- Home
- BACnet points lists
- AERCO
- C-More boilers with ACS / BMS II (ProtoNode RER)
Boiler controller and plant sequencer via ProtoNode gateway · BACnet points list
AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet points list
Updated 28 October 2026
The AERCO ProtoNode RER reads C-More boiler controllers and an ACS or BMS II sequencer over Modbus RTU and serves them as one BACnet IP or BACnet MS/TP device, using a DIP-selected profile for 4, 8 or 12 C-Mores. This file follows the 12-boiler profile: 11 values per boiler plus 30 plant values from the ACS/BMS II. All objects are analog values; only the network setpoints are writable.
This page lists 162 BACnet objects for the AERCO C-More boilers with ACS / BMS II (ProtoNode RER) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.
- Manufacturer
- AERCO
- Model
- C-More boilers with ACS / BMS II (ProtoNode RER)
- Equipment
- Boiler controller and plant sequencer via ProtoNode gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 162 (13 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Node_Offset + A-bank DIP switch value (MAC); the manual's example uses Node_Offset 50,000
- Also known as
- C-More, C-More controller, ACS, BMS II, BMS, ProtoNode RER, ProtoNode-RER, 64084, FPC-N34, GF-129, OMM-0080
Instance calculator. This list prints one unit; the other units follow a formula. ProtoNode boiler gateways (Laars, Peerless, Raypak, AERCO and more) instance calculator →
Reference only, provided as-is: verify against AERCO’s current documentation and the live device before use. Not official AERCO information. Terms of use.
BMS integration notes: AERCO C-More boilers with ACS / BMS II (ProtoNode RER)
Set the ProtoNode S-bank DIP switches to the BACnet profile for the number of C-Mores, give each C-More a Comm Address (1-12) and the ACS/BMS II Modbus address 128, then write the setpoint: 03-Net Header Set Temp on the ACS/BMS II for plant control, or each boiler's 03-Net Remote Setpt. The BAS must keep rewriting the setpoint, at least three times per network timeout.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 33 | 03-Net Header Set Temp | Plant header setpoint via ACS/BMS II, 40-220 °F | Write |
| AV 24 | 03-Net Remote Setpt | Boiler 1 network setpoint, 40-220 °F | Write |
| AV 23 | 08-Unit Status | Boiler 1 status; 5 = Fault | Read |
| AV 34 | 04-Header Temp | Header water temperature, °F | Read |
| AV 29 | 06-Outlet Temp | Boiler 1 outlet water temperature, °F | Read |
| AV 26 | 01-Fire Rate Out | Boiler 1 fire rate, % | Read |
| AV 22 | 07-Display Code | Boiler 1 status/fault message code | Read |
| AV 36 | 06-Display Code | ACS/BMS II fault bit field | Read |
Enable & remote start
No start/stop object. For plant control set the ACS/BMS II to Header Set Mode = Remote Setpt and Remote Signal = Network, then write AV 33. For a single C-More set Boiler Mode = Remote Setpt and Remote Signal = Network, then write its 03-Net Remote Setpt. Monitor-only needs just the Modbus address and 9600 baud.
Heartbeat & communication loss
The BAS must write the setpoint at least three times within the unit's Network Timeout or the unit stops using it. Defaults are 30 s on C-More (5-999 s, Configuration menu), ACS (5-240 s) and BMS II (5-240 s, RS-232 menu).
Network setup
- S0-S3 (A1 Off): all Off = 1 ACS/BMS II + 4 C-Mores, S0 On = 8 C-Mores, S1 On = 12 C-Mores (BACnet IP / MS/TP).
- Device instance = Node_Offset (set in the Web Configurator) + A-bank DIP value; MS/TP MAC is 1-127 on A0-A7, baud on B0-B3.
- Default IP 192.168.1.24; change it in the ProtoNode web GUI.
- Modbus side: every AERCO unit at 9600 baud, 8 data bits, 1 stop bit, no parity.
- C-More Comm Address 1-4, 1-8 or 1-12 to match the profile; ACS/BMS II: RS232 Mode = Modbus Slave, 9600 baud, Modbus Address 128, Modbus Pass-thru Enabled to see the boilers.
- The ACS/BMS II RS-232 port needs an RS-232 to RS-485 converter to reach the ProtoNode.
