Boiler controller · BACnet points list
AERCO Benchmark E / Edge X BACnet points list
Updated 28 October 2026
The Edge X controller on AERCO's Benchmark E boilers talks BACnet IP on its Ethernet port or BACnet MS/TP on its RS-485 port. Standalone and client units expose their own setpoints and readings, while a BST cascade manager also exposes plant-level values and a block of read-only points for every unit in the cascade (up to 16). Only analog inputs (read only) and analog values (read/write) are used.
This page lists 390 BACnet objects for the AERCO Benchmark E / Edge X — 38 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.
- Manufacturer
- AERCO
- Model
- Benchmark E / Edge X
- Equipment
- Boiler controller
- Equipment type
- Boilers & water heaters
- BACnet objects
- 390 (38 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Application software 1.0 (PICS dated October 2024)
- Also known as
- BMK E, BMKE, Benchmark, Edge X, Edge controller, OMM-0173
Reference only, provided as-is: verify against AERCO’s current documentation and the live device before use. Not official AERCO information. Terms of use.
BMS integration notes: AERCO Benchmark E / Edge X
Enable the BAS port in the Edge X Comm & Failsafe menu (BACnet IP on the J5 Ethernet jack or MS/TP on the RS-485 terminals), choose the comm-loss behaviour, then have the BAS write the setpoint. For a cascade, connect the BAS to the BST manager only; it exposes plant values plus a read-only block for each unit. A technician-level password is needed before BAS points are available.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 12 | Operating Mode | Selects constant, remote or outdoor-reset setpoint | Write |
| AV 13 | Remote Signal | Set to BAS so the remote setpoint comes from BACnet | Write |
| AV 4 | Setpoint | Unit temperature setpoint, 35-220 °F | Write |
| AV 200 | Setpoint | Plant setpoint on a BST manager | Write |
| AI 1 | Unit Status | Standby / manual / auto / fault state | Read |
| AI 2 | Outlet Temp | Outlet water temperature | Read |
| AI 0 | Active Event ID | Active event / fault code | Read |
| AI 108 | Units Faulted | Units faulted in the cascade | Read |
Enable & remote start
On the controller go to Settings > Advanced Setup > Comm & Failsafe and enable BAS; for IP turn on the "BAS (J6)" toggle, which actually uses the J5 jack. The object list has no separate start/stop object: the BAS controls the unit through AV 12 Operating Mode, AV 13 Remote Signal (0 = BAS) and the setpoint in AV 4, or AV 200 on a BST manager. Firing-rate control (Direct Drive) is listed only for legacy BMK units.
Heartbeat & communication loss
The BAS Comm Failsafe setting chooses whether the unit shuts down or runs at a constant setpoint when it loses the BAS (AV 24 Unit Failsafe Mode: 0 = Standby, 1 = Constant Setpt). The BACnet IP screen also has a delay-before-communication-fault setting; its range and default are not given.
Sensors & values from the BMS
AV 85 / AV 213 Supply Header Temp Source and AV 215 return header source can be set to BAS (2), but the object list has no writable header or outdoor temperature value. On BMK E the outdoor sensor source (AV 81 / AV 217) is listed as Direct only.
Network setup
- BACnet IP settings on the controller include DHCP on/off, IP address, a device-instance offset to avoid duplicates, the UDP port, network number and comm-fault delay; defaults are not printed.
- MS/TP uses the same configuration screen with only the baud rate added; wire to J16 pins 5 (+) and 7 (-) on the I/O board and use the MODBUS1 (SW4) TERM1 switch at the ends of the BAS trunk.
- One BAS connection per cascade manager or standalone unit; manager and clients talk to each other over Modbus RS-485.
- BACnet vendor ID 983; ReadProperty and WriteProperty only, no segmentation.
Watch out for
- Cascade unit blocks: unit 1 = AI 300-320, unit 2 = AI 400-420 ... unit 16 = AI 1800-1820.
- Several IDs have different names or ranges on legacy Benchmark (BMK) Edge units; check which controller you have.
- AV 8 switches the BAS interface between English and Metric units.
AERCO Benchmark E / Edge X BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 2 | BAS Password | Password for BAS write access | Write | ||
| AVmin | 4 | Setpoint | Unit temperature setpoint (35-220 °F) | °F | Write | |
| AV | 5 | Language | Display language | Write | 0=English (BMK also 1=Spanish, 2=French) | |
| AV | 6 | Time | Controller time (legacy BMK only) | Write | ||
| AV | 7 | Date | Controller date (legacy BMK only) | Write | ||
| AV | 8 | Unit of Measurement BAS | Units used on the BAS interface | Write | English / Metric | |
| AV | 9 | Cascade Baud Rate | Cascade (BST/IST/WHM) Modbus baud rate | Write | 0=9600, 1=19200, 2=38400, 3=57600, 4=115200 | |
| AV | 10 | Unit Type | Appliance type (legacy BMK only) | Write | 0=KC Boiler, 1=KC Boiler LN, 2=BMK Boiler Std, 3=BMK Blr Std Dual, 4=BMK Boiler LN, 5=BMK Blr LN Dual, 6=KC Water Heater, 7=KC Water Heater LN, 8=Innovation, 9=Innovation N | |
| AV | 11 | Unit Size | Appliance size (legacy BMK only) | Write | 0=Spare, 1=600 MBH, 2=800 MBH, 3=1060 MBH, 4=1350 MBH, 5=500 MBH, 6=750 MBH, 7=1000 MBH, 8=1.5 MBTU, 9=1500 MBH, 10=2.0 MBTU, 11=2000 MBH, 12=2500 MBH, 13=3.0 MBTU, 14=3000 MBH, 15=4000 MBH, 16=5000 MBH, 17=6000 MBH | |
| AVmin | 12 | Operating Mode | How the unit gets its setpoint | Write | 0=Constant Setpt, 1=Rmt Setpt, 2=Outdoor Reset (BMK: 0=Constant, 1=Remote, 2=Direct Drive, 3=Combination, 4=Outdoor Reset) | |
| AVmin | 13 | Remote Signal | Source of the remote setpoint signal | Write | 0=BAS, 1=Analog Input (BMK: 0=4-20mA/1-5V, 1=0-20mA/0-5V, 2=Network, 3=BAS, 4=BST PWM) | |
| AV | 16 | Outdoor Sensor On/Off | Enables the outdoor air sensor | Write | Disable / Enable | |
| AV | 17 | Warm Weather Standby Temperature | Outdoor temperature for warm weather standby (BMK: Warm Weather Shtdwn) | °F | Write | |
| AV | 18 | SH Temperature Control Setpoint Low Limit | Lowest allowed setpoint (BMK: Setpoint Low Limit) | °F | Write | |
| AV | 19 | SH Temperature Control Setpoint Hi Limit | Highest allowed setpoint (BMK: Setpoint High Limit) | °F | Write | |
| AV | 20 | Temperature High Limit | Outlet temperature high limit | °F | Write | |
| AV | 23 | Interlocks Aux Delay 2 | Auxiliary interlock delay (BMK: Auxiliary Delay) | s | Write | |
| AV | 24 | Unit Failsafe Mode | Behaviour when the BAS signal is lost | Write | 0=Standby, 1=Constant Setpt (BMK: 0=Shutdown, 1=Constant Setpt) | |
| AV | 26 | Proportional Band | PID proportional band | °F | Write | |
| AV | 27 | Integral Band | PID integral gain | Write | ||
| AV | 28 | Derivative Band | PID derivative time (legacy BMK only) | min | Write | |
| AV | 70 | BAS | BAS protocol selection (legacy BMK only) | Write | 0=Off, 1=BACnet MSTP, 2=BACnet IP, 3=Modbus RTU, 4=Modbus TCP | |
