- Home
- BACnet points lists
- Carrier
- AquaEdge 23XRV (PIC6)
Water-cooled screw chiller controller · BACnet points list
Carrier AquaEdge 23XRV (PIC6) BACnet points list
Updated 28 October 2026
The PIC6 controller on the 23XRV talks BACnet MS/TP (port J8) or BACnet IP (Ethernet) natively, plus Modbus, with no translator. The object list is a flat set of AV, BV and MSV objects named <CCN table>_<point>, covering unit status, temperatures and pressures per circuit, capacity, VFD data, setpoints and service settings. Network start must be enabled on the controller before BMS commands are obeyed.
This page lists 591 BACnet objects for the Carrier AquaEdge 23XRV (PIC6) — 155 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- AquaEdge 23XRV (PIC6)
- Equipment
- Water-cooled screw chiller controller
- Equipment type
- Chillers
- BACnet objects
- 591 (155 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier AquaEdge 23XRV (PIC6)
Enable BACnet MS/TP or BACnet IP under System Configuration > BMS protocol, then enable Network start on the Configure Startup Options screen. In Network mode the chiller runs when both its start/stop and occupancy inputs are true; monitor unit status, leaving/entering water and alarms, and write the LCW setpoint.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 404 | SETPOINT_lcw_sp | Cooling leaving water setpoint (writable) | Write |
| AV 407 | SETPOINT_dem_base | Base demand limit from the BMS, % | Write |
| BV 136 | PROTOCOL_BAC_S_S | Start/stop command; listed read-only, test writes | Read |
| BV 133 | PROTOCOL_BACOCC | Occupancy command; listed read-only, test writes | Read |
| BV 134 | PROTOCOL_BACESTOP | Emergency stop; listed read-only, test writes | Read |
| MV 4 | GENUNIT_STATUS | Unit run status | Read |
| AV 41 | TEMP_LCW | Leaving chilled water temperature | Read |
| AV 40 | TEMP_ECW | Entering chilled water temperature | Read |
| AV 35 | GENUNIT_CTRL_PNT | Control point in use | Read |
| AV 410 | ALARMRST_SYS_ALM | System alert/alarm state | Read |
Enable & remote start
Network start for BACnet must be ticked on the Configure Startup Options screen (User login or higher). In Network mode the chiller starts only when CHIL_S_S and CHIL_OCC are both true; each enabled start source must send a stop to stop the chiller. BACnet emergency stop (PROTOCOL_BACESTOP) is one of the emergency-stop sources.
Network setup
- Port J8 is RS-485 for BACnet MS/TP or Modbus RTU; BACnet MS/TP and BACnet IP cannot both be enabled.
- Modbus RTU can run alongside BACnet IP, and BACnet MS/TP alongside Modbus TCP.
- Ethernet ports: J15 defaults to 169.254.1.1/16, J16 to 192.168.100.100/24; DHCP is not supported.
- For BACnet IP set the IP config and any BBMD, then select Reboot; for MS/TP set MAC, baud and keep Max Masters low.
Watch out for
- The points table marks the PROTOCOL_BAC* command objects read-only; confirm which objects accept writes on the live controller before mapping commands.
- Object names carry the CCN table prefix (e.g. TEMP_, SETPOINT_, GENUNIT_); several descriptions in the table are internal variable names.
Carrier AquaEdge 23XRV (PIC6) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 411 | ALARMRST_alarm_1 | Jbus Current Alarm 1 | Read | ||
| AV | 412 | ALARMRST_alarm_2 | Jbus Current Alarm 2 | Read | ||
| AV | 413 | ALARMRST_alarm_3 | Jbus Current Alarm 3 | Read | ||
| AV | 414 | ALARMRST_alarm_4 | Jbus Current Alarm 4 | Read | ||
| AV | 415 | ALARMRST_alarm_5 | Jbus Current Alarm 5 | Read | ||
| BV | 161 | ALARMRST_RST_ALM | Alarm Reset | Read | ||
| AVmin | 410 | ALARMRST_SYS_ALM | System Alert/Alarm | Read | ||
| AV | 313 | CAPDCTL_actstpt | Active Fluid Temp Setpt | Write | ||
| AV | 314 | CAPDCTL_ck1capmn | cirVarSpdCapLimMinArray | Write | ||
| AV | 315 | CAPDCTL_ck1capmx | cirVarSpdCapLimMaxArray | Write | ||
| AV | 316 | CAPDCTL_ck1caprq | Circ Cap Req Array | Write | ||
| AV | 317 | CAPDCTL_compldrq | Comp Load Required | Write | ||
| BV | 131 | CAPDCTL_dem_act | Demand Limit Active | Write | ||
| BV | 130 | CAPDCTL_ramp_act | Ramp Loading Active | Write | ||
| AV | 318 | CAPDCTL_scstptof | Short Cycle Setpt Offset | Write | ||
| AV | 319 | CAPDCTL_stptbst | Setpoint Boost | Write | ||
| AV | 320 | CAPDCTL_syscapmx | sysVarSpdCapLimMax | Write | ||
| AV | 321 | CAPDCTL_syscaprq | System Capacity Req | Write | ||
| AV | 322 | CAPECTL_act_ccap | System Actual Comp Cap | Write | ||
| AV | 323 | CAPECTL_act_fcap | sysActualFixSpdComprCap | Write | ||
| AV | 324 | CAPECTL_act_vcap | sysActualVarSpdComprCap | Write | ||
| AV | 325 | CAPECTL_avl_cap | System Avail Comp Cap | Write | ||
| AV | 326 | CAPECTL_avl_fcap | SysAvailFixSpdComprCap | Write | ||
| AV | 327 | CAPECTL_avl_vcap | SysAvailVarSpdComprCap | Write | ||
| AV | 328 | CAPECTL_cap | System Capacity | Write | ||
| AV | 329 | CAPECTL_cap_pct | System Capacity Percent | Write | ||
| AV | 330 | CAPECTL_run_fcap | sysRunFixSpdComprCap | Write | ||
| AV | 331 | CAPECTL_run_vcap | sysRunVarSpdComprCap | Write | ||
| AV | 332 | CIRCACTL_cap_tons | System Capacity Tons | Write | ||
| AV | 333 | CIRCACTL_circ_wrd | Circuit A Diag Word | Write | ||
| AV | 334 | CIRCACTL_ck1_acap | Circ A Avail Comp Cap | Write | ||
| AV | 335 | CIRCACTL_ck1_cap | Circuit A Capacity | Write | ||
| AV | 336 | CIRCACTL_ck1_capp | Circuit A Capacity Pct | Write | ||
| AV | 337 | CIRCACTL_ck1accap | Circ A Actual Comp Cap | Write | ||
| AV | 338 | CIRCACTL_ck1afcap | cirAAvailFixSpdComprCap | Write | ||
| AV | 339 | CIRCACTL_ck1afscp | cirAActualFixSpdComprCap | Write | ||
| AV | 340 | CIRCACTL_ck1avcap | cirAAvailVarSpdComprCap | Write | ||
| AV | 341 | CIRCACTL_ck1avscp | cirAActualVarSpdComprCap | Write | ||
| AV | 342 | CIRCACTL_ck1rfcap | cirARunFixSpdComprCap | Write | ||
| AV | 343 | CIRCACTL_ck1rvcap | cirARunVarSpdComprCap | Write | ||
| AV | 344 | CIRCACTL_cmpn_wrd | Compression A Diag Word | Write | ||
| AV | 345 | CIRCACTL_status | Circuit A Status | Write | ||
| BV | 132 | CIRCACTL_stdystat | Circ A Steady State Flag | Write | ||
| AV | 179 | CMPA1CTL_aDSTMn | CmpA AbsDischSatTMin | Read | ||
| AV | 180 | CMPA1CTL_aDSTMx | CmpA AbsDischSatTMax | Read | ||
| AV | 181 | CMPA1CTL_aSSTMn | CmpA AbsSuctSat TMin | Read | ||
| AV | 182 | CMPA1CTL_aSSTMx | CmpA AbsSuctSatTMax | Read | ||
| AV | 183 | CMPA1CTL_cAN | CmpA Act Nom Capacity | Read | ||
| AV | 184 | CMPA1CTL_cANp | CmpA Act Nom Cap Pct | Read | ||
| AV | 185 | CMPA1CTL_cASp | CmpA Act Scal Cap pct | Read | ||
| AV | 186 | CMPA1CTL_cMax | CmpA Capacity Max | Read | ||
| AV | 189 | CMPA1CTL_cmd | CmpA Command | Read | ||
| AV | 187 | CMPA1CTL_cMin | CmpA Capacity Min | Read | ||
| AV | 188 | CMPA1CTL_cObj | CmpA Current Obj | Read | ||
| AV | 190 | CMPA1CTL_dSTS | CmpA SatDischTempSetpt | Read | ||
| AV | 191 | CMPA1CTL_dTS | CmpA DischTempSetpt | Read | ||