Watch out for
- Pick the profile for the number of boilers actually installed; with a profile for more units than are installed the Node Offline LED stays lit.
- Boiler 1 to 12 point names are identical; use the instance (or the description) to tell them apart.
- ACS/BMS II Boiler 1-8 Status covers PWM-controlled boilers; Net Blr 1-12 Status covers network boilers.
AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 26 | 01-Fire Rate Out | Boiler 1: fire rate output (0-100) | % | Read | |
| AV | 27 | 02-Active Setpoint | Boiler 1: setpoint in use (40-220) | °F | Read | |
| AVmin | 24 | 03-Net Remote Setpt | Boiler 1: network remote setpoint (40-220) | °F | Write | |
| AV | 28 | 05-Fire Rate In | Boiler 1: fire rate input (0-100) | % | Read | |
| AVmin | 29 | 06-Outlet Temp | Boiler 1: outlet water temperature (30-245) | °F | Read | |
| AVmin | 22 | 07-Display Code | Boiler 1: status/fault message code (1-48, see manual) | Read | ||
| AVmin | 23 | 08-Unit Status | Boiler 1: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 42 | 09-Run Cycles | Boiler 1: run cycle count (0-999,999) | Read | ||
| AV | 43 | 10-Run Hours | Boiler 1: run hours (0-999,999) | h | Read | |
| AV | 161 | 11-Oxygen | Boiler 1: flue O2 level (0-25) | % | Read | |
| AV | 181 | 12-Exhaust Temp | Boiler 1: exhaust temperature (50-550) | °F | Read | |
| AV | 30 | 01-Fire Rate Out | Boiler 2: fire rate output (0-100) | % | Read | |
| AV | 46 | 02-Active Setpoint | Boiler 2: setpoint in use (40-220) | °F | Read | |
| AV | 47 | 03-Net Remote Setpt | Boiler 2: network remote setpoint (40-220) | °F | Write | |
| AV | 50 | 05-Fire Rate In | Boiler 2: fire rate input (0-100) | % | Read | |
| AV | 51 | 06-Outlet Temp | Boiler 2: outlet water temperature (30-245) | °F | Read | |
| AV | 52 | 07-Display Code | Boiler 2: status/fault message code (1-48, see manual) | Read | ||
| AV | 53 | 08-Unit Status | Boiler 2: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 44 | 09-Run Cycles | Boiler 2: run cycle count (0-999,999) | Read | ||
| AV | 45 | 10-Run Hours | Boiler 2: run hours (0-999,999) | h | Read | |
| AV | 162 | 11-Oxygen | Boiler 2: flue O2 level (0-25) | % | Read | |
| AV | 182 | 12-Exhaust Temp | Boiler 2: exhaust temperature (50-550) | °F | Read | |
| AV | 54 | 01-Fire Rate Out | Boiler 3: fire rate output (0-100) | % | Read | |
| AV | 55 | 02-Active Setpoint | Boiler 3: setpoint in use (40-220) | °F | Read | |
| AV | 56 | 03-Net Remote Setpt | Boiler 3: network remote setpoint (40-220) | °F | Write | |
| AV | 60 | 05-Fire Rate In | Boiler 3: fire rate input (0-100) | % | Read | |
| AV | 61 | 06-Outlet Temp | Boiler 3: outlet water temperature (30-245) | °F | Read | |
| AV | 62 | 07-Display Code | Boiler 3: status/fault message code (1-48, see manual) | Read | ||
| AV | 63 | 08-Unit Status | Boiler 3: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 58 | 09-Run Cycles | Boiler 3: run cycle count (0-999,999) | Read | ||
| AV | 59 | 10-Run Hours | Boiler 3: run hours (0-999,999) | h | Read | |
| AV | 163 | 11-Oxygen | Boiler 3: flue O2 level (0-25) | % | Read | |
| AV | 183 | 12-Exhaust Temp | Boiler 3: exhaust temperature (50-550) | °F | Read | |
| AV | 70 | 01-Fire Rate Out | Boiler 4: fire rate output (0-100) | % | Read | |
| AV | 71 | 02-Active Setpoint | Boiler 4: setpoint in use (40-220) | °F | Read | |
| AV | 72 | 03-Net Remote Setpt | Boiler 4: network remote setpoint (40-220) | °F | Write | |
| AV | 73 | 05-Fire Rate In | Boiler 4: fire rate input (0-100) | % | Read | |
| AV | 65 | 06-Outlet Temp | Boiler 4: outlet water temperature (30-245) | °F | Read | |
| AV | 66 | 07-Display Code | Boiler 4: status/fault message code (1-48, see manual) | Read | ||
| AV | 67 | 08-Unit Status | Boiler 4: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 68 | 09-Run Cycles | Boiler 4: run cycle count (0-999,999) | Read | ||