| AV | 71 | BAS Baud Rate | BAS serial baud rate (legacy BMK only) | Write | 0=9600, 1=19200, 2=38400, 3=57600 | |
| AV | 81 | Outdoor Air Temp Sensor | Outdoor temperature source (BMK: Outdoor Temp Source) | Write | Direct (BMK: 0=Network, 1=Direct, 2=BAS) | |
| AV | 83 | PLM Enabled | Enables power limit management (BMK E only) | Write | 0=Disable, 1=Enable | |
| AV | 84 | PLM Power Limit | Power limit for PLM (BMK E only) | % | Write | |
| AV | 85 | Supply Header Temp Source | Supply header sensor source (BMK E only) | Write | 0=Off, 1=Direct, 2=BAS | |
| AImin | 0 | Active Event ID | Active event code (BMK: Message Code) | Read | ||
| AImin | 1 | Unit Status | Current unit state | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Direct Drive, 5=Fault, 6=Unit in Demand Delay, 7=Unit Starting (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AImin | 2 | Outlet Temp | Outlet water temperature | °F | Read | |
| AI | 3 | Inlet Temp | Inlet water temperature | °F | Read | |
| AI | 5 | Outdoor Air Temp | Outdoor air temperature (BMK: Outside Temp) | °F | Read | |
| AI | 11 | Run Cycles | Total burner run cycles | Read | ||
| AI | 13 | Run Hours | Total run hours | h | Read | |
| AI | 16 | Active Setpoint Temp | Setpoint currently in use | °F | Read | |
| AI | 17 | PID Output | PID output (legacy BMK only) | % | Read | |
| AI | 19 | BAS Communication Address | BAS network address of the unit | Read | ||
| AI | 45 | Valve Control Mode | Isolation valve control mode (BMK: Control Mode) | Read | 0=On/Off (BMK: 0=On/Off, 1=Linear Modulation, 2=Delta T Modulation) | |
| AI | 46 | Isolation Feedback Mode | Isolation valve feedback enabled | Read | Disable / Enable | |
| AI | 47 | Minimum Signal Level | Valve signal minimum (BMK: Open Vlv Control Signal) | Read | BMK E: 0-10 V / 0-20 mA (BMK: 0=0mA, 1=4mA, 2=20mA) | |
| AI | 48 | Maximum Signal Level | Valve signal maximum (BMK: Close Vlv Control Signal) | Read | BMK E: 0-10 V / 0-20 mA (BMK: 0=0mA, 1=4mA, 2=20mA) | |
| AI | 148 | Serial Alpha | Serial number letter (BMK: Unit Alpha) | Read | 0=E, 1=G, 2=H, 3=R, 4=N, 5=A, 6=Z | |
| AI | 149 | Serial Year | Serial number year (BMK: Unit Year) | Read | ||
| AI | 150 | Serial Number | Serial number digits (BMK: Unit Serial #) | Read | ||
| AI | 152 | Unit Mode | Standalone or cascade role | Read | 0=Standalone, 1=Cascade (BMK: 0=Off/Standalone, 1=Client, 2=Manager) | |
| AI | 153 | Unit Size | Benchmark E size (BMK E only) | Read | 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 154 | Unit Type | Appliance type (BMK E only) | Read | 0=KC Boiler, 1=KC Boiler LN, 2=BMK Boiler Std, 3=BMK Blr Std Dual, 4=BMK Boiler LN, 5=BMK Blr LN Dual, 6=BMK Inlet Natural Gas, 7=BMK Inlet Dual Fuel, 8=BMK Dual Inlet NGas, 9=BMK Dual Inlet Dual Fuel, 10=SmartPlate, 11=Benchmark E, 12=Other | |
| AI | 155 | BAS Enable | Active BAS protocol (BMK E only) | Read | 0=Off, 1=BACnet MSTP, 2=BACnet IP | |
| AI | 156 | BAS Baud Rate | BAS MS/TP baud rate (BMK E only) | Read | 0=9600, 1=19200, 2=38400, 4=115200 | |
| AI | 157 | Power Output | Current power output (BMK E only) | % | Read | |
| AI | 158 | Header Temp | Header temperature (BMK E only) | °F | Read | |
| AVmin | 200 | Setpoint | Plant setpoint | °F | Write | |
| AV | 201 | Setback Setpoint | Plant setback setpoint | °F | Write | |
| AV | 202 | Setback Start Time | Setback schedule start time | Write | ||
| AV | 203 | Setback Stop Time | Setback schedule stop time | Write | ||
| AV | 204 | SH Temperature Control Setback Schedule | Enables the setback schedule | Write | Disable / Enable | |
| AV | 213 | Supply Header Temp Source | Supply header sensor source | Write | 0=Off, 1=Direct, 2=BAS | |
| AV | 215 | Rtn Hdr Temp Sensor | Return header sensor source | Write | 0=Off, 1=Direct, 2=BAS | |
| AV | 217 | Outdoor Air Temp Sens | Outdoor air sensor source | Write | Direct | |
| AV | 219 | BACnet Communication Protocol | BACnet data link in use | Write | 0=BACnet IP, 1=BACnet MSTP (also printed as 0=Off, 1=BACnet MSTP, 2=BACnet IP) | |
| AV | 230 | PLM Enabled | Enables plant power limit management | Write | 0=Disable, 1=Enable | |
| AV | 231 | PLM Power Limit | Plant power limit | % | Write | |
| AI | 100 | Unit Role | Cascade role of this unit | Read | 0=BST Manager, 1=BST Client | |
| AI | 101 | Setpoint | Plant setpoint | °F | Read | |
| AI | 102 | Setback Setpoint | Plant setback setpoint | °F | Read | |
| AI | 103 | Setback Start Time | Setback schedule start time | Read | ||
| AI | 104 | Setback Stop Time | Setback schedule stop time | Read | ||
| AI | 106 | Average Outlet Temp | Average outlet temperature of the plant (BMK: Outlet Temp) | °F | Read | |
| AI | 107 | Units Available | Units available to the cascade | Read | ||
| AImin | 108 | Units Faulted | Units in fault | Read | ||
| AI | 109 | BAS Communication Address | BAS network address | Read | ||
| AI | 110 | Header Temp | Header temperature | °F | Read | |
| AI | 111 | Outdoor Air Temperature | Outdoor air temperature | °F | Read | |
| AI | 112 | Average Power Output | Average plant power output | % | Read | |
| AI | 113 | Units Active | Units currently firing | Read | ||
| AI | 114 | Active Setpoint | Plant setpoint currently in use | °F | Read | |
| AI | 115 | Gas Next On Threshold | Firing rate that brings on the next gas unit | % | Read | |
| AI | 116 | SH Temperature Control Setpoint Hi Limit | Highest allowed plant setpoint | °F | Read | |
| AI | 117 | SH Temperature Control Setpoint Low Limit | Lowest allowed plant setpoint | °F | Read | |
| AI | 118 | Temperature High Limit | Plant temperature high limit | °F | Read | |
| AI | 119 | Operating Mode | Plant setpoint mode | Read | 0=Constant Setpoint, 1=Rmt Setpt, 2=Outdoor Air Reset | |
| AI | 120 | Next Off Valve Pos Gas | Valve position that stages off the next gas unit | % | Read | |
| AI | 122 | Casc Next On Valve Pos Elec | Valve position that stages on the next electric unit | % | Read | |
| AI | 123 | Power Output | Plant power output | % | Read | |
| AI | 124 | Next Off Valve Pos Elec | Valve position that stages off the next electric unit | % | Read | |
| AI | 126 | BAS Baud Rate | BAS MS/TP baud rate | Read | 0=9600, 1=19200, 2=38400, 3=57600, 4=115200 | |
| AI | 300 | Cascade Unit Address | Cascade unit 1: cascade address (BMK: Communication Address) | Read | ||
| AI | 301 | Cascade Client State | Cascade unit 1: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 302 | Active Event ID | Cascade unit 1: active event code (BMK: Fault Code) | Read | ||
| AI | 303 | Outlet Temp | Cascade unit 1: outlet temperature | °F | Read | |
| AI | 305 | Inlet Temp | Cascade unit 1: inlet temperature | °F | Read | |
| AI | 306 | Exhaust Temp | Cascade unit 1: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 307 | Inlet Air Temp | Cascade unit 1: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 308 | Flame Strength | Cascade unit 1: flame strength (legacy BMK only) | % | Read | |
