Air-to-water modular heat pump (four-pipe) · BACnet points list
York YMAE Four-Pipe Modular Heat Pump BACnet points list
Updated 28 October 2026
The YMAE is the YORK by Johnson Controls modular air-to-water heat pump with inverter compressors; the four-pipe version heats and cools at the same time. Its BAS points list gives BACnet objects next to N2 and Modbus addresses: on/off and mode commands, entering and leaving water setpoints for cooling and heating, chiller-level status and temperatures, and module-level circuit values and bit-coded fault words. Module data is read one module at a time through AV 8.
This page lists 72 BACnet objects for the York YMAE Four-Pipe Modular Heat Pump — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from York’s own free documentation, linked below.
- Manufacturer
- York
- Model
- YMAE Four-Pipe Modular Heat Pump
- Equipment
- Air-to-water modular heat pump (four-pipe)
- Equipment type
- Heat pumps
- BACnet objects
- 72 (13 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- YORK YMAE, YMAE-130, YMAE four pipe, air-to-water heat pump
- Source document
- YMAE Four Pipe Points List · rev. Rev 1.1, 2023-08-24
Reference only, provided as-is: verify against York’s current documentation and the live device before use. Not official York information. Terms of use.
BMS integration notes: York YMAE Four-Pipe Modular Heat Pump
Enable BAS start/stop and mode at the HMI (MV 4 and MV 3 show the selection), then switch the unit with MV 1 and pick the mode with MV 2. Write the leaving (or entering) water setpoints for cooling and heating, and read BV 100 for actual on/off, chiller loading, the chiller leaving water temperatures and the unit fault words.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | CHILLER ON|OFF (CMD) | On/off command (1 = on, 2 = off, as printed) | Write |
| MV 2 | RUNNING MODE | Mode: cooling, heating, pump only, both | Write |
| AV 3 | COOL LWT SETPOINT | Cooling leaving water setpoint | Write |
| AV 4 | HEAT LWT SETPOINT | Heating leaving water setpoint | Write |
| MV 4 | CHILLER ON|OFF CONTROL SELECTION | On/off source; must include BAS (set at HMI) | Read |
| BV 100 | CHILLER ON|OFF (STATUS) | Actual on/off status | Read |
| AV 114 | CHILLER LOADING | Chiller loading, % | Read |
| AV 111 | CHILLER COOL LWT | Chiller cooling leaving water temperature | Read |
| AV 119 | CHILLER HEAT LWT | Chiller heating leaving water temperature | Read |
| AV 109 | UNIT FAULT STATUS (1-16) | Fault flags for modules 1-16, bit-coded | Read |
Enable & remote start
BAS start/stop and operating-mode control are enabled at the HMI. MV 4 (on/off source: HMI, Remote, HMI+BAS) and MV 3 (mode source: HMI, Remote, HMI+BAS, BAS) show the selection and are read-only over the network.
Network setup
- The sheet's notes describe the microboard's Modbus RTU link: 9600 baud, 8 data bits, no parity, 1 stop bit; the BAS is the leader and module 1's microboard the follower. BAS addresses are set at the HMI.
- BV 5 and BV 6 show whether cooling and heating control on entering or leaving water temperature; write the matching setpoints (AV 1/AV 2 or AV 3/AV 4).
Watch out for
- MV 1 only commands on/off; read the real state from BV 100.
- A BAS setpoint can be outside the unit's default range; read the setpoints back from the unit after writing.
- Data defaults to the leader module (No. 1). Write AV 8 to view another module's values; per-module AVs then show that module.