| AV | 193 | CMPA1CTL_eDSTMn | CmpA EnvDischSatTMin | Read | ||
| AV | 194 | CMPA1CTL_eDSTMx | CmpA EnvDischSatTMax | Read | ||
| AV | 205 | CMPA1CTL_elubsp | CmpA Oil Guidance Setpt | Read | ||
| AV | 206 | CMPA1CTL_envwrd | CmpA Env Diag Word | Read | ||
| AV | 195 | CMPA1CTL_eSSTMn | CmpA EnvSuctSatTMin | Read | ||
| AV | 196 | CMPA1CTL_eSSTMx | CmpA EnvSuctSatTMax | Read | ||
| AV | 197 | CMPA1CTL_fTStp | CmpA Fluid Temp Setpt | Read | ||
| AV | 198 | CMPA1CTL_fWd | CmpA Fault Word | Read | ||
| BV | 89 | CMPA1CTL_isEnable | CmpA Enable | Read | ||
| BV | 90 | CMPA1CTL_isNom | CmpA Nominal | Read | ||
| BV | 91 | CMPA1CTL_isRd2Go | CmpA Ready to Start | Read | ||
| BV | 92 | CMPA1CTL_isRd2St | CmpA Ready to Stop | Read | ||
| BV | 93 | CMPA1CTL_isStart | CmpA Started | Read | ||
| BV | 94 | CMPA1CTL_isStop | CmpA Stopped | Read | ||
| AV | 199 | CMPA1CTL_iTS | CmpA Inverter Temp Setpt | Read | ||
| AV | 200 | CMPA1CTL_mTS | CmpA Motor Temp Setpt | Read | ||
| AV | 201 | CMPA1CTL_oVS | CmpA Oil Viscosity Setpt | Read | ||
| AV | 202 | CMPA1CTL_rTS | CmpA RectifierTemp Setpt | Read | ||
| BV | 95 | CMPA1CTL_shrt_cyc | CmpA Short Cycle Prevent | Read | ||
| AV | 203 | CMPA1CTL_sSTS | CmpA Sat Suct Temp Setpt | Read | ||
| AV | 204 | CMPA1CTL_stall_ct | CmpA Stall Count | Read | ||
| AV | 192 | CMPA1CTL_statwrd | CmpA State Diag Word | Read | ||
| BV | 96 | CMPA1CTL_vi_cmd | CmpA Vi Command | Read | ||
| AV | 209 | CMPA1CTL_vi_cObj | CmpA Vi Curr Objective | Read | ||
| AV | 210 | CMPA1CTL_vi_dword | CmpA Vi Diag Word | Read | ||
| AV | 207 | CMPA1CTL_vi_sp1 | CmpA Vi Stpt 1 | Read | ||
| AV | 208 | CMPA1CTL_vi_sp2 | CmpA Vi Stpt 2 | Read | ||
| BV | 123 | CPMPCTL_disc_cmd | Cond Pump Cmd | Read | ||
| AV | 290 | CPMPCTL_dWd | Diagnostic Word | Read | ||
| AV | 291 | CPMPCTL_fWd | Fault Word | Read | ||
| BV | 55 | CPMPCTL_has_flo | Flow Established | Read | ||
| BV | 124 | CPMPCTL_isEnable | Enable | Read | ||
| BV | 125 | CPMPCTL_isNom | Nominal | Read | ||
| BV | 126 | CPMPCTL_isRd2Go | Ready to Start | Read | ||
| BV | 127 | CPMPCTL_isRd2St | Ready to Stop | Read | ||
| BV | 128 | CPMPCTL_isStart | Started | Read | ||
| BV | 129 | CPMPCTL_isStop | Stopped | Read | ||
| AV | 38 | CTLSTATE_ice_bld | Ice Building | Read | ||
| AV | 396 | DRVA1CFG_curr_lim | Current Limit Percent | Write | ||
| AV | 393 | DRVA1CFG_min_spd | Compressor Unload Spd | Write | ||
| AV | 397 | DRVA1CFG_pwm_freq | PWM Switch Frequency | Write | ||
| AV | 403 | DRVA1CFG_ramp_dec | Decrease Ramp Time | Write | ||
| AV | 402 | DRVA1CFG_ramp_inc | Increase Ramp Time | Write | ||
| AV | 389 | DRVA1CFG_rla | Motor Nameplate Current | Write | ||
| AV | 387 | DRVA1CFG_rla_m | Motor Rated Load Amps | Write | ||
| AV | 392 | DRVA1CFG_rlhz | Compressor 100% Speed | Write | ||
| AV | 391 | DRVA1CFG_rlkw | Motor Nameplate KW | Write | ||
| AV | 390 | DRVA1CFG_rlrpm | Motor Nameplate RPM | Write | ||
| AV | 388 | DRVA1CFG_rlv | Motor Nameplate Voltage | Write | ||
| AV | 386 | DRVA1CFG_rlv_i | Rated Line Voltage | Write | ||
| AV | 401 | DRVA1CFG_skipband | Skip Frequency Band | Write | ||
| AV | 398 | DRVA1CFG_skipfrq1 | Skip Frequency 1 | Write | ||
| AV | 399 | DRVA1CFG_skipfrq2 | Skip Frequency 2 | Write | ||
| AV | 400 | DRVA1CFG_skipfrq3 | Skip Frequency 3 | Write | ||
| AV | 394 | DRVA1CFG_strt_spd | Compressor Start Spd | Write | ||
| AV | 395 | DRVA1CFG_torq_lim | Torque Limit Percent | Write | ||
| AV | 174 | DRVA1STS_ALM_WD1 | VFD Alarm Word1 | Read | ||
| AV | 175 | DRVA1STS_ALM_WD2 | VFD Alarm Word2 | Read | ||
| AV | 172 | DRVA1STS_ALT_WD1 | VFD Alert Word1 | Read | ||
| AV | 173 | DRVA1STS_ALT_WD2 | VFD Alert Word2 | Read | ||
| AV | 161 | DRVA1STS_AMPS_PCT | VFD Motor Curr Pct Rated | Read | ||
| AV | 159 | DRVA1STS_BUS_V | VFD Bus Voltage | Read | ||
| MV | 8 | DRVA1STS_COMS | VFD Coms Status | Read | ||
| AV | 166 | DRVA1STS_IGBT_T | VFD IGBT Temp | Read | ||
| AV | 165 | DRVA1STS_INV_T | VFD Inverter Temp | Read | ||
| AV | 169 | DRVA1STS_LAST_FLT | VFD Last Fault Code | Read | ||
| AV | 157 | DRVA1STS_LINE_CUR | VFD Average Line Current | Read | ||
| AV | 158 | DRVA1STS_LINE_KW | VFD Average Line KW | Read | ||
| AV | 156 | DRVA1STS_LINE_V | VFD Average Line Voltage | Read | ||
| AV | 160 | DRVA1STS_MOT_CUR | VFD Motor Current | Read | ||
| AV | 162 | DRVA1STS_MOT_KW | VFD Motor KW | Read | ||
| AV | 168 | DRVA1STS_MOT_RPM | VFD Motor Rpm | Read | ||
| AV | 163 | DRVA1STS_PCT | VFD Capacity | Read | ||
| AV | 167 | DRVA1STS_RECT_T | VFD Rectifier Temp | Read | ||
| AV | 164 | DRVA1STS_SPD | VFD Speed | Read | ||
| AV | 170 | DRVA1STS_STAT_WD1 | VFD Status Word1 | Read | ||
| AV | 171 | DRVA1STS_STAT_WD2 | VFD Status Word2 | Read | ||
| AV | 226 | ECOACTL_cObj | Current Objective | Read | ||
| AV | 227 | ECOACTL_dTStpt | Econ Disch Temp Setpoint | Read | ||
| AV | 228 | ECOACTL_dWd | Diag Word | Read | ||
| AV | 229 | ECOACTL_fWd | Fault Word | Read | ||
| BV | 104 | ECOACTL_isEnable | Enable | Read | ||
| BV | 105 | ECOACTL_isNom | Nominal | Read | ||
| BV | 106 | ECOACTL_isRd2Go | Ready to Start | Read | ||
| BV | 107 | ECOACTL_isRd2St | Ready to Stop | Read | ||
| BV | 108 | ECOACTL_isStart | Started | Read | ||
| BV | 109 | ECOACTL_isStop | Stopped | Read | ||
| AV | 230 | ECOACTL_shTStpt | Econ Superheat Setpoint | Read | ||
| AV | 139 | ENERGY_acgpm | Actual Cond GPM | Read | ||
| AV | 138 | ENERGY_aegpm | Actual Evap GPM | Read | ||
| AV | 377 | ENERGY_dcgpm | Design Cond GPM | Write | ||
| AV | 378 | ENERGY_dcpdft | Design Cond Press Drop | Write | ||
| AV | 379 | ENERGY_dcrt | Design Cond Refrig Temp | Write | ||
| AV | 375 | ENERGY_decwt | Design Ent Cond Temp | Write | ||
| AV | 372 | ENERGY_degpm | Design Evap GPM | Write | ||
| AV | 373 | ENERGY_depdft | Design Evap Press Drop | Write | ||
| AV | 374 | ENERGY_dert | Design Evap Refrig Temp | Write | ||
| AV | 370 | ENERGY_dewt | Design Ent Evap Temp | Write | ||
| AV | 368 | ENERGY_din_kw | Design Input kW | Write | ||
| AV | 369 | ENERGY_dkw_ton | Design Input kW/Ton | Write | ||
| AV | 376 | ENERGY_dlcwt | Design Lvg Cond Temp | Write | ||
| AV | 371 | ENERGY_dlwt | Design Lvg Evap Temp | Write | ||
| AV | 348 | EPMPCTL_disc_cmd | Evap Pump Cmd | Read | ||
| AV | 349 | EPMPCTL_dWd | Diagnostic Word | Read | ||
| AV | 350 | EPMPCTL_fWd | Fault Word | Read | ||
| AV | 137 | EPMPCTL_has_flo | Flow Established | Read | ||
| BV | 140 | EPMPCTL_isEnable | Enable | Read | ||
| BV | 141 | EPMPCTL_isNom | Nominal | Read | ||
| BV | 142 | EPMPCTL_isRd2Go | Ready to Start | Read | ||
| BV | 143 | EPMPCTL_isRd2St | Ready to Stop | Read | ||
| BV | 144 | EPMPCTL_isStart | Started | Read | ||
| BV | 145 | EPMPCTL_isStop | Stopped | Read | ||
| AV | 7 | EXVACFG_aTStpt | EXV Approach Setpoint | Write | ||
| AV | 6 | EXVACFG_cll_stpt | EXV Cond Liq Lvl Stpt | Write | ||