| AV | 69 | 10-Run Hours | Boiler 4: run hours (0-999,999) | h | Read | |
| AV | 164 | 11-Oxygen | Boiler 4: flue O2 level (0-25) | % | Read | |
| AV | 184 | 12-Exhaust Temp | Boiler 4: exhaust temperature (50-550) | °F | Read | |
| AV | 80 | 01-Fire Rate Out | Boiler 5: fire rate output (0-100) | % | Read | |
| AV | 81 | 02-Active Setpoint | Boiler 5: setpoint in use (40-220) | °F | Read | |
| AV | 82 | 03-Net Remote Setpt | Boiler 5: network remote setpoint (40-220) | °F | Write | |
| AV | 74 | 05-Fire Rate In | Boiler 5: fire rate input (0-100) | % | Read | |
| AV | 75 | 06-Outlet Temp | Boiler 5: outlet water temperature (30-245) | °F | Read | |
| AV | 76 | 07-Display Code | Boiler 5: status/fault message code (1-48, see manual) | Read | ||
| AV | 77 | 08-Unit Status | Boiler 5: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 78 | 09-Run Cycles | Boiler 5: run cycle count (0-999,999) | Read | ||
| AV | 79 | 10-Run Hours | Boiler 5: run hours (0-999,999) | h | Read | |
| AV | 165 | 11-Oxygen | Boiler 5: flue O2 level (0-25) | % | Read | |
| AV | 185 | 12-Exhaust Temp | Boiler 5: exhaust temperature (50-550) | °F | Read | |
| AV | 90 | 01-Fire Rate Out | Boiler 6: fire rate output (0-100) | % | Read | |
| AV | 91 | 02-Active Setpoint | Boiler 6: setpoint in use (40-220) | °F | Read | |
| AV | 92 | 03-Net Remote Setpt | Boiler 6: network remote setpoint (40-220) | °F | Write | |
| AV | 84 | 05-Fire Rate In | Boiler 6: fire rate input (0-100) | % | Read | |
| AV | 85 | 06-Outlet Temp | Boiler 6: outlet water temperature (30-245) | °F | Read | |
| AV | 86 | 07-Display Code | Boiler 6: status/fault message code (1-48, see manual) | Read | ||
| AV | 87 | 08-Unit Status | Boiler 6: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 88 | 09-Run Cycles | Boiler 6: run cycle count (0-999,999) | Read | ||
| AV | 89 | 10-Run Hours | Boiler 6: run hours (0-999,999) | h | Read | |
| AV | 166 | 11-Oxygen | Boiler 6: flue O2 level (0-25) | % | Read | |
| AV | 186 | 12-Exhaust Temp | Boiler 6: exhaust temperature (50-550) | °F | Read | |
| AV | 100 | 01-Fire Rate Out | Boiler 7: fire rate output (0-100) | % | Read | |
| AV | 101 | 02-Active Setpoint | Boiler 7: setpoint in use (40-220) | °F | Read | |
| AV | 102 | 03-Net Remote Setpt | Boiler 7: network remote setpoint (40-220) | °F | Write | |
| AV | 94 | 05-Fire Rate In | Boiler 7: fire rate input (0-100) | % | Read | |
| AV | 95 | 06-Outlet Temp | Boiler 7: outlet water temperature (30-245) | °F | Read | |
| AV | 96 | 07-Display Code | Boiler 7: status/fault message code (1-48, see manual) | Read | ||
| AV | 97 | 08-Unit Status | Boiler 7: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 98 | 09-Run Cycles | Boiler 7: run cycle count (0-999,999) | Read | ||
| AV | 99 | 10-Run Hours | Boiler 7: run hours (0-999,999) | h | Read | |
| AV | 167 | 11-Oxygen | Boiler 7: flue O2 level (0-25) | % | Read | |
| AV | 187 | 12-Exhaust Temp | Boiler 7: exhaust temperature (50-550) | °F | Read | |
| AV | 110 | 01-Fire Rate Out | Boiler 8: fire rate output (0-100) | % | Read | |
| AV | 111 | 02-Active Setpoint | Boiler 8: setpoint in use (40-220) | °F | Read | |
| AV | 112 | 03-Net Remote Setpt | Boiler 8: network remote setpoint (40-220) | °F | Write | |
| AV | 104 | 05-Fire Rate In | Boiler 8: fire rate input (0-100) | % | Read | |
| AV | 105 | 06-Outlet Temp | Boiler 8: outlet water temperature (30-245) | °F | Read | |
| AV | 106 | 07-Display Code | Boiler 8: status/fault message code (1-48, see manual) | Read | ||
| AV | 107 | 08-Unit Status | Boiler 8: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 108 | 09-Run Cycles | Boiler 8: run cycle count (0-999,999) | Read | ||
| AV | 109 | 10-Run Hours | Boiler 8: run hours (0-999,999) | h | Read | |
