Air handling unit controller · BACnet points list
Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet points list
Updated 6 November 2026
The built-in IQlogic controller in Swegon GOLD generation E air handlers is a native BACnet IP device (B-AAC profile) with no gateway needed. It publishes over 1,400 objects: fan airflow/pressure readings and setpoints, temperatures and regulation levels, heat-exchanger and coil data, accessory functions (Xzone, SMART Link, AYC, MIRU, COOL DX), one binary input per alarm, plus calendars, a schedule and notification classes for intrinsic alarming. The unit is started, stopped and speed-selected from the BMS through a single multistate value.
This page lists 1452 BACnet objects for the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP — 525 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.
- Manufacturer
- Swegon
- Model
- GOLD generation E (RX/PX/CX/SD) BACnet IP
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 1452 (525 writable)
- Transport
- BACnet IP
- Firmware
- Program version 1.10 or later (driver in PV 1.16)
- Also known as
- GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_BACnet_150316
Reference only, provided as-is: verify against Swegon’s current documentation and the live device before use. Not official Swegon information. Terms of use.
BMS integration notes: Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP
Command the unit with MV-793 Communication operation level (Auto lets the internal time channel run it; other states force stop, low or high speed) and read back MI-592 Operation level plus the low/high speed BIs. Adjust the main temperature setpoints (AV-132 supply, AV-135 extract/room) and airflow or pressure setpoints for low and high speed, and monitor BI-13/14 for A/B alarms with BV-1 to reset. The object summary on page 3 of the source lists these as the key points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 793 | Communication operation level | BMS start/stop and speed command | Write |
| AV 132 | SA temperature set point | Supply air temperature setpoint | Write |
| AV 135 | EA/Room temperature set point | Extract/room temperature setpoint | Write |
| BV 1 | Alarm reset | Resets all active alarms | Write |
| MI 592 | Operation level | Actual operating state and who stopped the unit | Read |
| AI 64 | SA Temperature | Supply air temperature | Read |
| AI 66 | EA Temperature | Extract air temperature | Read |
| AI 73 | Outdoor temperature | Outdoor air temp measured by the unit, °C | Read |
| BI 13 | A-alarm active | Any A-class alarm | Read |
| BI 14 | B-alarm active | Any B-class alarm | Read |
Enable & remote start
MV-793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI-592 shows whether a stop came from communication, the hand terminal, a digital input, the time channel or an alarm.
Sensors & values from the BMS
Room temperature can come from the BMS by enabling BV-167 'External room temp from BMS function' and writing AV-168; outdoor temperature likewise via BV-177 and AV-178. Each has an 'alarm time' AV in minutes (AV-169, AV-179; AV-179 defaults to 5). Xzone has its own BMS room temperature (BV-379, AV-380, AV-381).
Network setup
- BACnet IP only; the device is a B-AAC with intrinsic alarming (notification classes NC-0, 1, 3, 10, 11).
- Swegon also publishes a BACnet PICS and an EDE file for GOLD; device instance and IP settings are not given in this document.
Watch out for
- Calibration BVs (29-56) trigger pressure-sensor zero calibration.
- Setpoints are split by low and high speed (e.g. AV-3/5 SA airflow, AV-19/21 SA duct pressure); write the one for the active speed.
- Many objects only mean something when the related accessory or heat exchanger type (RX/PX/CX/SD) is installed.
- Schedule #1 values are 1-5 (total stop to extended normal stop) with up to 6 time-values a day.
Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Component name | Read | 25=IQlogic | ||
| AI | 4 | SA Air flow | Present supply air flow. | l/s | Read | |
| AI | 5 | SA Air flow regulator | Present supply air flow regulator set point. | l/s | Read | |
| AI | 6 | EA Air flow | Present extract air flow. | l/s | Read | |
| AI | 7 | EA Air flow regulator | Present extract air flow regulator set point. | l/s | Read | |
| AI | 8 | SA Duct pressure | Present supply air duct pressure. | Pa | Read | |
| AI | 9 | SA Duct pressure regulator | Present supply air duct pressure regulator set point. | Pa | Read | |
| AI | 10 | EA Duct pressure | Present extract air duct pressure. | Pa | Read | |
| AI | 11 | EA Duct pressure regulator | Present extract air duct pressure regulator set point. | Pa | Read | |
| AI | 12 | Demand input level | Present input signal for demand regulation. | % | Read | |
| AI | 13 | Demand regulator | Present demand regulator set point. | % | Read | |
| AI | 14 | SA Air flow pressure | Present air flow pressure in the supply air fan inlet. | Pa | Read | |
| AI | 15 | EA Air flow pressure | Present air flow pressure in the extract air fan inlet. | Pa | Read | |
| AI | 23 | SA Pre-filter pressure level | Present supply air pre-filter pressure drop. | Pa | Read | |
| AI | 24 | SA Pre-filter pressure alarm limit | Present supply air pre-filter pressure alarm limit. | Pa | Read | |
| AI | 25 | EA Pre-filter pressure level | Present extract air pre-filter pressure drop. | Pa | Read | |
| AI | 26 | EA Pre-filter pressure alarm limit | Present extract air pre-filter pressure alarm limit. | Pa | Read | |
| AI | 27 | SA AHU filter pressure level | Present supply air filter pressure drop. | Pa | Read | |
| AI | 28 | SA AHU filter pressure alarm limit | Present supply air filter pressure alarm limit. | Pa | Read | |
| AI | 29 | EA AHU filter pressure level | Present extract air filter pressure drop. | Pa | Read | |
| AI | 30 | EA AHU filter pressure alarm limit | Present extract air filter pressure alarm limit. | Pa | Read | |
| AI | 31 | SA End-filter pressure level | Present supply air end-filter pressure drop. | Pa | Read | |
| AI | 32 | SA End-filter pressure alarm limit | Present supply air end-filter pressure alarm limit. | Pa | Read | |
| AI | 37 | SA Fan level | Present fan speed level of the supply air fan. | % | Read | |
| AI | 38 | EA Fan level | Present fan speed level of the extract air fan. | % | Read | |
| AI | 39 | SA Fan speed | Present fan speed level of the supply air fan. | rpm | Read | |
| AI | 40 | EA Fan speed | Present fan speed level of the extract air fan. | rpm | Read | |
| AI | 41 | SA Voltage | Present voltage level of the supply air fan. | V | Read | |
| AI | 42 | EA Voltage | Present voltage level of the extract air fan. | V | Read | |
| AI | 43 | SA Fan current | Present current level of the supply air fans. | A | Read | |
| AI | 44 | EA Fan current | Present current level of the extract air fans. | A | Read | |
| AI | 45 | SA Fan power | Present power level of the supply air fans. | kW | Read | |
| AI | 46 | EA Fan power | Present power consumption level of the extract air fans. | kW | Read | |
| AI | 47 | SA Fan kWh | Total power consumption of the supply air fans. | kWh | Read | |
| AI | 48 | EA Fan kWh | Total power consumption level of the extract air fans. | kWh | Read | |
| AI | 49 | SA Fan MWh | Total power consumption of the supply air fans. | MWh | Read | |
| AI | 50 | EA Fan MWh | Total power consumption level of the extract air fans. | MWh | Read | |
| AI | 51 | SA Fan operation time | Total operation time of the supply air fan presented in days (24h). | days | Read | |
| AI | 52 | EA Fan operation time | Total operation time of the extract air fan presented in days (24h). | days | Read | |
| AI | 55 | SA Fan min air flow | Supply air AHU min air flow | l/s | Read | |
| AI | 56 | EA Fan min air flow | Extract air AHU min air flow | l/s | Read | |
| AI | 57 | SA Fan max air flow | Supply air AHU max air flow | l/s | Read | |
| AI | 58 | EA Fan max air flow | Extract air AHU max air flow | l/s | Read | |
| AI | 63 | SFP | Calculated SFP level. | kW/m3/s | Read | |
| AImin | 64 | SA Temperature | Present supply air temperature. | °C | Read | |
| AI | 65 | SA-D Temperature | Present supply air density temperature. | °C | Read | |
| AImin | 66 | EA Temperature | Present extract air temperature in the unit. | °C | Read | |
| AI | 67 | EA-D Temperature | Present extract air density temperature. | °C | Read | |
| AI | 68 | EA Regulation temperature | Present extract air temperature used for regulation. | °C | Read | |
| AI | 69 | EA Temperature PX/CX | Present extract air temperature in the unit (only AHU type PX/CX). | °C | Read | |
| AI | 70 | EA Temperature SD | Present extract air temperature in the unit (only AHU type SD). | °C | Read | |
| AI | 72 | Outdoor temperature COOL DX | Present outdoor air temperature in the COOL DX unit. | °C | Read | |
| AImin | 73 | Outdoor temperature | Present outdoor air temperature in the unit. | °C | Read | |
| AI | 74 | Outdoor regulation temperature | Present outdoor air temperature used for regulation. | °C | Read | |
| AI | 75 | External outdoor temperature 1 | Present external outdoor temperature of sensor 1. | °C | Read | |
| AI | 76 | External outdoor temperature 2 | Present external outdoor temperature of sensor 2. | °C | Read | |
| AI | 77 | External outdoor temperature 3 | Present external outdoor temperature of sensor 3. | °C | Read | |
| AI | 78 | External outdoor temperature 4 | Present external outdoor temperature of sensor 4. | °C | Read | |
| AI | 79 | External outdoor temperature min/max/average | Present calculated min, max or average | °C | Read | |
| AI | 80 | EA Duct temperature | Present extract air duct air temperature. | °C | Read | |
| AI | 81 | Room temperature 1 | Present room temperature of sensor 1. | °C | Read | |
| AI | 82 | Room temperature 2 | Present room temperature of sensor 2. | °C | Read | |
| AI | 83 | Room temperature 3 | Present room temperature of sensor 3. | °C | Read | |
| AI | 84 | Room temperature 4 | Present room temperature of sensor 4. | °C | Read | |
| AI | 85 | Room temperature min/max/average | Present calculated min, max or average | °C | Read | |
| AI | 87 | SA Temp regulator | Present supply air temperature regulator set point. | °C | Read | |
| AI | 88 | EA Temp regulator | Present extract air temperature regulator set point. | °C | Read | |
| AI | 90 | Cool exchanger regulator level | Present operation level of cool recovery. | % | Read | |
| AI | 91 | Heat exchanger regulator level | Present operation level of heat recovery. | % | Read | |
| AI | 92 | Extra regulation sequence 1 heat regulator level | Present level of extra regulation heat. | % | Read | |
| AI | 93 | Extra regulation sequence 1 heat output level | % | Read | ||
| AI | 94 | Reheat regulator level | Present level of reheat. | % | Read | |
| AI | 95 | Reheat output level | % | Read | ||
| AI | 96 | ReCO2 heat level | Present level of ReCO2 heat. | % | Read | |
| AI | 97 | Down regulation level | Present level of fan down regulation. | % | Read | |
| AI | 98 | Heating boost level | Present level of heating boost. | % | Read | |
| AI | 99 | Extra regulation sequence 1 cool regulator level | Present level of extra regulation cool. | % | Read | |
| AI | 100 | Extra regulation sequence 1 cool output level | Present level of extra regulation cool. | % | Read | |
| AI | 101 | Cool regulator level | Present level of cooling. | % | Read | |
| AI | 102 | Cool output level | Present level of cooling. | % | Read | |
| AI | 103 | ReCO2 cool level | Present level of ReCO2 heat. | % | Read | |
| AI | 104 | Cooling boost level | Present level of cooling boost. | % | Read | |
| AI | 105 | RHX operation level | Present speed level of the rotary heat exchanger. | % | Read | |
| AI | 106 | RHX efficiency | Calculated level of rotary heat exchanger efficiency. | % | Read | |
| AI | 107 | RHX defrost pressure level | Present pressure drop for the rotary heat exchanger. | Pa | Read | |
| AI | 108 | RHX defrost pressure alarm limit | Present pressure drop alarm limit for the | Pa | Read | |
