- Home
- BACnet points lists
- Laars
- SV2 gas valve - ProtoNode
Gas valve gateway · BACnet points list
Laars SV2 gas valve - ProtoNode BACnet points list
Updated 6 November 2026
The ProtoNode reads the SV2 over Modbus RTU and serves 82 objects per device. Most are read-only: valve open states, VPS test results, pressure module readings and status, gas pressure limit setup, active alarm count, the last two fault codes and accumulated hours and cycles. Only the four unit-selection objects are writable.
This page lists 82 BACnet objects for the Laars SV2 gas valve - ProtoNode — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Laars’s own free documentation, linked below.
- Manufacturer
- Laars
- Model
- SV2 gas valve - ProtoNode
- Equipment
- Gas valve gateway
- Equipment type
- Valves & actuators
- BACnet objects
- 82 (4 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 50000 + device Node-ID
- Also known as
- SV2, Laars SV2, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode
Instance calculator. This list prints one unit; the other units follow a formula. ProtoNode boiler gateways (Laars, Peerless, Raypak, AERCO and more) instance calculator →
Reference only, provided as-is: verify against Laars’s current documentation and the live device before use. Not official Laars information. Terms of use.
BMS integration notes: Laars SV2 gas valve - ProtoNode
Monitoring only: read the valve system state, MV1/MV2 open status and the pressure module reading, then watch the lockout flag, the active alarm count and the most recent fault code. The only writable objects are the unit selections.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MI 54 | Valve System States | Valve system state code | Read |
| BI 26 | MV1 Open | Main valve 1 open | Read |
| BI 27 | MV2 Open | Main valve 2 open | Read |
| AI 36 | Current Pressure Mod Press Reading | Current pressure module reading | Read |
| MI 37 | Pressure Module Status | Pressure module status code | Read |
| BI 32 | Lockout | Valve in lockout | Read |
| AI 24 | Num of Currently Active Alarms | Number of active alarms | Read |
| AI 64 | Fault Code Of Most Recent Fault | Fault code of the latest fault | Read |
Network setup
- Device instance = Node_Offset + device Node-ID. Node_Offset defaults to 50000 and is changed in the ProtoNode web configurator; Node-IDs must be unique, 1-255.
- Device to ProtoNode: Modbus RTU, 38400 baud, 8 data bits, no parity, 1 stop bit.
- Default ProtoNode IP address 192.168.1.24, mask 255.255.255.0. Choose BACnet IP or BACnet MS/TP with the Protocol Selector, then add one profile per device with its Node-ID.
- With more than one device on a ProtoNode, set BACnet Virtual Server Nodes to Yes. For BACnet MS/TP also set MAC address, baud rate and Max Master.
- Two or more ProtoNodes on the same subnet need different BACnet Network Numbers (default 50).
- A ProtoNode handles 1,500 registers in total; the SV2 profile counts as 82 per device.
Watch out for
- BV 1, MV 2, MV 3 and BV 4 set the units the valve reports in; set them once, not from a schedule.
- Remote Reset Command (AI 5) is read-only in this mapping, so a remote reset can't be written through it.