| AV | 168 | 11-Oxygen | Boiler 8: flue O2 level (0-25) | % | Read | |
| AV | 188 | 12-Exhaust Temp | Boiler 8: exhaust temperature (50-550) | °F | Read | |
| AV | 120 | 01-Fire Rate Out | Boiler 9: fire rate output (0-100) | % | Read | |
| AV | 121 | 02-Active Setpoint | Boiler 9: setpoint in use (40-220) | °F | Read | |
| AV | 122 | 03-Net Remote Setpt | Boiler 9: network remote setpoint (40-220) | °F | Write | |
| AV | 114 | 05-Fire Rate In | Boiler 9: fire rate input (0-100) | % | Read | |
| AV | 115 | 06-Outlet Temp | Boiler 9: outlet water temperature (30-245) | °F | Read | |
| AV | 116 | 07-Display Code | Boiler 9: status/fault message code (1-48, see manual) | Read | ||
| AV | 117 | 08-Unit Status | Boiler 9: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 118 | 09-Run Cycles | Boiler 9: run cycle count (0-999,999) | Read | ||
| AV | 119 | 10-Run Hours | Boiler 9: run hours (0-999,999) | h | Read | |
| AV | 169 | 11-Oxygen | Boiler 9: flue O2 level (0-25) | % | Read | |
| AV | 189 | 12-Exhaust Temp | Boiler 9: exhaust temperature (50-550) | °F | Read | |
| AV | 130 | 01-Fire Rate Out | Boiler 10: fire rate output (0-100) | % | Read | |
| AV | 131 | 02-Active Setpoint | Boiler 10: setpoint in use (40-220) | °F | Read | |
| AV | 132 | 03-Net Remote Setpt | Boiler 10: network remote setpoint (40-220) | °F | Write | |
| AV | 124 | 05-Fire Rate In | Boiler 10: fire rate input (0-100) | % | Read | |
| AV | 125 | 06-Outlet Temp | Boiler 10: outlet water temperature (30-245) | °F | Read | |
| AV | 126 | 07-Display Code | Boiler 10: status/fault message code (1-48, see manual) | Read | ||
| AV | 127 | 08-Unit Status | Boiler 10: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 128 | 09-Run Cycles | Boiler 10: run cycle count (0-999,999) | Read | ||
| AV | 129 | 10-Run Hours | Boiler 10: run hours (0-999,999) | h | Read | |
| AV | 170 | 11-Oxygen | Boiler 10: flue O2 level (0-25) | % | Read | |
| AV | 190 | 12-Exhaust Temp | Boiler 10: exhaust temperature (50-550) | °F | Read | |
| AV | 140 | 01-Fire Rate Out | Boiler 11: fire rate output (0-100) | % | Read | |
| AV | 141 | 02-Active Setpoint | Boiler 11: setpoint in use (40-220) | °F | Read | |
| AV | 142 | 03-Net Remote Setpt | Boiler 11: network remote setpoint (40-220) | °F | Write | |
| AV | 134 | 05-Fire Rate In | Boiler 11: fire rate input (0-100) | % | Read | |
| AV | 135 | 06-Outlet Temp | Boiler 11: outlet water temperature (30-245) | °F | Read | |
| AV | 136 | 07-Display Code | Boiler 11: status/fault message code (1-48, see manual) | Read | ||
| AV | 137 | 08-Unit Status | Boiler 11: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 138 | 09-Run Cycles | Boiler 11: run cycle count (0-999,999) | Read | ||
| AV | 139 | 10-Run Hours | Boiler 11: run hours (0-999,999) | h | Read | |
| AV | 171 | 11-Oxygen | Boiler 11: flue O2 level (0-25) | % | Read | |
| AV | 191 | 12-Exhaust Temp | Boiler 11: exhaust temperature (50-550) | °F | Read | |
| AV | 150 | 01-Fire Rate Out | Boiler 12: fire rate output (0-100) | % | Read | |
| AV | 151 | 02-Active Setpoint | Boiler 12: setpoint in use (40-220) | °F | Read | |
| AV | 152 | 03-Net Remote Setpt | Boiler 12: network remote setpoint (40-220) | °F | Write | |
| AV | 144 | 05-Fire Rate In | Boiler 12: fire rate input (0-100) | % | Read | |
| AV | 145 | 06-Outlet Temp | Boiler 12: outlet water temperature (30-245) | °F | Read | |
| AV | 146 | 07-Display Code | Boiler 12: status/fault message code (1-48, see manual) | Read | ||
| AV | 147 | 08-Unit Status | Boiler 12: unit operating status | Read | 0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault | |
| AV | 148 | 09-Run Cycles | Boiler 12: run cycle count (0-999,999) | Read | ||
| AV | 149 | 10-Run Hours | Boiler 12: run hours (0-999,999) | h | Read | |