| AV | 9 | EXVACFG_lo_dshof | EXV Lo Disch Superh Ofst | Write | ||
| AV | 8 | EXVACFG_lo_dshsp | EXV Lo Disch Superh Stpt | Write | ||
| AV | 10 | EXVACFG_max_dist | EXV Max Disch Temp Stpt | Write | ||
| AV | 11 | EXVACFG_sbc_min | EXV Subcooling Min Stpt | Write | ||
| AV | 12 | EXVACFG_sbc_of | EXV Subcooling Min Ofst | Write | ||
| AV | 13 | EXVACFG_spsSTLeMO | EXV LowSatSuctOffset | Write | ||
| AV | 211 | EXVACTL_aTStpt | Approach Setpoint | Read | ||
| AV | 213 | EXVACTL_cll_stpt | Cond Liq Level Setpoint | Read | ||
| AV | 212 | EXVACTL_cObj | Current Objective | Read | ||
| AV | 214 | EXVACTL_dPHStpt | Hi Disch Sat Temp Stpt | Read | ||
| AV | 215 | EXVACTL_dWd | Diag Word | Read | ||
| AV | 223 | EXVACTL_ecliqlvl | Est Cond Liq Level | Read | ||
| AV | 225 | EXVACTL_estcflo | Est Cond Flow | Read | ||
| AV | 224 | EXVACTL_esteflo | Est Evap Flow | Read | ||
| BV | 103 | EXVACTL_estflag | Cond Lvl Est Flag | Read | ||
| AV | 216 | EXVACTL_fWd | Fault Word | Read | ||
| AV | 221 | EXVACTL_hi_dtsp | Disch Temp Hi Stpt | Read | ||
| BV | 97 | EXVACTL_isEnable | Enable | Read | ||
| BV | 98 | EXVACTL_isNom | Nominal | Read | ||
| BV | 99 | EXVACTL_isRd2Go | Ready to Start | Read | ||
| BV | 100 | EXVACTL_isRd2St | Ready to Stop | Read | ||
| BV | 101 | EXVACTL_isStart | Started | Read | ||
| BV | 102 | EXVACTL_isStop | Stopped | Read | ||
| AV | 217 | EXVACTL_lo_dshsp | Low Disch S/H Stpt | Read | ||
| AV | 222 | EXVACTL_lo_sbcsp | Subcool Low Stpt | Read | ||
| AV | 218 | EXVACTL_max_dist | Max Discharge Temp | Read | ||
| AV | 219 | EXVACTL_sPHStpt | suctSatTempHighStpt | Read | ||
| AV | 220 | EXVACTL_sPLStpt | suctSatTempLowStpt | Read | ||
| AV | 366 | FACTORY_aux_io | Auxilary IO Location | Write | ||
| MV | 11 | FACTORY_comp_typ | Compressor Type | Write | ||
| MV | 15 | FACTORY_econ_opt | Economizer Option | Write | ||
| MV | 14 | FACTORY_exv_opt | EXV Control Type | Write | ||
| BV | 159 | FACTORY_hgbp_opt | HGBP Control Option | Write | ||
| AV | 367 | FACTORY_oilassy | Oil Assembly Option | Write | ||
| MV | 12 | FACTORY_refrig | Refrigerant Type | Write | ||
| AV | 365 | FACTORY_tons | Chiller Tons | Write | ||
| MV | 13 | FACTORY_vfd_opt | VFD Option | Write | ||
| AV | 4 | GENCONF_caplim_a | Circuit A Capacity Limit | Write | ||
| AV | 5 | GENCONF_caplim_b | Circuit B Capacity Limit | Write | ||
| MV | 3 | GENCONF_dem_sel | Demand Limit Source | Write | ||
| BV | 2 | GENCONF_ice_rec | Ice Mode Recycle | Write | ||
| MV | 2 | GENCONF_lead_ck | Lead Circuit Selection | Write | ||
| BV | 3 | GENCONF_leak_en | Refrigerant Leak Option | Write | ||
| BV | 1 | GENCONF_ramp_en | Enable Ramp Loading | Write | ||
| MV | 1 | GENCONF_rampsel | Ramp Loading Type | Write | ||
| AV | 2 | GENCONF_rrate_a | Ramp Rate (per Min) | Write | ||
| AV | 3 | GENCONF_rrate_k | Ramp Rate (per Min) | Write | ||
| AV | 1 | GENCONF_rrate_t | Ramp Rate (per Min) | Write | ||
| BV | 4 | GENUNIT_BAC_OCC | BACnet Occupied | Read | ||
| BV | 6 | GENUNIT_CHIL_S_S | Cmd Start/Stop | Read | ||
| AVmin | 35 | GENUNIT_CTRL_PNT | Control Point | Read | ||
| AV | 36 | GENUNIT_DEM_LIM | Active Demand Limit | Read | ||
| BV | 7 | GENUNIT_EMSTOP | Emergency Stop | Read | ||
| BV | 9 | GENUNIT_ICE_OCC | Ice Build Occupied | Read | ||
| AV | 37 | GENUNIT_LAG_LIM | Lag Demand Limit | Read | ||
| BV | 5 | GENUNIT_LCL_S_S | HMI Start/Stop Cmd | Read | ||
| BV | 8 | GENUNIT_LOC_OCC | Local Sched Occupied | Read | ||
| AV | 33 | GENUNIT_min_left | Time Until Start | Read | ||
| AV | 34 | GENUNIT_min_run | Minimum Runtime Timer | Read | ||
| MV | 5 | GENUNIT_ONOFFSVC | Unit Mode | Read | ||
| BV | 10 | GENUNIT_ramp_act | Ramp Loading Active | Read | ||
| AV | 39 | GENUNIT_ramprate | Ramp Rate (per Min) | Read | ||
| MV | 7 | GENUNIT_rpdrstst | Swift Restart State | Read | ||
| MVmin | 4 | GENUNIT_STATUS | Unit Status | Read | ||
| MV | 6 | GENUNIT_SYS_STAT | System State | Read | ||
| AV | 233 | HGBPACTL_cmd | HGBPA Command | Read | ||
| AV | 231 | HGBPACTL_cObj | HGBPA Current Obj | Read | ||
| AV | 235 | HGBPACTL_cSS | HGBPA Comp Spd Stpt | Read | ||
| BV | 110 | HGBPACTL_do_cmd | HGBPA Disc Out Cmd | Read | ||
| AV | 237 | HGBPACTL_dWd | HGBPA Diag Word | Read | ||
| AV | 234 | HGBPACTL_fTS | HGBPA Fluid T Stpt | Read | ||
| AV | 238 | HGBPACTL_fWd | HGBPA Fault Word | Read | ||
| AV | 232 | HGBPACTL_hgbpa_pt | HGBPA Process Temp | Read | ||
| BV | 111 | HGBPACTL_isEnable | HGBPA Enable | Read | ||
| BV | 112 | HGBPACTL_isNom | HGBPA Nominal | Read | ||
| BV | 113 | HGBPACTL_isRd2Go | HGBPA Ready to Start | Read | ||
| BV | 114 | HGBPACTL_isRd2St | HGBPA Ready to Stop | Read | ||
| BV | 115 | HGBPACTL_isStart | HGBPA Started | Read | ||
| BV | 116 | HGBPACTL_isStop | HGBPA Stopped | Read | ||
| AV | 236 | HGBPACTL_svPS | HGBPA SV Pos Stpt | Read | ||
| AV | 385 | HYDRCFG_cflo_vt | Cond Flow Verify time | Write | ||
| AV | 383 | HYDRCFG_condfdtp | Cond Flow Detection Type | Write | ||
| AV | 384 | HYDRCFG_condfldp | Cond Min Flow dP | Write | ||
| AV | 382 | HYDRCFG_eflo_vt | Evap Flow Verify time | Write | ||
| AV | 380 | HYDRCFG_evapfdtp | Evap Flow Detection Type | Write | ||
| AV | 381 | HYDRCFG_evapfldp | Evap Min Flow dP | Write | ||
| AV | 127 | INPUTS_AUTO_DEM | Auto Demand Limit Input | Read | ||
| AV | 128 | INPUTS_AUTO_RES | Auto Water Temp Reset | Read | ||
| AV | 133 | INPUTS_CNDLVL_A | Cond Liq Lev A | Read | ||
| AV | 136 | INPUTS_CNDLVL_B | Cond Liq Lev B | Read | ||
| BV | 49 | INPUTS_COND_FSW | Condenser Flow Switch | Read | ||
| BV | 42 | INPUTS_E_STOP | Emergency Stop Contact | Read | ||
| AV | 131 | INPUTS_ECOA_FBK | Econ A EXV Feedback | Read | ||
| AV | 135 | INPUTS_ECOB_FBK | Econ B EXV Feedback | Read | ||
| BV | 50 | INPUTS_EVAP_FSW | Evaporator Flow Switch | Read | ||
| AV | 130 | INPUTS_EXVA_FBK | Main EXV A Feedback | Read | ||
| AV | 134 | INPUTS_EXVB_FBK | Main EXV B Feedback | Read | ||
| BV | 43 | INPUTS_FS_LOCK | Fire Security Interlock | Read | ||
| BV | 52 | INPUTS_HPS_A | High Pressure Switch A | Read | ||
| BV | 54 | INPUTS_HPS_B | High Pressure Switch B | Read | ||
| BV | 44 | INPUTS_ICE_CON | Ice Build Contact | Read | ||
| BV | 45 | INPUTS_ICE_SW | Ice Done Storage Switch | Read | ||
| BV | 51 | INPUTS_OIL_L_A | Oil Level Input A | Read | ||
| BV | 53 | INPUTS_OIL_L_B | Oil Level Input B | Read | ||
| AV | 129 | INPUTS_REF_LEAK | Refrig Leakage Sensor | Read | ||
| BV | 46 | INPUTS_REM_CON | Remote Start/Stop | Read | ||
| BV | 47 | INPUTS_REM_LOCK | Remote Lockout | Read | ||
| BV | 48 | INPUTS_SAFETY | Spare Safety Input | Read | ||
| AV | 132 | INPUTS_SVA_FBK | Slide Valve A Feedback | Read | ||
| AV | 29 | LIMITCFG_ap_dgap | Design Evap Appr | Write | ||
| AV | 27 | LIMITCFG_cdp_alrt | Cond Press Alert | Write | ||