| AI | 309 | Fire Rate In | Cascade unit 1: fire rate in (legacy BMK only) | % | Read | |
| AI | 310 | Fire Rate Out | Cascade unit 1: fire rate out (legacy BMK only) | % | Read | |
| AI | 311 | Unit Type | Cascade unit 1: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 312 | Unit Size | Cascade unit 1: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 313 | Valve Status | Cascade unit 1: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 314 | Plant Setpoint | Cascade unit 1: plant setpoint seen by the unit | °F | Read | |
| AI | 315 | Run Cycles | Cascade unit 1: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 316 | Run Cycle Lower | Cascade unit 1: run cycles low word (legacy BMK only) | Read | ||
| AI | 317 | Run Hours | Cascade unit 1: run hours | h | Read | |
| AI | 319 | Oxygen Level | Cascade unit 1: flue oxygen (legacy BMK only) | % | Read | |
| AI | 320 | Power Output | Cascade unit 1: power output | % | Read | |
| AI | 400 | Cascade Unit Address | Cascade unit 2: cascade address (BMK: Communication Address) | Read | ||
| AI | 401 | Cascade Client State | Cascade unit 2: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 402 | Active Event ID | Cascade unit 2: active event code (BMK: Fault Code) | Read | ||
| AI | 403 | Outlet Temp | Cascade unit 2: outlet temperature | °F | Read | |
| AI | 405 | Inlet Temp | Cascade unit 2: inlet temperature | °F | Read | |
| AI | 406 | Exhaust Temp | Cascade unit 2: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 407 | Inlet Air Temp | Cascade unit 2: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 408 | Flame Strength | Cascade unit 2: flame strength (legacy BMK only) | % | Read | |
| AI | 409 | Fire Rate In | Cascade unit 2: fire rate in (legacy BMK only) | % | Read | |
| AI | 410 | Fire Rate Out | Cascade unit 2: fire rate out (legacy BMK only) | % | Read | |
| AI | 411 | Unit Type | Cascade unit 2: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 412 | Unit Size | Cascade unit 2: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 413 | Valve Status | Cascade unit 2: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 414 | Plant Setpoint | Cascade unit 2: plant setpoint seen by the unit | °F | Read | |
| AI | 415 | Run Cycles | Cascade unit 2: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 416 | Run Cycle Lower | Cascade unit 2: run cycles low word (legacy BMK only) | Read | ||
| AI | 417 | Run Hours | Cascade unit 2: run hours | h | Read | |
| AI | 419 | Oxygen Level | Cascade unit 2: flue oxygen (legacy BMK only) | % | Read | |
| AI | 420 | Power Output | Cascade unit 2: power output | % | Read | |
| AI | 500 | Cascade Unit Address | Cascade unit 3: cascade address (BMK: Communication Address) | Read | ||
| AI | 501 | Cascade Client State | Cascade unit 3: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 502 | Active Event ID | Cascade unit 3: active event code (BMK: Fault Code) | Read | ||
| AI | 503 | Outlet Temp | Cascade unit 3: outlet temperature | °F | Read | |
| AI | 505 | Inlet Temp | Cascade unit 3: inlet temperature | °F | Read | |
| AI | 506 | Exhaust Temp | Cascade unit 3: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 507 | Inlet Air Temp | Cascade unit 3: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 508 | Flame Strength | Cascade unit 3: flame strength (legacy BMK only) | % | Read | |
| AI | 509 | Fire Rate In | Cascade unit 3: fire rate in (legacy BMK only) | % | Read | |
| AI | 510 | Fire Rate Out | Cascade unit 3: fire rate out (legacy BMK only) | % | Read | |
| AI | 511 | Unit Type | Cascade unit 3: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 512 | Unit Size | Cascade unit 3: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 513 | Valve Status | Cascade unit 3: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 514 | Plant Setpoint | Cascade unit 3: plant setpoint seen by the unit | °F | Read | |
| AI | 515 | Run Cycles | Cascade unit 3: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 516 | Run Cycle Lower | Cascade unit 3: run cycles low word (legacy BMK only) | Read | ||
| AI | 517 | Run Hours | Cascade unit 3: run hours | h | Read | |
| AI | 519 | Oxygen Level | Cascade unit 3: flue oxygen (legacy BMK only) | % | Read | |
| AI | 520 | Power Output | Cascade unit 3: power output | % | Read | |
| AI | 600 | Cascade Unit Address | Cascade unit 4: cascade address (BMK: Communication Address) | Read | ||
| AI | 601 | Cascade Client State | Cascade unit 4: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 602 | Active Event ID | Cascade unit 4: active event code (BMK: Fault Code) | Read | ||
| AI | 603 | Outlet Temp | Cascade unit 4: outlet temperature | °F | Read | |
| AI | 605 | Inlet Temp | Cascade unit 4: inlet temperature | °F | Read | |
| AI | 606 | Exhaust Temp | Cascade unit 4: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 607 | Inlet Air Temp | Cascade unit 4: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 608 | Flame Strength | Cascade unit 4: flame strength (legacy BMK only) | % | Read | |
| AI | 609 | Fire Rate In | Cascade unit 4: fire rate in (legacy BMK only) | % | Read | |
| AI | 610 | Fire Rate Out | Cascade unit 4: fire rate out (legacy BMK only) | % | Read | |
| AI | 611 | Unit Type | Cascade unit 4: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 612 | Unit Size | Cascade unit 4: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 613 | Valve Status | Cascade unit 4: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 614 | Plant Setpoint | Cascade unit 4: plant setpoint seen by the unit | °F | Read | |
| AI | 615 | Run Cycles | Cascade unit 4: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 616 | Run Cycle Lower | Cascade unit 4: run cycles low word (legacy BMK only) | Read | ||
| AI | 617 | Run Hours | Cascade unit 4: run hours | h | Read | |
| AI | 619 | Oxygen Level | Cascade unit 4: flue oxygen (legacy BMK only) | % | Read | |
| AI | 620 | Power Output | Cascade unit 4: power output | % | Read | |
| AI | 700 | Cascade Unit Address | Cascade unit 5: cascade address (BMK: Communication Address) | Read | ||
| AI | 701 | Cascade Client State | Cascade unit 5: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 702 | Active Event ID | Cascade unit 5: active event code (BMK: Fault Code) | Read | ||
| AI | 703 | Outlet Temp | Cascade unit 5: outlet temperature | °F | Read | |
| AI | 705 | Inlet Temp | Cascade unit 5: inlet temperature | °F | Read | |
| AI | 706 | Exhaust Temp | Cascade unit 5: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 707 | Inlet Air Temp | Cascade unit 5: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 708 | Flame Strength | Cascade unit 5: flame strength (legacy BMK only) | % | Read | |
| AI | 709 | Fire Rate In | Cascade unit 5: fire rate in (legacy BMK only) | % | Read | |