| AV | 172 | 11-Oxygen | Boiler 12: flue O2 level (0-25) | % | Read | |
| AV | 192 | 12-Exhaust Temp | Boiler 12: exhaust temperature (50-550) | °F | Read | |
| AV | 31 | 01-Fire Rate Out | ACS/BMS II: plant fire rate output (0-100) | % | Read | |
| AV | 32 | 02-Header Set Temp | ACS/BMS II: header setpoint in use (40-220) | °F | Read | |
| AVmin | 33 | 03-Net Header Set Temp | ACS/BMS II: network header setpoint (40-220) | °F | Write | |
| AVmin | 34 | 04-Header Temp | ACS/BMS II: header temperature (40-220) | °F | Read | |
| AV | 35 | 05-Outside Air Temp | ACS/BMS II: outdoor air temperature (-60 to 120) | °F | Read | |
| AVmin | 36 | 06-Display Code | ACS/BMS II: fault/message bit field | Read | Bit 0=Outside air sensor error, Bit 1=Header sensor error, Bit 2=Interlock 1 error, Bit 3=Interlock 2 error, Bit 4=Indoor air/return sensor error, Bit 5=4-20 mA input error | |
| AV | 37 | 07-Num Boilers Fired | ACS/BMS II: number of boilers firing | Read | ||
| AV | 38 | 08-Num Boilers Online | ACS/BMS II: number of boilers on line | Read | ||
| AV | 39 | 09-Last Blr Fired | ACS/BMS II: last boiler fired | Read | ||
| AV | 40 | 10-Boiler 1 Status | ACS/BMS II: status of PWM-controlled boiler 1 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired | |
| AV | 41 | 11-Boiler 2 Status | ACS/BMS II: status of PWM-controlled boiler 2 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired | |
| AV | 48 | 12-Boiler 3 Status | ACS/BMS II: status of PWM-controlled boiler 3 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired | |
| AV | 1 | 13-Boiler 4 Status | ACS/BMS II: status of PWM-controlled boiler 4 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired | |
| AV | 2 | 14-Boiler 5 Status | ACS/BMS II: status of PWM-controlled boiler 5 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired | |
| AV | 3 | 15-Boiler 6 Status | ACS/BMS II: status of PWM-controlled boiler 6 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired | |
| AV | 4 | 16-Boiler 7 Status | ACS/BMS II: status of PWM-controlled boiler 7 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired | |
| AV | 5 | 17-Boiler 8 Status | ACS/BMS II: status of PWM-controlled boiler 8 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired | |
| AV | 6 | 18-Net Blr 1 Status | ACS/BMS II: status of network boiler 1 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 7 | 19-Net Blr 2 Status | ACS/BMS II: status of network boiler 2 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 8 | 20-Net Blr 3 Status | ACS/BMS II: status of network boiler 3 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 9 | 21-Net Blr 4 Status | ACS/BMS II: status of network boiler 4 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 10 | 22-Net Blr 5 Status | ACS/BMS II: status of network boiler 5 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 11 | 23-Net Blr 6 Status | ACS/BMS II: status of network boiler 6 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 12 | 24-Net Blr 7 Status | ACS/BMS II: status of network boiler 7 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 13 | 25-Net Blr 8 Status | ACS/BMS II: status of network boiler 8 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 14 | 26-Net Blr 9 Status | ACS/BMS II: status of network boiler 9 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 15 | 27-Net Blr 10 Status | ACS/BMS II: status of network boiler 10 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 16 | 28-Net Blr 11 Status | ACS/BMS II: status of network boiler 11 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 17 | 29-Net Blr 12 Status | ACS/BMS II: status of network boiler 12 | Read | 1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted | |
| AV | 173 | 30-Return Temp | ACS/BMS II: return temperature | °F | Read |
No points match these filters.