York YMAE Four-Pipe Modular Heat Pump BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 1 | CHILLER ON|OFF (CMD) | Chiller on/off command | Write | 0=Invalid, 1=On, 2=Off | |
| MVmin | 2 | RUNNING MODE | Running Mode | Write | 0=Cooling, 1=Heating, 8=Pump Only, 9=Cooling+Heating | |
| AV | 1 | COOL EWT SETPOINT | Cool Entering Water Temperature Setpoint, 19.4-86.0 °F | °F | Write | |
| AV | 2 | HEAT EWT SETPOINT | Heat Entering Water Temperature Setpoint, 59.0-131.0 °F | °F | Write | |
| AVmin | 3 | COOL LWT SETPOINT | Cool Leaving Water Temperature Setpoint, 14.0-68.0 °F | °F | Write | |
| AVmin | 4 | HEAT LWT SETPOINT | Heat Leaving Water Temperature Setpoint, 77.0-140.0 °F | °F | Write | |
| BV | 1 | NOISE REDUCTION | Noise Reduction | Write | 0=Off, 1=On | |
| BV | 5 | COOLING CONTROL SELECT | Cooling Control Select | Write | 0=Manual EWT control, 1=Manual LWT control | |
| BV | 6 | HEATING CONTROL SELECT | Heating Control Select | Write | 0=Manual EWT control, 1=Manual LWT control | |
| AV | 5 | TEMP CONTROL CYCLE | Temperature Control Cycle, 10-120 Sec | Sec | Write | |
| AV | 6 | WATER TEMP CONTROL DIFF | Water Temperature Control Differential, 1.8-5.4 °F (diff) | °F (diff) | Write | |
| AV | 7 | EWT PULLDOWN RATE SELECT | Entering Water Temperature Pulldown Rate Select, 0-6 | Write | ||
| AV | 8 | MODULE NUMBER | Module number to read (1-32) | Write | ||
| MV | 3 | CHILLER MODE CONTROL SELECTION | Chiller Mode Control Selection | Read | 0=HMI, 1=Remote, 2=HMI+BAS, 3=BAS | |
| MVmin | 4 | CHILLER ON|OFF CONTROL SELECTION | Chiller ON/OFF Control Selection | Read | 0=HMI, 1=Remote, 2=HMI+BAS | |
| BVmin | 100 | CHILLER ON|OFF (STATUS) | Chiller on/off status | Read | 0=Off, 1=On | |
| MV | 101 | SYSTEM STATUS | System Status | Read | 0=Cooling, 1=Heating, 8=Pump Only, 9=Cooling+Heating | |
| AV | 102 | OTHER STATUS | Other Status | Read | ||
| BV | 103 | HMI COMMUNICATION STATUS | Human Machine Interface Communication Status | Read | 0=Offline, 1=Online | |
| AV | 104 | UNIT NETWORK STATUS (1-16) | Network status of units 1-16, bit-coded | Read | ||
| AVmin | 109 | UNIT FAULT STATUS (1-16) | Fault status of units 1-16, bit-coded | Read | ||
| AV | 110 | CHILLER COOL EWT | Chiller Cool Entering Water Temp | °F | Read | |
| AVmin | 111 | CHILLER COOL LWT | Chiller Cool Leaving Water Temp | °F | Read | |
| AV | 113 | AMBIENT TEMP | Ambient Temperature | °F | Read | |
| AVmin | 114 | CHILLER LOADING | Chiller Loading | % | Read | |
| AV | 117 | TOTAL RUN HOURS | Total Run Hours | Hours | Read | |
| AV | 118 | CHILLER HEAT EWT | Chiller Heat Entering Water Temp | °F | Read | |
| AVmin | 119 | CHILLER HEAT LWT | Chiller Heat Leaving Water Temp | °F | Read | |
| AV | 121 | UNIT NETWORK STATUS (17-32) | Network status of units 17-32, bit-coded | Read | ||
| AV | 122 | UNIT FAULT STATUS (17-32) | Fault status of units 17-32, bit-coded | Read | ||
| AV | 123 | UNIT QUANTITY | Unit Quantity | Read | ||
| AV | 1021 | UNIT COOL EWT | Unit Cool Entering Water Temp | °F | Read | |
| AV | 1023 | CKT1 COIL TEMP | Circuit 1 Coil Temperature | °F | Read | |
| AV | 1024 | CKT2 COIL TEMP | Circuit 2 Coil Temperature | °F | Read | |
| AV | 1025 | UNIT COOL LWT | Unit Cool Leaving Water Temp | °F | Read | |
| AV | 1027 | CKT1 SUCT TEMP | Circuit 1 Suction Temperature | °F | Read | |
| AV | 1028 | CKT2 SUCT TEMP | Circuit 2 Suction Temperature | °F | Read | |
| AV | 1029 | SYS 1 DISCHARGE TEMP | System 1 Discharge Temp | °F | Read | |
| AV | 1033 | CKT1 ECO ENTERING TEMP | Circuit 1 Economizer Entering Temp | °F | Read | |
| AV | 1031 | SYS 2 DISCHARGE TEMP | System 2 Discharge Temp | °F | Read | |
| AV | 1035 | CKT2 ECO ENTERING TEMP | Circuit 2 Economizer Entering Temp | °F | Read | |
| AV | 1034 | CKT1 ECO LEAVING TEMP | Circuit 1 Economizer Leaving Temp | °F | Read | |