| AI | 710 | Fire Rate Out | Cascade unit 5: fire rate out (legacy BMK only) | % | Read | |
| AI | 711 | Unit Type | Cascade unit 5: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 712 | Unit Size | Cascade unit 5: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 713 | Valve Status | Cascade unit 5: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 714 | Plant Setpoint | Cascade unit 5: plant setpoint seen by the unit | °F | Read | |
| AI | 715 | Run Cycles | Cascade unit 5: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 716 | Run Cycle Lower | Cascade unit 5: run cycles low word (legacy BMK only) | Read | ||
| AI | 717 | Run Hours | Cascade unit 5: run hours | h | Read | |
| AI | 719 | Oxygen Level | Cascade unit 5: flue oxygen (legacy BMK only) | % | Read | |
| AI | 720 | Power Output | Cascade unit 5: power output | % | Read | |
| AI | 800 | Cascade Unit Address | Cascade unit 6: cascade address (BMK: Communication Address) | Read | ||
| AI | 801 | Cascade Client State | Cascade unit 6: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 802 | Active Event ID | Cascade unit 6: active event code (BMK: Fault Code) | Read | ||
| AI | 803 | Outlet Temp | Cascade unit 6: outlet temperature | °F | Read | |
| AI | 805 | Inlet Temp | Cascade unit 6: inlet temperature | °F | Read | |
| AI | 806 | Exhaust Temp | Cascade unit 6: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 807 | Inlet Air Temp | Cascade unit 6: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 808 | Flame Strength | Cascade unit 6: flame strength (legacy BMK only) | % | Read | |
| AI | 809 | Fire Rate In | Cascade unit 6: fire rate in (legacy BMK only) | % | Read | |
| AI | 810 | Fire Rate Out | Cascade unit 6: fire rate out (legacy BMK only) | % | Read | |
| AI | 811 | Unit Type | Cascade unit 6: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 812 | Unit Size | Cascade unit 6: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 813 | Valve Status | Cascade unit 6: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 814 | Plant Setpoint | Cascade unit 6: plant setpoint seen by the unit | °F | Read | |
| AI | 815 | Run Cycles | Cascade unit 6: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 816 | Run Cycle Lower | Cascade unit 6: run cycles low word (legacy BMK only) | Read | ||
| AI | 817 | Run Hours | Cascade unit 6: run hours | h | Read | |
| AI | 819 | Oxygen Level | Cascade unit 6: flue oxygen (legacy BMK only) | % | Read | |
| AI | 820 | Power Output | Cascade unit 6: power output | % | Read | |
| AI | 900 | Cascade Unit Address | Cascade unit 7: cascade address (BMK: Communication Address) | Read | ||
| AI | 901 | Cascade Client State | Cascade unit 7: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 902 | Active Event ID | Cascade unit 7: active event code (BMK: Fault Code) | Read | ||
| AI | 903 | Outlet Temp | Cascade unit 7: outlet temperature | °F | Read | |
| AI | 905 | Inlet Temp | Cascade unit 7: inlet temperature | °F | Read | |
| AI | 906 | Exhaust Temp | Cascade unit 7: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 907 | Inlet Air Temp | Cascade unit 7: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 908 | Flame Strength | Cascade unit 7: flame strength (legacy BMK only) | % | Read | |
| AI | 909 | Fire Rate In | Cascade unit 7: fire rate in (legacy BMK only) | % | Read | |
| AI | 910 | Fire Rate Out | Cascade unit 7: fire rate out (legacy BMK only) | % | Read | |
| AI | 911 | Unit Type | Cascade unit 7: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 912 | Unit Size | Cascade unit 7: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 913 | Valve Status | Cascade unit 7: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 914 | Plant Setpoint | Cascade unit 7: plant setpoint seen by the unit | °F | Read | |
| AI | 915 | Run Cycles | Cascade unit 7: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 916 | Run Cycle Lower | Cascade unit 7: run cycles low word (legacy BMK only) | Read | ||
| AI | 917 | Run Hours | Cascade unit 7: run hours | h | Read | |
| AI | 919 | Oxygen Level | Cascade unit 7: flue oxygen (legacy BMK only) | % | Read | |
| AI | 920 | Power Output | Cascade unit 7: power output | % | Read | |
| AI | 1000 | Cascade Unit Address | Cascade unit 8: cascade address (BMK: Communication Address) | Read | ||
| AI | 1001 | Cascade Client State | Cascade unit 8: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1002 | Active Event ID | Cascade unit 8: active event code (BMK: Fault Code) | Read | ||
| AI | 1003 | Outlet Temp | Cascade unit 8: outlet temperature | °F | Read | |
| AI | 1005 | Inlet Temp | Cascade unit 8: inlet temperature | °F | Read | |
| AI | 1006 | Exhaust Temp | Cascade unit 8: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1007 | Inlet Air Temp | Cascade unit 8: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1008 | Flame Strength | Cascade unit 8: flame strength (legacy BMK only) | % | Read | |
| AI | 1009 | Fire Rate In | Cascade unit 8: fire rate in (legacy BMK only) | % | Read | |
| AI | 1010 | Fire Rate Out | Cascade unit 8: fire rate out (legacy BMK only) | % | Read | |
| AI | 1011 | Unit Type | Cascade unit 8: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1012 | Unit Size | Cascade unit 8: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1013 | Valve Status | Cascade unit 8: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1014 | Plant Setpoint | Cascade unit 8: plant setpoint seen by the unit | °F | Read | |
| AI | 1015 | Run Cycles | Cascade unit 8: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1016 | Run Cycle Lower | Cascade unit 8: run cycles low word (legacy BMK only) | Read | ||
| AI | 1017 | Run Hours | Cascade unit 8: run hours | h | Read | |
| AI | 1019 | Oxygen Level | Cascade unit 8: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1020 | Power Output | Cascade unit 8: power output | % | Read | |
| AI | 1100 | Cascade Unit Address | Cascade unit 9: cascade address (BMK: Communication Address) | Read | ||
| AI | 1101 | Cascade Client State | Cascade unit 9: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1102 | Active Event ID | Cascade unit 9: active event code (BMK: Fault Code) | Read | ||
| AI | 1103 | Outlet Temp | Cascade unit 9: outlet temperature | °F | Read | |
| AI | 1105 | Inlet Temp | Cascade unit 9: inlet temperature | °F | Read | |
| AI | 1106 | Exhaust Temp | Cascade unit 9: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1107 | Inlet Air Temp | Cascade unit 9: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1108 | Flame Strength | Cascade unit 9: flame strength (legacy BMK only) | % | Read | |
| AI | 1109 | Fire Rate In | Cascade unit 9: fire rate in (legacy BMK only) | % | Read | |
| AI | 1110 | Fire Rate Out | Cascade unit 9: fire rate out (legacy BMK only) | % | Read | |
