Boiler controller gateway · BACnet points list
Laars OmniTherm - ProtoNode BACnet points list
Updated 28 October 2026
The ProtoNode reads the OmniTherm control over Modbus RTU and serves 121 objects per unit. Analog inputs cover temperatures, flame signal, 0-10 V inputs and outputs, firing rate, lockout and alarm codes, burner status, history counters and cascade lead/lag states; binary inputs break out the safety chain and output bits. Writable AVs and BVs hold the CH1, CH2, DHW and cascade enables, set points and PID terms plus three demand switches.
This page lists 121 BACnet objects for the Laars OmniTherm - ProtoNode — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Laars’s own free documentation, linked below.
- Manufacturer
- Laars
- Model
- OmniTherm - ProtoNode
- Equipment
- Boiler controller gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 121 (28 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 50000 + device Node-ID
- Also known as
- OmniTherm, Laars OmniTherm, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode
Instance calculator. This list prints one unit; the other units follow a formula. ProtoNode boiler gateways (Laars, Peerless, Raypak, AERCO and more) instance calculator →
Reference only, provided as-is: verify against Laars’s current documentation and the live device before use. Not official Laars information. Terms of use.
BMS integration notes: Laars OmniTherm - ProtoNode
Enable CH1 with AV 0, set BV 1 CH 1 Demand switch for a call for heat and write the CH1 set point (or the cascade CH set point for a cascade). Read the run contact, Burner Status 2, outlet temperature and firing rate, and watch the alarm contact and lockout code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | CH1 Enable/Disable | CH1 enable (1 = enable) | Write |
| BV 1 | CH 1 Demand switch | CH1 call for heat (1 = heat demand) | Write |
| AV 1 | CH1 Set Point | CH1 water set point | Write |
| AV 27 | Cascade CH Set Point | Set point when units run in cascade | Write |
| BI 11 | Digital Output Status - Run contact | Run output | Read |
| AI 85 | Burner Status 2 | Burner state; 51 = firing, 1 = locked out | Read |
| AI 1 | Outlet sensor | Outlet water temperature | Read |
| AI 33 | Modulating Burner1 Firing rate | Burner 1 firing rate | Read |
| BI 12 | Digital Output Status - Alarm Contact | Alarm output | Read |
| AI 35 | Lockout code | Lockout code (0-29) | Read |
Enable & remote start
AV 0 CH1 Enable/Disable (0 = disable, 1 = enable) and BV 1 CH 1 Demand switch (0 = no heat demand, 1 = heat demand). CH2 and DHW have matching objects.
Network setup
- Device instance = Node_Offset + unit Node-ID. Node_Offset defaults to 50000 and is changed in the ProtoNode web configurator; Node-IDs must be unique, 1-255.
- Unit to ProtoNode: Modbus RTU, 38400 baud, 8 data bits, no parity, 1 stop bit.
- Default ProtoNode IP address 192.168.1.24, mask 255.255.255.0. Choose BACnet IP or BACnet MS/TP with the Protocol Selector, then add one profile per device with its Node-ID.
- With more than one device on a ProtoNode, set BACnet Virtual Server Nodes to Yes. For BACnet MS/TP also set MAC address, baud rate and Max Master.
- Two or more ProtoNodes on the same subnet need different BACnet Network Numbers (default 50).
- A ProtoNode handles 1,500 registers in total; this profile uses 174 per device.
Watch out for
- AI 36 Alarm reason uses codes 30-44, continuing the lockout code list in AI 35.
- PID terms for each circuit are writable AVs; they are tuning values, not BMS commands.