| AV | 25 | LIMITCFG_cond_al | Cond Approach Alert | Write | ||
| AV | 26 | LIMITCFG_dgt_alrt | Comp Discharge Alert | Write | ||
| AV | 24 | LIMITCFG_evap_al | Evap Approach Alert | Write | ||
| AV | 32 | LIMITCFG_PpmLim | Refrig Leak Alarm PPM | Write | ||
| AV | 28 | LIMITCFG_rch_cath | Refr Charge Cond Alert | Write | ||
| AV | 31 | LIMITCFG_RefPpm20 | Ref Leak PPM at 20 mA | Write | ||
| AV | 30 | LIMITCFG_vfdsptad | VFD Speed Alrt Dband | Write | ||
| AV | 21 | LUBECFG_hgbpoff | Turn Off HGBP | Write | ||
| AV | 20 | LUBECFG_hgbpon | Turn On HGBP | Write | ||
| AV | 23 | LUBECFG_minhz | Minimum Hz | Write | ||
| AV | 22 | LUBECFG_minlift | Minimum Lift | Write | ||
| AV | 17 | LUBECFG_smp1off | Sump1 Heater Off | Write | ||
| AV | 16 | LUBECFG_smp1on | Sump1 Heater On | Write | ||
| AV | 19 | LUBECFG_smp2off | Sump2 Heater Off | Write | ||
| AV | 18 | LUBECFG_smp2on | Sump2 Heater On | Write | ||
| AV | 15 | LUBECFG_vphtoff | Vaporizer Heater Off | Write | ||
| AV | 14 | LUBECFG_vphton | Vaporizer Heater On | Write | ||
| AV | 264 | OILHCTL_fWd | Fault Word | Read | ||
| AV | 265 | OILHCTL_isEnable | Enable | Read | ||
| AV | 266 | OILHCTL_isNom | Nominal | Read | ||
| AV | 267 | OILHCTL_isRd2Go | Ready to Start | Read | ||
| AV | 268 | OILHCTL_isRd2St | Ready to Stop | Read | ||
| AV | 269 | OILHCTL_isStart | Started | Read | ||
| AV | 270 | OILHCTL_isStop | Stopped | Read | ||
| AV | 271 | OILPCTL_fWd | Fault Word | Read | ||
| AV | 272 | OILPCTL_isEnable | Enable | Read | ||
| AV | 273 | OILPCTL_isNom | Nominal | Read | ||
| AV | 274 | OILPCTL_isRd2Go | Ready to Start | Read | ||
| AV | 275 | OILPCTL_isRd2St | Ready to Stop | Read | ||
| AV | 276 | OILPCTL_isStart | Started | Read | ||
| AV | 277 | OILPCTL_isStop | Stopped | Read | ||
| AV | 278 | OILRCTL_isEnable | Enable | Read | ||
| AV | 279 | OILRCTL_isNom | Nominal | Read | ||
| AV | 280 | OILRCTL_isRd2Go | Ready to Start | Read | ||
| AV | 281 | OILRCTL_isRd2St | Ready to Stop | Read | ||
| AV | 282 | OILRCTL_isStart | Started | Read | ||
| AV | 283 | OILRCTL_isStop | Stopped | Read | ||
| AV | 346 | OILVCTL_oil_visc | Oil Viscosity | Read | ||
| BV | 11 | OUTPUTS_ALE | Alert Relay | Read | ||
| BV | 12 | OUTPUTS_ALM | Alarm Relay | Read | ||
| BV | 26 | OUTPUTS_BP_ECO_A | Econ Bypass Solenoid A | Read | ||
| BV | 40 | OUTPUTS_BP_ECO_B | Econ Bypass Solenoid B | Read | ||
| AV | 120 | OUTPUTS_CAPOUT_A | Analog Capacity Output A | Read | ||
| AV | 124 | OUTPUTS_CAPOUT_B | Analog Capacity Output B | Read | ||
| AV | 116 | OUTPUTS_CAPT | Capacity Output Total | Read | ||
| BV | 16 | OUTPUTS_CDWP1 | Cond Water Pump | Read | ||
| AV | 117 | OUTPUTS_CHST_OUT | Unit Status Output | Read | ||
| BV | 17 | OUTPUTS_CHWP1 | Chill Water Pump | Read | ||
| BV | 27 | OUTPUTS_CP_A_LOCK | Comp A VFD Interlock | Read | ||
| BV | 41 | OUTPUTS_CP_B_LOCK | Comp B VFD Interlock | Read | ||
| AV | 121 | OUTPUTS_ECOEXV_A | Economizer EXV A | Read | ||
| AV | 125 | OUTPUTS_ECOEXV_B | Economizer EXV B | Read | ||
| AV | 122 | OUTPUTS_EXV_A | Main EXV A | Read | ||
| AV | 126 | OUTPUTS_EXV_B | Main EXV B | Read | ||
| AV | 118 | OUTPUTS_HDPV_OUT | Head Pres Output | Read | ||
| BV | 20 | OUTPUTS_HGBP_A | HGBP Soleniod A | Read | ||
| BV | 34 | OUTPUTS_HGBP_B | HGBP Soleniod B | Read | ||
| BV | 22 | OUTPUTS_MTR_CL_A | Motor Cooling Solenoid A | Read | ||
| BV | 36 | OUTPUTS_MTR_CL_B | Motor Cooling Solenoid B | Read | ||
| BV | 23 | OUTPUTS_OIL_DL_A | Dual Oil Flow Solenoid A | Read | ||
| BV | 37 | OUTPUTS_OIL_DL_B | Dual Oil Flow Solenoid B | Read | ||
| AV | 123 | OUTPUTS_OIL_RECL | Oil Reclaim Valve | Read | ||
| BV | 31 | OUTPUTS_OILHEAT1 | Oil Heater - Primary | Read | ||
| BV | 32 | OUTPUTS_OILHEAT2 | Oil Heater - Secondary | Read | ||
| BV | 33 | OUTPUTS_OILR | Oil Pump Relay | Read | ||
| BV | 21 | OUTPUTS_OILSOL_A | Oil Solenoid A | Read | ||
| BV | 35 | OUTPUTS_OILSOL_B | Oil Solenoid B | Read | ||
| BV | 13 | OUTPUTS_RUN | Running Relay | Read | ||
| BV | 14 | OUTPUTS_SET_FLOW | Cooler Flow SP Out | Read | ||
| BV | 15 | OUTPUTS_SHTDN | Shutdown Relay | Read | ||
| BV | 28 | OUTPUTS_SLV_LD_A | Slide Valve Load A | Read | ||
| BV | 29 | OUTPUTS_SLV_UL_A | Slide Valve Unload A | Read | ||
| BV | 18 | OUTPUTS_TFR_HIGH | Tower Fan Relay High | Read | ||
| BV | 19 | OUTPUTS_TFR_LOW | Tower Fan Relay Low | Read | ||
| AV | 119 | OUTPUTS_TOW_FAN | VFD Tower Fan | Read | ||
| BV | 30 | OUTPUTS_VAP_HEAT | Vaporizer Heater | Read | ||
| BV | 24 | OUTPUTS_VFDSOL_A | VFD Coolant Solenoid A | Read | ||
| BV | 38 | OUTPUTS_VFDSOL_B | VFD Coolant Solenoid B | Read | ||
| BV | 25 | OUTPUTS_VI_CMP_A | VI Piston Solenoid A | Read | ||
| BV | 39 | OUTPUTS_VI_CMP_B | VI Piston Solenoid B | Read | ||
| BV | 146 | PLTSPRT_rs485_u1_tres | LEN Port J6 Term Res | Write | ||
| BV | 147 | PLTSPRT_rs485_u3_tres | CCN Port J7 Term Res | Write | ||
| BV | 148 | PLTSPRT_rs485_u4_tres | Mod Master J10 Term Res | Write | ||
| BV | 149 | PLTSPRT_rs485_u5_tres | BMS Port J8 Term Res | Write | ||
| AV | 97 | PRESSURE_CND_P_A | Condenser Pressure A | Read | ||
| AV | 108 | PRESSURE_CND_P_B | Condenser Pressure B | Read | ||
| AV | 91 | PRESSURE_COND_EWP | Entering Cond Water Pres | Read | ||
| AV | 92 | PRESSURE_COND_LWP | Leaving Cond Water Pres | Read | ||
| AV | 93 | PRESSURE_COND_WDP | Cond Water Delta P | Read | ||
| AV | 96 | PRESSURE_DIS_P_A | Discharge Pressure A | Read | ||
| AV | 107 | PRESSURE_DIS_P_B | Discharge Pressure B | Read | ||
| AV | 98 | PRESSURE_ECO_P_A | Economizer Pressure A | Read | ||
| AV | 109 | PRESSURE_ECO_P_B | Economizer Pressure B | Read | ||
| AV | 88 | PRESSURE_EVAP_EWP | Entering Evap Water Pres | Read | ||
| AV | 89 | PRESSURE_EVAP_LWP | Leaving Evap Water Pres | Read | ||
| AV | 94 | PRESSURE_EVAP_P_A | Evaporator Pressure A | Read | ||
| AV | 105 | PRESSURE_EVAP_P_B | Evaporator Pressure B | Read | ||
| AV | 90 | PRESSURE_EVAP_WDP | Evap Water Delta P | Read | ||
| AV | 103 | PRESSURE_LIQ_P_A | Liquid Line Press A | Read | ||
| AV | 114 | PRESSURE_LIQ_P_B | Liquid Line Press B | Read | ||
| AV | 104 | PRESSURE_MTR_P_A | Motor Injection Press A | Read | ||
| AV | 115 | PRESSURE_MTR_P_B | Motor Injection Press B | Read | ||
| AV | 100 | PRESSURE_OIL_DP_A | Oil Discharge Pressure A | Read | ||
| AV | 111 | PRESSURE_OIL_DP_B | Oil Discharge Pressure B | Read | ||
| AV | 101 | PRESSURE_OIL_PD_A | Oil Press Diff A | Read | ||
| AV | 112 | PRESSURE_OIL_PD_B | Oil Press Diff B | Read | ||
| AV | 102 | PRESSURE_OILPA1RQ | Oil Pressure Required A | Read | ||
| AV | 113 | PRESSURE_OILPB1RQ | Oil Pressure Required B | Read | ||
| AV | 99 | PRESSURE_OILPSMPA | Oil Sump Pressure A | Read | ||
| AV | 110 | PRESSURE_OILPSMPB | Oil Sump Pressure B | Read | ||
| AV | 95 | PRESSURE_SUCT_P_A | Suction Pressure A | Read | ||
| AV | 106 | PRESSURE_SUCT_P_B | Suction Pressure B | Read | ||