| AV | 1036 | CKT2 ECO LEAVING TEMP | Circuit 2 Economizer Leaving Temp | °F | Read | |
| AV | 1200 | R454B RELATIVE LFL | R454B leak sensor, % of lower flammable limit | % | Read | |
| AV | 1037 | UNIT HEAT LWT | Unit Heat Leaving Water Temp | °F | Read | |
| AV | 1039 | UNIT HEAT EWT | Unit Heat Entering Water Temp | °F | Read | |
| AV | 1040 | CKT1 SUCT PRS | Circuit 1 Suction Pressure | PSIG | Read | |
| AV | 1041 | CKT2 SUCT PRS | Circuit 2 Suction Pressure | PSIG | Read | |
| AV | 1042 | CKT1 DISCH PRS | Circuit 1 Discharge Pressure | PSIG | Read | |
| AV | 1043 | CKT2 DISCH PRS | Circuit 2 Discharge Pressure | PSIG | Read | |
| AV | 1053 | DI17-32 | Digital inputs 17-32, bit-coded | Read | ||
| AV | 1054 | DI1-16 | Digital inputs 1-16, bit-coded | Read | ||
| AV | 1055 | DO17-33 | Digital outputs 17-32, bit-coded | Read | ||
| AV | 1056 | DO1-16 | Digital outputs 1-16, bit-coded | Read | ||
| AV | 1057 | CKT1 EEV | Circuit 1 electronic expansion valve opening, steps | Read | ||
| AV | 1058 | CKT2 EEV | Circuit 2 electronic expansion valve opening, steps | Read | ||
| AV | 1059 | CKT1 ECO EEV | Circuit 1 economizer EEV opening, steps | Read | ||
| AV | 1060 | CKT2 ECO EEV | Circuit 2 economizer EEV opening, steps | Read | ||
| AV | 1065 | CKT1 FAN SPEED | Circuit 1 Fan Speed | RPM | Read | |
| AV | 1066 | CKT2 FAN SPEED | Circuit 2 Fan Speed | RPM | Read | |
| AV | 1073 | DIAL SWITCH STATUS | Dial Switch Status | Read | ||
| AV | 1080 | CKT1 INV COMP FREQ | Circuit 1 Inverter Compressor Frequency | Hz | Read | |
| AV | 1096 | CKT2 INV COMP FREQ | Circuit 2 Inverter Compressor Frequency | Hz | Read | |
| AV | 1155 | FAULT STATUS 1 | Fault status word 1, bit-coded | Read | Bit 0=Unit cooling entering water temperature sensor fault, Bit 1=Ambient temperature sensor fault, Bit 2=Circuit 1 coil temperature sensor fault, Bit 3=Circuit 2 coil temperature sensor fault, Bit 4=Unit cooling leaving water temperature sensor fault, Bit 5=Chiller cooling leaving water temperature sensor fault, Bit 6=Circuit 1 accumulator inlet temperature sensor fault, Bit 7=Circuit 2 accumulator inlet temperature sensor fault, Bit 8=Circuit 1 compressor 1 discharge port temperature sensor fault, Bit 10=Circuit 2 compressor 1 discharge port temperature sensor fault, Bit 12=Circuit 1 economizer entering temperature sensor fault, Bit 13=Circuit 1 economizer leaving temperature sensor fault, Bit 14=Circuit 2 economizer entering temperature sensor fault, Bit 15=Circuit 2 economizer leaving temperature sensor fault (1=fault) | |
| AV | 1156 | FAULT STATUS 2 | Fault status word 2, bit-coded | Read | Bit 0=Unit heating leaving water temperature sensor fault, Bit 1=Chiller heating leaving water temperature sensor fault, Bit 2=Unit heating entering water temperature sensor fault, Bit 3=Circuit 1 low pressure transducer fault, Bit 4=Circuit 2 low pressure transducer fault, Bit 5=Circuit 1 high pressure transducer fault, Bit 6=Circuit 2 high pressure transducer fault (1=fault) | |
| AV | 1157 | FAULT STATUS 3 | Fault status word 3, bit-coded | Read | Bit 0=Circuit 1 fan motor fault, Bit 1=Circuit 2 fan motor fault, Bit 2=Circuit 1 high pressure switch fault, Bit 3=Circuit 1 low pressure switch fault, Bit 4=Chiller cooling Water flow fault, Bit 7=External interlock fault, Bit 8=Power fault, Bit 9=Circuit 2 high pressure switch fault, Bit 10=Circuit 2 low pressure switch fault, Bit 11=Unit cooling Water flow fault, Bit 12=Unit heating Water flow fault, Bit 13=Chiller heating Water flow fault (1=fault) | |
| AV | 1158 | FAULT STATUS 4 | Fault status word 4, bit-coded | Read | ||