Laars OmniTherm - ProtoNode BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Inlet sensor | Read | |||
| AImin | 1 | Outlet sensor | Read | |||
| AI | 2 | Stack sensor | Read | |||
| AI | 3 | DHW sensor | Read | |||
| AI | 4 | System Inlet Sensor | Read | |||
| AI | 5 | System Outlet Sensor | Read | |||
| AI | 6 | Outdoor Sensor | Read | |||
| AI | 12 | Flame Signal 1 | Read | |||
| AI | 14 | 0-10VDC (4-20mA) Input for BAS | Read | |||
| AI | 15 | 0-10VDC (4-20mA) Input for Pump | Read | |||
| AI | 16 | 0-10VDC (4-20mA) Input for Mixing Valve | Read | |||
| AI | 17 | 0-10VDC (4-20mA) Input for Auxiliary | Read | |||
| AI | 20 | Demand source | Read | 0=None, 1=Anti-Short Cycle, 2=Service, 3=DHW, 4=Cascade, 5=External, 6=CH1, 7=CH2, 8=CH3, 9=CH4, 10=Anti-Frost, 11=Warm weather shutdown | ||
| AI | 23 | 0-10VDC (4-20mA) Output for Pump Speed | Read | |||
| AI | 24 | 0-10VDC (4-20mA) Output for Fan Speed | Read | |||
| AI | 25 | 0-10VDC (4-20mA) Output for Mixing Valve | Read | |||
| AI | 26 | 0-10VDC (4-20mA) Output for Auxiliary 1 | Read | |||
| AI | 27 | Modulating Fan 1 - Speed | Read | |||
| AImin | 33 | Modulating Burner1 Firing rate | Read | |||
| AImin | 35 | Lockout code | Read | 0=Low Flow Error, 1=Low Water Cut Off Error, 2=Manual Reset High Limit Error, 3=Blocked Flue Error, 4=High Gas Pressure Error, 5=Low Gas Pressure Error, 6=Auto Reset High Limit Error, 7=Spare Safety Chain Error, 8=Outlet Probe Error, 9=Outlet Probe Drift Error, 10=Outlet Probe High Limit Error, 11=Flue Probe Error, 12=Condensing Shutdown Error, 13=Flue Probe Drift Error, 14=Flue Probe High Limit Error, 15=Inlet Probe Error, 16=Delta T Error, 17=Generic Lockout, 18=Burner1 APS Switch Error, 19=Burner2 APS Switch Error, 20=Burner1 HSI Flame Error, 21=Burner2 HSI Flame Error, 22=Burner1 Max Trials Error, 23=Burner2 Max Trials Error, 24=Burner1 Max Flame Lost Error, 25=Burner2 Max Flame Lost Error, 26=Burner1 Proven HSI Error, 27=Burner2 Proven HSI Error, 28=Burner1 Fan Speed Error, 29=Burner2 Fan Speed Error | ||
| AI | 36 | Alarm reason | Read | 30=24VDC Error, 31=24VAC Error, 32=DHW Probe Error, 33=System Supply Probe Error, 34=System Return Probe Error, 35=Outdoor Probe Error, 36=Spare1 Probe Error, 37=Spare2 Probe Error, 38=Spare3 Probe Error, 39=Spare4 Probe Error, 40=Spare5 Probe Error, 41=High Limit Auto Error, 42=High Delta T Error, 43=Fan Speed Error, 44=Condensing Alarm | ||
| AI | 37 | Hold code | Read | |||
| AI | 38 | History - DHW Demand Cycles | Read | |||
| AI | 39 | History - CH1 Demand Cycles | Read | |||
| AI | 40 | History - CH2 Demand Cycles | Read | |||
| AI | 43 | History - Cascade Demand Cycles | Read | |||
| AI | 44 | History - Burner Stage 1 Cycles | Read | |||
| AI | 48 | History - Boiler Pump Cycles | Read | |||
| AI | 49 | History - DHW Pump Cycles | Read | |||
| AI | 50 | History - System Pump Cycles | Read | |||
| AI | 51 | History - Average Boiler Outlet Temperature | Read | |||
| AI | 52 | History - Maximum Boiler Outlet Temperature | Read | |||
| AI | 53 | History - Minimum Boiler Outlet Temperature | Read | |||
