Boiler controller gateway · BACnet points list
Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode BACnet points list
Updated 28 October 2026
A ProtoNode FPC-N34 reads the boiler control over Modbus RTU and presents it as a BACnet IP or BACnet MS/TP device with 831 objects numbered in one sequence across AI, AV, BI and MI. Besides temperatures, status, counters and lockout history, it carries the priority and network (cascade) settings, a block per cascade member (Shadow 2-8), and bit-level BIs for relay outputs, inputs and lockout causes.
This page lists 831 BACnet objects for the Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode — 111 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Weil-McLain’s own free documentation, linked below.
- Manufacturer
- Weil-McLain
- Model
- Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode
- Equipment
- Boiler controller gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 831 (111 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Evergreen, SlimFit 550-750, SlimFit 1000-2000 Series 2, SVF, ProtoNode FPC-N34, ProtoNode FPC-N35, ProtoNode
Reference only, provided as-is: verify against Weil-McLain’s current documentation and the live device before use. Not official Weil-McLain information. Terms of use.
BMS integration notes: Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode
Most objects are read-only monitoring. Map boiler status, target and outlet temperatures, modulation rate, gas valve output and sensor warnings. The writable AVs are the priority, network and cascade settings (supply targets, outdoor reset, differentials, rates, times); the supplement does not say which one a BMS should use as a run or setpoint command.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MI 138 | Boiler Status | Boiler status code | Read |
| AI 10 | Active Target Supply Temperature | Supply temperature the boiler is aiming for | Read |
| AI 7 | Boiler Out 1 Temperature | Boiler outlet water temperature | Read |
| AI 307 | Boiler Modulation Rate | Burner modulation rate | Read |
| BI 594 | Relay Output Gas Valve ON | Gas valve energized (burner firing) | Read |
| AI 19 | Outdoor Temp | Outdoor air temperature | Read |
| AI 160 | Sensor Warnings | Sensor warning code | Read |
Network setup
- Device instance, MAC address and baud rate are set on the ProtoNode (see the ProtoNode start-up guide); this supplement does not list them.
- Object IDs are unique across object types (1-831), so AI 7 and AV 7 never both exist.
Watch out for
- No read/write column: AVs are writable settings, all AI/BI/MI are read-only.
- Several names repeat (for example Boiler Status is MI 138 and AI 653, AI 75 Local Return Temp and AI 151 Local Return Temperature); use the object ID, not the name.
- Writable AVs are boiler configuration values; avoid writing them cyclically.
Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Pad00HB | Read | |||
| MI | 2 | Boiler Model | Read | |||
| AI | 3 | U1 Sw Version | Read | |||
| AI | 4 | U2 Sw Version | Read | |||
| AI | 5 | NET Volts Output | Read | |||
| AI | 6 | Relay Output Status | Read | |||
| AImin | 7 | Boiler Out 1 Temperature | Boiler outlet 1 temperature | Read | ||
| AI | 8 | Mod Return Temp | Read | |||
| AI | 9 | MHEOTmp F1 | Read | |||
| AImin | 10 | Active Target Supply Temperature | Active target supply temperature | Read | ||
| AI | 11 | Mod Temp | Read | |||
| AI | 12 | Fire Rate Selection | Read | |||
| BI | 13 | Boiler Status 2 | Read | |||
| AI | 14 | HLOReset | Read | |||
| AI | 15 | Fan Speed | Read | |||
| AI | 16 | Flame Sense Value | Read | |||
| AI | 17 | AvgFlameL | Read | |||
| AI | 18 | Slave Fire Rate Unconverted | Read | |||
| AImin | 19 | Outdoor Temp | Outdoor temperature | Read | ||
| AV | 20 | System Time (Minutes) | Write | |||
| AV | 21 | System Time (Hours) | Write | |||
| AV | 22 | System Date (Day) | Write | |||
| AV | 23 | System Date (Month) | Write | |||
| AV | 24 | System Date (Year) | Write | |||
| AI | 25 | 0-10V Output | Read | |||
| AI | 26 | 0-10V Output | Read | |||
| AI | 27 | 0-10V Input | Read | |||
| AI | 28 | Max Blower RPM | Read | |||
| AI | 29 | Flame Boost | Read | |||
| AV | 30 | Circulator Exercise/Freeze Protection | Write | |||
| AI | 31 | Input 2 Hours RAM MSB | Read | |||
| AI | 32 | Priority 1 Settings | Read | |||
| AV | 33 | Priority 1 Supply Max Target | Write | |||
| AV | 34 | Priority 1 Supply Min Target | Write | |||
| AV | 35 | Priority 1 OD Reset/Volts Max | Write | |||
| AV | 36 | Priority 1 OD Reset/Volts Min | Write | |||
| AV | 37 | Priority 1 Max Boiler Temperature | Write | |||
| AV | 38 | Priority 3 Max Rate Volts | Write | |||
| AI | 39 | OAT Configuration | Read | |||
| AI | 40 | Active Network Priority's Boiler Off Diff | Read | |||
| AV | 41 | Priority 1 System On Diff | Write | |||
| AV | 42 | Priority 1 Max On Time Setting | Write | |||
| AV | 43 | Priority 1 Post Pump Time | Write | |||
| AV | 44 | Priority 1 Boost Time | Write | |||
| AI | 45 | Input 1 Priority | Read | |||
| AV | 46 | Priority 1 Pre Pump Time | Write | |||
| AI | 47 | Min Blower RPM | Read | |||
| AV | 48 | Priority 1 Boiler On Diff | Write | |||
| AV | 49 | Priority 1 Boiler Off Diff | Write | |||
| AV | 50 | Priority 1 Max Rate | Write | |||
| AV | 51 | Priority 1 Min Rate | Write | |||
| AI | 52 | Active Network Priority's Max BLR Temp | Read | |||
| AI | 53 | Active Network Priority's Boiler On Diff | Read | |||
| AI | 54 | Input 2 Hours RAM LSB | Read | |||
| AI | 55 | Priority 2 Setting | Read | |||
| AV | 56 | Priority 2 Supply Max Target | Write | |||
| AV | 57 | Priority 2 Supply Min Target | Write | |||
| AV | 58 | Priority 2 OD Reset/Volts Max | Write | |||
| AV | 59 | Priority 2 OD Reset/Volts Min | Write | |||
| AI | 60 | Active Network Prepump Time | Read | |||
| AI | 61 | Ignition Counter RAM | Read | |||
| AV | 62 | Priority 2 Min On Time Setting | Write | |||
| AV | 63 | Priority 2 Max On Time Setting | Write | |||
| AV | 64 | Priority 2 Post Pump Time | Write | |||
| AV | 65 | Priority 2 Boost Time | Write | |||
| AI | 66 | Boiler Control Type | Read | |||
| AV | 67 | Priority 1 Pre Pump Time | Write | |||
| AV | 68 | Priority 2 System Off Diff | Write | |||
| AI | 69 | Network Minimum On Time | Read | |||
| AV | 70 | Priority 2 Boiler On Diff | Write | |||
| AV | 71 | Priority 2 Boiler Off Diff | Write | |||
| AV | 72 | Priority 2 Max Rate | Write | |||
| AV | 73 | Priority 2 Min Rate | Write | |||
| AI | 74 | Network Return Temp | Read | |||
| AI | 75 | Local Return Temp | Read | |||
| AI | 76 | Active Network Priority Post Pump Time | Read | |||
| AI | 77 | Single Boiler: Pri 3 Setting/Master Boiler: Network 1 Pri Setting | Read | |||
| AV | 78 | Priority 3/Net1 Supply Max Target | Write | |||
| AV | 79 | Priority 3/Net1 Supply Min Target | Write | |||
| AV | 80 | Priority 3/Net1 OD Reset/Volts Max | Write | |||
| AV | 81 | Priority 3/Net1 OD Reset/Volts Min | Write | |||
| AI | 82 | Network Max On Time | Read | |||
| AV | 83 | Priority 3/Net1 System On Diff | Write | |||
| AV | 84 | Priority 3 Min On Time Setting | Write | |||
| AV | 85 | Priority 3/Net1 System Off Diff | Write | |||
| AV | 86 | Priority 3/Net1 Post Pump Time | Write | |||
| AV | 87 | Priority 3/Net1 Boost Time | Write | |||
| AV | 88 | Priority 2 Max Boiler Temperature | Write | |||
| AV | 89 | Priority 3/Net1 Pre Pump Time | Write | |||
| AI | 90 | Boiler Status 3 | Read | |||
| AI | 91 | Network Modulation Rate | Modulation rate requested over the network | Read | ||
| AV | 92 | Priority 3/Net1 Boiler On Diff | Write | |||
| AV | 93 | Priority 3/Net1 Boiler Off Diff | Write | |||
| AV | 94 | Priority 3 Max Rate (for single) | Write | |||
| AV | 95 | Priority 3 Min Rate (for single) | Write | |||
| AV | 96 | P3 Max Boiler Temp | Write | |||
| AI | 97 | Network Run Pumps | Read | |||
| AV | 98 | High Limit Temp | Write | |||
| AV | 99 | WWSD Temp | Write | |||
| AV | 100 | P1 More Settings | Write | |||
| AV | 101 | P1 Min Rate Volts | Write | |||
| AV | 102 | P2 More Settings | Write | |||
| AV | 103 | Outdoor Temp Correction | Write | |||
| AV | 104 | P3 More Settings | Write | |||
| AI | 105 | Input 2 Hours LSB | Read | |||
| AV | 106 | P1 System Off Diff | Write | |||
| AI | 107 | Input 2 Hours MSB | Read | |||
| AV | 108 | P2 Min Rate Volts | Write | |||
| AI | 109 | Boiler Model Number | Read | |||
| AV | 110 | P3 Min rate Volts | Write | |||
| AI | 111 | Input 1 Hours MSB | Read | |||
| AI | 112 | Input 1 Hours LSB | Read | |||
| AI | 113 | Input 1 Hours RAM MSB | Read | |||
| AI | 114 | Input 1 Hours RAM LSB | Read | |||
| AV | 115 | P2 System On Diff | Write | |||
| AV | 116 | P1 Response Time | Write | |||
| AV | 117 | P2 Response Time | Write | |||
| AV | 118 | P3 Response Time | Write | |||
| AI | 119 | Network Hours LSB | Read | |||
| AI | 120 | Ignition Speed | Read | |||
| AI | 121 | Input 2 Priority | Read | |||
| AI | 122 | Input 3 Priority | Read | |||
| AI | 123 | Ignition Counts | Read | |||
| AI | 124 | Burner Hours | Read | |||
| AI | 125 | Burner Hours RAM | Read | |||
| AI | 126 | Reset Factory MSB | Read | |||
| AI | 127 | Reset Factory LSB | Read | |||
| AI | 128 | Network Hours MSB | Read | |||
| MI | 129 | Boiler Out 1 | Read | |||
| AI | 130 | Network Hours RAM MSB | Read | |||
| AI | 131 | Network Hours RAM LSB | Read | |||
| MI | 132 | Boiler Out 2 | Read | |||
| AI | 133 | Heat Xchgr 1 | Read | |||
| AI | 134 | Max EE | Read | |||
| AI | 135 | Heat Xchgr 2 | Read | |||
| AI | 136 | Available to run | Read | |||
| MI | 137 | Boiler In Temperature | Read | |||
| MImin | 138 | Boiler Status | Boiler status code | Read | ||
| AI | 139 | bHeatXchgrIn2 | Read | |||
| AI | 140 | Input Status | Read | |||
| MI | 141 | Flue Temperature 1 | Read | |||
| AI | 142 | Local Supply Temp | Read | |||
| MI | 143 | Flue Temperature 2 | Read | |||