Laars SV2 gas valve - ProtoNode BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 5 | Remote Reset Command | Read | |||
| AI | 6 | Pressure Module Factory Data | Read | |||
| AI | 10 | Max Allowed Leakage in User Units | Read | |||
| AI | 11 | Space Between Valves Volume | Read | |||
| AI | 12 | Ext Chmbr Space for Ext Pip btwn V1/V | Read | |||
| AI | 16 | Max HGP Lim Per Deviation | % | Read | ||
| AI | 17 | Max LGP Lim Per Deviation | % | Read | ||
| AI | 19 | Calc LGP Lim SP | Read | |||
| AI | 20 | Calc HGP Lim SP | Read | |||
| AI | 21 | User Entered Valve Name | Read | |||
| AI | 22 | Date Stamp | Read | |||
| AI | 23 | Valve Electronic SW Rev | Read | |||
| AImin | 24 | Num of Currently Active Alarms | Read | |||
| AI | 34 | Min Applicable Pressure | Read | |||
| AI | 35 | Max Applicable Pressure | Read | |||
| AImin | 36 | Current Pressure Mod Press Reading | Read | |||
| AI | 41 | Pressure Module Sensor 1 Ser Num | Read | |||
| AI | 42 | Pressure Module Sensor 2 Ser Num | Read | |||
| AI | 43 | Pressure Module Sensor 3 Ser Num | Read | |||
| AI | 44 | Valve Test Mode State | Read | |||
| AI | 45 | VPS Min Calc Vlv Pwr Tim Req | s | Read | ||
| AI | 48 | Valve 1 Max Leak Det dur Lst VPS Seq | Read | |||
| AI | 49 | Valve 2 Max Leak Det dur Lst VPS Seq | Read | |||
| AI | 50 | VPS Min Test Time Req | s | Read | ||
| AI | 52 | Op Prs Val for LGP Lim SP | Read | |||
| AI | 53 | Op Prs Val for HGP Lim SP | Read | |||
| AImin | 64 | Fault Code Of Most Recent Fault | Read | |||
| AI | 65 | Time Stamp Of Most Recent Fault | Read | |||
| AI | 66 | Cycle Count Of Most Recent Fault | Read | |||
| AI | 67 | Fault Code Of Previous Fault | Read | |||
| AI | 68 | Time Stamp Of Previous Fault | Read | |||
| AI | 69 | Cycle Count Of Previous Fault | Read | |||
| AI | 70 | Valve Accumulated Op Time | h | Read | ||
| AI | 71 | Valve Accumulated Number of Cycles | Read | |||
| AI | 72 | Valve 1 Accum Hours during last VPS | h | Read | ||
| AI | 73 | Valve 1 Accum Cycles during last VPS | Read | |||
| AI | 74 | Valve 2 Accum Hours during last VPS | h | Read | ||
| AI | 75 | Valve 2 Accum Cycles during last VPS | Read | |||
| AI | 77 | Preigniton Calbiration S1 | Read | |||
| AI | 78 | Preigniton Test S1 | Read | |||
| AI | 79 | Preigniton Calbiration Gain S2A | Read | |||
| AI | 80 | Preigniton Calbiration Gain S2B | Read | |||
| AI | 81 | Preigniton Test Gain S2A | Read | |||
| AI | 82 | Preigniton Test Gain S2B | Read | |||
| BI | 7 | Valve MV1/MV2 LED | Read | |||
| BI | 9 | VPS Disable/Enable Status | Read | |||
| BI | 13 | VPS Relay Polarity | Read | |||
| BI | 25 | Reset Button | Read | |||
| BImin | 26 | MV1 Open | Read | |||
| BImin | 27 | MV2 Open | Read | |||
| BI | 28 | Fuel/Air Module Comm OK | Read | |||
| BI | 29 | Pressure Module Comm OK | Read | |||
| BI | 30 | Fuel/Air Module Check Valve | Read | |||
| BI | 31 | Safety Param Verification Req | Read | |||
| BImin | 32 | Lockout | Read | |||
| BI | 33 | Valve Cycle Counter Lim Reached | Read | |||
| BV | 1 | Selectable Units for Temperature | Write | |||
| BV | 4 | Selectable Volumetric Units | Write | |||
| MI | 8 | Body Size of Attached Valve | Read | |||
| MI | 14 | LGP Limit Lockout Type | Read | |||
| MI | 15 | HGP Limit Lockout Type | Read | |||
| MI | 18 | LGP and HGP Setup Indication | Read | |||
| MImin | 37 | Pressure Module Status | Read | |||
| MI | 38 | Pressure Module Sensor 1 Status | Read | |||
| MI | 39 | Pressure Module Sensor 2 Status | Read | |||
| MI | 40 | Pressure Module Sensor 3 Status | Read | |||
| MI | 46 | VPS Valve 1 Status | Read | |||