| AI | 109 | RHX carry over control pressure level | Present pressure difference for the rotary heat exchangers purging sector. | Pa | Read | |
| AI | 111 | RHX operation time | Total operation time of the rotary heat exchanger presented in days (24h). | Days | Read | |
| AI | 116 | PX defrost pressure level | PHX-2/3: Present pressure drop for the plate heat exchanger. | Pa | Read | |
| AI | 117 | PHX-3D Bypass output | PHX-1: Present level of plate heat exchanger bypass output. | % | Read | |
| AI | 118 | PHX-3D Bypass input | PHX-1: Present level of plate heat exchanger bypass input. | % | Read | |
| AI | 119 | PHX-3D Bypass temperature 1 | PHX-1: Present bypass temperature sensor 1 in plate heat exchanger. | °C | Read | |
| AI | 120 | PHX-3D Bypass temperature 2 | PHX-1: Present bypass temperature sensor 2 in plate heat exchanger. | °C | Read | |
| AI | 121 | PX exchanger damper 1 output | PHX-2: Present level of plate heat exchanger damper 1 output. | % | Read | |
| AI | 122 | PHX-2 Damper 1 input | Present level of plate heat exchanger damper 1 input. | % | Read | |
| AI | 123 | PX exchanger damper 2 output | PHX-2: Present level of plate heat exchanger damper 2 output. | % | Read | |
| AI | 124 | PHX-2 Damper 2 input | Present level of plate heat exchanger damper 2 input. | % | Read | |
| AI | 125 | PX exchanger bypass output | PHX-2: Present level of plate heat exchanger bypass output. | % | Read | |
| AI | 126 | PX exchanger bypass feedback | PHX-2: Present level of plate heat exchanger bypass input. | % | Read | |
| AI | 127 | CHX Valve output | Present level of coil heat exchanger valve output. | % | Read | |
| AI | 128 | CHX Valve input | Present level of coil heat exchanger valve input. | % | Read | |
| AI | 129 | CHX Return water temperature | Present return water temperature for coil heat exchanger. | °C | Read | |
| AI | 130 | PHX/CHX operation time | Total operation time of the coil heat exchanger presented in days (24h). | Days | Read | |
| AI | 132 | PHX-1D Bypass output | PHX-3: Present level of plate heat exchanger bypass output. | % | Read | |
| AI | 133 | PHX-1D Bypass input | PHX-3: Present level of plate heat exchanger bypass input. | % | Read | |
| AI | 136 | PHX/CHX Humidity level | PHX-1/2: Present level of air-humidity for calculation of bypass/valve | % | Read | |
| AI | 141 | Extra regulation sequence 1 anti frost temp/overheat input | Present extra regulation anti frost temperature for water | °C | Read | |
| AI | 143 | Extra regulation sequence 2 anti frost temp/overheat input | Present extra regulation anti frost temperature for water | °C | Read | |
| AI | 146 | Extra regulation sequence 1 input level | % | Read | ||
| AI | 147 | Extra regulation sequence 1 heat operation time | Total operation time of extra regulation heat presented in days (24h). | Days | Read | |
| AI | 148 | Extra regulation sequence 1 cool operation time | Total operation time of extra regulation cool presented in days (24h). | Days | Read | |
| AI | 149 | Extra regulation sequence 2 input level | % | Read | ||
| AI | 150 | Extra regulation sequence 2 heat operation time | Total operation time of extra regulation heat presented in days (24h). | Days | Read | |
| AI | 151 | Extra regulation sequence 2 cool operation time | Total operation time of extra regulation cool presented in days (24h). | Days | Read | |
| AI | 153 | Re-heat anti frost temp/overheat input | Present anti frost temperature for water | °C | Read | |
| AI | 158 | Re-heat input level | % | Read | ||
| AI | 159 | Re-heat operation time | Total operation time of re-heat presented in days (24h). | Days | Read | |
| AI | 164 | Cool water temperature | Present cool water temperature for water cool coil. | °C | Read | |
| AI | 168 | Cool input level | % | Read | ||
| AI | 169 | Cool operation time | Total operation time of cool presented in days (24h). | Days | Read | |
| AI | 174 | Xzone SA temperature | Present supply air temperature. | °C | Read | |
| AI | 175 | Xzone EA temperature | Present extract air temperature in the unit. | °C | Read | |
| AI | 176 | Xzone EA regulation temperature | Present extract air temperature used for regulation. | °C | Read | |
| AI | 177 | Xzone Room temperature 1 | Present room temperature of sensor 1. | °C | Read | |
| AI | 178 | Xzone Room temperature 2 | Present room temperature of sensor 2. | °C | Read | |
| AI | 179 | Xzone Room temperature 3 | Present room temperature of sensor 3. | °C | Read | |
| AI | 180 | Xzone Room temperature 4 | Present room temperature of sensor 4. | °C | Read | |
| AI | 181 | Xzone Room temperature min/max/average | Present calculated min, max or average | °C | Read | |
| AI | 186 | Xzone SA Temp regulator | Present supply air temperature regulator set point. | °C | Read | |
| AI | 187 | Xzone EA Temp regulator | Present extract air temperature regulator set point. | °C | Read | |
| AI | 190 | Xzone re-heat regulator level | % | Read | ||
| AI | 193 | Xzone cool regulator level | % | Read | ||
| AI | 199 | Xzone heat, anti frost temp/overheat input | Present Xzone heat anti frost temperature for water | °C | Read | |
| AI | 203 | Xzone heat, output level | Present level of Xzone heat output. | % | Read | |
| AI | 204 | Xzone heat, input level | Present Xzone heat input. | % | Read | |
| AI | 205 | Xzone heat, operation time | Total operation time of Xzone heat presented in days (24h). | Days | Read | |
| AI | 210 | Xzone cool, water temperature | °C | Read | ||
| AI | 214 | Xzone cool, output level | Present level of Xzone cool. | % | Read | |
| AI | 215 | Xzone cool, input level | Present Xzone cool valve position. | % | Read | |
| AI | 216 | Xzone cool, operation time | Total operation time of Xzone cool presented in days (24h). | Days | Read | |
| AI | 220 | Pre-heat temperature | Present pre-heat temperature. | °C | Read | |
| AI | 221 | Pre-heat temp regulator set point | Present pre-heat temperature regulator set point. | °C | Read | |
| AI | 222 | Pre-heat temp regulator level | Read | |||
| AI | 225 | Pre-heat anti frost temp/overheat input | Present pre-heat anti frost temperature for water | °C | Read | |
| AI | 228 | Pre-heat output level | Present pre-heat output level. | % | Read | |
| AI | 229 | Pre-heat input level | Present pre-heat input level. | % | Read | |
| AI | 230 | Pre-heat operation time | Total operation time of pre-heat presented in days (24h). | Days | Read | |
| AI | 233 | ReCO2 recirculation damper output | Present output signal to the recirculation damper. | % | Read | |
| AI | 234 | ReCO2 recirculation damper input | Present input signal from the recirculation damper. | % | Read | |
| AI | 235 | ReCO2 outdoor damper output | Present output signal to the outdoor air damper. | % | Read | |
| AI | 236 | ReCO2 outdoor damper input | Present input signal from the outdoor air damper. | % | Read | |
| AI | 237 | ReCO2 outdoor air flow | Present outdoor air flow level. | l/s | Read | |
| AI | 238 | ReCO2 outdoor air flow regulator set point | Present outdoor air flow regulator set point. | l/s | Read | |
| AI | 244 | SA humidity level | Present level of supply air humidity | %RH | Read | |
| AI | 245 | SA humidity temperature | Present temperature inside the supply air humidity sensor. | °C | Read | |
| AI | 246 | SA dew point | Calculated supply air dew point. | °C | Read | |
| AI | 247 | EA humidity level | Present level of extract air humidity. | %RH | Read | |
| AI | 248 | EA humidity temperature | Present temperature inside the extract air humidity sensor. | °C | Read | |
| AI | 249 | EA dew point | Calculated extract air dew point. | °C | Read | |
| AI | 251 | Dehumidifying SA dew point regulator set point | Present supply air dew point regulator point. | °C | Read | |
| AI | 252 | Dehumidifying output level | Present level of the dehumidifying output. | % | Read | |
| AI | 254 | Humidifying SA regulator set point | %RH | Read | ||
| AI | 255 | Humidifying output level | Present level of the dehumidifying output. | % | Read | |
| AI | 266 | VOC level | Present level of VOC | ppm | Read | |
| AI | 271 | COOL DX, unit power size | Read | |||
| AI | 274 | COOL DX, compressor 1 low pressure level | Bar | Read | ||
| AI | 275 | COOL DX, compressor 1 high pressure level | Bar | Read | ||
| AI | 276 | COOL DX, compressor 2 low pressure level | Bar | Read | ||
| AI | 277 | COOL DX, compressor 2 high pressure level | Bar | Read | ||
| AI | 289 | SMART Link, WB outlet water 1 | °C | Read | ||
| AI | 290 | SMART Link, WB outlet water 2 | °C | Read | ||
| AI | 291 | SMART Link, WB outlet water 3 | °C | Read | ||
| AI | 292 | SMART Link, WB outlet water 4 | °C | Read | ||
| AI | 293 | SMART Link, WB outlet water average | °C | Read | ||
| AI | 294 | SMART Link, WB return water | °C | Read | ||
| AI | 297 | SMART Link WB, heated water set point | °C | Read | ||
| AI | 298 | SMART Link WB, chilled water set point | °C | Read | ||
| AI | 299 | SMART Link WB, Min heated water set point | °C | Read | ||
| AI | 300 | SMART Link WB, Max heated water set point | °C | Read | ||
| AI | 301 | SMART Link WB, Min chilled water set point | °C | Read | ||
| AI | 302 | SMART Link WB, Max chilled water set point | °C | Read | ||
| AI | 327 | SMART Link, DX unit 1 power level set point | % | Read | ||
| AI | 328 | SMART Link, DX unit 1 power level | % | Read | ||
| AI | 329 | SMART Link, DX unit 1 operation time | Days | Read | ||
| AI | 338 | SMART Link, DX unit 2 power level set point | % | Read | ||
| AI | 339 | SMART Link, DX unit 2 power level | % | Read | ||
| AI | 340 | SMART Link, DX unit 2 operation time | Days | Read | ||
| AI | 349 | SMART Link, DX unit 3 power level set point | % | Read | ||
| AI | 350 | SMART Link, DX unit 3 power level | % | Read | ||
| AI | 351 | SMART Link, DX unit 3 operation time | Days | Read | ||
| AI | 360 | SMART Link, DX unit 4 power level set point | % | Read | ||
| AI | 361 | SMART Link, DX unit 4 power level | % | Read | ||
| AI | 362 | SMART Link, DX unit 4 operation time | Days | Read | ||
| AI | 374 | AYC Heat, heated water | Present heat temperature. | °C | Read | |
| AI | 375 | AYC Heated water set point | Present heat temperature regulator set point. | °C | Read | |
| AI | 376 | AYC Heat, valve output | Present level of the heat valve output. | % | Read | |
| AI | 377 | AYC Heat, valve input | Present level of the heat valve input. | % | Read | |
| AI | 378 | AYC Heat, operation time | Total operation time of AYC heat presented in days (24h). | Days | Read | |
| AI | 379 | AYC Heated water heat demand | % | Read | ||
| AI | 387 | AYC Cool, chilled water | Present cool temperature. | °C | Read | |
| AI | 388 | AYC Chilled water set point | Present cool temperature regulator set point. | °C | Read | |
| AI | 389 | AYC Cool, valve output | Present cool of the heat valve output. | % | Read | |
| AI | 390 | AYC Cool, valve input | Present cool of the heat valve input. | % | Read | |
| AI | 391 | AYC Cool, operation time | Total operation time of AYC cool presented in days (24h). | Days | Read | |
| AI | 392 | AYC Chilled water cool demand | % | Read | ||
| AI | 400 | MIRU Control 1 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 401 | MIRU Control 1 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 402 | MIRU Control 1 Air flow | Present air flow. | l/s | Read | |
| AI | 403 | MIRU Control 1 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 404 | MIRU Control 1 Pressure | Present duct pressure. | Pa | Read | |
| AI | 405 | MIRU Control 1 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 406 | MIRU Control 1 External temperature | Present external temperature. | °C | Read | |
| AI | 407 | MIRU Control 1 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 408 | MIRU Control 1 Fan level | Present running level of the fan. | % | Read | |
| AI | 409 | MIRU Control 1 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 410 | MIRU Control 1 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 411 | MIRU Control 1 kWh | kWh value. | kWh | Read | |
| AI | 412 | MIRU Control 1 MWh | MWh value. | MWh | Read | |