| AI | 54 | History - Boiler Average Firing Temperature | Read | |||
| AI | 55 | History - Boiler Maximum Firing Time | Read | |||
| AI | 56 | History - Boiler Minimum Firing Time | Read | |||
| AI | 57 | Controller Cycle Count | Read | |||
| AI | 58 | Controller run time | Read | |||
| AI | 59 | Lead Lag (Cascade) lead status | Read | |||
| AI | 60 | Lead Lag (Cascade) lag status | Read | |||
| AI | 61 | Lead Lag (Cascade) lead Setpoint Source | Read | |||
| AI | 62 | Lead Lag (Cascade) lead Pump Demand | Read | |||
| AI | 63 | Lead Lag (Cascade) setpoint | Read | |||
| AI | 64 | Lead Lag (Cascade) modulation sensor | Read | |||
| AI | 65 | Lead Lag (Cascade) active service | Read | |||
| AI | 66 | Lag 1 State | Read | 0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | ||
| AI | 67 | Lag 1 Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 68 | Lag 2 State | Read | 0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | ||
| AI | 69 | Lag 2 Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 70 | Lag 3 State | Read | 0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | ||
| AI | 71 | Lag 3 Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 72 | Lag 4 State | Read | 0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | ||
| AI | 73 | Lag 4 Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 74 | Lag 5 State | Read | 0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | ||
| AI | 75 | Lag 5 Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 76 | Lag 6 State | Read | 0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | ||
| AI | 77 | Lag 6 Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 78 | Lag 7 State | Read | 0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | ||
| AI | 79 | Lag 7 Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 80 | Lead 0 State | Read | 0=Lead is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering | ||
| AI | 81 | Lead 0 Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 82 | Lead Firing Rate | Firing rate, 0-100 % | % | Read | |
| AI | 83 | Active CH Setpoint | Read | |||
| AI | 84 | Burner Status 1 | Read | 0=None, 5=Start, 24=Error Block, 160=Standby, 165=Check Safety Swtich, 166=Run, 177=Prepurge Open, 181=Parameter Block, 183=Lockout, 188=Testmode, 194=Prepurge Closed, 195=Wait for HIS Free, 196=HIS Preheat/Prespark, 200=Verify Primary SF, 217=interpurge, 241=Postpurge, 245=Trial for Ignition, 250=Trial for Ignition Main, 52=Post Purge | ||
| AImin | 85 | Burner Status 2 | Read | 0=Disabled, 1=Locked out, 2-3=Reserved, 4=Anti-short cycle, 34=Standby Hold, 35=Standby Delay, 48=Normal Standby, 49=Preparing, 50=Ignition, 51=Firing, 52=Post Purge | ||
| AI | 86 | CH Set Point Source | Read | 0=no CH source, 1=CH1, 2=CH2, 3=CH3, 4=CH4, 5=External Demand | ||
| AI | 87 | CH Requested Rate | Read | |||
| AI | 88 | DHW Requested Rate | Read | |||
| AI | 89 | Boiler Pump Status | Read | |||
| AI | 90 | Cascade Master Heat Demand | Read | |||
| AI | 91 | Burner 1 Run Time | Read | |||
| AI | 92 | Burner 2 Run Time | Read | |||
| AVmin | 0 | CH1 Enable/Disable | Write | 0=Disable, 1=Enable | ||
| AVmin | 1 | CH1 Set Point | Write | |||