| MI | 47 | VPS Valve 2 Status | Read | |||
| MI | 51 | Hi/Lo Gas Pressure Function Status | Read | |||
| MImin | 54 | Valve System States | Read | |||
| MI | 55 | Valve 1 Demand | Read | |||
| MI | 56 | Valve 2 Demand | Read | |||
| MI | 57 | Interlock String | Read | |||
| MI | 58 | Proof of Closure Feedback | Read | |||
| MI | 59 | Sol 1 Feedback – Full Power Mode | Read | |||
| MI | 60 | Sol 2 Feedback – Full Power Mode | Read | |||
| MI | 61 | Sol 1 Feedback – Power Save Mode | Read | |||
| MI | 62 | Sol 2 Feedback – Power Save Mode | Read | |||
| MI | 63 | Sol 1 Fb for MV1 Rel Test – Full Pwr | Read | |||
| MI | 76 | Safety Param Verification Status | Read | |||
| MV | 2 | Selectable Units for Pressure | Write | |||
| MV | 3 | Selectable Units for Volumetric Flow | Write |
No points match these filters.
Object ID lookup: Laars SV2 gas valve point IDs by name
AI5Remote Reset CommandAI6Pressure Module Factory DataAI10Max Allowed Leakage in User UnitsAI11Space Between Valves VolumeAI12Ext Chmbr Space for Ext Pip btwn V1/VAI16Max HGP Lim Per DeviationAI17Max LGP Lim Per DeviationAI19Calc LGP Lim SPAI20Calc HGP Lim SPAI21User Entered Valve NameAI22Date StampAI23Valve Electronic SW RevAI24Num of Currently Active AlarmsAI34Min Applicable PressureAI35Max Applicable PressureAI36Current Pressure Mod Press ReadingAI41Pressure Module Sensor 1 Ser NumAI42Pressure Module Sensor 2 Ser NumAI43Pressure Module Sensor 3 Ser NumAI44Valve Test Mode StateAI45VPS Min Calc Vlv Pwr Tim ReqAI48Valve 1 Max Leak Det dur Lst VPS SeqAI49Valve 2 Max Leak Det dur Lst VPS SeqAI50VPS Min Test Time ReqAI52Op Prs Val for LGP Lim SPAI53Op Prs Val for HGP Lim SPAI64Fault Code Of Most Recent FaultAI65Time Stamp Of Most Recent FaultAI66Cycle Count Of Most Recent FaultAI67Fault Code Of Previous FaultAI68Time Stamp Of Previous FaultAI69Cycle Count Of Previous FaultAI70Valve Accumulated Op TimeAI71Valve Accumulated Number of CyclesAI72Valve 1 Accum Hours during last VPSAI73Valve 1 Accum Cycles during last VPSAI74Valve 2 Accum Hours during last VPSAI75Valve 2 Accum Cycles during last VPSAI77Preigniton Calbiration S1AI78Preigniton Test S1AI79Preigniton Calbiration Gain S2AAI80Preigniton Calbiration Gain S2BAI81Preigniton Test Gain S2AAI82Preigniton Test Gain S2BBI7Valve MV1/MV2 LEDBI9VPS Disable/Enable StatusBI13VPS Relay PolarityBI25Reset ButtonBI26MV1 OpenBI27MV2 OpenBI28Fuel/Air Module Comm OKBI29Pressure Module Comm OKBI30Fuel/Air Module Check ValveBI31Safety Param Verification ReqBI32LockoutBI33Valve Cycle Counter Lim ReachedBV1Selectable Units for TemperatureBV4Selectable Volumetric UnitsMI8Body Size of Attached ValveMI14LGP Limit Lockout TypeMI15HGP Limit Lockout TypeMI18LGP and HGP Setup IndicationMI37Pressure Module StatusMI38Pressure Module Sensor 1 StatusMI39Pressure Module Sensor 2 StatusMI40Pressure Module Sensor 3 StatusMI46VPS Valve 1 StatusMI47VPS Valve 2 StatusMI51Hi/Lo Gas Pressure Function StatusMI54Valve System StatesMI55Valve 1 DemandMI56Valve 2 DemandMI57Interlock StringMI58Proof of Closure FeedbackMI59Sol 1 Feedback – Full Power ModeMI60Sol 2 Feedback – Full Power ModeMI61Sol 1 Feedback – Power Save ModeMI62Sol 2 Feedback – Power Save ModeMI63Sol 1 Fb for MV1 Rel Test – Full PwrMI76Safety Param Verification StatusMV2Selectable Units for PressureMV3Selectable Units for Volumetric Flow
Integration notes
- Each device on the ProtoNode's RS-485 bus shows up as its own BACnet device, and every one uses the same object IDs. The device instance is Node_Offset (default 50000) plus the device's Node-ID, so Node-ID 1 = device 50001.