| AV | 1159 | FAULT STATUS 5 | Fault status word 5, bit-coded | Read | Bit 0=Communication failure (Follower unit with leader), Bit 1=Chiller Dial Switch setting error, Bit 2=Time limit protection, Bit 3=Low ambient temperature in cooling, Bit 4=High ambient temperature in heating, Bit 5=Chiller low leaving temperature in cooling, Bit 6=Chiller high leaving temperature in heating, Bit 7=Chiller locking, Bit 8=Communication failure (FCU with leader), Bit 10=Unit low leaving temperature in cooling, Bit 12=Unit high leaving temperature in heating, Bit 14=Unit low leaving temperature in heatinging (1=fault) | |
| AV | 1160 | FAULT STATUS 6 | Fault status word 6, bit-coded | Read | Bit 0=Circuit 1 compressor 1 high discharge port temperature, Bit 2=Circuit 2 compressor 1 high discharge port temperature, Bit 8=Circuit 1 cooling brazed plate heat exchanger anti-freeze protect, Bit 9=Circuit 2 Cooling brazed plate heat exchanger anti-freeze protect, Bit 10=Circuit 1 heating brazed plate heat exchanger anti-freeze protect, Bit 11=Circuit 2 heating brazed plate heat exchanger anti-freeze protect, Bit 14=Circuit 1 four way valve action failure, Bit 15=Circuit 2 four way valve action failure (1=fault) | |
| AV | 1161 | FAULT STATUS 7 | Fault status word 7, bit-coded | Read | Bit 0=Unit Dial Switch setting error, Bit 1=Communication failure (unit with circuit 1 driver), Bit 2=Communication failure (unit with circuit 1 fan), Bit 3=Communication failure (unit with circuit 2 fan), Bit 4=Communication failure (unit with circuit 2 driver), Bit 5=Driver fault or inverter compressor fault, Bit 7=Circuit 1 fan motor overspeed, Bit 8=Circuit 2 fan motor overspeed, Bit 9=Circuit 1 fan motor underspeed, Bit 10=Circuit 2 fan motor underspeed, Bit 11=Circuit 1 VSD heat dissipation alarm, Bit 12=Circuit 2 VSD heat dissipation alarm, Bit 13=Communication failure (Mainboard with Expansion Board) (1=fault) | |
| AV | 1162 | FAULT STATUS 8 | Fault status word 8, bit-coded | Read | Bit 2=Circuit 1 High pressure alarm, Bit 3=Circuit 2 High pressure alarm, Bit 4=Circuit 1 Low discharge pressure alarm, Bit 5=Circuit 2 Low discharge pressure alarm, Bit 6=Circuit 1 Low pressure alarm, Bit 7=Circuit 2 Low pressure alarm (1=fault) | |
| AV | 1163 | CHILLER MODEL NUMBER | Chiller Model Number | Read |
No points match these filters.
Object ID lookup: York YMAE Four-Pipe Modular Heat Pump point IDs by name
MV1CHILLER ON|OFF (CMD)MV2RUNNING MODEAV1COOL EWT SETPOINTAV2HEAT EWT SETPOINTAV3COOL LWT SETPOINTAV4HEAT LWT SETPOINTBV1NOISE REDUCTIONBV5COOLING CONTROL SELECTBV6HEATING CONTROL SELECTAV5TEMP CONTROL CYCLEAV6WATER TEMP CONTROL DIFFAV7EWT PULLDOWN RATE SELECTAV8MODULE NUMBERMV3CHILLER MODE CONTROL SELECTIONMV4CHILLER ON|OFF CONTROL SELECTIONBV100CHILLER ON|OFF (STATUS)MV101SYSTEM STATUSAV102OTHER STATUSBV103HMI COMMUNICATION STATUSAV104UNIT NETWORK STATUS (1-16)AV109UNIT FAULT STATUS (1-16)AV110CHILLER COOL EWTAV111CHILLER COOL LWTAV113AMBIENT TEMPAV114CHILLER LOADINGAV117TOTAL RUN HOURSAV118CHILLER HEAT EWTAV119CHILLER HEAT LWTAV121UNIT NETWORK STATUS (17-32)AV122UNIT FAULT STATUS (17-32)AV123UNIT QUANTITYAV1021UNIT COOL EWTAV1023CKT1 COIL TEMPAV1024CKT2 COIL TEMPAV1025UNIT COOL LWTAV1027CKT1 SUCT TEMPAV1028CKT2 SUCT TEMPAV1029SYS 1 DISCHARGE TEMPAV1033CKT1 ECO ENTERING TEMPAV1031SYS 2 DISCHARGE TEMPAV1035CKT2 ECO ENTERING TEMPAV1034CKT1 ECO LEAVING TEMPAV1036CKT2 ECO LEAVING TEMPAV1200R454B RELATIVE LFLAV1037UNIT HEAT LWTAV1039UNIT HEAT EWTAV1040CKT1 SUCT PRSAV1041CKT2 SUCT PRSAV1042CKT1 DISCH PRSAV1043CKT2 DISCH PRSAV1053DI17-32AV1054DI1-16AV1055DO17-33AV1056DO1-16AV1057CKT1 EEVAV1058CKT2 EEVAV1059CKT1 ECO EEVAV1060CKT2 ECO EEVAV1065CKT1 FAN SPEEDAV1066CKT2 FAN SPEEDAV1073DIAL SWITCH STATUSAV1080CKT1 INV COMP FREQAV1096CKT2 INV COMP FREQAV1155FAULT STATUS 1AV1156FAULT STATUS 2AV1157FAULT STATUS 3AV1158FAULT STATUS 4AV1159FAULT STATUS 5AV1160FAULT STATUS 6AV1161FAULT STATUS 7AV1162FAULT STATUS 8AV1163CHILLER MODEL NUMBER
Integration notes
- Access comes from the Modbus function code column: points written with function 06 are marked writable, function 03 points read-only.