Object ID lookup: AERCO C-More boilers with ACS / BMS II point IDs by name
AV2601-Fire Rate OutAV2702-Active SetpointAV2403-Net Remote SetptAV2805-Fire Rate InAV2906-Outlet TempAV2207-Display CodeAV2308-Unit StatusAV4209-Run CyclesAV4310-Run HoursAV16111-OxygenAV18112-Exhaust TempAV3001-Fire Rate OutAV4602-Active SetpointAV4703-Net Remote SetptAV5005-Fire Rate InAV5106-Outlet TempAV5207-Display CodeAV5308-Unit StatusAV4409-Run CyclesAV4510-Run HoursAV16211-OxygenAV18212-Exhaust TempAV5401-Fire Rate OutAV5502-Active SetpointAV5603-Net Remote SetptAV6005-Fire Rate InAV6106-Outlet TempAV6207-Display CodeAV6308-Unit StatusAV5809-Run CyclesAV5910-Run HoursAV16311-OxygenAV18312-Exhaust TempAV7001-Fire Rate OutAV7102-Active SetpointAV7203-Net Remote SetptAV7305-Fire Rate InAV6506-Outlet TempAV6607-Display CodeAV6708-Unit StatusAV6809-Run CyclesAV6910-Run HoursAV16411-OxygenAV18412-Exhaust TempAV8001-Fire Rate OutAV8102-Active SetpointAV8203-Net Remote SetptAV7405-Fire Rate InAV7506-Outlet TempAV7607-Display CodeAV7708-Unit StatusAV7809-Run CyclesAV7910-Run HoursAV16511-OxygenAV18512-Exhaust TempAV9001-Fire Rate OutAV9102-Active SetpointAV9203-Net Remote SetptAV8405-Fire Rate InAV8506-Outlet TempAV8607-Display CodeAV8708-Unit StatusAV8809-Run CyclesAV8910-Run HoursAV16611-OxygenAV18612-Exhaust TempAV10001-Fire Rate OutAV10102-Active SetpointAV10203-Net Remote SetptAV9405-Fire Rate InAV9506-Outlet TempAV9607-Display CodeAV9708-Unit StatusAV9809-Run CyclesAV9910-Run HoursAV16711-OxygenAV18712-Exhaust TempAV11001-Fire Rate OutAV11102-Active SetpointAV11203-Net Remote SetptAV10405-Fire Rate InAV10506-Outlet TempAV10607-Display CodeAV10708-Unit StatusAV10809-Run CyclesAV10910-Run HoursAV16811-OxygenAV18812-Exhaust TempAV12001-Fire Rate OutAV12102-Active SetpointAV12203-Net Remote SetptAV11405-Fire Rate InAV11506-Outlet TempAV11607-Display CodeAV11708-Unit StatusAV11809-Run CyclesAV11910-Run HoursAV16911-OxygenAV18912-Exhaust TempAV13001-Fire Rate OutAV13102-Active SetpointAV13203-Net Remote SetptAV12405-Fire Rate InAV12506-Outlet TempAV12607-Display CodeAV12708-Unit StatusAV12809-Run CyclesAV12910-Run HoursAV17011-OxygenAV19012-Exhaust TempAV14001-Fire Rate OutAV14102-Active SetpointAV14203-Net Remote SetptAV13405-Fire Rate InAV13506-Outlet TempAV13607-Display CodeAV13708-Unit StatusAV13809-Run CyclesAV13910-Run HoursAV17111-OxygenAV19112-Exhaust TempAV15001-Fire Rate OutAV15102-Active SetpointAV15203-Net Remote SetptAV14405-Fire Rate InAV14506-Outlet TempAV14607-Display CodeAV14708-Unit StatusAV14809-Run CyclesAV14910-Run HoursAV17211-OxygenAV19212-Exhaust TempAV3101-Fire Rate OutAV3202-Header Set TempAV3303-Net Header Set TempAV3404-Header TempAV3505-Outside Air TempAV3606-Display CodeAV3707-Num Boilers FiredAV3808-Num Boilers OnlineAV3909-Last Blr FiredAV4010-Boiler 1 StatusAV4111-Boiler 2 StatusAV4812-Boiler 3 StatusAV113-Boiler 4 StatusAV214-Boiler 5 StatusAV315-Boiler 6 StatusAV416-Boiler 7 StatusAV517-Boiler 8 StatusAV618-Net Blr 1 StatusAV719-Net Blr 2 StatusAV820-Net Blr 3 StatusAV921-Net Blr 4 StatusAV1022-Net Blr 5 StatusAV1123-Net Blr 6 StatusAV1224-Net Blr 7 StatusAV1325-Net Blr 8 StatusAV1426-Net Blr 9 StatusAV1527-Net Blr 10 StatusAV1628-Net Blr 11 StatusAV1729-Net Blr 12 StatusAV17330-Return Temp
