- YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card) · BACnet points list
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet points list
Updated 28 October 2026
The YMC2's SC-EQ card puts the chiller on a BACnet MS/TP trunk (or Modbus RTU / N2). Besides run/stop, the leaving chilled liquid setpoint and the input current limit, it exposes VSD input and output data, harmonic distortion, magnetic bearing (MBC) levitation and speed, VGD/PRV positions and the operation, fault and warning codes. Some points apply only to Mod A or Mod B chillers.
This page lists 112 BACnet objects for the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
- Equipment
- Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
- Equipment type
- Chillers
- BACnet objects
- 112 (5 writable)
- Transport
- BACnet MS/TP
- Firmware
- SC-EQ software 4.2.0.20
- Default device instance
- 5000 + MAC address
- Also known as
- YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1
- Source document
- YMC2 SC-EQ BAS Points List · rev. Rev 2.11, 2021-12-08
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
Wire the BAS to the SC-EQ J12 RS-485 port, set the MAC address on the DIP switch and let the card detect BACnet MS/TP. Write the remote run/stop, leaving chilled liquid setpoint and input current limit, then read motor run status, the operation code, leaving chilled liquid temperature, % FLA and the safety fault code. Check MV 5 and MV 10-13 to confirm the chiller is taking its commands from the BAS.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | REM RUN STOP CMD | Remote run/stop (1 = run) | Command |
| AV 1 | REM LEAVING CHL TEMP SP | Remote leaving chilled liquid setpoint | Command |
| AV 2 | REMOTE INPUT CURRENT SP | Remote input current limit, % | Command |
| MV 1 | UNIT OPERATION CODE | Operating state (stopped, starting, running) | Read |
| BV 5 | COMPR MOTOR STATUS | Compressor motor running | Read |
| MV 5 | UNIT CONTROL SOURCE | Control source; ISN (BAS) for BMS control | Read |
| AV 5 | LEAVING CH LIQ TEMP | Leaving chilled liquid temperature | Read |
| AV 29 | MOTOR CURRENT PCT FLA | Motor current, % FLA (load indication) | Read |
| MV 2 | UNIT SAFETY FAULT CODE | Safety shutdown code (1 = none) | Read |
| MV 3 | UNIT CYCLING FAULT CODE | Cycling shutdown code (1 = none) | Read |
Enable & remote start
BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop, and the REM AVs are the remote setpoints. MV 5 Unit Control Source shows Local, ISN (BAS), Analog, Digital, Modem or Remote. MV 10 shows the run/stop source (Local, BAS, Hardwire) and MV 11-13 the cooling setpoint, heating setpoint and current limit sources (Local, BAS, 0-10 V, 4-20 mA, PWM); check they read BAS. The points list has no write-enable point and doesn't say how the source is chosen at the chiller panel.
Network setup
- The BAS connects to the SC-EQ J12 port (RS-485: +, -, COM/REF, SHLD). The card detects BACnet MS/TP, Modbus RTU or N2 and the baud rate by itself; allow up to 120 seconds after power-up.
- The MAC address (1-127) is set on DIP switch SW1 (switch 8 unused). Cycle the card's power after changing it.
- The device instance defaults to 5000 + the MAC address (MAC 6 gives 5006). To use another number, set Device Instance Mode to Manual and enter the instance with the SC-AP / MAP tool, or write BV 65000 (mode) and AV 65000 (instance ID).
- MV 65001 Units sets whether the BAS sees IP or SI values, independent of the chiller display; set it to match the chiller.
- Turn the card's RS-485 end-of-line switches on only when it is at the end of the trunk.
Watch out for
- The BAS port is RS-485 only (BACnet MS/TP, Modbus RTU or N2); the card has no BACnet IP port.
- Points marked Mod A or Mod B only appear on that chiller generation.
- Remote setpoints show as unreliable until the BAS has written them once.
- The card only exposes points that apply to the detected chiller and its options. Replacing an E-Link leaves the old, non-applicable points offline in the BAS until you rediscover the device.
- Code points come in pairs: the MV state is the code + 1, and the AV copy (AV 401 and up) carries the raw code.