| AI | 417 | MIRU Control 2 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 418 | MIRU Control 2 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 419 | MIRU Control 2 Air flow | Present air flow. | l/s | Read | |
| AI | 420 | MIRU Control 2 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 421 | MIRU Control 2 Pressure | Present duct pressure. | Pa | Read | |
| AI | 422 | MIRU Control 2 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 423 | MIRU Control 2 External temperature | Present external temperature. | °C | Read | |
| AI | 424 | MIRU Control 2 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 425 | MIRU Control 2 Fan level | Present running level of the fan. | % | Read | |
| AI | 426 | MIRU Control 2 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 427 | MIRU Control 2 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 428 | MIRU Control 2 kWh | kWh value. | kWh | Read | |
| AI | 429 | MIRU Control 2 MWh | MWh value. | MWh | Read | |
| AI | 434 | MIRU Control 3 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 435 | MIRU Control 3 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 436 | MIRU Control 3 Air flow | Present air flow. | l/s | Read | |
| AI | 437 | MIRU Control 3 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 438 | MIRU Control 3 Pressure | Present duct pressure. | Pa | Read | |
| AI | 439 | MIRU Control 3 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 440 | MIRU Control 3 External temperature | Present external temperature. | °C | Read | |
| AI | 441 | MIRU Control 3 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 442 | MIRU Control 3 Fan level | Present running level of the fan. | % | Read | |
| AI | 443 | MIRU Control 3 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 444 | MIRU Control 3 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 445 | MIRU Control 3 kWh | kWh value. | kWh | Read | |
| AI | 446 | MIRU Control 3 MWh | MWh value. | MWh | Read | |
| AI | 451 | MIRU Control 4 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 452 | MIRU Control 4 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 453 | MIRU Control 4 Air flow | Present air flow. | l/s | Read | |
| AI | 454 | MIRU Control 4 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 455 | MIRU Control 4 Pressure | Present duct pressure. | Pa | Read | |
| AI | 456 | MIRU Control 4 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 457 | MIRU Control 4 External temperature | Present external temperature. | °C | Read | |
| AI | 458 | MIRU Control 4 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 459 | MIRU Control 4 Fan level | Present running level of the fan. | % | Read | |
| AI | 460 | MIRU Control 4 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 461 | MIRU Control 4 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 462 | MIRU Control 4 kWh | kWh value. | kWh | Read | |
| AI | 463 | MIRU Control 4 MWh | MWh value. | MWh | Read | |
| AI | 468 | MIRU Control 5 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 469 | MIRU Control 5 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 470 | MIRU Control 5 Air flow | Present air flow. | l/s | Read | |
| AI | 471 | MIRU Control 5 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 472 | MIRU Control 5 Pressure | Present duct pressure. | Pa | Read | |
| AI | 473 | MIRU Control 5 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 474 | MIRU Control 5 External temperature | Present external temperature. | °C | Read | |
| AI | 475 | MIRU Control 5 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 476 | MIRU Control 5 Fan level | Present running level of the fan. | % | Read | |
| AI | 477 | MIRU Control 5 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 478 | MIRU Control 5 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 479 | MIRU Control 5 kWh | kWh value. | kWh | Read | |
| AI | 480 | MIRU Control 5 MWh | MWh value. | MWh | Read | |
| AI | 485 | MIRU Control 6 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 486 | MIRU Control 6 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 487 | MIRU Control 6 Air flow | Present air flow. | l/s | Read | |
| AI | 488 | MIRU Control 6 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 489 | MIRU Control 6 Pressure | Present duct pressure. | Pa | Read | |
| AI | 490 | MIRU Control 6 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 491 | MIRU Control 6 External temperature | Present external temperature. | °C | Read | |
| AI | 492 | MIRU Control 6 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 493 | MIRU Control 6 Fan level | Present running level of the fan. | % | Read | |
| AI | 494 | MIRU Control 6 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 495 | MIRU Control 6 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 496 | MIRU Control 6 kWh | kWh value. | kWh | Read | |
| AI | 497 | MIRU Control 6 MWh | MWh value. | MWh | Read | |
| AI | 502 | MIRU Control 7 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 503 | MIRU Control 7 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 504 | MIRU Control 7 Air flow | Present air flow. | l/s | Read | |
| AI | 505 | MIRU Control 7 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 506 | MIRU Control 7 Pressure | Present duct pressure. | Pa | Read | |
| AI | 507 | MIRU Control 7 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 508 | MIRU Control 7 External temperature | Present external temperature. | °C | Read | |
| AI | 509 | MIRU Control 7 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 510 | MIRU Control 7 Fan level | Present running level of the fan. | % | Read | |
| AI | 511 | MIRU Control 7 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 512 | MIRU Control 7 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 513 | MIRU Control 7 kWh | kWh value. | kWh | Read | |
| AI | 514 | MIRU Control 7 MWh | MWh value. | MWh | Read | |
| AI | 519 | MIRU Control 8 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 520 | MIRU Control 8 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 521 | MIRU Control 8 Air flow | Present air flow. | l/s | Read | |
| AI | 522 | MIRU Control 8 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 523 | MIRU Control 8 Pressure | Present duct pressure. | Pa | Read | |
| AI | 524 | MIRU Control 8 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 525 | MIRU Control 8 External temperature | Present external temperature. | °C | Read | |
| AI | 526 | MIRU Control 8 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 527 | MIRU Control 8 Fan level | Present running level of the fan. | % | Read | |
| AI | 528 | MIRU Control 8 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 529 | MIRU Control 8 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 530 | MIRU Control 8 kWh | kWh value. | kWh | Read | |
| AI | 531 | MIRU Control 8 MWh | MWh value. | MWh | Read | |
| AI | 536 | MIRU Control 9 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 537 | MIRU Control 9 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 538 | MIRU Control 9 Air flow | Present air flow. | l/s | Read | |
| AI | 539 | MIRU Control 9 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 540 | MIRU Control 9 Pressure | Present duct pressure. | Pa | Read | |
| AI | 541 | MIRU Control 9 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 542 | MIRU Control 9 External temperature | Present external temperature. | °C | Read | |
| AI | 543 | MIRU Control 9 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 544 | MIRU Control 9 Fan level | Present running level of the fan. | % | Read | |
| AI | 545 | MIRU Control 9 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 546 | MIRU Control 9 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 547 | MIRU Control 9 kWh | kWh value. | kWh | Read | |
| AI | 548 | MIRU Control 9 MWh | MWh value. | MWh | Read | |
| AI | 553 | MIRU Control 10 Min air flow | Min possible air flow setting | l/s | Read | |
| AI | 554 | MIRU Control 10 Max air flow | Max possible air flow setting | l/s | Read | |
| AI | 555 | MIRU Control 10 Air flow | Present air flow. | l/s | Read | |
| AI | 556 | MIRU Control 10 Air flow set point | Present air flow regulator set point. | l/s | Read | |
| AI | 557 | MIRU Control 10 Pressure | Present duct pressure. | Pa | Read | |
| AI | 558 | MIRU Control 10 Pressure set point | Present duct pressure regulator set point. | Pa | Read | |
| AI | 559 | MIRU Control 10 External temperature | Present external temperature. | °C | Read | |
| AI | 560 | MIRU Control 10 Operation time | Present operation time, present in days (24h). | Days | Read | |
| AI | 561 | MIRU Control 10 Fan level | Present running level of the fan. | % | Read | |
| AI | 562 | MIRU Control 10 Fan power | Present power consumption level of the fan. | W | Read | |
| AI | 563 | MIRU Control 10 SFP | Present SFP value. | kW/m3/s | Read | |
| AI | 564 | MIRU Control 10 kWh | kWh value. | kWh | Read | |
| AI | 565 | MIRU Control 10 MWh | MWh value. | MWh | Read | |
| AI | 570 | IQlogic software version | Present controller software version | Read | ||
| AI | 604 | Triggered alarm #1 | ((Alarm group - 1) x 15) + alarm number in group=Triggered alarm | Read | ||
| AI | 605 | Triggered alarm #2 | Read | |||
| AI | 606 | Triggered alarm #3 | Read | |||
| AI | 607 | Triggered alarm #4 | Read | |||
| AI | 608 | Triggered alarm #5 | Read | |||
| AI | 609 | Triggered alarm #6 | Read | |||
| AI | 610 | Triggered alarm #7 | Read | |||
| AI | 611 | Triggered alarm #8 | Read | |||
| AI | 612 | Triggered alarm #9 | Read | |||
| AI | 613 | Triggered alarm #10 | Read | |||
| AI | 614 | Triggered alarm group #1 | Zero if no triggered alarm group. | Read | ||
| AI | 615 | Triggered alarm group #2 | Read | |||
| AI | 616 | Triggered alarm group #3 | Read | |||
| AI | 617 | Triggered alarm group #4 | Read | |||
| AI | 618 | Triggered alarm group #5 | Read | |||
| AI | 619 | Triggered alarm group #6 | Read | |||
| AI | 620 | Triggered alarm group #7 | Read | |||
| AI | 621 | Triggered alarm group #8 | Read | |||
| AI | 622 | Triggered alarm group #9 | Read | |||
| AI | 623 | Triggered alarm group #10 | Read | |||
| AO | 1 | Extract air start up | Extract air start up flow. | l/s | Write | |
| AV | 3 | SA low speed air flow set point | Supply air flow set point for the unit when running in low | l/s | Write | |
| AV | 4 | EA low speed air flow set point | Extract air flow set point for the unit when running in low | l/s | Write | |
| AV | 5 | SA high speed air flow set point | Supply air flow set point for the unit when running in high | l/s | Write | |
| AV | 6 | EA high speed air flow set point | Extract air flow set point for the unit when running in high | l/s | Write | |
| AV | 7 | SA max speed air flow set point | Supply air flow max. limit for the unit when the low/high speed | l/s | Write | |
| AV | 8 | EA max speed air flow set point | Extract air flow max. limit for the unit when the low/high speed | l/s | Write | |
| AV | 9 | SA regulation zone | Supply air flow regulation zone setting in % of the present air | % | Write | |
| AV | 10 | EA regulation zone | Extract air flow regulation zone setting in % of the present air | % | Write | |
| AV | 11 | SA regulation I-time | Supply air flow regulator affection setting. | s | Write | |
| AV | 12 | EA regulation I-time | Extract air flow regulator affection setting. | s | Write | |
| AV | 19 | SA low speed pressure set point | Supply air duct pressure set point for the unit when running in | Pa | Write | |
| AV | 20 | EA low speed pressure set point | Extract air duct pressure set point for the unit when running in | Pa | Write | |
| AV | 21 | SA high speed pressure set point | Supply air duct pressure for the unit when running in high speed | Pa | Write | |
| AV | 22 | EA high speed pressure set point | Extract air duct pressure set point for the unit when running in | Pa | Write | |
| AV | 23 | SA max speed pressure set point | Supply air duct pressure max. limit for the unit when the low/high | Pa | Write | |
| AV | 24 | EA max speed pressure set point | Extract air duct pressure max. limit for the unit when the low/high | Pa | Write | |
