Scroll chiller / heat pump controller · BACnet points list
Carrier AquaSnap 30MP (PIC6 Carrier Controller) BACnet points list
Updated 28 October 2026
The 30MP's Carrier Controller publishes about 230 BACnet objects (AV, BV and one MV) on its ETH0 Ethernet port. Commands come as separate read (_rd) and write (_wr) objects, with the writable copies numbered 10000 and up, and alarm flags are BVs numbered after Carrier alarm codes (e.g. BV 110001). Water-cooled condenser, head pressure and heat pump points only apply to some unit types.
This page lists 232 BACnet objects for the Carrier AquaSnap 30MP (PIC6 Carrier Controller) — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaSnap 30MP (PIC6 Carrier Controller)
- Equipment
- Scroll chiller / heat pump controller
- Equipment type
- Chillers
- BACnet objects
- 232 (24 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Default device instance
- 1600001
- Also known as
- 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Set bacena to 1 (BACnet IP) under Main Menu > Configuration > BACnet, set the device ID and network, then put the unit in Network control with the Start/Stop button. Command through the _wr objects (start/stop, occupancy, control point, demand limit, heat/cool select, emergency stop) and read run status, water temperatures, capacity and alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10012 | GENUNIT_CHIL_S_S_wr | Network start/stop command | Write |
| BV 10058 | GENUNIT_CHIL_OCC_wr | Network occupied command | Write |
| AV 10023 | GENUNIT_HC_SEL_wr | Heat/cool select command | Write |
| AV 10006 | GENUNIT_CTRL_PNT_wr | Leaving water control point from the BMS | Write |
| AV 10008 | GENUNIT_DEM_LIM_wr | Demand limit command | Write |
| AV 21 | GENUNIT_CTRL_TYP | Control type: Local, Network or Remote | Read |
| AV 22 | GENUNIT_STATUS | Running status | Read |
| AV 2 | TEMP_LWT | Leaving water temperature | Read |
| AV 9 | GENUNIT_CAP_T | Percent total capacity | Read |
| AV 990 | ALARMRST_ALM | Unit alarm state | Read |
Enable & remote start
Select the Network machine control method with the Start/Stop button. The unit then follows CCN, BACnet (if enabled) or Modbus (if enabled) commands and ignores the remote control contacts. Start/stop and occupancy are written to the _wr objects.
Heartbeat & communication loss
The manual says that if communication with the network is lost while under network control, the machine starts and runs under local control.
Network setup
- BACnet is disabled by default (bacena 0); set 1 for BACnet IP (2 selects MS/TP in the menu).
- Defaults shown: network 1600, UDP port 47808 (47808-47823), manual device ID 1600001, auto device ID option off.
- BACnet IP uses the ETH0 port (IP port interface option 0 = J5/J15, 1 = J16).
- MS/TP menu defaults: MAC 1, baud option 2 (38400), Max Master 10, Max Info Frames 5.
Watch out for
- Write the _wr object, not the _rd one; the _rd copy only reports the current value.
- The BACnet menu has a "BACnet Manage Occupancy" option (mng_occ, default No) and the list has a writable BACnet_BMS_OCC (AV 66, 0 = unocc, 1 = occ, 2 = none); check how they interact with CHIL_OCC before relying on either.
- The manual says CCN loadshed demand limiting needs the unit in Network control.
Carrier AquaSnap 30MP (PIC6 Carrier Controller) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | TEMP_EWT | Entering Water Temp | Read | ||
| AVmin | 2 | TEMP_LWT | Leaving Water Temp | Read | ||
| AV | 3 | TEMP_OAT | Outdoor Air Temperature | Read | ||