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | REM LEAVING CHL TEMP SP | Remote Leaving Chilled Liquid Setpoint | °F | Command | |
| AVmin | 2 | REMOTE INPUT CURRENT SP | Remote Input Current Limit Setpoint | % | Command | |
| AV | 3 | REM HEATING SP | Remote Heating Setpoint | °F | Command | |
| BVmin | 1 | REM RUN STOP CMD | Remote Run/Stop | Command | 0=Stop, 1=Run | |
| MV | 65001 | Units | Unit system reported by the SC-EQ | Write | 0=IP (English), 1=SI (Metric) | |
| AVmin | 5 | LEAVING CH LIQ TEMP | Leaving Chilled Liquid Temperature | °F | Read | |
| AV | 6 | ENTERING CH LIQ TEMP | Entering Chilled Liquid Temperature | °F | Read | |
| AV | 7 | LEAVING COND WATER TEMP | Leaving Condenser Liquid Temperature | °F | Read | |
| AV | 8 | ENTERING COND WATER TEMP | Entering Condenser Liquid Temperature | °F | Read | |
| AV | 9 | EVAPORATOR PRESSURE | Evaporator Pressure | PSIG | Read | |
| AV | 10 | CONDENSER PRESSURE | Condenser Pressure | PSIG | Read | |
| AV | 11 | DISCHARGE TEMP | Discharge Temperature | °F | Read | |
| AV | 12 | EVAP REFRIGERANT TEMP | Evaporator Refrigerant Temperature (Evaporator Refrigerant Temperature enabled only) | °F | Read | |
| AV | 13 | VSD PHASE A OUTPUT CURRENT | VSD Phase A Output Current (RMS) | Amps | Read | |
| AV | 14 | VSD PHASE B OUTPUT CURRENT | VSD Phase B Output Current (RMS) | Amps | Read | |
| AV | 15 | VSD PHASE C OUTPUT CURRENT | VSD Phase C Output Current (RMS) | Amps | Read | |
| AV | 17 | VSD RMS INPUT CURRENT L1 | VSD L1 Input Current (RMS) | Amps | Read | |
| AV | 18 | VSD RMS INPUT CURRENT L2 | VSD L2 Input Current (RMS) | Amps | Read | |
| AV | 19 | VSD RMS INPUT CURRENT L3 | VSD L3 Input Current (RMS) | Amps | Read | |
| AV | 20 | LEAVING CH LIQ TEMP ACT SP | Leaving Chilled Liquid Setpoint - Selected | °F | Read | |
| AV | 21 | INPUT CURRENT LMT ACTIVE | Active Input Current Limit | % | Read | |
| AV | 22 | EVAP SATURATION TEMP | Evaporator Saturation Temperature | °F | Read | |
| AV | 23 | COND SATURATION TEMP | Condenser Saturation Temperature | °F | Read | |
| AV | 24 | INPUT CURRENT PCT FLA | Input % Full Load Amps | % | Read | |
| AV | 25 | COND REFRIGERANT LEVEL | Condenser Refrigerant Level | % | Read | |
| AV | 26 | OPERATING HOURS | Operating Hours | Hr | Read | |
| AV | 27 | NUMBER OF STARTS | Number Of Starts | Read | ||
| AV | 28 | HOT GAS BYPASS VLV CMD | Hot Gas Bypass Command (Hot Gas Bypass enabled only) | % | Read | |
| AVmin | 29 | MOTOR CURRENT PCT FLA | Motor % Full Load Amps | % | Read | |
| BVmin | 5 | COMPR MOTOR STATUS | Motor Run | Read | 0=Off, 1=On | |
| BV | 6 | CH LIQ PUMP STAT | Chilled Liquid Pump | Read | 0=Off, 1=On | |
| BV | 7 | VSD COOLING SYS STAT | VSD Cooling System | Read | 0=Off, 1=On | |
| BV | 8 | RUN PERMISSIVE | Run Permissive | Read | 0=Off, 1=On | |
| BV | 9 | CH LIQ FLOW SWITCH STAT | Chilled Liquid Flow Switch | Read | 0=Open, 1=Closed | |