| AI | 1111 | Unit Type | Cascade unit 9: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1112 | Unit Size | Cascade unit 9: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1113 | Valve Status | Cascade unit 9: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1114 | Plant Setpoint | Cascade unit 9: plant setpoint seen by the unit | °F | Read | |
| AI | 1115 | Run Cycles | Cascade unit 9: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1116 | Run Cycle Lower | Cascade unit 9: run cycles low word (legacy BMK only) | Read | ||
| AI | 1117 | Run Hours | Cascade unit 9: run hours | h | Read | |
| AI | 1119 | Oxygen Level | Cascade unit 9: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1120 | Power Output | Cascade unit 9: power output | % | Read | |
| AI | 1200 | Cascade Unit Address | Cascade unit 10: cascade address (BMK: Communication Address) | Read | ||
| AI | 1201 | Cascade Client State | Cascade unit 10: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1202 | Active Event ID | Cascade unit 10: active event code (BMK: Fault Code) | Read | ||
| AI | 1203 | Outlet Temp | Cascade unit 10: outlet temperature | °F | Read | |
| AI | 1205 | Inlet Temp | Cascade unit 10: inlet temperature | °F | Read | |
| AI | 1206 | Exhaust Temp | Cascade unit 10: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1207 | Inlet Air Temp | Cascade unit 10: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1208 | Flame Strength | Cascade unit 10: flame strength (legacy BMK only) | % | Read | |
| AI | 1209 | Fire Rate In | Cascade unit 10: fire rate in (legacy BMK only) | % | Read | |
| AI | 1210 | Fire Rate Out | Cascade unit 10: fire rate out (legacy BMK only) | % | Read | |
| AI | 1211 | Unit Type | Cascade unit 10: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1212 | Unit Size | Cascade unit 10: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1213 | Valve Status | Cascade unit 10: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1214 | Plant Setpoint | Cascade unit 10: plant setpoint seen by the unit | °F | Read | |
| AI | 1215 | Run Cycles | Cascade unit 10: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1216 | Run Cycle Lower | Cascade unit 10: run cycles low word (legacy BMK only) | Read | ||
| AI | 1217 | Run Hours | Cascade unit 10: run hours | h | Read | |
| AI | 1219 | Oxygen Level | Cascade unit 10: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1220 | Power Output | Cascade unit 10: power output | % | Read | |
| AI | 1300 | Cascade Unit Address | Cascade unit 11: cascade address (BMK: Communication Address) | Read | ||
| AI | 1301 | Cascade Client State | Cascade unit 11: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1302 | Active Event ID | Cascade unit 11: active event code (BMK: Fault Code) | Read | ||
| AI | 1303 | Outlet Temp | Cascade unit 11: outlet temperature | °F | Read | |
| AI | 1305 | Inlet Temp | Cascade unit 11: inlet temperature | °F | Read | |
| AI | 1306 | Exhaust Temp | Cascade unit 11: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1307 | Inlet Air Temp | Cascade unit 11: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1308 | Flame Strength | Cascade unit 11: flame strength (legacy BMK only) | % | Read | |
| AI | 1309 | Fire Rate In | Cascade unit 11: fire rate in (legacy BMK only) | % | Read | |
| AI | 1310 | Fire Rate Out | Cascade unit 11: fire rate out (legacy BMK only) | % | Read | |
| AI | 1311 | Unit Type | Cascade unit 11: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1312 | Unit Size | Cascade unit 11: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1313 | Valve Status | Cascade unit 11: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1314 | Plant Setpoint | Cascade unit 11: plant setpoint seen by the unit | °F | Read | |
| AI | 1315 | Run Cycles | Cascade unit 11: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1316 | Run Cycle Lower | Cascade unit 11: run cycles low word (legacy BMK only) | Read | ||
| AI | 1317 | Run Hours | Cascade unit 11: run hours | h | Read | |
| AI | 1319 | Oxygen Level | Cascade unit 11: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1320 | Power Output | Cascade unit 11: power output | % | Read | |
| AI | 1400 | Cascade Unit Address | Cascade unit 12: cascade address (BMK: Communication Address) | Read | ||
| AI | 1401 | Cascade Client State | Cascade unit 12: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1402 | Active Event ID | Cascade unit 12: active event code (BMK: Fault Code) | Read | ||
| AI | 1403 | Outlet Temp | Cascade unit 12: outlet temperature | °F | Read | |
| AI | 1405 | Inlet Temp | Cascade unit 12: inlet temperature | °F | Read | |
| AI | 1406 | Exhaust Temp | Cascade unit 12: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1407 | Inlet Air Temp | Cascade unit 12: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1408 | Flame Strength | Cascade unit 12: flame strength (legacy BMK only) | % | Read | |
| AI | 1409 | Fire Rate In | Cascade unit 12: fire rate in (legacy BMK only) | % | Read | |
| AI | 1410 | Fire Rate Out | Cascade unit 12: fire rate out (legacy BMK only) | % | Read | |
| AI | 1411 | Unit Type | Cascade unit 12: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1412 | Unit Size | Cascade unit 12: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1413 | Valve Status | Cascade unit 12: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1414 | Plant Setpoint | Cascade unit 12: plant setpoint seen by the unit | °F | Read | |
| AI | 1415 | Run Cycles | Cascade unit 12: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1416 | Run Cycle Lower | Cascade unit 12: run cycles low word (legacy BMK only) | Read | ||
| AI | 1417 | Run Hours | Cascade unit 12: run hours | h | Read | |
| AI | 1419 | Oxygen Level | Cascade unit 12: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1420 | Power Output | Cascade unit 12: power output | % | Read | |
| AI | 1500 | Cascade Unit Address | Cascade unit 13: cascade address (BMK: Communication Address) | Read | ||
| AI | 1501 | Cascade Client State | Cascade unit 13: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1502 | Active Event ID | Cascade unit 13: active event code (BMK: Fault Code) | Read | ||
| AI | 1503 | Outlet Temp | Cascade unit 13: outlet temperature | °F | Read | |
| AI | 1505 | Inlet Temp | Cascade unit 13: inlet temperature | °F | Read | |
| AI | 1506 | Exhaust Temp | Cascade unit 13: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1507 | Inlet Air Temp | Cascade unit 13: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1508 | Flame Strength | Cascade unit 13: flame strength (legacy BMK only) | % | Read | |
| AI | 1509 | Fire Rate In | Cascade unit 13: fire rate in (legacy BMK only) | % | Read | |
| AI | 1510 | Fire Rate Out | Cascade unit 13: fire rate out (legacy BMK only) | % | Read | |