| AI | 144 | P1 Max Rate Volts | Read | |||
| AI | 145 | bDHWSensor1 | Read | |||
| MI | 146 | Local Outdoor Temperature | Read | |||
| AI | 147 | bDHWSensor2 | Read | |||
| MI | 148 | Network Outdoor Temperature | Read | |||
| MI | 149 | Network Supply Temperature | Read | |||
| AI | 150 | Local Supply Temperature | Read | |||
| AI | 151 | Local Return Temperature | Read | |||
| AI | 152 | Input 3 Hours MSB | Read | |||
| AI | 153 | Input 3 Hours LSB | Read | |||
| AI | 154 | Bad EEPROM Count | Read | |||
| AI | 155 | Bad Ram Count | Read | |||
| AI | 156 | Default Count | Read | |||
| AI | 157 | Ignition Retries | Read | |||
| AI | 158 | Lockout History 1 Expansion Board Errors | Read | |||
| AI | 159 | Manual Lockout Count | Read | |||
| AImin | 160 | Sensor Warnings | Sensor warning code | Read | ||
| AI | 161 | Auto Lockout Count | Read | |||
| AI | 162 | Lockout History 1 Hard Lockout Errors | Read | |||
| AI | 163 | Lockout History 1 Soft Lockout Errors | Read | |||
| AI | 164 | Lockout History 1 Minutes | Read | |||
| AI | 165 | Lockout History 1 Hours | Read | |||
| AI | 166 | Lockout History 1 Day | Read | |||
| AI | 167 | Lockout History 1 Month | Read | |||
| AI | 168 | Lockout History 1 Year | Read | |||
| AI | 169 | Lockout History 1 Boiler Model | Read | |||
| AI | 170 | Lockout History 1 Input Status | Read | |||
| AI | 171 | Lockout History 1 Relay Output Status | Read | |||
| AI | 172 | Lockout History 1 Flame Signal MSB | Read | |||
| AI | 173 | Lockout History 1 Flame Signal LSB | Read | |||
| AI | 174 | Lockout History 1 Outdoor Temperature | Read | |||
| AI | 175 | Lockout History 1 Flue Temperature 2 | Read | |||
| AI | 176 | Lockout History 1 Boiler Out Temp 2 | Read | |||
| AI | 177 | Lockout History 1 Boiler In Temp 2 | Read | |||
| AI | 178 | bErrSDW | Read | |||
| AI | 179 | Lockout History 1 Flue Temperature 1 | Read | |||
| AI | 180 | Lockout History 1 Boiler Out Temp 1 | Read | |||
| AI | 181 | Lockout History 1 Heat Exchanger Temp 1 | Read | |||
| AI | 182 | Lockout History 1 Supply Temperature | Read | |||
| AI | 183 | Lockout History 1 Return Temperature | Read | |||
| AI | 184 | Lockout History 1 Boiler In Temp 1 | Read | |||
| AI | 185 | Lockout History 1 0-10V Output | Read | |||
| AI | 186 | Lockout History 1 Blower Speed (RPM) | Read | |||
| AI | 187 | Lockout History 2 Hard Lockout Errors | Read | |||
| AI | 188 | Lockout History 2 Soft Lockout Errors | Read | |||
| AI | 189 | Lockout History 2 Minutes | Read | |||
| AI | 190 | Lockout History 2 Hours | Read | |||
| AI | 191 | Lockout History 2 Day | Read | |||
| AI | 192 | Lockout History 2 Month | Read | |||
| AI | 193 | Lockout History 2 Year | Read | |||
| AI | 194 | Lockout History 2 Boiler Model | Read | |||
| AI | 195 | Lockout History 2 Input Status | Read | |||
| AI | 196 | Lockout History 2 Relay Output Status | Read | |||
| AI | 197 | Lockout History 2 Flame Signal MSB | Read | |||
| AI | 198 | Lockout History 2 Flame Signal LSB | Read | |||
| AI | 199 | Lockout History 2 Outdoor Temperature | Read | |||
| AI | 200 | Lockout History 2 Flue Temperature 2 | Read | |||
| AI | 201 | Lockout History 2 Boiler Out Temp 2 | Read | |||
| AI | 202 | Lockout History 2 Boiler In Temp 2 | Read | |||
| AI | 203 | bH1ErrSDW | Read | |||
| AI | 204 | Lockout History 2 Flue Temperature 1 | Read | |||
| AI | 205 | Lockout History 2 Boiler Out Temp 1 | Read | |||
| AI | 206 | Lockout History 2 Heat Exchanger Temp 1 | Read | |||
| AI | 207 | Lockout History 2 Supply Temperature | Read | |||
| AI | 208 | Lockout History 2 Return Temperature | Read | |||
| AI | 209 | Lockout History 2 Boiler In Temp 1 | Read | |||
| AI | 210 | Lockout History 2 0-10V Output | Read | |||
| AI | 211 | Lockout History 2 Blower Speed (RPM) | Read | |||
| AI | 212 | Lockout History 3 Hard Lockout Errors | Read | |||
| AI | 213 | Lockout History 3 Soft Lockout Errors | Read | |||
| AI | 214 | Lockout History 3 Minutes | Read | |||
| AI | 215 | Lockout History 3 Hours | Read | |||
| AI | 216 | Lockout History 3 Day | Read | |||
| AI | 217 | Lockout History 3 Month | Read | |||
| AI | 218 | Lockout History 3 Year | Read | |||
| AI | 219 | Lockout History 3 Boiler Model | Read | |||
| AI | 220 | Lockout History 3 Input Status | Read | |||
| AI | 221 | Lockout History 3 Relay Output Status | Read | |||
| AI | 222 | Lockout History 3 Flame Signal MSB | Read | |||
| AI | 223 | Lockout History 3 Flame Signal LSB | Read | |||
| AI | 224 | Lockout History 3 Outdoor Temperature | Read | |||
| AI | 225 | Lockout History 3 Flue Temperature 2 | Read | |||
| AI | 226 | Lockout History 3 Boiler Out Temp 2 | Read | |||
| AI | 227 | Lockout History 3 Boiler In Temp 2 | Read | |||
| AI | 228 | bH1ErrSDW | Read | |||
| AI | 229 | Lockout History 3 Flue Temperature 1 | Read | |||
| AI | 230 | Lockout History 3 Boiler Out Temp 1 | Read | |||
| AI | 231 | Lockout History 3 Heat Exchanger Temp 1 | Read | |||
| AI | 232 | Lockout History 3 Supply Temperature | Read | |||
| AI | 233 | Lockout History 3 Return Temperature | Read | |||
| AI | 234 | Lockout History 3 Boiler In Temp 1 | Read | |||
| AI | 235 | Lockout History 3 0-10V Output | Read | |||
| AI | 236 | Lockout History 3 Blower Speed (RPM) | Read | |||
| AI | 237 | P2 Max Rate Volts | Read | |||
| AI | 238 | Clear Error History | Read | |||
| AI | 239 | Installer Name 1 | Read | |||
| AI | 240 | Installer Name 2 | Read | |||
| AI | 241 | Installer Name 3 | Read | |||
| AI | 242 | Installer Name 4 | Read | |||
| AI | 243 | Installer Name 5 | Read | |||
| AI | 244 | Installer Name 6 | Read | |||
| AI | 245 | Installer Name 7 | Read | |||
| AI | 246 | Installer Name 8 | Read | |||
| AI | 247 | Installer Name 9 | Read | |||
| AI | 248 | Installer Name 10 | Read | |||
| AI | 249 | Installer Name 11 | Read | |||
| AI | 250 | Installer Name 12 | Read | |||
| AI | 251 | Installer Name 13 | Read | |||
| AI | 252 | Installer Name 14 | Read | |||
| AI | 253 | Installer Name 15 | Read | |||
| AI | 254 | bPad88LB | Read | |||
| AI | 255 | Installer Phone 1 | Read | |||
| AI | 256 | Installer Phone 2 | Read | |||
| AI | 257 | Installer Phone 3 | Read | |||
| AI | 258 | Installer Phone 4 | Read | |||
| AI | 259 | Installer Phone 5 | Read | |||
| AI | 260 | Installer Phone 6 | Read | |||
| AI | 261 | Last Maintenance Reminder Month | Read | |||
| AI | 262 | Last Maintenance Reminder Day | Read | |||
| AI | 263 | Last Maintenance Reminder Year | Read | |||
| AV | 264 | Maintenance Reminder Interval | Write | |||
| AI | 265 | Installation Month | Read | |||
| AI | 266 | Installation Day | Read | |||
| AI | 267 | Installation Year | Read | |||
| AI | 268 | Last Maintenance Performed Month | Read | |||
| AI | 269 | Last Maintenance Performed Day | Read | |||
| AI | 270 | Last Maintenance Performed Year | Read | |||
| AI | 271 | Boiler CP Number 1 | Read | |||
| AI | 272 | Boiler CP Number 2 | Read | |||
| AI | 273 | Boiler CP Number 3 | Read | |||
| AI | 274 | Boiler CP Number 4 | Read | |||
| AI | 275 | Boiler CP Number 5 | Read | |||
| AI | 276 | Boiler CP Number 6 | Read | |||
| AI | 277 | Boiler CP Number 7 | Read | |||
| AI | 278 | bInstModelNumber | Read | |||
| AI | 279 | bUTTest2 | Read | |||
| AI | 280 | bUTTest1 | Read | |||
| AI | 281 | bCrntErrFR | Read | |||
| AI | 282 | bH1ErrFR | Read | |||
| AI | 283 | bH2ErrFR | Read | |||
| AI | 284 | bCrntErrExpBrd | Read | |||
| AI | 285 | Lockout History 2 Expansion Board Errors | Read | |||
| AI | 286 | Lockout History 3 Expansion Board Errors | Read | |||
| AI | 287 | Lockout History 1 Boiler Status 2 | Read | |||
| AI | 288 | Lockout History 2 Boiler Status 2 | Read | |||
| AI | 289 | Lockout History 3 Boiler Status 2 | Read | |||
| AI | 290 | Lockout History 1 10 Volt Input | Read | |||
| AI | 291 | Lockout History 2 10 Volt Input | Read | |||
| AI | 292 | Lockout History 3 10 Volt Input | Read | |||
| AI | 293 | bInput3HoursRAM MSB | Read | |||
| AI | 294 | bInput3HoursRAM LSB | Read | |||
| AI | 295 | Ignore Flame Signal Shutdown | Read | |||
| AI | 296 | P1 ODT Setpoint | Read | |||
| AI | 297 | bCommGVCtrlRd | Read | |||
| AI | 298 | Number of Failed Ignitions | Read | |||
| AI | 299 | bExpBrdRev | Read | |||
| AI | 300 | bPad9FLB | Read | |||
| AI | 301 | bCommGVSts1 | Read | |||
| AI | 302 | bCommGVSts2 | Read | |||
| AI | 303 | bCGVOutputs | Read | |||
| AI | 304 | bCommGVCtrl | Read | |||
| AI | 305 | P3 ODT Setpoint | Read | |||
| AI | 306 | P2 ODT Setpoint | Read | |||
| AImin | 307 | Boiler Modulation Rate | Boiler modulation rate | Read | ||
| AI | 308 | Shadow Number | Read | |||
| AV | 309 | Max Time Network | Write | |||
| AV | 310 | Min Time Network | Write | |||
| AV | 311 | Max Rate Network | Write | |||
| AV | 312 | Min Rate Network | Write | |||
| AV | 313 | High Temp Limit | Write | |||
| AI | 314 | Days Passed | Read | |||
| AV | 315 | Base Rate High | Write | |||
| AV | 316 | Base Rate Low | Write | |||
| AI | 317 | Sequence Type | Read | |||
| AV | 318 | Boiler Rotation Method | Write | |||
| AV | 319 | Force Lead Rotate | Write | |||
| AI | 320 | User Mode | Read | |||
| AI | 321 | Net1 P Gain Adjust | Read | |||
| AI | 322 | Net1 I Gain Adjust | Read | |||
| AI | 323 | Net1 Maximum Step Size | Read | |||
| AI | 324 | Net1 Minimum Step Size | Read | |||
| AI | 325 | Net2 P Gain Adjust | Read | |||
| AI | 326 | Net2 I Gain Adjust | Read | |||
| AI | 327 | Net2 Maximum Step Size | Read | |||
| AI | 328 | Net2 Minimum Step Size | Read | |||
| AI | 329 | Modify Equation | Read | |||
| AV | 330 | Net1 Priority System Add Boiler Diff | Write | |||
| AV | 331 | Net1 Priority System Drop Boiler Diff | Write | |||
| AV | 332 | Net1 Priority Mod Delay Time | Write | |||
| AV | 333 | Net1 Priority Stabilization Time | Write | |||
| AV | 334 | Net1 Priority Drop Delay Time | Write | |||