| BV | 10 | CND FLOW SWITCH STAT | Condenser Liquid Flow Switch | Read | 0=Open, 1=Closed | |
| BV | 11 | COND REF LEVEL CNTRL MODE | Condenser Level Control Valve Mode | Read | 0=Auto, 1=Manual | |
| BV | 12 | CND LIQ PUMP STAT | Condenser Liquid Pump | Read | 0=Off, 1=On | |
| MVmin | 1 | UNIT OPERATION CODE | Unit Operation Code | Read | 1=Unit Stopped - Ready To Start, 2=Unit Stopped - Local Shutdown, 3=Unit Stopped - Remote Shutdown, 4=Unit Stopped - Warning Active, 5=Unit Stopped - Cycling Shutdown, 6=Unit Stopped - Safety Shutdown, 7=Unit Start Inhibit, 8=Unit Starting, 9=Unit Running - No Abnormal Condition, 10=Unit Running - Warning Active, 11=Unit Running - Soft Shutdown, 12=Unit Coastdown, 13=Unit Running - Modified Run, 14=Unit Stopped - Internal Shutdown, 16=Unit Running - Active Low Lift - No Abnormal Condition, 17=Unit Running - Active Low Lift - Warning Active, 18=Unit Running - Active Low Lift - Modified Run, 19=Unit Running - Passive Low Lift - No Abnormal Condition, 20=Unit Running - Passive Low Lift - Warning Active, 21=Unit Running - Passive Low Lift - Modified Run, 22=Unit Running - Cooling - No Abnormal Condition, 23=Unit Running - Cooling - Warning Active, 24=Unit Running - Cooling - Modified Run, 25=Unit Running - Heating - No Abnormal Condition, 26=Unit Running - Heating - Warning Active, 27=Unit Running - Heating - Modified Run, 28=Unit Running - Cooling & Heating - No Abnormal Condition, 29=Unit Running - Cooling & Heating - Warning Active, 30=Unit Running - Cooling & Heating - Modified Run | |
| AV | 401 | UNIT OPERATION CODE AV | Unit Operation Code, raw code (MV 1 shows code + 1) | Read | ||
| MVmin | 2 | UNIT SAFETY FAULT CODE | Unit Safety Fault Code | Read | 1=No Safety Faults Present; other values (up to 164) are YMC2 Safety Fault Code table SC.2 codes plus 1 (133 codes listed in the source doc) | |
| AV | 402 | UNIT SAFETY FAULT CODE AV | Unit Safety Fault Code, raw code (MV 2 shows code + 1) | Read | ||
| MVmin | 3 | UNIT CYCLING FAULT CODE | Unit Cycling Fault Code | Read | 1=No Cycling Faults Present; other values (up to 162) are YMC2 Cycling Fault Code table SC.3 codes plus 1 (111 codes listed in the source doc) | |
| AV | 403 | UNIT CYCLING FAULT CODE AV | Unit Cycling Fault Code, raw code (MV 3 shows code + 1) | Read | ||
| MV | 4 | UNIT WARNING CODE | Unit Warning Code | Read | 1=No Warnings Present, 2=WARNING - REAL TIME CLOCK FAILURE, 3=WARNING - SETPOINT OVERRIDE, 4=WARNING - CONDENSER OR EVAPORATOR XDCR ERROR, 5=WARNING - EVAPORATOR - LOW PRESSURE LIMIT, 6=WARNING - CONDENSER - HIGH PRESSURE LIMIT, 8=WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI, 9=WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI, 10=WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE, 11=WARNING - MBC - LOW AMPLIFIER RESISTANCE, 12=WARNING - MBC - HIGH AMPLIFIER RESISTANCE, 13=WARNING - MBC - LOW AMPLIFIER