- JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
Variable frequency drive BACnet IP option card · BACnet points list
Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet points list
Updated 28 October 2026
The JOHB-SMP3 is a plug-in card that puts Yaskawa HVAC and general-purpose drives on BACnet IP. Each object maps to a drive Modbus register, so the same list covers several drive families; bypass-only and gateway-mode objects simply do not appear on a plain drive. AV29/AV30 give generic read/write access to any drive register.
This page lists 213 BACnet objects for the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) — 67 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Yaskawa’s own free documentation, linked below.
- Manufacturer
- Yaskawa
- Model
- JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
- Equipment
- Variable frequency drive BACnet IP option card
- Equipment type
- VFDs & pumps
- BACnet objects
- 213 (67 writable)
- Transport
- BACnet IP
- Firmware
- Option firmware 3.x (application VST9070xx); GA500/GA700/GA800/FP605 bypass need option software PRG 7001 or later
- Also known as
- JOHB-SMP3, SMP3, HV600 BACnet/IP, Z1000U BACnet/IP, FP605 BACnet/IP, GA800 BACnet/IP, SIEP C730600 0MB
Reference only, provided as-is: verify against Yaskawa’s current documentation and the live device before use. Not official Yaskawa information. Terms of use.
BMS integration notes: Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
Set b1-01 = 3 (Option PCB) so the BMS sets frequency and b1-02 = 3 or 9 so it starts and stops the drive. Write BV1 Run FWD Cmd (BV58 on a bypass) and AV2 Frequency Cmd, read BV13/BV16 and AV10/AV12/AV13, and reset with BV4. Set the device instance in F6-48/F6-49 and the IP settings in F7-xx, and decide on the F7-57 bus timeout.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | Run FWD Cmd | Start/stop from the BMS (drive) | Command |
| AV 2 | Frequency Cmd | Frequency reference, units per o1-03 | Command |
| BV 4 | Drive Fault Reset | Reset a tripped drive | Command |
| BV 13 | RUN-STOP | Running status | Read |
| BV 15 | READY | Drive ready to run | Read |
| AV 10 | Output Frequency | Output frequency, units per o1-03 | Read |
| AV 12 | Output Current | Motor amps | Read |
| AV 13 | Output Power | Drive power in kW | Read |
| BV 16 | FAULT | Any active drive fault | Read |
| AV 40 | Last Drive Fault | Most recent fault code | Read |
Enable & remote start
b1-01 Frequency Reference Selection 1 = 3 (Option PCB) and b1-02 Run Command Selection 1 = 3 (Option PCB) or 9 (AUTO Command + Option Run); both default to 1. On a bypass use BV58/BV59 instead of BV1/BV2. BV5 Drive Com Net Command and BV6 Drive Com Control Command (COM/LOCAL) are also provided. In HAND or LOCAL mode the drive ignores the network and disables the bus timeout.
Heartbeat & communication loss
F7-57 BACnet/IP bUS Timeout Value: when above 0 the BMS must keep sending AV2 Frequency Cmd or a run command (AV1, BV1, BV2, BV58, BV59, AV43-AV51). If none arrives within that time while the drive is running, it trips on bUS Option Communication Error, handled per F6-01 (0 ramp, 1 coast (default), 2 fast stop, 3 alarm only, 4 alarm and run at d1-04, 5 alarm and ramp stop). F7-57 = 0 disables it. Switching to AUTO/REMOTE with no recent command gives an immediate bUS. With F6-14 = 1 and F6-01 set to 0-2, the option resets the fault and returns control to BACnet when comms recover.
Sensors & values from the BMS
AV3 PI Setpoint Cmd lets the BMS write the PI setpoint; BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it as the setpoint input.
Network setup
- Device instance = F6-49 (high word) and F6-48 (low word), in hex; e.g. instance 1234 is F6-48 = 4D2, F6-49 = 0.
- F7-13 picks static or DHCP addressing (default DHCP); static IP, mask and gateway are F7-01 to F7-12 (defaults 192.168.1.20 / 255.255.255.0 / 192.168.1.1).
- F7-50 sets the BACnet UDP port (default 47808); F7-51 to F7-56 set BBMD foreign registration.
- F6-xx/F7-xx changes need a power cycle, or F6-15 = 1 Reload Now on non-Z1000U drives.
- DIP switch S1 must read 75 in monitor U4-75 (switches 1 and 3 on) for BACnet/IP to work.
- U6-80 to U6-83 show the IP address actually in use.
Watch out for
- Bits written to AV1 and BV7-BV11 are ORed with the hard-wired digital inputs.
- Do not combine AV4 with BO1-BO3/BV12, or AV5 with AV1, BO4 or BV9-BV11.
- F6-01 = 3 or 4 keeps the drive running after a bus fault; provide separate safety stops.
- With RSTP ring networks, set F7-57 long enough for the ring to converge.
- Frequency units for AV2, AV9 and AV10 follow drive parameter o1-03.
- Bypass-only and gateway-mode objects are missing on a plain drive.
Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Drive Analog Input 1 Level | Shown as 'Drv Anlg In 1 Level'; Modbus 004E | % | Read | |
| AI | 2 | Drive Analog Input 2 Level | Shown as 'Drv Anlg In 2 Level'; Modbus 004F | % | Read | |
| AI | 3 | Drive Analog Input 3 Level | Shown as 'Drv Anlg In 3 Level'; not on all drives | % | Read | |
| AI | 4 | Bypass Analog Input 1 Level | Shown as 'Byp Anlg In 1 Level'; Modbus 8795; bypass only | % | Read | |
| AI | 6 | Display Format o1-03 | Modbus 0502 | Read | ||
| AI | 7 | Scale Format b5-20 | Modbus 01E2 | Read | ||
| AI | 8 | Inverter Model o2-04 | Modbus 0508 | Read | ||
| AI | 9 | Rated Current n9-01 | Modbus 05D0 | A | Read | |
| AI | 10 | Motor Current UB-01 | Modbus 8780; bypass only | A | Read | |
| AI | 11 | Contactor Voltage | Modbus 8790; bypass only | V | Read | |
| AO | 1 | Drive Analog Output 1 Level | Drive terminal FM; set H4-01 = 0 | % | Command | |
| AO | 2 | Drive Analog Output 2 Level | Drive terminal AM; set H4-01 = 0; not on all drives | % | Command | |
| AV | 1 | Drive Operation Command | Run/command bitmap, Modbus 0001; bits OR with hard-wired inputs | Command | ||
| AVmin | 2 | Frequency Cmd | Modbus 0002 | per o1-03 | Command | |
| AV | 3 | PI Setpoint Cmd | Modbus 0006 | % | Command | |
| AV | 4 | Drive Multi-Function Output Command | Bitmap for MF digital outputs and fault contact | Command | ||
| AV | 5 | Drive Reference Select Command | Bitmap selecting PID setpoint, PI2 target, MF inputs | Command | ||
| AV | 6 | System Status | Bitmap: run, reverse, ready, fault, outputs, com status | Read | ||
| AV | 7 | Fault Details | Bitmap of active fault groups | Read | ||
| AV | 8 | Data Link Status | Bitmap of register write and limit errors | Read | ||
| AV | 9 | Frequency Reference | Modbus 0040 | per o1-03 | Read | |
| AVmin | 10 | Output Frequency | Modbus 0041 | per o1-03 | Read | |
| AV | 11 | Output Voltage | Modbus 0045 | V | Read | |
| AVmin | 12 | Output Current | Modbus 0026 | A | Read | |
| AVmin | 13 | Output Power | Modbus 0047 | kW | Read | |
| AV | 14 | Torque Reference | Modbus 0048; not on all drives | % | Read | |
| AV | 15 | Drive Multi-Function Input Status | Shown as 'MF Input Status'; Modbus 002B | Read | ||
| AV | 16 | Drive Status 2 | Modbus 002C | Read | ||
| AV | 17 | Drive Multi-Function Output Status | Shown as 'MF Output Status'; Modbus 002D | Read | ||
| AV | 18 | DC Bus Voltage | Modbus 0031 | V | Read | |
| AV | 19 | PI Feedback Level | Modbus 0038 | % | Read | |
| AV | 20 | PI Input Level | Modbus 0039 | % | Read | |
| AV | 21 | PI Output Level | Modbus 003A | % | Read | |
| AV | 22 | CPU Software | Drive software number; bypass shows Drive SW Num | Read | ||
| AV | 23 | Flash Number | Flash number; bypass shows Bypass SW Num | Read | ||
| AV | 25 | KVA Setting | Modbus 0508 | Read | ||
| AV | 26 | Control Method | Modbus 0043 | Read | ||
| AV | 27 | Accel Time | Modbus 0200 | Sec | Write | |
| AV | 28 | Decel Time | Modbus 0201 | Sec | Write | |
| AV | 29 | Parameter Number | Register number to read or write via AV30 | Write | ||
| AV | 30 | Parameter Data | Data read from or written to register in AV29 | Write | ||
| AV | 31 | Motor Current | Modbus 8780; bypass only | A | Read | |
| AV | 32 | 120V to Kx Coils | Modbus 8790; bypass only | V | Read | |
| AV | 33 | Drive kWh consumed | Energy consumed | kWh | Read | |
| AV | 34 | Drive kWh Regenerated | Energy regenerated; Z1000U only | kWh | Read | |
| AV | 35 | Drive Run Time | Modbus 004C | Hours | Read | |
| AV | 36 | Output Freq in % | Modbus 003F | % | Read | |
| AV | 37 | Output Freq in RPM | Modbus 003E | RPM | Read | |
| AV | 38 | Torque Iq (U6-01) | Modbus 0051 | % | Read | |
| AV | 39 | Drive HOA Status | Hand/Off/Auto state; GA drives report Lo/Re | Read | ||
| AVmin | 40 | Last Drive Fault | Modbus 0081 | Read | ||
| AV | 41 | Last BypassFault | Modbus 878C; bypass only | Read | ||
| AV | 42 | Current Sys Fault | Shown as 'Current Sys Flt'; Modbus 0080 | Read | ||
| AV | 43 | Ext Drive Cmd Update | Modbus 15C5; gateway mode only | Command | ||
| AV | 44 | Ext Drive 1 Command | Modbus 15C6; gateway mode only | Command | ||
| AV | 45 | Ext Drive 1 Freq Ref | Modbus 15C7; gateway mode only | Command | ||
| AV | 46 | Ext Drive 2 Command | Modbus 15C8; gateway mode only | Command | ||
| AV | 47 | Ext Drive 2 Freq Ref | Modbus 15C9; gateway mode only | Command | ||
| AV | 48 | Ext Drive 3 Command | Modbus 15CA; gateway mode only | Command | ||
| AV | 49 | Ext Drive 3 Freq Ref | Modbus 15CB; gateway mode only | Command | ||