| AI | 1511 | Unit Type | Cascade unit 13: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1512 | Unit Size | Cascade unit 13: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1513 | Valve Status | Cascade unit 13: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1514 | Plant Setpoint | Cascade unit 13: plant setpoint seen by the unit | °F | Read | |
| AI | 1515 | Run Cycles | Cascade unit 13: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1516 | Run Cycle Lower | Cascade unit 13: run cycles low word (legacy BMK only) | Read | ||
| AI | 1517 | Run Hours | Cascade unit 13: run hours | h | Read | |
| AI | 1519 | Oxygen Level | Cascade unit 13: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1520 | Power Output | Cascade unit 13: power output | % | Read | |
| AI | 1600 | Cascade Unit Address | Cascade unit 14: cascade address (BMK: Communication Address) | Read | ||
| AI | 1601 | Cascade Client State | Cascade unit 14: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1602 | Active Event ID | Cascade unit 14: active event code (BMK: Fault Code) | Read | ||
| AI | 1603 | Outlet Temp | Cascade unit 14: outlet temperature | °F | Read | |
| AI | 1605 | Inlet Temp | Cascade unit 14: inlet temperature | °F | Read | |
| AI | 1606 | Exhaust Temp | Cascade unit 14: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1607 | Inlet Air Temp | Cascade unit 14: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1608 | Flame Strength | Cascade unit 14: flame strength (legacy BMK only) | % | Read | |
| AI | 1609 | Fire Rate In | Cascade unit 14: fire rate in (legacy BMK only) | % | Read | |
| AI | 1610 | Fire Rate Out | Cascade unit 14: fire rate out (legacy BMK only) | % | Read | |
| AI | 1611 | Unit Type | Cascade unit 14: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1612 | Unit Size | Cascade unit 14: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1613 | Valve Status | Cascade unit 14: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1614 | Plant Setpoint | Cascade unit 14: plant setpoint seen by the unit | °F | Read | |
| AI | 1615 | Run Cycles | Cascade unit 14: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1616 | Run Cycle Lower | Cascade unit 14: run cycles low word (legacy BMK only) | Read | ||
| AI | 1617 | Run Hours | Cascade unit 14: run hours | h | Read | |
| AI | 1619 | Oxygen Level | Cascade unit 14: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1620 | Power Output | Cascade unit 14: power output | % | Read | |
| AI | 1700 | Cascade Unit Address | Cascade unit 15: cascade address (BMK: Communication Address) | Read | ||
| AI | 1701 | Cascade Client State | Cascade unit 15: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1702 | Active Event ID | Cascade unit 15: active event code (BMK: Fault Code) | Read | ||
| AI | 1703 | Outlet Temp | Cascade unit 15: outlet temperature | °F | Read | |
| AI | 1705 | Inlet Temp | Cascade unit 15: inlet temperature | °F | Read | |
| AI | 1706 | Exhaust Temp | Cascade unit 15: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1707 | Inlet Air Temp | Cascade unit 15: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1708 | Flame Strength | Cascade unit 15: flame strength (legacy BMK only) | % | Read | |
| AI | 1709 | Fire Rate In | Cascade unit 15: fire rate in (legacy BMK only) | % | Read | |
| AI | 1710 | Fire Rate Out | Cascade unit 15: fire rate out (legacy BMK only) | % | Read | |
| AI | 1711 | Unit Type | Cascade unit 15: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1712 | Unit Size | Cascade unit 15: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1713 | Valve Status | Cascade unit 15: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1714 | Plant Setpoint | Cascade unit 15: plant setpoint seen by the unit | °F | Read | |
| AI | 1715 | Run Cycles | Cascade unit 15: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1716 | Run Cycle Lower | Cascade unit 15: run cycles low word (legacy BMK only) | Read | ||
| AI | 1717 | Run Hours | Cascade unit 15: run hours | h | Read | |
| AI | 1719 | Oxygen Level | Cascade unit 15: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1720 | Power Output | Cascade unit 15: power output | % | Read | |
| AI | 1800 | Cascade Unit Address | Cascade unit 16: cascade address (BMK: Communication Address) | Read | ||
| AI | 1801 | Cascade Client State | Cascade unit 16: unit state (BMK: Unit Status) | Read | 0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault) | |
| AI | 1802 | Active Event ID | Cascade unit 16: active event code (BMK: Fault Code) | Read | ||
| AI | 1803 | Outlet Temp | Cascade unit 16: outlet temperature | °F | Read | |
| AI | 1805 | Inlet Temp | Cascade unit 16: inlet temperature | °F | Read | |
| AI | 1806 | Exhaust Temp | Cascade unit 16: exhaust temperature (legacy BMK only) | °F | Read | |
| AI | 1807 | Inlet Air Temp | Cascade unit 16: inlet air temperature (legacy BMK only) | °F | Read | |
| AI | 1808 | Flame Strength | Cascade unit 16: flame strength (legacy BMK only) | % | Read | |
| AI | 1809 | Fire Rate In | Cascade unit 16: fire rate in (legacy BMK only) | % | Read | |
| AI | 1810 | Fire Rate Out | Cascade unit 16: fire rate out (legacy BMK only) | % | Read | |
| AI | 1811 | Unit Type | Cascade unit 16: appliance type code | Read | BMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154) | |
| AI | 1812 | Unit Size | Cascade unit 16: appliance size code | Read | BMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW | |
| AI | 1813 | Valve Status | Cascade unit 16: isolation valve status | Read | 0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed | |
| AI | 1814 | Plant Setpoint | Cascade unit 16: plant setpoint seen by the unit | °F | Read | |
| AI | 1815 | Run Cycles | Cascade unit 16: run cycles (BMK: Run Cycle Upper) | Read | ||
| AI | 1816 | Run Cycle Lower | Cascade unit 16: run cycles low word (legacy BMK only) | Read | ||
| AI | 1817 | Run Hours | Cascade unit 16: run hours | h | Read | |
| AI | 1819 | Oxygen Level | Cascade unit 16: flue oxygen (legacy BMK only) | % | Read | |
| AI | 1820 | Power Output | Cascade unit 16: power output | % | Read |
No points match these filters.
Object ID lookup: AERCO Benchmark E / Edge X point IDs by name