Integration notes
- Older document (OMM-0080_0H, November 2014) for the ProtoNode RER gateway.
- Object IDs are fixed per profile and do not follow a formula; the 4- and 8-boiler profiles use the same IDs for the boilers and ACS values they include.
- Each boiler's points carry the same names (01-Fire Rate Out ...); the boiler number is in the description.
- The read-only column marks 03-Net Remote Setpt inconsistently between profiles; it is a Modbus holding register (40001) and is listed here as writable.
- 04-Net Direct Drive (C-More firing rate) appears only in special profiles and is not in this table.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the C-More boilers with ACS / BMS II (ProtoNode RER) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AERCO C-More boilers with ACS / BMS II (ProtoNode RER)
How many BACnet points does the AERCO C-More boilers with ACS / BMS II (ProtoNode RER) have?
This list has 162 BACnet objects: 162 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet points are writable?
13 of the 162 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet documentation?
The source is AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 (OMM-0080_0H), revision 2014-11-06, published free by AERCO at https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/58249-source/637395359810000000/omm-0080-0h-gf-129-protonode-ler-rer-11-06-14.pdf.
What are the minimum BACnet points to integrate the AERCO C-More boilers with ACS / BMS II (ProtoNode RER)?
Start with AV 33 03-Net Header Set Temp (Plant header setpoint via ACS/BMS II, 40-220 °F); AV 24 03-Net Remote Setpt (Boiler 1 network setpoint, 40-220 °F); AV 23 08-Unit Status (Boiler 1 status; 5 = Fault); AV 34 04-Header Temp (Header water temperature, °F); AV 29 06-Outlet Temp (Boiler 1 outlet water temperature, °F); AV 26 01-Fire Rate Out (Boiler 1 fire rate, %); AV 22 07-Display Code (Boiler 1 status/fault message code); AV 36 06-Display Code (ACS/BMS II fault bit field).
How do I enable BMS control of the AERCO C-More boilers with ACS / BMS II (ProtoNode RER)?
No start/stop object. For plant control set the ACS/BMS II to Header Set Mode = Remote Setpt and Remote Signal = Network, then write AV 33. For a single C-More set Boiler Mode = Remote Setpt and Remote Signal = Network, then write its 03-Net Remote Setpt. Monitor-only needs just the Modbus address and 9600 baud.
Does the AERCO C-More boilers with ACS / BMS II (ProtoNode RER) need a BACnet heartbeat or have a communication timeout?
The BAS must write the setpoint at least three times within the unit's Network Timeout or the unit stops using it. Defaults are 30 s on C-More (5-999 s, Configuration menu), ACS (5-240 s) and BMS II (5-240 s, RS-232 menu).