| AV | 25 | SA max speed output signal | Max. limit for the supply air fan speed when running in pressure | % | Write | |
| AV | 26 | EA max speed output signal | Max. limit for the extract air fan speed when running in pressure | % | Write | |
| AV | 27 | SA pressure regulation zone | Supply air pressure regulation zone setting in % of the present duct | % | Write | |
| AV | 28 | EA pressure regulation zone | Extract air pressure regulation zone setting in % of the present duct | % | Write | |
| AV | 29 | SA pressure I-time | Supply air pressure regulator affection setting. | s | Write | |
| AV | 30 | EA pressure I-time | Extract air pressure regulator affection setting. | s | Write | |
| AV | 37 | Demand low speed demand set point | Set point for the 0..10V input signal for the unit when running | % | Write | |
| AV | 38 | Demand high speed demand set point | Set point for the 0..10V input signal for the unit when running | % | Write | |
| AV | 39 | SA min speed air flow set point | Supply air flow min. limit for the unit when the low/high speed | l/s | Write | |
| AV | 40 | EA min speed air flow set point | Extract air flow min. limit for the unit when the low/high speed | l/s | Write | |
| AV | 41 | SA max speed air flow set point | Supply air flow max limit for the unit when the low/high speed | l/s | Write | |
| AV | 42 | EA max speed air flow set point | Extract air flow max. limit for the unit when the low/high speed | l/s | Write | |
| AV | 43 | SA demand P-band | Supply air demand regulator P-band setting. | % | Write | |
| AV | 44 | SA demand I-time | Supply air demand regulator affection setting. | s | Write | |
| AV | 50 | Slave offset factor | % | Write | ||
| AV | 54 | Outdoor temp compensation X1 | °C | Write | ||
| AV | 55 | Outdoor temp compensation X2 | °C | Write | ||
| AV | 56 | Outdoor temp compensation X3 | °C | Write | ||
| AV | 57 | Outdoor temp compensation X4 | °C | Write | ||
| AV | 58 | Outdoor temp compensation Y1 SA air flow | l/s | Write | ||
| AV | 59 | Outdoor temp compensation Y2 SA air flow | l/s | Write | ||
| AV | 60 | Outdoor temp compensation Y3 SA air flow | l/s | Write | ||
| AV | 61 | Outdoor temp compensation Y4 SA air flow | l/s | Write | ||
| AV | 62 | Outdoor temp compensation Y1 EA air flow | l/s | Write | ||
| AV | 63 | Outdoor temp compensation Y2 EA air flow | l/s | Write | ||
| AV | 64 | Outdoor temp compensation Y3 EA air flow | l/s | Write | ||
| AV | 65 | Outdoor temp compensation Y4 EA air flow | l/s | Write | ||
| AV | 66 | Outdoor temp compensation Y1 SA pressure | Pa | Write | ||
| AV | 67 | Outdoor temp compensation Y2 SA pressure | Pa | Write | ||
| AV | 68 | Outdoor temp compensation Y3 SA pressure | Pa | Write | ||
| AV | 69 | Outdoor temp compensation Y4 SA pressure | Pa | Write | ||
| AV | 70 | Outdoor temp compensation Y1 EA pressure | Pa | Write | ||
| AV | 71 | Outdoor temp compensation Y2 EA pressure | Pa | Write | ||
| AV | 72 | Outdoor temp compensation Y3 EA pressure | Pa | Write | ||
| AV | 73 | Outdoor temp compensation Y4 EA pressure | Pa | Write | ||
| AV | 79 | Down regulation neutralzone | K | Write | ||
| AV | 80 | Down regulation P-band | K | Write | ||
| AV | 81 | Down regulation I-time | s | Write | ||
| AV | 85 | SA fan speed at fire alarm 1 | % | Write | ||
| AV | 86 | EA fan speed at fire alarm 1 | % | Write | ||
| AV | 88 | SA fan speed at fire alarm 2 | % | Write | ||
| AV | 89 | EA fan speed at fire alarm 2 | % | Write | ||
| AV | 91 | SA fan speed at internal fire alarm | % | Write | ||
| AV | 92 | EA fan speed at internal fire alarm | % | Write | ||
| AV | 97 | SA pre-filter alarm limit | Pa | Write | ||
| AV | 98 | EA pre-filter alarm limit | Pa | Write | ||
| AV | 103 | SA AHU-filter alarm limit | Pa | Write | ||
| AV | 104 | EA AHU-filter alarm limit | Pa | Write | ||
| AV | 109 | SA end-filter alarm limit | Pa | Write | ||
| AV | 117 | ERS 1 step | Curve setting according to the diagram for ERS 1. | Write | ||
| AV | 118 | ERS 1 diff | Supply air temp difference setting according to the diagram for ERS 1. | K | Write | |
| AV | 119 | ERS 1 breakpoint | Breakpoint temp setting according to the diagram for ERS 1. | °C | Write | |
| AV | 122 | ERS 2 breakpoint X1 | Breakpoint X1 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 123 | ERS 2 breakpoint X2 | Breakpoint X2 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 124 | ERS 2 breakpoint X3 | Breakpoint X3 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 125 | ERS 2 breakpoint X4 | Breakpoint X4 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 126 | ERS 2 breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 127 | ERS 2 breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 128 | ERS 2 breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 129 | ERS 2 breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ERS 2. | °C | Write | |
| AVmin | 132 | SA temperature set point | Supply air temperature setting | °C | Write | |
| AVmin | 135 | EA/Room temperature set point | Extract air/room temperature setting | °C | Write | |
| AV | 136 | SA min temp set point | Supply air min. set point during EA/room | °C | Write | |
| AV | 137 | SA max temp set point | Supply air max. set point during EA/room | °C | Write | |
| AV | 138 | EA regultaion P-band | K | Write | ||
| AV | 139 | EA regultaion I-time | s | Write | ||
| AV | 142 | ORS breakpoint X1 | Breakpoint X1 setting according to the diagram for ORS. | °C | Write | |
| AV | 143 | ORS breakpoint X2 | Breakpoint X2 setting according to the diagram for ORS. | °C | Write | |
| AV | 144 | ORS breakpoint X3 | Breakpoint X3 setting according to the diagram for ORS. | °C | Write | |
| AV | 145 | ORS breakpoint X4 | Breakpoint X4 setting according to the diagram for ORS. | °C | Write | |
| AV | 146 | ORS breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ORS. | °C | Write | |
| AV | 147 | ORS breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ORS. | °C | Write | |
| AV | 148 | ORS breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ORS. | °C | Write | |
| AV | 149 | ORS breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ORS. | °C | Write | |
| AV | 152 | ORE breakpoint X1 | Breakpoint X1 setting according to the diagram for ORE. | °C | Write | |
| AV | 153 | ORE breakpoint X2 | Breakpoint X2 setting according to the diagram for ORE. | °C | Write | |
| AV | 154 | ORE breakpoint X3 | Breakpoint X3 setting according to the diagram for ORE. | °C | Write | |
| AV | 155 | ORE breakpoint X4 | Breakpoint X4 setting according to the diagram for ORE. | °C | Write | |
| AV | 156 | ORE breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ORE. | °C | Write | |
| AV | 157 | ORE breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ORE. | °C | Write | |
| AV | 158 | ORE breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ORE. | °C | Write | |
| AV | 159 | ORE breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ORE. | °C | Write | |
| AV | 168 | External room temp from BMS | °C | Write | ||
| AV | 169 | External room temp from BMS alarm time | min | Write | ||
| AV | 178 | External OA temp from BMS | °C | Write | ||
| AV | 179 | External OA temp from BMS alarm time | min | Write | ||
| AV | 184 | RHX defrost start limit | Pa | Write | ||
| AV | 188 | RHX sorption rotor function | Moved to Multistate Value 188 | Write | ||
| AV | 191 | RHX min exhaust air temp set point | °C | Write | ||
| AV | 192 | RHX min exhaust air temp P-band | K | Write | ||
| AV | 193 | RHX min exhaust air temp I-time | s | Write | ||
| AV | 199 | PHX periodic operation interval | h | Write | ||
| AV | 200 | PHX periodic operation time | min | Write | ||
| AV | 207 | CHX periodic operation interval | h | Write | ||
| AV | 208 | CHX periodic operation time | min | Write | ||
| AV | 213 | PHX/CHX Bypass defrost limit | PHX is default 3°C, CHX is default 5°C. | °C | Write | |
| AV | 214 | PHX/CHX Bypass defrost P-band | K | Write | ||
| AV | 215 | PHX/CHX Bypass defrost I-time | s | Write | ||
| AV | 220 | Heat exchange temperature regulation P-band | K | Write | ||
| AV | 221 | Heat exchange temperature regulation I-time | s | Write | ||
| AV | 222 | Cool exchange temperature regulation P-band | K | Write | ||
| AV | 223 | Cool exchange temperature regulation I-time | s | Write | ||
| AV | 226 | Re-heat P-band | K | Write | ||
| AV | 227 | Re-heat I-time | s | Write | ||
| AV | 230 | Re-heat periodic operation interval | h | Write | ||
| AV | 231 | Re-heat periodic operation time | min | Write | ||
| AV | 239 | Extra regulation sequence 1 heat max output signal | Maximum output signal setting for the extra regulation sequence. | % | Write | |
| AV | 240 | Extra regulation sequence 1 cool max output signal | Maximum output signal setting for the extra regulation sequence. | % | Write | |
| AV | 241 | Extra regulation sequence 1 heat P-band | K | Write | ||
| AV | 242 | Extra regulation sequence 1 heat I-time | s | Write | ||
| AV | 243 | Extra regulation sequence 1 cool P-band | K | Write | ||
| AV | 244 | Extra regulation sequence 1 cool I-time | s | Write | ||
| AV | 247 | Extra regulation 1 periodic operation interval | h | Write | ||
| AV | 248 | Extra regulation 1 periodic operation time | min | Write | ||
| AV | 252 | Extra regulation 1 temperature protection temperature | °C | Write | ||
| AV | 253 | Extra regulation 1 temperature protection alarm delay | min | Write | ||
| AV | 258 | Cool step 1 min supply air flow limit | l/s | Write | ||
| AV | 259 | Cool step 2 min supply air flow limit | l/s | Write | ||
| AV | 260 | Cool step 3 min supply air flow limit | l/s | Write | ||
| AV | 262 | Cool SA neutral zone | K | Write | ||
| AV | 263 | Cool EA neutral zone | K | Write | ||
| AV | 264 | Cool outdoor temp limit 1 | °C | Write | ||
| AV | 265 | Cool outdoor temp limit 2 | °C | Write | ||
| AV | 266 | Cool outdoor temp limit 3 | °C | Write | ||
| AV | 267 | Cool 0-10V min supply air flow limit | l/s | Write | ||
| AV | 268 | Cool 0-10V min extract air flow limit | l/s | Write | ||
| AV | 269 | Cool restart time | Setting of cool restart time between start-start. | min | Write | |
| AV | 270 | Cool step up delay time | Setting of on/off cooling and COOL DX time delay between steps. | min | Write | |
| AV | 271 | Cool stand still time | Setting of on/off cooling and COOL DX time delay before stop-start | min | Write | |
| AV | 272 | Cool P-band | K | Write | ||
| AV | 273 | Cool I-time | s | Write | ||
| AV | 277 | Cool periodic operation interval | h | Write | ||
| AV | 278 | Cool periodic operation time | min | Write | ||
| AV | 279 | Cool step 1 min extract air flow limit | l/s | Write | ||
| AV | 280 | Cool step 2 min extract air flow limit | l/s | Write | ||
| AV | 281 | Cool step 3 min extract air flow limit | l/s | Write | ||
| AV | 285 | Summer night cool start time (hour) | h | Write | ||
| AV | 286 | Summer night cool start time (minute) | min | Write | ||
| AV | 287 | Summer night cool stop time (hour) | h | Write | ||
| AV | 288 | Summer night cool stop time (minute) | min | Write | ||
| AV | 289 | Summer night cool OA temp start limit | °C | Write | ||
| AV | 290 | Summer night cool EA temp start limit | °C | Write | ||
| AV | 291 | Summer night cool EA temp stop limit | °C | Write | ||
| AV | 292 | Summer night cool SA temp set point | °C | Write | ||
| AV | 297 | Intermittent night heat SA flow set point | l/s | Write | ||
| AV | 298 | Intermittent night heat SA duct pressure set point | Pa | Write | ||
| AV | 299 | Intermittent night heat EA temp start limit | °C | Write | ||
| AV | 300 | Intermittent night heat EA temp stop limit | °C | Write | ||
| AV | 301 | Intermittent night heat SA temp set point | °C | Write | ||
| AV | 303 | Intermittent night heat EA flow set point | l/s | Write | ||
| AV | 304 | Intermittent night heat EA duct pressure set point | Pa | Write | ||
| AV | 306 | Morning boost start time (hour) | h | Write | ||
| AV | 307 | Morning boost start time (minute) | min | Write | ||