| AI | 335 | Net1 Priority Max Sys Rate | Read | |||
| AI | 336 | Net1 Priority Min Boilers | Read | |||
| AV | 337 | Net1 Priority Max On Time | Write | |||
| AV | 338 | Rotation Frequency | Write | |||
| AI | 339 | Boiler Order 1 | Read | |||
| AI | 340 | Boiler Order 2 | Read | |||
| AI | 341 | Boiler Order 3 | Read | |||
| AI | 342 | Boiler Order 4 | Read | |||
| AI | 343 | Boiler Order 5 | Read | |||
| AI | 344 | Boiler Order 6 | Read | |||
| AI | 345 | Boiler Order 7 | Read | |||
| AI | 346 | Boiler Order 8 | Read | |||
| AV | 347 | Net2 Priority System Type | Write | |||
| AI | 348 | Net2 Priority target Mod Sensor | Read | |||
| AV | 349 | Net2 Priority target Adjust | Write | |||
| AV | 350 | Net2 Priority supply Max | Write | |||
| AV | 351 | Net2 Priority supply Min | Write | |||
| AV | 352 | Net2 Priority Outdoor Reset Max | Write | |||
| AV | 353 | Net2 Priority Outdoor Reset Min | Write | |||
| AV | 354 | Net2 Priority Volts Max | Write | |||
| AV | 355 | Net2 Priority Volts Min | Write | |||
| AV | 356 | Net2 Priority Boost Time | Write | |||
| AV | 357 | Net2 Priority System Off Differential | Write | |||
| AV | 358 | Net2 Priority System On Differential | Write | |||
| AV | 359 | Net2 Priority System Add Boiler Differential | Write | |||
| AV | 360 | Net2 Prioirty System Drop Boiler Diff | Write | |||
| AV | 361 | Net2 Priority Mod Delay Time | Write | |||
| AV | 362 | Net2 Priority Stabilization Time | Write | |||
| AV | 363 | Net2 Priority Drop Delay Time | Write | |||
| AV | 364 | Net2 Priority Max Boiler Temp | Write | |||
| AV | 365 | Net2 Priority Boiler On Diff | Write | |||
| AV | 366 | Net2 Priority Boiler Off Diff | Write | |||
| AI | 367 | Net2 Priority Max On Time | Read | |||
| AV | 368 | Net2 Priority Min On Time | Write | |||
| AI | 369 | Net2 Priority Run Boiler Pump | Read | |||
| AI | 370 | Net2 Prioirity Run Sys Pump Aux Type | Read | |||
| AV | 371 | Net2 Priority Pre Pump Time | Write | |||
| AV | 372 | Net2 Priority Post Pump Time | Write | |||
| AV | 373 | Net2 Priority Max Rate | Write | |||
| AV | 374 | Net2 Priority Min Rate | Write | |||
| AV | 375 | Net2 Priority Max Sys Rate | Write | |||
| AI | 376 | Net2 Priority Min Boilers | Read | |||
| AV | 377 | Net2 Priority Activate Contact Setting | Write | |||
| AV | 378 | Net2 Priority Response Time | Write | |||
| AI | 379 | Custom Type String 1 | Read | |||
| AI | 380 | Custom Type String 2 | Read | |||
| AI | 381 | Custom Type String 3 | Read | |||
| AI | 382 | Custom Type String 4 | Read | |||
| AI | 383 | Custom Type String 5 | Read | |||
| AI | 384 | Custom Type String 6 | Read | |||
| AI | 385 | Custom Type String 7 | Read | |||
| AI | 386 | Custom Type String 8 | Read | |||
| AI | 387 | Custom Type String 9 | Read | |||
| AI | 388 | Custom Type String 10 | Read | |||
| AI | 389 | Custom Type String 11 | Read | |||
| AI | 390 | Custom Type String 12 | Read | |||
| AI | 391 | Custom Type String 13 | Read | |||
| AI | 392 | Master Boiler Commanded Pump Running Bits 1 | Read | |||
| AI | 393 | Master Boiler Commanded Pump Running Bits 2 | Read | |||
| AI | 394 | Master Boiler Commanded Pump Running Bits 3 | Read | |||
| AI | 395 | Master Boiler Commanded Pump Running Bits 4 | Read | |||
| AI | 396 | Master Boiler Commanded Pump Running Bits 5 | Read | |||
| AI | 397 | Master Boiler Commanded Pump Running Bits 6 | Read | |||
| AI | 398 | Master Boiler Commanded Pump Running Bits 7 | Read | |||
| AI | 399 | Master Boiler Commanded Modulation Rates 1 | Read | |||
| AI | 400 | Master Boiler Commanded Modulation Rates 2 | Read | |||
| AI | 401 | Master Boiler Commanded Modulation Rates 3 | Read | |||
| AI | 402 | Master Boiler Commanded Modulation Rates 4 | Read | |||
| AI | 403 | Master Boiler Commanded Modulation Rates 5 | Read | |||
| AI | 404 | Master Boiler Commanded Modulation Rates 6 | Read | |||
| AI | 405 | Master Boiler Commanded Modulation Rates 7 | Read | |||
| AI | 406 | Master Boiler Net1 or Net2 | Read | |||
| AI | 407 | Master Boiler Max Boiler Temp | Read | |||
| AI | 408 | Master Boiler Boiler On Diff | Read | |||
| AI | 409 | Master Boiler Boiler Off Diff | Read | |||
| AI | 410 | Master Boiler Pre Pump Time | Read | |||
| AI | 411 | Master Boiler Post Pump Time | Read | |||
| AI | 412 | Master Boiler Number of Boilers on Network | Read | |||
| MI | 413 | Master Boiler Supply Temp | Read | |||
| MI | 414 | Master Boiler Return Temp | Read | |||
| AI | 415 | Master Boiler Outdoor Temp | Read | |||
| AI | 416 | Master Boiler System Types | Read | |||
| AI | 417 | Shadow 2 Input 1 Priority | Read | |||
| AI | 418 | Shadow 2 Input 1 System Type | Read | |||
| AI | 419 | Shadow 2 Input 2 Priority | Read | |||
| AI | 420 | Shadow 2 Input 2 System Type | Read | |||
| AI | 421 | Shadow 2 Input 3 Priority | Read | |||
| AI | 422 | Shadow 2 Input 3 System Type | Read | |||
| AI | 423 | Shadow 2 Input Status | Read | |||
| MI | 424 | Shadow 2 Boiler Status | Read | |||
| AI | 425 | Shadow 2 Supply Temp (local) | Read | |||
| AI | 426 | Shadow 2 Return Temp (local) | Read | |||
| AI | 427 | Shadow 2 Outdoor Temp (local) | Read | |||
| AI | 428 | Shadow 2 Boiler 1 Out Temp | Read | |||
| AI | 429 | Shadow 2 Relay Output Status | Read | |||
| AI | 430 | Shadow 2 Model Number | Read | |||
| AI | 431 | Shadow 2 Burner Hours | Read | |||
| AI | 432 | Shadow 2 Min Rate | Read | |||
| AI | 433 | Shadow 2 Max Rate | Read | |||
| AI | 434 | Shadow 2 Modulation Rate | Read | |||
| AI | 435 | Shadow 2 Boiler Status 3 and Available Status | Read | |||
| AI | 436 | Shadow 3 Input 1 Priority | Read | |||
| AI | 437 | Shadow 3 Input 1 System Type | Read | |||
| AI | 438 | Shadow 3 Input 2 Priority | Read | |||
| AI | 439 | Shadow 3 Input 2 System Type | Read | |||
| AI | 440 | Shadow 3 Input 3 Priority | Read | |||
| AI | 441 | Shadow 3 Input 3 System Type | Read | |||
| AI | 442 | Shadow 3 Input Status | Read | |||
| MI | 443 | Shadow 3 Boiler Status | Read | |||
| AI | 444 | Shadow 3 Supply Temp (local) | Read | |||
| AI | 445 | Shadow 3 Return Temp (local) | Read | |||
| AI | 446 | Shadow 3 Outdoor Temp (local) | Read | |||
| AI | 447 | Shadow 3 Boiler 1 Out Temp | Read | |||
| AI | 448 | Shadow 3 Relay Output Status | Read | |||
| AI | 449 | Shadow 3 Model Number | Read | |||
| AI | 450 | Shadow 3 Burner Hours | Read | |||
| AI | 451 | Shadow 3 Min Rate | Read | |||
| AI | 452 | Shadow 3 Max Rate | Read | |||
| AI | 453 | Shadow 3 Modulation Rate | Read | |||
| AI | 454 | Shadow 3 Boiler Status 3 and Available Status | Read | |||
| AI | 455 | Shadow 4 Input 1 Priority | Read | |||
| AI | 456 | Shadow 4 Input 1 System Type | Read | |||
| AI | 457 | Shadow 4 Input 2 Priority | Read | |||
| AI | 458 | Shadow 4 Input 2 System Type | Read | |||
| AI | 459 | Shadow 4 Input 3 Priority | Read | |||
| AI | 460 | Shadow 4 Input 3 System Type | Read | |||
| AI | 461 | Shadow 4 Input Status | Read | |||
| MI | 462 | Shadow 4 Boiler Status | Read | |||
| AI | 463 | Shadow 4 Supply Temp (local) | Read | |||
| AI | 464 | Shadow 4 Return Temp (local) | Read | |||
| AI | 465 | Shadow 4 Outdoor Temp (local) | Read | |||
| AI | 466 | Shadow 4 Boiler 1 Out Temp | Read | |||
| AI | 467 | Shadow 4 Relay Output Status | Read | |||
| AI | 468 | Shadow 4 Model Number | Read | |||
| AI | 469 | Shadow 4 Burner Hours | Read | |||
| AI | 470 | Shadow 4 Min Rate | Read | |||
| AI | 471 | Shadow 4 Max Rate | Read | |||
| AI | 472 | Shadow 4 Modulation Rate | Read | |||
| AI | 473 | Shadow 4 Boiler Status 3 and Available Status | Read | |||
| AI | 474 | Shadow 5 Input 1 Priority | Read | |||
| AI | 475 | Shadow 5 Input 1 System Type | Read | |||
| AI | 476 | Shadow 5 Input 2 Priority | Read | |||
| AI | 477 | Shadow 5 Input 2 System Type | Read | |||
| AI | 478 | Shadow 5 Input 3 Priority | Read | |||
| AI | 479 | Shadow 5 Input 3 System Type | Read | |||
| AI | 480 | Shadow 5 Input Status | Read | |||
| MI | 481 | Shadow 5 Boiler Status | Read | |||
| AI | 482 | Shadow 5 Supply Temp (local) | Read | |||
| AI | 483 | Shadow 5 Return Temp (local) | Read | |||
| AI | 484 | Shadow 5 Outdoor Temp (local) | Read | |||
| AI | 485 | Shadow 5 Boiler 1 Out Temp | Read | |||
| AI | 486 | Shadow 5 Relay Output Status | Read | |||
| AI | 487 | Shadow 5 Model Number | Read | |||
| AI | 488 | Shadow 5 Burner Hours | Read | |||
| AI | 489 | Shadow 5 Min Rate | Read | |||
| AI | 490 | Shadow 5 Max Rate | Read | |||
| AI | 491 | Shadow 5 Modulation Rate | Read | |||
| AI | 492 | Shadow 5 Boiler Status 3 and Available Status | Read | |||
| AI | 493 | Shadow 6 Input 1 Priority | Read | |||
| AI | 494 | Shadow 6 Input 1 System Type | Read | |||
| AI | 495 | Shadow 6 Input 2 Priority | Read | |||
| AI | 496 | Shadow 6 Input 2 System Type | Read | |||
| AI | 497 | Shadow 6 Input 3 Priority | Read | |||
| AI | 498 | Shadow 6 Input 3 System Type | Read | |||
| AI | 499 | Shadow 6 Input Status | Read | |||
| MI | 500 | Shadow 6 Boiler Status | Read | |||
| AI | 501 | Shadow 6 Supply Temp (local) | Read | |||
| AI | 502 | Shadow 6 Return Temp (local) | Read | |||
| AI | 503 | Shadow 6 Outdoor Temp (local) | Read | |||
| AI | 504 | Shadow 6 Boiler 1 Out Temp | Read | |||
| AI | 505 | Shadow 6 Relay Output Status | Read | |||
| AI | 506 | Shadow 6 Model Number | Read | |||
| AI | 507 | Shadow 6 Burner Hours | Read | |||
| AI | 508 | Shadow 6 Min Rate | Read | |||
| AI | 509 | Shadow 6 Max Rate | Read | |||
| AI | 510 | Shadow 6 Modulation Rate | Read | |||
| AI | 511 | Shadow 6 Boiler Status 3 and Available Status | Read | |||
| AI | 512 | Shadow 7 Input 1 Priority | Read | |||
| AI | 513 | Shadow 7 Input 1 System Type | Read | |||
| AI | 514 | Shadow 7 Input 2 Priority | Read | |||
| AI | 515 | Shadow 7 Input 2 System Type | Read | |||
| AI | 516 | Shadow 7 Input 3 Priority | Read | |||
| AI | 517 | Shadow 7 Input 3 System Type | Read | |||