- The sheet does not name the BACnet interface or transport; its notes describe the unit's Modbus RTU link (9600 baud, 8-N-1) with the BAS as leader.
- Writable setpoint ranges (IP units) are in the descriptions; SI ranges are in the sheet.
- All MV enums are printed in the points table and the sheet has no add-1 note. Multistate states with their own enum in the points table are shown as printed, from 0. BACnet multistate values start at 1, so the device may report the printed number + 1; confirm by discovery (read the state text).
- The Fault point in the sheet has no BACnet object and is left out.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the YMAE Four-Pipe Modular Heat Pump and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the York YMAE Four-Pipe Modular Heat Pump
How many BACnet points does the York YMAE Four-Pipe Modular Heat Pump have?
This list has 72 BACnet objects: 62 analog values, 5 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which York YMAE Four-Pipe Modular Heat Pump BACnet points are writable?
13 of the 72 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official York YMAE Four-Pipe Modular Heat Pump BACnet documentation?
The source is YMAE Four Pipe Points List, revision Rev 1.1, 2023-08-24, published free by York at https://docs.johnsoncontrols.com/chillers/api/khub/documents/DAKAK2ryzuHrZbBA1Ny6_A/content.
What are the minimum BACnet points to integrate the York YMAE Four-Pipe Modular Heat Pump?
Start with MV 1 CHILLER ON|OFF (CMD) (On/off command (1 = on, 2 = off, as printed)); MV 2 RUNNING MODE (Mode: cooling, heating, pump only, both); AV 3 COOL LWT SETPOINT (Cooling leaving water setpoint); AV 4 HEAT LWT SETPOINT (Heating leaving water setpoint); MV 4 CHILLER ON|OFF CONTROL SELECTION (On/off source; must include BAS (set at HMI)); BV 100 CHILLER ON|OFF (STATUS) (Actual on/off status); AV 114 CHILLER LOADING (Chiller loading, %); AV 111 CHILLER COOL LWT (Chiller cooling leaving water temperature); AV 119 CHILLER HEAT LWT (Chiller heating leaving water temperature); AV 109 UNIT FAULT STATUS (1-16) (Fault flags for modules 1-16, bit-coded).
How do I enable BMS control of the York YMAE Four-Pipe Modular Heat Pump?
BAS start/stop and operating-mode control are enabled at the HMI. MV 4 (on/off source: HMI, Remote, HMI+BAS) and MV 3 (mode source: HMI, Remote, HMI+BAS, BAS) show the selection and are read-only over the network.
How do I check these points on the real YMAE Four-Pipe Modular Heat Pump?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More York BACnet points lists
- Centrifugal chiller retrofit control panel (via SC-EQ card)
York Competitive Retrofit Chiller Panel (SC-EQ)
Other makers' centrifugal chillers retrofitted with a YORK by Johnson Controls OptiView-style control panel and the SC-EQ communication card.
Also known as: YORK competitive retrofit, OptiView retrofit panel, CR SC-EQ, SC-EQ, SE-SCC1001-1 - Packaged rooftop unit controller (ECO2, 50-130 ton)
York ECO2 Rooftop Unit, 50-130 ton, Mod D/E (IPU 1, native BACnet MS/TP)
YORK ECO2 Mod D and Mod E packaged rooftop units, 50 to 130 tons, with the IPU 1 microboard.
Also known as: YORK ECO2, ECO 2, IPU 1, IPU1, YORK Series 100, Series 100 rooftop, ECO2 Native - Dedicated outdoor air system (DOAS) controller
York JDHA DOAS, Option D19 Space Temperature Control (BACnet MS/TP card)
YORK JDHA dedicated outdoor air units with the Option D19 space temperature control program and the BHB8 BACnet card.
