- Home
- BACnet points lists
- Carrier
- 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
Applied rooftop unit controller · BACnet points list
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet points list
Updated 28 October 2026
The SmartVu touchscreen control with PIC 6.1 hardware runs Carrier's 48/50K and 48/50V applied rooftop units. It speaks BACnet MS/TP on port J8 or BACnet IP on either Ethernet port, plus CCN; Modbus is not offered for BAS use. Almost every object is an analog, binary or multistate value, grouped into setpoints, sensor readings, network inputs, unit states, outputs, runtimes and a large set of configuration and alert-limit values.
This page lists 715 BACnet objects for the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) — 393 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Carrier’s own free documentation, linked below.
- Manufacturer
- Carrier
- Model
- 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
- Equipment
- Applied rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 715 (393 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Software 2.5.0 (versions before 2.4.0 may use different instances and names)
- Also known as
- SmartVu, PIC 6.1, PIC6.1, 48K, 50K, 48V, 50V, 48/50K, 48/50V, Carrier applied rooftop, 48-50-ART-SVU-1T
Reference only, provided as-is: verify against Carrier’s current documentation and the live device before use. Not official Carrier information. Terms of use.
BMS integration notes: Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
On the SmartVu Controller Config screens (user password 1111) set Primary BAS Network to BACnet and BACnet Enable to MS/TP or BACnet IP, then reboot. Occupancy comes from BACnet schedule objects or the Network Occupancy point (AV 363); write the occupied setpoints directly and read unit states, temperatures and the alarm relay. Check the numeric codes of configuration AVs on the touchscreen before writing them.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 363 | GENUNIT_NETOCC | Network occupancy; Primary BAS Network must be BACnet | Write |
| AV 195 | COOLSTP_CLSP_OCC | Occupied cooling setpoint | Write |
| AV 313 | HEATSTP_HTSP_OCC | Occupied heating setpoint | Write |
| BV 1 | ALARMRST_RST_ALM | Alarm reset command | Write |
| MV 22 | STATES_IDFNUM | Indoor fan state; 5 = running | Read |
| AV 289 | GENUNIT_OCCUPIED | Confirms occupied/unoccupied | Read |
| AV 7 | AIRTEMP_SPT | Space temperature | Read |
| AV 4 | AIRTEMP_SAT | Supply air temperature | Read |
| BV 83 | DISCOUT_ALMOUT | Common alarm relay output | Read |
Enable & remote start
Primary BAS Network selects the network that drives occupancy; it must be BACnet to use the Network Occupancy point (GENUNIT_NETOCC, AV 363) when BACnet schedule objects are not used. The guide does not say what the 0-2 values of AV 363 mean (default 2). Occupancy Source (MV 26) shows where occupancy currently comes from.
Sensors & values from the BMS
The Network Inputs group has writable objects for BMS values, e.g. Net SPT (AV 360), Net OAT (AV 362), Net SPRH (AV 347), Net Indoor Air Quality (AV 357), Net Building Pressure (AV 352), and network thermostat calls Network Y1/Y2/W1/W2/G/HSTAT (BV 141-146). The guide does not explain how the unit selects them or give any refresh timeout.
Network setup
- Communication settings are on the Controller Config screen, shown only after logging in with the user password 1111 (touchscreen or VNC).
- BACnet MS/TP uses port J8 (field-supplied plug). First set Zone Sensor Config > Serial Port Config to Modbus_J8_MSTP so J10 stays Modbus for the internal drives, then set BACnet Enable = MS/TP, MAC, baud, network and identifier. Max Masters 127 and Max Info Frames 20 or less are recommended.
- BACnet IP: Ethernet 0 (J15, default 169.254.1.1/255.255.0.0) or Ethernet 1 (J16, default 192.168.100.100/255.255.0.0); UDP 47808 by default; BACnet Mgmt Device can be None, Foreign Device or BBMD. Reboot after IP changes.
- J8 carries either BACnet MS/TP or Rnet sensors, not both, on software 2.5.0.
- The SmartVu is locally biased: don't put it on a network-biased segment, and terminate with a TERM485 rather than router end-of-line switches.
Watch out for
- The list is for software 2.5.0; versions before 2.4.0 may use different instances and names.
- Most configuration values are AVs with undocumented numeric codes; read the current value and check the touchscreen before writing.
- BV 83 is the alarm relay output. Alarm Output (BV 101, Equipment Configs) and Alarm Relay inversion (BV 206, Switch Inversion) also exist; the guide doesn't explain them, so check on the touchscreen.
- Percentages read as 0.00-1.00 or 0-100 depending on the Percentage Conversion setting.
Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 3 | AIRPRESS_BP | Building Pressure (BP) | in. w.c. | Read | |
| AV | 15 | AIRTEMP_DXLAT | Direct Expansion LAT | °F | Read | |
| AV | 14 | AIRTEMP_EFF_CP | Effective Control Point | °F | Read | |
| AV | 11 | AIRTEMP_EAT | Exhaust Air Temp (EAT) | °F | Read | |
| AV | 10 | AIRTEMP_MAT | Mixed Air Temp (MAT) | °F | Read | |
| AV | 120 | AIRTEMP_OADP | Outside Air Dew Point | °F | Read | |
| AV | 9 | AIRTEMP_OAT | Outside Air Temp (OAT) | °F | Read | |
| AV | 1 | AIRPRESS_RAP | Return Air Pressure | in. w.c. | Read | |
| AV | 6 | AIRTEMP_RAT | Return Air Temp (RAT) | °F | Read | |
| AVmin | 7 | AIRTEMP_SPT | Space Temp (SPT) | °F | Read | |
| AV | 8 | AIRTEMP_SPTO | Space Temp Offset | °F | Read | |
| AV | 13 | AIRTEMP_LAT | Staged Gas LAT | °F | Read | |
| AV | 12 | AIRTEMP_LST | Staged Gas Limit Temp | °F | Read | |
| AV | 123 | AIRTEMP_SADP | Supply Air Dew Point | °F | Read | |
| AVmin | 4 | AIRTEMP_SAT | Supply Air Temp (SAT) | °F | Read | |
| AV | 5 | AIRTEMP_SATO | Supply Air Temp Offset | °F | Read | |
| AV | 2 | AIRPRESS_SDP | Supply Pressure (SP) | in. w.c. | Read | |
| BVmin | 1 | ALARMRST_RST_ALM | Alarm Reset | Write | 1=NO; 2=YES | |
| AV | 35 | ALERTCFG_BP_HLMT | BP High Limit (default 0.1, 0 to 0.15) | in. w.c. | Write | |
| AV | 34 | ALERTCFG_BP_LLMT | BP Low Limit (default -0.1, -0.15 to 0) | in. w.c. | Write | |
| AV | 74 | ALERTCFG_COFS_ACT | COFS Action (default 0) | Write | ||
| AV | 76 | ALERTCFG_COFS_TME | COFS Time (default 5, 1 to 20) | h | Write | |
| AV | 75 | ALERTCFG_COFS_TRP | COFS Trips (default 5, 1 to 20) | Write | ||
| AV | 60 | ALERTCFG_CP_C_TH | Comp Cycling Threshold (default 200) | min | Write | |
| AV | 54 | ALERTCFG_CMPCMD_T | Compressor Cmd Time (default 15, 1 to 30) | s | Write | |
| AV | 45 | ALERTCFG2_ERV_ALRT | ERV Frost Alert Limit (default 35, 25 to 40) | °F | Write | |
| AV | 59 | ALERTCFG_POSTFL | Final Filter Reminder (default 2880, 0 to 43200) | Write | ||
| AV | 48 | ALERTCFG_HIGH_SST | High SST Time (default 10) | min | Write | |
| AV | 40 | ALERTCFG_IAQ_HLMT | IAQ High Limit (default 1200, 0 to 5000) | ppm | Write | |
| BV | 4 | ALERTCFG_LOCK_OUT | Lockout Notification | Write | 1=OFF; 2=ON | |
| BV | 448 | LPALMEN | Low Power Alarm Enable | Write | 1=DISABLE; 2=ENABLE | |
| AV | 575 | LPALMHYS | Low Power Hysteresis (mS) (default 500, 0 to 2000) | Write | ||
| AV | 72 | ALERTCFG_LPRL | Low Press Ratio Limit (default 1.3, 1 to 2) | psig | Write | |
| AV | 65 | ALERTCFG_SSHALOW | Low SSH A Alert (default 4, 2 to 10) | °F | Write | |
| AV | 67 | ALERTCFG_SSHAFLLO | Low SSH A Full Load Alrt (default 4, 2 to 10) | °F | Write | |
| AV | 66 | ALERTCFG_SSHAPLLO | Low SSH A Part Load Alrt (default 9, 7 to 15) | °F | Write | |
| AV | 71 | ALERTCFG_LSSHTIME | Low SSH Alert Time (default 30, 5 to 120) | s | Write | |
| AV | 68 | ALERTCFG_SSHBLOW | Low SSH B Alert (default 4, 2 to 10) | °F | Write | |
| AV | 70 | ALERTCFG_SSHBFLLO | Low SSH B Full Load Alrt (default 4, 2 to 10) | °F | Write | |
| AV | 69 | ALERTCFG_SSHBPLLO | Low SSH B Part Load Alrt (default 9, 7 to 15) | °F | Write | |
| AV | 63 | ALERTCFG_LSST1T | Low SST 1Min Threshold (default 0, -30 to 40) | °F | Write | |
| AV | 64 | ALERTCFG_LSST20sT | Low SST 20Sec Threshold (default -20, -30 to 40) | °F | Write | |
| AV | 62 | ALERTCFG_LSST2T | Low SST 2Min Threshold (default 10, -30 to 40) | °F | Write | |
| AV | 61 | ALERTCFG_LSST4T | Low SST 4Min Threshold (default 20, -30 to 40) | °F | Write | |
| AV | 50 | ALERTCFG_MINDISA | Min Disc Chg Cir A (default 11, 0 to 99) | psig | Write | |
| AV | 52 | ALERTCFG_MINDISB | Min Disc Chg Cir B (default 11, 0 to 99) | psig | Write | |
| AV | 49 | ALERTCFG_MINSUCA | Min Suc Chg Cir A (default 20, 0 to 99) | psig | Write | |
| AV | 51 | ALERTCFG_MINSUCB | Min Suc Chg Cir B (default 20, 0 to 99) | psig | Write | |
| AV | 56 | ALERTCFG_ECMINCFM | OAD Min CFM (default 0) | cfm | Write | |
| AV | 39 | ALERTCFG_OAT_HLMT | OAT High Limit (default 150) | °F | Write | |
| AV | 38 | ALERTCFG_OAT_LLMT | OAT Low Limit (default -40) | °F | Write | |
| AV | 53 | ALERTCFG_OFF_PRES | Off Press Ratio (default -0.2, -1 to 1) | psig | Write | |
| AV | 55 | ALERTCFG_OCFMSENS | Outdoor Air CFM (default 0, 0 to 1) | cfm | Write | |
| AV | 41 | ALERTCFG_MAINFLT | Pre-Filter Change Time (default 2000, 168 to 8760) | h | Write | |
| AV | 31 | ALERTCFG_RARH_HT | RARH High Limit (default 100, 0 to 100) | % | Write | |
| AV | 30 | ALERTCFG_RARH_LT | RARH Low Limit (default 0, 0 to 100) | % | Write | |
| AV | 27 | ALERTCFG_RATHLMTO | RAT High Occu Limit (default 90, -40 to 245) | °F | Write | |
| AV | 28 | ALERTCFG_RATHLMTU | RAT High Unoc Limit (default 100, -40 to 245) | °F | Write | |
| AV | 26 | ALERTCFG_RATLLMTO | RAT Low Occu Limit (default 60, -40 to 245) | °F | Write | |
| AV | 29 | ALERTCFG_RATLLMTU | RAT Low Unoc Limit (default 40, -40 to 245) | °F | Write | |
| AV | 37 | ALERTCFG_SAT_HTMP | SAT High Limit (default 130, 105 to 160) | °F | Write | |
| AV | 23 | ALERTCFG_SATHLMTO | SAT High Occu Limit (default 130, 105 to 160) | °F | Write | |
| AV | 25 | ALERTCFG_SATHLMTU | SAT High Unoc Limit (default 130, 105 to 160) | °F | Write | |
| AV | 36 | ALERTCFG_SAT_LTMP | SAT Low Limit (default 45, 0 to 50) | °F | Write | |
| AV | 22 | ALERTCFG_SATLLMTO | SAT Low Occu Limit (default 40, 0 to 45) | °F | Write | |
| AV | 24 | ALERTCFG_SATLLMTU | SAT Low Unoc Limit (default 40, 0 to 45) | °F | Write | |
| AV | 33 | ALERTCFG_SP_HLMT | SP High Limit (default 2, 1.5 to 2.2) | in. w.c. | Write | |
| AV | 32 | ALERTCFG_SP_LLMT | SP Low Limit (default 0.1, 0 to 0.5) | in. w.c. | Write | |
| AV | 16 | ALERTCFG_SPRHHL | SPRH High Limit (default 80, 0 to 100) | % | Write | |
| AV | 17 | ALERTCFG_SPRHLL | SPRH Low Limit (default 20, 0 to 100) | % | Write | |
| AV | 19 | ALERTCFG_SPTHLMTO | SPT High Occu Limit (default 85, -10 to 245) | °F | Write | |
| AV | 21 | ALERTCFG_SPTHLMTU | SPT High Unoc Limit (default 100, -10 to 245) | °F | Write | |
| AV | 18 | ALERTCFG_SPTLLMTO | SPT Low Occu Limit (default 60, -10 to 245) | °F | Write | |
| AV | 20 | ALERTCFG_SPTLLMTU | SPT Low Unoc Limit (default 45, -10 to 245) | °F | Write | |
| AV | 86 | ALERTCFG_MSDPT | Static Duct Press Limit (default 3, 0 to 5) | in. w.c. | Write | |
| BV | 5 | ALERTCFG_T24ENAB | T24 Diagnostic | Write | 1=DISABLE; 2=ENABLE | |
| AV | 83 | ALERTCFG_T24ECMAX | T24 Econ Max Pos (default 85, 50 to 100) | % | Write | |
| AV | 82 | ALERTCFG_T24ECMIN | T24 Econ Min Pos (default 15, 0 to 50) | % | Write | |
| AV | 84 | ALERTCFG_HCDELAY | T24 Heat-Cool Delay (default 25, 0 to 60) | min | Write | |
| AV | 80 | ALERTCFG_MOVEDTEC | T24 Move Detect (default 1, 1 to 10) | % | Write | |
| AV | 77 | ALERTCFG_OARADIFF | T24 OA RA diff (default 15, 5 to 20) | °F | Write | |
| AV | 79 | ALERTCFG_SATCHNGE | T24 Sat Change (default 0.2, 0 to 5) | °F | Write | |
| AV | 78 | ALERTCFG_SATMOVE | T24 SAT Move Chk (default 10, 10 to 20) | % | Write | |
| AV | 81 | ALERTCFG_SASETTLE | T24 SAT Settle (default 120, 5 to 450) | s | Write | |
| AV | 135 | ANALOGIN_ODF1SPD | CF 1 Speed | Hz | Read | |
| AV | 136 | ANALOGIN_ODF2SPD | CF 2 Speed | Hz | Read | |
| AV | 137 | ANALOGIN_ODF3SPD | CF 3 Speed | Hz | Read | |
| AV | 131 | ANALOGIN_CMPA1SPD | Comp A1 Speed | Hz | Read | |
| AV | 132 | ANALOGIN_CMPA2SPD | Comp A2 Speed | Hz | Read | |
| AV | 133 | ANALOGIN_CMPB1SPD | Comp B1 Speed | Hz | Read | |
| AV | 134 | ANALOGIN_CMPB2SPD | Comp B2 Speed | Hz | Read | |
| AV | 146 | ANALOGIN_DLC | Demand Limit Control | Read | ||