| AV | 5 | TEMP_DLWT | Dual Leaving Water Temp | Read | ||
| AV | 6 | GENUNIT_CTRL_PNT_rd | Control Point | Read | ||
| AV | 7 | GENUNIT_SP | Current Setpoint | Read | ||
| AV | 8 | GENUNIT_DEM_LIM_rd | Active Demand Limit Val | Read | ||
| AVmin | 9 | GENUNIT_CAP_T | Percent Total Capacity | Read | ||
| AV | 11 | GENUNIT_min_left | Minutes Left for Start | Read | ||
| AV | 20 | INPUTS_ICE_SW | Ice Done Storage Switch | Read | ||
| AVmin | 21 | GENUNIT_CTRL_TYP | Local=0 Network=1 Remote=2 | Read | ||
| AVmin | 22 | GENUNIT_STATUS | Running Status | Read | ||
| AV | 23 | GENUNIT_HC_SEL_rd | Heat/Cool Select | Read | ||
| AV | 24 | GENUNIT_SP_SEL_rd | Setpoint Select | Read | ||
| AV | 25 | TEMP_CEWT | Cond Entering Water Temp | Read | ||
| AV | 26 | TEMP_CLWT | Cond Leaving Water Temp | Read | ||
| AV | 45 | INPUTS_HC_SW | Remote Heat/Cool Switch | Read | ||
| AV | 62 | BACnet_network | Network | Read | ||
| AV | 63 | BACnet_ident | Device Id Actually Used | Read | ||
| AV | 65 | BACnet_PRIME_V | ALC Prime Value | Read | ||
| AV | 66 | BACnet_BMS_OCC | BMS's request for occupancy: 0=UNOCC, 1=OCC, 2, None. | Write | ||
| AV | 73 | PUMPCONF_pump_seq | Cooler Pumps Sequence | Read | ||
| AV | 77 | GENUNIT_HEATCOOL | Heat/Cool status | Read | ||
| AV | 900 | SETPOINT_csp1 | Cooling Setpoint 1 | Write | ||
| AV | 901 | SETPOINT_csp2 | Cooling Setpoint 2 | Write | ||
| AV | 903 | SETPOINT_hsp1 | Heating Setpoint 1 | Write | ||
| AV | 904 | SETPOINT_hsp2 | Heating Setpoint 2 | Write | ||
| AV | 905 | SETPOINT_lim_sp1 | Switch Limit Setpoint 1 | Write | ||
| AV | 906 | SETPOINT_lim_sp2 | Switch Limit Setpoint 2 | Write | ||
| AV | 907 | SETPOINT_lim_sp3 | Switch Limit Setpoint 3 | Write | ||
| AV | 960 | RUNTIME_hr_mach | Machine Operating Hours | Read | ||
| AV | 961 | RUNTIME_st_mach | Machine Starts Number | Read | ||
| AV | 962 | RUNTIME_hr_pump1 | Water Pump no. 1 Hours | Read | ||
| AV | 963 | RUNTIME_hr_pump2 | Water Pump no. 2 Hours | Read | ||
| AV | 966 | HR_PARTIAL_DOWNTIME | Cumul Time Partial Alm | Read | ||
| AV | 967 | HR_TOTAL_DOWNTIME | Cumul Time Tripout Alm | Read | ||
| AV | 980 | ALARMRST_alarm_1c | Current Alarm 1 | Read | ||
| AV | 981 | ALARMRST_alarm_2c | Current Alarm 2 | Read | ||
| AV | 982 | ALARMRST_alarm_3c | Current Alarm 3 | Read | ||
| AV | 983 | ALARMRST_alarm_4c | Current Alarm 4 | Read | ||
| AV | 984 | ALARMRST_alarm_5c | Current Alarm 5 | Read | ||
| AV | 985 | ALARMRST_alarm_1 | Current Alarm 1 index | Read | ||
| AV | 986 | ALARMRST_alarm_2 | Current Alarm 2 index | Read | ||
| AV | 987 | ALARMRST_alarm_3 | Current Alarm 3 index | Read | ||
| AV | 988 | ALARMRST_alarm_4 | Current Alarm 4 index | Read | ||
| AV | 989 | ALARMRST_alarm_5 | Current Alarm 5 index | Read | ||
| AVmin | 990 | ALARMRST_ALM | Alarm State | Read | ||
| AV | 1000 | PRESSURE_DP_A | Discharge Pressure A | Read | ||
| AV | 1001 | PRESSURE_SP_A | Suction Pressure A | Read | ||
| AV | 1005 | TEMP_SCT_A | Saturated Cond Tmp Cir A | Read | ||
| AV | 1006 | TEMP_SST_A | Saturated Suction Temp A | Read | ||
| AV | 1007 | TEMP_SUCT_A | Suction Temp Circuit A | Read | ||
| AV | 1009 | TEMP_DGT_A | Discharge Gas Temp A | Read | ||
| AV | 1011 | LOADFACT_SH_A | Suction Superheat A | Read | ||
| AV | 1015 | OUTPUTS_VFAN | Variable Fan Speed | Read | ||
| AV | 1017 | GENUNIT_CAPA_T | Circuit A Total Capacity | Read | ||
| AV | 1960 | RUNTIME_hr_cp_a1 | Compressor A1 Hours | Read | ||
| AV | 1961 | RUNTIME_hr_cp_a2 | Compressor A2 Hours | Read | ||
| AV | 1962 | RUNTIME_hr_cp_a3 | Compressor A3 Hours | Read | ||