| AV | 308 | Morning boost air flow set point | l/s | Write | ||
| AV | 309 | Morning boost duct pressure set point | Pa | Write | ||
| AV | 314 | Cooling boost comfort start limit | K | Write | ||
| AV | 315 | Cooling boost comfort regulation speed | %/s | Write | ||
| AV | 316 | Cooling boost economy P-band | K | Write | ||
| AV | 317 | Cooling boost economy I-time | s | Write | ||
| AV | 321 | Heating boost comfort start limit | K | Write | ||
| AV | 322 | Heating boost comfort regulation speed | %/s | Write | ||
| AV | 331 | Xzone ERS 1 step | Curve setting according to the diagram for ERS 1. | Write | ||
| AV | 332 | Xzone ERS 1 diff | Supply air temp differental setting according to the diagram for ERS 1. | K | Write | |
| AV | 333 | Xzone ERS 1 breakpoint | Breakpoint temp setting according to the diagram for ERS 1. | °C | Write | |
| AV | 336 | Xzone ERS 2 breakpoint X1 | Breakpoint X1 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 337 | Xzone ERS 2 breakpoint X2 | Breakpoint X2 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 338 | Xzone ERS 2 breakpoint X3 | Breakpoint X3 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 339 | Xzone ERS 2 breakpoint X4 | Breakpoint X4 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 340 | Xzone ERS 2 breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 341 | Xzone ERS 2 breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 342 | Xzone ERS 2 breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 343 | Xzone ERS 2 breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ERS 2. | °C | Write | |
| AV | 346 | Xzone SA temperature set point | Supply air temperature setting, for supply air temp regulation mode. | °C | Write | |
| AV | 349 | Xzone EA/Room temperature set point | Extract air/room temperature setting | °C | Write | |
| AV | 350 | Xzone SA min temp set point | Supply air min. set point during EA/room | °C | Write | |
| AV | 351 | Xzone SA max temp set point | Supply air max. set point during EA/room | °C | Write | |
| AV | 352 | Xzone EA regultaion P-band | K | Write | ||
| AV | 353 | Xzone EA regultaion I-time | s | Write | ||
| AV | 354 | Xzone ORS breakpoint X1 | Breakpoint X1 setting according to the diagram for ORS. | °C | Write | |
| AV | 355 | Xzone ORS breakpoint X2 | Breakpoint X2 setting according to the diagram for ORS. | °C | Write | |
| AV | 356 | Xzone ORS breakpoint X3 | Breakpoint X3 setting according to the diagram for ORS. | °C | Write | |
| AV | 357 | Xzone ORS breakpoint X4 | Breakpoint X4 setting according to the diagram for ORS. | °C | Write | |
| AV | 358 | Xzone ORS breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ORS. | °C | Write | |
| AV | 359 | Xzone ORS breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ORS. | °C | Write | |
| AV | 360 | Xzone ORS breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ORS. | °C | Write | |
| AV | 361 | Xzone ORS breakpoint Y4 | Breakpoint Y4 setting according to the diagram for ORS. | °C | Write | |
| AV | 364 | Xzone ORE breakpoint X1 | Breakpoint X1 setting according to the diagram for ORE. | °C | Write | |
| AV | 365 | Xzone ORE breakpoint X2 | Breakpoint X2 setting according to the diagram for ORE. | °C | Write | |
| AV | 366 | Xzone ORE breakpoint X3 | Breakpoint X3 setting according to the diagram for ORE. | °C | Write | |
| AV | 367 | Xzone ORE breakpoint X4 | Breakpoint X4 setting according to the diagram for ORE. | °C | Write | |
| AV | 368 | Xzone ORE breakpoint Y1 | Breakpoint Y1 setting according to the diagram for ORE. | °C | Write | |
| AV | 369 | Xzone ORE breakpoint Y2 | Breakpoint Y2 setting according to the diagram for ORE. | °C | Write | |
| AV | 370 | Xzone ORE breakpoint Y3 | Breakpoint Y3 setting according to the diagram for ORE. | °C | Write | |
| AV | 371 | Xzone ORE breakpoint Y4 | °C | Write | ||
| AV | 380 | Xzone external room temp from BMS | °C | Write | ||
| AV | 381 | Xzone external room temp from BMS alarm time | min | Write | ||
| AV | 384 | Xzone reheat P-band | K | Write | ||
| AV | 385 | Xzone reheat I-time | s | Write | ||
| AV | 388 | Xzone reheat periodic operation interval | h | Write | ||
| AV | 389 | Xzone reheat periodic operation time | min | Write | ||
| AV | 396 | Xzone Cool SA neutral zone | K | Write | ||
| AV | 397 | Xzone Cool EA neutral zone | K | Write | ||
| AV | 398 | Xzone Cool P-band | K | Write | ||
| AV | 399 | Xzone Cool I-time | s | Write | ||
| AV | 403 | Xzone Cool periodic operation interval | h | Write | ||
| AV | 404 | Xzone Cool periodic operation time | min | Write | ||
| AV | 411 | Pre-heat temperature set point | °C | Write | ||
| AV | 412 | Pre-heat P-band | K | Write | ||
| AV | 413 | Pre-heat I-time | s | Write | ||
| AV | 416 | Pre-heat periodic operation interval | h | Write | ||
| AV | 417 | Pre-heat periodic operation time | min | Write | ||
| AV | 426 | ReCO2-CO2 set point | % | Write | ||
| AV | 427 | ReCO2 min. outdoor air | l/s | Write | ||
| AV | 428 | ReCO2 min. exhaust air | l/s | Write | ||
| AV | 429 | ReCO2-CO2 P-band | % | Write | ||
| AV | 430 | ReCO2-CO2 I-time | s | Write | ||
| AV | 431 | ReCO2-CO2 air flow boost reg. P-band | % | Write | ||
| AV | 432 | ReCO2-CO2 air flow boost reg. I-time | s | Write | ||
| AV | 433 | ReCO2 heat P-band | K | Write | ||
| AV | 434 | ReCO2 heat I-time | s | Write | ||
| AV | 435 | ReCO2 cool P-band | K | Write | ||
| AV | 436 | ReCO2 cool I-time | s | Write | ||
| AV | 443 | Humidifying on/off start level | %RH | Write | ||
| AV | 444 | Humidifying on/off stop level | %RH | Write | ||
| AV | 448 | Humidifying 0-10V set point | %RH | Write | ||
| AV | 449 | Humidifying 0-10V SA max set point | %RH | Write | ||
| AV | 450 | Humidifying 0-10V SA P-band | %RH | Write | ||
| AV | 451 | Humidifying 0-10V SA I-time | s | Write | ||
| AV | 452 | Humidifying 0-10V EA P-band | %RH | Write | ||
| AV | 453 | Humidifying 0-10V EA I-time | s | Write | ||
| AV | 458 | Dehumidifying set point | %RH | Write | ||
| AV | 470 | COOL DX Low pressure stop limit | Bar | Write | ||
| AV | 471 | COOL DX High pressure stop limit | Bar | Write | ||
| AV | 472 | COOL DX Restart time | Time setting between start - start | min | Write | |
| AV | 482 | SMART Link WB Heat temperature set point | °C | Write | ||
| AV | 483 | SMART Link WB Heat temperature heat zone | K | Write | ||
| AV | 484 | SMART Link WB Cool temperature set point | °C | Write | ||
| AV | 485 | SMART Link WB Cool temperature heat zone | K | Write | ||
| AV | 491 | SMART Link WB Optimize valve upper limit | % | Write | ||
| AV | 492 | SMART Link WB Optimize valve lower limit | % | Write | ||
| AV | 493 | SMART Link WB Optimize time delay | s | Write | ||
| AV | 494 | SMART Link WB Optimize heat regulation speed | K/s | Write | ||
| AV | 495 | SMART Link WB Optimize cool regulation speed | K/s | Write | ||
| AV | 510 | SMART Link DX Amount of units | Write | |||
| AV | 519 | SMART Link OA temp limit | °C | Write | ||
| AV | 524 | AYC Heated water temp set point | °C | Write | ||
| AV | 526 | AYC Heated water OA temp for start of pump | °C | Write | ||
| AV | 527 | AYC Heated water OA temp for stop of pump | °C | Write | ||
| AV | 532 | AYC Heated water periodic operation interval | h | Write | ||
| AV | 533 | AYC Heated water periodic operation time | min | Write | ||
| AV | 537 | AYC Heated water OA temp compensation X1 | °C | Write | ||
| AV | 538 | AYC Heated water OA temp compensation X2 | °C | Write | ||
| AV | 539 | AYC Heated water OA temp compensation X3 | °C | Write | ||
| AV | 540 | AYC Heated water OA temp compensation X4 | °C | Write | ||
| AV | 541 | AYC Heated water OA temp compensation Y1 | °C | Write | ||
| AV | 542 | AYC Heated water OA temp compensation Y2 | °C | Write | ||
| AV | 543 | AYC Heated water OA temp compensation Y3 | °C | Write | ||
| AV | 544 | AYC Heated water OA temp compensation Y4 | °C | Write | ||
| AV | 549 | AYC Heated water room temp compensation temperature | °C | Write | ||
| AV | 550 | AYC Heated water room temp compensation P-band | K | Write | ||
| AV | 554 | AYC Heated water night temp compensation temp | K | Write | ||
| AV | 556 | AYC Heated water night temp compensation start time 1 (hour) | h | Write | ||
| AV | 557 | AYC Heated water night temp compensation start time 1 (minutes) | min | Write | ||
| AV | 558 | AYC Heated water night temp compensation stop time 1 (hour) | h | Write | ||
| AV | 559 | AYC Heated water night temp compensation stop time 1 (minutes) | min | Write | ||
| AV | 563 | AYC Heated water night temp compensation start time 2 (hour) | h | Write | ||
| AV | 564 | AYC Heated water night temp compensation start time 2 (minutes) | min | Write | ||
| AV | 565 | AYC Heated water night temp compensation stop time 2 (hour) | h | Write | ||
| AV | 566 | AYC Heated water night temp compensation stop time 2 (minutes) | min | Write | ||
| AV | 569 | AYC Heated water P-band | K | Write | ||
| AV | 570 | AYC Heated water I-time | s | Write | ||
| AV | 572 | AYC Chilled water temp set point | °C | Write | ||
| AV | 575 | AYC Chilled water OA temp for start of pump | °C | Write | ||
| AV | 576 | AYC Chilled water OA temp for stop of pump | °C | Write | ||
| AV | 581 | AYC Chilled water periodic operation interval | h | Write | ||
| AV | 582 | AYC Chilled water periodic operation time | min | Write | ||
| AV | 586 | AYC Chilled water OA temp compensation X1 | °C | Write | ||
| AV | 587 | AYC Chilled water OA temp compensation X2 | °C | Write | ||
| AV | 588 | AYC Chilled water OA temp compensation X3 | °C | Write | ||
| AV | 589 | AYC Chilled water OA temp compensation X4 | °C | Write | ||
| AV | 590 | AYC Chilled water OA temp compensation Y1 | °C | Write | ||
| AV | 591 | AYC Chilled water OA temp compensation Y2 | °C | Write | ||
| AV | 592 | AYC Chilled water OA temp compensation Y3 | °C | Write | ||
| AV | 593 | AYC Chilled water OA temp compensation Y4 | °C | Write | ||
| AV | 598 | AYC Chilledwater room temp compensation temperature | °C | Write | ||
| AV | 599 | AYC Chilled water room temp compensation P-band | K | Write | ||
| AV | 603 | AYC Chilled water night temp compensation temp | K | Write | ||
| AV | 605 | AYC Chilled water night temp compensation start time 1 (hour) | h | Write | ||
| AV | 606 | AYC Chilled water night temp compensation start time 1 (minutes) | min | Write | ||
| AV | 607 | AYC Chilled water night temp compensation stop time 1 (hour) | h | Write | ||
| AV | 608 | AYC Chilled water night temp compensation stop time 1 (minutes) | min | Write | ||
| AV | 612 | AYC Chilled water night temp compensation start time 2 (hour) | h | Write | ||
| AV | 613 | AYC Chilled water night temp compensation start time 2 (minutes) | min | Write | ||
| AV | 614 | AYC Chilledwater night temp compensation stop time 2 (hour) | h | Write | ||
| AV | 615 | AYC Chilled water night temp compensation stop time 2 (minutes) | min | Write | ||
| AV | 619 | AYC Chilled water dew point compensation neutral zone | K | Write | ||
| AV | 620 | AYC Chilled water dew point compensation regulation speed | Percent air flow boost of each increased chilled water set point. | %/K | Write | |
| AV | 623 | AYC Chilled water P-band | K | Write | ||
| AV | 624 | AYC Chilled water I-time | s | Write | ||
| AV | 638 | Optimize SA pressure set point | Pa | Write | ||
| AV | 639 | Optimize EA pressure set point | Pa | Write | ||
| AV | 672 | MIRU Control 1 Low speed duct pressure set point | Pa | Write | ||
| AV | 673 | MIRU Control 1 High speed duct pressure set point | Pa | Write | ||
| AV | 674 | MIRU Control 1 Low speed air flow set point | l/s | Write | ||
| AV | 675 | MIRU Control 1 High speed air flow set point | l/s | Write | ||
| AV | 680 | MIRU Control 2 Low speed duct pressure set point | Pa | Write | ||
| AV | 681 | MIRU Control 2 High speed duct pressure set point | Pa | Write | ||
| AV | 682 | MIRU Control 2 Low speed air flow set point | l/s | Write | ||
| AV | 683 | MIRU Control 2 High speed air flow set point | l/s | Write | ||
| AV | 688 | MIRU Control 3 Low speed duct pressure set point | Pa | Write | ||
| AV | 689 | MIRU Control 3 High speed duct pressure set point | Pa | Write | ||