| AV | 50 | Ext Drive 4 Command | Modbus 15CC; gateway mode only | Command | ||
| AV | 51 | Ext Drive 4 Freq Ref | Modbus 15CD; gateway mode only | Command | ||
| AV | 52 | Ext Drive 1 Status | Modbus 15E7; gateway mode only | Read | ||
| AV | 53 | Ext Drive 1 Freq Output | Shown as 'Ext Drive 1 Freq Out'; Modbus 15E8; gateway mode only | Read | ||
| AV | 54 | Ext Drive 2 Status | Modbus 15E9; gateway mode only | Read | ||
| AV | 55 | Ext Drive 2 Freq Output | Shown as 'Ext Drive 2 Freq Out'; Modbus 15EA; gateway mode only | Read | ||
| AV | 56 | Ext Drive 3 Status | Modbus 15EB; gateway mode only | Read | ||
| AV | 57 | Ext Drive 3 Freq Output | Shown as 'Ext Drive 3 Freq Out'; Modbus 15EC; gateway mode only | Read | ||
| AV | 58 | Ext Drive 4 Status | Modbus 15ED; gateway mode only | Read | ||
| AV | 59 | Ext Drive 4 Freq Output | Shown as 'Ext Drive 4 Freq Out'; Modbus 15EE; gateway mode only | Read | ||
| AV | 60 | Ext Drive Register Write Access | Shown as 'Gateway Reg 0x15CE'; Modbus 15CE; gateway mode only | Write | ||
| AV | 61 | Ext Drive Write Register Number | Shown as 'Gateway Reg 0x15CF'; Modbus 15CF; gateway mode only | Write | ||
| AV | 62 | Ext Drive Write Register Data | Shown as 'Gateway Reg 0x15D0'; Modbus 15D0; gateway mode only | Write | ||
| AV | 63 | Ext Drive Register Read Access | Shown as 'Gateway Reg 0x15EF'; Modbus 15EF; gateway mode only | Read | ||
| AV | 64 | Ext Drive Read Register Number | Shown as 'Gateway Reg 0x15F0'; Modbus 15F0; gateway mode only | Read | ||
| AV | 65 | Ext Drive Read Register Data | Shown as 'Gateway Reg 0x15F1'; Modbus 15F1; gateway mode only | Read | ||
| BI | 1 | Drive Input Terminal 1 | Shown as 'Input Terminal 1'; Modbus 002B: Bit 0 | Read | Active: ON, Inactive: OFF | |
| BI | 2 | Drive Input Terminal 2 | Shown as 'Input Terminal 2'; Modbus 002B: Bit 1 | Read | Active: ON, Inactive: OFF | |
| BI | 3 | Drive Input Terminal 3 | Shown as 'Input Terminal 3'; Modbus 002B: Bit 2 | Read | Active: ON, Inactive: OFF | |
| BI | 4 | Drive Input Terminal 4 | Shown as 'Input Terminal 4'; Modbus 002B: Bit 3 | Read | Active: ON, Inactive: OFF | |
| BI | 5 | Drive Input Terminal 5 | Shown as 'Input Terminal 5'; Modbus 002B: Bit 4 | Read | Active: ON, Inactive: OFF | |
| BI | 6 | Drive Input Terminal 6 | Shown as 'Input Terminal 6'; Modbus 002B: Bit 5 | Read | Active: ON, Inactive: OFF | |
| BI | 7 | Drive Input Terminal 7 | Shown as 'Input Terminal 7'; Modbus 002B: Bit 6 | Read | Active: ON, Inactive: OFF | |
| BI | 8 | Drive MF Output 1 | Shown as 'Multi Function Out 1'; Modbus 0020: Bit 5 | Read | Active: ON, Inactive: OFF | |
| BI | 9 | Drive MF Output 2 | Shown as 'Multi Function Out 2'; Modbus 0020: Bit 6 | Read | Active: ON, Inactive: OFF | |
| BI | 10 | Drive MF Output 3 | On bypass this is BYP DI-1 STAT | Read | Active: ON, Inactive: OFF | |
| BI | 11 | Drive Input Terminal 8 | On bypass this is BYP DI-2 STAT | Read | Active: ON, Inactive: OFF | |
| BI | 12 | BYP DI-3 STAT | Modbus 8781: Bit 2; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 13 | BYP DI-4 STAT | Modbus 8781: Bit 3; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 14 | BYP DI-5 STAT | Modbus 8781: Bit 4; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 15 | BYP DI-6 STAT | Modbus 8781: Bit 5; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 16 | BYP DI-7 STAT | Modbus 8781: Bit 6; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 17 | BYP DI-8 STAT | Modbus 8781: Bit 7; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 18 | BYP DO-1 STAT | Modbus 8782: Bit 0; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 19 | BYP DO-2 STAT | Modbus 8782: Bit 1; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 20 | BYP DO-3 STAT | Modbus 8782: Bit 2; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 21 | BYP DO-4 STAT | Modbus 8782: Bit 3; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 22 | BYP DO-5 STAT | Modbus 8782: Bit 4; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 23 | BYP DO-6 STAT | Modbus 8782: Bit 5; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 24 | BYP DO-7 STAT | Modbus 8782: Bit 6; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 25 | BYP DO-8 STAT | Modbus 8782: Bit 7; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 26 | BYP DO-9 STAT | Modbus 8783: Bit 0; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 27 | BYP DO-10 STAT | Modbus 8783: Bit 1; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 28 | Drive Fault Status | Modbus 004B: Bit 7 | Read | Active: FAULT, Inactive: OK | |
| BI | 29 | Drive Alarm Status | Modbus 004B: Bit 6 | Read | Active: ALARM, Inactive: OK | |