| AV | 1964 | RUNTIME_st_cp_a1 | Compressor A1 Starts | Read | ||
| AV | 1965 | RUNTIME_st_cp_a2 | Compressor A2 Starts | Read | ||
| AV | 1966 | RUNTIME_st_cp_a3 | Compressor A3 Starts | Read | ||
| AV | 2000 | PRESSURE_DP_B | Discharge Pressure B | Read | ||
| AV | 2001 | PRESSURE_SP_B | Suction Pressure B | Read | ||
| AV | 2005 | TEMP_SCT_B | Saturated Cond Tmp Cir B | Read | ||
| AV | 2006 | TEMP_SST_B | Saturated Suction Temp B | Read | ||
| AV | 2007 | TEMP_SUCT_B | Suction Temp Circuit B | Read | ||
| AV | 2009 | TEMP_DGT_B | Discharge Gas Temp B | Read | ||
| AV | 2011 | LOADFACT_SH_B | Suction Superheat B | Read | ||
| AV | 2017 | GENUNIT_CAPB_T | Circuit B Total Capacity | Read | ||
| AV | 2960 | RUNTIME_hr_cp_b1 | Compressor B1 Hours | Read | ||
| AV | 2961 | RUNTIME_hr_cp_b2 | Compressor B2 Hours | Read | ||
| AV | 2964 | RUNTIME_st_cp_b1 | Compressor B1 Starts | Read | ||
| AV | 2965 | RUNTIME_st_cp_b2 | Compressor B2 Starts | Read | ||
| AV | 5001 | PUMPCONF_pump_del | Pump Auto Rotation Delay | Read | ||
| AV | 5003 | GENCONF_lim_sel | Demand Limit Type Select | Read | ||
| AV | 5005 | INPUTS_SP_RESET | Setpoint Reset Signal | Read | ||
| AV | 5006 | INPUTS_leak_v1 | Leakage Detection 1 | Read | ||
| AV | 5007 | INPUTS_leak_v2 | Leakage Detection 2 | Read | ||
| AV | 5008 | INPUTS_DSHTR_SW | Desuperheater Switch | Read | ||
| AV | 5013 | FACTORY_unit_typ | Unit Type (WaterCooled=3) | Read | ||
| AV | 5014 | FACTORY_unitsize | Unit Capacity Model | Read | ||
| AV | 5015 | SETPOINT_ramp_sp | Ramp Loading | Write | ||
| AV | 5016 | SETPOINT_cauto_sp | Cool Changeover Setpt | Write | ||
| AV | 5017 | SETPOINT_hauto_sp | Heat Changeover Setpt | Write | ||
| AV | 5019 | HCCONFIG_cr_sel | Cooling Reset Select | Read | ||
| AV | 5020 | HCCONFIG_hr_sel | Heating Reset Select | Read | ||
| AV | 5023 | OUTPUTS_EXV_A | EXV Position Circuit A | Read | ||
| AV | 5024 | OUTPUTS_EXV_B | EXV Position Circuit B | Read | ||
| AV | 5027 | RESETCFG_oat_crno | OAT No Reset Value | Read | ||
| AV | 5028 | RESETCFG_oat_crfu | OAT Full Reset Value | Read | ||
| AV | 5029 | RESETCFG_dt_cr_no | Delta T No Reset Value | Read | ||
| AV | 5030 | RESETCFG_dt_cr_fu | Delta T Full Reset Value | Read | ||
| AV | 5031 | RESETCFG_I_cr_no | Current No Reset Value | Read | ||
| AV | 5032 | RESETCFG_I_cr_fu | Current Full Reset Value | Read | ||
| AV | 5033 | RESETCFG_spacr_no | Space T No Reset Value | Read | ||
| AV | 5034 | RESETCFG_spacr_fu | Space T Full Reset Value | Read | ||
| AV | 5035 | RESETCFG_cr_deg | Cooling Reset Deg. Value | Read | ||
| AV | 5036 | RESETCFG_oat_hrno | OAT No Reset Value | Read | ||
| AV | 5037 | RESETCFG_oat_hrfu | OAT Full Reset Value | Read | ||
| AV | 5038 | RESETCFG_dt_hr_no | Delta T No Reset Value | Read | ||
| AV | 5039 | RESETCFG_dt_hr_fu | Delta T Full Reset Value | Read | ||
| AV | 5040 | RESETCFG_I_hr_no | Current No Reset Value | Read | ||
| AV | 5041 | RESETCFG_I_hr_fu | Current Full Reset Value | Read | ||
| AV | 5042 | RESETCFG_spahr_no | Space T No Reset Value | Read | ||
| AV | 5043 | RESETCFG_spahr_fu | Space T Full Reset Value | Read | ||
| AV | 5044 | RESETCFG_hr_deg | Heating Reset Deg. Value | Read | ||
| AV | 5064 | SETPOINT_min_sct | Desuperheater Min Sct | Write | ||
| AV | 5082 | TEMP_SPACETMP | Space Temperature | Read | ||
| AV | 5106 | INPUTS_CSP_IN | 4_20mA Cooling Setpoint | Read | ||
| AV | 5443 | FACTORY_flui_typ | Cooler Fluid Type | Read | ||
| AV | 5447 | SERVICE1_freezesp | Brine Freeze Setpoint | Read | ||