CURRENT, 14=WARNING - MBC - HIGH AMPLIFIER CURRENT, 15=WARNING - MBC - POSITION SENSOR ERROR, 16=WARNING - MBC - J BEARING SENSOR DISABLED, 17=WARNING - MBC - K BEARING SENSOR DISABLED, 18=WARNING - MBC - H BEARING SENSOR DISABLED, 21=WARNING – UPS – NOT CHARGING, 22=WARNING – UPS – LINE LOW BATTERY VOLTAGE, 23=WARNING – UPS – BATTERY NOT CONNECTED, 24=WARNING – UPS – CHECK BATTERY CONNECTION, 25=WARNING – UPS – BATTERY TEST FAILED, 26=WARNING - SALES ORDER - INVALID SERIAL NUMBER, 30=WARNING - SURGE PROTECTION - EXCESS SURGE LIMIT, 31=WARNING - EXCESS SURGE DETECTED, 35=WARNING - CONDENSER OR VGD SENSOR FAILURE, 36=WARNING - HARMONIC FILTER - INVALID MODEL, 37=WARNING - HARMONIC FILTER - OPERATION INHIBITED, 38=WARNING - HARMONIC FILTER - DATA LOSS, 40=WARNING - HARMONIC FILTER - NOT RUNNING, 41=WARNING - MOTOR - HIGH WINDING TEMPERATURE, 42=WARNING - MOTOR - HIGH ROTOR TEMPERATURE, 45=WARNING - VSD - INPUT VOLTAGE IMBALANCE, 46=WARNING - VSD - HIGH HX APPROACH TEMPERATURE, 49=WARNING - MBC - LANDING COUNTER HIGH, 56=WARNING – MBC – CHECKSUM CENTERING, 57=WARNING – MBC – DSP WATCHDOG, 58=WARNING – MBC – AMP WATCHDOG, 59=WARNING – MBC – INTERNAL ALARM, 60=WARNING – MBC – HIGH RADIAL OSCILLATOR VOLTAGE, 61=WARNING – MBC – HIGH AXIAL OSCILLATOR VOLTAGE, 66=WARNING - MBC - ROTATION MODE OFF, 67=WARNING - MOTOR - HIGH CURRENT LIMIT, 68=WARNING - MOTOR - HIGH HOUSING TEMPERATURE, 69=WARNING - VSD - DC BUS ACTIVE, 70=WARNING - LIQUID LEVEL SETPOINT NOT ACHIEVED, 71=WARNING - LOSS OF SUBCOOLER LIQUID SEAL | |
| AV | 404 | UNIT WARNING CODE AV | Unit Warning Code, raw code (MV 4 shows code + 1) | Read | ||
| MVmin | 5 | UNIT CONTROL SOURCE | Unit Control Source | Read | 0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote | |
| AV | 405 | UNIT CONTROL SOURCE AV | Unit Control Source, same codes as MV 5 | Read | 0=Local, 1=ISN (BAS), 2=Analog, 3=Digital, 4=Modem, 5=Remote | |
| MV | 6 | UNIT MODIFIED RUN CODE | Unit Modified Run Code | Read | 1=No Modified Run Conditions Present, 2=VSD - DC BUS ACTIVE, 3=MOTOR - HIGH CURRENT LIMIT, 5=VSD - INPUT PULLDOWN LIMIT, 6=VSD - HIGH INPUT CURRENT LIMIT | |
| AV | 406 | UNIT MODIFIED RUN CODE AV | Unit Modified Run Code, raw code (MV 6 shows code + 1) | Read | ||
| MV | 7 | UNIT START INHIBIT CODE | Unit Start Inhibit Code | Read | 1=No Start Inhibits Present, 2=ANTI-RECYCLE, 4=VGD STROKE NOT CALIBRATED, 5=VGD FEEDBACK NOT CALIBRATED, 6=MBC - BEARING CALIBRATION IN PROGRESS, 7=MBC - BEARING CLEARANCE CHECK IN PROGRESS, 8=VSD - INITIALIZATION IN PROGRESS, 11=PRV NOT CALIBRATED, 13=VGD NOT CALIBRATED, 14=LINE VOLTAGE NOT SET, 15=LINE FREQUENCY NOT SET, 16=MBC - INITIALIZATION IN PROGRESS | |
| AV | 407 | UNIT START INHIBIT CODE AV | Unit Start Inhibit Code, raw code (MV 7 shows code + 1) | Read | ||