| AV | 2 | CH1 P | Write | |||
| AV | 3 | CH1 I | Write | |||
| AV | 4 | CH1 D | Write | |||
| AV | 5 | CH2 Enable/Disable | Write | 0=Disable, 1=Enable | ||
| AV | 6 | CH2 Set Point | Write | |||
| AV | 7 | CH2 P | Write | |||
| AV | 8 | CH2 I | Write | |||
| AV | 9 | CH2 D | Write | |||
| AV | 20 | DHW Enable/Disable | Write | 0=Disable, 1=Enable | ||
| AV | 21 | DHW Set Point | Write | |||
| AV | 22 | DHW P | Write | |||
| AV | 23 | DHW I | Write | |||
| AV | 24 | DHW D | Write | |||
| AVmin | 27 | Cascade CH Set Point | Write | |||
| AV | 28 | Cascade CH P | Write | |||
| AV | 29 | Cascade CH I | Write | |||
| AV | 30 | Cascade CH D | Write | |||
| AV | 35 | Hybrid Set Point | Write | |||
| AV | 36 | Hybrid Differential Temperature | Write | |||
| AV | 37 | Vari-Prime P - Proportional Term | Write | |||
| AV | 38 | Vari-Prime I - Integral Term | Write | |||
| AV | 39 | Vari-Prime D - Derivative Term | Write | |||
| AV | 40 | Vari-Prime Delta T | Write | |||
| BI | 1 | Safety Chain Status - Flow Switch | Modbus register 18 bit 0 | Read | ||
| BI | 2 | Safety Chain Status - LWCO | Modbus register 18 bit 1 | Read | ||
| BI | 3 | Safety Chain Status - MRHL | Modbus register 18 bit 2 | Read | ||
| BI | 4 | Safety Chain Status - Blocked Flue | Modbus register 18 bit 3 | Read | ||
| BI | 5 | Safety Chain Status - High Gas Pressure | Modbus register 18 bit 4 | Read | ||
| BI | 6 | Safety Chain Status - Low Gas Pressure | Modbus register 18 bit 5 | Read | ||
| BI | 7 | Safety Chain Status - Field Interlock | Modbus register 18 bit 6 | Read | ||
| BI | 8 | Safety Chain Status - ARHL | Modbus register 18 bit 7 | Read | ||
| BI | 9 | Non-safety Chain Status - Field Input 1 | Modbus register 19 bit 0 | Read | ||
| BI | 10 | Non-safety Chain Status - Field Input 2 | Modbus register 19 bit 1 | Read | ||
| BImin | 11 | Digital Output Status - Run contact | Modbus register 21 bit 0 | Read | ||
| BImin | 12 | Digital Output Status - Alarm Contact | Modbus register 21 bit 1 | Read | ||
| BI | 13 | Digital Output Status - DHW Pump | Modbus register 21 bit 2 | Read | ||
| BI | 14 | Digital Output Status - System Pump | Modbus register 21 bit 3 | Read | ||
| BI | 15 | Digital Output Status - Louver contact | Modbus register 21 bit 4 | Read | ||
| BI | 16 | Digital Output Status - Aux dry contact 1 | Modbus register 21 bit 5 | Read | ||
| BI | 17 | Digital Output Status - Aux dry contact 2 | Modbus register 21 bit 6 | Read | ||
| BI | 18 | Digital Output Status - Boiler pump | Modbus register 21 bit 7 | Read | ||
| BI | 19 | Digital Output Status - Aux powered contact | Modbus register 21 bit 8 | Read | ||
| BI | 20 | Gas and Pilot Valve Status - Burner 1 Pilot Gas valve | Modbus register 22 bit 0 | Read | ||
| BI | 21 | Gas and Pilot Valve Status - Burner 1 Gas valve 1 | Modbus register 22 bit 1 | Read | ||
| BV | 0 | DHW Demand switch | Write | 0=No Heat Demand, 1=Heat Demand | ||
| BVmin | 1 | CH 1 Demand switch | Write | 0=No Heat Demand, 1=Heat Demand | ||
| BV | 2 | CH 2 Demand switch | Write | 0=No Heat Demand, 1=Heat Demand |
No points match these filters.