| AV | 5711 | OUTPUTS_BOILER | Boiler Output | Read | ||
| AV | 5752 | OUTPUTS_HEAD_ACT | Head Pressure Actuator A | Read | ||
| AV | 5753 | OUTPUTS_HGBP_V | Hot Gas ByPass Valve | Read | ||
| AV | 5754 | OUTPUTS_DUS | Digital Unload Solenoid | Read | ||
| AV | 5757 | OUTPUTS_LLSV_B | Soleniod Valve B | Read | ||
| AV | 5758 | OUTPUTS_LLSV_A | Soleniod Valve A | Read | ||
| AV | 5759 | INPUTS_CWP1 | Water Pump Interlock 1 | Read | ||
| AV | 5760 | INPUTS_CWP2 | Water Pump Interlock 2 | Read | ||
| AV | 5761 | INPUTS_REV_ROT | Phase Reversal | Read | ||
| AV | 5762 | OUTPUTS_FANC_1 | Fan Contactor 1 | Read | ||
| AV | 5763 | OUTPUTS_FANC_2 | Fan Contactor 2 | Read | ||
| AV | 5764 | INPUTS_LIM_4_20 | Capacity Limit Control | Read | ||
| AV | 5765 | OUTPUTS_EISOR | Evaporator Isolator Rly | Read | ||
| AV | 5766 | FACTORY2_cap_a1 | Compressor A1 Capacity | Read | ||
| AV | 5767 | FACTORY2_cap_a2 | Compressor A2 Capacity | Read | ||
| AV | 5768 | FACTORY2_cap_a3 | Compressor A3 Capacity | Read | ||
| AV | 5769 | FACTORY2_cap_b1 | Compressor B1 Capacity | Read | ||
| AV | 5771 | OUTPUTS_Mod_CPA1 | Digital Module A1 | Read | ||
| AV | 5772 | HEADCTRL_condsp | Computed Cond Setpoint | Read | ||
| AV | 5773 | HEADCTRL_fan | Fan Speed | Read | ||
| AVmin | 10006 | GENUNIT_CTRL_PNT_wr | Control Point | Write | ||
| AVmin | 10008 | GENUNIT_DEM_LIM_wr | Active Demand Limit Val | Write | ||
| AVmin | 10023 | GENUNIT_HC_SEL_wr | Heat/Cool Select | Write | ||
| AV | 10024 | GENUNIT_SP_SEL_wr | Setpoint Select | Write | ||
| AV | 110073 | ALM_COND_PUMP_F | Condenser Pump Default | Read | ||
| BV | 12 | GENUNIT_CHIL_S_S_rd | Net.: Cmd Start/Stop | Read | ||
| BV | 13 | GENUNIT_EMSTOP_rd | Emergency Stop | Read | ||
| BV | 15 | OUTPUTS_RUN | Running Relay | Read | ||
| BV | 16 | INPUTS_ONOFF_SW | Remote On/Off Switch | Read | ||
| BV | 18 | INPUTS_LIM_SW1 | Limit Switch 1 | Read | ||
| BV | 19 | INPUTS_LIM_SW2 | Limit Switch 2 | Read | ||
| BV | 48 | INPUTS_SETP_SW | Second Setpoint Switch | Read | ||
| BV | 50 | PUMPSTAT_PUMP_1_rd | Water Pump no. 1 | Read | ||
| BV | 51 | PUMPSTAT_PUMP_2_rd | Water Pump no. 2 | Read | ||
| BV | 52 | INPUTS_FLOW_SW | Flow Switch Interlock | Read | ||
| BV | 55 | INPUTS_CNFS | Condenser Water Flow SW | Read | ||
| BV | 57 | OUTPUTS_EXCH_HTR | Exchanger Heater | Read | ||
| BV | 58 | GENUNIT_CHIL_OCC_rd | Net.: Cmd Occupied | Read | ||
| BV | 59 | GENUNIT_SP_OCC_rd | Setpoint Occupied? | Read | ||
| BV | 60 | BACnet_bacena | BACnet Enable Option | Read | ||
| BV | 61 | BACnet_bacunit | Metric Units? | Read | ||
| BV | 1032 | OUTPUTS_CP_A1 | Compressor A1 | Read | ||
| BV | 1033 | OUTPUTS_CP_A2 | Compressor A2 | Read | ||
| BV | 1034 | OUTPUTS_CP_A3 | Compressor A3 | Read | ||
| BV | 2032 | OUTPUTS_CP_B1 | Compressor B1 | Read | ||
| BV | 2033 | OUTPUTS_CP_B2 | Compressor B2 | Read | ||
| BV | 5002 | PUMPCONF_pump_per | Pump Sticking Protection | Read | ||
| BV | 5003 | PUMPCONF_pump_sby | Stop Pump During Standby | Read | ||
| BV | 5004 | PUMPCONF_pump_loc | Flow Checked if Pump Off | Read | ||
| BV | 5009 | INPUTS_HP_SW_A | High Pressure Switch A | Read | ||
| BV | 5011 | INPUTS_HP_SW_B | High Pressure Switch B | Read | ||
| BV | 5012 | OUTPUTS_ALARM | Alarm Relay | Read | ||
| BV | 5061 | OPT_SEL_boil_en | Boiler Enable | Write | ||
| BV | 5078 | GENCONF_ewt_opt | Entering Fluid Control | Read | ||
| BV | 5301 | MODES_m_ice | Ice Mode In Effect | Read | ||
| BV | 5756 | PUMPSTAT_CPUMP | Condenser Pump Relay | Read | ||
| BV | 5770 | FACTORY_hgbp_sel | Hot Gas Bypass Selection | Read | ||