| AV | 114 | ANALOGIN_EF3P_CMD | EXF 3rd Party Modulation | % | Read | |
| AV | 140 | ANALOGIN_EFSPD | Exhaust Fan Speed | % | Read | |
| AV | 141 | ANALOGIN_EXV_A1 | EXV A1 | % | Read | |
| AV | 142 | ANALOGIN_EXV_A2 | EXV A2 | % | Read | |
| AV | 143 | ANALOGIN_EXV_B1 | EXV B1 | % | Read | |
| AV | 144 | ANALOGIN_EXV_B2 | EXV B2 | % | Read | |
| AV | 148 | ANALOGIN_FFPD | Final Filt Press Drop | in. w.c. | Read | |
| AV | 130 | ANALOGIN_HMD2 | HGRH Valve 2 Feedback | % | Read | |
| AV | 129 | ANALOGIN_HMD | HGRH Valve Feedback | % | Read | |
| AV | 116 | ANALOGIN_IAQOPRST | IAQ OAD Pos Reset | % | Read | |
| AV | 115 | ANALOGIN_SF3P_CMD | IDF 3rd Party Modulation | % | Read | |
| AV | 138 | ANALOGIN_IDFSPD | IDF Speed | % | Read | |
| AV | 139 | ANALOGIN_IDFRPM | IDF Speed RPM | rpm | Read | |
| AV | 117 | ANALOGIN_IAQ | Indoor Air Quality | ppm | Read | |
| AV | 125 | ANALOGIN_MARH | Mixed Air RH (MARH) | % | Read | |
| AV | 113 | ANALOGIN_OD3P_CMD | OAD 3rd Party Modulation | % | Read | |
| AV | 127 | ANALOGIN_DAMPPOS | OAD Feedback | % | Read | |
| AV | 111 | ANALOGIN_OACFM | Outdoor Air CFM | cfm | Read | |
| AV | 112 | ANALOGIN_OACFMRST | Outdoor Air CFM Reset | cfm | Read | |
| AV | 149 | ANALOGIN_OA_ENTH | Outdoor Air Enthalpy | BTU/lb | Read | |
| AV | 118 | ANALOGIN_OAQ | Outdoor Air Quality | ppm | Read | |
| AV | 119 | ANALOGIN_OARH | Outdoor Air RH (OARH) | % | Read | |
| AV | 147 | ANALOGIN_PFPD | Pre Filt Press Drop | Read | ||
| AV | 128 | ANALOGIN_DAMPPOS2 | RAD Feedback | % | Read | |
| AV | 150 | ANALOGIN_RA_ENTH | Return Air Enthalpy | BTU/lb | Read | |
| AV | 121 | ANALOGIN_RARH | Return Air RH (RARH) | % | Read | |
| AV | 124 | ANALOGIN_SPRH | Space RH (SPRH) | % | Read | |
| AV | 145 | ANALOGIN_SPSR | Static Pressure Stpt Rst | in. w.c. | Read | |
| AV | 122 | ANALOGIN_SARH | Supply Air RH (SARH) | % | Read | |
| AV | 126 | ANALOGIN_ZDP | Zone Damper Position | % | Read | |
| AV | 94 | ANALGOUT_HEATCMD | Actual heat command | % | Read | |
| AV | 104 | ANALGOUT_ODF1CMD | CF 1 Command | % | Read | |
| AV | 105 | ANALGOUT_ODF2CMD | CF 2 Command | % | Read | |
| AV | 106 | ANALGOUT_ODF3CMD | CF 3 Command | % | Read | |
| AV | 99 | ANALGOUT_CMPA1CMD | Comp A1 Command | % | Read | |
| AV | 100 | ANALGOUT_CMPA2CMD | Comp A2 Command | % | Read | |
| AV | 101 | ANALGOUT_CMPB1CMD | Comp B1 Command | % | Read | |
| AV | 102 | ANALGOUT_CMPB2CMD | Comp B2 Command | % | Read | |
| AV | 98 | ANALGOUT_ERV_OAF | ERV Outdoor Air Fan | % | Read | |
| AV | 97 | ANALGOUT_EFCMD | Exhaust Fan Cmd | % | Read | |
| AV | 107 | ANALGOUT_EXVA1CMD | EXV A1 Cmd | % | Read | |
| AV | 108 | ANALGOUT_EXVA2CMD | EXV A2 Cmd | % | Read | |
| AV | 109 | ANALGOUT_EXVB1CMD | EXV B1 Cmd | % | Read | |
| AV | 110 | ANALGOUT_EXVB2CMD | EXV B2 Cmd | % | Read | |
| AV | 96 | ANALGOUT_HMV2 | HGRH 2 Command | % | Read | |
| AV | 95 | ANALGOUT_HMV | HGRH Command | % | Read | |
| AV | 103 | ANALGOUT_IDFCMD | IDF1 Control Command | % | Read | |
| AV | 92 | ANALGOUT_DAMPCMD | OAD Command | % | Read | |
| AV | 93 | ANALGOUT_DAMPCMD2 | RAD Cmd | % | Read | |
| AV | 295 | BACNET_loc_occ | Local Sched Occ Request | Read | ||
| MV | 27 | BACNET_ALC_COLOR | Operation Status Color | Read | 1=Gray; 2=Red; 3=DarkBlue; 4=LightBlue; 5=Green; 6=LightGreen; 7=Yellow; 8=Orange; 9=Red; 10=White; 13=Coral; 14=Charcoal; 15=Purple | |
| AV | 294 | BACNET_SCH_Objj | Sched Linked BACnet Obj | Read | ||
| AV | 573 | BACNET_ALC_PRIME | Value of Prime variable | °F | Read | |
| AV | 193 | COOLCFG_GAP_CLHT | Cool Heat Gap Config (default 5, 2 to 10) | °F | Write | |
| BV | 7 | COOLCFG_TMPDVNT | Cool Tempered Venting | Write | 1=DISABLE; 2=ENABLE | |
| AV | 191 | COOLCFG_CLTREND | Cool Trend Level (default 0.2, 0.1 to 5) | °F | Write | |
| AV | 192 | COOLCFG_CLTNDTM | Cool Trend Time (default 2, 1 to 5) | min | Write | |
| AV | 186 | COOLCFG_DEMAND | Cool/Heat Demand Source (default 3, 0 to 5) | Write | ||
| AV | 483 | COOLCFG_SATHI_DB | SAT High Deadband (default 5, 2.5 to 10) | °F | Write | |
| AV | 482 | COOLCFG_SATLO_DB | SAT Lo Deadband (default 10, 5 to 15) | °F | Write | |
| AV | 190 | COOLCFG_RSTLMIT | SAT Reset Limit (default 10, 0 to 20) | Write | ||
| AV | 189 | COOLCFG_RSTRTIO | SAT Reset Ratio (default 3, 0 to 10) | Write | ||
| AV | 188 | COOLCFG_TPCTLRST | SAT Reset Source (default 0, 0 to 5) | Write | ||
| AV | 187 | COOLCFG_SPLYDB | Vent Deadband (default 15, 10 to 30) | °F | Write | |
| AV | 296 | COOLSTP_HODACLSP | 100% OA Cool SAT | °F | Read | |
| AV | 200 | COOLSTP_HODAHCL | 100% OA High Cool SAT (default 70, 55 to 75) | °F | Write | |
| AV | 199 | COOLSTP_HODALCL | 100% OA Low Cool SAT (default 75, 55 to 75) | °F | Write | |
| AV | 224 | COOLSTP_CAPLIMS1 | Cool Capacity Limit S1 (default 50, 0 to 100) | % | Write | |
| AV | 225 | COOLSTP_CAPLIMS2 | Cool Capacity Limit S2 (default 0, 0 to 100) | % | Write | |
| AV | 233 | COOLSTP_DMDRSTCL | Dmd Reset Cool Adjust (default 4, 0 to 10) | °F | Write | |
| AV | 203 | COOLCFG_DOHICLON | Hi Cool On DB (default 1, 0.5 to 20) | °F | Write | |
| AV | 198 | COOLSTP_SAHICLSP | Hi Cool SAT (default 55, 55 to 75) | °F | Write | |
| AV | 202 | COOLCFG_DOLOCLOF | Lo Cool Off DB (default 1, 0.5 to 2) | °F | Write | |
| AV | 201 | COOLCFG_DOLOCLON | Lo Cool On DB (default 1, 0 to 2) | °F | Write | |
| AV | 197 | COOLSTP_SALOCLSP | Lo Cool SAT (default 65, 55 to 75) | °F | Write | |
| AVmin | 195 | COOLSTP_CLSP_OCC | Occupied Cooling (default 73, 55 to 80) | °F | Write | |
| AV | 527 | COOLSTP_ACTV_SP | SAT Setpt | °F | Read | |
| AV | 196 | COOLSTP_CLSP_UNO | Unoccupied Cooling (default 83, 55 to 110) | °F | Write | |
| AV | 206 | COOLCFG_DOVAVCOF | VAV Cool Off DB (default 2, 1 to 25) | °F | Write | |
| AV | 205 | COOLCFG_DOVAVCON | VAV Cool On DB (default 3.5, 0 to 25) | °F | Write | |
| AV | 204 | COOLSTP_VAVCLSP | VAV Cooling SAT (default 55, 45 to 75) | °F | Write | |
| AV | 207 | COOLSTP_SPLYAVSP | Vent SAT (default 70, 55 to 85) | °F | Write | |
| AV | 218 | DHUMSTP_CCTSTP | Dehum CCT (default 55) | °F | Write | |
| AV | 484 | DHUMCFG_DHUMMODE | Dehum Control Mode (default 0, 0 to 3) | Write | ||
| AV | 208 | DHUMCFG_DMD_SRC | Dehum Demand Source (default 3, 0 to 8) | Write | ||
| AV | 215 | DHUMSTP_DHUMRHSP | Dehum RH (default 55, 40 to 100) | % | Write | |
| AV | 217 | DHUMCFG_RLOS_OFF | Dehum RH Off DB (default 5, 1 to 20) | % | Write | |
| AV | 216 | DHUMCFG_RLOS_ON | Dehum RH On DB (default 5, 0 to 20) | % | Write | |
| AV | 302 | DHUMSTP_DHUMSADP | Dehum SADP | °F | Read | |
| BV | 13 | DHUMCFG_DHUMHICL | High Cool Dehum | Write | 1=DISABLE; 2=ENABLE | |
| BV | 15 | DHUMCFG_DHUMHIHT | High Heat Dehum | Write | 1=DISABLE; 2=ENABLE | |
| BV | 14 | DHUMCFG_DHUMLOCL | Low Cool Dehum | Write | 1=DISABLE; 2=ENABLE | |
| BV | 16 | DHUMCFG_DHUMLOHT | Low Heat Dehum | Write | 1=DISABLE; 2=ENABLE | |
| BV | 18 | DHUMCFG_OFDHUMEN | Occupied Free Dehum | Write | 1=DISABLE; 2=ENABLE | |
| BV | 10 | DHUMCFG_SUPPHEAT | Supplemental Heat | Write | 1=DISABLE; 2=ENABLE | |
| BV | 9 | DHUMCFG_UNOCENAB | Unoccupied Dehum | Write | 1=DISABLE; 2=ENABLE | |
| BV | 19 | DHUMCFG_UFDHUMEN | Unoccupied Free Dehum | Write | 1=DISABLE; 2=ENABLE | |
| BV | 12 | DHUMCFG_DHUMVAV | VAV Cool Dehum | Write | 1=DISABLE; 2=ENABLE | |
| BV | 11 | DHUMCFG_DHUMVENT | Vent/None Dehum | Write | 1=DISABLE; 2=ENABLE | |
| AV | 152 | COMMADDR_AUX1 | AUX | Read | ||
| AV | 159 | COMMADDR_COMP_A1 | Compressor A1 | Read | ||
| AV | 153 | COMMADDR_NGC1 | NGC IOB 1 | Read | ||
| AV | 166 | COMMADDR_ODF_1 | ODF 1 | Read | ||
| AV | 167 | COMMADDR_ODF_2 | ODF 2 | Read | ||
| AV | 168 | COMMADDR_ODF_3 | ODF 3 | Read | ||
| AV | 154 | COMMADDR_PD4_EXV1 | PD4 EXV | Read | ||
| AV | 171 | COMMADDR_PWREXH_1 | Power Exhaust 1 | Read | ||
| AV | 172 | COMMADDR_PWREXH_2 | Power Exhaust 2 | Read | ||
| AV | 169 | COMMADDR_RF_1 | Return Fan 1 | Read | ||
| AV | 170 | COMMADDR_RF_2 | Return Fan 2 | Read | ||
| AV | 155 | COMMADDR_SIOB1 | SIOB 1 | Read | ||
| AV | 156 | COMMADDR_SIOB2 | SIOB 2 | Read | ||
| AV | 157 | COMMADDR_SIOB3 | SIOB 3 | Read | ||
| AV | 160 | COMMADDR_IDF_1 | Supply Fan 1 | Read | ||
| AV | 161 | COMMADDR_IDF_2 | Supply Fan 2 | Read | ||
| AV | 162 | COMMADDR_IDF_3 | Supply Fan 3 | Read | ||
| AV | 163 | COMMADDR_IDF_4 | Supply Fan 4 | Read | ||
| AV | 164 | COMMADDR_IDF_5 | Supply Fan 5 | Read | ||
| AV | 165 | COMMADDR_IDF_6 | Supply Fan 6 | Read | ||
| AV | 158 | COMMADDR_SYSTEMVU | ZIOB | Read | ||
| BV | 39 | DISCIN_HPSA | Cir A HPS Switch | Read | 1=OPEN; 2=CLOSE | |
| BV | 40 | DISCIN_HPSB | Cir B HPS Switch | Read | 1=OPEN; 2=CLOSE | |
| BV | 33 | DISCIN_CNDOSW | COFS | Read | 1=OPEN; 2=CLOSE | |
| BV | 35 | DISCIN_CMPFBKA1 | Comp A1 Feedback | Read | 1=OFF; 2=ON | |
| BV | 36 | DISCIN_CMPFBKA2 | Comp A2 Feedback | Read | 1=OFF; 2=ON | |
| BV | 37 | DISCIN_CMPFBKB1 | Comp B1 Feedback | Read | 1=OFF; 2=ON | |
| BV | 38 | DISCIN_CMPFBKB2 | Comp B2 Feedback | Read | 1=OFF; 2=ON | |
| BV | 34 | DISCIN_DEHUMSW | Dehumidify Switch | Read | 1=OPEN; 2=CLOSE | |
| BV | 45 | DISCIN_DLS1 | DemandLimSwitch1 | Read | 1=OFF; 2=ON | |
| BV | 46 | DISCIN_DLS2 | DemandLimSwitch2 | Read | 1=OFF; 2=ON | |
| BV | 42 | DISCIN_ERV_FRST | ERV Frost Indicator | Read | 1=OFF; 2=ON | |
| BV | 43 | DISCIN_WHEEL_ST | ERV Motion Sensor | Read | 1=OFF; 2=ON | |
| BV | 44 | DISCIN_ERVFSS | ERV OD Filt Stat Switch | Read | 1=OFF; 2=ON | |
| BV | 30 | DISCIN_FILTSTAT | Filter Switch | Read | 1=CLEAN; 2=DIRTY | |
| BV | 49 | DISCIN_PRESSSW | Fire Press Switch | Read | 1=OFF; 2=ON | |
| BV | 25 | DISCIN_FIRESW | Fire Shutdown Switch | Read | 1=OPEN; 2=CLOSE | |
| BV | 32 | DISCIN_HT_ALARM | Heat Alarm | Read | 1=OPEN; 2=CLOSE | |
| BV | 22 | DISCIN_TSTAT_Y2 | Hi Cool Input (Y2) | Read | 1=OPEN; 2=CLOSE | |
| BV | 24 | DISCIN_TSTAT_W2 | Hi Heat Input (W2) | Read | 1=OPEN; 2=CLOSE | |
| BV | 51 | DISCIN_FRZSW | Hydronic Freeze Switch | Read | 1=OFF; 2=ON | |
| BV | 53 | DISCIN_IAQSW | IAQ Switch | Read | 1=OFF; 2=ON | |
| BV | 47 | DISCIN_IGCFANSW | IGC IDF Switch | Read | 1=OFF; 2=ON | |
| BV | 20 | DISCIN_TSTAT_G | Indoor Fan Input (G) | Read | 1=OPEN; 2=CLOSE | |
| BV | 31 | DISCIN_IDF_LSM | Indoor Fan Limit Switch | Read | 1=OPEN; 2=CLOSE | |
| BV | 58 | DISCIN_INRFGLK | Indoor RFG Sensor ALM | Read | 1=NORMAL; 2=ALARM | |
| BV | 21 | DISCIN_TSTAT_Y1 | Lo Cool Input (Y1) | Read | 1=OPEN; 2=CLOSE | |
| BV | 23 | DISCIN_TSTAT_W1 | Lo Heat Input (W1) | Read | 1=OPEN; 2=CLOSE | |
| BV | 56 | DISCIN_ENEGPRES | OAD Neg Pressure | Read | 1=OFF; 2=ON | |
| BV | 54 | DISCIN_OAQSW | OAQ Switch | Read | 1=OFF; 2=ON | |
| BV | 55 | DISCIN_ODENTHSW | Outdoor Enthalpy | Read | 1=OFF; 2=ON | |
| BV | 59 | DISCIN_OUTRFGLK | Outdoor RFG Sensor ALM | Read | 1=NORMAL; 2=ALARM | |
| BV | 28 | DISCIN_PMR_STAT | Phase Monitor | Read | 1=OPEN; 2=CLOSE | |
| BV | 48 | DISCIN_PFPSS | Pre Filter Switch | Read | 1=OFF; 2=ON | |
| BV | 52 | DISCIN_PPSS | Pressure Safety | Read | 1=OFF; 2=ON | |
| BV | 41 | DISCIN_RESW | Remote Switch | Read | 1=OPEN; 2=CLOSE | |
| BV | 29 | DISCIN_SHTDWNSW | Shutdown Switch | Read | 1=OFF; 2=ON | |
| BV | 26 | DISCIN_SMOKESW | Smoke Detector | Read | 1=OPEN; 2=CLOSE | |
| BV | 50 | DISCIN_EVACSW | Smoke Evac Switch | Read | 1=OFF; 2=ON | |
| BV | 27 | DISCIN_SMKPRGSW | Smoke Purge Switch | Read | 1=OPEN; 2=CLOSE | |
| BV | 57 | DISCIN_VSOLSWA | VS Oil Level Switch A | Read | 1=OFF; 2=ON | |
| BV | 73 | DISCOUT_RH3PRLY | 3rd Party Reheat Relay | Read | 1=OFF; 2=ON | |
| BVmin | 83 | DISCOUT_ALMOUT | Alarm | Read | 1=OFF; 2=ON | |
| BV | 70 | DISCOUT_CCHRA | CCH A | Read | 1=OFF; 2=ON | |
| BV | 71 | DISCOUT_CCHRB | CCH B | Read | 1=OFF; 2=ON | |
| BV | 67 | DISCOUT_ODF1 | CF 1 Relay | Read | 1=OFF; 2=ON | |
| BV | 68 | DISCOUT_ODF2 | CF 2 Relay | Read | 1=OFF; 2=ON | |
| BV | 69 | DISCOUT_ODF3 | CF 3 Relay | Read | 1=OFF; 2=ON | |
| BV | 61 | DISCOUT_CMPRELA1 | Comp A1 Modulation RLY | Read | 1=OPEN; 2=CLOSE | |
| BV | 63 | DISCOUT_CMPRELA2 | Comp A2 Modulation RLY | Read | 1=OPEN; 2=CLOSE | |
| BV | 60 | DISCOUT_CPA1 | Compressor A1 | Read | 1=OFF; 2=ON | |
| BV | 62 | DISCOUT_CPA2 | Compressor A2 | Read | 1=OFF; 2=ON | |
| BV | 64 | DISCOUT_CPB1 | Compressor B1 | Read | 1=OFF; 2=ON | |
| BV | 65 | DISCOUT_CPB2 | Compressor B2 | Read | 1=OFF; 2=ON | |