Also known as: JDHA, YORK JDHA, Option D19, D19, 100.55-O1, LD18545, DOAS - Make-up air unit / DOAS controller
York JDMA DOAS, Option D21 Makeup Air Control (BACnet MS/TP card)
YORK JDMA dedicated outdoor air units with the Option D21 makeup air control program and the BHB8 BACnet card.
Also known as: JDMA, YORK JDMA, Option D21, D21, 100.55-O2, LD18456, DOAS, makeup air - Water-cooled self-contained unit controller (IPU2)
York L-Series LSWU / LSWD / LSWF Water-Cooled Self-Contained Unit, 25-105 ton (IPU2, native BACnet MS/TP)
YORK L-Series LSWU, LSWD and LSWF water-cooled self-contained air conditioning units, 25-105 ton, with the IPU2 unit controller.
Also known as: LSWU, LSWD, LSWF, L-Series, IPU2, 145.05-NOM7, YSWU, YSWD, Versecon - Rooftop unit controller
York Millennium / Series 40 Packaged Rooftop Units 25-40 Ton with IPU Control
YORK Millennium (Series 40) 25, 30 and 40 ton packaged rooftop units with the IPU control, constant volume, VAV and FlexSys versions.
Also known as: YORK Millennium, Millennium 25-40 ton, Series 40 Rooftop, YORK Series 40, IPU control, 100.50-NOM8, LD14136 - Rooftop unit (packaged, via BACnet IP gateway kit)
York Roomtop RTC/RTH-L with YKN2Open BMS kit (BACnet IP)
York (Johnson Controls Europe) Roomtop RTC/RTH-L cooling and heat pump rooftops, ACTIVA and Large ACTIVA rooftops and VITALITY VAC/VAH/VCH-VIR units with the YKN2Open control and the S606791244 BACnet IP kit.
Also known as: Roomtop RTC-L, Roomtop RTH-L, YKN2Open, S606791244, FS-QS-1010-0122, ACTIVA Rooftop, Large ACTIVA Rooftop, VITALITY VAC, VITALITY VAH, VCH-VIR, N-40462 - Scroll chiller / heat pump / condensing unit
York Scroll Chiller / Heat Pump / Condensing Unit (native BACnet MS/TP)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (including YCWL and YLAE) with the 031-02550 board and its native BAS port.
Also known as: YORK scroll chiller, YORK scroll heat pump, YCWL, YLAE, 031-02550, C.MMC.13, C.MMC.14, C.MMC.16 - Scroll chiller / heat pump / condensing unit (via SC-EQ card)
York Scroll Chiller / Heat Pump / Condensing Unit (SC-EQ)
YORK by Johnson Controls scroll-compressor chillers, heat pumps and condensing units (one or two refrigerant systems, including the YCWL) fitted with the SC-EQ communication card.
Also known as: YORK scroll chiller, YORK scroll heat pump, YORK condensing unit, YCWL, SC-EQ, SE-SCC1001-1 - Scroll chiller / heat pump (via E-Link gateway)
York Scroll Chiller / Heat Pump / Condensing Unit - BAS (ISN) E-Link (YorkTalk 2)
YORK scroll chillers, heat pumps and condensing units (board 031-02550, including YCWL and YLAE variants named on the sheet), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK scroll chiller, YCWL, YLAE, Scroll BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Packaged rooftop unit controller (Series 100, 50-65 ton)
York Series 100 YPAL Rooftop, 50-65 ton, Mod F (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 50-65 ton Mod F, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 50-65 Mod F, 100.50-NOM5, IPU - Packaged rooftop unit controller (Series 100, 70-150 ton)
York Series 100 YPAL Rooftop, 70-150 ton, Mod F/G (IPU, native BACnet MS/TP)
YORK Series 100 YPAL single packaged rooftop units, 70-105 ton Mod F and 120-150 ton Mod G, with the IPU control board.
Also known as: YPAL, YORK Series 100, Series 100 rooftop, YPAL 120-150 Mod G, YPAL 70-105 Mod F, 100.50-NOM11, 100.50-NOM9, IPU - Air-cooled variable-speed screw chiller
York YCAV / YCIV Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YCAV and YCIV air-cooled variable-speed screw chillers (up to four refrigerant systems) with the 031-03478 microboard and its native BAS port.