Object ID lookup: Laars OmniTherm point IDs by name
AI0Inlet sensorAI1Outlet sensorAI2Stack sensorAI3DHW sensorAI4System Inlet SensorAI5System Outlet SensorAI6Outdoor SensorAI12Flame Signal 1AI140-10VDC (4-20mA) Input for BASAI150-10VDC (4-20mA) Input for PumpAI160-10VDC (4-20mA) Input for Mixing ValveAI170-10VDC (4-20mA) Input for AuxiliaryAI20Demand sourceAI230-10VDC (4-20mA) Output for Pump SpeedAI240-10VDC (4-20mA) Output for Fan SpeedAI250-10VDC (4-20mA) Output for Mixing ValveAI260-10VDC (4-20mA) Output for Auxiliary 1AI27Modulating Fan 1 - SpeedAI33Modulating Burner1 Firing rateAI35Lockout codeAI36Alarm reasonAI37Hold codeAI38History - DHW Demand CyclesAI39History - CH1 Demand CyclesAI40History - CH2 Demand CyclesAI43History - Cascade Demand CyclesAI44History - Burner Stage 1 CyclesAI48History - Boiler Pump CyclesAI49History - DHW Pump CyclesAI50History - System Pump CyclesAI51History - Average Boiler Outlet TemperatureAI52History - Maximum Boiler Outlet TemperatureAI53History - Minimum Boiler Outlet TemperatureAI54History - Boiler Average Firing TemperatureAI55History - Boiler Maximum Firing TimeAI56History - Boiler Minimum Firing TimeAI57Controller Cycle CountAI58Controller run timeAI59Lead Lag (Cascade) lead statusAI60Lead Lag (Cascade) lag statusAI61Lead Lag (Cascade) lead Setpoint SourceAI62Lead Lag (Cascade) lead Pump DemandAI63Lead Lag (Cascade) setpointAI64Lead Lag (Cascade) modulation sensorAI65Lead Lag (Cascade) active serviceAI66Lag 1 StateAI67Lag 1 Firing RateAI68Lag 2 StateAI69Lag 2 Firing RateAI70Lag 3 StateAI71Lag 3 Firing RateAI72Lag 4 StateAI73Lag 4 Firing RateAI74Lag 5 StateAI75Lag 5 Firing RateAI76Lag 6 StateAI77Lag 6 Firing RateAI78Lag 7 StateAI79Lag 7 Firing RateAI80Lead 0 StateAI81Lead 0 Firing RateAI82Lead Firing RateAI83Active CH SetpointAI84Burner Status 1AI85Burner Status 2AI86CH Set Point SourceAI87CH Requested RateAI88DHW Requested RateAI89Boiler Pump StatusAI90Cascade Master Heat DemandAI91Burner 1 Run TimeAI92Burner 2 Run TimeAV0CH1 Enable/DisableAV1CH1 Set PointAV2CH1 PAV3CH1 IAV4CH1 DAV5CH2 Enable/DisableAV6CH2 Set PointAV7CH2 PAV8CH2 IAV9CH2 DAV20DHW Enable/DisableAV21DHW Set PointAV22DHW PAV23DHW IAV24DHW DAV27Cascade CH Set PointAV28Cascade CH PAV29Cascade CH IAV30Cascade CH DAV35Hybrid Set PointAV36Hybrid Differential TemperatureAV37Vari-Prime P - Proportional TermAV38Vari-Prime I - Integral TermAV39Vari-Prime D - Derivative TermAV40Vari-Prime Delta TBI1Safety Chain Status - Flow SwitchBI2Safety Chain Status - LWCOBI3Safety Chain Status - MRHLBI4Safety Chain Status - Blocked FlueBI5Safety Chain Status - High Gas PressureBI6Safety Chain Status - Low Gas PressureBI7Safety Chain Status - Field InterlockBI8Safety Chain Status - ARHLBI9Non-safety Chain Status - Field Input 1BI10Non-safety Chain Status - Field Input 2BI11Digital Output Status - Run contactBI12Digital Output Status - Alarm ContactBI13Digital Output Status - DHW PumpBI14Digital Output Status - System PumpBI15Digital Output Status - Louver contactBI16Digital Output Status - Aux dry contact 1BI17Digital Output Status - Aux dry contact 2BI18Digital Output Status - Boiler pumpBI19Digital Output Status - Aux powered contactBI20Gas and Pilot Valve Status - Burner 1 Pilot Gas valveBI21Gas and Pilot Valve Status - Burner 1 Gas valve 1BV0DHW Demand switchBV1CH 1 Demand switchBV2CH 2 Demand switch
Integration notes
- Each unit on the ProtoNode's RS-485 bus shows up as its own BACnet device, and every one uses the same object IDs. The device instance is Node_Offset (default 50000) plus the unit's Node-ID, so Node-ID 1 = device 50001.