| BV | 81 | DISCOUT_BYP_DAMP | ERV Bypass Damper | Read | 1=OFF; 2=ON | |
| BV | 74 | DISCOUT_ERVWHEEL | ERV Wheel | Read | 1=OFF; 2=ON | |
| BV | 90 | DISCOUT_AUTOADDR | Fan Auto Address | Read | 1=OFF; 2=ON | |
| BV | 75 | DISCOUT_STGHEAT1 | Heat Enable 1 | Read | 1=OFF; 2=ON | |
| BV | 76 | DISCOUT_STGHEAT2 | Heat Enable 2 | Read | 1=OFF; 2=ON | |
| BV | 77 | DISCOUT_STGHEAT3 | Heat Enable 3 | Read | 1=OFF; 2=ON | |
| BV | 78 | DISCOUT_STGHEAT4 | Heat Enable 4 | Read | 1=OFF; 2=ON | |
| BV | 79 | DISCOUT_STGHEAT5 | Heat Enable 5 | Read | 1=OFF; 2=ON | |
| BV | 80 | DISCOUT_STGHEAT6 | Heat Enable 6 | Read | 1=OFF; 2=ON | |
| BV | 84 | DISCOUT_HIR | Heat Interlock Relay | Read | 1=OFF; 2=ON | |
| BV | 86 | DISCOUT_HRR | Heat Reclaim | Read | 1=OFF; 2=ON | |
| BV | 85 | DISCOUT_HMFR | Humidifier | Read | 1=OFF; 2=ON | |
| BV | 66 | DISCOUT_IDFBYREL | IDF VFD Bypass Relay | Read | 1=OFF; 2=ON | |
| BV | 87 | DISCOUT_PEA | Power Exh A | Read | 1=OFF; 2=ON | |
| BV | 88 | DISCOUT_PEB | Power Exh B | Read | 1=OFF; 2=ON | |
| BV | 89 | DISCOUT_PEC | Power Exh C | Read | 1=OFF; 2=ON | |
| AV | 219 | DISCOUT_POWEXH1 | Power Exhaust Enable | Read | ||
| BV | 72 | DISCOUT_HMS | Reheat 3-way valve | Read | 1=OFF; 2=ON | |
| BV | 445 | DISCOUT_VSCA1_SS | VSC A1 Safe Stop | Read | 1=OFF; 2=ON | |
| BV | 82 | DISCOUT_ZDOR | Zone Damper Override RLY | Read | 1=OFF; 2=ON | |
| AV | 260 | ERVCFG_CHKTYPE | ERV Check Type (default 0, 0 to 2) | Write | ||
| AV | 262 | ERVCFG_ENTTOL | ERV Enthalpy Tolerance (default 2, 0 to 2) | BTU/lb | Write | |
| AV | 265 | ERVCFG_ERVMINPS | ERV Fan Damper Min Pos (default 10, 0 to 100) | % | Write | |
| AV | 264 | ERVCFG_MAXBYPCL | ERV Fan Max Bypass Close (default 100, 0 to 100) | % | Write | |
| AV | 263 | ERVCFG_MAXBYPOP | ERV Fan Max Bypass Open (default 100, 0 to 100) | % | Write | |
| AV | 269 | ERVCFG_OFFENTDB | ERV Off Enthalpy DB (default 0.5, 0 to 2) | BTU/lb | Write | |
| AV | 268 | ERVCFG_OFFTMPDB | ERV Off Temp DB (default 5, 0 to 10) | Δ°F | Write | |
| AV | 261 | ERVCFG_TMPTOL | ERV Temp Tolerance (default 10, 0 to 20) | Δ°F | Write | |
| AV | 267 | ERVCFG_ERVEFMIN | ERV Wheel Exh Min Speed (default 0, 0 to 100) | % | Write | |
| AV | 266 | ERVCFG_WHMINPOS | ERV Wheel-Minimum Pos (default 10, 0 to 100) | % | Write | |
| BV | 108 | EQUIPCFG_RH3PEN | 3rd Party Reheat Enable | Write | 1=DISABLE; 2=ENABLE | |
| BV | 101 | EQUIPCFG_ALARMEN | Alarm Output | Write | 1=DISABLE; 2=ENABLE | |
| AV | 256 | EQUIPCFG_AUXRELAY | Aux Relay (default 0, 0 to 2) | Write | ||
| BV | 123 | EQUIPCFG_CONDEN | COFS | Write | 1=DISABLE; 2=ENABLE | |
| BV | 122 | EQUIPCFG_DMDRSTEN | Demand Reset Switch | Write | 1=DISABLE; 2=ENABLE | |
| BV | 93 | EQUIPCFG_DMDLIM | Demand/Capacity Anlg In | Write | 1=DISABLE; 2=ENABLE | |
| BV | 102 | EQUIPCFG_EATEN | EAT Sensor | Write | 1=DISABLE; 2=ENABLE | |
| BV | 117 | EQUIPCFG_ECONEN | Economizer (OAD) | Write | 1=DISABLE; 2=ENABLE | |
| BV | 99 | EQUIPCFG_SHTDWNEN | Emergency Shutdown En | Write | 1=DISABLE; 2=ENABLE | |
| BV | 124 | EQUIPCFG_ENTHSWEN | Enthalpy Switch | Write | 1=DISABLE; 2=ENABLE | |
| BV | 110 | EQUIPCFG_ERVEN | ERV | Write | 1=DISABLE; 2=ENABLE | |
| BV | 112 | EQUIPCFG_ERVBYPEN | ERV Bypass Damper | Write | 1=DISABLE; 2=ENABLE | |
| BV | 111 | EQUIPCFG_ERVOAFEN | ERV OAF | Write | 1=DISABLE; 2=ENABLE | |
| BV | 114 | EQUIPCFG_EVACEN | Evacuation Switch | Write | 1=DISABLE; 2=ENABLE | |
| BV | 107 | EQUIPCFG_EF3PEN | EXF 3rd Party Mod | Write | 1=DISABLE; 2=ENABLE | |
| BV | 116 | EQUIPCFG_EFEN | Exhaust Fan | Write | 1=DISABLE; 2=ENABLE | |
| BV | 113 | EQUIPCFG_FIRESWEN | Fire Switch | Write | 1=DISABLE; 2=ENABLE | |
| AV | 303 | EQUIPCFG_FRZSWEN | Freeze Switch | Read | ||
| BV | 118 | EQUIPCFG_HT1EN | Heat Stage 1 Relay | Write | 1=DISABLE; 2=ENABLE | |
| BV | 119 | EQUIPCFG_HT2EN | Heat Stage 2 Relay | Write | 1=DISABLE; 2=ENABLE | |
| BV | 120 | EQUIPCFG_HT3EN | Heat Stage 3 Relay | Write | 1=DISABLE; 2=ENABLE | |
| BV | 121 | EQUIPCFG_HT4EN | Heat Stage 4 Relay | Write | 1=DISABLE; 2=ENABLE | |
| BV | 96 | EQUIPCFG_HUMSWEN | Humidistat | Write | 1=DISABLE; 2=ENABLE | |
| BV | 127 | EQUIPCFG_IAQSWEN | IAQ Switch | Write | 1=DISABLE; 2=ENABLE | |
| AV | 257 | EQUIPCFG_SIO1AI10 | IAQ/OAD Input Config (default 0, 0 to 5) | Write | ||
| BV | 125 | EQUIPCFG_IAQOREN | IAQ-OD Pos Reset Enable | Write | 1=DISABLE; 2=ENABLE | |
| BV | 105 | EQUIPCFG_SF3PEN | IDF 3rd Party Mod | Write | 1=DISABLE; 2=ENABLE | |
| BV | 104 | EQUIPCFG_IDFVFDBY | IDF VFD Bypass | Write | 1=DISABLE; 2=ENABLE | |
| BV | 103 | EQUIPCFG_OACFMEN | OACFM Sensor | Write | 1=DISABLE; 2=ENABLE | |
| BV | 109 | EQUIPCFG_OAD3PEN | OAD 3rd Party Mod | Write | 1=DISABLE; 2=ENABLE | |
| BV | 126 | EQUIPCFG_OAQSWEN | OAQ Switch | Write | 1=DISABLE; 2=ENABLE | |
| BV | 98 | EQUIPCFG_PMREN | Phase Monitor | Write | 1=DISABLE; 2=ENABLE | |
| BV | 97 | EQUIPCFG_FILTSWEN | Pre-Filter Switch | Write | 1=DISABLE; 2=ENABLE | |
| BV | 115 | EQUIPCFG_PRESSEN | Pressurization Switch | Write | 1=DISABLE; 2=ENABLE | |
| AV | 255 | EQUIPCFG_RESWEN | Remote Input (default 0, 0 to 2) | Write | ||
| AV | 574 | EQUIPCFG_SIO3DI7 | Select IAQ or OAQ Switch (default 0, 0 to 2) | Write | ||
| BV | 94 | EQUIPCFG_SMOKEEN | Smoke Detector | Write | 1=DISABLE; 2=ENABLE | |
| BV | 106 | EQUIPCFG_SPSREN | SPSR Sensor | Write | 1=DISABLE; 2=ENABLE | |
| BV | 95 | EQUIPCFG_TSTATEN | Thermostat | Write | 1=DISABLE; 2=ENABLE | |
| BV | 100 | EQUIPCFG_ZDOREN | ZDOR | Write | 1=DISABLE; 2=ENABLE | |
| AV | 235 | EFCFG_CONTROL | EXF Control Config (default 0, 0 to 3) | Write | ||
| AV | 249 | EFCFG_EXFEVAC | EXF Evacuation Speed (default 0, 0 to 100) | % | Write | |
| AV | 237 | EFCFG_MAXSPD | EXF Max Speed (default 50, 20 to 100) | % | Write | |
| AV | 236 | EFCFG_MINSPD | EXF Min Speed (default 10, 0 to 100) | % | Write | |
| AV | 240 | EFCFG_DAMPPOS1 | EXF OAD Pos 1 (default 50, 0 to 100) | % | Write | |
| AV | 241 | EFCFG_DAMPPOS2 | EXF OAD Pos 2 (default 100, 0 to 100) | % | Write | |
| AV | 242 | EFCFG_PEOAD1 | EXF OAD Position 1 (default 25, 0 to 100) | % | Write | |
| AV | 243 | EFCFG_PEOAD2 | EXF OAD Position 2 (default 50, 0 to 100) | % | Write | |
| AV | 244 | EFCFG_PEOAD3 | EXF OAD Position 3 (default 75, 0 to 100) | % | Write | |
| AV | 245 | EFCFG_PEOAD4 | EXF OAD Position 4 (default 100, 0 to 100) | % | Write | |
| AV | 246 | EFCFG_PEOAD5 | EXF OAD Position 5 (default 100, 0 to 100) | % | Write | |
| AV | 247 | EFCFG_PEOAD6 | EXF OAD Position 6 (default 100, 0 to 100) | % | Write | |
| AV | 248 | EFCFG_EXFPURGE | EXF Smoke Purge Speed (default 0, 0 to 100) | % | Write | |
| AV | 238 | EFCFG_SPEED1 | EXF Speed OAD Pos 1 (default 25, 0 to 100) | % | Write | |
| AV | 239 | EFCFG_SPEED2 | EXF Speed OAD Pos 2 (default 50, 0 to 100) | % | Write | |
| AV | 85 | EFCFG_RAP_TH | Ret Air Press Threshold (default -0.4, -1 to 1) | in. w.c. | Write | |
| AV | 250 | EFSTP_EFBPSPT | Building Pressure (default 0.05, -0.3 to 0.3) | in. w.c. | Write | |
| AV | 278 | FRECLCFG_CHNGSEL | Changeover Select (default 0, 0 to 3) | Write | ||
| AV | 282 | FRECLCFG_DIFFDBTH | Diff Dry Bulb Threshold (default 0, 0 to 10) | °F | Write | |
| AV | 279 | FRECLCFG_DIFFENTH | Diff Enthalpy Threshold (default 0.5, 0 to 2) | BTU/lb | Write | |
| BV | 132 | FRECLCFG_DRYBLB | Dry Bulb Chngeover (OAT) | Write | 1=DISABLE; 2=ENABLE | |
| AV | 473 | FRECLCFG_FCOOL_TG | Free Cool Timeguard (default 5, 0 to 30) | min | Write | |
| AV | 283 | FRECLCFG_IAQOADRS | IAQ Switch OAD Pos Reset (default -10, -100 to 0) | % | Write | |
| BV | 133 | FRECLCFG_DEWLIM | OADP Limit Check | Write | 1=DISABLE; 2=ENABLE | |
| AV | 281 | FRECLCFG_DEWLIMTH | OADP Threshold (default 55, 50 to 62) | °F | Write | |
| BV | 147 | FRECLCFG_ODAIRQ | OAQ Check | Write | 1=DISABLE; 2=ENABLE | |
| AV | 395 | FRECLCFG_ODAIRQTH | OAQ Lockout (default 1300, 1000 to 2000) | ppm | Write | |
| AV | 280 | FRECLCFG_DRYBLBTH | OAT Dry Bulb Threshold (default 75, -40 to 120) | °F | Write | |
| BV | 130 | FRECLCFG_FREECLEN | Occ Free Cool | Write | 1=DISABLE; 2=ENABLE | |
| BV | 131 | FRECLCFG_UFC | Unocc Free Cooling | Write | 1=DISABLE; 2=ENABLE | |
| AV | 309 | HEATCFG_HT2DTG | Heat 2Stage Dn Timeguard (default 120, 30 to 300) | s | Write | |
| AV | 310 | HEATCFG_HT2UTG | Heat 2Stage Up Timeguard (default 120, 30 to 300) | s | Write | |
| AV | 312 | HEATCFG_HEAT_FOD | Heat Fan Off Delay Timer (default 45, 30 to 120) | s | Write | |
| BV | 135 | HEATCFG_HTTEMPCL | Heat Tempered Cooling | Write | 1=DISABLE; 2=ENABLE | |
| AV | 306 | HEATCFG_HEATTTDB | Heat Tempered Cooling DB (default 0) | Write | ||
| BV | 134 | HEATCFG_HTMPDVNT | Heat Tempered Venting | Write | 1=DISABLE; 2=ENABLE | |
| AV | 307 | HEATCFG_HTTREND | Heat Trend Level (default 0.1, 0.1 to 5) | °F | Write | |
| AV | 308 | HEATCFG_HTTNDTM | Heat Trend Time (default 120, 30 to 600) | s | Write | |
| BV | 137 | HEATCFG_HEAT_EBL | Morning Warmup Only | Write | 1=DISABLE; 2=ENABLE | |
| AV | 318 | HEATSTP_HODAHHT | 100% OA High Heat SAT (default 85, 65 to 125) | °F | Write | |
| AV | 317 | HEATSTP_HODALHT | 100% OA Low Heat SAT (default 75, 65 to 125) | °F | Write | |
| AV | 321 | HEATCFG_DOHIHTON | Hi Heat On DB (default 1, 0.5 to 20) | °F | Write | |
| AV | 316 | HEATSTP_SAHIHTSP | Hi Heat SAT (default 95, 60 to 125) | °F | Write | |
| AV | 320 | HEATCFG_DOLOHTOF | Lo Heat Off DB (default 1, 0.5 to 2) | °F | Write | |
| AV | 319 | HEATCFG_DOLOHTON | Lo Heat On DB (default 1, 0 to 2) | °F | Write | |
| AV | 315 | HEATSTP_SALOHTSP | Lo Heat SAT (default 85, 60 to 125) | °F | Write | |
| AVmin | 313 | HEATSTP_HTSP_OCC | Occupied Heating (default 68, 55 to 80) | °F | Write | |
| AV | 314 | HEATSTP_HTSP_UNO | Unoccupied Heating (default 58, 40 to 99) | °F | Write | |
| AV | 328 | IDFCFG_IDFCSPD2 | Hi Cool IDF Speed (default 100, 0 to 100) | % | Write | |
| AV | 333 | IDFCFG_IDFHSPD2 | Hi Heat IDF Speed (default 100, 0 to 100) | % | Write | |
| AV | 322 | IDFCFG_OPSELECT | IDF Control (default 1, 0 to 8) | Write | ||
| AV | 336 | IDFCFG_IDFEVAC | IDF Evacuation Speed (default 34, 0 to 100) | % | Write | |
| AV | 335 | IDFCFG_IDFPRESS | IDF Pressurization Speed (default 34, 0 to 100) | % | Write | |
| AV | 334 | IDFCFG_IDFPURGE | IDF PURGE Speed (default 34, 0 to 100) | % | Write | |
| AV | 325 | IDFCFG_IDFMXSPD | Indoor Fan Max Speed (default 100, 0 to 100) | % | Write | |
| AV | 324 | IDFCFG_IDFMNSPD | Indoor Fan Min Speed (default 34, 0 to 100) | % | Write | |
| AV | 326 | IDFCFG_IDFCSPD1 | Lo Cool IDF Speed (default 66, 0 to 100) | % | Write | |
| AV | 332 | IDFCFG_IDFHSPD1 | Lo Heat IDF Speed (default 66, 0 to 100) | % | Write | |
| AV | 327 | IDFCFG_IDFMCSPD | Med Cool IDF Speed (default 88, 0 to 100) | % | Write | |
| AV | 337 | IDFCFG_OCCUCFG | Occupied Fan (default 0, 0 to 1) | Write | ||
| AV | 331 | IDFCFG_SAVHCCTH | SAV High Cool Cap Thresh (default 90, 0 to 100) | % | Write | |
| AV | 329 | IDFCFG_SAVLCCTH | SAV Low Cool Cap Thresh (default 70, 0 to 100) | % | Write | |
| AV | 330 | IDFCFG_SAVMCCTH | SAV Med Cool Cap Thresh (default 75, 0 to 100) | % | Write | |
| AV | 323 | IDFCFG_SAVTYPE | SAV Mode Selection (default 0, 0 to 1) | Write | ||
| AV | 341 | IDFCFG_SDPRTIME | SDP Reset Time (default 15, 5 to 30) | min | Write | |
| AV | 342 | IDFCFG_SDPRZDP | SDP Reset ZDP Threshold (default 85, 40 to 100) | % | Write | |
| AV | 288 | IDFCFG_SDPRLMIT | SP Reset Limit | in. w.c. | Read | |
| AV | 340 | IDFCFG_SDPRRTIO | SP Reset Ratio (default 0.2, 0 to 3) | in. w.c. | Write | |
| AV | 339 | IDFCFG_SDPRS | SP Reset Source (default 0, 0 to 5) | Write | ||
| AV | 338 | IDFCFG_UNOCCFG | Unoccupied Fan (default 0, 0 to 1) | Write | ||
| AV | 345 | IDFSTP_AIRFLOW | Air Flow Setpoint (default 1200, 0 to 50000) | cfm | Write | |
| AV | 343 | IDFSTP_CO2LVL | CO2 Level (default 2000, 0 to 2000) | ppm | Write | |
| AV | 344 | IDFSTP_DUCTSET | Supply Pressure (default 1.5, 0 to 2.5) | in. w.c. | Write | |
| AV | 287 | IDFSTP_ZPSETPT | Zone Pressure | in. w.c. | Read | |
| AV | 221 | DMDLMCFG_AICLSEL | Analog Limit Mode (default 0, 0 to 2) | Write | ||
| AV | 305 | DMDLMCFG_DMDCPEN | Capacity Limit Enable | Read | ||
| AV | 222 | DMDLMCFG_CAPLMSRC | Capacity Limit Source (default 0, 0 to 3) | Write | ||