| MV | 8 | UNIT INTERNAL FAULT CODE | Unit Internal Fault Code | Read | 1=No Internal Faults Present, 2=INTERNAL ERROR - NO TIMER HANDLES AVAILABLE, 3=WATCHDOG - SOFTWARE REBOOT, 4=INTERNAL ERROR - CANNOT CREATE TASK, 5=INTERNAL ERROR - CANNOT REGISTER CONTROL, 6=INTERNAL ERROR - INVALID BRAM | |
| AV | 408 | UNIT INTERNAL FAULT CODE AV | Unit Internal Fault Code, raw code (MV 8 shows code + 1) | Read | ||
| AV | 30 | VGD CONTROL STATE | VGD Control State (Mod A Chillers only) | Read | 0=[Unused], 1=Probing or Capacity Control, 2=Stall Reacting, 3=Stall Waiting, 4=Surge Reacting, 5=Surge Waiting, 6=Sensor Override, 7=[Unused], 8=PRV Position Override | |
| AV | 31 | VGD STALL COUNT | VGD Stall Count (Mod A Chillers only) | Read | ||
| AV | 32 | ACTIVE ANTI SURGE MIN FREQ | Active Anti-Surge Minimum Frequency | Hz | Read | |
| AV | 34 | VSD OUTPUT VOLTAGE | VSD Output Voltage | Volts | Read | |
| AV | 35 | VSD INPUT POWER | VSD Input Power | kW | Read | |
| AV | 36 | VSD INPUT KWH | VSD Input Kilowatt Hours | kWh | Read | |
| AV | 37 | VSD DC BUS VOLTAGE | VSD DC Bus Voltage | Volts | Read | |
| AV | 38 | VSD INPUT VOLTAGE L1 | VSD L1 Input Voltage (RMS) | Volts | Read | |
| AV | 39 | SURGE COUNT | Surge Count | Read | ||
| AV | 40 | VSD OUTPUT FREQUENCY | VSD Output Frequency | Hz | Read | |
| AV | 41 | VSD INPUT VOLTAGE L2 | VSD L2 Input Voltage (RMS) | Volts | Read | |
| AV | 42 | VSD INPUT VOLTAGE L3 | VSD L3 Input Voltage (RMS) | Volts | Read | |
| AV | 43 | COND LVL CTRL VLV CMD | Condenser Level Control Valve Command | % | Read | |
| BV | 26 | MBC LEVITATION MODE | MBC Levitation Mode | Read | 0=Off, 1=On | |
| BV | 27 | MBC ROTATION MODE | MBC Rotation Mode | Read | 0=Off, 1=On | |
| AV | 48 | MOTOR HOUSING TEMP | Motor Housing Temp | °F | Read | |
| AV | 107 | MOTOR COOLING VALVE CMD | Motor Cooling Valve Command (Mod A FAB comp & Mod B chillers) | % | Read | |
| AV | 108 | VSD INTERNAL AMBIENT TEMP 2 | VSD Internal Ambient Temperature 2 | °F | Read | |
| AV | 109 | MTR WINDING AVG TEMP | Average Motor Winding Temperature | °F | Read | |
| AV | 110 | VSD INTERNAL AMBIENT TEMP 1 | VSD Internal Ambient Temperature 1 | °F | Read | |
| AV | 111 | VGD POSITION | VGD Position | % | Read | |
| AV | 112 | PRE ROTATION VANES POS | Pre Rotation Vanes (PRV) Position (Mod A chiller FAA comp only) | % | Read | |
| AV | 113 | COND REFRIGERANT LEVEL SP | Condenser Active Level Setpoint | % | Read | |
| AV | 114 | DROP LEG REFRIG TEMP | Drop Leg Refrigerant Temperature | °F | Read | |
| AV | 115 | VSD L1 VOLTAGE THD | VSD L1 Voltage Total Harmonic Distortion | % | Read | |
| AV | 116 | VSD L2 VOLTAGE THD | VSD L2 Voltage Total Harmonic Distortion | % | Read | |
| AV | 117 | VSD L3 VOLTAGE THD | VSD L3 Voltage Total Harmonic Distortion | % | Read | |
| AV | 118 | VSD L1 INPUT CURRENT TDD | VSD L1 Input Current Total Demand Distortion | % | Read | |
| AV | 119 | VSD L2 INPUT CURRENT TDD | VSD L2 Input Current Total Demand Distortion | % | Read | |