| BI | 30 | Sys Alarm Status | Modbus 8784: Bit 8; bypass only | Read | Active: ALARM, Inactive: OK | |
| BI | 31 | Safe Torque Off HW Status | Shown as 'Saf Trq Off Hw Stat'; not on Z1000U | Read | Active: ALARM, Inactive: OK | |
| BI | 32 | Safe Torque Off Status | Shown as 'Saf Trq Off Stat'; not on Z1000U | Read | Active: ALARM, Inactive: OK | |
| BO | 1 | MF Output, M1-M2 | Set H2-01 = F; GA500 uses MA-MB-MC | Command | Active: ON, Inactive: OFF | |
| BO | 2 | MF Output, M3-M4 | Set H2-02 = F; GA500 uses P1-C1 | Command | Active: ON, Inactive: OFF | |
| BO | 3 | MF Output, M5-M6 | Set H2-03 = F; Z1000U MD-ME-MF, GA500 P2-C2 | Command | Active: ON, Inactive: OFF | |
| BO | 4 | Ref Sel: PI Setpoint | Modbus 000F: Bit 1 | Command | Active: ON, Inactive: OFF | |
| BO | 5 | Ref Sel:Term S5 IN | Modbus 0001: Bit 8 | Command | Active: ON, Inactive: OFF | |
| BO | 6 | Ref Sel:Term S6 IN | Modbus 0001: Bit 9 | Command | Active: ON, Inactive: OFF | |
| BO | 7 | Ref Sel:Term S7 IN | Modbus 0001: Bit A | Command | Active: ON, Inactive: OFF | |
| BO | 8 | BYP DO-07 COMMAND | Modbus 8403: Bit 6; set matching Z2 parameter to 99; bypass only | Command | Active: ON, Inactive: OFF | |
| BO | 9 | BYP DO-08 COMMAND | Modbus 8403: Bit 7; set matching Z2 parameter to 99; bypass only | Command | Active: ON, Inactive: OFF | |
| BO | 10 | BYP DO-09 COMMAND | Modbus 8403: Bit 8; set matching Z2 parameter to 99; bypass only | Command | Active: ON, Inactive: OFF | |
| BO | 11 | BYP DO-010 COMMAND | Modbus 8403: Bit 9; set matching Z2 parameter to 99; bypass only | Command | Active: ON, Inactive: OFF | |
| BVmin | 1 | Run FWD Cmd | Modbus 0001: Bit 0; drive only; bypass uses BV58 | Command | Active: RUN, Inactive: OFF | |
| BV | 2 | Run REV Cmd | Modbus 0001: Bit 1; drive only; bypass uses BV59 | Command | Active: REV, Inactive: OFF | |
| BV | 3 | Drive EF0 | Shown as 'Ext Fault Cmd'; Modbus 0001: Bit 2 | Command | Active: FAULT, Inactive: OFF | |
| BVmin | 4 | Drive Fault Reset | Shown as 'Fault Reset Cmd'; Modbus 0001: Bit 3 | Command | Active: RESET, Inactive: OFF | |
| BV | 5 | Drive Com Net Command | Shown as 'Com Net Cmd' | Command | Active: COM, Inactive: LOCAL | |
| BV | 6 | Drive Com Control Command | Shown as 'Com Control Cmd' | Command | Active: COM, Inactive: LOCAL | |
| BV | 7 | Drive Multi-Function Input 3 Command | Shown as 'MF Input 3 Cmd'; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 8 | Drive Multi-Function Input 4 Command | Modbus 0001: Bit 7; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 9 | Drive Multi-Function Input 5 Command | Shown as 'MF Input 5 Cmd'; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 10 | Drive Multi-Function Input 6 Command | Shown as 'MF Input 6 Cmd'; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 11 | Drive Multi-Function Input 7 Command | Shown as 'MF Input 7 Cmd'; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 12 | Set Fault Contact Cmd | Shown as 'Set Flt Contact Cmd'; not on GA500 | Command | Active: ENABLE, Inactive: OFF | |
| BVmin | 13 | RUN-STOP | Modbus 0020: Bit 0 | Read | Active: RUN, Inactive: OFF | |
| BV | 14 | REV-FWD | Modbus 0020: Bit 1 | Read | Active: REV, Inactive: FWD | |
| BVmin | 15 | READY | Modbus 004B: Bit 5 | Read | Active: READY, Inactive: OFF | |
| BVmin | 16 | FAULT | Modbus 0020: Bit 3 | Read | Active: FAULTED, Inactive: OFF | |
| BV | 17 | Data Set Error | Modbus 004B: Bit 8 | Read | Active: ERROR, Inactive: OFF | |
| BV | 18 | Overcurrent – Ground Fault | Shown as 'Overcurrent– Gnd Flt'; Modbus 0021: Bit 0 | Read | Active: OC – GF, Inactive: OFF | |
| BV | 19 | Main Circuit Overvoltage | Shown as 'Main Ckt Overvoltage'; Modbus 0021: Bit 1 | Read | Active: OV, Inactive: OFF | |
| BV | 20 | Drive Overload | Modbus 0021: Bit 2 | Read | Active: OL2, Inactive: OFF | |
| BV | 21 | Drive Overheat | Modbus 0021: Bit 3 | Read | Active: OH1-OH2, Inactive: OFF | |
| BV | 22 | Fuse Blown | Modbus 0021: Bit 5 | Read | Active: PUF, Inactive: OFF | |
| BV | 23 | PI Feedback Loss | Modbus 0021: Bit 6 | Read | Active: FBL, Inactive: OFF | |
| BV | 24 | External Fault | Modbus 0021: Bit 7 | Read | Active: EF0 – EF, Inactive: OFF | |
| BV | 25 | Hardware Error | Modbus 0021: Bit 8 | Read | Active: CPF, Inactive: OFF | |
| BV | 26 | Motor Overload – Overtorque | Shown as 'Mtr OvrLd – OvrTorque'; Modbus 0021: Bit 9 | Read | Active: OL1 – OL3, Inactive: OFF | |
| BV | 27 | Overspeed | Modbus 0021: Bit A | Read | Active: OS –DEV, Inactive: OFF | |