| AI | 518 | Shadow 7 Input Status | Read | |||
| MI | 519 | Shadow 7 Boiler Status | Read | |||
| AI | 520 | Shadow 7 Supply Temp (local) | Read | |||
| AI | 521 | Shadow 7 Return Temp (local) | Read | |||
| AI | 522 | Shadow 7 Outdoor Temp (local) | Read | |||
| AI | 523 | Shadow 7 Boiler 1 Out Temp | Read | |||
| AI | 524 | Shadow 7 Relay Output Status | Read | |||
| AI | 525 | Shadow 7 Model Number | Read | |||
| AI | 526 | Shadow 7 Burner Hours | Read | |||
| AI | 527 | Shadow 7 Min Rate | Read | |||
| AI | 528 | Shadow 7 Max Rate | Read | |||
| AI | 529 | Shadow 7 Modulation Rate | Read | |||
| AI | 530 | Shadow 7 Boiler Status 3 and Available Status | Read | |||
| AI | 531 | Shadow 8 Input 1 Priority | Read | |||
| AI | 532 | Shadow 8 Input 1 System Type | Read | |||
| AI | 533 | Shadow 8 Input 2 Priority | Read | |||
| AI | 534 | Shadow 8 Input 2 System Type | Read | |||
| AI | 535 | Shadow 8 Input 3 Priority | Read | |||
| AI | 536 | Shadow 8 Input 3 System Type | Read | |||
| AI | 537 | Shadow 8 Input Status | Read | |||
| MI | 538 | Shadow 8 Boiler Status | Read | |||
| AI | 539 | Shadow 8 Supply Temp (local) | Read | |||
| AI | 540 | Shadow 8 Return Temp (local) | Read | |||
| AI | 541 | Shadow 8 Outdoor Temp (local) | Read | |||
| AI | 542 | Shadow 8 Boiler 1 Out Temp | Read | |||
| AI | 543 | Shadow 8 Relay Output Status | Read | |||
| AI | 544 | Shadow 8 Model Number | Read | |||
| AI | 545 | Shadow 8 Burner Hours | Read | |||
| AI | 546 | Shadow 8 Min Rate | Read | |||
| AI | 547 | Shadow 8 Max Rate | Read | |||
| AI | 548 | Shadow 8 Modulation Rate | Read | |||
| AI | 549 | Shadow 8 Boiler Status 3 and Available Status | Read | |||
| AI | 550 | Custom Type String 2 1 | Read | |||
| AI | 551 | Custom Type String 2 2 | Read | |||
| AI | 552 | Custom Type String 2 3 | Read | |||
| AI | 553 | Custom Type String 2 4 | Read | |||
| AI | 554 | Custom Type String 2 5 | Read | |||
| AI | 555 | Custom Type String 2 6 | Read | |||
| AI | 556 | Custom Type String 2 7 | Read | |||
| AI | 557 | Custom Type String 2 8 | Read | |||
| AI | 558 | Custom Type String 2 9 | Read | |||
| AI | 559 | Custom Type String 2 10 | Read | |||
| AI | 560 | Custom Type String 2 11 | Read | |||
| AI | 561 | Custom Type String 2 12 | Read | |||
| AI | 562 | Custom Type String 2 13 | Read | |||
| AI | 563 | Custom Type String 3 1 | Read | |||
| AI | 564 | Custom Type String 3 2 | Read | |||
| AI | 565 | Custom Type String 3 3 | Read | |||
| AI | 566 | Custom Type String 3 4 | Read | |||
| AI | 567 | Custom Type String 3 5 | Read | |||
| AI | 568 | Custom Type String 3 6 | Read | |||
| AI | 569 | Custom Type String 3 7 | Read | |||
| AI | 570 | Custom Type String 3 8 | Read | |||
| AI | 571 | Custom Type String 3 9 | Read | |||
| AI | 572 | Custom Type String 3 10 | Read | |||
| AI | 573 | Custom Type String 3 11 | Read | |||
| AI | 574 | Custom Type String 3 12 | Read | |||
| AI | 575 | Custom Type String 3 13 | Read | |||
| AI | 576 | Custom Type String 4 1 | Read | |||
| AI | 577 | Custom Type String 4 2 | Read | |||
| AI | 578 | Custom Type String 4 3 | Read | |||
| AI | 579 | Custom Type String 4 4 | Read | |||
| AI | 580 | Custom Type String 4 5 | Read | |||
| AI | 581 | Custom Type String 4 6 | Read | |||
| AI | 582 | Custom Type String 4 7 | Read | |||
| AI | 583 | Custom Type String 4 8 | Read | |||
| AI | 584 | Custom Type String 4 9 | Read | |||
| AI | 585 | Custom Type String 4 10 | Read | |||
| AI | 586 | Custom Type String 4 11 | Read | |||
| AI | 587 | Custom Type String 4 12 | Read | |||
| AI | 588 | Custom Type String 4 13 | Read | |||
| AV | 589 | Net Priority 1 Add Boiler Delay | Write | |||
| AV | 590 | Net Priority 2 Add Boiler Delay | Write | |||
| AI | 591 | P of the PI | Read | |||
| AI | 592 | I of the PI | Read | |||
| AI | 593 | PI Output t-1 | Read | |||
| BImin | 594 | Relay Output Gas Valve ON | Gas valve relay output on | Read | ||
| BI | 595 | Relay Output Circulator 1 ON | On/off value | Read | ||
| BI | 596 | Relay Output Circulator 2 ON | On/off value | Read | ||
| BI | 597 | Relay Output Circulator 3 ON | On/off value | Read | ||
| BI | 598 | Relay Output Additional Heat Demand ON | On/off value | Read | ||
| BI | 599 | Relay Output Boiler Circulator ON | On/off value | Read | ||
| BI | 600 | Boiler Status 2 Flue Temperature Warning | On/off value | Read | ||
| BI | 601 | Boiler Status 2 Modulation Sensor | On/off value | Read | ||
| BI | 602 | Boiler Status 2 Freeze Protection | On/off value | Read | ||
| BI | 603 | Boiler Status 2 Warm Weather Shutdown | On/off value | Read | ||
| BI | 604 | Exercise Circulator 1 ON | On/off value | Read | ||
| BI | 605 | Exercise Circulator 2 ON | On/off value | Read | ||
| BI | 606 | Exercise Circulator 3 ON | On/off value | Read | ||
| BI | 607 | Exercise Boiler Circulator ON | On/off value | Read | ||
| BI | 608 | Freeze Protect Circulator 1 ON | On/off value | Read | ||
| BI | 609 | Freeze Protect Circulator 2 ON | On/off value | Read | ||
| BI | 610 | Freeze Protect Circulator 3 ON | On/off value | Read | ||
| BI | 611 | Freeze Protect Boiler Circulator ON | On/off value | Read | ||
| AI | 612 | Priority 1 System Type | Read | |||
| AI | 613 | Priority 1 Target Adjustment | Read | |||
| BI | 614 | Priority 1 Run Aux Pump/Output setting | On/off value | Read | ||
| BI | 615 | Priority 1 Run Boiler Pump setting | On/off value | Read | ||
| AI | 616 | Input 1 Priority Boiler | Read | |||
| AI | 617 | Input 1 Aux Pump/Output Type | Read | |||
| BI | 618 | Input 1 Source is set to 0-10V | On/off value | Read | ||
| AI | 619 | Priority 2 System Type | Read | |||
| AI | 620 | Priority 2 Target Adjustment | Read | |||
| BI | 621 | Priority 2 Run Aux Pump/Output setting | On/off value | Read | ||
| BI | 622 | Priority 2 Run Boiler Pump setting | On/off value | Read | ||
| AI | 623 | Priority 3 System Type | Read | |||
| AI | 624 | Priority 3 Target Adjustment | Read | |||
| BI | 625 | Priority 3 Run Aux Pump/Output setting | On/off value | Read | ||
| BI | 626 | Priority 3 Run Boiler Pump setting | On/off value | Read | ||
| BI | 627 | Target was Reduced Flue Temp | On/off value | Read | ||
| BI | 628 | Target was Reduced Boiler In Out | On/off value | Read | ||
| BI | 629 | Modulation was Reduced | On/off value | Read | ||
| BI | 630 | Turn on Additional Heat Contact | On/off value | Read | ||
| BI | 631 | Run Circulator 1 | On/off value | Read | ||
| BI | 632 | Run Circulator 2 | On/off value | Read | ||
| BI | 633 | Run Circulator 3 | On/off value | Read | ||
| BI | 634 | Run Boiler Pump | On/off value | Read | ||
| AI | 635 | P1 activate Contact Setting | Read | |||
| BI | 636 | P1 target ModSensor | On/off value | Read | ||
| BI | 637 | P1 Add Heat Temp Dep | On/off value | Read | ||
| AI | 638 | P1 Add Heat Below SP | Read | |||
| AI | 639 | P2 activate Contact Setting | Read | |||
| BI | 640 | P2 target ModSensor | On/off value | Read | ||
| BI | 641 | P2 Add Heat Temp Dep | On/off value | Read | ||
| AI | 642 | P2 Add Heat Below SP | Read | |||
| AI | 643 | P3 activate Contact Setting | Read | |||
| BI | 644 | P3 target ModSensor | On/off value | Read | ||
| BI | 645 | P3 Add Heat Temp Dep | On/off value | Read | ||
| AI | 646 | P3 Add Heat Below SP | Read | |||
| AI | 647 | Input 2 Priority Boiler | Read | |||
| AI | 648 | Input 2 Aux Pump/Output Type | Read | |||
| BI | 649 | Input 2 Source is set to 0-20V | On/off value | Read | ||
| AI | 650 | Input 3 Priority Boiler | Read | |||
| AI | 651 | Input 3 Aux Pump/Output Type | Read | |||
| BI | 652 | Input 3 Source is set to 0-30V | On/off value | Read | ||
| AI | 653 | Boiler Status | Read | |||
| BI | 654 | Running DHW | On/off value | Read | ||
| BI | 655 | Local Priority 1 Running | On/off value | Read | ||
| BI | 656 | Local Priority 2 Running | On/off value | Read | ||
| BI | 657 | Local Priority 2 Running | On/off value | Read | ||
| BI | 658 | Input 1 active | On/off value | Read | ||
| BI | 659 | Input 2 active | On/off value | Read | ||
| BI | 660 | Input 3 active | On/off value | Read | ||
| BI | 661 | Manual Limit Open | On/off value | Read | ||
| BI | 662 | Auto Limit Open | On/off value | Read | ||
| BI | 663 | Low Water Cutoff Open | On/off value | Read | ||
| BI | 664 | Air P-Switch Open | On/off value | Read | ||
| BI | 665 | Flow Switch Open | On/off value | Read | ||
| BI | 666 | Supply Sensor Error | On/off value | Read | ||
| BI | 667 | Return Sensor Error | On/off value | Read | ||
| BI | 668 | Outdoor Temperature Sensor Error | On/off value | Read | ||
| BI | 669 | Gas Valve Fault 1 | On/off value | Read | ||
| BI | 670 | Gas Valve Fault 2 | On/off value | Read | ||
| BI | 671 | Gas Valve Fault 3 | On/off value | Read | ||
| BI | 672 | Gas Valve Fault 4 | On/off value | Read | ||
| BI | 673 | LKHS1 Hard Flame Fault | On/off value | Read | ||
| BI | 674 | LKHS1 Hard Ignition Fault | On/off value | Read | ||
| BI | 675 | LKHS1 Hard High Temp Limit | On/off value | Read | ||
| BI | 676 | LKHS1 Hard Blower Fault | On/off value | Read | ||
| BI | 677 | LKHS1 Hard Expansion Board Fault Hw Fault | On/off value | Read | ||
| BI | 678 | LKHS1 Hard Air Pressure Switch Fault | On/off value | Read | ||
| BI | 679 | LKHS1 Hard Gas Valve Fault see Sensor Warnings | On/off value | Read | ||
| BI | 680 | LKHS1 Hard Low Water Cutoff | On/off value | Read | ||
| BI | 681 | LKHS1 Hard Limit Open | On/off value | Read | ||
| BI | 682 | LKHS1 Hard Flow Switch Fault Sys Temp High Fault | On/off value | Read | ||
| BI | 683 | LKHS1 Hard Return Water Temp High | On/off value | Read | ||
| BI | 684 | LKHS1 Hard Return above Supply Temp | On/off value | Read | ||
| BI | 685 | LKHS1 Hard Temp Rise Too Quickly | On/off value | Read | ||
| BI | 686 | LKHS1 Hard Supply 58F above Return | On/off value | Read | ||
| BI | 687 | LKHS1 Hard Temperature Sensor | On/off value | Read | ||