Also known as: YORK YCAV, YORK YCIV, 031-03478, YCAV_IV Native, Latitude - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YCAV / YCIV Air-Cooled Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YCAV and YCIV air-cooled screw chillers (1/2 and 3/4 compressor sections, microboard 031-02478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YCAV, YORK YCIV, YCAV_YCIV BAS, E-Link, eLink, YorkTalk 2, 031-02478 - Water-cooled dual-compressor centrifugal chiller (via SC-EQ card)
York YD Dual-Compressor Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YD water-cooled centrifugal chillers with two compressors, fitted with the SC-EQ communication card.
Also known as: YD, YORK YD, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YD Dual-Compressor Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YD dual-compressor centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YD, YD OptiView, E-Link, eLink, YorkTalk 3 - Absorption chiller, steam or hot water (via SC-EQ card)
York YIA Absorption Chiller (SC-EQ)
YORK YIA steam- or hot-water-fired absorption chillers fitted with the SC-EQ communication card.
Also known as: YORK YIA, YIA absorption, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via SC-EQ card)
York YK Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK water-cooled centrifugal chillers (OptiView panel) fitted with the SC-EQ communication card.
Also known as: YK, YORK YK, SC-EQ, SC-EQUIP, SE-SCC1001-1, OptiView - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with Electro-Mechanical or Solid State Starter - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and an electro-mechanical or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK SSS, YK EM starter, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YK, YK OptiView, YK VSD, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller with economizer compressor (via SC-EQ card)
York YK-EP Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YK-EP (Efficiency Plus) water-cooled centrifugal chillers, which pair the main compressor with an economizer compressor, fitted with the SC-EQ communication card.
Also known as: YK-EP, YKEP, YK EP, YK-EP Efficiency Plus, SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with EM or SSS Starter - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and electro-mechanical or solid-state starters, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via E-Link gateway)
York YK-EP Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YK-EP (YKEP) centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YKEP, YK-EP, YKEP OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled centrifugal heat pump chiller (via SC-EQ card)
York YKHT Centrifugal Heat Pump Chiller, YT3 panel (SC-EQ)
YORK YKHT two-stage centrifugal heat pump chillers with the YT3 control panel, fitted with the SC-EQ communication card.
Also known as: YORK YKHT, YKHT, YT3, YT3 YKHT, SC-EQ, YKHT heat pump chiller - Air-to-water modular heat pump (two-pipe)
York YMAE Two-Pipe Modular Heat Pump
YORK YMAE air-to-water modular heat pumps with inverter compressors in the two-pipe (heating or cooling) version.
Also known as: YORK YMAE, YMAE two pipe, YMAE 2-pipe, air-to-water heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YMC2 Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK by Johnson Controls YMC2 oil-free, magnetic-bearing centrifugal chillers with a variable speed drive, fitted with the SC-EQ communication card.
Also known as: YMC2, YORK YMC2, YMC², SC-EQ, SC-EQUIP, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YMC2 Magnetic-Bearing Centrifugal Chiller - OptiView E-Link (YorkTalk 3)
YORK YMC2 magnetic-bearing centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YMC2, YMC², YMC2 OptiView, E-Link, eLink, YorkTalk 3, 031-02430 - Water-cooled screw chiller (via SC-EQ card)
York YR Screw Chiller (OptiView, SC-EQ)
YORK YR water-cooled screw chillers with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YR, YR OptiView, YR chiller, SC-EQ, SE-SCC1001-1 - Water-cooled screw chiller (via E-Link gateway)
York YR Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YR water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YR, YR OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled screw chiller (via E-Link gateway)
York YS / YN Screw Chiller - OptiView E-Link (YorkTalk 3)
YORK YS and YN water-cooled screw chillers with OptiView panel and standard or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YS, YORK YN, YS OptiView, YN OptiView, E-Link, eLink, YorkTalk 3 - Water-cooled screw chiller / heat pump (via SC-EQ card)
York YS / YS HP / YN Screw Chiller (SC-EQ)
YORK YS and YN water-cooled screw chillers and YS HP heat pumps with OptiView controls, fitted with the SC-EQ communication card.
Also known as: YORK YS, YS HP, YORK YN, YS heat pump, OptiView YS, SC-EQ, SE-SCC1001-1 - Air-cooled screw chiller
York YSAA Air-Cooled Screw Chiller (native BACnet MS/TP)
YORK YSAA air-cooled screw chillers (two refrigerant systems) with the 031-02550 board and its native BAS port.