| BV | 28 | Main Circuit Undervoltage | Shown as 'Main Ckt Undrvoltage'; Modbus 0021: Bit B | Read | Active: UV, Inactive: OFF | |
| BV | 29 | MCU, Control Power Supply Error | Shown as 'MCU Cntrl Pwr Sy Err'; Modbus 0021: Bit C | Read | Active: UV1-2-3, Inactive: OFF | |
| BV | 30 | Output Phase Loss | Modbus 0021: Bit D | Read | Active: LF, Inactive: OFF | |
| BV | 31 | BUS Fault | Modbus 0021: Bit E | Read | Active: BUS, Inactive: OFF | |
| BV | 32 | Operator Disconnect | Modbus 0021: Bit F | Read | Active: OPR, Inactive: OFF | |
| BV | 33 | Operating | Modbus 002C: Bit 0 | Read | Active: OPERATING, Inactive: OFF | |
| BV | 34 | Zero Speed | Modbus 002C: Bit 1 | Read | Active: ON, Inactive: OFF | |
| BV | 35 | Frequency Agree | Modbus 002C: Bit 2 | Read | Active: ON, Inactive: OFF | |
| BV | 36 | Desired Frequency Agree | Shown as 'Desired Freq Agree'; Modbus 002C: Bit 3 | Read | Active: ON, Inactive: OFF | |
| BV | 37 | Frequency Detect 1 | Modbus 002C: Bit 4 | Read | Active: ON, Inactive: OFF | |
| BV | 38 | Frequency Detect 2 | Modbus 002C: Bit 5 | Read | Active: ON, Inactive: OFF | |
| BV | 39 | Drive Startup Complete | Shown as 'Drv Startup Complete'; Modbus 002C: Bit 6 | Read | Active: ON, Inactive: OFF | |
| BV | 40 | Low Voltage Detect | Modbus 002C: Bit 7 | Read | Active: ON, Inactive: OFF | |
| BV | 41 | Base Block | Modbus 002C: Bit 8 | Read | Active: ON, Inactive: OFF | |
| BV | 42 | Frequency Reference Mode | Shown as 'Frequency Ref Mode'; Modbus 002C: Bit 9 | Read | Active: LOCAL, Inactive: COM | |
| BV | 43 | Run Command Mode | Modbus 002C: Bit A | Read | Active: LOCAL, Inactive: COM | |
| BV | 44 | Over Torque Detect | Modbus 002C: Bit B | Read | Active: ON, Inactive: OFF | |
| BV | 45 | Frequency Reference Loss | Shown as 'Frequency Ref Loss'; Modbus 002C: Bit C | Read | Active: ON, Inactive: OFF | |
| BV | 46 | Retry Error | Modbus 002C: Bit D | Read | Active: ON, Inactive: OFF | |
| BV | 55 | Parameter Accept | Runs the RAM enter command | Write | Active: ON, Inactive: OFF | |
| BV | 56 | Parameter Enter | Runs the ROM (EEPROM) enter command | Write | Active: ON, Inactive: OFF | |
| BV | 58 | Bypass Forward Run Cmd | Shown as 'BYP Run Fwd CMD'; Modbus 0001: Bit 0; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 59 | Bypass Reverse Run Cmd | Shown as 'BYP Run Rev CMD'; Modbus 0001: Bit 1; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 60 | Emergency Override Drive Reverse | HV600/FP605 only; needs b1-04 = 0 | Command | Active: ON, Inactive: OFF | |
| BV | 61 | Bypass Transfer to Bypass Cmd | Shown as 'BYP Xfer to BYP CMD'; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 62 | Emergency Overide Bypass | Shown as 'Em Over BYPASS CMD'; Modbus 8400: Bit 4; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 63 | Emergency Override Drive Forward | Shown as 'Em Over DRV FWD CMD'; HV600/FP605 only | Command | Active: ON, Inactive: OFF | |
| BV | 64 | Bypass Motor OR Select Command | Shown as 'BYP Mtr OR Sel CMD'; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 65 | Bypass Motor AND Select Command | Shown as 'BYP Mtr AND Sel CMD'; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 69 | Bypass BYPASS Select Command | Shown as 'BYP BYPASS Sel CMD'; bypass only; needs Z1-39 = 3 | Command | Active: BYP, Inactive: DRV | |
| BV | 70 | Bypass Fault Reset Command | Shown as 'BYP Fault Reset CMD'; Modbus 8400: Bit D; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 71 | Bypass External Fault Command | Shown as 'BYP Ext Fault CMD'; Modbus 8400: Bit E; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 72 | Bypass DI-01 Command | Shown as 'BYP DI-01 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 73 | Bypass DI-02 Command | Shown as 'BYP DI-02 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 74 | Bypass DI-03 Command | Shown as 'BYP DI-03 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 75 | Bypass DI-04 Command | Shown as 'BYP DI-04 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 76 | Bypass DI-05 Command | Shown as 'BYP DI-05 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 77 | Bypass DI-06 Command | Shown as 'BYP DI-06 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 78 | Bypass DI-07 Command | Shown as 'BYP DI-07 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 79 | Bypass DI-08 Command | Shown as 'BYP DI-08 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 80 | Bypass HAND Mode Status | Shown as 'BYP HAND Mode Status'; Modbus 8784: Bit 0; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 81 | Bypass OFF Mode Status | Shown as 'BYP OFF Mode Status'; Modbus 8784: Bit 1; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 82 | Bypass AUTO Mode Status | Shown as 'BYPAUTO Mode Status'; Modbus 8784: Bit 2; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 83 | Bypass DRIVE Mode Status | Shown as 'BYP DRV Mode Status'; Modbus 8784: Bit 3; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 84 | Bypass BYPASS Mode Status | Shown as 'BYP BYPASS Mode Stat'; Modbus 8784: Bit 4; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 85 | Bypass Emergency Run Bypass Status | Shown as 'BYP Em-Over BYP Stat'; Modbus 8784: Bit 5; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 86 | Bypass Emergency Run Drive Fwd Status | Shown as 'BYP Em-Over DRV Stat'; Modbus 8784: Bit 6; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 87 | Bypass Safety Status | Shown as 'BYP Safety Status'; Modbus 8784: Bit 7; bypass only | Read | Active: OPEN, Inactive: CLOSED | |
| BV | 88 | Bypass BAS Interlock Status | Shown as 'BYP BAS Interlk Stat'; Modbus 8785: Bit 0; bypass only | Read | Active: OPEN, Inactive: CLOSED | |
| BV | 89 | Bypass Run Status | Shown as 'BYP RUN Status'; Modbus 8785: Bit 1; bypass only | Read | Active: RUN, Inactive: OFF | |
| BV | 90 | Bypass Fault Status | Shown as 'BYP Fault Status'; Modbus 8785: Bit 2; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 91 | Bypass Auto Transfer Status | Shown as 'BYPAuto Xfer Status'; Modbus 8785: Bit 3; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 92 | Bypass Remote Transfer Status | Shown as 'BYP Remote Xfer Stat'; Modbus 8785: Bit 4; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 93 | Bypass Energy Savings Status | Shown as 'BYP Energy Save Stat'; Modbus 8785: Bit 5; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 94 | Bypass Motor 1 Select Status | Shown as 'BYP Motor 1 Sel Stat'; bypass only | Read | Active: SELECT, Inactive: OFF | |
| BV | 95 | Bypass Motor 2 Select Status | Shown as 'BYP Motor 2 Sel Stat'; bypass only | Read | Active: SELECT, Inactive: OFF | |
| BV | 96 | Bypass Drive Fault Status | Shown as 'BYP Drive Flt Status'; Modbus 8786: Bit 0; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 97 | BYP Safety Status 2 | Shown as 'BYP Safety Status 2'; Modbus 8786: Bit 1; bypass only | Read | Active: OPEN, Inactive: CLOSED | |
| BV | 98 | Bypass BAS Interlock Fault Status | Shown as 'BYP BAS ILock Status'; Modbus 8786: Bit 2; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 99 | Bypass External Fault Status | Shown as 'BYP Ext Fault Stat'; Modbus 8786: Bit 3; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 101 | Bypass Motor OL Status | Shown as 'BYP Motor OL Stat'; Modbus 8786: Bit 5; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 102 | Bypass Motor 1 External OL Status | Shown as 'BYP Motor 1 OL Stat'; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 103 | Bypass Motor 2 External OL Status | Shown as 'BYP Mtr 2 OL Stat'; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 104 | Bypass Brownout Detect Status | Shown as 'BYP Brownout Detect'; Modbus 8787: Bit 0; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 105 | Bypass Drive Comms Status | Shown as 'BYP Drive Comms'; Modbus 8787: Bit 2; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 106 | Bypass Loss of Load Status | Shown as 'BYP Loss Of Load'; Modbus 8787: Bit 5; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 107 | Option Board on Drive Status | Shown as 'BYP Option Brd Comms'; Modbus 8787: Bit 4; bypass only | Read | Active: FAULT, Inactive: OFF |
No points match these filters.
Object ID lookup: Yaskawa JOHB-SMP3 BACnet/IP option point IDs by name
AI1Drive Analog Input 1 LevelAI2Drive Analog Input 2 LevelAI3Drive Analog Input 3 LevelAI4Bypass Analog Input 1 LevelAI6Display Format o1-03AI7Scale Format b5-20AI8Inverter Model o2-04AI9Rated Current n9-01AI10Motor Current UB-01AI11Contactor VoltageAO1Drive Analog Output 1 LevelAO2Drive Analog Output 2 LevelAV1Drive Operation CommandAV2Frequency CmdAV3PI Setpoint CmdAV4Drive Multi-Function Output CommandAV5Drive Reference Select CommandAV6System StatusAV7Fault DetailsAV8Data Link StatusAV9Frequency ReferenceAV10Output FrequencyAV11Output VoltageAV12Output CurrentAV13Output PowerAV14Torque ReferenceAV15Drive Multi-Function Input StatusAV16Drive Status 2AV17Drive Multi-Function Output StatusAV18DC Bus VoltageAV19PI Feedback LevelAV20PI Input LevelAV21PI Output LevelAV22CPU SoftwareAV23Flash NumberAV25KVA SettingAV26Control MethodAV27Accel TimeAV28Decel TimeAV29Parameter NumberAV30Parameter DataAV31Motor CurrentAV32120V to Kx CoilsAV33Drive kWh consumedAV34Drive kWh RegeneratedAV35Drive