| BVmin | 136 | PROTOCOL_BAC_S_S | BACNET Start/Stop | Read | ||
| BV | 138 | PROTOCOL_BACALARM | BACNET Alarm Flag | Read | ||
| BV | 139 | PROTOCOL_BACALERT | BACNET Alert Flag | Read | ||
| AV | 347 | PROTOCOL_BACDEML | BACNET Demand Limit | Read | ||
| BVmin | 134 | PROTOCOL_BACESTOP | BACNET Estop | Read | ||
| BV | 137 | PROTOCOL_BACLKOUT | BACNET Lockout | Read | ||
| BVmin | 133 | PROTOCOL_BACOCC | BACNET Occupy | Read | ||
| BV | 135 | PROTOCOL_BACSFTY | BACNET Fire Safety | Read | ||
| AV | 307 | RUNTIME_hr_comp_a | Compressor A Hours | Read | ||
| AV | 308 | RUNTIME_hr_comp_b | Compressor B Hours | Read | ||
| AV | 312 | RUNTIME_hr_cpmp1 | Cond Pump 1 Hours | Read | ||
| AV | 311 | RUNTIME_hr_epmp1 | Evap Pump 1 Hours | Read | ||
| AV | 306 | RUNTIME_hr_mach | Machine Operating Hours | Read | ||
| AV | 309 | RUNTIME_hr_oilpa | Oil Pump A Hours | Read | ||
| AV | 310 | RUNTIME_hr_oilpb | Oil Pump B Hours | Read | ||
| AV | 305 | RUNTIME_hr_svc | Service Runtime | Read | ||
| AV | 298 | RUNTIME_rcycst_a | CompA Recy Strts in 4 Hr | Read | ||
| AV | 299 | RUNTIME_rcycst_b | CompB Recy Strts in 4 Hr | Read | ||
| AV | 303 | RUNTIME_spst_a | Comp A Stop to Start | Read | ||
| AV | 304 | RUNTIME_spst_b | Comp B Stop to Start | Read | ||
| AV | 294 | RUNTIME_st_oilpa | Oil Pump A Starts | Read | ||
| AV | 295 | RUNTIME_st_oilpb | Oil Pump B Starts | Read | ||
| AV | 296 | RUNTIME_st12_a | CompA Starts in 12 Hrs | Read | ||
| AV | 297 | RUNTIME_st12_b | CompB Starts in 12 Hrs | Read | ||
| AV | 292 | RUNTIME_str_comp_a | Compressor A Starts | Read | ||
| AV | 293 | RUNTIME_str_comp_b | Compressor B Starts | Read | ||
| AV | 301 | RUNTIME_stst_a | Comp A Start to Start | Read | ||
| AV | 302 | RUNTIME_stst_b | Comp B Start to Start | Read | ||
| AV | 300 | RUNTIME_swiftcnt | Swift Restarts in 1 Hr | Read | ||
| BV | 155 | SERVICE1_CirA_En | Enable Circuit A | Write | ||
| BV | 156 | SERVICE1_CirB_En | Enable Circuit B | Write | ||
| AV | 359 | SERVICE1_cmpstper_A | Comp Start Period | Write | ||
| AV | 361 | SERVICE1_cmpstper_B | Comp Start Period | Write | ||
| AV | 353 | SERVICE1_dem_20ma | Demand Limit At 20 mA | Write | ||
| BV | 150 | SERVICE1_emstopen | Emergency Stop Enable | Write | ||
| MV | 9 | SERVICE1_flui_typ | Evaporator Fluid Type | Write | ||
| AV | 351 | SERVICE1_freezesp | Brine Freeze Setpoint | Write | ||
| BV | 151 | SERVICE1_lockout | Service Lockout | Write | ||
| AV | 355 | SERVICE1_max_lwt | Maximum Fluid Temp | Write | ||
| AV | 354 | SERVICE1_min_lwt | Minimum Fluid Temp | Write | ||
| AV | 352 | SERVICE1_min_off | Comp Min Off Time | Write | ||
| BV | 153 | SERVICE1_oilsw_by_A | Oil Switch Bypass A | Write | ||
| BV | 154 | SERVICE1_oilsw_by_B | Oil Switch Bypass B | Write | ||
| AV | 364 | SERVICE1_pwautlim | Powerloss Autoreset Lim | Write | ||
| AV | 356 | SERVICE1_rspdmaxA | Comp Speed Max A | Write | ||
| AV | 357 | SERVICE1_rspdmaxB | Comp Speed Max B | Write | ||
| BV | 157 | SERVICE1_rsthrsvc | Reset Service Runtime | Write | ||
| MV | 10 | SERVICE1_rstrtopt | Restart Options | Write | ||
| BV | 158 | SERVICE1_sftst_en | Soft Stop Enable | Write | ||
| AV | 362 | SERVICE1_sftst_th | Soft Stop Threshold | Write | ||
| AV | 363 | SERVICE1_spstopen | Spare Safety Enable | Write | ||
| BV | 152 | SERVICE1_stlim_by | Starts Limit Bypass | Write | ||
| AV | 358 | SERVICE1_stpperlim_A | Starts Per Period Lim | Write | ||
| AV | 360 | SERVICE1_stpperlim_B | Starts Per Period Lim | Write | ||
| AVmin | 407 | SETPOINT_dem_base | Base Demand Limit | Write | ||
| AV | 406 | SETPOINT_ecw_sp | Cooling ECW Setpoint | Write | ||
| BV | 160 | SETPOINT_EWT_OPT | EWT Control Option | Write | ||
| AV | 405 | SETPOINT_ice_sp | Ice Build Setpoint | Write | ||
| AVmin | 404 | SETPOINT_lcw_sp | Cooling LCW Setpoint | Write | ||
| AV | 409 | SETPOINT_rcyc_hi | Recycle Startup Offset | Write | ||
| AV | 408 | SETPOINT_rcyc_lo | Recycle Shutdown Offset | Write | ||
| AV | 247 | SLVA1CTL_cAN | SVA Act Nom Capacity | Read | ||
| AV | 248 | SLVA1CTL_cANp | SVA Actual Nom Cap Pct | Read | ||
| AV | 249 | SLVA1CTL_cASp | SVA Actual Scal Cap Pct | Read | ||
| AV | 250 | SLVA1CTL_cMax | SVA Capacity Max | Read | ||
| AV | 239 | SLVA1CTL_cmd | SVA Command | Read | ||
| AV | 251 | SLVA1CTL_cMin | SVA Capacity Min | Read | ||
| AV | 252 | SLVA1CTL_cObj | SVA Current Objective | Read | ||
| AV | 240 | SLVA1CTL_dstcmd | Hi Disch Sat Temp PI | Read | ||
| AV | 253 | SLVA1CTL_dSTS | SVA SatDischTempSetpt | Read | ||
| AV | 241 | SLVA1CTL_dtcmd | Hi Disch Temp PI | Read | ||
| AV | 254 | SLVA1CTL_dTS | SVA Disch Temp Setpt | Read | ||
| AV | 256 | SLVA1CTL_dty_cyc | SVA Duty Cycle | Read | ||
| AV | 255 | SLVA1CTL_dWd | SVA Diag Word | Read | ||
| AV | 242 | SLVA1CTL_ftcmd | Fluid Temp PI | Read | ||
| AV | 257 | SLVA1CTL_fTStp | SVA Fluid Temp Setpt | Read | ||
| AV | 258 | SLVA1CTL_fWd | SVA Fault Word | Read | ||
| BV | 117 | SLVA1CTL_isEnable | SVA Enable | Read | ||
| BV | 118 | SLVA1CTL_isNom | SVA Nominal | Read | ||
| BV | 119 | SLVA1CTL_isRd2Go | SVA Ready to Start | Read | ||
| BV | 120 | SLVA1CTL_isRd2St | SVA Ready to Stop | Read | ||
| BV | 121 | SLVA1CTL_isStart | SVA Started | Read | ||
| BV | 122 | SLVA1CTL_isStop | SVA Stopped | Read | ||
| AV | 259 | SLVA1CTL_iTS | SVA Inverter Temp Setpt | Read | ||
| AV | 260 | SLVA1CTL_mCS | SVA Motor Current Setpt | Read | ||
| AV | 243 | SLVA1CTL_mcurcmd | Motor Curr PI | Read | ||
| AV | 244 | SLVA1CTL_mtmpmd | Motor Temp PI | Read | ||
| AV | 261 | SLVA1CTL_mTS | SVA Motor Temp Setpt | Read | ||
| AV | 245 | SLVA1CTL_oilrecmd | Oil Recovery PI | Read | ||
| AV | 262 | SLVA1CTL_oVS | SVA Oil Viscosity Setpt | Read | ||
| AV | 246 | SLVA1CTL_sstcmd | Lo Sat Evap Temp PI | Read | ||
| AV | 263 | SLVA1CTL_sSTS | SVA Sat Suct Temp Setpt | Read | ||
| AV | 176 | STGECTL_cmp1cknb | Cmp 1 Circ Num | Read | ||
| BV | 83 | STGECTL_cmp1hgbp | Cmp 1 HGBP | Read | ||
| BV | 84 | STGECTL_cmp1ldrq | Cmp1 Load Required | Read | ||
| BV | 85 | STGECTL_comp_ld | Cmp Load | Read | ||
| BV | 86 | STGECTL_comp_ul | Cmp Unload | Read | ||
| BV | 87 | STGECTL_ld_alwd | Loading Allowed | Read | ||
| AV | 177 | STGECTL_leadck | Lead Circ Num | Read | ||
| AV | 178 | STGECTL_stat_wrd | Stage Status Word | Read | ||
| BV | 88 | STGECTL_ul_alwd | Unloading Allowed | Read | ||
| BV | 76 | STRTSTS_accelflt | Starter Accel Fault | Read | ||
| BV | 62 | STRTSTS_amp_unb | Current Imbalance | Read | ||
| AV | 147 | STRTSTS_AMPS_AVG | Average Line Current | Read | ||
| AV | 144 | STRTSTS_AMPS_H1 | Line Current Phase 1 | Read | ||
| AV | 145 | STRTSTS_AMPS_H2 | Line Current Phase 2 | Read | ||
| AV | 146 | STRTSTS_AMPS_H3 | Line Current Phase 3 | Read | ||
| BV | 79 | STRTSTS_ampstop | Motor Amps When Stopped | Read | ||
| BV | 81 | STRTSTS_calfc_er | Calibration Factor Error | Read | ||