| BVmin | 10012 | GENUNIT_CHIL_S_S_wr | Net.: Cmd Start/Stop | Write | ||
| BV | 10013 | GENUNIT_EMSTOP_wr | Emergency Stop | Write | ||
| BV | 10050 | PUMPSTAT_PUMP_1_wr | Evaporator pump 1 | Write | ||
| BV | 10051 | PUMPSTAT_PUMP_2_wr | Evaporator pump 2 | Write | ||
| BV | 10053 | PROTOCOL_PUMP_C | Condenser pump | Write | ||
| BVmin | 10058 | GENUNIT_CHIL_OCC_wr | Net.: Cmd Occupied | Write | ||
| BV | 10059 | GENUNIT_SP_OCC_wr | Setpoint Occupied? | Write | ||
| BV | 104701 | ALM_FAN_DRIVE_COM_F | Loss of communication with VFD Fan Drive | Read | ||
| BV | 104901 | ALM_CIOB_CIR_A_COM_F | Loss of communication with CIOB Board Number A | Read | ||
| BV | 104902 | ALM_CIOB_CIR_B_COM_F | Loss of communication with CIOB Board Number B | Read | ||
| BV | 107001 | ALM_ILL_FACT_CONF_F | Illegal configuration | Read | ||
| BV | 108000 | ALM_INI_FACT_CONF_F | Initial factory configuration required | Read | ||
| BV | 109001 | ALM_M_S_CONFIG_F | Primary chiller configuration error | Read | ||
| BV | 110001 | ALM_COOLER_FREEZE_F | Water Exchanger Freeze Protection | Read | ||
| BV | 110005 | ALM_LOW_SUCTION_A_F | Circuit A Low Saturated Suction Temperature | Read | ||
| BV | 110006 | ALM_LOW_SUCTION_B_F | Circuit B Low Saturated Suction Temperature | Read | ||
| BV | 110011 | ALM_LOW_SH_A_F | Circuit A Low Superheat | Read | ||
| BV | 110012 | ALM_LOW_SH_B_F | Circuit B Low Superheat | Read | ||
| BV | 110014 | ALM_COOLER_LOCK_F | Cooler Interlock Failure | Read | ||
| BV | 110015 | ALM_CONDENSER_LOCK_F | Condenser Flow Switch Failure | Read | ||
| BV | 110016 | ALM_CPA1_REVERSE_ROT_F | Compressor A1 Not Started Or Pressure Increase not Established | Read | ||
| BV | 110017 | ALM_CPA2_REVERSE_ROT_F | Compressor A2 Not Started Or Pressure Increase not Established | Read | ||
| BV | 110018 | ALM_CPA3_REVERSE_ROT_F | Compressor A3 Not Started Or Pressure Increase not Established | Read | ||
| BV | 110020 | ALM_CPB1_REVERSE_ROT_F | Compressor B1 Not Started Or Pressure Increase not Established | Read | ||
| BV | 110021 | ALM_CPB2_REVERSE_ROT_F | Compressor B2 Not Started Or Pressure Increase not Established | Read | ||
| BV | 110029 | ALM_LOSS_COM_SM_F | Loss of communication with System Manager | Read | ||
| BV | 110030 | ALM_LOSS_COM_MS_F | Primary/Secondary communication Failure | Read | ||
| BV | 110031 | ALM_NETWORK_EMSTOP_F | Unit is in Network emergency stop. | Read | ||
| BV | 110032 | ALM_COOL_PUMP1_F | Cooler Pump 1 Default | Read | ||
| BV | 110033 | ALM_COOL_PUMP2_F | Cooler Pump 2 Default | Read | ||
| BV | 110037 | ALM_REPEATED_HI_DGT_A_F | Circuit A Repeated High Discharge Gas Overrides | Read | ||
| BV | 110038 | ALM_REPEATED_HI_DGT_B_F | Circuit B Repeated High Discharge Gas Overrides | Read | ||
| BV | 110040 | ALM_REPEATED_LO_SST_A_F | Circuit A Repeated Low Suction Temp Overrides | Read | ||
| BV | 110041 | ALM_REPEATED_LO_SST_B_F | Circuit B Repeated Low Suction Temp Overrides | Read | ||
| BV | 110063 | ALM_HP_SWITCH_A_F | Circuit A High pressure switch Failure | Read | ||
| BV | 110064 | ALM_HP_SWITCH_B_F | Circuit B High pressure switch Failure | Read | ||
| BV | 110097 | ALM_SENSORS_SWAP_F | Water Exchanger Temperature Sensors Swapped | Read | ||
| BV | 110098 | ALM_COND_SENSORS_SWAP_F | Condenser Water Exchanger Temperature Sensors Swapped | Read | ||
| BV | 110099 | ALM_FLUIDE_FAIL | Possible Refrigerant Leakage Failure | Read | ||
| BV | 110210 | ALM_RUN_OUT_MAP_A_F | Compressor Running Outside MAP - cir A | Read | ||