| AV | 226 | COOLSTP_DMDLIMS1 | Cool Demand Limit S1 (default 4, 0 to 10) | Δ°F | Write | |
| AV | 227 | COOLSTP_DMDLIMS2 | Cool Demand Limit S2 (default 6, 0 to 10) | Δ°F | Write | |
| AV | 304 | DMDLMCFG_DMDLMEN | Demand Limit Enable | Read | ||
| AV | 220 | DMDLMCFG_DMDLMSRC | Demand Limit Source (default 0, 0 to 3) | Write | ||
| BV | 91 | DMDLMCFG_DLSWSEN | Demand Switch Enable | Write | 1=DISABLE; 2=ENABLE | |
| AV | 234 | HEATSTP_DMDRSTHT | Dmd Reset Heat Adjust (default 4, 0 to 10) | °F | Write | |
| AV | 229 | HEATSTP_CAPLIMS1 | Heat Capacity Limit S1 (default 50, 0 to 100) | % | Write | |
| AV | 230 | HEATSTP_CAPLIMS2 | Heat Capacity Limit S2 (default 0, 0 to 100) | % | Write | |
| AV | 231 | HEATSTP_DMDLIMS1 | Heat Demand Limit S1 (default 4, 0 to 10) | Δ°F | Write | |
| AV | 232 | HEATSTP_DMDLIMS2 | Heat Demand Limit S2 (default 6, 0 to 10) | Δ°F | Write | |
| AV | 223 | COOLSTP_CLCAPSTP | Max Cool Capacity (default 100, 50 to 100) | % | Write | |
| AV | 228 | HEATSTP_HTCAPSTP | Max Heat Capacity (default 100, 50 to 100) | % | Write | |
| MV | 7 | MDESTS_ODF1MDN | CF 1 Mode | Read | 1=NONE; 2=MANUAL; 3=DP_OPT; 4=DP_LOW; 5=DP_LOW; 6=DP_HIGH; 7=DT_HIGH | |
| MV | 8 | MDESTS_ODF2MDN | CF 2 Mode | Read | 1=NONE; 2=MANUAL; 3=DP_OPT; 4=DP_LOW; 5=DP_LOW; 6=DP_HIGH; 7=DT_HIGH | |
| MV | 9 | MDESTS_ODF3MDN | CF 3 Mode | Read | 1=NONE; 2=MANUAL; 3=DP_OPT; 4=DP_LOW; 5=DP_LOW; 6=DP_HIGH; 7=DT_HIGH | |
| MV | 1 | MDESTS_CIRCAMDN | Circuit A Mode | Read | 1=NORMAL; 2=TEST | |
| MV | 2 | MDESTS_CIRCBMDN | Circuit B Mode | Read | 1=NORMAL; 2=TEST | |
| MV | 3 | MDESTS_CMPA1MDN | Comp A1 Mode | Read | 1=NONE; 2=MANUAL; 3=FLD_TEMP; 4=DP_HIGH; 5=DP; 6=LOW; 7=P_HIGH; 8=SP_LOW; 9=DT_HIGH; 10=MOTTMPHI; 11=FLDTMPHI; 12=INVTMPHI; 13=RCTTMPHI; 14=OILVISLO; 15=MOTCURHI; 16=CMPSURGE; 17=MODE_MAX; 18=DP_HIGHF; 19=SP_LOWF | |
| MV | 4 | MDESTS_CMPA2MDN | Comp A2 Mode | Read | 1=NONE; 2=MANUAL; 3=FLD_TEMP; 4=DP_HIGH; 5=DP; 6=LOW; 7=P_HIGH; 8=SP_LOW; 9=DT_HIGH; 10=MOTTMPHI; 11=FLDTMPHI; 12=INVTMPHI; 13=RCTTMPHI; 14=OILVISLO; 15=MOTCURHI; 16=CMPSURGE; 17=MODE_MAX; 18=DP_HIGHF; 19=SP_LOWF | |
| MV | 5 | MDESTS_CMPB1MDN | Comp B1 Mode | Read | 1=NONE; 2=MANUAL; 3=FLD_TEMP; 4=DP_HIGH; 5=DP; 6=LOW; 7=P_HIGH; 8=SP_LOW; 9=DT_HIGH; 10=MOTTMPHI; 11=FLDTMPHI; 12=INVTMPHI; 13=RCTTMPHI; 14=OILVISLO; 15=MOTCURHI; 16=CMPSURGE; 17=MODE_MAX; 18=DP_HIGHF; 19=SP_LOWF | |
| MV | 6 | MDESTS_CMPB2MDN | Comp B2 Mode | Read | 1=NONE; 2=MANUAL; 3=FLD_TEMP; 4=DP_HIGH; 5=DP; 6=LOW; 7=P_HIGH; 8=SP_LOW; 9=DT_HIGH; 10=MOTTMPHI; 11=FLDTMPHI; 12=INVTMPHI; 13=RCTTMPHI; 14=OILVISLO; 15=MOTCURHI; 16=CMPSURGE; 17=MODE_MAX; 18=DP_HIGHF; 19=SP_LOWF | |
| AV | 290 | MDESTS_DMD_DET | Demand Determination | Read | ||
| BV | 138 | MDESTS_ERVCHECK | ERV Check Status | Read | 1=FALSE; 2=TRUE | |
| MV | 11 | MDESTS_HEATRMDN | Heater Mode | Read | 1=NONE; 2=SAT; 3=RAT; 4=ZONE; 5=MAT; 6=EXTERNAL, MANUAL; 7=SAT; 8=RAT; 9=ZONE; 10=MAT; 11=EXTERNAL, MANUAL | |
| MV | 10 | MDESTS_IDFMDNUM | Indoor Fan Mode | Read | 1=NONE; 2=MANUAL; 3=SDP_NOM; 4=SDP_HIGH; 5=SDP_LOW; 6=CO2_NOM; 7=CO2_LOW; 8=CTLFLUID; 9=SST_LOW; 10=ST_LOW; 11=FLOW_NOM; 12=BP_NOM; 13=BP_HIGH, BP_LOW, TRACK, ON | |
| MV | 12 | MDESTS_ECONMNUM | OAD Mode | Read | 1=NONE; 2=MANUAL; 3=AMB_FLOW; 4=MNAIRQLY; 5=NOM_TRAC; 6=SAT; 7=IAQ_OVR; 8=AMBFLWSW | |
| AV | 291 | MDESTS_OP_STATE | Operational State | Read | ||
| BV | 139 | MDESTS_DHUMPURG | Reheat Oil Purge | Read | 1=OFF; 2=ON | |
| BV | 177 | MDESTS_MODETCST | Temp Compensated Start | Read | 1=OFF; 2=ON | |
| AV | 353 | ANALOGIN_EF3P_NET | Net 3rd Party EXF (default 0) | % | Write | |
| AV | 355 | ANALOGIN_SF3P_NET | Net 3rd Party IDF (default 0) | % | Write | |
| AV | 354 | ANALOGIN_OD3P_NET | Net 3rd Party OAD (default 0) | % | Write | |
| AV | 352 | AIRPRESS_BPNET | Net Building Pressure (default 0) | in. w.c. | Write | |
| AV | 351 | ANALOGIN_IAQORNET | Net IAQ OAD Pos Reset (default 0) | % | Write | |
| AV | 358 | ANALOGIN_IAQRNET | Net IAQ Reset (default 0) | ppm | Write | |
| AV | 357 | ANALOGIN_IAQNET | Net Indoor Air Quality (default 0) | ppm | Write | |
| AV | 350 | ANALOGIN_OCFMRNET | Net OA CFM Reset (default 0) | cfm | Write | |
| AV | 362 | AIRTEMP_OATNET | Net OAT (default 0) | °F | Write | |
| AV | 349 | ANALOGIN_OACFMNET | Net Outdoor Air CFM (default 0) | cfm | Write | |
| AV | 356 | ANALOGIN_OAQNET | Net Outdoor Air Quality (default 0) | ppm | Write | |
| AV | 348 | ANALOGIN_RARHNET | Net RARH (default 0) | % | Write | |
| AV | 364 | ANALOGIN_SPSR_NET | Net SP Reset (default 0, 0 to 5) | in. w.c. | Write | |
| AV | 361 | AIRTEMP_SPTONET | Net Space Temp Offset (default 0) | °F | Write | |
| AV | 347 | ANALOGIN_SPRHNET | Net SPRH (default 0) | % | Write | |
| AV | 360 | AIRTEMP_SPTNET | Net SPT (default 0) | °F | Write | |
| AV | 365 | ANALOGIN_ZDPNET | Net Zone Damper Position (default 0) | % | Write | |
| BV | 145 | NETIN_G_NET | Network G | Write | 1=OFF; 2=ON | |
| BV | 146 | NETIN_HSTATNET | Network HSTAT | Write | 1=OFF; 2=ON | |
| AV | 359 | AIRPRESS_SDP_NET | Network Supply Pressure (default 0) | in. w.c. | Write | |
| BV | 143 | NETIN_W1_NET | Network W1 | Write | 1=OFF; 2=ON | |
| BV | 144 | NETIN_W2_NET | Network W2 | Write | 1=OFF; 2=ON | |
| BV | 141 | NETIN_Y1_NET | Network Y1 | Write | 1=OFF; 2=ON | |
| BV | 142 | NETIN_Y2_NET | Network Y2 | Write | 1=OFF; 2=ON | |
| AV | 398 | OADCFG_OABPORDB | Bld Pressure Deadband (default 0.01, 0 to 0.05) | in. w.c. | Write | |
| AV | 396 | OADCFG_OABPOREN | Bld Pressure Override En (default 0, 0 to 1) | Write | ||
| AV | 397 | OADCFG_OABPORTH | Bld Pressure Threshold (default 0.02, 0 to 0.2) | in. w.c. | Write | |
| AV | 392 | OADCFG_IAQCFMRS | IAQ OA CFM Reset (default 0, -40000 to 0) | cfm | Write | |
| AV | 369 | OADCFG_IAQOCFG | IAQ Override Conf (default 0, 0 to 2) | Write | ||
| AV | 384 | OADCFG_IAQODB | IAQ Override Deadband (default 200, 100 to 1000) | ppm | Write | |
| AV | 385 | OADCFG_IAQOPOS | IAQ Override Position (default 50, 0 to 100) | % | Write | |
| AV | 383 | OADCFG_IAQOTH | IAQ Override Threshold (default 1200, 400 to 2000) | ppm | Write | |
| BV | 149 | OADCFG_IAQPOP | IAQ Pre-Occ Purge | Write | 1=DISABLE; 2=ENABLE | |
| AV | 386 | OADCFG_IAQPDUR | IAQ Purge Duration (default 15, 5 to 60) | min | Write | |
| AV | 391 | OADCFG_IAQPHITP | IAQ Purge Hi Temp Pos (default 35, 0 to 100) | % | Write | |
| AV | 390 | OADCFG_IAQPLOTP | IAQ Purge Lo Temp Pos (default 10, 0 to 100) | % | Write | |
| AV | 387 | OADCFG_IAQPLOCK | IAQ Purge Lockout (default 50, 35 to 70) | °F | Write | |
| AV | 389 | OADCFG_IAQPRGHL | IAQ Purge OAT Hi Lockout (default 95, 85 to 115) | °F | Write | |
| AV | 388 | OADCFG_IAQPRGLL | IAQ Purge OAT Lo Lockout (default 45, 0 to 50) | °F | Write | |
| AV | 382 | OADCFG_IAQRESET | IAQ Reset Source (default 0, 0 to 3) | Write | ||
| BV | 148 | OADCFG_IAQSBVEN | IAQ Vent Standby Demand | Write | 1=DISABLE; 2=ENABLE | |
| AV | 374 | IDFCFG_VENTSPD1 | IDF Vent Speed 1 (default 66, 0 to 100) | % | Write | |
| AV | 375 | IDFCFG_VENTSPD2 | IDF Vent Speed 2 (default 70, 0 to 100) | % | Write | |
| AV | 376 | IDFCFG_VENTSPD3 | IDF Vent Speed 3 (default 80, 0 to 100) | % | Write | |
| AV | 377 | IDFCFG_VENTSPD4 | IDF Vent Speed 4 (default 100, 0 to 100) | % | Write | |
| AV | 372 | OADCFG_MINOADCP | Min OAD Control Point (default 75, 0 to 100) | % | Write | |
| AV | 378 | OADCFG_OADPOS1 | OA Damper Vent Pos 1 (default 60, 0 to 100) | % | Write | |
| AV | 379 | OADCFG_OADPOS2 | OA Damper Vent Pos 2 (default 38, 0 to 100) | % | Write | |
| AV | 380 | OADCFG_OADPOS3 | OA Damper Vent Pos 3 (default 30, 0 to 100) | % | Write | |
| AV | 381 | OADCFG_OADPOS4 | OA Damper Vent Pos 4 (default 0, 0 to 100) | % | Write | |
| BV | 17 | OADCFG_OADHUMEN | OA Dehum Enable | Write | 1=DISABLE; 2=ENABLE | |
| AV | 399 | OADCFG_CFMSP | OACFM Setpoint (default 780, 0 to 20000) | cfm | Write | |
| AV | 57 | OADCFG_FLTGAP | OAD Fault Detect Gap (default 5, 2 to 100) | % | Write | |
| AV | 58 | OADCFG_FLTTIME | OAD Fault Detect Time (default 20, 10 to 240) | s | Write | |
| AV | 371 | OADCFG_MAXPOS | OAD Max Position (default 100, 0 to 100) | % | Write | |
| AV | 370 | OADCFG_MINPOS | OAD Min Position (default 10, 0 to 100) | % | Write | |
| AV | 373 | OADCFG_OADEVAC | OAD Smoke Evac Speed (default 0, 0 to 100) | % | Write | |
| AV | 394 | OADCFG_PRGLONG | Purge Long Duration (default 60, 10 to 60) | min | Write | |
| AV | 393 | OADCFG_PRGSHORT | Purge Short Duration (default 20, 5 to 30) | min | Write | |
| AV | 368 | OADCFG_ECONCTRL | Ventilation Control (default 0, 0 to 5) | Write | ||
| BV | 207 | UNITCFG_AUTRST | Auto Restart | Write | 1=OFF; 2=ON | |
| AV | 259 | UNITCFG_OCC_OT | Occupancy Override Time (default 2, 0 to 4) | h | Write | |
| BV | 179 | OCCSB | Occupied Standby | Read | 1=DISABLE; 2=ENABLE | |
| BV | 92 | OCCSB_EN | Occupied Standby Enable | Write | 1=DISABLE; 2=ENABLE | |
| AV | 366 | OCCSBNET | Occupied Standby Net (default 0) | Write | ||
| AV | 258 | OCCSTNDT | Occupied Standby Time (default 5, 5 to 30) | min | Write | |
| AV | 367 | ZS_OCCSB | Occupied Standby ZS (default 0) | Write | ||
| AV | 453 | RUNTIME_CCHRA_RT | CCH A Minutes | Read | ||
| AV | 455 | RUNTIME_CCHRA_RC | CCH A Reset Count | Read | ||
| AV | 454 | RUNTIME_CCHRA_SC | CCH A Start Count | Read | ||
| AV | 456 | RUNTIME_CCHRB_RT | CCH B Minutes | Read | ||
| AV | 458 | RUNTIME_CCHRB_RC | CCH B Reset Count | Read | ||
| AV | 457 | RUNTIME_CCHRB_SC | CCH B Start Count | Read | ||
| AV | 429 | RUNTIME_CND1_RT | CF 1 Minutes | Read | ||
| AV | 431 | RUNTIME_CND1_RC | CF 1 Reset Count | Read | ||
| AV | 430 | RUNTIME_CND1_SC | CF 1 Start Count | Read | ||
| AV | 432 | RUNTIME_CND2_RT | CF 2 Minutes | Read | ||
| AV | 434 | RUNTIME_CND2_RC | CF 2 Reset Count | Read | ||
| AV | 433 | RUNTIME_CND2_SC | CF 2 Start Count | Read | ||
| AV | 435 | RUNTIME_CND3_RT | CF 3 Minutes | Read | ||
| AV | 437 | RUNTIME_CND3_RC | CF 3 Reset Count | Read | ||
| AV | 436 | RUNTIME_CND3_SC | CF 3 Start Count | Read | ||
| AV | 417 | RUNTIME_COMPA1RT | Comp A1 Minutes | Read | ||
| AV | 419 | RUNTIME_COMPA1RC | Comp A1 Reset Count | Read | ||
| AV | 418 | RUNTIME_COMPA1SC | Comp A1 Start Count | Read | ||
| AV | 420 | RUNTIME_COMPA2RT | Comp A2 Minutes | Read | ||
| AV | 422 | RUNTIME_COMPA2RC | Comp A2 Reset Count | Read | ||
| AV | 421 | RUNTIME_COMPA2SC | Comp A2 Start Count | Read | ||
| AV | 423 | RUNTIME_COMPB1RT | Comp B1 Minutes | Read | ||
| AV | 425 | RUNTIME_COMPB1RC | Comp B1 Reset Count | Read | ||
| AV | 424 | RUNTIME_COMPB1SC | Comp B1 Start Count | Read | ||
| AV | 426 | RUNTIME_COMPB2RT | Comp B2 Minutes | Read | ||
| AV | 428 | RUNTIME_COMPB2RC | Comp B2 Reset Count | Read | ||
| AV | 427 | RUNTIME_COMPB2SC | Comp B2 Start Count | Read | ||
| AV | 441 | RUNTIME_EFAN_RT | Exhaust Fan Minutes | Read | ||
| AV | 443 | RUNTIME_EFAN_RC | Exhaust Fan Reset Count | Read | ||
| AV | 442 | RUNTIME_EFAN_SC | Exhaust Fan Start Count | Read | ||
| AV | 446 | RUNTIME_SHEAT_RC | Heat Reset Count | Read | ||
| AV | 444 | RUNTIME_SHEAT_RT | Heat Minutes | Read | ||
| AV | 445 | RUNTIME_SHEAT_SC | Heat Start Count | Read | ||
| AV | 447 | RUNTIME_HMVLV_RT | HGRH Valve Minutes | Read | ||
| AV | 449 | RUNTIME_HMVLV_RC | HGRH Valve Reset Count | Read | ||
| AV | 448 | RUNTIME_HMVLV_SC | HGRH Valve Start Count | Read | ||
| AV | 465 | RUNTIME_HUMPUSC | Humdimizer Cycle Cnt | Read | ||
| AV | 438 | RUNTIME_IDF_RT | Indoor Fan Minutes | Read | ||
| AV | 440 | RUNTIME_IDF_RC | Indoor Fan Reset Count | Read | ||
| AV | 439 | RUNTIME_IDF_SC | Indoor Fan Start Count | Read | ||
| AV | 450 | RUNTIME_DAMP_RT | OAD Minutes | Read | ||
| AV | 452 | RUNTIME_DAMP_RC | OAD Reset Count | Read | ||
| AV | 451 | RUNTIME_DAMP_SC | OAD Start Count | Read | ||
| AV | 459 | RUNTIME_OILACYSC | Oil Cir A Count | Read | ||
| AV | 460 | RUNTIME_OILBCYSC | Oil Cir B Count | Read | ||
| AV | 274 | EXVSTP_EXVSTA1 | A1 Start Pos (default 35, 0 to 100) | % | Write | |
| AV | 270 | EXVSTP_SupHtA1 | A1 Superheat Setpoint (default 0) | °F | Write | |
| AV | 408 | RFGTEMP_SSHA1 | A1 Superheat Temp | °F | Read | |
| AV | 275 | EXVSTP_EXVSTA2 | A2 Start Pos (default 35, 0 to 100) | % | Write | |
| AV | 271 | EXVSTP_SupHtA2 | A2 Superheat Setpoint (default 0) | °F | Write | |
| AV | 409 | RFGTEMP_SSHA2 | A2 Superheat Temp | °F | Read | |