| BV | 82 | STRTSTS_conf_err | Invalid Configuration | Read | ||
| BV | 58 | STRTSTS_cycle_1 | Single Cycle Dropout | Read | ||
| AV | 148 | STRTSTS_FREQ_H | Line Frequency | Read | ||
| BV | 69 | STRTSTS_freqflt | Frequency Out of Range | Read | ||
| AV | 149 | STRTSTS_GRFT_H1 | Ground Fault Phase 3 | Read | ||
| AV | 150 | STRTSTS_GRFT_H2 | Ground Fault Phase 2 | Read | ||
| AV | 151 | STRTSTS_GRFT_H3 | Ground Fault Phase 1 | Read | ||
| BV | 67 | STRTSTS_grnd_flt | Ground Fault | Read | ||
| BV | 80 | STRTSTS_hardware | Hardware Failure | Read | ||
| BV | 77 | STRTSTS_highamps | Excessive Motor Amps | Read | ||
| BV | 70 | STRTSTS_ism_por | ISM Power On Reset | Read | ||
| AV | 155 | STRTSTS_KW | Motor KW | Read | ||
| BV | 65 | STRTSTS_lratrip | Locked Rotor Trip | Read | ||
| BV | 71 | STRTSTS_m1_flt | 1M Start/Run Fault | Read | ||
| BV | 78 | STRTSTS_m1m2stop | 1M/2M Stop Fault | Read | ||
| BV | 72 | STRTSTS_m2_flt | 2M Start/Run Fault | Read | ||
| BV | 75 | STRTSTS_no_amps | Motor Amps Not Sensed | Read | ||
| BV | 60 | STRTSTS_ov_volt | Over Voltage | Read | ||
| BV | 64 | STRTSTS_overload | Overload Trip | Read | ||
| BV | 59 | STRTSTS_ph_loss | Phase Loss | Read | ||
| BV | 68 | STRTSTS_ph_rev | Phase Reversal | Read | ||
| BV | 73 | STRTSTS_prs_trip | Pressure Trip Contact | Read | ||
| BV | 66 | STRTSTS_slratrip | Starter Lock Rotor Trip | Read | ||
| BV | 56 | STRTSTS_start_ok | 1CR Start Complete | Read | ||
| BV | 57 | STRTSTS_stop_ok | 1CR Stop Complete | Read | ||
| BV | 74 | STRTSTS_strt_flt | Starter Fault | Read | ||
| AV | 152 | STRTSTS_sum1ht_h | I2T Sum Heat Phase 1 | Read | ||
| AV | 153 | STRTSTS_sum2ht_h | I2T Sum Heat Phase 2 | Read | ||
| AV | 154 | STRTSTS_sum3ht_h | I2T Sum Heat Phase 3 | Read | ||
| BV | 61 | STRTSTS_un_volt | Under Voltage | Read | ||
| AV | 143 | STRTSTS_VOLT_AVG | Average Line Voltage | Read | ||
| AV | 140 | STRTSTS_VOLT_H1 | Line Voltage Phase 1 | Read | ||
| AV | 141 | STRTSTS_VOLT_H2 | Line Voltage Phase 2 | Read | ||
| AV | 142 | STRTSTS_VOLT_H3 | Line Voltage Phase 3 | Read | ||
| BV | 63 | STRTSTS_volt_unb | Voltage Imbalance | Read | ||
| AV | 55 | TEMP_CND_ST_A | Cond Sat Temp A | Read | ||
| AV | 76 | TEMP_CND_ST_B | Cond Sat Temp B | Read | ||
| AV | 57 | TEMP_CNDAPP_A | Condenser Approach A | Read | ||
| AV | 78 | TEMP_CNDAPP_B | Condenser Approach | Read | ||
| AV | 45 | TEMP_CTL_FLUI | Control Fluid Temp | Read | ||
| AV | 53 | TEMP_DGT_A | Discharge Gas Temp A | Read | ||
| AV | 74 | TEMP_DGT_B | Discharge Gas Temp B | Read | ||
| AV | 54 | TEMP_DIS_ST_A | Discharge Sat Temp A | Read | ||
| AV | 75 | TEMP_DIS_ST_B | Discharge Sat Temp B | Read | ||
| AV | 56 | TEMP_DSH_A | Discharge Superheat A | Read | ||
| AV | 77 | TEMP_DSH_B | Discharge Superheat B | Read | ||
| AV | 42 | TEMP_ECDW | Entering Cond Water Temp | Read | ||
| AV | 61 | TEMP_ECO_SH_A | Econ Superheat A | Read | ||
| AV | 82 | TEMP_ECO_SH_B | Econ Superheat B | Read | ||
| AV | 59 | TEMP_ECO_T_A | Economizer Gas Temp A | Read | ||
| AV | 80 | TEMP_ECO_T_B | Economizer Gas Temp B | Read | ||
| AV | 60 | TEMP_ECOST_A | Econ Saturated Temp A | Read | ||
| AV | 81 | TEMP_ECOST_B | Econ Saturated Temp B | Read | ||
| AVmin | 40 | TEMP_ECW | Ent Chill Water Temp | Read | ||
| AV | 46 | TEMP_EVAP_T_A | Evap Rfrg Liq Temp A | Read | ||
| AV | 68 | TEMP_EVAP_T_B | Evap Rfrg Liq Temp B | Read | ||
| AV | 47 | TEMP_EVP_ST_A | Evap Saturated Temp A | Read | ||
| AV | 69 | TEMP_EVP_ST_B | Evap Saturated Temp B | Read | ||
| AV | 48 | TEMP_EVPAPP_A | Evaporator Approach A | Read | ||
| AV | 70 | TEMP_EVPAPP_B | Evaporator Approach B | Read | ||
| AV | 43 | TEMP_LCDW | Leaving Cond Water Temp | Read | ||
| AVmin | 41 | TEMP_LCW | Leaving Chill Water Temp | Read | ||
| AV | 62 | TEMP_LIQ_T_A | Liquid Line Temp A | Read | ||
| AV | 83 | TEMP_LIQ_T_B | Liquid Line Temp B | Read | ||
| AV | 64 | TEMP_LLS_A | Liquid Line Subcool A | Read | ||
| AV | 85 | TEMP_LLS_B | Liquid Line Subcool B | Read | ||
| AV | 58 | TEMP_MTRW_A | Motor Winding Temp A | Read | ||
| AV | 79 | TEMP_MTRW_B | Motor Winding Temp B | Read | ||
| AV | 67 | TEMP_OIL_A | Oil Temp A | Read | ||
| AV | 87 | TEMP_OIL_B | Oil Temp B | Read | ||
| AV | 65 | TEMP_OILTSMPA | Oil Sump Temp A | Read | ||
| AV | 86 | TEMP_OILTSMPB | Oil Sump Temp B | Read | ||
| AV | 44 | TEMP_R_RESET | Remote Reset Temp | Read | ||
| AV | 50 | TEMP_ROT_T_A | Rotor Inlet Temp A | Read | ||
| AV | 63 | TEMP_SLT_A | Saturated Liquid Temp A | Read | ||
| AV | 84 | TEMP_SLT_B | Saturated Liquid Temp B | Read | ||
| AV | 52 | TEMP_SSH_A | Suction Superheat A | Read | ||
| AV | 73 | TEMP_SSH_B | Suction Superheat B | Read | ||
| AV | 51 | TEMP_SST_A | Suct Saturated Temp A | Read | ||
| AV | 72 | TEMP_SST_B | Suct Saturated Temp B | Read | ||
| AV | 49 | TEMP_SUCT_T_A | Suction Temperature A | Read | ||
| AV | 71 | TEMP_SUCT_T_B | Suction Temperature B | Read | ||
| AV | 66 | TEMP_VAP_TEMP | Oil Vaporizer Temp | Read | ||
| AV | 284 | VAPCTL_isEnable | Enable | Read | ||
| AV | 285 | VAPCTL_isNom | Nominal | Read | ||
| AV | 286 | VAPCTL_isRd2Go | Ready to Start | Read | ||
| AV | 287 | VAPCTL_isRd2St | Ready to Stop | Read | ||
| AV | 288 | VAPCTL_isStart | Started | Read | ||
| AV | 289 | VAPCTL_isStop | Stopped | Read |
No points match these filters.
Object ID lookup: Carrier AquaEdge 23XRV point IDs by name
AV411ALARMRST_alarm_1AV412ALARMRST_alarm_2AV413ALARMRST_alarm_3AV414ALARMRST_alarm_4AV415ALARMRST_alarm_5BV161ALARMRST_RST_ALMAV410ALARMRST_SYS_ALMAV313CAPDCTL_actstptAV314CAPDCTL_ck1capmnAV315CAPDCTL_ck1capmxAV316CAPDCTL_ck1caprqAV317CAPDCTL_compldrqBV131CAPDCTL_dem_actBV130CAPDCTL_ramp_actAV318CAPDCTL_scstptofAV319CAPDCTL_stptbstAV320CAPDCTL_syscapmxAV321CAPDCTL_syscaprqAV322CAPECTL_act_ccapAV323CAPECTL_act_fcapAV324CAPECTL_act_vcapAV325CAPECTL_avl_capAV326CAPECTL_avl_fcapAV327CAPECTL_avl_vcapAV328CAPECTL_capAV329CAPECTL_cap_pctAV330CAPECTL_run_fcapAV331CAPECTL_run_vcapAV332CIRCACTL_cap_tonsAV333CIRCACTL_circ_wrdAV334CIRCACTL_ck1_acapAV335CIRCACTL_ck1_capAV336CIRCACTL_ck1_cappAV337CIRCACTL_ck1accapAV338CIRCACTL_ck1afcapAV339CIRCACTL_ck1afscpAV340CIRCACTL_ck1avcapAV341CIRCACTL_ck1avscpAV342CIRCACTL_ck1rfcapAV343CIRCACTL_ck1rvcapAV344CIRCACTL_cmpn_wrdAV345CIRCACTL_statusBV132CIRCACTL_stdystatAV179CMPA1CTL_aDSTMnAV180CMPA1CTL_aDSTMxAV181CMPA1CTL_aSSTMnAV182CMPA1CTL_aSSTMxAV183CMPA1CTL_cANAV184CMPA1CTL_cANpAV185CMPA1CTL_cASpAV186CMPA1CTL_cMaxAV189CMPA1CTL_cmdAV187CMPA1CTL_cMinAV188CMPA1CTL_cObjAV190CMPA1CTL_dSTSAV191CMPA1CTL_dTSAV193CMPA1CTL_eDSTMnAV194CMPA1CTL_eDSTMxAV205CMPA1CTL_elubspAV206CMPA1CTL_envwrdAV195CMPA1CTL_eSSTMnAV196CMPA1CTL_eSSTMxAV197CMPA1CTL_fTStpAV198CMPA1CTL_fWdBV89CMPA1CTL_isEnableBV90CMPA1CTL_isNomBV91CMPA1CTL_isRd2GoBV92CMPA1CTL_isRd2StBV93CMPA1CTL_isStartBV94CMPA1CTL_isStopAV199CMPA1CTL_iTSAV200CMPA1CTL_mTSAV201CMPA1CTL_oVSAV202CMPA1CTL_rTSBV95CMPA1CTL_shrt_cycAV203CMPA1CTL_sSTSAV204CMPA1CTL_stall_ctAV192CMPA1CTL_statwrdBV96CMPA1CTL_vi_cmdAV209CMPA1CTL_vi_cObjAV210CMPA1CTL_vi_dwordAV207CMPA1CTL_vi_sp1AV208CMPA1CTL_vi_sp2BV123CPMPCTL_disc_cmdAV290CPMPCTL_dWdAV291CPMPCTL_fWdBV55CPMPCTL_has_floBV124CPMPCTL_isEnableBV125CPMPCTL_isNomBV126CPMPCTL_isRd2GoBV127CPMPCTL_isRd2StBV128CPMPCTL_isStartBV129CPMPCTL_isStopAV38CTLSTATE_ice_bldAV396DRVA1CFG_curr_limAV393DRVA1CFG_min_spdAV397DRVA1CFG_pwm_freqAV403DRVA1CFG_ramp_decAV402DRVA1CFG_ramp_incAV389DRVA1CFG_rlaAV387DRVA1CFG_rla_mAV392DRVA1CFG_rlhzAV391DRVA1CFG_rlkwAV390DRVA1CFG_rlrpmAV388DRVA1CFG_rlvAV386DRVA1CFG_rlv_iAV401DRVA1CFG_skipbandAV398DRVA1CFG_skipfrq1AV399DRVA1CFG_skipfrq2AV400DRVA1CFG_skipfrq3AV394DRVA1CFG_strt_spdAV395DRVA1CFG_torq_limAV174DRVA1STS_ALM_WD1AV175DRVA1STS_ALM_WD2AV172DRVA1STS_ALT_WD1AV173DRVA1STS_ALT_WD2AV161DRVA1STS_AMPS_PCTAV159DRVA1STS_BUS_VMV8DRVA1STS_COMSAV166DRVA1STS_IGBT_TAV165DRVA1STS_INV_TAV169DRVA1STS_LAST_FLTAV157DRVA1STS_LINE_CURAV158DRVA1STS_LINE_KWAV156DRVA1STS_LINE_VAV160DRVA1STS_MOT_CURAV162DRVA1STS_MOT_KWAV168DRVA1STS_MOT_RPMAV163DRVA1STS_PCTAV167DRVA1STS_RECT_TAV164DRVA1STS_SPDAV170DRVA1STS_STAT_WD1AV171DRVA1STS_STAT_WD2AV226ECOACTL_cObjAV227ECOACTL_dTStptAV228ECOACTL_dWdAV229ECOACTL_fWdBV104ECOACTL_isEnableBV105ECOACTL_isNomBV106ECOACTL_isRd2GoBV107ECOACTL_isRd2StBV108ECOACTL_isStartBV109ECOACTL_isStopAV230ECOACTL_shTStptAV139ENERGY_acgpmAV138ENERGY_aegpmAV377ENERGY_dcgpmAV378ENERGY_dcpdftAV379ENERGY_dcrtAV375ENERGY_decwtAV372ENERGY_degpmAV373ENERGY_depdftAV374ENERGY_dertAV370ENERGY_dewtAV368ENERGY_din_kwAV369ENERGY_dkw_tonAV376ENERGY_dlcwtAV371ENERGY_dlwtAV348EPMPCTL_disc_cmdAV349EPMPCTL_dWdAV350EPMPCTL_fWdAV137EPMPCTL_has_floBV140EPMPCTL_isEnableBV141EPMPCTL_isNomBV142EPMPCTL_isRd2GoBV143EPMPCTL_isRd2StBV144EPMPCTL_isStartBV145EPMPCTL_isStopAV7EXVACFG_aTStptAV6EXVACFG_cll_stptAV9EXVACFG_lo_dshofAV8EXVACFG_lo_dshspAV10EXVACFG_max_distAV11EXVACFG_sbc_minAV12EXVACFG_sbc_ofAV13EXVACFG_spsSTLeMOAV211EXVACTL_aTStptAV213EXVACTL_cll_stptAV212EXVACTL_cObjAV214EXVACTL_dPHStptAV215EXVACTL_dWdAV223EXVACTL_ecliqlvlAV225EXVACTL_estcfloAV224EXVACTL_estefloBV103EXVACTL_estflagAV216EXVACTL_fWdAV221EXVACTL_hi_dtspBV97EXVACTL_isEnableBV98EXVACTL_isNomBV99EXVACTL_isRd2GoBV100EXVACTL_isRd2StBV101EXVACTL_isStartBV102EXVACTL_isStopAV217EXVACTL_lo_dshspAV222EXVACTL_lo_sbcspAV218EXVACTL_max_distAV219EXVACTL_sPHStptAV220EXVACTL_sPLStptAV366FACTORY_aux_ioMV11FACTORY_comp_typMV15FACTORY_econ_optMV14FACTORY_exv_optBV159FACTORY_hgbp_optAV367FACTORY_oilassyMV12FACTORY_refrigAV365FACTORY_tonsMV13FACTORY_vfd_optAV4GENCONF_caplim_aAV5GENCONF_caplim_bMV3GENCONF_dem_selBV2GENCONF_ice_recMV2GENCONF_lead_ckBV3GENCONF_leak_enBV1GENCONF_ramp_enMV1GENCONF_rampselAV2GENCONF_rrate_aAV3GENCONF_rrate_kAV1GENCONF_rrate_tBV4GENUNIT_BAC_OCCBV6GENUNIT_CHIL_S_SAV35GENUNIT_CTRL_PNTAV36GENUNIT_DEM_LIMBV7GENUNIT_EMSTOPBV9GENUNIT_ICE_OCCAV37GENUNIT_LAG_LIMBV5GENUNIT_LCL_S_SBV8GENUNIT_LOC_OCCAV33GENUNIT_min_leftAV34GENUNIT_min_runMV5GENUNIT_ONOFFSVCBV10GENUNIT_ramp_actAV39GENUNIT_ramprateMV7GENUNIT_rpdrststMV4GENUNIT_STATUSMV6GENUNIT_SYS_STATAV233HGBPACTL_cmdAV231HGBPACTL_cObjAV235HGBPACTL_cSSBV110HGBPACTL_do_cmdAV237HGBPACTL_dWdAV234HGBPACTL_fTSAV238HGBPACTL_fWdAV232HGBPACTL_hgbpa_ptBV111HGBPACTL_isEnableBV112HGBPACTL_isNomBV113HGBPACTL_isRd2GoBV114HGBPACTL_isRd2StBV115HGBPACTL_isStartBV116HGBPACTL_isStopAV236HGBPACTL_svPSAV385HYDRCFG_cflo_vtAV383HYDRCFG_condfdtpAV384HYDRCFG_condfldpAV382HYDRCFG_eflo_vtAV380HYDRCFG_evapfdtpAV381HYDRCFG_evapfldpAV127INPUTS_AUTO_DEMAV128INPUTS_AUTO_RESAV133INPUTS_CNDLVL_AAV136INPUTS_CNDLVL_BBV49INPUTS_COND_FSWBV42INPUTS_E_STOPAV131INPUTS_ECOA_FBKAV135INPUTS_ECOB_FBKBV50INPUTS_EVAP_FSWAV130INPUTS_EXVA_FBKAV134INPUTS_EXVB_FBKBV43INPUTS_FS_LOCKBV52INPUTS_HPS_ABV54INPUTS_HPS_BBV44INPUTS_ICE_CONBV45INPUTS_ICE_SWBV51INPUTS_OIL_L_ABV53INPUTS_OIL_L_BAV129INPUTS_REF_LEAKBV46INPUTS_REM_CONBV47INPUTS_REM_LOCKBV48INPUTS_SAFETYAV132INPUTS_SVA_FBKAV29LIMITCFG_ap_dgapAV27LIMITCFG_cdp_alrtAV25LIMITCFG_cond_alAV26LIMITCFG_dgt_alrtAV24LIMITCFG_evap_alAV32LIMITCFG_PpmLimAV28LIMITCFG_rch_cathAV31LIMITCFG_RefPpm20AV30LIMITCFG_vfdsptadAV21LUBECFG_hgbpoffAV20LUBECFG_hgbponAV23LUBECFG_minhzAV22LUBECFG_minliftAV17LUBECFG_smp1offAV16LUBECFG_smp1onAV19LUBECFG_smp2offAV18LUBECFG_smp2onAV15LUBECFG_vphtoffAV14LUBECFG_vphtonAV264OILHCTL_fWdAV265OILHCTL_isEnableAV266OILHCTL_isNomAV267OILHCTL_isRd2GoAV268OILHCTL_isRd2StAV269OILHCTL_isStartAV270OILHCTL_isStopAV271OILPCTL_fWdAV272OILPCTL_isEnableAV273OILPCTL_isNomAV274OILPCTL_isRd2GoAV275OILPCTL_isRd2StAV276OILPCTL_isStartAV277OILPCTL_isStopAV278OILRCTL_isEnableAV279OILRCTL_isNomAV280OILRCTL_isRd2GoAV281OILRCTL_isRd2StAV282OILRCTL_isStartAV283OILRCTL_isStopAV346OILVCTL_oil_viscBV11OUTPUTS_ALEBV12OUTPUTS_ALMBV26OUTPUTS_BP_ECO_ABV40OUTPUTS_BP_ECO_BAV120OUTPUTS_CAPOUT_AAV124OUTPUTS_CAPOUT_BAV116OUTPUTS_CAPTBV16OUTPUTS_CDWP1AV117OUTPUTS_CHST_OUTBV17OUTPUTS_CHWP1BV27OUTPUTS_CP_A_LOCKBV41OUTPUTS_CP_B_LOCKAV121OUTPUTS_ECOEXV_AAV125OUTPUTS_ECOEXV_BAV122OUTPUTS_EXV_AAV126OUTPUTS_EXV_BAV118OUTPUTS_HDPV_OUTBV20OUTPUTS_HGBP_ABV34OUTPUTS_HGBP_BBV22OUTPUTS_MTR_CL_ABV36OUTPUTS_MTR_CL_BBV23OUTPUTS_OIL_DL_ABV37OUTPUTS_OIL_DL_BAV123OUTPUTS_OIL_RECLBV31OUTPUTS_OILHEAT1BV32OUTPUTS_OILHEAT2BV33OUTPUTS_OILRBV21OUTPUTS_OILSOL_ABV35OUTPUTS_OILSOL_BBV13OUTPUTS_RUNBV14OUTPUTS_SET_FLOWBV15OUTPUTS_SHTDNBV28OUTPUTS_SLV_LD_ABV29OUTPUTS_SLV_UL_ABV18OUTPUTS_TFR_HIGHBV19OUTPUTS_TFR_LOWAV119OUTPUTS_TOW_FANBV30OUTPUTS_VAP_HEATBV24OUTPUTS_VFDSOL_ABV38OUTPUTS_VFDSOL_BBV25OUTPUTS_VI_CMP_ABV39OUTPUTS_VI_CMP_BBV146PLTSPRT_rs485_u1_tresBV147PLTSPRT_rs485_u3_tresBV148PLTSPRT_rs485_u4_tresBV149PLTSPRT_rs485_u5_tresAV97PRESSURE_CND_P_AAV108PRESSURE_CND_P_BAV91PRESSURE_COND_EWPAV92PRESSURE_COND_LWPAV93PRESSURE_COND_WDPAV96PRESSURE_DIS_P_AAV107PRESSURE_DIS_P_BAV98PRESSURE_ECO_P_AAV109PRESSURE_ECO_P_BAV88PRESSURE_EVAP_EWPAV89PRESSURE_EVAP_LWPAV94PRESSURE_EVAP_P_AAV105PRESSURE_EVAP_P_BAV90PRESSURE_EVAP_WDPAV103PRESSURE_LIQ_P_AAV114PRESSURE_LIQ_P_BAV104PRESSURE_MTR_P_AAV115PRESSURE_MTR_P_BAV100PRESSURE_OIL_DP_AAV111PRESSURE_OIL_DP_BAV101PRESSURE_OIL_PD_AAV112PRESSURE_OIL_PD_BAV102PRESSURE_OILPA1RQAV113PRESSURE_OILPB1RQAV99PRESSURE_OILPSMPAAV110PRESSURE_OILPSMPBAV95PRESSURE_SUCT_P_AAV106PRESSURE_SUCT_P_BBV136PROTOCOL_BAC_S_SBV138PROTOCOL_BACALARMBV139PROTOCOL_BACALERTAV347PROTOCOL_BACDEMLBV134PROTOCOL_BACESTOPBV137PROTOCOL_BACLKOUTBV133PROTOCOL_BACOCCBV135PROTOCOL_BACSFTYAV307RUNTIME_hr_comp_aAV308RUNTIME_hr_comp_bAV312RUNTIME_hr_cpmp1AV311RUNTIME_hr_epmp1AV306RUNTIME_hr_machAV309RUNTIME_hr_oilpaAV310RUNTIME_hr_oilpbAV305RUNTIME_hr_svcAV298RUNTIME_rcycst_aAV299RUNTIME_rcycst_bAV303RUNTIME_spst_aAV304RUNTIME_spst_bAV294RUNTIME_st_oilpaAV295RUNTIME_st_oilpbAV296RUNTIME_st12_aAV297RUNTIME_st12_bAV292RUNTIME_str_comp_aAV293RUNTIME_str_comp_