| BV | 110211 | ALM_RUN_OUT_MAP_B_F | Compressor Running Outside MAP - cir B | Read | ||
| BV | 112001 | ALM_DP_A_F | Circuit A Discharge Pressure Transducer Failure | Read | ||
| BV | 112002 | ALM_DP_B_F | Circuit B Discharge Pressure Transducer Failure | Read | ||
| BV | 112004 | ALM_SP_A_F | Circuit A Suction Pressure Transducer Failure | Read | ||
| BV | 112005 | ALM_SP_B_F | Circuit B Suction Pressure Transducer Failure | Read | ||
| BV | 113001 | ALM_SERVICE_MAINT_ALERT | Service maintenance alert | Read | ||
| BV | 113005 | ALM_FGAS_NEEDED | Fgas check needed, call your maintenance company | Read | ||
| BV | 115001 | ALM_COOL_EWT_F | Water Exchanger Entering Fluid Thermistor Failure | Read | ||
| BV | 115002 | ALM_COOL_LWT_F | Water Exchanger Leaving Fluid Thermistor Failure | Read | ||
| BV | 115006 | ALM_COND_EWT_F | Condenser Entering Fluid Thermistor Failure | Read | ||
| BV | 115007 | ALM_COND_LWT_F | Condenser Leaving Fluid Thermistor Failure | Read | ||
| BV | 115010 | ALM_OAT_F | OAT Thermistor Failure | Read | ||
| BV | 115011 | ALM_DLWT_F | Primary/Secondary Common Fluid Thermistor Failure | Read | ||
| BV | 115012 | ALM_SUCTION_T_A_F | Circuit A Suction Gas Thermistor Failure | Read | ||
| BV | 115013 | ALM_SUCTION_T_B_F | Circuit B Suction Gas Thermistor Failure | Read | ||
| BV | 115015 | ALM_DGT_A_F | Circuit A Discharge Gas Thermistor Failure | Read | ||
| BV | 115021 | ALM_SPACETMP | Space Temperature Failure | Read | ||
| BV | 117001 | ALM_FAN_VFD_DRIVE_F | Circuit A VFD Fan Drive Failure | Read | ||
| BV | 157001 | ALM_CIOB_A_LOW_VOLT_F | Circuit A CIOB Low Voltage Failure | Read | ||
| BV | 157002 | ALM_CIOB_B_LOW_VOLT_F | Circuit B CIOB Low Voltage Failure | Read | ||
| BV | 157020 | ALM_EXV_A_F | Main EXV Stepper Motor Failure - Cir A | Read | ||
| BV | 157021 | ALM_EXV_B_F | Main EXV Stepper Motor Failure - Cir B | Read | ||
| MV | 64 | BACnet_COLOR | ALC Color Value | Read |
No points match these filters.
Object ID lookup: Carrier AquaSnap 30MP point IDs by name
AV1TEMP_EWTAV2TEMP_LWTAV3TEMP_OATAV5TEMP_DLWTAV6GENUNIT_CTRL_PNT_rdAV7GENUNIT_SPAV8GENUNIT_DEM_LIM_rdAV9GENUNIT_CAP_TAV11GENUNIT_min_leftAV20INPUTS_ICE_SWAV21GENUNIT_CTRL_TYPAV22GENUNIT_STATUSAV23GENUNIT_HC_SEL_rdAV24GENUNIT_SP_SEL_rdAV25TEMP_CEWTAV26TEMP_CLWTAV45INPUTS_HC_SWAV62BACnet_networkAV63BACnet_identAV65BACnet_PRIME_VAV66BACnet_BMS_OCCAV73PUMPCONF_pump_seqAV77GENUNIT_HEATCOOLAV900SETPOINT_csp1AV901SETPOINT_csp2AV903SETPOINT_hsp1AV904SETPOINT_hsp2AV905SETPOINT_lim_sp1AV906SETPOINT_lim_sp2AV907SETPOINT_lim_sp3AV960RUNTIME_hr_machAV961RUNTIME_st_machAV962RUNTIME_hr_pump1AV963RUNTIME_hr_pump2AV966HR_PARTIAL_DOWNTIMEAV967HR_TOTAL_DOWNTIMEAV980ALARMRST_alarm_1cAV981ALARMRST_alarm_2cAV982ALARMRST_alarm_3cAV983ALARMRST_alarm_4cAV984ALARMRST_alarm_5cAV985ALARMRST_alarm_1AV986ALARMRST_alarm_2AV987ALARMRST_alarm_3AV988ALARMRST_alarm_4AV989ALARMRST_alarm_5AV990ALARMRST_ALMAV1000PRESSURE_DP_AAV1001PRESSURE_SP_AAV1005TEMP_SCT_AAV1006TEMP_SST_AAV1007TEMP_SUCT_AAV1009TEMP_DGT_AAV1011LOADFACT_SH_AAV1015OUTPUTS_VFANAV1017GENUNIT_CAPA_TAV1960RUNTIME_hr_cp_a1AV1961RUNTIME_hr_cp_a2AV1962RUNTIME_hr_cp_a3AV1964RUNTIME_st_cp_a1AV1965RUNTIME_st_cp_a2AV1966RUNTIME_st_cp_a3AV2000PRESSURE_DP_BAV2001PRESSURE_SP_BAV2005TEMP_SCT_BAV2006TEMP_SST_BAV2007TEMP_SUCT_BAV2009TEMP_DGT_BAV2011LOADFACT_SH_BAV2017GENUNIT_CAPB_TAV2960RUNTIME_hr_cp_b1AV2961RUNTIME_hr_cp_b2AV2964RUNTIME_st_cp_b1AV2965RUNTIME_st_cp_b2AV5001PUMPCONF_pump_delAV5003GENCONF_lim_selAV5005INPUTS_SP_RESETAV5006INPUTS_leak_v1AV5007INPUTS_leak_v2AV5008INPUTS_DSHTR_SWAV5013FACTORY_unit_typAV5014FACTORY_unitsizeAV5015SETPOINT_ramp_spAV5016SETPOINT_cauto_spAV5017SETPOINT_hauto_spAV5019HCCONFIG_cr_selAV5020HCCONFIG_hr_selAV5023OUTPUTS_EXV_AAV5024OUTPUTS_EXV_BAV5027RESETCFG_oat_crnoAV5028RESETCFG_oat_crfuAV5029RESETCFG_dt_cr_noAV5030RESETCFG_dt_cr_fuAV5031RESETCFG_I_cr_noAV5032RESETCFG_I_cr_fuAV5033RESETCFG_spacr_noAV5034RESETCFG_spacr_fuAV5035RESETCFG_cr_degAV5036RESETCFG_oat_hrnoAV5037RESETCFG_oat_hrfuAV5038RESETCFG_dt_hr_noAV5039RESETCFG_dt_hr_fuAV5040RESETCFG_I_hr_noAV5041RESETCFG_I_hr_fuAV5042RESETCFG_spahr_noAV5043RESETCFG_spahr_fuAV5044RESETCFG_hr_degAV5064SETPOINT_min_sctAV5082TEMP_SPACETMPAV5106INPUTS_CSP_INAV5443FACTORY_flui_typAV5447SERVICE1_freezespAV5711OUTPUTS_BOILERAV5752OUTPUTS_HEAD_ACTAV5753OUTPUTS_HGBP_VAV5754OUTPUTS_DUSAV5757OUTPUTS_LLSV_BAV5758OUTPUTS_LLSV_AAV5759INPUTS_CWP1AV5760INPUTS_CWP2AV5761INPUTS_REV_ROTAV5762OUTPUTS_FANC_1AV5763OUTPUTS_FANC_2AV5764INPUTS_LIM_4_20AV5765OUTPUTS_EISORAV5766FACTORY2_cap_a1AV5767FACTORY2_cap_a2AV5768FACTORY2_cap_a3AV5769FACTORY2_cap_b1AV5771OUTPUTS_Mod_CPA1AV5772HEADCTRL_condspAV5773HEADCTRL_fanAV10006GENUNIT_CTRL_PNT_wrAV10008GENUNIT_DEM_LIM_wrAV10023GENUNIT_HC_SEL_wrAV10024GENUNIT_SP_SEL_wrAV110073ALM_COND_PUMP_FBV12GENUNIT_CHIL_S_S_rdBV13GENUNIT_EMSTOP_rdBV15OUTPUTS_RUNBV16INPUTS_ONOFF_SWBV18INPUTS_LIM_SW1BV19INPUTS_LIM_SW2BV48INPUTS_SETP_SWBV50PUMPSTAT_PUMP_1_rdBV51PUMPSTAT_PUMP_2_rdBV52INPUTS_FLOW_SWBV55INPUTS_CNFSBV57OUTPUTS_EXCH_HTRBV58GENUNIT_CHIL_OCC_rdBV59GENUNIT_SP_OCC_rdBV60BACnet_bacenaBV61BACnet_bacunitBV1032OUTPUTS_CP_A1BV1033OUTPUTS_CP_A2BV1034OUTPUTS_CP_A3BV2032OUTPUTS_CP_B1BV2033OUTPUTS_CP_B2BV5002PUMPCONF_pump_perBV5003PUMPCONF_pump_sbyBV5004PUMPCONF_pump_locBV5009INPUTS_HP_SW_ABV5011INPUTS_HP_SW_BBV5012OUTPUTS_ALARMBV5061OPT_SEL_boil_enBV5078GENCONF_ewt_optBV5301MODES_m_iceBV5756PUMPSTAT_CPUMPBV5770FACTORY_hgbp_selBV10012GENUNIT_CHIL_S_S_wrBV10013GENUNIT_EMSTOP_wrBV10050PUMPSTAT_PUMP_1_wrBV10051PUMPSTAT_PUMP_2_wrBV10053PROTOCOL_PUMP_CBV10058GENUNIT_CHIL_OCC_wrBV10059GENUNIT_SP_OCC_wrBV104701ALM_FAN_DRIVE_COM_FBV104901ALM_CIOB_CIR_A_COM_FBV104902ALM_CIOB_CIR_B_COM_FBV107001ALM_ILL_FACT_CONF_FBV108000ALM_INI_FACT_CONF_FBV109001ALM_M_S_CONFIG_FBV110001ALM_COOLER_FREEZE_FBV110005ALM_LOW_SUCTION_A_FBV110006ALM_LOW_SUCTION_B_FBV110011ALM_LOW_SH_A_FBV110012ALM_LOW_SH_B_FBV110014ALM_COOLER_LOCK_FBV110015ALM_CONDENSER_LOCK_FBV110016ALM_CPA1_REVERSE_ROT_FBV110017ALM_CPA2_REVERSE_ROT_FBV110018ALM_CPA3_REVERSE_ROT_FBV110020ALM_CPB1_REVERSE_ROT_FBV110021ALM_CPB2_REVERSE_ROT_FBV110029ALM_LOSS_COM_SM_FBV110030ALM_LOSS_COM_MS_FBV110031ALM_NETWORK_EMSTOP_FBV110032ALM_COOL_PUMP1_FBV110033ALM_COOL_PUMP2_FBV110037ALM_REPEATED_HI_DGT_A_FBV110038ALM_REPEATED_HI_DGT_B_FBV110040ALM_REPEATED_LO_SST_A_FBV110041ALM_REPEATED_LO_SST_B_FBV110063ALM_HP_SWITCH_A_FBV110064ALM_HP_SWITCH_B_FBV110097ALM_SENSORS_SWAP_FBV110098ALM_COND_SENSORS_SWAP_FBV110099ALM_FLUIDE_FAILBV110210ALM_RUN_OUT_MAP_A_FBV110211ALM_RUN_OUT_MAP_B_FBV112001ALM_DP_A_FBV112002ALM_DP_B_FBV112004ALM_SP_A_FBV112005ALM_SP_B_FBV113001ALM_SERVICE_MAINT_ALERTBV113005ALM_FGAS_NEEDEDBV115001ALM_COOL_EWT_FBV115002ALM_COOL_LWT_FBV115006ALM_COND_EWT_FBV115007ALM_COND_LWT_FBV115010ALM_OAT_FBV115011ALM_DLWT_FBV115012ALM_SUCTION_T_A_FBV115013ALM_SUCTION_T_B_FBV115015ALM_DGT_A_FBV115021ALM_SPACETMPBV117001ALM_FAN_VFD_DRIVE_FBV157001ALM_CIOB_A_LOW_VOLT_FBV157002ALM_CIOB_B_LOW_VOLT_FBV157020ALM_EXV_A_FBV157021ALM_EXV_B_FMV64BACnet_COLOR
Integration notes
- Command points have a read object (e.g. BV 12 GENUNIT_CHIL_S_S_rd) and a separate write object (BV 10012 GENUNIT_CHIL_S_S_wr).