| AV | 690 | MIRU Control 3 Low speed air flow set point | l/s | Write | ||
| AV | 691 | MIRU Control 3 High speed air flow set point | l/s | Write | ||
| AV | 696 | MIRU Control 4 Low speed duct pressure set point | Pa | Write | ||
| AV | 697 | MIRU Control 4 High speed duct pressure set point | Pa | Write | ||
| AV | 698 | MIRU Control 4 Low speed air flow set point | l/s | Write | ||
| AV | 699 | MIRU Control 4 High speed air flow set point | l/s | Write | ||
| AV | 704 | MIRU Control 5 Low speed duct pressure set point | Pa | Write | ||
| AV | 705 | MIRU Control 5 High speed duct pressure set point | Pa | Write | ||
| AV | 706 | MIRU Control 5 Low speed air flow set point | l/s | Write | ||
| AV | 707 | MIRU Control 5 High speed air flow set point | l/s | Write | ||
| AV | 712 | MIRU Control 6 Low speed duct pressure set point | Pa | Write | ||
| AV | 713 | MIRU Control 6 High speed duct pressure set point | Pa | Write | ||
| AV | 714 | MIRU Control 6 Low speed air flow set point | l/s | Write | ||
| AV | 715 | MIRU Control 6 High speed air flow set point | l/s | Write | ||
| AV | 720 | MIRU Control 7 Low speed duct pressure set point | Pa | Write | ||
| AV | 721 | MIRU Control 7 High speed duct pressure set point | Pa | Write | ||
| AV | 722 | MIRU Control 7 Low speed air flow set point | l/s | Write | ||
| AV | 723 | MIRU Control 7 High speed air flow set point | l/s | Write | ||
| AV | 728 | MIRU Control 8 Low speed duct pressure set point | Pa | Write | ||
| AV | 729 | MIRU Control 8 High speed duct pressure set point | Pa | Write | ||
| AV | 730 | MIRU Control 8 Low speed air flow set point | l/s | Write | ||
| AV | 731 | MIRU Control 8 High speed air flow set point | l/s | Write | ||
| AV | 736 | MIRU Control 9 Low speed duct pressure set point | Pa | Write | ||
| AV | 737 | MIRU Control 9 High speed duct pressure set point | Pa | Write | ||
| AV | 738 | MIRU Control 9 Low speed air flow set point | l/s | Write | ||
| AV | 739 | MIRU Control 9 High speed air flow set point | l/s | Write | ||
| AV | 744 | MIRU Control 10 Low speed duct pressure set point | Pa | Write | ||
| AV | 745 | MIRU Control 10 High speed duct pressure set point | Pa | Write | ||
| AV | 746 | MIRU Control 10 Low speed air flow set point | l/s | Write | ||
| AV | 747 | MIRU Control 10 High speed air flow set point | l/s | Write | ||
| BI | 1 | Operation active | Relay output status | Read | ||
| BI | 2 | Damper operation active | Relay output status | Read | ||
| BI | 3 | Low speed operation active | Low speed operation status | Read | ||
| BI | 4 | High speed operation active | High speed operation status | Read | ||
| BI | 5 | Intermittent night heat active | Read | |||
| BI | 6 | Morning boost active | Read | |||
| BI | 7 | Heating boost active | Read | |||
| BI | 8 | Cooling boost active | Read | |||
| BI | 9 | Summer night cool active | Read | |||
| BImin | 13 | A-alarm active | Any alarm with priority class A active | Read | ||
| BImin | 14 | B-alarm active | Any alarm with priority class B active | Read | ||
| BI | 17 | HX operation active | HX status | Read | ||
| BI | 18 | HX cool recovery active | HX cool recovery status | Read | ||
| BI | 19 | HX defrost active | HX defrost status | Read | ||
| BI | 22 | RHX speed monitor signal | RHX speed monitor status | Read | ||
| BI | 27 | CHX pump output | Relay output status | Read | ||
| BI | 28 | CHX pump input | Digital input status | Read | ||
| BI | 31 | Season heat, extra regulation sequence allowed | Read | |||
| BI | 32 | Season heat, re-heat allowed | Read | |||
| BI | 33 | Extra regulation sequence 1, output | Relay output status | Read | ||
| BI | 34 | Extra regulation sequence 1, power reduction active | Read | |||
| BI | 35 | Extra regulation sequence 1, anti-frost regulation active | Read | |||
| BI | 38 | Re-heat output | Relay output status | Read | ||
| BI | 39 | Re-heat power reduction active | Read | |||
| BI | 40 | Re-heat anti-frost regulation active | Read | |||
| BI | 43 | Cool output 1 | Relay output status | Read | ||
| BI | 44 | Cool output 2 | Relay output status | Read | ||
| BI | 48 | Extra regulation sequence 2, output | Relay output status | Read | ||
| BI | 49 | Extra regulation sequence 2, power reduction active | Read | |||
| BI | 50 | Extra regulation sequence 2, anti-frost regulation active | Read | |||
| BI | 51 | Pre-heat output | Relay output status | Read | ||
| BI | 52 | Pre-heat power reduction active | Read | |||
| BI | 53 | Pre-heat anti-frost regulation active | Read | |||
| BI | 56 | Xzone heat output | Relay output status | Read | ||
| BI | 57 | Xzone heat power reduction active | Read | |||
| BI | 58 | Xzone heat anti-frost regulation active | Read | |||
| BI | 63 | Xzone cool output 1 | Relay output status | Read | ||
| BI | 64 | Xzone cool output 2 | Relay output status | Read | ||
| BI | 99 | AYC heat pump output | Relay output status | Read | ||
| BI | 100 | AYC heat pump input | Digital input status | Read | ||
| BI | 104 | Max. limit for the supply air fan speed when running in pressure regulation mo | Relay output status | Read | ||
| BI | 105 | AYC cool pump input | Digital input status | Read | ||
| BI | 109 | COOL DX compressor 1 output | Relay output status | Read | ||
| BI | 110 | COOL DX compressor 1 input | Digital input status | Read | ||
| BI | 115 | COOL DX compressor 2 output | Relay output status | Read | ||
| BI | 116 | COOL DX compressor 2 input | Digital input status | Read | ||
| BI | 319 | SMART Link, DX operation | Read | |||
| BI | 323 | SMART Link, DX unit 1 operation | Read | |||
| BI | 324 | SMART Link, DX unit 1 cool mode | Read | |||
| BI | 325 | SMART Link, DX unit 1 defrost request | Read | |||
| BI | 326 | SMART Link, DX unit 1 defrost active | Read | |||
| BI | 334 | SMART Link, DX unit 2 operation | Read | |||
| BI | 335 | SMART Link, DX unit 2 cool mode | Read | |||
| BI | 336 | SMART Link, DX unit 2 defrost request | Read | |||
| BI | 337 | SMART Link, DX unit 2 defrost active | Read | |||
| BI | 345 | SMART Link, DX unit 3 operation | Read | |||
| BI | 346 | SMART Link, DX unit 3 cool mode | Read | |||
| BI | 347 | SMART Link, DX unit 3 defrost request | Read | |||
| BI | 348 | SMART Link, DX unit 3 defrost active | Read | |||
| BI | 356 | SMART Link, DX unit 4 operation | Read | |||
| BI | 357 | SMART Link, DX unit 4 cool mode | Read | |||
| BI | 358 | SMART Link, DX unit 4 defrost request | Read | |||
| BI | 359 | SMART Link, DX unit 4 power defrost active | Read | |||
| BI | 501 | Alarm 1:1 External fire alarm no. 1 tripped | Read | |||
| BI | 502 | Alarm 1:2 External fire alarm no. 2 tripped | Read | |||
| BI | 503 | Alarm 1:3 Internal fire alarm tripped | Read | |||
| BI | 516 | Alarm 2:1 External alarm no. 1 tripped | Read | |||
| BI | 517 | Alarm 2:2 External alarm no. 2 tripped | Read | |||
| BI | 531 | Alarm 3:1 Pre-heat I/O-module no. 9 com. error | Read | |||
| BI | 532 | Alarm 3:2 Pre-heat electrical heater overheat protection tripped | Read | |||
| BI | 533 | Alarm 3:3 Pre-heat frost protection tripped | Read | |||
| BI | 534 | Alarm 3:4 Pre-heat frost protection temperature sensor defective | Read | |||
| BI | 535 | Alarm 3:5 Pre-heat temperature sensor defective | Read | |||
| BI | 536 | Alarm 3:6 Pre-heat valve monitoring tripped | Read | |||
| BI | 537 | Alarm 3:7 Pre-heat temperature below set point alarm limit | Read | |||
| BI | 538 | Alarm 3:8 Pre-heat alarm input tripped | Read | |||
| BI | 546 | Alarm 4:1 Extra reg. sequence 1 I/O-module no. E com. error | Read | |||
| BI | 547 | Alarm 4:2 Extra reg. sequence 1 electrical heater overheat protection tripped | Read | |||
| BI | 548 | Alarm 4:3 Extra reg. sequence 1 frost protection tripped | Read | |||
| BI | 549 | Alarm 4:4 Extra reg. sequence 1 frost protection temperature sensor defective | Read | |||
| BI | 550 | Alarm 4:5 Extra reg. sequence 1 valve monitoring tripped | Read | |||
| BI | 551 | Alarm 4:6 Extra reg. sequence 1 alarm input tripped | Read | |||
| BI | 552 | Alarm 4:7 Extra reg. sequence 1 temperature protection from com. Error | Read | |||
| BI | 554 | Alarm 4:9 Extra reg. sequence 2 I/O-module no. F com. error | Read | |||
| BI | 555 | Alarm 4:10 Extra reg. sequence 2 electrical heater overheat protection tripped | Read | |||
| BI | 556 | Alarm 4:11 Extra reg. sequence 2 frost protection tripped | Read | |||
| BI | 557 | Alarm 4:12 Extra reg. sequence 2 frost protection temperature sensor defective | Read | |||
| BI | 558 | Alarm 4:13 Extra reg. sequence 2 valve monitoring tripped | Read | |||
| BI | 559 | Alarm 4:14 Extra reg. sequence 2 alarm input tripped | Read | |||
| BI | 561 | Alarm 5:1 Re-heat electrical heater over heat protection tripped | Read | |||
| BI | 562 | Alarm 5:2 Re-heat frost protection tripped | Read | |||
| BI | 563 | Alarm 5:3 Re-heat frost protection temperature sensor defective | Read | |||
| BI | 564 | Alarm 5:4 Re-heat heat valve monitoring tripped | Read | |||
| BI | 576 | Alarm 6:1 Xzone I/O-module no. A com. error | Read | |||
| BI | 577 | Alarm 6:2 Xzone electrical heater overheat protection tripped | Read | |||
| BI | 578 | Alarm 6:3 Xzone frost protection tripped | Read | |||
| BI | 579 | Alarm 6:4 Xzone frost protection temperature sensor defective | Read | |||
| BI | 580 | Alarm 6:5 Xzone supply air temperature sensor defective | Read | |||
| BI | 581 | Alarm 6:6 Xzone heat valve monitoring tripped | Read | |||
| BI | 582 | Alarm 6:7 Xzone supply air temperature below set point alarm limit | Read | |||
| BI | 583 | Alarm 6:8 Xzone supply air temperature above set point alarm limit | Read | |||
| BI | 584 | Alarm 6:9 Xzone heat alarm input tripped | Read | |||
| BI | 591 | Alarm 7:1 Xzone I/O-module no. B com. error | Read | |||
| BI | 592 | Alarm 7:2 Xzone extract air temperature sensor defective | Read | |||
| BI | 593 | Alarm 7:3 Xzone cool valve monitoring tripped | Read | |||
| BI | 594 | Alarm 7:4 Xzone extract air temperature below set point alarm limit | Read | |||
| BI | 595 | Alarm 7:5 Xzone cool alarm input 1 tripped | Read | |||
| BI | 596 | Alarm 7:6 Xzone cool alarm input 2 tripped | Read | |||
| BI | 610 | Alarm 8:5 Cool valve monitoring tripped | Read | |||
| BI | 636 | Alarm 10:1 Supply air temperature sensor defective | Read | |||
| BI | 637 | Alarm 10:2 Supply air temperature sensor for density compensation defective | Read | |||
| BI | 638 | Alarm 10:3 Extract air temperature sensor defective | Read | |||
| BI | 639 | Alarm 10:4 Extract air temperature sensor for density compensation defective | Read | |||
| BI | 640 | Alarm 10:5 Extract air temperature sensor for heat exchanger defrosting def. | Read | |||
| BI | 641 | Alarm 10:6 Extract air temp. sensor for density compensation in SD AHU def. | Read | |||
| BI | 642 | Alarm 10:7 Extract air duct temperature sensor defective | Read | |||
| BI | 645 | Alarm 10:10 Outdoor air temperature sensor defective | Read | |||
| BI | 651 | Alarm 11:1 Room temperature sensor no. 1 defective | Read | |||
| BI | 652 | Alarm 11:2 Room temperature sensor no. 2 defective | Read | |||
| BI | 653 | Alarm 11:3 Room temperature sensor no. 3 defective | Read | |||
| BI | 654 | Alarm 11:4 Room temperature sensor no. 4 defective | Read | |||
| BI | 655 | Alarm 11:5 Xzone room temperature sensor no. 5 defective | Read | |||
| BI | 656 | Alarm 11:6 Xzone room temperature sensor no. 6 defective | Read | |||
| BI | 657 | Alarm 11:7 Xzone room temperature sensor no. 7 defective | Read | |||
| BI | 658 | Alarm 11:8 Xzone room temperature sensor no. 8 defective | Read | |||
| BI | 659 | Alarm 11:9 Outdoor temperature sensor no. A defective | Read | |||
| BI | 660 | Alarm 11:10 Outdoor temperature sensor no. B defective | Read | |||
| BI | 661 | Alarm 11:11 Outdoor temperature sensor no. C defective | Read | |||
| BI | 662 | Alarm 11:12 Outdoor temperature sensor no. D defective | Read | |||
| BI | 663 | Alarm 11:13 Room temperature from com. error | Read | |||
| BI | 664 | Alarm 11:14 Xzone room temperature from com. error | Read | |||
| BI | 665 | Alarm 11:15 Outdoor temperature from com. error | Read | |||