| AV | 120 | VSD L3 INPUT CURRENT TDD | VSD L3 Input Current Total Demand Distortion | % | Read | |
| AV | 121 | INPUT KWH LO | Input Kilowatt Hours Low | Read | ||
| AV | 122 | INPUT KWH OFFSET | Input Kilowatt Hours Offset | Read | ||
| AV | 123 | OPERATING HOURS LO | Operating Hours Low | Read | ||
| AV | 124 | OPERATING HOURS OFFSET | Operating Hours Offset | Read | ||
| AV | 125 | MBC MOTOR SPEED | MBC Motor Speed | Hz | Read | |
| AV | 126 | MBC LANDING COUNTER | MBC Landing Counter (Mod A chillers only) | Read | ||
| AV | 127 | ACTIVE MIN PRV POS | Active Minimum PRV Position (Mod A chiller FAA comp only) | % | Read | |
| AV | 137 | UPS BATTERY VOLTAGE | UPS Battery Voltage (Mod B Chillers only) | Volts | Read | |
| AV | 138 | VSD PH A REC BASEPLATE TEMP | VSD Phase A Rectifier Baseplate Temperature | °F | Read | |
| AV | 139 | VSD PH B REC BASEPLATE TEMP | VSD Phase B Rectifier Baseplate Temperature | °F | Read | |
| AV | 140 | VSD PH C REC BASEPLATE TEMP | VSD Phase C Rectifier Baseplate Temperature | °F | Read | |
| AV | 141 | VSD PH A INV BASEPLATE TEMP | VSD Phase A Inverter Baseplate Temperature | °F | Read | |
| AV | 142 | VSD PH B INV BASEPLATE TEMP | VSD Phase B Inverter Baseplate Temperature | °F | Read | |
| AV | 143 | VSD PH C INV BASEPLATE TEMP | VSD Phase C Inverter Baseplate Temperature | °F | Read | |
| AV | 144 | EVAP SMALL TEMP DIFF | Evaporator Small Temp Difference | °F (diff) | Read | |
| AV | 145 | COND SMALL TEMP DIFF | Condenser Small Temp Difference | °F (diff) | Read | |
| AV | 146 | DISCHARGE SUPERHEAT | Discharge Superheat | °F (diff) | Read | |
| AV | 147 | SUBCOOLLER EFFECTIVENESS | Subcooler Effectiveness | Read | ||
| AV | 148 | SUBCOOLING TEMP | Subcooling Temperature | °F (diff) | Read | |
| AV | 149 | DELTA P DIV P | Delta P / P | Read | ||
| AV | 150 | HEAD PRESSURE | Head Pressure | PSID | Read | |
| MV | 10 | RUN STOP CTRL SOURCE | Run/Stop Control Source | Read | 0=Local, 1=BAS, 2=Hardwire | |
| AV | 421 | RUN STOP CTRL SOURCE AV | Run/Stop Control Source, same codes as MV 10 | Read | 0=Local, 1=BAS, 2=Hardwire | |
| MV | 11 | COOL SETP CTRL SOURCE | Cooling Setp Control Source | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| AV | 422 | COOL SETP CTRL SOURCE AV | Cooling Setp Control Source, same codes as MV 11 | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| MV | 12 | HEAT SETP CTRL SOURCE | Heating Setp Control Source | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| AV | 423 | HEAT SETP CTRL SOURCE AV | Heating Setp Control Source, same codes as MV 12 | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| MV | 13 | CURR LIM CTRL SOURCE | Current Limit Control Source | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM | |
| AV | 424 | CURR LIM CTRL SOURCE AV | Current Limit Control Source, same codes as MV 13 | Read | 0=Local, 1=BAS, 2=0-10 Volts, 3=4-20 mA, 4=PWM |
No points match these filters.