| AV | 276 | EXVSTP_EXVSTB1 | B1 Start Pos (default 35, 0 to 100) | % | Write | |
| AV | 272 | EXVSTP_SupHtB1 | B1 Superheat Setpoint (default 0) | °F | Write | |
| AV | 410 | RFGTEMP_SSHB1 | B1 Superheat Temp | °F | Read | |
| AV | 277 | EXVSTP_EXVSTB2 | B2 Start Pos (default 35, 0 to 100) | % | Write | |
| AV | 273 | EXVSTP_SupHtB2 | B2 Superheat Setpoint (default 0) | °F | Write | |
| AV | 411 | RFGTEMP_SSHB2 | B2 Superheat Temp | °F | Read | |
| AV | 471 | COOLCFG_CCHTHA | CCH A OAT Lockout (default 80, 50 to 90) | °F | Write | |
| AV | 472 | COOLCFG_CCHTHB | CCH B OAT Lockout (default 80, 50 to 90) | °F | Write | |
| AV | 497 | COOLCFG_CFSPDMX1 | CF Speed MAX (default 100) | % | Write | |
| AV | 496 | COOLCFG_CFSPDMN1 | CF Speed MIN (default 0) | % | Write | |
| BV | 172 | CNDSTP_SPDStpEN | CF User Start Spd Enab | Write | 1=DISABLE; 2=ENABLE | |
| AV | 498 | COOLCFG_CFSTSPD1 | CF User Start Speed (default 0) | % | Write | |
| AV | 402 | RFGPRESS_DPA | Cir A Discharge Pressure | psig | Read | |
| AV | 462 | CMPASTS_ORTMLFTA | Cir A Oil Rec Time Left | s | Read | |
| AV | 400 | RFGPRESS_SPA | Cir A Suction Pressure | psig | Read | |
| AV | 346 | CMPASTS_BOOSTSTA | Cir A VSC Boost State | Read | ||
| AV | 403 | RFGPRESS_DPB | Cir B Discharge Pressure | psig | Read | |
| AV | 464 | CMPBSTS_ORTMLFTB | Cir B Oil Rec Time Left | s | Read | |
| AV | 401 | RFGPRESS_SPB | Cir B Suction Pressure | psig | Read | |
| AV | 474 | COOLSTP_CMPMAXA1 | Cmp Nominal Spd Max A1 (default 100) | % | Write | |
| AV | 476 | COOLSTP_CMPMAXA2 | Cmp Nominal Spd Max A2 (default 100) | % | Write | |
| AV | 478 | COOLSTP_CMPMAXB1 | Cmp Nominal Spd Max B1 (default 100) | % | Write | |
| AV | 480 | COOLSTP_CMPMAXB2 | Cmp Nominal Spd Max B2 (default 100) | % | Write | |
| AV | 475 | COOLSTP_CMPMINA1 | Cmp Nominal Spd Min A1 (default 0) | % | Write | |
| AV | 477 | COOLSTP_CMPMINA2 | Cmp Nominal Spd Min A2 (default 0) | % | Write | |
| AV | 479 | COOLSTP_CMPMINB1 | Cmp Nominal Spd Min B1 (default 0) | % | Write | |
| AV | 481 | COOLSTP_CMPMINB2 | Cmp Nominal Spd Min B2 (default 0) | % | Write | |
| AV | 88 | CMPFLRTM | Compressor Failure Timer (default 5, 2 to 20) | s | Write | |
| AV | 87 | CMPSTKTM | Compressor Stuck On Time (default 4, 2 to 20) | s | Write | |
| AV | 212 | DHUMCFG_CCBYPTME | Con Coil Bypass Time (default 0) | min | Write | |
| AV | 213 | DHUMCFG_CCPRGPOS | Cond Coil Purge Pos (default 50) | % | Write | |
| AV | 214 | DHUMCFG_CCPRGTME | Cond Coil Purge Time (default 10) | min | Write | |
| AV | 293 | RFGTEMP_CCT | Cooling Coil Temp | °F | Read | |
| AV | 506 | DHUMCFG_OILTIME | Dehum Oil Recov Time (default 60, 0 to 120) | min | Write | |
| AV | 300 | RFGTEMP_DGTA | Discharge Gas Temp A | °F | Read | |
| AV | 523 | OUTPUTS_EXVA1OBJ | EXV A1 Objective | Read | ||
| AV | 524 | OUTPUTS_EXVA2OBJ | EXV A2 Objective | Read | ||
| AV | 525 | OUTPUTS_EXVB1OBJ | EXV B1 Objective | Read | ||
| AV | 526 | OUTPUTS_EXVB2OBJ | EXV B2 Objective | Read | ||
| AV | 89 | HEATSINK_HSCTRLOF | Heat Sink Ctrl Offset (default 10, 0 to 20) | °F | Write | |
| AV | 211 | DHUMCFG_RHTCLTME | HGRH Coil Closed Time (default 45, 5 to 120) | min | Write | |
| AV | 210 | DHUMCFG_RHTOPTME | HGRH Coil Open Time (default 2, 1 to 5) | min | Write | |
| AV | 489 | DHUMCFG_RHSTART | HGRH Start Pos (default 5, 0 to 100) | % | Write | |
| AV | 490 | DHUMCFG_RHTIME | HGRH Startup Time (default 30, 0 to 120) | s | Write | |
| AV | 488 | DHUMCFG_RHMAXPOS | HGRH Valve Max Pos (default 99, 50 to 100) | % | Write | |
| AV | 487 | DHUMCFG_RHMINPOS | HGRH Valve Min Pos (default 1, 0 to 50) | % | Write | |
| AV | 91 | HEATSINK_HSHTEMP | High Heat Sink Temp (default 200, 100 to 250) | °F | Write | |
| AV | 90 | HEATSINK_HSHTMPDB | High Heat Sink Temp DB (default 8, 0 to 20) | °F | Write | |
| AV | 209 | DHUMCFG_DHMATLCK | High MT Dehum Lockout (default 105, 90 to 115) | °F | Write | |
| AV | 301 | HMZR_CONDPURG | Humidizer Purge | Read | ||
| AV | 519 | CMPA1STS_LOADREQ | Load Request Comp A1 | Read | ||
| AV | 520 | CMPA2STS_LOADREQ | Load Request Comp A2 | Read | ||
| AV | 521 | CMPB1STS_LOADREQ | Load Request Comp B1 | Read | ||
| AV | 522 | CMPB2STS_LOADREQ | Load Request Comp B2 | Read | ||
| BV | 174 | COOLCFG_LCRCO | Low Cap Req Comp On | Write | 1=NO; 2=YES | |
| AV | 73 | LPRTIME | Low Pressure Ratio Time (default 30, 5 to 120) | s | Write | |
| BV | 129 | EXVSTP_EXVSTENB | Manual Start Pos Enable | Write | 1=DISABLE; 2=ENABLE | |
| AV | 505 | DHUMCFG_OILHITH | Oil Recov High Thld (default 50, 0 to 100) | % | Write | |
| AV | 504 | DHUMCFG_OILLOWTH | Oil Recov Low Thld (default 20, 0 to 100) | % | Write | |
| AV | 461 | CMPASTS_OILRECAC | Oil Recovery Actv Cir A | Read | ||
| AV | 463 | CMPBSTS_OILRECAC | Oil Recovery Actv Cir B | Read | ||
| AV | 416 | RFGTEMP_OILTSMPA | Oil Sump Temp | °F | Read | |
| AV | 406 | RFGTEMP_SDTA | Saturated Discharge CirA | °F | Read | |
| AV | 407 | RFGTEMP_SDTB | Saturated Discharge CirB | °F | Read | |
| AV | 404 | RFGTEMP_SSTA | Saturated Suction A | °F | Read | |
| AV | 405 | RFGTEMP_SSTB | Saturated Suction B | °F | Read | |
| AV | 485 | COOLCFG_SCT_HLIM | SCT High Limit (default 115, 100 to 140) | °F | Write | |
| AV | 486 | COOLCFG_SCT_LLIM | SCT Low Limit (default 80, 40 to 90) | °F | Write | |
| AV | 539 | CMPASTS_SDTABSMX | SDT Abs Max Cir A | Read | ||
| AV | 543 | CMPBSTS_SDTABSMX | SDT Abs Max Cir B | Read | ||
| AV | 538 | CMPASTS_SDTABSMN | SDT Abs Min Cir A | Read | ||
| AV | 542 | CMPBSTS_SDTABSMN | SDT Abs Min Cir B | Read | ||
| AV | 535 | CMPBSTS_SDTENVMX | SDT Env Max Cir B | Read | ||
| AV | 531 | CMPASTS_SDTENVMX | SDT Env Max CirA | Read | ||
| AV | 534 | CMPBSTS_SDTENVMN | SDT Env Min Cir B | Read | ||
| AV | 530 | CMPASTS_SDTENVMN | SDT Env Min CirA | Read | ||
| AV | 493 | CNDSTP_SDTTEMP1 | SDT Setpoint 1 (default 0) | °F | Write | |
| AV | 494 | CNDSTP_SDTTEMP2 | SDT Setpoint 2 (default 0) | °F | Write | |
| AV | 495 | CNDSTP_SDTTEMP3 | SDT Setpoint 3 (default 0) | °F | Write | |
| BV | 171 | CNDSTP_SDTStpEn | SDT Setpoint Enable | Write | 1=DISABLE; 2=ENABLE | |
| AV | 541 | CMPBSTS_SSTABSMX | SST Abs Max Cir B | Read | ||
| AV | 537 | CMPASTS_SSTABSMX | SST Abs Max CirA | Read | ||
| AV | 540 | CMPBSTS_SSTABSMN | SST Abs Min Cir B | Read | ||
| AV | 536 | CMPASTS_SSTABSMN | SST Abs Min CirA | Read | ||
| AV | 533 | CMPBSTS_SSTENVMX | SST Env Max Cir B | Read | ||
| AV | 529 | CMPASTS_SSTENVMX | SST Env Max CirA | Read | ||
| AV | 532 | CMPBSTS_SSTENVMN | SST Env Min Cir B | Read | ||
| AV | 528 | CMPASTS_SSTENVMN | SST Env Min CirA | Read | ||
| AV | 299 | RFGTEMP_SGT1 | Suction Gas Temp 1 | °F | Read | |
| AV | 412 | RFGTEMP_SGTA1 | Suction Gas Temp Cir A1 | °F | Read | |
| AV | 413 | RFGTEMP_SGTA2 | Suction Gas Temp Cir A2 | °F | Read | |
| AV | 414 | RFGTEMP_SGTB1 | Suction Gas Temp Cir B1 | °F | Read | |
| AV | 415 | RFGTEMP_SGTB2 | Suction Gas Temp Cir B2 | °F | Read | |
| BV | 128 | EXVSTP_SETPTENB | User Setpoint Enable | Write | 1=DISABLE; 2=ENABLE | |
| BV | 175 | COOLCFG_VSCFS_OR | VSC Fixed Speed Override | Write | 1=DISABLE; 2=ENABLE | |
| BV | 136 | SVCOUT_CMTRNDAH | Add Heat Comfort Trend | Write | 1=DISABLE; 2=ENABLE | |
| MV | 20 | STATES_ODF2STN | CF 2 State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 21 | STATES_ODF3STN | CF 3 State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 13 | STATES_CIRCASTN | Circuit A State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 14 | STATES_CIRCBSTN | Circuit B State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 15 | STATES_CMPA1STN | Comp A1 State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 16 | STATES_CMPA2STN | Comp A2 State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 17 | STATES_CMPB1STN | Comp B1 State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 18 | STATES_CMPB2STN | Comp B2 State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| BV | 8 | SVCOUT_CMTRNDAC | Cool Comfort Trending | Write | 1=DISABLE; 2=ENABLE | |
| BV | 176 | STATES_OKTOFRCL | Free Cooling Available | Read | 1=YES; 2=NO | |
| BV | 180 | STATES_OKTOFDHM | Free Dehum Status | Read | 1=DISABLE; 2=ENABLE | |
| MV | 24 | STATES_HEATRSTN | Heater State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 23 | STATES_RHTSTNUM | HGRH State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MVmin | 22 | STATES_IDFNUM | Indoor Fan State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 25 | STATES_ECONNUM | OAD State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| MV | 26 | STATES_OCCSRNUM | Occupancy Source | Read | 1=DefaultSchedule; 2=LocalSchedule; 3=BMSSchedule; 4=RemoteSwitch; 5=TimedOverride; 6=Linkage; 7=Forced; 8=MotionSensing | |
| MV | 19 | STATES_ODF1STN | ODF A State | Read | 1=OFF; 2=NOT_RDY; 3=READY; 4=STARTING; 5=RUNNING; 6=STOPPING; 7=DISABLE; 8=TRIPOUT | |
| BV | 178 | STATES_PURGEACT | Pre-Occ Purge State | Read | 1=OFF; 2=ON | |
| AV | 516 | STATES_MINTILOC | Time Until Next Occupied | min | Read | |
| BV | 206 | SWTCHCFG_ALARMINV | Alarm Relay | Write | 1=NORMAL; 2=INVERTED | |
| BV | 200 | SWTCHCFG_CMPA1INV | Compressor A1 | Write | 1=NORMAL; 2=INVERTED | |
| BV | 201 | SWTCHCFG_CMPA2INV | Compressor A2 | Write | 1=NORMAL; 2=INVERTED | |
| BV | 182 | SWTCHCFG_CNDSWINV | Condensate Ovrflw Switch | Write | 1=NORMAL; 2=INVERTED | |
| BV | 202 | SWTCHCFG_CCHRAINV | Crankcase Heater A | Write | 1=NORMAL; 2=INVERTED | |
| BV | 199 | SWTCHCFG_DORINV | Damper Override Relay | Write | 1=NORMAL; 2=INVERTED | |
| BV | 204 | SWTCHCFG_EVBYPINV | ERV Bypass Damper | Write | 1=NORMAL; 2=INVERTED | |
| BV | 196 | SWTCHCFG_FRSTINV | ERV Frost Indication | Write | 1=NORMAL; 2=INVERTED | |
| BV | 205 | SWTCHCFG_ERVINV | ERV Wheel | Write | 1=NORMAL; 2=INVERTED | |
| BV | 197 | SWTCHCFG_WHLSTINV | ERV Wheel Motion Sensor | Write | 1=NORMAL; 2=INVERTED | |
| BV | 203 | SWTCHCFG_PEENINV | EXF Enable | Write | 1=NORMAL; 2=INVERTED | |
| BV | 192 | SWTCHCFG_FLTSWINV | Filter Status Switch | Write | 1=NORMAL; 2=INVERTED | |
| BV | 195 | SWTCHCFG_FRESWINV | Fire Shutdown | Write | 1=NORMAL; 2=INVERTED | |
| BV | 181 | SWTCHCFG_HTALMINV | Heat Alarm/Limit Switch | Write | 1=NORMAL; 2=INVERTED | |
| BV | 198 | SWTCHCFG_HTENINV | Heat Enable | Write | 1=NORMAL; 2=INVERTED | |
| BV | 185 | SWTCHCFG_HPSAINV | High Pressure Switch | Write | 1=NORMAL; 2=INVERTED | |
| BV | 189 | SWTCHCFG_DHMSWINV | Humidistat Switch | Write | 1=NORMAL; 2=INVERTED | |
| BV | 184 | SWTCHCFG_IDFSWINV | Indoor Fan Limit Switch | Write | 1=NORMAL; 2=INVERTED | |
| BV | 194 | SWTCHCFG_PMRSWINV | Phase Monitor | Write | 1=NORMAL; 2=INVERTED | |
| BV | 193 | SWTCHCFG_RESWINV | Remote Input | Write | 1=NORMAL; 2=INVERTED | |
| BV | 183 | SWTCHCFG_SMKSWINV | Smoke Detector | Write | 1=NORMAL; 2=INVERTED | |
| BV | 186 | SWTCHCFG_TSTGINV | Thermostat G | Write | 1=NORMAL; 2=INVERTED | |
| BV | 190 | SWTCHCFG_TSTW1INV | Thermostat W1 | Write | 1=NORMAL; 2=INVERTED | |
| BV | 191 | SWTCHCFG_TSTW2INV | Thermostat W2 | Write | 1=NORMAL; 2=INVERTED | |
| BV | 187 | SWTCHCFG_TSTY1INV | Thermostat Y1 | Write | 1=NORMAL; 2=INVERTED | |
| BV | 188 | SWTCHCFG_TSTY2INV | Thermostat Y2 | Write | 1=NORMAL; 2=INVERTED | |
| AV | 286 | HCSTATUS_CAPACT | Cooling Capacity | Read | ||
| AV | 466 | GENUINIT_FILT_RT | Filter Minutes | Read | ||
| AV | 297 | FILTER_STATUS | Filter Status | Read | ||
| AV | 284 | HCSTATUS_HEATREQ | Heat Request from UI | % | Read | |
| AV | 292 | GENUNIT_HEATCOOL | Heat/Cool status | Read | ||
| BV | 6 | IDFFDBK_STATUS | IDF Feedback Status | Read | 1=DISABLE; 2=ENABLE | |
| BV | 140 | LINK_ACT | Linkage Active | Read | 1=NO; 2=YES | |
| AVmin | 363 | GENUNIT_NETOCC | Network Occupancy (default 2, 0 to 2) | Write | ||
| AVmin | 289 | GENUNIT_OCCUPIED | Occupied | Read | ||
| AV | 43 | GENUNIT_PREFLTR_LIM | Pre-Filter Press Limit (default 1.5, 0.5 to 5) | in. w.c. | Write | |
| AV | 42 | GENUNIT_PREFLTR_SRC | Pre-Filter Source (default 0, 0 to 3) | Write | ||
| BV | 167 | GENUNIT_FLTR_RST | Reset Filter Hours | Write | 1=NO; 2=YES | |
| AV | 285 | HCSTATUS_SATCTLPT | Supply Air Temp Cntrl Pt | Read | ||
| AV | 567 | GENUNIT_SMAXCCAP | Sys Max Cool Cap | % | Read | |
| AV | 568 | GENUNIT_SMAXHCAP | Sys Max Heat Cap | % | Read |
No points match these filters.