| BI | 666 | Alarm 12:1 Supply air temperature below set point alarm limit | Read | |||
| BI | 667 | Alarm 12:2 Supply air temperature above set point alarm limit | Read | |||
| BI | 671 | Alarm 12:6 Extract air temperature below alarm limit | Read | |||
| BI | 676 | Alarm 12:11 Temperature guard below alarm limit | Read | |||
| BI | 681 | Alarm 13:1 Humidification I/O-module no. 4 com. error | Read | |||
| BI | 682 | Alarm 13:2 Supply air humidity sensor defective | Read | |||
| BI | 683 | Alarm 13:3 Extract air humidity sensor defective | Read | |||
| BI | 689 | Alarm 13:9 Humidifier alarm output tripped | Read | |||
| BI | 691 | Alarm 13:11 VOC sensor com. error | Read | |||
| BI | 692 | Alarm 13:12 VOC sensor internal com. error | Read | |||
| BI | 693 | Alarm 13:13 VOC sensor internal error | Read | |||
| BI | 694 | Alarm 13:14 VOC sensor level below/above set point alarm limit | Read | |||
| BI | 711 | Alarm 15:1 Plate heat exchanger I/O-module no. 2 com. error | Read | |||
| BI | 712 | Alarm 15:2 Plate heat exchanger temperature sensor no. 1 defective | Read | |||
| BI | 713 | Alarm 15:3 Plate heat exchanger temperature sensor no. 2 defective | Read | |||
| BI | 714 | Alarm 15:4 Plate heat exchanger damper monitor tripped | Read | |||
| BI | 717 | Alarm 15:7 Plate heat exchanger I/O-module no. 3 com. error | Read | |||
| BI | 718 | Alarm 15:8 Plate heat exchanger bypass damper monitor tripped | Read | |||
| BI | 719 | Alarm 15:9 Plate heat exchanger damper no. 1 monitor tripped | Read | |||
| BI | 720 | Alarm 15:10 Plate heat exchanger damper no. 2 monitor tripped | Read | |||
| BI | 721 | Alarm 15:11 Plate heat exchanger I/O-module no. 3 com. error | Read | |||
| BI | 722 | Alarm 15:12 Plate heat exchanger bypass damper monitor tripped | Read | |||
| BI | 724 | Alarm 15:14 Plate heat exchanger defrost pressure sensor no. C com. error | Read | |||
| BI | 725 | Alarm 15:15 Plate heat exchanger defrost pressure above alarm limit | Read | |||
| BI | 726 | Alarm 16:1 Coil heat exchanger I/O-module no. 1 com. error | Read | |||
| BI | 727 | Alarm 16:2 Coil heat exchanger temperature sensor defective | Read | |||
| BI | 728 | Alarm 16:3 Coil heat exchanger valve monitor tripped | Read | |||
| BI | 729 | Alarm 16:4 Coil heat exchanger pump monitor tripped | Read | |||
| BI | 741 | Alarm 17:1 Rotary heat exchanger motor controller com. error | Read | |||
| BI | 742 | Alarm 17:2 Rotary heat exchanger defrost pressure sensor no. 7 com. error | Read | |||
| BI | 743 | Alarm 17:3 Rotary heat exchanger defrost pressure above alarm limit | Read | |||
| BI | 744 | Alarm 17:4 Rotary heat exchanger speed monitor tripped | Read | |||
| BI | 745 | Alarm 17:5 Rotary heat exchanger motor controller over current | Read | |||
| BI | 746 | Alarm 17:6 Rotary heat exchanger motor controller under voltage | Read | |||
| BI | 747 | Alarm 17:7 Rotary heat exchanger motor controller over voltage | Read | |||
| BI | 748 | Alarm 17:8 Rotary heat exchanger motor controller over temperature | Read | |||
| BI | 749 | Alarm 17:9 Rotary heat exchanger motor controller start error | Read | |||
| BI | 756 | Alarm 18:1 AYC I/O-module no. 7 com. error | Read | |||
| BI | 757 | Alarm 18:2 AYC heat temperature sensor defective | Read | |||
| BI | 758 | Alarm 18:3 AYC heat valve monitor tripped | Read | |||
| BI | 759 | Alarm 18:4 AYC heat pump monitor tripped | Read | |||
| BI | 760 | Alarm 18:5 AYC heat temperature below set point alarm limit | Read | |||
| BI | 761 | Alarm 18:6 AYC heat temperature above set point alarm limit | Read | |||
| BI | 764 | Alarm 18:9 AYC cool temperature sensor defective | Read | |||
| BI | 765 | Alarm 18:10 AYC cool valve monitor tripped | Read | |||
| BI | 766 | Alarm 18:11 AYC cool pump monitor tripped | Read | |||
| BI | 767 | Alarm 18:12 AYC cool temperature below set point alarm limit | Read | |||
| BI | 768 | Alarm 18:13 AYC cool temperature above set point alarm limit | Read | |||
| BI | 801 | Alarm 21:1 COOL DX I/O-module no. 2 com. error | Read | |||
| BI | 802 | Alarm 21:2 COOL DX compressor no. 1 low pressure sensor defective | Read | |||
| BI | 803 | Alarm 21:3 COOL DX compressor no. 1 low pressure below alarm limit | Read | |||
| BI | 804 | Alarm 21:4 COOL DX compressor no. 1 high pressure sensor defective | Read | |||
| BI | 805 | Alarm 21:5 COOL DX compressor no. 1 high pressure above alarm limit | Read | |||
| BI | 806 | Alarm 21:6 COOL DX compressor no. 1 monitor tripped | Read | |||
| BI | 807 | Alarm 21:7 COOL DX compressor no. 1 restart error | Read | |||
| BI | 808 | Alarm 21:8 COOL DX compressor no. 2 low pressure sensor defective | Read | |||
| BI | 809 | Alarm 21:9 COOL DX compressor no. 2 low pressure below alarm limit | Read | |||
| BI | 810 | Alarm 21:10 COOL DX compressor no. 2 high pressure sensor defective | Read | |||
| BI | 811 | Alarm 21:11 COOL DX compressor no. 2 high pressure above alarm limit | Read | |||
| BI | 812 | Alarm 21:12 COOL DX compressor no. 2 monitor tripped | Read | |||
| BI | 813 | Alarm 21:13 COOL DX compressor no. 2 restart error | Read | |||
| BI | 814 | Alarm 21:14 COOL DX outdoor air temperature sensor defective | Read | |||
| BI | 815 | Alarm 21:15 COOL DX phase sequence error | Read | |||
| BI | 831 | Alarm 23:1 SMART Link com. error | Read | |||
| BI | 832 | Alarm 23:2 SMART Link alarm level 1 tripped | Read | |||
| BI | 833 | Alarm 23:3 SMART Link alarm level 2 tripped | Read | |||
| BI | 834 | Alarm 23:4 SMART Link alarm level 3 tripped | Read | |||
| BI | 840 | Alarm 23:10 AQUA Link I/O-module no. 5 com. error | Read | |||
| BI | 841 | Alarm 23:11 AQUA Link pump monitor tripped | Read | |||
| BI | 846 | Alarm 24:1 SMART Link no. 1 com. error | Read | |||
| BI | 847 | Alarm 24:2 SMART Link no. 1 alarm tripped | Read | |||
| BI | 849 | Alarm 24:4 SMART Link no. 2 com. error | Read | |||
| BI | 850 | Alarm 24:5 SMART Link no. 2 alarm tripped | Read | |||
| BI | 852 | Alarm 24:7 SMART Link no. 3 com. error | Read | |||
| BI | 853 | Alarm 24:8 SMART Link no. 3 alarm tripped | Read | |||
| BI | 855 | Alarm 24:10 SMART Link no. 4 com. error | Read | |||
| BI | 856 | Alarm 24:11 SMART Link no. 4 alarm tripped | Read | |||
| BI | 876 | Alarm 26:1 Pre-filter supply air pressure sensor no.8 com. error | Read | |||
| BI | 877 | Alarm 26:2 Pre-filter supply air dirty | Read | |||
| BI | 882 | Alarm 26:7 Pre-filter extract air pressure sensor no.9 com. error | Read | |||
| BI | 883 | Alarm 26:8 Pre-filter extract air dirty | Read | |||
| BI | 891 | Alarm 27:1 AHU filter supply air pressure sensor no. 3/4 com. error | Read | |||
| BI | 892 | Alarm 27:2 AHU filter supply air dirty | Read | |||
| BI | 897 | Alarm 27:7 AHU filter extract air pressure sensor no. 3/4 com. error | Read | |||
| BI | 898 | Alarm 27:8 AHU filter extract air dirty | Read | |||
| BI | 906 | Alarm 28:1 End filter supply air pressure sensor no. A com. error | Read | |||
| BI | 907 | Alarm 28:2 End filter supply air dirty | Read | |||
| BI | 936 | Alarm 30:1 Air flow measurement supply air pressure sensor no. 1/2 com. error | Read | |||
| BI | 937 | Alarm 30:2 Air flow measurement supply air flow below set point alarm limit | Read | |||
| BI | 938 | Alarm 30:3 Air flow measurement supply air flow above set point alarm limit | Read | |||
| BI | 941 | Alarm 30:6 Air flow measurement extract air pressure sensor no. 1/2 com. error | Read | |||
| BI | 942 | Alarm 30:7 Air flow measurement extract air flow below set point alarm limit | Read | |||
| BI | 943 | Alarm 30:8 Air flow measurement extract air flow above set point alarm limit | Read | |||
| BI | 946 | Alarm 30:11 Air flow meas. carry over control press. sensor no. B com. error | Read | |||
| BI | 951 | Alarm 31:1 Pressure regulation supply air pressure sensor no. 5 com. error | Read | |||
| BI | 952 | Alarm 31:2 Pressure regulation supply air pressure below set point alarm limit | Read | |||
| BI | 953 | Alarm 31:3 Pressure regulation supply air pressure above set point alarm limit | Read | |||
| BI | 956 | Alarm 31:6 Pressure regulation extract air pressure sensor no. 6 com. error | Read | |||
| BI | 957 | Alarm 31:7 Pressure regulation extract air press. below set point alarm limit | Read | |||
| BI | 958 | Alarm 31:8 Pressure regulation extract air press. above set point alarm limit | Read | |||
| BI | 966 | Alarm 32:1 ReCO2 I/O-module no. 0 com. error | Read | |||
| BI | 967 | Alarm 32:2 ReCO2 pressure sensor no. 0 com. error | Read | |||
| BI | 968 | Alarm 32:3 ReCO2 recirculation damper monitoring tripped | Read | |||
| BI | 969 | Alarm 32:4 ReCO2 outdoor air damper monitoring tripped | Read | |||
| BI | 981 | Alarm 33:1 Service period above alarm limit | Read | |||
| BI | 995 | Alarm 33:15 Lock function tripped | Read | |||
| BI | 996 | Alarm 34:1 External control I/O-module no. 3 com. error | Read | |||
| BI | 997 | Alarm 34:2 External control I/O-module no. 6 com. error | Read | |||
| BI | 1011 | Alarm 35:1 Booster diffusers I/O-module no. 8 com. error | Read | |||
| BI | 1056 | Alarm 38:1 MIRU 1 com. error | Read | |||
| BI | 1057 | Alarm 38:2 MIRU 1 motor controller alarm tripped | Read | |||
| BI | 1058 | Alarm 38:3 MIRU 1 motor controller com. error | Read | |||
| BI | 1059 | Alarm 38:4 MIRU 1 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1060 | Alarm 38:5 MIRU 1 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1061 | Alarm 38:6 MIRU 1 temperature sensor defective | Read | |||
| BI | 1062 | Alarm 38:7 MIRU 1 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1071 | Alarm 39:1 MIRU 2 com. error | Read | |||
| BI | 1072 | Alarm 39:2 MIRU 2 motor controller alarm tripped | Read | |||
| BI | 1073 | Alarm 39:3 MIRU 2 motor controller com. error | Read | |||
| BI | 1074 | Alarm 39:4 MIRU 2 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1075 | Alarm 39:5 MIRU 2 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1076 | Alarm 39:6 MIRU 2 temperature sensor defective | Read | |||
| BI | 1077 | Alarm 39:7 MIRU 2 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1086 | Alarm 40:1 MIRU 3 com. error | Read | |||
| BI | 1087 | Alarm 40:2 MIRU 3 motor controller alarm tripped | Read | |||
| BI | 1088 | Alarm 40:3 MIRU 3 motor controller com. error | Read | |||
| BI | 1089 | Alarm 40:4 MIRU 3 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1090 | Alarm 40:5 MIRU 3 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1091 | Alarm 40:6 MIRU 3 temperature sensor defective | Read | |||
| BI | 1092 | Alarm 40:7 MIRU 3 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1101 | Alarm 41:1 MIRU 4 com. error | Read | |||
| BI | 1102 | Alarm 41:2 MIRU 4 motor controller alarm tripped | Read | |||
| BI | 1103 | Alarm 41:3 MIRU 4 motor controller com. error | Read | |||
| BI | 1104 | Alarm 41:4 MIRU 4 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1105 | Alarm 41:5 MIRU 4 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1106 | Alarm 41:6 MIRU 4 temperature sensor defective | Read | |||
| BI | 1107 | Alarm 41:7 MIRU 4 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1116 | Alarm 42:1 MIRU 5 com. error | Read | |||
| BI | 1117 | Alarm 42:2 MIRU 5 motor controller alarm tripped | Read | |||
| BI | 1118 | Alarm 42:3 MIRU 5 motor controller com. error | Read | |||
| BI | 1119 | Alarm 42:4 MIRU 5 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1120 | Alarm 42:5 MIRU 5 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1121 | Alarm 42:6 MIRU 5 temperature sensor defective | Read | |||
| BI | 1122 | Alarm 42:7 MIRU 5 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1131 | Alarm 43:1 MIRU 6 com. error | Read | |||
| BI | 1132 | Alarm 43:2 MIRU 6 motor controller alarm tripped | Read | |||
| BI | 1133 | Alarm 43:3 MIRU 6 motor controller com. error | Read | |||
| BI | 1134 | Alarm 43:4 MIRU 6 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1135 | Alarm 43:5 MIRU 6 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1136 | Alarm 43:6 MIRU 6 temperature sensor defective | Read | |||
| BI | 1137 | Alarm 43:7 MIRU 6 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1146 | Alarm 44:1 MIRU 7 com. error | Read | |||