bAV301RUNTIME_stst_aAV302RUNTIME_stst_bAV300RUNTIME_swiftcntBV155SERVICE1_CirA_EnBV156SERVICE1_CirB_EnAV359SERVICE1_cmpstper_AAV361SERVICE1_cmpstper_BAV353SERVICE1_dem_20maBV150SERVICE1_emstopenMV9SERVICE1_flui_typAV351SERVICE1_freezespBV151SERVICE1_lockoutAV355SERVICE1_max_lwtAV354SERVICE1_min_lwtAV352SERVICE1_min_offBV153SERVICE1_oilsw_by_ABV154SERVICE1_oilsw_by_BAV364SERVICE1_pwautlimAV356SERVICE1_rspdmaxAAV357SERVICE1_rspdmaxBBV157SERVICE1_rsthrsvcMV10SERVICE1_rstrtoptBV158SERVICE1_sftst_enAV362SERVICE1_sftst_thAV363SERVICE1_spstopenBV152SERVICE1_stlim_byAV358SERVICE1_stpperlim_AAV360SERVICE1_stpperlim_BAV407SETPOINT_dem_baseAV406SETPOINT_ecw_spBV160SETPOINT_EWT_OPTAV405SETPOINT_ice_spAV404SETPOINT_lcw_spAV409SETPOINT_rcyc_hiAV408SETPOINT_rcyc_loAV247SLVA1CTL_cANAV248SLVA1CTL_cANpAV249SLVA1CTL_cASpAV250SLVA1CTL_cMaxAV239SLVA1CTL_cmdAV251SLVA1CTL_cMinAV252SLVA1CTL_cObjAV240SLVA1CTL_dstcmdAV253SLVA1CTL_dSTSAV241SLVA1CTL_dtcmdAV254SLVA1CTL_dTSAV256SLVA1CTL_dty_cycAV255SLVA1CTL_dWdAV242SLVA1CTL_ftcmdAV257SLVA1CTL_fTStpAV258SLVA1CTL_fWdBV117SLVA1CTL_isEnableBV118SLVA1CTL_isNomBV119SLVA1CTL_isRd2GoBV120SLVA1CTL_isRd2StBV121SLVA1CTL_isStartBV122SLVA1CTL_isStopAV259SLVA1CTL_iTSAV260SLVA1CTL_mCSAV243SLVA1CTL_mcurcmdAV244SLVA1CTL_mtmpmdAV261SLVA1CTL_mTSAV245SLVA1CTL_oilrecmdAV262SLVA1CTL_oVSAV246SLVA1CTL_sstcmdAV263SLVA1CTL_sSTSAV176STGECTL_cmp1cknbBV83STGECTL_cmp1hgbpBV84STGECTL_cmp1ldrqBV85STGECTL_comp_ldBV86STGECTL_comp_ulBV87STGECTL_ld_alwdAV177STGECTL_leadckAV178STGECTL_stat_wrdBV88STGECTL_ul_alwdBV76STRTSTS_accelfltBV62STRTSTS_amp_unbAV147STRTSTS_AMPS_AVGAV144STRTSTS_AMPS_H1AV145STRTSTS_AMPS_H2AV146STRTSTS_AMPS_H3BV79STRTSTS_ampstopBV81STRTSTS_calfc_erBV82STRTSTS_conf_errBV58STRTSTS_cycle_1AV148STRTSTS_FREQ_HBV69STRTSTS_freqfltAV149STRTSTS_GRFT_H1AV150STRTSTS_GRFT_H2AV151STRTSTS_GRFT_H3BV67STRTSTS_grnd_fltBV80STRTSTS_hardwareBV77STRTSTS_highampsBV70STRTSTS_ism_porAV155STRTSTS_KWBV65STRTSTS_lratripBV71STRTSTS_m1_fltBV78STRTSTS_m1m2stopBV72STRTSTS_m2_fltBV75STRTSTS_no_ampsBV60STRTSTS_ov_voltBV64STRTSTS_overloadBV59STRTSTS_ph_lossBV68STRTSTS_ph_revBV73STRTSTS_prs_tripBV66STRTSTS_slratripBV56STRTSTS_start_okBV57STRTSTS_stop_okBV74STRTSTS_strt_fltAV152STRTSTS_sum1ht_hAV153STRTSTS_sum2ht_hAV154STRTSTS_sum3ht_hBV61STRTSTS_un_voltAV143STRTSTS_VOLT_AVGAV140STRTSTS_VOLT_H1AV141STRTSTS_VOLT_H2AV142STRTSTS_VOLT_H3BV63STRTSTS_volt_unbAV55TEMP_CND_ST_AAV76TEMP_CND_ST_BAV57TEMP_CNDAPP_AAV78TEMP_CNDAPP_BAV45TEMP_CTL_FLUIAV53TEMP_DGT_AAV74TEMP_DGT_BAV54TEMP_DIS_ST_AAV75TEMP_DIS_ST_BAV56TEMP_DSH_AAV77TEMP_DSH_BAV42TEMP_ECDWAV61TEMP_ECO_SH_AAV82TEMP_ECO_SH_BAV59TEMP_ECO_T_AAV80TEMP_ECO_T_BAV60TEMP_ECOST_AAV81TEMP_ECOST_BAV40TEMP_ECWAV46TEMP_EVAP_T_AAV68TEMP_EVAP_T_BAV47TEMP_EVP_ST_AAV69TEMP_EVP_ST_BAV48TEMP_EVPAPP_AAV70TEMP_EVPAPP_BAV43TEMP_LCDWAV41TEMP_LCWAV62TEMP_LIQ_T_AAV83TEMP_LIQ_T_BAV64TEMP_LLS_AAV85TEMP_LLS_BAV58TEMP_MTRW_AAV79TEMP_MTRW_BAV67TEMP_OIL_AAV87TEMP_OIL_BAV65TEMP_OILTSMPAAV86TEMP_OILTSMPBAV44TEMP_R_RESETAV50TEMP_ROT_T_AAV63TEMP_SLT_AAV84TEMP_SLT_BAV52TEMP_SSH_AAV73TEMP_SSH_BAV51TEMP_SST_AAV72TEMP_SST_BAV49TEMP_SUCT_T_AAV71TEMP_SUCT_T_BAV66TEMP_VAP_TEMPAV284VAPCTL_isEnableAV285VAPCTL_isNomAV286VAPCTL_isRd2GoAV287VAPCTL_isRd2StAV288VAPCTL_isStartAV289VAPCTL_isStop
Integration notes
- The table has no units column; values follow the controller's configured unit system.
- Many configuration and factory objects are listed as RW; treat FACTORY_ and SERVICE1_ objects as commissioning-only.
- Integration with a BAS is not part of the standard Carrier start-up and is done by a Carrier controls technician.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AquaEdge 23XRV (PIC6) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier AquaEdge 23XRV (PIC6)
How many BACnet points does the Carrier AquaEdge 23XRV (PIC6) have?
This list has 591 BACnet objects: 415 analog values, 161 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier AquaEdge 23XRV (PIC6) BACnet points are writable?
155 of the 591 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier AquaEdge 23XRV (PIC6) BACnet documentation?
The source is AquaEdge 23XRV Variable Speed High-Efficiency Screw Liquid Chillers - Controls Operation and Troubleshooting (23XRV-3T), revision 2025-01, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0B/23XRV-3T.pdf.
What are the minimum BACnet points to integrate the Carrier AquaEdge 23XRV (PIC6)?
Start with AV 404 SETPOINT_lcw_sp (Cooling leaving water setpoint (writable)); AV 407 SETPOINT_dem_base (Base demand limit from the BMS, %); BV 136 PROTOCOL_BAC_S_S (Start/stop command; listed read-only, test writes); BV 133 PROTOCOL_BACOCC (Occupancy command; listed read-only, test writes); BV 134 PROTOCOL_BACESTOP (Emergency stop; listed read-only, test writes); MV 4 GENUNIT_STATUS (Unit run status); AV 41 TEMP_LCW (Leaving chilled water temperature); AV 40 TEMP_ECW (Entering chilled water temperature); AV 35 GENUNIT_CTRL_PNT (Control point in use); AV 410 ALARMRST_SYS_ALM (System alert/alarm state).
How do I enable BMS control of the Carrier AquaEdge 23XRV (PIC6)?
Network start for BACnet must be ticked on the Configure Startup Options screen (User login or higher). In Network mode the chiller starts only when CHIL_S_S and CHIL_OCC are both true; each enabled start source must send a stop to stop the chiller. BACnet emergency stop (PROTOCOL_BACESTOP) is one of the emergency-stop sources.
How do I check these points on the real AquaEdge 23XRV (PIC6)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Applied rooftop unit controller
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Carrier 48/50K and 48/50V applied rooftop units (gas heat or electric heat, R-454B) with SmartVu controls on PIC 6.1 hardware.
Also known as: SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points
Carrier AquaForce 30XV140-500 chillers with the Touch Pilot controller and the optional BACnet/Modbus Translator on BACnet MS/TP.
Also known as: 30XV, AquaForce 30XV, 30XV-2T, 30XV BACnet translator, BACnet/Modbus Translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points
Carrier AquaForce 30XV140-500 variable speed air-cooled screw chillers with the Touch Pilot display (original / Series A documentation, 2017).
Also known as: 30XV, AquaForce 30XV, 30XV-2T, 30XV Touch Pilot, 30XV Series A, Greenspeed 30XV - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the Carrier Controller as documented in the June 2019 manual (Form 30XV-3T).
Also known as: 30XV, AquaForce 30XV, 30XV-3T, 30XV Series B 2019, Carrier Controller, Greenspeed, 04-53300197-01 - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: AquaEdge 23XRV Variable Speed High-Efficiency Screw Liquid Chillers - Controls Operation and Troubleshooting · 23XRV-3T · rev. 2025-01. Object names, instances and units are reproduced as published; descriptions are our own.