AV2BAS PasswordAV4SetpointAV5LanguageAV6TimeAV7DateAV8Unit of Measurement BASAV9Cascade Baud RateAV10Unit TypeAV11Unit SizeAV12Operating ModeAV13Remote SignalAV16Outdoor Sensor On/OffAV17Warm Weather Standby TemperatureAV18SH Temperature Control Setpoint Low LimitAV19SH Temperature Control Setpoint Hi LimitAV20Temperature High LimitAV23Interlocks Aux Delay 2AV24Unit Failsafe ModeAV26Proportional BandAV27Integral BandAV28Derivative BandAV70BASAV71BAS Baud RateAV81Outdoor Air Temp SensorAV83PLM EnabledAV84PLM Power LimitAV85Supply Header Temp SourceAI0Active Event IDAI1Unit StatusAI2Outlet TempAI3Inlet TempAI5Outdoor Air TempAI11Run CyclesAI13Run HoursAI16Active Setpoint TempAI17PID OutputAI19BAS Communication AddressAI45Valve Control ModeAI46Isolation Feedback ModeAI47Minimum Signal LevelAI48Maximum Signal LevelAI148Serial AlphaAI149Serial YearAI150Serial NumberAI152Unit ModeAI153Unit SizeAI154Unit TypeAI155BAS EnableAI156BAS Baud RateAI157Power OutputAI158Header TempAV200SetpointAV201Setback SetpointAV202Setback Start TimeAV203Setback Stop TimeAV204SH Temperature Control Setback ScheduleAV213Supply Header Temp SourceAV215Rtn Hdr Temp SensorAV217Outdoor Air Temp SensAV219BACnet Communication ProtocolAV230PLM EnabledAV231PLM Power LimitAI100Unit RoleAI101SetpointAI102Setback SetpointAI103Setback Start TimeAI104Setback Stop TimeAI106Average Outlet TempAI107Units AvailableAI108Units FaultedAI109BAS Communication AddressAI110Header TempAI111Outdoor Air TemperatureAI112Average Power OutputAI113Units ActiveAI114Active SetpointAI115Gas Next On ThresholdAI116SH Temperature Control Setpoint Hi LimitAI117SH Temperature Control Setpoint Low LimitAI118Temperature High LimitAI119Operating ModeAI120Next Off Valve Pos GasAI122Casc Next On Valve Pos ElecAI123Power OutputAI124Next Off Valve Pos ElecAI126BAS Baud RateAI300Cascade Unit AddressAI301Cascade Client StateAI302Active Event IDAI303Outlet TempAI305Inlet TempAI306Exhaust TempAI307Inlet Air TempAI308Flame StrengthAI309Fire Rate InAI310Fire Rate OutAI311Unit TypeAI312Unit SizeAI313Valve StatusAI314Plant SetpointAI315Run CyclesAI316Run Cycle LowerAI317Run HoursAI319Oxygen LevelAI320Power OutputAI400Cascade Unit AddressAI401Cascade Client StateAI402Active Event IDAI403Outlet TempAI405Inlet TempAI406Exhaust TempAI407Inlet Air TempAI408Flame StrengthAI409Fire Rate InAI410Fire Rate OutAI411Unit TypeAI412Unit SizeAI413Valve StatusAI414Plant SetpointAI415Run CyclesAI416Run Cycle LowerAI417Run HoursAI419Oxygen LevelAI420Power OutputAI500Cascade Unit AddressAI501Cascade Client StateAI502Active Event IDAI503Outlet TempAI505Inlet TempAI506Exhaust TempAI507Inlet Air TempAI508Flame StrengthAI509Fire Rate InAI510Fire Rate OutAI511Unit TypeAI512Unit SizeAI513Valve StatusAI514Plant SetpointAI515Run CyclesAI516Run Cycle LowerAI517Run HoursAI519Oxygen LevelAI520Power OutputAI600Cascade Unit AddressAI601Cascade Client StateAI602Active Event IDAI603Outlet TempAI605Inlet TempAI606Exhaust TempAI607Inlet Air TempAI608Flame StrengthAI609Fire Rate InAI610Fire Rate OutAI611Unit TypeAI612Unit SizeAI613Valve StatusAI614Plant SetpointAI615Run CyclesAI616Run Cycle LowerAI617Run HoursAI619Oxygen LevelAI620Power OutputAI700Cascade Unit AddressAI701Cascade Client StateAI702Active Event IDAI703Outlet TempAI705Inlet TempAI706Exhaust TempAI707Inlet Air TempAI708Flame StrengthAI709Fire Rate InAI710Fire Rate OutAI711Unit TypeAI712Unit SizeAI713Valve StatusAI714Plant SetpointAI715Run CyclesAI716Run Cycle LowerAI717Run HoursAI719Oxygen LevelAI720Power OutputAI800Cascade Unit AddressAI801Cascade Client StateAI802Active Event IDAI803Outlet TempAI805Inlet TempAI806Exhaust TempAI807Inlet Air TempAI808Flame StrengthAI809Fire Rate InAI810Fire Rate OutAI811Unit TypeAI812Unit SizeAI813Valve StatusAI814Plant SetpointAI815Run CyclesAI816Run Cycle LowerAI817Run HoursAI819Oxygen LevelAI820Power OutputAI900Cascade Unit AddressAI901Cascade Client StateAI902Active Event IDAI903Outlet TempAI905Inlet TempAI906Exhaust TempAI907Inlet Air TempAI908Flame StrengthAI909Fire Rate InAI910Fire Rate OutAI911Unit TypeAI912Unit SizeAI913Valve StatusAI914Plant SetpointAI915Run CyclesAI916Run Cycle LowerAI917Run HoursAI919Oxygen LevelAI920Power OutputAI1000Cascade Unit AddressAI1001Cascade Client StateAI1002Active Event IDAI1003Outlet TempAI1005Inlet TempAI1006Exhaust TempAI1007Inlet Air TempAI1008Flame StrengthAI1009Fire Rate InAI1010Fire Rate OutAI1011Unit TypeAI1012Unit SizeAI1013Valve StatusAI1014Plant SetpointAI1015Run CyclesAI1016Run Cycle LowerAI1017Run HoursAI1019Oxygen LevelAI1020Power OutputAI1100Cascade Unit AddressAI1101Cascade Client StateAI1102Active Event IDAI1103Outlet TempAI1105Inlet TempAI1106Exhaust TempAI1107Inlet Air TempAI1108Flame StrengthAI1109Fire Rate InAI1110Fire Rate OutAI1111Unit TypeAI1112Unit SizeAI1113Valve StatusAI1114Plant SetpointAI1115Run CyclesAI1116Run Cycle LowerAI1117Run HoursAI1119Oxygen LevelAI1120Power OutputAI1200Cascade Unit AddressAI1201Cascade Client StateAI1202Active Event IDAI1203Outlet TempAI1205Inlet TempAI1206Exhaust TempAI1207Inlet Air TempAI1208Flame StrengthAI1209Fire Rate InAI1210Fire Rate OutAI1211Unit TypeAI1212Unit SizeAI1213Valve StatusAI1214Plant SetpointAI1215Run CyclesAI1216Run Cycle LowerAI1217Run HoursAI1219Oxygen LevelAI1220Power OutputAI1300Cascade Unit AddressAI1301Cascade Client StateAI1302Active Event IDAI1303Outlet TempAI1305Inlet TempAI1306Exhaust TempAI1307Inlet Air TempAI1308Flame StrengthAI1309Fire Rate InAI1310Fire Rate OutAI1311Unit TypeAI1312Unit SizeAI1313Valve StatusAI1314Plant SetpointAI1315Run CyclesAI1316Run Cycle LowerAI1317Run HoursAI1319Oxygen LevelAI1320Power OutputAI1400Cascade Unit AddressAI1401Cascade Client StateAI1402Active Event IDAI1403Outlet TempAI1405Inlet TempAI1406Exhaust TempAI1407Inlet Air TempAI1408Flame StrengthAI1409Fire Rate InAI1410Fire Rate OutAI1411Unit TypeAI1412Unit SizeAI1413Valve StatusAI1414Plant SetpointAI1415Run CyclesAI1416Run Cycle LowerAI1417Run HoursAI1419Oxygen LevelAI1420Power OutputAI1500Cascade Unit AddressAI1501Cascade Client StateAI1502Active Event IDAI1503Outlet TempAI1505Inlet TempAI1506Exhaust TempAI1507Inlet Air TempAI1508Flame StrengthAI1509Fire Rate InAI1510Fire Rate OutAI1511Unit TypeAI1512Unit SizeAI1513Valve StatusAI1514Plant SetpointAI1515Run CyclesAI1516Run Cycle LowerAI1517Run HoursAI1519Oxygen LevelAI1520Power OutputAI1600Cascade Unit AddressAI1601Cascade Client StateAI1602Active Event IDAI1603Outlet TempAI1605Inlet TempAI1606Exhaust TempAI1607Inlet Air TempAI1608Flame StrengthAI1609Fire Rate InAI1610Fire Rate OutAI1611Unit TypeAI1612Unit SizeAI1613Valve StatusAI1614Plant SetpointAI1615Run CyclesAI1616Run Cycle LowerAI1617Run HoursAI1619Oxygen LevelAI1620Power OutputAI1700Cascade Unit AddressAI1701Cascade Client StateAI1702Active Event IDAI1703Outlet TempAI1705Inlet TempAI1706Exhaust TempAI1707Inlet Air TempAI1708Flame StrengthAI1709Fire Rate InAI1710Fire Rate OutAI1711Unit TypeAI1712Unit SizeAI1713Valve StatusAI1714Plant SetpointAI1715Run CyclesAI1716Run Cycle LowerAI1717Run HoursAI1719Oxygen LevelAI1720Power OutputAI1800Cascade Unit AddressAI1801Cascade Client StateAI1802Active Event IDAI1803Outlet TempAI1805Inlet TempAI1806Exhaust TempAI1807Inlet Air TempAI1808Flame StrengthAI1809Fire Rate InAI1810Fire Rate OutAI1811Unit TypeAI1812Unit SizeAI1813Valve StatusAI1814Plant SetpointAI1815Run CyclesAI1816Run Cycle LowerAI1817Run HoursAI1819Oxygen LevelAI1820Power Output
Integration notes
- A technician-level password is needed on the controller before BAS points are available.