Run TimeAV36Output Freq in %AV37Output Freq in RPMAV38Torque Iq (U6-01)AV39Drive HOA StatusAV40Last Drive FaultAV41Last BypassFaultAV42Current Sys FaultAV43Ext Drive Cmd UpdateAV44Ext Drive 1 CommandAV45Ext Drive 1 Freq RefAV46Ext Drive 2 CommandAV47Ext Drive 2 Freq RefAV48Ext Drive 3 CommandAV49Ext Drive 3 Freq RefAV50Ext Drive 4 CommandAV51Ext Drive 4 Freq RefAV52Ext Drive 1 StatusAV53Ext Drive 1 Freq OutputAV54Ext Drive 2 StatusAV55Ext Drive 2 Freq OutputAV56Ext Drive 3 StatusAV57Ext Drive 3 Freq OutputAV58Ext Drive 4 StatusAV59Ext Drive 4 Freq OutputAV60Ext Drive Register Write AccessAV61Ext Drive Write Register NumberAV62Ext Drive Write Register DataAV63Ext Drive Register Read AccessAV64Ext Drive Read Register NumberAV65Ext Drive Read Register DataBI1Drive Input Terminal 1BI2Drive Input Terminal 2BI3Drive Input Terminal 3BI4Drive Input Terminal 4BI5Drive Input Terminal 5BI6Drive Input Terminal 6BI7Drive Input Terminal 7BI8Drive MF Output 1BI9Drive MF Output 2BI10Drive MF Output 3BI11Drive Input Terminal 8BI12BYP DI-3 STATBI13BYP DI-4 STATBI14BYP DI-5 STATBI15BYP DI-6 STATBI16BYP DI-7 STATBI17BYP DI-8 STATBI18BYP DO-1 STATBI19BYP DO-2 STATBI20BYP DO-3 STATBI21BYP DO-4 STATBI22BYP DO-5 STATBI23BYP DO-6 STATBI24BYP DO-7 STATBI25BYP DO-8 STATBI26BYP DO-9 STATBI27BYP DO-10 STATBI28Drive Fault StatusBI29Drive Alarm StatusBI30Sys Alarm StatusBI31Safe Torque Off HW StatusBI32Safe Torque Off StatusBO1MF Output, M1-M2BO2MF Output, M3-M4BO3MF Output, M5-M6BO4Ref Sel: PI SetpointBO5Ref Sel:Term S5 INBO6Ref Sel:Term S6 INBO7Ref Sel:Term S7 INBO8BYP DO-07 COMMANDBO9BYP DO-08 COMMANDBO10BYP DO-09 COMMANDBO11BYP DO-010 COMMANDBV1Run FWD CmdBV2Run REV CmdBV3Drive EF0BV4Drive Fault ResetBV5Drive Com Net CommandBV6Drive Com Control CommandBV7Drive Multi-Function Input 3 CommandBV8Drive Multi-Function Input 4 CommandBV9Drive Multi-Function Input 5 CommandBV10Drive Multi-Function Input 6 CommandBV11Drive Multi-Function Input 7 CommandBV12Set Fault Contact CmdBV13RUN-STOPBV14REV-FWDBV15READYBV16FAULTBV17Data Set ErrorBV18Overcurrent – Ground FaultBV19Main Circuit OvervoltageBV20Drive OverloadBV21Drive OverheatBV22Fuse BlownBV23PI Feedback LossBV24External FaultBV25Hardware ErrorBV26Motor Overload – OvertorqueBV27OverspeedBV28Main Circuit UndervoltageBV29MCU, Control Power Supply ErrorBV30Output Phase LossBV31BUS FaultBV32Operator DisconnectBV33OperatingBV34Zero SpeedBV35Frequency AgreeBV36Desired Frequency AgreeBV37Frequency Detect 1BV38Frequency Detect 2BV39Drive Startup CompleteBV40Low Voltage DetectBV41Base BlockBV42Frequency Reference ModeBV43Run Command ModeBV44Over Torque DetectBV45Frequency Reference LossBV46Retry ErrorBV55Parameter AcceptBV56Parameter EnterBV58Bypass Forward Run CmdBV59Bypass Reverse Run CmdBV60Emergency Override Drive ReverseBV61Bypass Transfer to Bypass CmdBV62Emergency Overide BypassBV63Emergency Override Drive ForwardBV64Bypass Motor OR Select CommandBV65Bypass Motor AND Select CommandBV69Bypass BYPASS Select CommandBV70Bypass Fault Reset CommandBV71Bypass External Fault CommandBV72Bypass DI-01 CommandBV73Bypass DI-02 CommandBV74Bypass DI-03 CommandBV75Bypass DI-04 CommandBV76Bypass DI-05 CommandBV77Bypass DI-06 CommandBV78Bypass DI-07 CommandBV79Bypass DI-08 CommandBV80Bypass HAND Mode StatusBV81Bypass OFF Mode StatusBV82Bypass AUTO Mode StatusBV83Bypass DRIVE Mode StatusBV84Bypass BYPASS Mode StatusBV85Bypass Emergency Run Bypass StatusBV86Bypass Emergency Run Drive Fwd StatusBV87Bypass Safety StatusBV88Bypass BAS Interlock StatusBV89Bypass Run StatusBV90Bypass Fault StatusBV91Bypass Auto Transfer StatusBV92Bypass Remote Transfer StatusBV93Bypass Energy Savings StatusBV94Bypass Motor 1 Select StatusBV95Bypass Motor 2 Select StatusBV96Bypass Drive Fault StatusBV97BYP Safety Status 2BV98Bypass BAS Interlock Fault StatusBV99Bypass External Fault StatusBV101Bypass Motor OL StatusBV102Bypass Motor 1 External OL StatusBV103Bypass Motor 2 External OL StatusBV104Bypass Brownout Detect StatusBV105Bypass Drive Comms StatusBV106Bypass Loss of Load StatusBV107Option Board on Drive Status
Integration notes
- Device instance is built from drive parameters F6-49 and F6-48; the default object name is 'Yaskawa VFD ID' plus those values in hex.
- IP settings come from F7-01 to F7-13 (or DHCP); the UDP port is set by F7-50.
- Object names in the drive may use the shorter network display name shown in each description.
- Points marked 'bypass only' exist only when the card is in an HV600 or FP605 bypass.
- AV43-AV65 are gateway-mode objects for up to four downstream drives and only appear in gateway mode.