Object ID lookup: York YMC2 Magnetic-Bearing Centrifugal Chiller point IDs by name
AV1REM LEAVING CHL TEMP SPAV2REMOTE INPUT CURRENT SPAV3REM HEATING SPBV1REM RUN STOP CMDMV65001UnitsAV5LEAVING CH LIQ TEMPAV6ENTERING CH LIQ TEMPAV7LEAVING COND WATER TEMPAV8ENTERING COND WATER TEMPAV9EVAPORATOR PRESSUREAV10CONDENSER PRESSUREAV11DISCHARGE TEMPAV12EVAP REFRIGERANT TEMPAV13VSD PHASE A OUTPUT CURRENTAV14VSD PHASE B OUTPUT CURRENTAV15VSD PHASE C OUTPUT CURRENTAV17VSD RMS INPUT CURRENT L1AV18VSD RMS INPUT CURRENT L2AV19VSD RMS INPUT CURRENT L3AV20LEAVING CH LIQ TEMP ACT SPAV21INPUT CURRENT LMT ACTIVEAV22EVAP SATURATION TEMPAV23COND SATURATION TEMPAV24INPUT CURRENT PCT FLAAV25COND REFRIGERANT LEVELAV26OPERATING HOURSAV27NUMBER OF STARTSAV28HOT GAS BYPASS VLV CMDAV29MOTOR CURRENT PCT FLABV5COMPR MOTOR STATUSBV6CH LIQ PUMP STATBV7VSD COOLING SYS STATBV8RUN PERMISSIVEBV9CH LIQ FLOW SWITCH STATBV10CND FLOW SWITCH STATBV11COND REF LEVEL CNTRL MODEBV12CND LIQ PUMP STATMV1UNIT OPERATION CODEAV401UNIT OPERATION CODE AVMV2UNIT SAFETY FAULT CODEAV402UNIT SAFETY FAULT CODE AVMV3UNIT CYCLING FAULT CODEAV403UNIT CYCLING FAULT CODE AVMV4UNIT WARNING CODEAV404UNIT WARNING CODE AVMV5UNIT CONTROL SOURCEAV405UNIT CONTROL SOURCE AVMV6UNIT MODIFIED RUN CODEAV406UNIT MODIFIED RUN CODE AVMV7UNIT START INHIBIT CODEAV407UNIT START INHIBIT CODE AVMV8UNIT INTERNAL FAULT CODEAV408UNIT INTERNAL FAULT CODE AVAV30VGD CONTROL STATEAV31VGD STALL COUNTAV32ACTIVE ANTI SURGE MIN FREQAV34VSD OUTPUT VOLTAGEAV35VSD INPUT POWERAV36VSD INPUT KWHAV37VSD DC BUS VOLTAGEAV38VSD INPUT VOLTAGE L1AV39SURGE COUNTAV40VSD OUTPUT FREQUENCYAV41VSD INPUT VOLTAGE L2AV42VSD INPUT VOLTAGE L3AV43COND LVL CTRL VLV CMDBV26MBC LEVITATION MODEBV27MBC ROTATION MODEAV48MOTOR HOUSING TEMPAV107MOTOR COOLING VALVE CMDAV108VSD INTERNAL AMBIENT TEMP 2AV109MTR WINDING AVG TEMPAV110VSD INTERNAL AMBIENT TEMP 1AV111VGD POSITIONAV112PRE ROTATION VANES POSAV113COND REFRIGERANT LEVEL SPAV114DROP LEG REFRIG TEMPAV115VSD L1 VOLTAGE THDAV116VSD L2 VOLTAGE THDAV117VSD L3 VOLTAGE THDAV118VSD L1 INPUT CURRENT TDDAV119VSD L2 INPUT CURRENT TDDAV120VSD L3 INPUT CURRENT TDDAV121INPUT KWH LOAV122INPUT KWH OFFSETAV123OPERATING HOURS LOAV124OPERATING HOURS OFFSETAV125MBC MOTOR SPEEDAV126MBC LANDING COUNTERAV127ACTIVE MIN PRV POSAV137UPS BATTERY VOLTAGEAV138VSD PH A REC BASEPLATE TEMPAV139VSD PH B REC BASEPLATE TEMPAV140VSD PH C REC BASEPLATE TEMPAV141VSD PH A INV BASEPLATE TEMPAV142VSD PH B INV BASEPLATE TEMPAV143VSD PH C INV BASEPLATE TEMPAV144EVAP SMALL TEMP DIFFAV145COND SMALL TEMP DIFFAV146DISCHARGE SUPERHEATAV147SUBCOOLLER EFFECTIVENESSAV148SUBCOOLING TEMPAV149DELTA P DIV PAV150HEAD PRESSUREMV10RUN STOP CTRL SOURCEAV421RUN STOP CTRL SOURCE AVMV11COOL SETP CTRL SOURCEAV422COOL SETP CTRL SOURCE AVMV12HEAT SETP CTRL SOURCEAV423HEAT SETP CTRL SOURCE AVMV13CURR LIM CTRL SOURCEAV424CURR LIM CTRL SOURCE AV
Integration notes
- Points list for the SC-EQ (SC-EQUIP) communication card, which replaced the E-Link gateway. The list has no read/write column: the REM remote command/setpoint objects are treated as commandable and MV 65001 Units as writable; everything else as read-only.