Object ID lookup: Carrier 48/50K and 48/50V Rooftop point IDs by name
AV3AIRPRESS_BPAV15AIRTEMP_DXLATAV14AIRTEMP_EFF_CPAV11AIRTEMP_EATAV10AIRTEMP_MATAV120AIRTEMP_OADPAV9AIRTEMP_OATAV1AIRPRESS_RAPAV6AIRTEMP_RATAV7AIRTEMP_SPTAV8AIRTEMP_SPTOAV13AIRTEMP_LATAV12AIRTEMP_LSTAV123AIRTEMP_SADPAV4AIRTEMP_SATAV5AIRTEMP_SATOAV2AIRPRESS_SDPBV1ALARMRST_RST_ALMAV35ALERTCFG_BP_HLMTAV34ALERTCFG_BP_LLMTAV74ALERTCFG_COFS_ACTAV76ALERTCFG_COFS_TMEAV75ALERTCFG_COFS_TRPAV60ALERTCFG_CP_C_THAV54ALERTCFG_CMPCMD_TAV45ALERTCFG2_ERV_ALRTAV59ALERTCFG_POSTFLAV48ALERTCFG_HIGH_SSTAV40ALERTCFG_IAQ_HLMTBV4ALERTCFG_LOCK_OUTBV448LPALMENAV575LPALMHYSAV72ALERTCFG_LPRLAV65ALERTCFG_SSHALOWAV67ALERTCFG_SSHAFLLOAV66ALERTCFG_SSHAPLLOAV71ALERTCFG_LSSHTIMEAV68ALERTCFG_SSHBLOWAV70ALERTCFG_SSHBFLLOAV69ALERTCFG_SSHBPLLOAV63ALERTCFG_LSST1TAV64ALERTCFG_LSST20sTAV62ALERTCFG_LSST2TAV61ALERTCFG_LSST4TAV50ALERTCFG_MINDISAAV52ALERTCFG_MINDISBAV49ALERTCFG_MINSUCAAV51ALERTCFG_MINSUCBAV56ALERTCFG_ECMINCFMAV39ALERTCFG_OAT_HLMTAV38ALERTCFG_OAT_LLMTAV53ALERTCFG_OFF_PRESAV55ALERTCFG_OCFMSENSAV41ALERTCFG_MAINFLTAV31ALERTCFG_RARH_HTAV30ALERTCFG_RARH_LTAV27ALERTCFG_RATHLMTOAV28ALERTCFG_RATHLMTUAV26ALERTCFG_RATLLMTOAV29ALERTCFG_RATLLMTUAV37ALERTCFG_SAT_HTMPAV23ALERTCFG_SATHLMTOAV25ALERTCFG_SATHLMTUAV36ALERTCFG_SAT_LTMPAV22ALERTCFG_SATLLMTOAV24ALERTCFG_SATLLMTUAV33ALERTCFG_SP_HLMTAV32ALERTCFG_SP_LLMTAV16ALERTCFG_SPRHHLAV17ALERTCFG_SPRHLLAV19ALERTCFG_SPTHLMTOAV21ALERTCFG_SPTHLMTUAV18ALERTCFG_SPTLLMTOAV20ALERTCFG_SPTLLMTUAV86ALERTCFG_MSDPTBV5ALERTCFG_T24ENABAV83ALERTCFG_T24ECMAXAV82ALERTCFG_T24ECMINAV84ALERTCFG_HCDELAYAV80ALERTCFG_MOVEDTECAV77ALERTCFG_OARADIFFAV79ALERTCFG_SATCHNGEAV78ALERTCFG_SATMOVEAV81ALERTCFG_SASETTLEAV135ANALOGIN_ODF1SPDAV136ANALOGIN_ODF2SPDAV137ANALOGIN_ODF3SPDAV131ANALOGIN_CMPA1SPDAV132ANALOGIN_CMPA2SPDAV133ANALOGIN_CMPB1SPDAV134ANALOGIN_CMPB2SPDAV146ANALOGIN_DLCAV114ANALOGIN_EF3P_CMDAV140ANALOGIN_EFSPDAV141ANALOGIN_EXV_A1AV142ANALOGIN_EXV_A2AV143ANALOGIN_EXV_B1AV144ANALOGIN_EXV_B2AV148ANALOGIN_FFPDAV130ANALOGIN_HMD2AV129ANALOGIN_HMDAV116ANALOGIN_IAQOPRSTAV115ANALOGIN_SF3P_CMDAV138ANALOGIN_IDFSPDAV139ANALOGIN_IDFRPMAV117ANALOGIN_IAQAV125ANALOGIN_MARHAV113ANALOGIN_OD3P_CMDAV127ANALOGIN_DAMPPOSAV111ANALOGIN_OACFMAV112ANALOGIN_OACFMRSTAV149ANALOGIN_OA_ENTHAV118ANALOGIN_OAQAV119ANALOGIN_OARHAV147ANALOGIN_PFPDAV128ANALOGIN_DAMPPOS2AV150ANALOGIN_RA_ENTHAV121ANALOGIN_RARHAV124ANALOGIN_SPRHAV145ANALOGIN_SPSRAV122ANALOGIN_SARHAV126ANALOGIN_ZDPAV94ANALGOUT_HEATCMDAV104ANALGOUT_ODF1CMDAV105ANALGOUT_ODF2CMDAV106ANALGOUT_ODF3CMDAV99ANALGOUT_CMPA1CMDAV100ANALGOUT_CMPA2CMDAV101ANALGOUT_CMPB1CMDAV102ANALGOUT_CMPB2CMDAV98ANALGOUT_ERV_OAFAV97ANALGOUT_EFCMDAV107ANALGOUT_EXVA1CMDAV108ANALGOUT_EXVA2CMDAV109ANALGOUT_EXVB1CMDAV110ANALGOUT_EXVB2CMDAV96ANALGOUT_HMV2AV95ANALGOUT_HMVAV103ANALGOUT_IDFCMDAV92ANALGOUT_DAMPCMDAV93ANALGOUT_DAMPCMD2AV295BACNET_loc_occMV27BACNET_ALC_COLORAV294BACNET_SCH_ObjjAV573BACNET_ALC_PRIMEAV193COOLCFG_GAP_CLHTBV7COOLCFG_TMPDVNTAV191COOLCFG_CLTRENDAV192COOLCFG_CLTNDTMAV186COOLCFG_DEMANDAV483COOLCFG_SATHI_DBAV482COOLCFG_SATLO_DBAV190COOLCFG_RSTLMITAV189COOLCFG_RSTRTIOAV188COOLCFG_TPCTLRSTAV187COOLCFG_SPLYDBAV296COOLSTP_HODACLSPAV200COOLSTP_HODAHCLAV199COOLSTP_HODALCLAV224COOLSTP_CAPLIMS1AV225COOLSTP_CAPLIMS2AV233COOLSTP_DMDRSTCLAV203COOLCFG_DOHICLONAV198COOLSTP_SAHICLSPAV202COOLCFG_DOLOCLOFAV201COOLCFG_DOLOCLONAV197COOLSTP_SALOCLSPAV195COOLSTP_CLSP_OCCAV527COOLSTP_ACTV_SPAV196COOLSTP_CLSP_UNOAV206COOLCFG_DOVAVCOFAV205COOLCFG_DOVAVCONAV204COOLSTP_VAVCLSPAV207COOLSTP_SPLYAVSPAV218DHUMSTP_CCTSTPAV484DHUMCFG_DHUMMODEAV208DHUMCFG_DMD_SRCAV215DHUMSTP_DHUMRHSPAV217DHUMCFG_RLOS_OFFAV216DHUMCFG_RLOS_ONAV302DHUMSTP_DHUMSADPBV13DHUMCFG_DHUMHICLBV15DHUMCFG_DHUMHIHTBV14DHUMCFG_DHUMLOCLBV16DHUMCFG_DHUMLOHTBV18DHUMCFG_OFDHUMENBV10DHUMCFG_SUPPHEATBV9DHUMCFG_UNOCENABBV19DHUMCFG_UFDHUMENBV12DHUMCFG_DHUMVAVBV11DHUMCFG_DHUMVENTAV152COMMADDR_AUX1AV159COMMADDR_COMP_A1AV153COMMADDR_NGC1AV166COMMADDR_ODF_1AV167COMMADDR_ODF_2AV168COMMADDR_ODF_3AV154COMMADDR_PD4_EXV1AV171COMMADDR_PWREXH_1AV172COMMADDR_PWREXH_2AV169COMMADDR_RF_1AV170COMMADDR_RF_2AV155COMMADDR_SIOB1AV156COMMADDR_SIOB2AV157COMMADDR_SIOB3AV160COMMADDR_IDF_1AV161COMMADDR_IDF_2AV162COMMADDR_IDF_3AV163COMMADDR_IDF_4AV164COMMADDR_IDF_5AV165COMMADDR_IDF_6AV158COMMADDR_SYSTEMVUBV39DISCIN_HPSABV40DISCIN_HPSBBV33DISCIN_CNDOSWBV35DISCIN_CMPFBKA1BV36DISCIN_CMPFBKA2BV37DISCIN_CMPFBKB1BV38DISCIN_CMPFBKB2BV34DISCIN_DEHUMSWBV45DISCIN_DLS1BV46DISCIN_DLS2BV42DISCIN_ERV_FRSTBV43DISCIN_WHEEL_STBV44DISCIN_ERVFSSBV30DISCIN_FILTSTATBV49DISCIN_PRESSSWBV25DISCIN_FIRESWBV32DISCIN_HT_ALARMBV22DISCIN_TSTAT_Y2BV24DISCIN_TSTAT_W2BV51DISCIN_FRZSWBV53DISCIN_IAQSWBV47DISCIN_IGCFANSWBV20DISCIN_TSTAT_GBV31DISCIN_IDF_LSMBV58DISCIN_INRFGLKBV21DISCIN_TSTAT_Y1BV23DISCIN_TSTAT_W1BV56DISCIN_ENEGPRESBV54DISCIN_OAQSWBV55DISCIN_ODENTHSWBV59DISCIN_OUTRFGLKBV28DISCIN_PMR_STATBV48DISCIN_PFPSSBV52DISCIN_PPSSBV41DISCIN_RESWBV29DISCIN_SHTDWNSWBV26DISCIN_SMOKESWBV50DISCIN_EVACSWBV27DISCIN_SMKPRGSWBV57DISCIN_VSOLSWABV73DISCOUT_RH3PRLYBV83DISCOUT_ALMOUTBV70DISCOUT_CCHRABV71DISCOUT_CCHRBBV67DISCOUT_ODF1BV68DISCOUT_ODF2BV69DISCOUT_ODF3BV61DISCOUT_CMPRELA1BV63DISCOUT_CMPRELA2BV60DISCOUT_CPA1BV62DISCOUT_CPA2BV64DISCOUT_CPB1BV65DISCOUT_CPB2BV81DISCOUT_BYP_DAMPBV74DISCOUT_ERVWHEELBV90DISCOUT_AUTOADDRBV75DISCOUT_STGHEAT1BV76DISCOUT_STGHEAT2BV77DISCOUT_STGHEAT3BV78DISCOUT_STGHEAT4BV79DISCOUT_STGHEAT5BV80DISCOUT_STGHEAT6BV84DISCOUT_HIRBV86DISCOUT_HRRBV85DISCOUT_HMFRBV66DISCOUT_IDFBYRELBV87DISCOUT_PEABV88DISCOUT_PEBBV89DISCOUT_PECAV219DISCOUT_POWEXH1BV72DISCOUT_HMSBV445DISCOUT_VSCA1_SSBV82DISCOUT_ZDORAV260ERVCFG_CHKTYPEAV262ERVCFG_ENTTOLAV265ERVCFG_ERVMINPSAV264ERVCFG_MAXBYPCLAV263ERVCFG_MAXBYPOPAV269ERVCFG_OFFENTDBAV268ERVCFG_OFFTMPDBAV261ERVCFG_TMPTOLAV267ERVCFG_ERVEFMINAV266ERVCFG_WHMINPOSBV108EQUIPCFG_RH3PENBV101EQUIPCFG_ALARMENAV256EQUIPCFG_AUXRELAYBV123EQUIPCFG_CONDENBV122EQUIPCFG_DMDRSTENBV93EQUIPCFG_DMDLIMBV102EQUIPCFG_EATENBV117EQUIPCFG_ECONENBV99EQUIPCFG_SHTDWNENBV124EQUIPCFG_ENTHSWENBV110EQUIPCFG_ERVENBV112EQUIPCFG_ERVBYPENBV111EQUIPCFG_ERVOAFENBV114EQUIPCFG_EVACENBV107EQUIPCFG_EF3PENBV116EQUIPCFG_EFENBV113EQUIPCFG_FIRESWENAV303EQUIPCFG_FRZSWENBV118EQUIPCFG_HT1ENBV119EQUIPCFG_HT2ENBV120EQUIPCFG_HT3ENBV121EQUIPCFG_HT4ENBV96EQUIPCFG_HUMSWENBV127EQUIPCFG_IAQSWENAV257EQUIPCFG_SIO1AI10BV125EQUIPCFG_IAQORENBV105EQUIPCFG_SF3PENBV104EQUIPCFG_IDFVFDBYBV103EQUIPCFG_OACFMENBV109EQUIPCFG_OAD3PENBV126EQUIPCFG_OAQSWENBV98EQUIPCFG_PMRENBV97EQUIPCFG_FILTSWENBV115EQUIPCFG_PRESSENAV255EQUIPCFG_RESWENAV574EQUIPCFG_SIO3DI7BV94EQUIPCFG_SMOKEENBV106EQUIPCFG_SPSRENBV95EQUIPCFG_TSTATENBV100EQUIPCFG_ZDORENAV235EFCFG_CONTROLAV249EFCFG_EXFEVACAV237EFCFG_MAXSPDAV236EFCFG_MINSPDAV240EFCFG_DAMPPOS1AV241EFCFG_DAMPPOS2AV242EFCFG_PEOAD1AV243EFCFG_PEOAD2AV244EFCFG_PEOAD3AV245EFCFG_PEOAD4AV246EFCFG_PEOAD5AV247EFCFG_PEOAD6AV248EFCFG_EXFPURGEAV238EFCFG_SPEED1AV239EFCFG_SPEED2AV85EFCFG_RAP_THAV250EFSTP_EFBPSPTAV278FRECLCFG_CHNGSELAV282FRECLCFG_DIFFDBTHAV279FRECLCFG_DIFFENTHBV132FRECLCFG_DRYBLBAV473FRECLCFG_FCOOL_TGAV283FRECLCFG_IAQOADRSBV133FRECLCFG_DEWLIMAV281FRECLCFG_DEWLIMTHBV147FRECLCFG_ODAIRQAV395FRECLCFG_ODAIRQTHAV280FRECLCFG_DRYBLBTHBV130FRECLCFG_FREECLENBV131FRECLCFG_UFCAV309HEATCFG_HT2DTGAV310HEATCFG_HT2UTGAV312HEATCFG_HEAT_FODBV135HEATCFG_HTTEMPCLAV306HEATCFG_HEATTTDBBV134HEATCFG_HTMPDVNTAV307HEATCFG_HTTRENDAV308HEATCFG_HTTNDTMBV137HEATCFG_HEAT_EBLAV318HEATSTP_HODAHHTAV317HEATSTP_HODALHTAV321HEATCFG_DOHIHTONAV316HEATSTP_SAHIHTSPAV320HEATCFG_DOLOHTOFAV319HEATCFG_DOLOHTONAV315HEATSTP_SALOHTSPAV313HEATSTP_HTSP_OCCAV314HEATSTP_HTSP_UNOAV328IDFCFG_IDFCSPD2AV333IDFCFG_IDFHSPD2AV322IDFCFG_OPSELECTAV336IDFCFG_IDFEVACAV335IDFCFG_IDFPRESSAV334IDFCFG_IDFPURGEAV325IDFCFG_IDFMXSPDAV324IDFCFG_IDFMNSPDAV326IDFCFG_IDFCSPD1AV332IDFCFG_IDFHSPD1AV327IDFCFG_IDFMCSPDAV337IDFCFG_OCCUCFGAV331IDFCFG_SAVHCCTHAV329IDFCFG_SAVLCCTHAV330IDFCFG_SAVMCCTHAV323IDFCFG_SAVTYPEAV341IDFCFG_SDPRTIMEAV342IDFCFG_SDPRZDPAV288IDFCFG_SDPRLMITAV340IDFCFG_SDPRRTIOAV339IDFCFG_SDPRSAV338IDFCFG_UNOCCFGAV345IDFSTP_AIRFLOWAV343IDFSTP_CO2LVLAV344IDFSTP_DUCTSETAV287IDFSTP_ZPSETPTAV221DMDLMCFG_AICLSELAV305DMDLMCFG_DMDCPENAV222DMDLMCFG_CAPLMSRCAV226COOLSTP_DMDLIMS1AV227COOLSTP_DMDLIMS2AV304DMDLMCFG_DMDLMENAV220DMDLMCFG_DMDLMSRCBV91DMDLMCFG_DLSWSENAV234HEATSTP_DMDRSTHTAV229HEATSTP_CAPLIMS1AV230HEATSTP_CAPLIMS2AV231HEATSTP_DMDLIMS1AV232HEATSTP_DMDLIMS2AV223COOLSTP_CLCAPSTPAV228HEATSTP_HTCAPSTPMV7MDESTS_ODF1MDNMV8MDESTS_ODF2MDNMV9MDESTS_ODF3MDNMV1MDESTS_CIRCAMDNMV2MDESTS_CIRCBMDNMV3MDESTS_CMPA1MDNMV4MDESTS_CMPA2MDNMV5MDESTS_CMPB1MDNMV6MDESTS_CMPB2MDNAV290MDESTS_DMD_DETBV138MDESTS_ERVCHECKMV11MDESTS_HEATRMDNMV10MDESTS_IDFMDNUMMV12MDESTS_ECONMNUMAV291MDESTS_OP_STATEBV139MDESTS_DHUMPURGBV177MDESTS_MODETCSTAV353ANALOGIN_EF3P_NETAV355ANALOGIN_SF3P_NETAV354ANALOGIN_OD3P_NETAV352AIRPRESS_BPNETAV351ANALOGIN_IAQORNETAV358ANALOGIN_IAQRNETAV357ANALOGIN_IAQNETAV350ANALOGIN_OCFMRNETAV362AIRTEMP_OATNETAV349ANALOGIN_OACFMNETAV356ANALOGIN_OAQNETAV348ANALOGIN_RARHNETAV364ANALOGIN_SPSR_NETAV361AIRTEMP_SPTONETAV347ANALOGIN_SPRHNETAV360AIRTEMP_SPTNETAV365ANALOGIN_ZDPNETBV145NETIN_G_NETBV146NETIN_HSTATNETAV359AIRPRESS_SDP_NETBV143NETIN_W1_NETBV144NETIN_W2_NETBV141NETIN_Y1_NETBV142NETIN_Y2_NETAV398OADCFG_OABPORDBAV396OADCFG_OABPORENAV397OADCFG_OABPORTHAV392OADCFG_IAQCFMRSAV369OADCFG_IAQOCFGAV384OADCFG_IAQODBAV385OADCFG_IAQOPOSAV383OADCFG_IAQOTHBV149OADCFG_IAQPOPAV386OADCFG_IAQPDURAV391OADCFG_IAQPHITPAV390OADCFG_IAQPLOTPAV387OADCFG_IAQPLOCKAV389OADCFG_IAQPRGHLAV388OADCFG_IAQPRGLLAV382OADCFG_IAQRESETBV148OADCFG_IAQSBVENAV374IDFCFG_VENTSPD1AV375IDFCFG_VENTSPD2AV376IDFCFG_VENTSPD3AV377IDFCFG_VENTSPD4AV372OADCFG_MINOADCPAV378OADCFG_OADPOS1AV379OADCFG_OADPOS2AV380OADCFG_OADPOS3AV381OADCFG_OADPOS4BV17OADCFG_OADHUMENAV399OADCFG_CFMSPAV57OADCFG_FLTGAPAV58OADCFG_FLTTIMEAV371OADCFG_MAXPOSAV370OADCFG_MINPOSAV373OADCFG_OADEVACAV394OADCFG_PRGLONGAV393OADCFG_PRGSHORTAV368OADCFG_ECONCTRLBV207UNITCFG_AUTRSTAV259UNITCFG_OCC_OTBV179OCCSBBV92OCCSB_ENAV366OCCSBNETAV258OCCSTNDTAV367ZS_OCCSBAV453RUNTIME_CCHRA_RTAV455RUNTIME_CCHRA_RCAV454RUNTIME_CCHRA_SCAV456RUNTIME_CCHRB_RTAV458RUNTIME_CCHRB_RCAV457RUNTIME_CCHRB_SCAV429RUNTIME_CND1_RTAV431RUNTIME_CND1_RCAV430RUNTIME_CND1_SCAV432RUNTIME_CND2_RTAV434RUNTIME_CND2_RCAV433RUNTIME_CND2_SCAV435RUNTIME_CND3_RTAV437RUNTIME_CND3_RCAV436RUNTIME_CND3_SCAV417RUNTIME_COMPA1RTAV419RUNTIME_COMPA1RCAV418RUNTIME_COMPA1SCAV420RUNTIME_COMPA2RTAV422RUNTIME_COMPA2RCAV421RUNTIME_COMPA2SCAV423RUNTIME_COMPB1RTAV425RUNTIME_COMPB1RCAV424RUNTIME_COMPB1SCAV426RUNTIME_COMPB2RTAV428RUNTIME_COMPB2RCAV427RUNTIME_COMPB2SCAV441RUNTIME_EFAN_RTAV443RUNTIME_EFAN_RCAV442RUNTIME_EFAN_SCAV446RUNTIME_SHEAT_RCAV444RUNTIME_SHEAT_RTAV445RUNTIME_SHEAT_SCAV447RUNTIME_HMVLV_RTAV449RUNTIME_HMVLV_RCAV448RUNTIME_HMVLV_SCAV465RUNTIME_HUMPUSCAV438RUNTIME_IDF_RTAV440RUNTIME_IDF_RCAV439RUNTIME_IDF_SCAV450RUNTIME_DAMP_RTAV452RUNTIME_DAMP_RCAV451RUNTIME_DAMP_SCAV459RUNTIME_OILACYSCAV460RUNTIME_OILBCYSCAV274EXVSTP_EXVSTA1AV270EXVSTP_SupHtA1AV408RFGTEMP_SSHA1AV275EXVSTP_EXVSTA2AV271EXVSTP_SupHtA2AV409RFGTEMP_SSHA2AV276EXVSTP_EXVSTB1AV272EXVSTP_SupHtB1AV410RFGTEMP_SSHB1AV277EXVSTP_EXVSTB2AV273EXVSTP_SupHtB2AV411RFGTEMP_SSHB2AV471COOLCFG_CCHTHAAV472COOLCFG_CCHTHBAV497COOLCFG_CFSPDMX1AV496COOLCFG_CFSPDMN1BV172CNDSTP_SPDStpENAV498COOLCFG_CFSTSPD1AV402RFGPRESS_DPAAV462CMPASTS_ORTMLFTAAV400RFGPRESS_SPAAV346CMPASTS_BOOSTSTAAV403RFGPRESS_DPBAV464CMPBSTS_ORTMLFTBAV401RFGPRESS_SPBAV474COOLSTP_CMPMAXA1AV476COOLSTP_CMPMAXA2AV478COOLSTP_CMPMAXB1AV480COOLSTP_CMPMAXB2AV475COOLSTP_CMPMINA1AV477COOLSTP_CMPMINA2AV479COOLSTP_CMPMINB1AV481COOLSTP_CMPMINB2AV88CMPFLRTMAV87CMPSTKTMAV212DHUMCFG_CCBYPTMEAV213DHUMCFG_CCPRGPOSAV214DHUMCFG_CCPRGTMEAV293RFGTEMP_CCTAV506DHUMCFG_OILTIMEAV300RFGTEMP_DGTAAV523OUTPUTS_EXVA1OBJAV524OUTPUTS_EXVA2OBJAV525OUTPUTS_EXVB1OBJAV526OUTPUTS_EXVB2OBJAV89HEATSINK_HSCTRLOFAV211DHUMCFG_RHTCLTMEAV210DHUMCFG_RHTOPTMEAV489DHUMCFG_RHSTARTAV490DHUMCFG_RHTIMEAV488DHUMCFG_RHMAXPOSAV487DHUMCFG_RHMINPOSAV91HEATSINK_HSHTEMPAV90HEATSINK_HSHTMPDBAV209DHUMCFG_DHMATLCKAV301HMZR_CONDPURGAV519CMPA1STS_LOADREQAV520CMPA2STS_LOADREQAV521CMPB1STS_LOADREQAV522CMPB2STS_LOADREQBV174COOLCFG_LCRCOAV73LPRTIMEBV129EXVSTP_EXVSTENBAV505DHUMCFG_OILHITHAV504DHUMCFG_OILLOWTHAV461CMPASTS_OILRECACAV463CMPBSTS_OILRECACAV416RFGTEMP_OILTSMPAAV406RFGTEMP_SDTAAV407RFGTEMP_SDTBAV404RFGTEMP_SSTAAV405RFGTEMP_SSTBAV485COOLCFG_SCT_HLIMAV486COOLCFG_SCT_LLIMAV539CMPASTS_SDTABSMXAV543CMPBSTS_SDTABSMXAV538CMPASTS_SDTABSMNAV542CMPBSTS_SDTABSMNAV535CMPBSTS_SDTENVMXAV531CMPASTS_SDTENVMXAV534CMPBSTS_SDTENVMNAV530CMPASTS_SDTENVMNAV493CNDSTP_SDTTEMP1AV494CNDSTP_SDTTEMP2AV495CNDSTP_SDTTEMP3BV171CNDSTP_SDTStpEnAV541CMPBSTS_SSTABSMXAV537CMPASTS_SSTABSMXAV540CMPBSTS_SSTABSMNAV536CMPASTS_SSTABSMNAV533CMPBSTS_SSTENVMXAV529CMPASTS_SSTENVMXAV532CMPBSTS_SSTENVMNAV528CMPASTS_SSTENVMNAV299RFGTEMP_SGT1AV412RFGTEMP_SGTA1AV413RFGTEMP_SGTA2AV414RFGTEMP_SGTB1AV415RFGTEMP_SGTB2BV128EXVSTP_SETPTENBBV175COOLCFG_VSCFS_ORBV136SVCOUT_CMTRNDAHMV20STATES_ODF2STNMV21STATES_ODF3STNMV13STATES_CIRCASTNMV14STATES_CIRCBSTNMV15STATES_CMPA1STNMV16STATES_CMPA2STNMV17STATES_CMPB1STNMV18STATES_CMPB2STNBV8SVCOUT_CMTRNDACBV176STATES_OKTOFRCLBV180STATES_OKTOFDHMMV24STATES_HEATRSTNMV23STATES_RHTSTNUMMV22STATES_IDFNUMMV25STATES_ECONNUMMV26STATES_OCCSRNUMMV19STATES_ODF1STNBV178STATES_PURGEACTAV516STATES_MINTILOCBV206SWTCHCFG_ALARMINVBV200SWTCHCFG_CMPA1INVBV201SWTCHCFG_CMPA2INVBV182SWTCHCFG_CNDSWINVBV202SWTCHCFG_CCHRAINVBV199SWTCHCFG_DORINVBV204SWTCHCFG_EVBYPINVBV196SWTCHCFG_FRSTINVBV205SWTCHCFG_ERVINVBV197SWTCHCFG_WHLSTINVBV203SWTCHCFG_PEENINVBV192SWTCHCFG_FLTSWINVBV195SWTCHCFG_FRESWINVBV181SWTCHCFG_HTALMINVBV198SWTCHCFG_HTENINVBV185SWTCHCFG_HPSAINVBV189SWTCHCFG_DHMSWINVBV184SWTCHCFG_IDFSWINVBV194SWTCHCFG_PMRSWINVBV193SWTCHCFG_RESWINVBV183SWTCHCFG_SMKSWINVBV186SWTCHCFG_TSTGINVBV190SWTCHCFG_TSTW1INVBV191SWTCHCFG_TSTW2INVBV187SWTCHCFG_TSTY1INVBV188SWTCHCFG_TSTY2INVAV286HCSTATUS_CAPACTAV466GENUINIT_FILT_RTAV297FILTER_STATUSAV284HCSTATUS_HEATREQAV292GENUNIT_HEATCOOLBV6IDFFDBK_STATUSBV140LINK_ACTAV363GENUNIT_NETOCCAV289GENUNIT_OCCUPIEDAV43GENUNIT_PREFLTR_LIMAV42GENUNIT_PREFLTR_SRCBV167GENUNIT_FLTR_RSTAV285HCSTATUS_SATCTLPTAV567GENUNIT_SMAXCCAPAV568GENUNIT_SMAXHCAP
Integration notes
- Point availability varies by model, unit type, size and options; not every object exists on every unit.
- Units are shown as printed (imperial). The Metric Units setting switches units, and the Percentage Conversion setting changes percentages between 0-100 and 0.00-1.00.
- Binary and multistate states are listed as printed, numbered from 1 (e.g. 1=OFF, 2=ON).
- Some multistate texts are printed oddly and kept as is: CF 1-3 Mode lists DP_LOW twice, Comp A1-B2 Mode splits '5=DP; 6=LOW', and Heater/Indoor Fan Mode carry unnumbered extra values.
- Many configuration points are AVs holding numeric option codes (e.g. Network Occupancy 0-2, Demand Limit Source 0-3) that the guide does not decode.
- The table also lists CCN point names; only the BACnet side is captured here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)
How many BACnet points does the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) have?
This list has 715 BACnet objects: 502 analog values, 186 binary values, 27 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet points are writable?
393 of the 715 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1) BACnet documentation?
The source is SmartVu Controls Version 2.X for Applied Rooftop Integration Guide (Appendix A: BACnet and CCN Network Points) (48-50-ART-SVU-1T), revision 2025-03, published free by Carrier at https://www.shareddocs.com/hvac/docs/1005/Public/0F/48-50-ART-SVU-1T.pdf.
What are the minimum BACnet points to integrate the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)?
Start with AV 363 GENUNIT_NETOCC (Network occupancy; Primary BAS Network must be BACnet); AV 195 COOLSTP_CLSP_OCC (Occupied cooling setpoint); AV 313 HEATSTP_HTSP_OCC (Occupied heating setpoint); BV 1 ALARMRST_RST_ALM (Alarm reset command); MV 22 STATES_IDFNUM (Indoor fan state; 5 = running); AV 289 GENUNIT_OCCUPIED (Confirms occupied/unoccupied); AV 7 AIRTEMP_SPT (Space temperature); AV 4 AIRTEMP_SAT (Supply air temperature); BV 83 DISCOUT_ALMOUT (Common alarm relay output).
How do I enable BMS control of the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)?
Primary BAS Network selects the network that drives occupancy; it must be BACnet to use the Network Occupancy point (GENUNIT_NETOCC, AV 363) when BACnet schedule objects are not used. The guide does not say what the 0-2 values of AV 363 mean (default 2). Occupancy Source (MV 26) shows where occupancy currently comes from.
Can the BMS supply sensor values to the Carrier 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)?
The Network Inputs group has writable objects for BMS values, e.g. Net SPT (AV 360), Net OAT (AV 362), Net SPRH (AV 347), Net Indoor Air Quality (AV 357), Net Building Pressure (AV 352), and network thermostat calls Network Y1/Y2/W1/W2/G/HSTAT (BV 141-146). The guide does not explain how the unit selects them or give any refresh timeout.
How do I check these points on the real 48/50K and 48/50V Rooftop (SmartVu PIC 6.1)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Carrier BACnet points lists
- Water-cooled screw chiller controller (BACnet option)
Carrier 30HXA / 30HXC 076-271 Series 9 (UPC Open BACnet option)
Carrier 30HXA condenserless and 30HXC water-cooled screw chillers, sizes 076-271, Series 9 with ComfortLink controls and the BACnet communication option.
Also known as: 30HX, 30HXA, 30HXC, 30HX-2T, UPC Open, ComfortLink, screw chiller - Water-cooled chiller and water-to-water heat pump controller
Carrier 30WG / 30WGA / 61WG with SmartVu (Carrier Europe, BACnet option 149)
Carrier Europe 30WG and 30WGA water-cooled/condenserless chillers and 61WG water-to-water heat pumps with SmartVu (PIC 6.0, software 11.x) or SmartVu 2.0 (PIC 6.1, software 1.x).
Also known as: 30WG, 30WGA, 61WG, AquaSnap 30WG, 61WG heat pump, SmartVu PIC 6.0, SmartVu 2.0 PIC 6.1, option 149, Carrier Europe - Air-cooled split condensing unit controller
Carrier 38APS/38APD 025-130 Condensing Unit (ComfortLink, UPC Open BACnet option)
Carrier 38APS and 38APD 025-130 air-cooled condensing units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 38AP, 38APS, 38APD, 38APS025, 38APD130, 38AP-3T, UPC Open, ComfortLink - VRF indoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (indoor unit objects)
Each indoor unit of a Carrier 40VM series VRF heat pump, heat recovery or mini-VRF system connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - VRF outdoor unit (via BACnet gateway)
Carrier 40VM Series VRF BACnet Interface 40VM900052A (outdoor header unit objects)
Outdoor header (and follower) units of Carrier 40VM series VRF systems connected to the 40VM900052A BACnet Interface.
Also known as: 40VM900052A, 40VM900052, 40VM-52ASI, Carrier VRF BACnet Interface, 40VM VRF - Fan coil (chilled water cassette) controller
Carrier 42WKN Chilled Water Cassette (microprocessor controller)
Carrier 42WKN chilled water cassette fan coils (model digit 9 = C) with the on-board microprocessor controller.
Also known as: 42WKN, 42WKN-1T, chilled water cassette, cassette fan coil, 5H1067400002 - Rooftop unit controller
Carrier 48/50FC and 48/50GC Rooftop (SystemVu)
Carrier 48/50FC 04-30 and 48/50GC 04-28 single-package rooftop units (R-410A) with SystemVu controls, version 5.X.
Also known as: SystemVu, 48FC, 50FC, 48GC, 50GC, 48/50FC, 48/50GC, SystemVu 5.X, 48-50FC-GC-05T - Rooftop unit controller
Carrier 48/50FE and 48/50GE Rooftop (SystemVu)
Carrier 48/50FE 04-30 and 48/50GE 04-28 single-package rooftop units (R-454B) with SystemVu controls, version 3.X.
Also known as: SystemVu, 48FE, 50FE, 48GE, 50GE, 48/50FE, 48/50GE, SystemVu 3.X, SYSVU-FE-GE-02T - Rooftop unit controller
Carrier 48/50JC 04-06 Rooftop (SystemVu)
Carrier 48/50JC 04-06 single-package rooftop units (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 48JC, 50JC, 48/50JC, SystemVu 4.X, 48-50JC-4-6-05T - Rooftop unit controller
Carrier 48/50K and 48/50V Applied Rooftop (SmartVu software 4.X network points)
Carrier 48/50K and 48/50V applied rooftop units with PIC 6.1 hardware and SmartVu controls running software version 4.X.