- AV4 must not be combined with BO1-BO3 or BV12; AV5 must not be combined with AV1, BO4 or BV9-BV11.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
How many BACnet points does the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) have?
This list has 213 BACnet objects: 10 analog inputs, 2 analog outputs, 64 analog values, 32 binary inputs, 11 binary outputs, 94 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet points are writable?
67 of the 213 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet documentation?
The source is YASKAWA AC Drive Option BACnet/IP Technical Manual, Model JOHB-SMP3 (SIEP C730600 0MB), revision 2023-11, published free by Yaskawa at https://www.yaskawa.eu.com/_downloads/download_d22897.
What are the minimum BACnet points to integrate the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?
Start with BV 1 Run FWD Cmd (Start/stop from the BMS (drive)); AV 2 Frequency Cmd (Frequency reference, units per o1-03); BV 4 Drive Fault Reset (Reset a tripped drive); BV 13 RUN-STOP (Running status); BV 15 READY (Drive ready to run); AV 10 Output Frequency (Output frequency, units per o1-03); AV 12 Output Current (Motor amps); AV 13 Output Power (Drive power in kW); BV 16 FAULT (Any active drive fault); AV 40 Last Drive Fault (Most recent fault code).
How do I enable BMS control of the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?
b1-01 Frequency Reference Selection 1 = 3 (Option PCB) and b1-02 Run Command Selection 1 = 3 (Option PCB) or 9 (AUTO Command + Option Run); both default to 1. On a bypass use BV58/BV59 instead of BV1/BV2. BV5 Drive Com Net Command and BV6 Drive Com Control Command (COM/LOCAL) are also provided. In HAND or LOCAL mode the drive ignores the network and disables the bus timeout.
Does the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) need a BACnet heartbeat or have a communication timeout?
F7-57 BACnet/IP bUS Timeout Value: when above 0 the BMS must keep sending AV2 Frequency Cmd or a run command (AV1, BV1, BV2, BV58, BV59, AV43-AV51). If none arrives within that time while the drive is running, it trips on bUS Option Communication Error, handled per F6-01 (0 ramp, 1 coast (default), 2 fast stop, 3 alarm only, 4 alarm and run at d1-04, 5 alarm and ramp stop). F7-57 = 0 disables it. Switching to AUTO/REMOTE with no recent command gives an immediate bUS. With F6-14 = 1 and F6-01 set to 0-2, the option resets the fault and returns control to BACnet when comms recover.
Can the BMS supply sensor values to the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?
AV3 PI Setpoint Cmd lets the BMS write the PI setpoint; BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it as the setpoint input.
How do I check these points on the real JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Yaskawa BACnet points lists
- Variable frequency drive (HVAC)
Yaskawa HV600 HVAC drive (embedded BACnet MS/TP)
Yaskawa HV600 HVAC fan and pump drives (HV60U, 208 V and 480 V class) using the built-in RS-485 port with H5-08 set to BACnet.
Also known as: HV600, HV60U, HV600 AC drive, HV600 BACnet MS/TP, SIEPC71061732 - Variable frequency drive with bypass (HVAC)
Yaskawa HV600 Narrow & Enclosed Bypass (BACnet MS/TP)
Yaskawa HV600 Narrow and Enclosed Bypass packages (H6B models) connected to BACnet MS/TP at the bypass controller.
Also known as: HV600 Bypass, HV600 Narrow Bypass, HV600 Enclosed Bypass, H6B1, H6BP, HV600 bypass controller, SIEPYAIH6B01 - Variable frequency drive BACnet MS/TP option card
Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)
Yaskawa A1000, P1000, iQpump1000, U1000, FP605 and iQpump605 drives fitted with the SI-B3 BACnet MS/TP option card.
Also known as: SI-B3, SI-B3/V, A1000 BACnet, P1000 BACnet, iQpump1000 BACnet, U1000 BACnet, FP605 BACnet, iQpump605 BACnet, TOEPYAICOM22 - Variable frequency drive BACnet MS/TP option card
Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive)
Yaskawa V1000 compact drives (CIMR-VA, software VST910120 and later) fitted with the SI-B3/V BACnet MS/TP option.
Also known as: SI-B3/V, SI-B3 V1000, V1000 BACnet, V1000 BACnet MS/TP, CIMR-VA BACnet, TOEP YAICOM 19 - Variable frequency drive with bypass (HVAC)
Yaskawa Z1000 Bypass (BACnet MS/TP)
Yaskawa Z1000 Bypass packages (Z1B1, 208 V and 480 V) connected to BACnet MS/TP at the bypass controller.
Also known as: Z1000 Bypass, Z1B1, Z1000 drive bypass, Z1000 bypass controller, SIEP YAIZ1B 01 - Variable frequency drive (HVAC)
Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP)
Yaskawa Z1000 HVAC fan and pump drives (CIMR-ZU, 200 V and 400 V class) using the built-in RS-485 port with H5-08 set to BACnet.
Also known as: Z1000, CIMR-ZU, CIMR-ZUA, Z1000 AC Drive for HVAC Fan and Pump, SIEP C710616 45 - Variable frequency drive with bypass (HVAC)
Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP)
Yaskawa Z1000U HVAC Matrix low-harmonic drive bypass packages (Z1D1, 208 V and 480 V) connected to BACnet MS/TP at the bypass controller.
Also known as: Z1000U Bypass, Z1000U Matrix Bypass, Z1D1, Z1000U HVAC MATRIX Drive Bypass, Z1000U low harmonic bypass, SIEP YAIZ1D 01
Source: YASKAWA AC Drive Option BACnet/IP Technical Manual, Model JOHB-SMP3 · SIEP C730600 0MB · rev. 2023-11. Object names, instances and units are reproduced as published; descriptions are our own.