- In the PDF the names of MV 11-13 and AV 422-424 overprint the enum text; the mixed-up letters spell COOL SETP CTRL SOURCE, HEAT SETP CTRL SOURCE and CURR LIM CTRL SOURCE (plus AV), as in the YK list.
- Operating hours and kWh are also split into Low and Offset AVs: total = Offset x 10,000 + Low.
- Units shown are the IP units; with MV 65001 set to SI the card reports °C, kPa and so on.
- Status-code MVs (operation, fault, warning, modified run, start inhibit, internal fault) are the printed code + 1, as the doc's status code tables say; the AV copies (AV 401 and up) carry the raw code. MVs with their own enum in the points table (Units, control sources) are shown as printed, from 0; BACnet multistate values start at 1, so the card may report the printed number + 1. Confirm by discovery.
- Long fault and warning code tables are summarised in the MV states; the full text is in the source document.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
How many BACnet points does the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) have?
This list has 112 BACnet objects: 88 analog values, 11 binary values, 13 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet points are writable?
5 of the 112 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ) BACnet documentation?
The source is YMC2 SC-EQ BAS Points List, revision Rev 2.11, 2021-12-08, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/5I6BffzkZybYzhNWLkSq1w/content.
What are the minimum BACnet points to integrate the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)?
Start with BV 1 REM RUN STOP CMD (Remote run/stop (1 = run)); AV 1 REM LEAVING CHL TEMP SP (Remote leaving chilled liquid setpoint); AV 2 REMOTE INPUT CURRENT SP (Remote input current limit, %); MV 1 UNIT OPERATION CODE (Operating state (stopped, starting, running)); BV 5 COMPR MOTOR STATUS (Compressor motor running); MV 5 UNIT CONTROL SOURCE (Control source; ISN (BAS) for BMS control); AV 5 LEAVING CH LIQ TEMP (Leaving chilled liquid temperature); AV 29 MOTOR CURRENT PCT FLA (Motor current, % FLA (load indication)); MV 2 UNIT SAFETY FAULT CODE (Safety shutdown code (1 = none)); MV 3 UNIT CYCLING FAULT CODE (Cycling shutdown code (1 = none)).
How do I enable BMS control of the York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)?
BV 1 REM RUN STOP CMD (0 = Stop, 1 = Run) is the BAS run/stop, and the REM AVs are the remote setpoints. MV 5 Unit Control Source shows Local, ISN (BAS), Analog, Digital, Modem or Remote. MV 10 shows the run/stop source (Local, BAS, Hardwire) and MV 11-13 the cooling setpoint, heating setpoint and current limit sources (Local, BAS, 0-10 V, 4-20 mA, PWM); check they read BAS. The points list has no write-enable point and doesn't say how the source is chosen at the chiller panel.
How do I check these points on the real YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (four-pipe)
York YMAE Four-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the four-pipe (simultaneous heating and cooling) version.
Also known as: YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: YMC2 SC-EQ BAS Points List · rev. Rev 2.11, 2021-12-08. Object names, instances and units are reproduced as published; descriptions are our own.