| BI | 688 | LKHS1 Hard Flue Temp Too High | On/off value | Read | ||
| BI | 689 | LKHS1 Soft Flame Fault | On/off value | Read | ||
| BI | 690 | LKHS1 Soft Ignition Fault | On/off value | Read | ||
| BI | 691 | LKHS1 Soft High Temp Limit | On/off value | Read | ||
| BI | 692 | LKHS1 Soft Blower Fault | On/off value | Read | ||
| BI | 693 | LKHS1 Soft Expansion Board Fault Hw Fault | On/off value | Read | ||
| BI | 694 | LKHS1 Soft Air Pressure Switch Fault | On/off value | Read | ||
| BI | 695 | LKHS1 Soft Gas Valve Fault see Sensor Warnings | On/off value | Read | ||
| BI | 696 | LKHS1 Soft Low Water Cutoff | On/off value | Read | ||
| BI | 697 | LKHS1 Soft Limit Open | On/off value | Read | ||
| BI | 698 | LKHS1 Soft Flow Switch Fault Sys Temp High Fault | On/off value | Read | ||
| BI | 699 | LKHS1 Soft Return Water Temp High | On/off value | Read | ||
| BI | 700 | LKHS1 Soft Return above Supply Temp | On/off value | Read | ||
| BI | 701 | LKHS1 Soft Temp Rise Too Quickly | On/off value | Read | ||
| BI | 702 | LKHS1 Soft Supply 58F above Return | On/off value | Read | ||
| BI | 703 | LKHS1 Soft Temperature Sensor | On/off value | Read | ||
| BI | 704 | LKHS1 Soft Flue Temp Too High | On/off value | Read | ||
| BI | 705 | LKHS1 In Input 1 active | On/off value | Read | ||
| BI | 706 | LKHS1 In Input 2 active | On/off value | Read | ||
| BI | 707 | LKHS1 In Input 3 active | On/off value | Read | ||
| BI | 708 | LKHS1 In Manual Limit Open | On/off value | Read | ||
| BI | 709 | LKHS1 In Auto Limit Open | On/off value | Read | ||
| BI | 710 | LKHS1 In Low Water Cutoff Open | On/off value | Read | ||
| BI | 711 | LKHS1 In Air P-Switch Open | On/off value | Read | ||
| BI | 712 | LKHS1 In Flow Switch Open | On/off value | Read | ||
| BI | 713 | LKHS1 RO Gas Valve ON | On/off value | Read | ||
| BI | 714 | LKHS1 RO Circulator 1 ON | On/off value | Read | ||
| BI | 715 | LKHS1 RO Circulator 2 ON | On/off value | Read | ||
| BI | 716 | LKHS1 RO Circulator 3 ON | On/off value | Read | ||
| BI | 717 | LKHS1 RO Additional Heat Demand ON | On/off value | Read | ||
| BI | 718 | LKHS1 RO Boiler Circulator ON | On/off value | Read | ||
| BI | 719 | LKHS2 Hard Limit Open | On/off value | Read | ||
| BI | 720 | LKHS2 Hard Flow Switch Fault | On/off value | Read | ||
| BI | 721 | LKHS2 Hard Return Water Temp High | On/off value | Read | ||
| BI | 722 | LKHS2 Hard Return > Supply Temp | On/off value | Read | ||
| BI | 723 | LKHS2 Hard Temp Rise Too Quickly | On/off value | Read | ||
| BI | 724 | LKHS2 Hard Supply 58F > Return | On/off value | Read | ||
| BI | 725 | LKHS2 Hard Temperature Sensor | On/off value | Read | ||
| BI | 726 | LKHS2 Hard Flue Temp Too High | On/off value | Read | ||
| BI | 727 | LKHS2 Hard Flame Fault | On/off value | Read | ||
| BI | 728 | LKHS2 Hard Ignition Fault | On/off value | Read | ||
| BI | 729 | LKHS2 Hard High Temp Limit | On/off value | Read | ||
| BI | 730 | LKHS2 Hard Blower Fault | On/off value | Read | ||
| BI | 731 | LKHS2 Hard Expansion Board Fault | On/off value | Read | ||
| BI | 732 | LKHS2 Hard Air Pressure Switch Fault | On/off value | Read | ||
| BI | 733 | LKHS2 Hard Gas Valve Fault | On/off value | Read | ||
| BI | 734 | LKHS2 Hard Low Water Cutoff | On/off value | Read | ||
| BI | 735 | LKHS2 Soft Limit Open | On/off value | Read | ||
| BI | 736 | LKHS2 Soft Flow Switch Fault | On/off value | Read | ||
| BI | 737 | LKHS2 Soft Return Water Temp High | On/off value | Read | ||
| BI | 738 | LKHS2 Soft Return > Supply Temp | On/off value | Read | ||
| BI | 739 | LKHS2 Soft Temp Rise Too Quickly | On/off value | Read | ||
| BI | 740 | LKHS2 Soft Supply 58F > Return | On/off value | Read | ||
| BI | 741 | LKHS2 Soft Temperature Sensor | On/off value | Read | ||
| BI | 742 | LKHS2 Soft Flue Temp Too High | On/off value | Read | ||
| BI | 743 | LKHS2 Soft Flame Fault | On/off value | Read | ||
| BI | 744 | LKHS2 Soft Ignition Fault | On/off value | Read | ||
| BI | 745 | LKHS2 Soft High Temp Limit | On/off value | Read | ||
| BI | 746 | LKHS2 Soft Blower Fault | On/off value | Read | ||
| BI | 747 | LKHS2 Soft Expansion Board Fault | On/off value | Read | ||
| BI | 748 | LKHS2 Soft Air Pressure Switch Fault | On/off value | Read | ||
| BI | 749 | LKHS2 Soft Gas Valve Fault | On/off value | Read | ||
| BI | 750 | LKHS2 Soft Low Water Cutoff | On/off value | Read | ||
| BI | 751 | LKHS2 In Input 1 active | On/off value | Read | ||
| BI | 752 | LKHS2 In Input 2 active | On/off value | Read | ||
| BI | 753 | LKHS2 In Input 3 active | On/off value | Read | ||
| BI | 754 | LKHS2 In Manual Limit Open | On/off value | Read | ||
| BI | 755 | LKHS2 In Auto Limit Open | On/off value | Read | ||
| BI | 756 | LKHS2 In Low Water Cutoff Open | On/off value | Read | ||
| BI | 757 | LKHS2 In Air P-Switch Open | On/off value | Read | ||
| BI | 758 | LKHS2 In Flow Switch Open | On/off value | Read | ||
| BI | 759 | LKHS2 RO Gas Valve ON | On/off value | Read | ||
| BI | 760 | LKHS2 RO Circulator 1 ON | On/off value | Read | ||
| BI | 761 | LKHS2 RO Circulator 2 ON | On/off value | Read | ||
| BI | 762 | LKHS2 RO Circulator 3 ON | On/off value | Read | ||
| BI | 763 | LKHS2 RO Additional Heat Demand ON | On/off value | Read | ||
| BI | 764 | LKHS2 RO Boiler Circulator ON | On/off value | Read | ||
| BI | 765 | LKHS3 Hard Limit Open | On/off value | Read | ||
| BI | 766 | LKHS3 Hard Flow Switch Fault | On/off value | Read | ||
| BI | 767 | LKHS3 Hard Return Water Temp High | On/off value | Read | ||
| BI | 768 | LKHS3 Hard Return > Supply Temp | On/off value | Read | ||
| BI | 769 | LKHS3 Hard Temp Rise Too Quickly | On/off value | Read | ||
| BI | 770 | LKHS3 Hard Supply 58F > Return | On/off value | Read | ||
| BI | 771 | LKHS3 Hard Temperature Sensor | On/off value | Read | ||
| BI | 772 | LKHS3 Hard Flue Temp Too High | On/off value | Read | ||
| BI | 773 | LKHS3 Hard Flame Fault | On/off value | Read | ||
| BI | 774 | LKHS3 Hard Ignition Fault | On/off value | Read | ||
| BI | 775 | LKHS3 Hard High Temp Limit | On/off value | Read | ||
| BI | 776 | LKHS3 Hard Blower Fault | On/off value | Read | ||
| BI | 777 | LKHS3 Hard Expansion Board Fault | On/off value | Read | ||
| BI | 778 | LKHS3 Hard Air Pressure Switch Fault | On/off value | Read | ||
| BI | 779 | LKHS3 Hard Gas Valve Fault | On/off value | Read | ||
| BI | 780 | LKHS3 Hard Low Water Cutoff | On/off value | Read | ||
| BI | 781 | LKHS3 Soft Limit Open | On/off value | Read | ||
| BI | 782 | LKHS3 Soft Flow Switch Fault | On/off value | Read | ||
| BI | 783 | LKHS3 Soft Return Water Temp High | On/off value | Read | ||
| BI | 784 | LKHS3 Soft Return > Supply Temp | On/off value | Read | ||
| BI | 785 | LKHS3 Soft Temp Rise Too Quickly | On/off value | Read | ||
| BI | 786 | LKHS3 Soft Supply 58F > Return | On/off value | Read | ||
| BI | 787 | LKHS3 Soft Temperature Sensor | On/off value | Read | ||
| BI | 788 | LKHS3 Soft Flue Temp Too High | On/off value | Read | ||
| BI | 789 | LKHS3 Soft Flame Fault | On/off value | Read | ||
| BI | 790 | LKHS3 Soft Ignition Fault | On/off value | Read | ||
| BI | 791 | LKHS3 Soft High Temp Limit | On/off value | Read | ||
| BI | 792 | LKHS3 Soft Blower Fault | On/off value | Read | ||
| BI | 793 | LKHS3 Soft Expansion Board Fault | On/off value | Read | ||
| BI | 794 | LKHS3 Soft Air Pressure Switch Fault | On/off value | Read | ||
| BI | 795 | LKHS3 Soft Gas Valve Fault | On/off value | Read | ||
| BI | 796 | LKHS3 Soft Low Water Cutoff | On/off value | Read | ||
| BI | 797 | LKHS3 In Input 1 active | On/off value | Read | ||
| BI | 798 | LKHS3 In Input 2 active | On/off value | Read | ||
| BI | 799 | LKHS3 In Input 3 active | On/off value | Read | ||
| BI | 800 | LKHS3 In Manual Limit Open | On/off value | Read | ||
| BI | 801 | LKHS3 In Auto Limit Open | On/off value | Read | ||
| BI | 802 | LKHS3 In Low Water Cutoff Open | On/off value | Read | ||
| BI | 803 | LKHS3 In Air P-Switch Open | On/off value | Read | ||
| BI | 804 | LKHS3 In Flow Switch Open | On/off value | Read | ||
| BI | 805 | LKHS3 RO Gas Valve ON | On/off value | Read | ||
| BI | 806 | LKHS3 RO Circulator 1 ON | On/off value | Read | ||
| BI | 807 | LKHS3 RO Circulator 2 ON | On/off value | Read | ||
| BI | 808 | LKHS3 RO Circulator 3 ON | On/off value | Read | ||
| BI | 809 | LKHS3 RO Additional Heat Demand ON | On/off value | Read | ||
| BI | 810 | LKHS3 RO Boiler Circulator ON | On/off value | Read | ||
| BI | 811 | LKHS1 Flue Temperature Warning | On/off value | Read | ||
| BI | 812 | LKHS1 Modulation Sensor | On/off value | Read | ||
| BI | 813 | LKHS1 Freeze Protection | On/off value | Read | ||
| BI | 814 | LKHS1 Warm Weather Shutdown | On/off value | Read | ||
| BI | 815 | LKHS2 Flue Temperature Warning | On/off value | Read | ||
| BI | 816 | LKHS2 Modulation Sensor | On/off value | Read | ||
| BI | 817 | LKHS2 Freeze Protection | On/off value | Read | ||
| BI | 818 | LKHS2 Warm Weather Shutdown | On/off value | Read | ||
| BI | 819 | LKHS3 Flue Temperature Warning | On/off value | Read | ||
| BI | 820 | LKHS3 Modulation Sensor | On/off value | Read | ||
| BI | 821 | LKHS3 Freeze Protection | On/off value | Read | ||
| BI | 822 | LKHS3 Warm Weather Shutdown | On/off value | Read | ||
| AI | 823 | Shad2 In1 Priority Boiler | Read | |||
| AI | 824 | Shad2 In1 Aux Pump/Output Type | Read | |||
| BI | 825 | Shad2 In1 Source is set to 0-10V | On/off value | Read | ||
| AI | 826 | Shad2 In2 Priority Boiler | Read | |||
| AI | 827 | Shad2 In2 Aux Pump/Output Type | Read | |||
| BI | 828 | Shad2 In2 Source is set to 0-10V | On/off value | Read | ||
| AI | 829 | Shad2 In3 Priority Boiler | Read | |||
| AI | 830 | Shad2 In3 Aux Pump/Output Type | Read | |||
| BI | 831 | Shad2 In3 Source is set to 0-10V | On/off value | Read |
No points match these filters.
