1B1, 208 V and 480 V) connected to BACnet MS/TP at the bypass controller.
Also known as: Z1000 Bypass, Z1B1, Z1000 drive bypass, Z1000 bypass controller, SIEP YAIZ1B 01 - Variable frequency drive (HVAC)
Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP)
Yaskawa Z1000 HVAC fan and pump drives (CIMR-ZU, 200 V and 400 V class) using the built-in RS-485 port with H5-08 set to BACnet.
Also known as: Z1000, CIMR-ZU, CIMR-ZUA, Z1000 AC Drive for HVAC Fan and Pump, SIEP C710616 45 - Variable frequency drive with bypass (HVAC)
Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP)
Yaskawa Z1000U HVAC Matrix low-harmonic drive bypass packages (Z1D1, 208 V and 480 V) connected to BACnet MS/TP at the bypass controller.
Also known as: Z1000U Bypass, Z1000U Matrix Bypass, Z1D1, Z1000U HVAC MATRIX Drive Bypass, Z1000U low harmonic bypass, SIEP YAIZ1D 01
Source: YASKAWA AC Drive Option BACnet MS/TP Installation & Technical Manual, Model SI-B3 · TOEP YAICOM 22B. Object names, instances and units are reproduced as published; descriptions are our own.