Also known as: YORK YSAA, YSAA chiller, 031-02550, YSAA Native - Air-cooled screw chiller (via E-Link gateway)
York YSAA Air-Cooled Screw Chiller - BAS (ISN) E-Link (YorkTalk 2)
YORK YSAA air-cooled screw chillers (board 031-02550), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YSAA, YSAA BAS, E-Link, eLink, YorkTalk 2, 031-02550 - Steam-turbine-driven centrifugal chiller (via SC-EQ card)
York YST Steam Turbine Chiller (SC-EQ)
YORK YST steam-turbine-driven centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YST, YST chiller, steam turbine drive chiller, SC-EQ, SE-SCC1001-1 - Steam turbine driven centrifugal chiller (via E-Link gateway)
York YST Steam Turbine Chiller - OptiView E-Link (YorkTalk 3)
YORK YST steam turbine driven centrifugal chillers with OptiView panel, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YST, YST OptiView, steam turbine chiller, E-Link, eLink, YorkTalk 3 - Water-cooled centrifugal chiller (via SC-EQ card)
York YT Centrifugal Chiller (SC-EQ)
YORK YT water-cooled centrifugal chillers with OptiView controls, fitted with the SC-EQ communication card (VSD, solid-state or electro-mechanical starters).
Also known as: YORK YT, YT chiller, OptiView YT, SC-EQ, SE-SCC1001-1 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller (Standard or Solid State Starter) - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and a standard (electro-mechanical) or solid-state starter, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, E-Link, eLink, YorkTalk 3, 031-01730, 031-02430 - Water-cooled centrifugal chiller (via E-Link gateway)
York YT Centrifugal Chiller with VSD - OptiView E-Link (YorkTalk 3)
YORK YT centrifugal chillers with OptiView panel and variable speed drive, connected through a YORK E-Link gateway over YorkTalk 3.
Also known as: YORK YT, YT OptiView, YT VSD, E-Link, eLink, YorkTalk 3 - Air-cooled variable-speed screw chiller
York YVAA / YVFA / YAGK Chiller (native BACnet MS/TP)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with the 031-03478 board and its native BAS port.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA native, 031-03478, Y.ACS.20 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA / YVFA / YAGK Chiller, YT3 panel (SC-EQ)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card and the YT3 control panel.
Also known as: YORK YVAA, YORK YVFA, YORK YAGK, YVAA, YVFA, YAGK, SC-EQ, SE-SCC1001-1, YT3, YVAA YT3 - Air-cooled variable-speed screw chiller (via E-Link gateway)
York YVAA / YVFA / YAGK E-Link (YorkTalk 2)
YORK YVAA, YVFA (free cooling) and YAGK air-cooled variable-speed screw chillers with 031-02478 or 031-03478 microboards, connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVAA, YORK YVFA, YAGK, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Air-cooled variable-speed screw chiller (via SC-EQ card)
York YVAA Style B Chiller (SC-EQ)
YORK YVAA Style B air-cooled variable-speed screw chillers (two refrigerant systems) fitted with the SC-EQ communication card.
Also known as: YORK YVAA, YVAA Style B, YVAA-B, SC-EQ, SE-SCC1001-1 - Air-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YVAM Air-Cooled Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YVAM air-cooled magnetic-bearing centrifugal chillers fitted with the SC-EQ communication card.
Also known as: YORK YVAM, YVAM chiller, YVAM mag bearing, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller / heat pump (via SC-EQ card)
York YVWA Water-Cooled Variable-Speed Screw Chiller (SC-EQ)
YORK YVWA water-cooled variable-speed screw chillers (one or two compressors, chiller or heat pump mode) fitted with the SC-EQ communication card.
Also known as: YORK YVWA, YVWA chiller, YVWA heat pump, SC-EQ, SE-SCC1001-1 - Water-cooled variable-speed screw chiller (via E-Link gateway)
York YVWA Water-Cooled Variable-Speed Screw Chiller - BAS E-Link (YorkTalk 2)
YORK YVWA water-cooled variable-speed screw chillers (microboards 031-02478 / 031-03478), connected through a YORK E-Link gateway over YorkTalk 2.
Also known as: YORK YVWA, YVWA BAS, E-Link, eLink, YorkTalk 2, 031-02478, 031-03478 - Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)
York YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)
YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.
Also known as: YORK YVWH, YVWH-200, YORK YVWE, YORK YGWH, SC-EQ, water-to-water screw heat pump - Water-cooled magnetic-bearing centrifugal chiller (via SC-EQ card)
York YZ Magnetic-Bearing Centrifugal Chiller (SC-EQ)
YORK YZ water-cooled magnetic-bearing centrifugal chillers (variable speed drive) fitted with the SC-EQ communication card.
Also known as: YORK YZ, YZ chiller, YZ mag bearing, SC-EQ, SE-SCC1001-1, OptiView
Source: YMAE Four Pipe Points List · rev. Rev 1.1, 2023-08-24. Object names, instances and units are reproduced as published; descriptions are our own.