Object ID lookup: Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF point IDs by name
AI1Pad00HBMI2Boiler ModelAI3U1 Sw VersionAI4U2 Sw VersionAI5NET Volts OutputAI6Relay Output StatusAI7Boiler Out 1 TemperatureAI8Mod Return TempAI9MHEOTmp F1AI10Active Target Supply TemperatureAI11Mod TempAI12Fire Rate SelectionBI13Boiler Status 2AI14HLOResetAI15Fan SpeedAI16Flame Sense ValueAI17AvgFlameLAI18Slave Fire Rate UnconvertedAI19Outdoor TempAV20System Time (Minutes)AV21System Time (Hours)AV22System Date (Day)AV23System Date (Month)AV24System Date (Year)AI250-10V OutputAI260-10V OutputAI270-10V InputAI28Max Blower RPMAI29Flame BoostAV30Circulator Exercise/Freeze ProtectionAI31Input 2 Hours RAM MSBAI32Priority 1 SettingsAV33Priority 1 Supply Max TargetAV34Priority 1 Supply Min TargetAV35Priority 1 OD Reset/Volts MaxAV36Priority 1 OD Reset/Volts MinAV37Priority 1 Max Boiler TemperatureAV38Priority 3 Max Rate VoltsAI39OAT ConfigurationAI40Active Network Priority's Boiler Off DiffAV41Priority 1 System On DiffAV42Priority 1 Max On Time SettingAV43Priority 1 Post Pump TimeAV44Priority 1 Boost TimeAI45Input 1 PriorityAV46Priority 1 Pre Pump TimeAI47Min Blower RPMAV48Priority 1 Boiler On DiffAV49Priority 1 Boiler Off DiffAV50Priority 1 Max RateAV51Priority 1 Min RateAI52Active Network Priority's Max BLR TempAI53Active Network Priority's Boiler On DiffAI54Input 2 Hours RAM LSBAI55Priority 2 SettingAV56Priority 2 Supply Max TargetAV57Priority 2 Supply Min TargetAV58Priority 2 OD Reset/Volts MaxAV59Priority 2 OD Reset/Volts MinAI60Active Network Prepump TimeAI61Ignition Counter RAMAV62Priority 2 Min On Time SettingAV63Priority 2 Max On Time SettingAV64Priority 2 Post Pump TimeAV65Priority 2 Boost TimeAI66Boiler Control TypeAV67Priority 1 Pre Pump TimeAV68Priority 2 System Off DiffAI69Network Minimum On TimeAV70Priority 2 Boiler On DiffAV71Priority 2 Boiler Off DiffAV72Priority 2 Max RateAV73Priority 2 Min RateAI74Network Return TempAI75Local Return TempAI76Active Network Priority Post Pump TimeAI77Single Boiler: Pri 3 Setting/Master Boiler: Network 1 Pri SettingAV78Priority 3/Net1 Supply Max TargetAV79Priority 3/Net1 Supply Min TargetAV80Priority 3/Net1 OD Reset/Volts MaxAV81Priority 3/Net1 OD Reset/Volts MinAI82Network Max On TimeAV83Priority 3/Net1 System On DiffAV84Priority 3 Min On Time SettingAV85Priority 3/Net1 System Off DiffAV86Priority 3/Net1 Post Pump TimeAV87Priority 3/Net1 Boost TimeAV88Priority 2 Max Boiler TemperatureAV89Priority 3/Net1 Pre Pump TimeAI90Boiler Status 3AI91Network Modulation RateAV92Priority 3/Net1 Boiler On DiffAV93Priority 3/Net1 Boiler Off DiffAV94Priority 3 Max Rate (for single)AV95Priority 3 Min Rate (for single)AV96P3 Max Boiler TempAI97Network Run PumpsAV98High Limit TempAV99WWSD TempAV100P1 More SettingsAV101P1 Min Rate VoltsAV102P2 More SettingsAV103Outdoor Temp CorrectionAV104P3 More SettingsAI105Input 2 Hours LSBAV106P1 System Off DiffAI107Input 2 Hours MSBAV108P2 Min Rate VoltsAI109Boiler Model NumberAV110P3 Min rate VoltsAI111Input 1 Hours MSBAI112Input 1 Hours LSBAI113Input 1 Hours RAM MSBAI114Input 1 Hours RAM LSBAV115P2 System On DiffAV116P1 Response TimeAV117P2 Response TimeAV118P3 Response TimeAI119Network Hours LSBAI120Ignition SpeedAI121Input 2 PriorityAI122Input 3 PriorityAI123Ignition CountsAI124Burner HoursAI125Burner Hours RAMAI126Reset Factory MSBAI127Reset Factory LSBAI128Network Hours MSBMI129Boiler Out 1AI130Network Hours RAM MSBAI131Network Hours RAM LSBMI132Boiler Out 2AI133Heat Xchgr 1AI134Max EEAI135Heat Xchgr 2AI136Available to runMI137Boiler In TemperatureMI138Boiler StatusAI139bHeatXchgrIn2AI140Input StatusMI141Flue Temperature 1AI142Local Supply TempMI143Flue Temperature 2AI144P1 Max Rate VoltsAI145bDHWSensor1MI146Local Outdoor TemperatureAI147bDHWSensor2MI148Network Outdoor TemperatureMI149Network Supply TemperatureAI150Local Supply TemperatureAI151Local Return TemperatureAI152Input 3 Hours MSBAI153Input 3 Hours LSBAI154Bad EEPROM CountAI155Bad Ram CountAI156Default CountAI157Ignition RetriesAI158Lockout History 1 Expansion Board ErrorsAI159Manual Lockout CountAI160Sensor WarningsAI161Auto Lockout CountAI162Lockout History 1 Hard Lockout ErrorsAI163Lockout History 1 Soft Lockout ErrorsAI164Lockout History 1 MinutesAI165Lockout History 1 HoursAI166Lockout History 1 DayAI167Lockout History 1 MonthAI168Lockout History 1 YearAI169Lockout History 1 Boiler ModelAI170Lockout History 1 Input StatusAI171Lockout History 1 Relay Output StatusAI172Lockout History 1 Flame Signal MSBAI173Lockout History 1 Flame Signal LSBAI174Lockout History 1 Outdoor TemperatureAI175Lockout History 1 Flue Temperature 2AI176Lockout History 1 Boiler Out Temp 2AI177Lockout History 1 Boiler In Temp 2AI178bErrSDWAI179Lockout History 1 Flue Temperature 1AI180Lockout History 1 Boiler Out Temp 1AI181Lockout History 1 Heat Exchanger Temp 1AI182Lockout History 1 Supply TemperatureAI183Lockout History 1 Return TemperatureAI184Lockout History 1 Boiler In Temp 1AI185Lockout History 1 0-10V OutputAI186Lockout History 1 Blower Speed (RPM)AI187Lockout History 2 Hard Lockout ErrorsAI188Lockout History 2 Soft Lockout ErrorsAI189Lockout History 2 MinutesAI190Lockout History 2 HoursAI191Lockout History 2 DayAI192Lockout History 2 MonthAI193Lockout History 2 YearAI194Lockout History 2 Boiler ModelAI195Lockout History 2 Input StatusAI196Lockout History 2 Relay Output StatusAI197Lockout History 2 Flame Signal MSBAI198Lockout History 2 Flame Signal LSBAI199Lockout History 2 Outdoor TemperatureAI200Lockout History 2 Flue Temperature 2AI201Lockout History 2 Boiler Out Temp 2AI202Lockout History 2 Boiler In Temp 2AI203bH1ErrSDWAI204Lockout History 2 Flue Temperature 1AI205Lockout History 2 Boiler Out Temp 1AI206Lockout History 2 Heat Exchanger Temp 1AI207Lockout History 2 Supply TemperatureAI208Lockout History 2 Return TemperatureAI209Lockout History 2 Boiler In Temp 1AI210Lockout History 2 0-10V OutputAI211Lockout History 2 Blower Speed (RPM)AI212Lockout History 3 Hard Lockout ErrorsAI213Lockout History 3 Soft Lockout ErrorsAI214Lockout History 3 MinutesAI215Lockout History 3 HoursAI216Lockout History 3 DayAI217Lockout History 3 MonthAI218Lockout History 3 YearAI219Lockout History 3 Boiler ModelAI220Lockout History 3 Input StatusAI221Lockout History 3 Relay Output StatusAI222Lockout History 3 Flame Signal MSBAI223Lockout History 3 Flame Signal LSBAI224Lockout History 3 Outdoor TemperatureAI225Lockout History 3 Flue Temperature 2AI226Lockout History 3 Boiler Out Temp 2AI227Lockout History 3 Boiler In Temp 2AI228bH1ErrSDWAI229Lockout History 3 Flue Temperature 1AI230Lockout History 3 Boiler Out Temp 1AI231Lockout History 3 Heat Exchanger Temp 1AI232Lockout History 3 Supply TemperatureAI233Lockout History 3 Return TemperatureAI234Lockout History 3 Boiler In Temp 1AI235Lockout History 3 0-10V OutputAI236Lockout History 3 Blower Speed (RPM)AI237P2 Max Rate VoltsAI238Clear Error HistoryAI239Installer Name 1AI240Installer Name 2AI241Installer Name 3AI242Installer Name 4AI243Installer Name 5AI244Installer Name 6AI245Installer Name 7AI246Installer Name 8AI247Installer Name 9AI248Installer Name 10AI249Installer Name 11AI250Installer Name 12AI251Installer Name 13AI252Installer Name 14AI253Installer Name 15AI254bPad88LBAI255Installer Phone 1AI256Installer Phone 2AI257Installer Phone 3AI258Installer Phone 4AI259Installer Phone 5AI260Installer Phone 6AI261Last Maintenance Reminder MonthAI262Last Maintenance Reminder DayAI263Last Maintenance Reminder YearAV264Maintenance Reminder IntervalAI265Installation MonthAI266Installation DayAI267Installation YearAI268Last Maintenance Performed MonthAI269Last Maintenance Performed DayAI270Last Maintenance Performed YearAI271Boiler CP Number 1AI272Boiler CP Number 2AI273Boiler CP Number 3AI274Boiler CP Number 4AI275Boiler CP Number 5AI276Boiler CP Number 6AI277Boiler CP Number 7AI278bInstModelNumberAI279bUTTest2AI280bUTTest1AI281bCrntErrFRAI282bH1ErrFRAI283bH2ErrFRAI284bCrntErrExpBrdAI285Lockout History 2 Expansion Board ErrorsAI286Lockout History 3 Expansion Board ErrorsAI287Lockout History 1 Boiler Status 2AI288Lockout History 2 Boiler Status 2AI289Lockout History 3 Boiler Status 2AI290Lockout History 1 10 Volt InputAI291Lockout History 2 10 Volt InputAI292Lockout History 3 10 Volt InputAI293bInput3HoursRAM MSBAI294bInput3HoursRAM LSBAI295Ignore Flame Signal ShutdownAI296P1 ODT SetpointAI297bCommGVCtrlRdAI298Number of Failed IgnitionsAI299bExpBrdRevAI300bPad9FLBAI301bCommGVSts1AI302bCommGVSts2AI303bCGVOutputsAI304bCommGVCtrlAI305P3 ODT SetpointAI306P2 ODT SetpointAI307Boiler Modulation RateAI308Shadow NumberAV309Max Time NetworkAV310Min Time NetworkAV311Max Rate NetworkAV312Min Rate NetworkAV313High Temp LimitAI314Days PassedAV315Base Rate HighAV316Base Rate LowAI317Sequence TypeAV318Boiler Rotation MethodAV319Force Lead RotateAI320User ModeAI321Net1 P Gain AdjustAI322Net1 I Gain AdjustAI323Net1 Maximum Step SizeAI324Net1 Minimum Step SizeAI325Net2 P Gain AdjustAI326Net2 I Gain AdjustAI327Net2 Maximum Step SizeAI328Net2 Minimum Step SizeAI329Modify EquationAV330Net1 Priority System Add Boiler DiffAV331Net1 Priority System Drop Boiler DiffAV332Net1 Priority Mod Delay TimeAV333Net1 Priority Stabilization TimeAV334Net1 Priority Drop Delay TimeAI335Net1 Priority Max Sys RateAI336Net1 Priority Min