How do I check these points on the real C-More boilers with ACS / BMS II (ProtoNode RER)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AERCO BACnet points lists
- Digital DHW mixing valve system (water tempering)
AERCO ADMS Smart Water Tempering System
AERCO ADMS digital mixing (water tempering) systems for domestic hot water.
Also known as: ADMS, AERCO ADMS, Smart Water Tempering System, 106902, OMM-0126 - Boiler / water heater controller gateway
AERCO AM Series Dependent boiler / water heater (ProtoNode FPC-N34/N35)
AERCO AM Series boilers or water heaters set up as dependent units of a cascade, read through the AERCO ProtoNode FPC-N34 / FPC-N35.
Also known as: AM Series, AM Dependent, AM Dep, AERCO AM, ProtoNode FPC-N34, FPC-N35 - Boiler / water heater cascade controller gateway
AERCO AM Series Managing boiler / water heater (ProtoNode FPC-N34/N35)
AERCO AM Series boilers or water heaters set up as the managing (or stand-alone) unit of a cascade, read through the AERCO ProtoNode FPC-N34 / FPC-N35.
Also known as: AM Series, AM Manager, AM Mngr, AERCO AM, ProtoNode FPC-N34, FPC-N35 - Boiler plant manager (sequencing controller)
AERCO Benchmark / Innovation Edge controller - BST Manager plant objects
AERCO Benchmark boilers and Innovation water heaters with an Edge [i] or Edge [ii] controller acting as BST Manager for up to 16 units, with optional SmartPlate / SmartPlate EV units.
Also known as: BST Manager, Boiler Sequencing Technology, Edge [i], Edge [ii], Benchmark Edge, BMK Edge, Innovation Edge, OMM-0140, SmartPlate via Edge - Boiler controller
AERCO Benchmark E / Edge X
AERCO Benchmark E (BMK E) condensing boilers with the Edge X controller, including BST cascade plants; the table also lists the legacy Benchmark (BMK) Edge equivalents.
Also known as: BMK E, BMKE, Benchmark, Edge X, Edge controller, OMM-0173 - Boiler and water heater plant controller via ProtoNode gateway
AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)
AERCO C-More boilers running on-board BST sequencing and C-More water heaters (KC, Innovation) running WHM, up to 8 units, through the ProtoNode RER SSD profile.
Also known as: C-More, BST, Boiler Sequencing Technology, WHM, Water Heater Management, SSD, Slave/Slave Device, Innovation, KC, Benchmark, ProtoNode RER, 64084, GF-129, OMM-0080 - Boiler and water heater plant gateway (multi-unit)
AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)
A combined AERCO plant of 12 C-More boilers, 4 Modulex boilers, 6 ECS/SmartPlate water heater valves and two BMS II boiler managers on one gateway.
Also known as: AERCO ProtoNode, C-More, Modulex, ECS, SmartPlate, BMS II, AERCO-ProtoNode-Control-Points - Water heater controller via ProtoNode gateway
AERCO ECS and SmartPlate water heaters (ProtoNode RER)
AERCO SmartPlate and ECS (Electric Valve) water heaters, up to four, read through the AERCO ProtoNode RER.
Also known as: ECS, Electronic Control System, SmartPlate, SmartPlate water heater, E Valve, ProtoNode RER, 64084, GF-129, OMM-0080 - Commercial water heater controller
AERCO Edge [ii] water heater controller (standalone / WHM)
AERCO Innovation 1600-2000 water heaters with the Edge [ii] controller, run standalone or as a WHM (Water Heater Management) manager or client.
Also known as: Edge [ii], Edge ii, Edge 2, WHM, Water Heater Management, Centurion, OMM-0176, Innovation 1600-2000 - Boiler controller and plant sequencer via ProtoNode gateway
AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)
AERCO Modulex boilers with a BCM, up to four, plus an ACS or BMS II sequencer, read through the AERCO ProtoNode RER.
Also known as: Modulex, MLX, Modulex E8, BCM, ACS, BMS II, ProtoNode RER, 64084, GF-129, OMM-0080
Source: AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 · OMM-0080_0H · rev. 2014-11-06. Object names, instances and units are reproduced as published; descriptions are our own.