Also known as: 48K, 50K, 48V, 50V, 48/50K, 48/50V, SmartVu 4.X, 48-50-ART-SMVU-3T, Applied Rooftop SmartVu, PIC 6.1 - Rooftop unit controller
Carrier 48/50LC 04-26 Rooftop (SystemVu)
Carrier 48/50LC 04-26 single-package rooftop units (R-410A) with the factory-installed SystemVu control, version 7.X.
Also known as: SystemVu, 48LC, 50LC, 48/50LC, 48LC 04-26, 50LC 04-26, SystemVu 7.X, S-VU-LC-4-26-06T - Rooftop unit controller (VAV)
Carrier 48/50LC B 07-26 VAV Rooftop (VAV-RTU Open)
Carrier 48/50LC B 07-26 variable air volume rooftop units with the factory VAV-RTU Open controller.
Also known as: VAV-RTU Open, VAV RTU Open, 48LCB, 50LCB, 48/50LCB, 48/50LC B, 48LC B 07-26, 50LC B 07-26, 48-50LCB-7-26-04T - Packaged rooftop unit controller
Carrier 48/50LC*H Light Commercial Rooftop (SmartVu 2.X, PIC 6.0)
Carrier 48/50LC*H light commercial high outdoor air rooftop units (R-410A) with factory SmartVu controls version 2.X on PIC 6.0 hardware.
Also known as: 48/50LC*H, 48LCH, 50LCH, 48/50LCH, SmartVu, PIC 6.0, Carrier light commercial high outdoor air rooftop, 48-50-LRT-SMVU-2T - Self-contained unit controller
Carrier 50BVT/50BVV/50BVQ/50VQP/50BVW Indoor Self-Contained Units (SCU Open, UC Open XP)
Carrier 50BV and 50VQP indoor water-cooled self-contained units and 50BVW units with the factory SCU Open program on a UC Open XP controller.
Also known as: 50BV, 50BVT, 50BVV, 50BVQ, 50VQP, 50BVW, SCU Open, UC Open XP, 50BV-SCU-3T, water-cooled self-contained unit - Rooftop unit controller (heat-pump units)
Carrier 50FCQ/50GCQ Rooftop Heat Pump (SystemVu)
Carrier 50FCQ 04-28 and 50GCQ 04-12 single-package rooftop heat pumps (R-410A) with SystemVu controls, version 4.X.
Also known as: SystemVu, 50FCQ, 50GCQ, 50FCQ 04-28, 50GCQ 04-12, SystemVu 4.X, 50FCQ-GCQ-04T - Rooftop unit controller (heat-pump units)
Carrier 50FEQ/50GEQ/48QE Heat Pump and Hybrid Heat Rooftop (SystemVu)
Carrier 50FEQ and 50GEQ 04-28 packaged rooftop heat pumps and 48QE 04-28 hybrid heat units (R-454B) with SystemVu controls, version 5.X.
Also known as: SystemVu, 50FEQ, 50GEQ, 48QE, 50FEQ 04-28, 50GEQ 04-28, 48QE 04-28, SystemVu 5.X, SYSVU-FEQGEQQE-03T - Dedicated outdoor air unit (DOAS) controller
Carrier 62DA/DB/DC/DD 07-38 Dedicated Outdoor Air Unit (I/O Flex 6126, 100% OA program)
Carrier 62DA, 62DB, 62DC and 62DD 07-38 vertical or horizontal 100% outdoor air units, with optional energy conservation wheel, controlled by the I/O Flex 6126 running the 100% OA standard program.
Also known as: 62D, 62DA, 62DB, 62DC, 62DD, 62D-1T, I/O Flex 6126, 100% OA STD 021711, Carrier 62D DOAS - Dedicated outdoor air unit (DOAS) controller
Carrier 62H Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62H 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62H, Carrier 62H DOAS, Revision K controls, LS-1628u, 62H-2T - Dedicated outdoor air unit (DOAS) controller
Carrier 62X / 62W Dedicated Outdoor Air Unit (Rev. K controls)
Carrier 62X and 62W 03-55 ton dedicated outdoor air units with Revision K controls (100% outdoor air).
Also known as: 62X, 62W, Carrier 62X DOAS, Carrier 62W DOAS, Revision K controls, LS-1628u, 62X-6T, 62W-2T - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19DV (PIC6)
Carrier AquaEdge 19DV two-stage centrifugal chillers with the PIC6 controller.
Also known as: 19DV, AquaEdge 19DV, PIC6, 19DV-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19MV (PIC6)
Carrier AquaEdge 19MV two-stage semi-hermetic centrifugal chillers with Greenspeed Intelligence (magnetic bearings) and PIC6 controls.
Also known as: 19MV, AquaEdge 19MV, 19MV-CLT-3T, PIC6, magnetic bearing centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR-CLT-3T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC 5, software version 3.0)
Carrier AquaEdge 19XR two-stage semi-hermetic centrifugal chillers with PIC 5 controls, software version 3.0.
Also known as: 19XR, AquaEdge 19XR, PIC 5, PIC5, 19XR PIC 5 v3.0, 19XR-CLT-2T, 19XR-CLT-1T, centrifugal chiller - Water-cooled centrifugal chiller controller
Carrier AquaEdge 19XR (PIC6.1)
Carrier AquaEdge 19XR single-stage and two-stage centrifugal chillers with the PIC6.1 controller.
Also known as: 19XR, AquaEdge 19XR, 19XR PIC6.1, PIC6.1, 19XR-CLT-9T, centrifugal chiller - Water-cooled screw chiller controller
Carrier AquaEdge 23XRV (PIC6)
Carrier AquaEdge 23XRV variable-speed water-cooled screw chillers with the PIC6 touchscreen controller.
Also known as: 23XRV, AquaEdge 23XRV, PIC6, 23XRV-3T, variable speed screw chiller - Air-cooled screw chiller controller (BACnet option)
Carrier AquaForce 30XA 080-501 (UPC Open BACnet option)
Carrier AquaForce 30XA080-501 air-cooled screw chillers with the BACnet communication option (UPC Open controller).
Also known as: 30XA, AquaForce 30XA, 30XA-7T, UPC Open, Carrier Controller, screw chiller - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XA 140-352 (BACnet/Modbus Translator)
Carrier AquaForce 30XA 140-352 air-cooled screw chillers with Touch Pilot controls and the factory BACnet/Modbus translator.
Also known as: 30XA, AquaForce 30XA, 30XA-100T, Touch Pilot, BACnet/Modbus translator - Air-cooled screw chiller (via BACnet translator)
Carrier AquaForce 30XV 140-500 (Touch Pilot) BACnet/Modbus Translator points
Carrier AquaForce 30XV140-500 chillers with the Touch Pilot controller and the optional BACnet/Modbus Translator on BACnet MS/TP.
Also known as: 30XV, AquaForce 30XV, 30XV-2T, 30XV BACnet translator, BACnet/Modbus Translator - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 (Touch Pilot, 2017) native BACnet IP points
Carrier AquaForce 30XV140-500 variable speed air-cooled screw chillers with the Touch Pilot display (original / Series A documentation, 2017).
Also known as: 30XV, AquaForce 30XV, 30XV-2T, 30XV Touch Pilot, 30XV Series A, Greenspeed 30XV - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B (PIC6.1 Carrier Controller)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the PIC6.1 Carrier Controller and version 9.x software.
Also known as: 30XV, AquaForce 30XV, 30XV Series B, 30XV-6T, PIC6.1, Carrier Controller, Greenspeed - Air-cooled screw chiller controller
Carrier AquaForce 30XV 140-500 Series B, Carrier Controller (2019 software, 30XV-3T)
Carrier AquaForce 30XV140-500 Series B variable-speed air-cooled screw chillers with the Carrier Controller as documented in the June 2019 manual (Form 30XV-3T).
Also known as: 30XV, AquaForce 30XV, 30XV-3T, 30XV Series B 2019, Carrier Controller, Greenspeed, 04-53300197-01 - Scroll chiller / heat pump controller
Carrier AquaSnap 30MP (PIC6 Carrier Controller)
Carrier AquaSnap 30MPW017-080 water-cooled, 30MPA021-080 condenserless and 30MPQ021-080 heat pump chillers with scroll compressors and PIC6 (Carrier Controller).
Also known as: 30MPW, 30MPA, 30MPQ, 30MP, AquaSnap 30MP, 30MP-8T, Carrier Controller - Scroll chiller controller (BACnet option)
Carrier AquaSnap 30MPA/30MPW 016-071 (ComfortLink, UPC Open BACnet option)
Carrier AquaSnap 30MPA (condenserless) and 30MPW (water-cooled) 016-071 scroll chillers with ComfortLink controls and the factory BACnet communication option.
Also known as: 30MP, 30MPA, 30MPW, 30MPA016-071, 30MPW016-071, AquaSnap 30MP, 30MP-6T, UPC Open, ComfortLink, scroll chiller - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RAP 010-150 (UPC Open BACnet option)
Carrier AquaSnap 30RAP010-150 air-cooled chillers and 30RAP011-060 with Greenspeed Intelligence (R-410A, ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RAP, AquaSnap 30RAP, 30RAP-8T, 30RAP Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller (BACnet option)
Carrier AquaSnap 30RB 060-390 (UPC Open BACnet option)
Carrier AquaSnap 30RB060-390 air-cooled chillers and 30RB080-390 with Greenspeed Intelligence (ComfortLink controls) fitted with the BACnet communication option.
Also known as: 30RB, AquaSnap 30RB, 30RB-8T, 30RB Greenspeed, UPC Open, ComfortLink - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 010-060
Carrier AquaSnap 30RC 010-060 air-cooled scroll chillers (with or without Greenspeed fans) using the Carrier Controller.
Also known as: 30RC, AquaSnap 30RC, 30RC-101T, Carrier Controller, 30RC BACnet IP - Air-cooled scroll chiller controller
Carrier AquaSnap 30RC 065-252 (Carrier Controller)
Carrier AquaSnap 30RC 065-252 air-cooled scroll chillers (including Greenspeed intelligence models) with the Carrier Controller.
Also known as: 30RC, 30RC065, 30RC252, AquaSnap 30RC, 30RC Greenspeed, 30RC-3T, air-cooled scroll chiller - Close control air handling unit
Carrier CCU Controller close control unit (Modbus to BACnet gateway option)
Carrier (Europe) close control / precision air conditioning units with the CCU controller and the optional Modbus RTU to BACnet gateway kit.
Also known as: Carrier CCU Controller, Carrier close control unit, Precision air conditioning controller, EN7519369 - Networked room thermostat
Carrier ComfortVu BACnet Thermostat
Carrier ComfortVu wall thermostats controlling fan coils or AC/heat pump units.
Also known as: ComfortVu, Carrier ComfortVu, 11-808-726-01 - Networked room thermostat
Carrier Connect Wi-Fi Thermostat (33CONNECTSTAT43)
Carrier Connect Wi-Fi wall thermostats controlling packaged or split AC, heat pump and furnace/air handler systems.
Also known as: 33CONNECTSTAT43, Carrier Connect thermostat, Connect Wi-Fi thermostat, ConnectStat, 11-808-728-01 - Commercial Wi-Fi thermostat
Carrier Connect Wi-Fi Thermostat 33TCSPF-4 / 33TWSPF-4
Carrier Connect Wi-Fi thermostats 33TCSPF-4 (Carrier branded) and 33TWSPF-4 (unbranded), 24 VAC touchscreen thermostats with built-in BACnet.
Also known as: 33TCSPF-4, 33TWSPF-4, 33TCSPF4, 33TWSPF4 - Fan coil unit controller
Carrier Fan Coil Open
Carrier fan coil units fitted with the Fan Coil Open (OPN-FC) multi-protocol controller.
Also known as: Fan Coil Open, OPN-FC, Carrier Fan Coil controller, 11-808-540-01 - Condensing unit (split system) controller
Carrier Gemini Select 38RCS/38RCD Condensing Unit (BACnet IP and MS/TP option)
Carrier Gemini Select 38RCS025-050 and 38RCD025-130 commercial air-cooled condensing units.
Also known as: 38RC, 38RCS, 38RCD, 38RCS025-050, 38RCD025-130, Gemini Select, 38RC-3T, air-cooled condensing unit - Rooftop unit controller
Carrier RTU Open v5
Carrier packaged rooftop units and heat pumps retrofitted or factory-fitted with the RTU Open controller.
Also known as: RTU Open, OPN-RTU, RTU-Open, 11-808-697-01 - Heat pump plant sequencer (system manager)
Carrier System Management Sequencer (SMS) Option 275A for modular R-290 air-source heat pumps
Carrier's System Management Sequencer (option 275A), a control cabinet that stages up to four modular R-290 air-source heat pumps with zones, pumps, DHW and a back-up boiler.
Also known as: SMS, OPT275A, Option 275A, System Management Sequencer, modular R-290 air source heat pump, Carrier Europe - Unit ventilator controller (fan coil / terminal unit)
Carrier Unit Ventilator Open
Carrier unit ventilators with the factory-installed Unit Vent (OPN-UV) multi-protocol controller.
Also known as: UV Open, Unit Vent Open, OPN-UV, Carrier unit ventilator controller, 11-808-513-01 - VAV terminal unit controller
Carrier VAV Zone II
Single-duct (OPN-VAVB1-02) and fan-powered (OPN-VAVB3-02) VAV terminals controlled by the Carrier VAV Zone II.
Also known as: OPN-VAVB1-02, OPN-VAVB3-02, VAV Zone II Single Duct, VAV Zone II Fan Terminal, i-Vu VAV Zone II, 11-808-602-01 - VVT bypass damper / duct static pressure controller (terminal zoning)
Carrier VVT Bypass II
Bypass dampers or supply-fan VFDs in Carrier VVT systems, controlled by the VVT Bypass II (OPN-VVTBP-02).
Also known as: OPN-VVTBP-02, VVT Bypass II controller, i-Vu VVT Bypass, 11-808-601-01 - VVT zone damper controller (VAV / terminal zoning)
Carrier VVT Zone II
Carrier VVT (variable volume and temperature) zone dampers and single-duct or fan-powered zone terminals run by the VVT Zone II controller.
Also known as: VVT Zone II controller, OPN-VVTZ2, i-Vu VVT Zone II, 11-808-603-01 - Water-to-water heat pump controller
Carrier W2W Open
Carrier water-to-water heat pumps fitted with the W2W Open (OPN-WSHPW2WM) multi-protocol controller.
Also known as: W2W Open, Water-to-Water Open, OPN-WSHPW2WM, Carrier water-to-water heat pump controller, 11-808-538-01 - Water source heat pump controller
Carrier Water Source Heat Pump TruVu Controller (TV-WSHP)
Carrier 50 Series water source heat pumps (50WC, 50WD, 50WT, 50HQP, 50VQP) with the factory TruVu TV-WSHP controller.
Also known as: TV-WSHP, TruVu WSHP, TVWSHP-02T, 50WC, 50WD, 50WT, 50HQP, 50VQP, 50 Series WSHP - Packaged rooftop unit controller (BACnet option)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink 6.x, UPC Open BACnet option)
Carrier WeatherExpert 48/50N2 through N9 packaged rooftop units (gas, electric or hydronic heat) with ComfortLink version 6.x controls and the BACnet communication option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, ComfortLink 6.x, UPC Open, 48/50N-6T, 48_50N-6T - Rooftop unit controller (gateway)
Carrier WeatherExpert 48/50N2-N9 Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherExpert 48N and 50N (sizes N2-N9) large rooftop units with ComfortLink controls and the factory UPC Open BACnet option.
Also known as: 48N, 50N, 48N2, 50N9, 48/50N, WeatherExpert, 48-50N-8T, UPC Open, ComfortLink - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A Rooftop (ComfortLink, UPC Open BACnet option)
Carrier WeatherMaker 48/50A020-060 single-package applied rooftop units with ComfortLink 11.x controls and the factory UPC Open BACnet option.
Also known as: 48/50A, 48A, 50A, 48/50A020-060, WeatherMaker 48/50A, UPC Open, ComfortLink, 48-50A-17T - Packaged rooftop unit controller (BACnet option)
Carrier WeatherMaker 48/50A2-A5 020-060 Rooftop (ComfortLink 8.x, UPC Open BACnet option)
Carrier WeatherMaker 48/50A2, A3, A4 and A5 020-060 single-package large rooftop units with ComfortLink version 8.x controls and the UPC Open BACnet option.
Also known as: 48/50A2, 48/50A3, 48/50A4, 48/50A5, 48A2, 50A2, 48/50A020-060, WeatherMaker 48/50A, ComfortLink 8.x, UPC Open, 48/50A-13T, 48_50A-13T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P Large Rooftop (ComfortLink, UPC Open BACnet option)
Carrier Weathermaster 48/50P030-100 single-package large rooftop units with ComfortLink 9.x controls and the factory UPC Open BACnet option.
Also known as: 48/50P, 48P, 50P, 48/50P030-100, Weathermaster 48/50P, UPC Open, ComfortLink, 48-50P-15T - Packaged rooftop unit controller (BACnet option)
Carrier Weathermaster 48/50P2-P5 030-100 Large Rooftop (ComfortLink 7.x, UPC Open BACnet option)
Carrier Weathermaster 48/50P2, P3, P4 and P5 030-100 single-package large rooftop units with ComfortLink version 7.x controls and the UPC Open BACnet option.
Also known as: 48/50P2, 48/50P3, 48/50P4, 48/50P5, 48P2, 50P2, 48/50P030-100, Weathermaster 48/50P, ComfortLink 7.x, UPC Open, 48/50P-8T, 48_50P-8T - Water-source heat pump controller
Carrier WSHP Open v3
Carrier water-source heat pumps fitted with the WSHP Open multi-protocol controller.
Also known as: WSHP Open, WSHP-Open, Carrier water source heat pump controller, 11-808-539-01
Source: SmartVu Controls Version 2.X for Applied Rooftop Integration Guide (Appendix A: BACnet and CCN Network Points) · 48-50-ART-SVU-1T · rev. 2025-03. Object names, instances and units are reproduced as published; descriptions are our own.