- BACnet vendor ID is 983; device profile B-ASC; ReadProperty and WriteProperty only, no segmentation.
- Cascade unit points repeat in blocks: unit 1 uses IDs 300-320, unit 2 uses 400-420, and so on up to unit 16 at 1800-1820.
- The manual lists one BAS connection per cascade manager or standalone unit; cascade members talk to the manager over Modbus RS-485.
- Several IDs carry different names or ranges on legacy Benchmark (BMK) Edge units; legacy names are given in the descriptions, and points marked legacy BMK only are not used on BMK E.
- Temperatures are listed in °F; AV 8 switches the BAS interface between English and Metric.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Benchmark E / Edge X and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AERCO Benchmark E / Edge X
How many BACnet points does the AERCO Benchmark E / Edge X have?
This list has 390 BACnet objects: 352 analog inputs, 38 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AERCO Benchmark E / Edge X BACnet points are writable?
38 of the 390 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official AERCO Benchmark E / Edge X BACnet documentation?
The source is Edge X Communication Guide for Systems Integrators (Edge X Communication Manual) (OMM-0173E), revision 2025-06-17, published free by AERCO at https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/664721-source/638954248340000000/omm-0173-edge-x-communication-manual-6-17-25.pdf.
What are the minimum BACnet points to integrate the AERCO Benchmark E / Edge X?
Start with AV 12 Operating Mode (Selects constant, remote or outdoor-reset setpoint); AV 13 Remote Signal (Set to BAS so the remote setpoint comes from BACnet); AV 4 Setpoint (Unit temperature setpoint, 35-220 °F); AV 200 Setpoint (Plant setpoint on a BST manager); AI 1 Unit Status (Standby / manual / auto / fault state); AI 2 Outlet Temp (Outlet water temperature); AI 0 Active Event ID (Active event / fault code); AI 108 Units Faulted (Units faulted in the cascade).
How do I enable BMS control of the AERCO Benchmark E / Edge X?
On the controller go to Settings > Advanced Setup > Comm & Failsafe and enable BAS; for IP turn on the "BAS (J6)" toggle, which actually uses the J5 jack. The object list has no separate start/stop object: the BAS controls the unit through AV 12 Operating Mode, AV 13 Remote Signal (0 = BAS) and the setpoint in AV 4, or AV 200 on a BST manager. Firing-rate control (Direct Drive) is listed only for legacy BMK units.
Does the AERCO Benchmark E / Edge X need a BACnet heartbeat or have a communication timeout?
The BAS Comm Failsafe setting chooses whether the unit shuts down or runs at a constant setpoint when it loses the BAS (AV 24 Unit Failsafe Mode: 0 = Standby, 1 = Constant Setpt). The BACnet IP screen also has a delay-before-communication-fault setting; its range and default are not given.
Can the BMS supply sensor values to the AERCO Benchmark E / Edge X?
AV 85 / AV 213 Supply Header Temp Source and AV 215 return header source can be set to BAS (2), but the object list has no writable header or outdoor temperature value. On BMK E the outdoor sensor source (AV 81 / AV 217) is listed as Direct only.
How do I check these points on the real Benchmark E / Edge X?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AERCO BACnet points lists
- Digital DHW mixing valve system (water tempering)
AERCO ADMS Smart Water Tempering System
AERCO ADMS digital mixing (water tempering) systems for domestic hot water.
Also known as: ADMS, AERCO ADMS, Smart Water Tempering System, 106902, OMM-0126 - Boiler / water heater controller gateway
AERCO AM Series Dependent boiler / water heater (ProtoNode FPC-N34/N35)
AERCO AM Series boilers or water heaters set up as dependent units of a cascade, read through the AERCO ProtoNode FPC-N34 / FPC-N35.
Also known as: AM Series, AM Dependent, AM Dep, AERCO AM, ProtoNode FPC-N34, FPC-N35 - Boiler / water heater cascade controller gateway
AERCO AM Series Managing boiler / water heater (ProtoNode FPC-N34/N35)
AERCO AM Series boilers or water heaters set up as the managing (or stand-alone) unit of a cascade, read through the AERCO ProtoNode FPC-N34 / FPC-N35.
Also known as: AM Series, AM Manager, AM Mngr, AERCO AM, ProtoNode FPC-N34, FPC-N35 - Boiler plant manager (sequencing controller)
AERCO Benchmark / Innovation Edge controller - BST Manager plant objects
AERCO Benchmark boilers and Innovation water heaters with an Edge [i] or Edge [ii] controller acting as BST Manager for up to 16 units, with optional SmartPlate / SmartPlate EV units.
Also known as: BST Manager, Boiler Sequencing Technology, Edge [i], Edge [ii], Benchmark Edge, BMK Edge, Innovation Edge, OMM-0140, SmartPlate via Edge - Boiler and water heater plant controller via ProtoNode gateway
AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)
AERCO C-More boilers running on-board BST sequencing and C-More water heaters (KC, Innovation) running WHM, up to 8 units, through the ProtoNode RER SSD profile.
Also known as: C-More, BST, Boiler Sequencing Technology, WHM, Water Heater Management, SSD, Slave/Slave Device, Innovation, KC, Benchmark, ProtoNode RER, 64084, GF-129, OMM-0080 - Boiler controller and plant sequencer via ProtoNode gateway
AERCO C-More boilers with ACS / BMS II (ProtoNode RER)
AERCO boilers with the C-More controller plus an ACS or BMS II plant sequencer, read through the AERCO ProtoNode RER.
Also known as: C-More, C-More controller, ACS, BMS II, BMS, ProtoNode RER, ProtoNode-RER, 64084, FPC-N34, GF-129, OMM-0080 - Boiler and water heater plant gateway (multi-unit)
AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)
A combined AERCO plant of 12 C-More boilers, 4 Modulex boilers, 6 ECS/SmartPlate water heater valves and two BMS II boiler managers on one gateway.
Also known as: AERCO ProtoNode, C-More, Modulex, ECS, SmartPlate, BMS II, AERCO-ProtoNode-Control-Points - Water heater controller via ProtoNode gateway
AERCO ECS and SmartPlate water heaters (ProtoNode RER)
AERCO SmartPlate and ECS (Electric Valve) water heaters, up to four, read through the AERCO ProtoNode RER.
Also known as: ECS, Electronic Control System, SmartPlate, SmartPlate water heater, E Valve, ProtoNode RER, 64084, GF-129, OMM-0080 - Commercial water heater controller
AERCO Edge [ii] water heater controller (standalone / WHM)
AERCO Innovation 1600-2000 water heaters with the Edge [ii] controller, run standalone or as a WHM (Water Heater Management) manager or client.
Also known as: Edge [ii], Edge ii, Edge 2, WHM, Water Heater Management, Centurion, OMM-0176, Innovation 1600-2000 - Boiler controller and plant sequencer via ProtoNode gateway
AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)
AERCO Modulex boilers with a BCM, up to four, plus an ACS or BMS II sequencer, read through the AERCO ProtoNode RER.
Also known as: Modulex, MLX, Modulex E8, BCM, ACS, BMS II, ProtoNode RER, 64084, GF-129, OMM-0080
Source: Edge X Communication Guide for Systems Integrators (Edge X Communication Manual) · OMM-0173E · rev. 2025-06-17. Object names, instances and units are reproduced as published; descriptions are our own.