BoilersAV337Net1 Priority Max On TimeAV338Rotation FrequencyAI339Boiler Order 1AI340Boiler Order 2AI341Boiler Order 3AI342Boiler Order 4AI343Boiler Order 5AI344Boiler Order 6AI345Boiler Order 7AI346Boiler Order 8AV347Net2 Priority System TypeAI348Net2 Priority target Mod SensorAV349Net2 Priority target AdjustAV350Net2 Priority supply MaxAV351Net2 Priority supply MinAV352Net2 Priority Outdoor Reset MaxAV353Net2 Priority Outdoor Reset MinAV354Net2 Priority Volts MaxAV355Net2 Priority Volts MinAV356Net2 Priority Boost TimeAV357Net2 Priority System Off DifferentialAV358Net2 Priority System On DifferentialAV359Net2 Priority System Add Boiler DifferentialAV360Net2 Prioirty System Drop Boiler DiffAV361Net2 Priority Mod Delay TimeAV362Net2 Priority Stabilization TimeAV363Net2 Priority Drop Delay TimeAV364Net2 Priority Max Boiler TempAV365Net2 Priority Boiler On DiffAV366Net2 Priority Boiler Off DiffAI367Net2 Priority Max On TimeAV368Net2 Priority Min On TimeAI369Net2 Priority Run Boiler PumpAI370Net2 Prioirity Run Sys Pump Aux TypeAV371Net2 Priority Pre Pump TimeAV372Net2 Priority Post Pump TimeAV373Net2 Priority Max RateAV374Net2 Priority Min RateAV375Net2 Priority Max Sys RateAI376Net2 Priority Min BoilersAV377Net2 Priority Activate Contact SettingAV378Net2 Priority Response TimeAI379Custom Type String 1AI380Custom Type String 2AI381Custom Type String 3AI382Custom Type String 4AI383Custom Type String 5AI384Custom Type String 6AI385Custom Type String 7AI386Custom Type String 8AI387Custom Type String 9AI388Custom Type String 10AI389Custom Type String 11AI390Custom Type String 12AI391Custom Type String 13AI392Master Boiler Commanded Pump Running Bits 1AI393Master Boiler Commanded Pump Running Bits 2AI394Master Boiler Commanded Pump Running Bits 3AI395Master Boiler Commanded Pump Running Bits 4AI396Master Boiler Commanded Pump Running Bits 5AI397Master Boiler Commanded Pump Running Bits 6AI398Master Boiler Commanded Pump Running Bits 7AI399Master Boiler Commanded Modulation Rates 1AI400Master Boiler Commanded Modulation Rates 2AI401Master Boiler Commanded Modulation Rates 3AI402Master Boiler Commanded Modulation Rates 4AI403Master Boiler Commanded Modulation Rates 5AI404Master Boiler Commanded Modulation Rates 6AI405Master Boiler Commanded Modulation Rates 7AI406Master Boiler Net1 or Net2AI407Master Boiler Max Boiler TempAI408Master Boiler Boiler On DiffAI409Master Boiler Boiler Off DiffAI410Master Boiler Pre Pump TimeAI411Master Boiler Post Pump TimeAI412Master Boiler Number of Boilers on NetworkMI413Master Boiler Supply TempMI414Master Boiler Return TempAI415Master Boiler Outdoor TempAI416Master Boiler System TypesAI417Shadow 2 Input 1 PriorityAI418Shadow 2 Input 1 System TypeAI419Shadow 2 Input 2 PriorityAI420Shadow 2 Input 2 System TypeAI421Shadow 2 Input 3 PriorityAI422Shadow 2 Input 3 System TypeAI423Shadow 2 Input StatusMI424Shadow 2 Boiler StatusAI425Shadow 2 Supply Temp (local)AI426Shadow 2 Return Temp (local)AI427Shadow 2 Outdoor Temp (local)AI428Shadow 2 Boiler 1 Out TempAI429Shadow 2 Relay Output StatusAI430Shadow 2 Model NumberAI431Shadow 2 Burner HoursAI432Shadow 2 Min RateAI433Shadow 2 Max RateAI434Shadow 2 Modulation RateAI435Shadow 2 Boiler Status 3 and Available StatusAI436Shadow 3 Input 1 PriorityAI437Shadow 3 Input 1 System TypeAI438Shadow 3 Input 2 PriorityAI439Shadow 3 Input 2 System TypeAI440Shadow 3 Input 3 PriorityAI441Shadow 3 Input 3 System TypeAI442Shadow 3 Input StatusMI443Shadow 3 Boiler StatusAI444Shadow 3 Supply Temp (local)AI445Shadow 3 Return Temp (local)AI446Shadow 3 Outdoor Temp (local)AI447Shadow 3 Boiler 1 Out TempAI448Shadow 3 Relay Output StatusAI449Shadow 3 Model NumberAI450Shadow 3 Burner HoursAI451Shadow 3 Min RateAI452Shadow 3 Max RateAI453Shadow 3 Modulation RateAI454Shadow 3 Boiler Status 3 and Available StatusAI455Shadow 4 Input 1 PriorityAI456Shadow 4 Input 1 System TypeAI457Shadow 4 Input 2 PriorityAI458Shadow 4 Input 2 System TypeAI459Shadow 4 Input 3 PriorityAI460Shadow 4 Input 3 System TypeAI461Shadow 4 Input StatusMI462Shadow 4 Boiler StatusAI463Shadow 4 Supply Temp (local)AI464Shadow 4 Return Temp (local)AI465Shadow 4 Outdoor Temp (local)AI466Shadow 4 Boiler 1 Out TempAI467Shadow 4 Relay Output StatusAI468Shadow 4 Model NumberAI469Shadow 4 Burner HoursAI470Shadow 4 Min RateAI471Shadow 4 Max RateAI472Shadow 4 Modulation RateAI473Shadow 4 Boiler Status 3 and Available StatusAI474Shadow 5 Input 1 PriorityAI475Shadow 5 Input 1 System TypeAI476Shadow 5 Input 2 PriorityAI477Shadow 5 Input 2 System TypeAI478Shadow 5 Input 3 PriorityAI479Shadow 5 Input 3 System TypeAI480Shadow 5 Input StatusMI481Shadow 5 Boiler StatusAI482Shadow 5 Supply Temp (local)AI483Shadow 5 Return Temp (local)AI484Shadow 5 Outdoor Temp (local)AI485Shadow 5 Boiler 1 Out TempAI486Shadow 5 Relay Output StatusAI487Shadow 5 Model NumberAI488Shadow 5 Burner HoursAI489Shadow 5 Min RateAI490Shadow 5 Max RateAI491Shadow 5 Modulation RateAI492Shadow 5 Boiler Status 3 and Available StatusAI493Shadow 6 Input 1 PriorityAI494Shadow 6 Input 1 System TypeAI495Shadow 6 Input 2 PriorityAI496Shadow 6 Input 2 System TypeAI497Shadow 6 Input 3 PriorityAI498Shadow 6 Input 3 System TypeAI499Shadow 6 Input StatusMI500Shadow 6 Boiler StatusAI501Shadow 6 Supply Temp (local)AI502Shadow 6 Return Temp (local)AI503Shadow 6 Outdoor Temp (local)AI504Shadow 6 Boiler 1 Out TempAI505Shadow 6 Relay Output StatusAI506Shadow 6 Model NumberAI507Shadow 6 Burner HoursAI508Shadow 6 Min RateAI509Shadow 6 Max RateAI510Shadow 6 Modulation RateAI511Shadow 6 Boiler Status 3 and Available StatusAI512Shadow 7 Input 1 PriorityAI513Shadow 7 Input 1 System TypeAI514Shadow 7 Input 2 PriorityAI515Shadow 7 Input 2 System TypeAI516Shadow 7 Input 3 PriorityAI517Shadow 7 Input 3 System TypeAI518Shadow 7 Input StatusMI519Shadow 7 Boiler StatusAI520Shadow 7 Supply Temp (local)AI521Shadow 7 Return Temp (local)AI522Shadow 7 Outdoor Temp (local)AI523Shadow 7 Boiler 1 Out TempAI524Shadow 7 Relay Output StatusAI525Shadow 7 Model NumberAI526Shadow 7 Burner HoursAI527Shadow 7 Min RateAI528Shadow 7 Max RateAI529Shadow 7 Modulation RateAI530Shadow 7 Boiler Status 3 and Available StatusAI531Shadow 8 Input 1 PriorityAI532Shadow 8 Input 1 System TypeAI533Shadow 8 Input 2 PriorityAI534Shadow 8 Input 2 System TypeAI535Shadow 8 Input 3 PriorityAI536Shadow 8 Input 3 System TypeAI537Shadow 8 Input StatusMI538Shadow 8 Boiler StatusAI539Shadow 8 Supply Temp (local)AI540Shadow 8 Return Temp (local)AI541Shadow 8 Outdoor Temp (local)AI542Shadow 8 Boiler 1 Out TempAI543Shadow 8 Relay Output StatusAI544Shadow 8 Model NumberAI545Shadow 8 Burner HoursAI546Shadow 8 Min RateAI547Shadow 8 Max RateAI548Shadow 8 Modulation RateAI549Shadow 8 Boiler Status 3 and Available StatusAI550Custom Type String 2 1AI551Custom Type String 2 2AI552Custom Type String 2 3AI553Custom Type String 2 4AI554Custom Type String 2 5AI555Custom Type String 2 6AI556Custom Type String 2 7AI557Custom Type String 2 8AI558Custom Type String 2 9AI559Custom Type String 2 10AI560Custom Type String 2 11AI561Custom Type String 2 12AI562Custom Type String 2 13AI563Custom Type String 3 1AI564Custom Type String 3 2AI565Custom Type String 3 3AI566Custom Type String 3 4AI567Custom Type String 3 5AI568Custom Type String 3 6AI569Custom Type String 3 7AI570Custom Type String 3 8AI571Custom Type String 3 9AI572Custom Type String 3 10AI573Custom Type String 3 11AI574Custom Type String 3 12AI575Custom Type String 3 13AI576Custom Type String 4 1AI577Custom Type String 4 2AI578Custom Type String 4 3AI579Custom Type String 4 4AI580Custom Type String 4 5AI581Custom Type String 4 6AI582Custom Type String 4 7AI583Custom Type String 4 8AI584Custom Type String 4 9AI585Custom Type String 4 10AI586Custom Type String 4 11AI587Custom Type String 4 12AI588Custom Type String 4 13AV589Net Priority 1 Add Boiler DelayAV590Net Priority 2 Add Boiler DelayAI591P of the PIAI592I of the PIAI593PI Output t-1BI594Relay Output Gas Valve ONBI595Relay Output Circulator 1 ONBI596Relay Output Circulator 2 ONBI597Relay Output Circulator 3 ONBI598Relay Output Additional Heat Demand ONBI599Relay Output Boiler Circulator ONBI600Boiler Status 2 Flue Temperature WarningBI601Boiler Status 2 Modulation SensorBI602Boiler Status 2 Freeze ProtectionBI603Boiler Status 2 Warm Weather ShutdownBI604Exercise Circulator 1 ONBI605Exercise Circulator 2 ONBI606Exercise Circulator 3 ONBI607Exercise Boiler Circulator ONBI608Freeze Protect Circulator 1 ONBI609Freeze Protect Circulator 2 ONBI610Freeze Protect Circulator 3 ONBI611Freeze Protect Boiler Circulator ONAI612Priority 1 System TypeAI613Priority 1 Target AdjustmentBI614Priority 1 Run Aux Pump/Output settingBI615Priority 1 Run Boiler Pump settingAI616Input 1 Priority BoilerAI617Input 1 Aux Pump/Output TypeBI618Input 1 Source is set to 0-10VAI619Priority 2 System TypeAI620Priority 2 Target AdjustmentBI621Priority 2 Run Aux Pump/Output settingBI622Priority 2 Run Boiler Pump settingAI623Priority 3 System TypeAI624Priority 3 Target AdjustmentBI625Priority 3 Run Aux Pump/Output settingBI626Priority 3 Run Boiler Pump settingBI627Target was Reduced Flue TempBI628Target was Reduced Boiler In OutBI629Modulation was ReducedBI630Turn on Additional Heat ContactBI631Run Circulator 1BI632Run Circulator 2BI633Run Circulator 3BI634Run Boiler PumpAI635P1 activate