- The table has no units column; temperatures follow the BACnet Metric Units setting (bacunit, default Yes).
- The table also lists a database alias name, low/high limits and COV increment, not reproduced here.
- The BACnet menu includes MS/TP settings, but the controller connection table lists the RS-485 port as unused and the appendix is titled BACnet IP points.
- Descriptions are as printed, including Carrier spellings such as "Soleniod".
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaSnap 30MP (PIC6 Carrier Controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaSnap 30MP (PIC6 Carrier Controller)
How many BACnet points does the Carrier AquaSnap 30MP (PIC6 Carrier Controller) have?
This list has 232 BACnet objects: 137 analog values, 94 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaSnap 30MP (PIC6 Carrier Controller) BACnet points are writable?
24 of the 232 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaSnap 30MP (PIC6 Carrier Controller) BACnet documentation?
The source is AquaSnap 30MPW017-080, 30MPA021-080, 30MPQ021-080 Liquid Chillers/Heat Pumps with Scroll Compressors and PIC6 Controls - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix C, BACnet IP Points) (30MP-8T), revision 6-25, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/01/30MP-8T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaSnap 30MP (PIC6 Carrier Controller)?
Start with BV 10012 GENUNIT_CHIL_S_S_wr (Network start/stop command); BV 10058 GENUNIT_CHIL_OCC_wr (Network occupied command); AV 10023 GENUNIT_HC_SEL_wr (Heat/cool select command); AV 10006 GENUNIT_CTRL_PNT_wr (Leaving water control point from the BMS); AV 10008 GENUNIT_DEM_LIM_wr (Demand limit command); AV 21 GENUNIT_CTRL_TYP (Control type: Local, Network or Remote); AV 22 GENUNIT_STATUS (Running status); AV 2 TEMP_LWT (Leaving water temperature); AV 9 GENUNIT_CAP_T (Percent total capacity); AV 990 ALARMRST_ALM (Unit alarm state).
How do I enable BMS control of the Carrier AquaSnap 30MP (PIC6 Carrier Controller)?
Select the Network machine control method with the Start/Stop button. The unit then follows CCN, BACnet (if enabled) or Modbus (if enabled) commands and ignores the remote control contacts. Start/stop and occupancy are written to the _wr objects.
Does the Carrier AquaSnap 30MP (PIC6 Carrier Controller) need a BACnet heartbeat or have a communication timeout?
The manual says that if communication with the network is lost while under network control, the machine starts and runs under local control.
How do I check these points on the real AquaSnap 30MP (PIC6 Carrier Controller)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points
Carrier AquaForce 30XV140-500 chillers with the Touch Pilot controller and the optional BACnet/Modbus Translator on BACnet MS/TP.
Also known as: 30XV, AquaForce 30XV, 30XV-2T, 30XV BACnet translator, BACnet/Modbus Translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points
Carrier AquaForce 30XV140-500 variable speed air-cooled screw chillers with the Touch Pilot display (original / Series A documentation, 2017).
Also known as: 30XV, AquaForce 30XV, 30XV-2T, 30XV Touch Pilot, 30XV Series A, Greenspeed 30XV - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the Carrier Controller as documented in the June 2019 manual (Form 30XV-3T).
Also known as: 30XV, AquaForce 30XV, 30XV-3T, 30XV Series B 2019, Carrier Controller, Greenspeed, 04-53300197-01 - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaSnap 30MPW017-080, 30MPA021-080, 30MPQ021-080 Liquid Chillers/Heat Pumps with Scroll Compressors and PIC6 Controls - Controls, Start-Up, Operation, Service, and Troubleshooting (Appendix C, BACnet IP Points) · 30MP-8T · rev. 6-25. Object names, instances and units are reproduced as published; descriptions are our own.