- The mapping has no read/write column. AV, BV and MV objects are mapped to Metasys N2 outputs and LonWorks input variables, so they are listed here as writable; AI, BI and MI objects are read-only.
- The mapping gives no units for temperatures or set points.
- Bit-mapped registers (safety chain, non-safety chain, digital outputs, gas and pilot valve) are split into one BI per bit; the object names here join the register name and the bit label.
- Compared with the MagnaTherm list this one has no DHW recirculation objects but adds the auxiliary 1 output (AI 26) and fan 1 speed (AI 27).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OmniTherm - ProtoNode and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Laars OmniTherm - ProtoNode
How many BACnet points does the Laars OmniTherm - ProtoNode have?
This list has 121 BACnet objects: 72 analog inputs, 25 analog values, 21 binary inputs, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Laars OmniTherm - ProtoNode BACnet points are writable?
28 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Laars OmniTherm - ProtoNode BACnet documentation?
The source is Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) (4404), revision Document Revision 14.B, October 2020, published free by Laars at https://www.laars.com/uploads/products/4404.pdf.
What are the minimum BACnet points to integrate the Laars OmniTherm - ProtoNode?
Start with AV 0 CH1 Enable/Disable (CH1 enable (1 = enable)); BV 1 CH 1 Demand switch (CH1 call for heat (1 = heat demand)); AV 1 CH1 Set Point (CH1 water set point); AV 27 Cascade CH Set Point (Set point when units run in cascade); BI 11 Digital Output Status - Run contact (Run output); AI 85 Burner Status 2 (Burner state; 51 = firing, 1 = locked out); AI 1 Outlet sensor (Outlet water temperature); AI 33 Modulating Burner1 Firing rate (Burner 1 firing rate); BI 12 Digital Output Status - Alarm Contact (Alarm output); AI 35 Lockout code (Lockout code (0-29)).
How do I enable BMS control of the Laars OmniTherm - ProtoNode?
AV 0 CH1 Enable/Disable (0 = disable, 1 = enable) and BV 1 CH 1 Demand switch (0 = no heat demand, 1 = heat demand). CH2 and DHW have matching objects.
How do I check these points on the real OmniTherm - ProtoNode?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Laars BACnet points lists
- Boiler controller gateway
Laars HTD control - ProtoNode
Laars boilers with the HTD control, read through a ProtoNode FPC-N34 gateway (the document does not name the models).
Also known as: HTD, Laars HTD, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode - Boiler controller gateway
Laars MagnaTherm - ProtoNode
Laars MagnaTherm units, read through a ProtoNode FPC-N34 gateway.
Also known as: MagnaTherm, Laars MagnaTherm, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode - Boiler controller gateway
Laars Multiburner control - ProtoNode
Laars boilers with the Multiburner control, read through a ProtoNode FPC-N34 gateway (the document does not name the models).
Also known as: Multiburner, Laars Multiburner, Multi-burner, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode - Boiler controller gateway
Laars Sola control - ProtoNode
Laars boilers with the Sola control, read through a ProtoNode FPC-N34 gateway (the document does not name the models).
Also known as: Sola, Laars Sola, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode - Gas valve gateway
Laars SV2 gas valve - ProtoNode
The SV2 device on Laars equipment, read through a ProtoNode FPC-N34 gateway. The document does not describe the SV2; its point names cover a gas valve with VPS tests and pressure and fuel/air modules.
Also known as: SV2, Laars SV2, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode
Source: Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) · 4404 · rev. Document Revision 14.B, October 2020. Object names, instances and units are reproduced as published; descriptions are our own.