Contact SettingBI636P1 target ModSensorBI637P1 Add Heat Temp DepAI638P1 Add Heat Below SPAI639P2 activate Contact SettingBI640P2 target ModSensorBI641P2 Add Heat Temp DepAI642P2 Add Heat Below SPAI643P3 activate Contact SettingBI644P3 target ModSensorBI645P3 Add Heat Temp DepAI646P3 Add Heat Below SPAI647Input 2 Priority BoilerAI648Input 2 Aux Pump/Output TypeBI649Input 2 Source is set to 0-20VAI650Input 3 Priority BoilerAI651Input 3 Aux Pump/Output TypeBI652Input 3 Source is set to 0-30VAI653Boiler StatusBI654Running DHWBI655Local Priority 1 RunningBI656Local Priority 2 RunningBI657Local Priority 2 RunningBI658Input 1 activeBI659Input 2 activeBI660Input 3 activeBI661Manual Limit OpenBI662Auto Limit OpenBI663Low Water Cutoff OpenBI664Air P-Switch OpenBI665Flow Switch OpenBI666Supply Sensor ErrorBI667Return Sensor ErrorBI668Outdoor Temperature Sensor ErrorBI669Gas Valve Fault 1BI670Gas Valve Fault 2BI671Gas Valve Fault 3BI672Gas Valve Fault 4BI673LKHS1 Hard Flame FaultBI674LKHS1 Hard Ignition FaultBI675LKHS1 Hard High Temp LimitBI676LKHS1 Hard Blower FaultBI677LKHS1 Hard Expansion Board Fault Hw FaultBI678LKHS1 Hard Air Pressure Switch FaultBI679LKHS1 Hard Gas Valve Fault see Sensor WarningsBI680LKHS1 Hard Low Water CutoffBI681LKHS1 Hard Limit OpenBI682LKHS1 Hard Flow Switch Fault Sys Temp High FaultBI683LKHS1 Hard Return Water Temp HighBI684LKHS1 Hard Return above Supply TempBI685LKHS1 Hard Temp Rise Too QuicklyBI686LKHS1 Hard Supply 58F above ReturnBI687LKHS1 Hard Temperature SensorBI688LKHS1 Hard Flue Temp Too HighBI689LKHS1 Soft Flame FaultBI690LKHS1 Soft Ignition FaultBI691LKHS1 Soft High Temp LimitBI692LKHS1 Soft Blower FaultBI693LKHS1 Soft Expansion Board Fault Hw FaultBI694LKHS1 Soft Air Pressure Switch FaultBI695LKHS1 Soft Gas Valve Fault see Sensor WarningsBI696LKHS1 Soft Low Water CutoffBI697LKHS1 Soft Limit OpenBI698LKHS1 Soft Flow Switch Fault Sys Temp High FaultBI699LKHS1 Soft Return Water Temp HighBI700LKHS1 Soft Return above Supply TempBI701LKHS1 Soft Temp Rise Too QuicklyBI702LKHS1 Soft Supply 58F above ReturnBI703LKHS1 Soft Temperature SensorBI704LKHS1 Soft Flue Temp Too HighBI705LKHS1 In Input 1 activeBI706LKHS1 In Input 2 activeBI707LKHS1 In Input 3 activeBI708LKHS1 In Manual Limit OpenBI709LKHS1 In Auto Limit OpenBI710LKHS1 In Low Water Cutoff OpenBI711LKHS1 In Air P-Switch OpenBI712LKHS1 In Flow Switch OpenBI713LKHS1 RO Gas Valve ONBI714LKHS1 RO Circulator 1 ONBI715LKHS1 RO Circulator 2 ONBI716LKHS1 RO Circulator 3 ONBI717LKHS1 RO Additional Heat Demand ONBI718LKHS1 RO Boiler Circulator ONBI719LKHS2 Hard Limit OpenBI720LKHS2 Hard Flow Switch FaultBI721LKHS2 Hard Return Water Temp HighBI722LKHS2 Hard Return > Supply TempBI723LKHS2 Hard Temp Rise Too QuicklyBI724LKHS2 Hard Supply 58F > ReturnBI725LKHS2 Hard Temperature SensorBI726LKHS2 Hard Flue Temp Too HighBI727LKHS2 Hard Flame FaultBI728LKHS2 Hard Ignition FaultBI729LKHS2 Hard High Temp LimitBI730LKHS2 Hard Blower FaultBI731LKHS2 Hard Expansion Board FaultBI732LKHS2 Hard Air Pressure Switch FaultBI733LKHS2 Hard Gas Valve FaultBI734LKHS2 Hard Low Water CutoffBI735LKHS2 Soft Limit OpenBI736LKHS2 Soft Flow Switch FaultBI737LKHS2 Soft Return Water Temp HighBI738LKHS2 Soft Return > Supply TempBI739LKHS2 Soft Temp Rise Too QuicklyBI740LKHS2 Soft Supply 58F > ReturnBI741LKHS2 Soft Temperature SensorBI742LKHS2 Soft Flue Temp Too HighBI743LKHS2 Soft Flame FaultBI744LKHS2 Soft Ignition FaultBI745LKHS2 Soft High Temp LimitBI746LKHS2 Soft Blower FaultBI747LKHS2 Soft Expansion Board FaultBI748LKHS2 Soft Air Pressure Switch FaultBI749LKHS2 Soft Gas Valve FaultBI750LKHS2 Soft Low Water CutoffBI751LKHS2 In Input 1 activeBI752LKHS2 In Input 2 activeBI753LKHS2 In Input 3 activeBI754LKHS2 In Manual Limit OpenBI755LKHS2 In Auto Limit OpenBI756LKHS2 In Low Water Cutoff OpenBI757LKHS2 In Air P-Switch OpenBI758LKHS2 In Flow Switch OpenBI759LKHS2 RO Gas Valve ONBI760LKHS2 RO Circulator 1 ONBI761LKHS2 RO Circulator 2 ONBI762LKHS2 RO Circulator 3 ONBI763LKHS2 RO Additional Heat Demand ONBI764LKHS2 RO Boiler Circulator ONBI765LKHS3 Hard Limit OpenBI766LKHS3 Hard Flow Switch FaultBI767LKHS3 Hard Return Water Temp HighBI768LKHS3 Hard Return > Supply TempBI769LKHS3 Hard Temp Rise Too QuicklyBI770LKHS3 Hard Supply 58F > ReturnBI771LKHS3 Hard Temperature SensorBI772LKHS3 Hard Flue Temp Too HighBI773LKHS3 Hard Flame FaultBI774LKHS3 Hard Ignition FaultBI775LKHS3 Hard High Temp LimitBI776LKHS3 Hard Blower FaultBI777LKHS3 Hard Expansion Board FaultBI778LKHS3 Hard Air Pressure Switch FaultBI779LKHS3 Hard Gas Valve FaultBI780LKHS3 Hard Low Water CutoffBI781LKHS3 Soft Limit OpenBI782LKHS3 Soft Flow Switch FaultBI783LKHS3 Soft Return Water Temp HighBI784LKHS3 Soft Return > Supply TempBI785LKHS3 Soft Temp Rise Too QuicklyBI786LKHS3 Soft Supply 58F > ReturnBI787LKHS3 Soft Temperature SensorBI788LKHS3 Soft Flue Temp Too HighBI789LKHS3 Soft Flame FaultBI790LKHS3 Soft Ignition FaultBI791LKHS3 Soft High Temp LimitBI792LKHS3 Soft Blower FaultBI793LKHS3 Soft Expansion Board FaultBI794LKHS3 Soft Air Pressure Switch FaultBI795LKHS3 Soft Gas Valve FaultBI796LKHS3 Soft Low Water CutoffBI797LKHS3 In Input 1 activeBI798LKHS3 In Input 2 activeBI799LKHS3 In Input 3 activeBI800LKHS3 In Manual Limit OpenBI801LKHS3 In Auto Limit OpenBI802LKHS3 In Low Water Cutoff OpenBI803LKHS3 In Air P-Switch OpenBI804LKHS3 In Flow Switch OpenBI805LKHS3 RO Gas Valve ONBI806LKHS3 RO Circulator 1 ONBI807LKHS3 RO Circulator 2 ONBI808LKHS3 RO Circulator 3 ONBI809LKHS3 RO Additional Heat Demand ONBI810LKHS3 RO Boiler Circulator ONBI811LKHS1 Flue Temperature WarningBI812LKHS1 Modulation SensorBI813LKHS1 Freeze ProtectionBI814LKHS1 Warm Weather ShutdownBI815LKHS2 Flue Temperature WarningBI816LKHS2 Modulation SensorBI817LKHS2 Freeze ProtectionBI818LKHS2 Warm Weather ShutdownBI819LKHS3 Flue Temperature WarningBI820LKHS3 Modulation SensorBI821LKHS3 Freeze ProtectionBI822LKHS3 Warm Weather ShutdownAI823Shad2 In1 Priority BoilerAI824Shad2 In1 Aux Pump/Output TypeBI825Shad2 In1 Source is set to 0-10VAI826Shad2 In2 Priority BoilerAI827Shad2 In2 Aux Pump/Output TypeBI828Shad2 In2 Source is set to 0-10VAI829Shad2 In3 Priority BoilerAI830Shad2 In3 Aux Pump/Output TypeBI831Shad2 In3 Source is set to 0-10V
Integration notes
- This supplement only lists the objects; device instance, MAC address and baud rate are set on the ProtoNode as described in its start-up guide, which is a separate document.
- The same object list is served over BACnet IP or BACnet MS/TP, depending on how the ProtoNode is set up.
- No units or state texts are given. The LonWorks types in the source show which values are temperatures, percentages or hours.
- The supplement has no read/write column. The 111 AVs map to LonWorks input variables, so they are marked writable; every other object is read-only.
- Object IDs run in one sequence (1-831) across AI, AV, BI and MI; each ID is used by one object type only.
- Shadow 2-8 blocks repeat the status of the other boilers in a cascade.
- SlimFit 1000-2000 Series 1 (SOLA) boilers use a different object list.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode
How many BACnet points does the Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode have?
This list has 831 BACnet objects: 487 analog inputs, 111 analog values, 214 binary inputs, 19 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode BACnet points are writable?
111 of the 831 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode BACnet documentation?
The source is ProtoNode FPC-N34 and ProtoNode FPC-N35 Complete Point List Supplement (Weil-McLain) (T17022), revision Document Revision 7.D, January 2019, published free by Weil-McLain at https://www.weil-mclain.com/wp-content/uploads/ProtoNode-Complete-Point-List-Supplement-JAN19_1.pdf.
What are the minimum BACnet points to integrate the Weil-McLain Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode?
Start with MI 138 Boiler Status (Boiler status code); AI 10 Active Target Supply Temperature (Supply temperature the boiler is aiming for); AI 7 Boiler Out 1 Temperature (Boiler outlet water temperature); AI 307 Boiler Modulation Rate (Burner modulation rate); BI 594 Relay Output Gas Valve ON (Gas valve energized (burner firing)); AI 19 Outdoor Temp (Outdoor air temperature); AI 160 Sensor Warnings (Sensor warning code).
How do I check these points on the real Evergreen / SlimFit Series 2 & 3 / SVF - ProtoNode?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Weil-McLain BACnet points lists
- Commercial boiler controller gateway
Weil-McLain SlimFit 1000-2000 - UPC BACnet translator
Weil-McLain SlimFit 1000-2000 boilers (SOLA control) fitted with the UPC BACnet translator kit 383-600-304.
Also known as: SlimFit, SlimFit 1000, SlimFit 2000, UPC BACnet, 383-600-304, SOLA - Boiler controller gateway
Weil-McLain SlimFit 1000-2000 Series 1 (SOLA) - ProtoNode
Weil-McLain SlimFit 1000-2000 Series 1 boilers with the Honeywell SOLA control, read through a ProtoNode FPC-N34 gateway.
Also known as: SlimFit Series 1, SlimFit SOLA, SOLA, ProtoNode FPC-N34, ProtoNode FPC-N35, ProtoNode
Source: ProtoNode FPC-N34 and ProtoNode FPC-N35 Complete Point List Supplement (Weil-McLain) · T17022 · rev. Document Revision 7.D, January 2019. Object names, instances and units are reproduced as published; descriptions are our own.