- The mapping has no read/write column. AV, BV and MV objects are mapped to Metasys N2 outputs and LonWorks input variables, so they are listed here as writable; AI, BI and MI objects are read-only.
- No units or state texts are given for the multistate inputs.
- Several objects span more than one Modbus register (e.g. the user-entered valve name, 40255-40259), and some multistate inputs are two-bit fields inside one register.
- Remote Reset Command is mapped as a read-only AI.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SV2 gas valve - ProtoNode and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Laars SV2 gas valve - ProtoNode
How many BACnet points does the Laars SV2 gas valve - ProtoNode have?
This list has 82 BACnet objects: 44 analog inputs, 12 binary inputs, 2 binary values, 22 multi-state inputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Laars SV2 gas valve - ProtoNode BACnet points are writable?
4 of the 82 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Laars SV2 gas valve - ProtoNode BACnet documentation?
The source is Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) (4404), revision Document Revision 14.B, October 2020, published free by Laars at https://www.laars.com/uploads/products/4404.pdf.
What are the minimum BACnet points to integrate the Laars SV2 gas valve - ProtoNode?
Start with MI 54 Valve System States (Valve system state code); BI 26 MV1 Open (Main valve 1 open); BI 27 MV2 Open (Main valve 2 open); AI 36 Current Pressure Mod Press Reading (Current pressure module reading); MI 37 Pressure Module Status (Pressure module status code); BI 32 Lockout (Valve in lockout); AI 24 Num of Currently Active Alarms (Number of active alarms); AI 64 Fault Code Of Most Recent Fault (Fault code of the latest fault).
How do I check these points on the real SV2 gas valve - ProtoNode?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Laars BACnet points lists
- Boiler controller gateway
Laars HTD control - ProtoNode
Laars boilers with the HTD control, read through a ProtoNode FPC-N34 gateway (the document does not name the models).
Also known as: HTD, Laars HTD, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode - Boiler controller gateway
Laars MagnaTherm - ProtoNode
Laars MagnaTherm units, read through a ProtoNode FPC-N34 gateway.
Also known as: MagnaTherm, Laars MagnaTherm, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode - Boiler controller gateway
Laars Multiburner control - ProtoNode
Laars boilers with the Multiburner control, read through a ProtoNode FPC-N34 gateway (the document does not name the models).
Also known as: Multiburner, Laars Multiburner, Multi-burner, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode - Boiler controller gateway
Laars OmniTherm - ProtoNode
Laars OmniTherm units, read through a ProtoNode FPC-N34 gateway.
Also known as: OmniTherm, Laars OmniTherm, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode - Boiler controller gateway
Laars Sola control - ProtoNode
Laars boilers with the Sola control, read through a ProtoNode FPC-N34 gateway (the document does not name the models).
Also known as: Sola, Laars Sola, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode
Source: Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) · 4404 · rev. Document Revision 14.B, October 2020. Object names, instances and units are reproduced as published; descriptions are our own.