| BI | 1147 | Alarm 44:2 MIRU 7 motor controller alarm tripped | Read | |||
| BI | 1148 | Alarm 44:3 MIRU 7 motor controller com. error | Read | |||
| BI | 1149 | Alarm 44:4 MIRU 7 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1150 | Alarm 44:5 MIRU 7 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1151 | Alarm 44:6 MIRU 7 temperature sensor defective | Read | |||
| BI | 1152 | Alarm 44:7 MIRU 7 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1161 | Alarm 45:1 MIRU 8 com. error | Read | |||
| BI | 1162 | Alarm 45:2 MIRU 8 motor controller alarm tripped | Read | |||
| BI | 1163 | Alarm 45:3 MIRU 8 motor controller com. error | Read | |||
| BI | 1164 | Alarm 45:4 MIRU 8 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1165 | Alarm 45:5 MIRU 8 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1166 | Alarm 45:6 MIRU 8 temperature sensor defective | Read | |||
| BI | 1167 | Alarm 45:7 MIRU 8 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1176 | Alarm 46:1 MIRU 9 com. error | Read | |||
| BI | 1177 | Alarm 46:2 MIRU 9 motor controller alarm tripped | Read | |||
| BI | 1178 | Alarm 46:3 MIRU 9 motor controller com. error | Read | |||
| BI | 1179 | Alarm 46:4 MIRU 9 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1180 | Alarm 46:5 MIRU 9 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1181 | Alarm 46:6 MIRU 9 temperature sensor defective | Read | |||
| BI | 1182 | Alarm 46:7 MIRU 9 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1191 | Alarm 47:1 MIRU 10 com. error | Read | |||
| BI | 1192 | Alarm 47:2 MIRU 10 motor controller alarm tripped | Read | |||
| BI | 1193 | Alarm 47:3 MIRU 10 motor controller com. error | Read | |||
| BI | 1194 | Alarm 47:4 MIRU 10 air flow pressure sensor no. 0 com. error | Read | |||
| BI | 1195 | Alarm 47:5 MIRU 10 pressure regulation sensor no. 1 com. error | Read | |||
| BI | 1196 | Alarm 47:6 MIRU 10 temperature sensor defective | Read | |||
| BI | 1197 | Alarm 47:7 MIRU 10 air flow/pressure set point deviation from alarm limit | Read | |||
| BI | 1221 | Alarm 49:1 Supply air fan no. 1A com. error | Read | |||
| BI | 1222 | Alarm 49:2 Supply air fan no. 1A motor controller over current | Read | |||
| BI | 1223 | Alarm 49:3 Supply air fan no. 1A motor controller under voltage | Read | |||
| BI | 1224 | Alarm 49:4 Supply air fan no. 1A motor controller over voltage | Read | |||
| BI | 1225 | Alarm 49:5 Supply air fan no. 1A motor controller over temperature | Read | |||
| BI | 1226 | Alarm 49:6 Supply air fan no. 1A motor controller start error | Read | |||
| BI | 1227 | Alarm 49:7 Supply air fan no. 1A motor controller ripple error | Read | |||
| BI | 1228 | Alarm 49:8 Supply air fan no. 1A motor controller phase error | Read | |||
| BI | 1229 | Alarm 49:9 Supply air fan no. 1A motor controller internal memory error | Read | |||
| BI | 1230 | Alarm 49:10 Supply air fan no. 1A motor controller current reduction | Read | |||
| BI | 1236 | Alarm 50:1 Supply air fan no. 2A com. error | Read | |||
| BI | 1237 | Alarm 50:2 Supply air fan no. 2A motor controller over current | Read | |||
| BI | 1238 | Alarm 50:3 Supply air fan no. 2A motor controller under voltage | Read | |||
| BI | 1239 | Alarm 50:4 Supply air fan no. 2A motor controller over voltage | Read | |||
| BI | 1240 | Alarm 50:5 Supply air fan no. 2A motor controller over temperature | Read | |||
| BI | 1241 | Alarm 50:6 Supply air fan no. 2A motor controller start error | Read | |||
| BI | 1242 | Alarm 50:7 Supply air fan no. 2A motor controller ripple error | Read | |||
| BI | 1243 | Alarm 50:8 Supply air fan no. 2A motor controller phase error | Read | |||
| BI | 1244 | Alarm 50:9 Supply air fan no. 2A motor controller internal memory error | Read | |||
| BI | 1245 | Alarm 50:10 Supply air fan no. 2A motor controller current reduction | Read | |||
| BI | 1251 | Alarm 51:1 Supply air fan no. 3A com. error | Read | |||
| BI | 1252 | Alarm 51:2 Supply air fan no. 3A motor controller over current | Read | |||
| BI | 1253 | Alarm 51:3 Supply air fan no. 3A motor controller under voltage | Read | |||
| BI | 1254 | Alarm 51:4 Supply air fan no. 3A motor controller over voltage | Read | |||
| BI | 1255 | Alarm 51:5 Supply air fan no. 3A motor controller over temperature | Read | |||
| BI | 1256 | Alarm 51:6 Supply air fan no. 3A motor controller start error | Read | |||
| BI | 1257 | Alarm 51:7 Supply air fan no. 3A motor controller ripple error | Read | |||
| BI | 1258 | Alarm 51:8 Supply air fan no. 3A motor controller phase error | Read | |||
| BI | 1259 | Alarm 51:9 Supply air fan no. 3A motor controller internal memory error | Read | |||
| BI | 1260 | Alarm 51:10 Supply air fan no. 3A motor controller current reduction | Read | |||
| BI | 1266 | Alarm 52:1 Supply air fan no. 1B com. error | Read | |||
| BI | 1267 | Alarm 52:2 Supply air fan no. 1B motor controller over current | Read | |||
| BI | 1268 | Alarm 52:3 Supply air fan no. 1B motor controller under voltage | Read | |||
| BI | 1269 | Alarm 52:4 Supply air fan no. 1B motor controller over voltage | Read | |||
| BI | 1270 | Alarm 52:5 Supply air fan no. 1B motor controller over temperature | Read | |||
| BI | 1271 | Alarm 52:6 Supply air fan no. 1B motor controller start error | Read | |||
| BI | 1272 | Alarm 52:7 Supply air fan no. 1B motor controller ripple error | Read | |||
| BI | 1273 | Alarm 52:8 Supply air fan no. 1B motor controller phase error | Read | |||
| BI | 1274 | Alarm 52:9 Supply air fan no. 1B motor controller internal memory error | Read | |||
| BI | 1275 | Alarm 52:10 Supply air fan no. 1B motor controller current reduction | Read | |||
| BI | 1281 | Alarm 53:1 Supply air fan no. 2B com. error | Read | |||
| BI | 1282 | Alarm 53:2 Supply air fan no. 2B motor controller over current | Read | |||
| BI | 1283 | Alarm 53:3 Supply air fan no. 2B motor controller under voltage | Read | |||
| BI | 1284 | Alarm 53:4 Supply air fan no. 2B motor controller over voltage | Read | |||
| BI | 1285 | Alarm 53:5 Supply air fan no. 2B motor controller over temperature | Read | |||
| BI | 1286 | Alarm 53:6 Supply air fan no. 2B motor controller start error | Read | |||
| BI | 1287 | Alarm 53:7 Supply air fan no. 2B motor controller ripple error | Read | |||
| BI | 1288 | Alarm 53:8 Supply air fan no. 2B motor controller phase error | Read | |||
| BI | 1289 | Alarm 53:9 Supply air fan no. 2B motor controller internal memory error | Read | |||
| BI | 1290 | Alarm 53:10 Supply air fan no. 2B motor controller current reduction | Read | |||
| BI | 1296 | Alarm 54:1 Supply air fan no. 3B com. error | Read | |||
| BI | 1297 | Alarm 54:2 Supply air fan no. 3B motor controller over current | Read | |||
| BI | 1298 | Alarm 54:3 Supply air fan no. 3B motor controller under voltage | Read | |||
| BI | 1299 | Alarm 54:4 Supply air fan no. 3B motor controller over voltage | Read | |||
| BI | 1300 | Alarm 54:5 Supply air fan no. 3B motor controller over temperature | Read | |||
| BI | 1301 | Alarm 54:6 Supply air fan no. 3B motor controller start error | Read | |||
| BI | 1302 | Alarm 54:7 Supply air fan no. 3B motor controller ripple error | Read | |||
| BI | 1303 | Alarm 54:8 Supply air fan no. 3B motor controller phase error | Read | |||
| BI | 1304 | Alarm 54:9 Supply air fan no. 3B motor controller internal memory error | Read | |||
| BI | 1305 | Alarm 54:10 Supply air fan no. 3B motor controller current reduction | Read | |||
| BI | 1311 | Alarm 55:1 Extract air fan no. 1A com. error | Read | |||
| BI | 1312 | Alarm 55:2 Extract air fan no. 1A motor controller over current | Read | |||
| BI | 1313 | Alarm 55:3 Extract air fan no. 1A motor controller under voltage | Read | |||
| BI | 1314 | Alarm 55:4 Extract air fan no. 1A motor controller over voltage | Read | |||
| BI | 1315 | Alarm 55:5 Extract air fan no. 1A motor controller over temperature | Read | |||
| BI | 1316 | Alarm 55:6 Extract air fan no. 1A motor controller start error | Read | |||
| BI | 1317 | Alarm 55:7 Extract air fan no. 1A motor controller ripple error | Read | |||
| BI | 1318 | Alarm 55:8 Extract air fan no. 1A motor controller phase error | Read | |||
| BI | 1319 | Alarm 55:9 Extract air fan no. 1A motor controller internal memory error | Read | |||
| BI | 1320 | Alarm 55:10 Extract air fan no. 1A motor controller current reduction | Read | |||
| BI | 1326 | Alarm 56:1 Extract air fan no. 2A com. error | Read | |||
| BI | 1327 | Alarm 56:2 Extract air fan no. 2A motor controller over current | Read | |||
| BI | 1328 | Alarm 56:3 Extract air fan no. 2A motor controller under voltage | Read | |||
| BI | 1329 | Alarm 56:4 Extract air fan no. 2A motor controller over voltage | Read | |||
| BI | 1330 | Alarm 56:5 Extract air fan no. 2A motor controller over temperature | Read | |||
| BI | 1331 | Alarm 56:6 Extract air fan no. 2A motor controller start error | Read | |||
| BI | 1332 | Alarm 56:7 Extract air fan no. 2A motor controller ripple error | Read | |||
| BI | 1333 | Alarm 56:8 Extract air fan no. 2A motor controller phase error | Read | |||
| BI | 1334 | Alarm 56:9 Extract air fan no. 2A motor controller internal memory error | Read | |||
| BI | 1335 | Alarm 56:10 Extract air fan no. 2A motor controller current reduction | Read | |||
| BI | 1341 | Alarm 57:1 Extract air fan no. 3A com. error | Read | |||
| BI | 1342 | Alarm 57:2 Extract air fan no. 3A motor controller over current | Read | |||
| BI | 1343 | Alarm 57:3 Extract air fan no. 3A motor controller under voltage | Read | |||
| BI | 1344 | Alarm 57:4 Extract air fan no. 3A motor controller over voltage | Read | |||
| BI | 1345 | Alarm 57:5 Extract air fan no. 3A motor controller over temperature | Read | |||
| BI | 1346 | Alarm 57:6 Extract air fan no. 3A motor controller start error | Read | |||
| BI | 1347 | Alarm 57:7 Extract air fan no. 3A motor controller ripple error | Read | |||
| BI | 1348 | Alarm 57:8 Extract air fan no. 3A motor controller phase error | Read | |||
| BI | 1349 | Alarm 57:9 Extract air fan no. 3A motor controller internal memory error | Read | |||
| BI | 1350 | Alarm 57:10 Extract air fan no. 3A motor controller current reduction | Read | |||
| BI | 1356 | Alarm 58:1 Extract air fan no. 1B com. error | Read | |||
| BI | 1357 | Alarm 58:2 Extract air fan no. 1B motor controller over current | Read | |||
| BI | 1358 | Alarm 58:3 Extract air fan no. 1B motor controller under voltage | Read | |||
| BI | 1359 | Alarm 58:4 Extract air fan no. 1B motor controller over voltage | Read | |||
| BI | 1360 | Alarm 58:5 Extract air fan no. 1B motor controller over temperature | Read | |||
| BI | 1361 | Alarm 58:6 Extract air fan no. 1B motor controller start error | Read | |||
| BI | 1362 | Alarm 58:7 Extract air fan no. 1B motor controller ripple error | Read | |||
| BI | 1363 | Alarm 58:8 Extract air fan no. 1B motor controller phase error | Read | |||
| BI | 1364 | Alarm 58:9 Extract air fan no. 1B motor controller internal memory error | Read | |||
| BI | 1365 | Alarm 58:10 Extract air fan no. 1B motor controller current reduction | Read | |||
| BI | 1371 | Alarm 59:1 Extract air fan no. 2B com. error | Read | |||
| BI | 1372 | Alarm 59:2 Extract air fan no. 2B motor controller over current | Read | |||
| BI | 1373 | Alarm 59:3 Extract air fan no. 2B motor controller under voltage | Read | |||
| BI | 1374 | Alarm 59:4 Extract air fan no. 2B motor controller over voltage | Read | |||
| BI | 1375 | Alarm 59:5 Extract air fan no. 2B motor controller over temperature | Read | |||
| BI | 1376 | Alarm 59:6 Extract air fan no. 2B motor controller start error | Read | |||
| BI | 1377 | Alarm 59:7 Extract air fan no. 2B motor controller ripple error | Read | |||
| BI | 1378 | Alarm 59:8 Extract air fan no. 2B motor controller phase error | Read | |||
| BI | 1379 | Alarm 59:9 Extract air fan no. 2B motor controller internal memory error | Read | |||
| BI | 1380 | Alarm 59:10 Extract air fan no. 2B motor controller current reduction | Read | |||
| BI | 1386 | Alarm 60:1 Extract air fan no. 3B com. error | Read | |||
| BI | 1387 | Alarm 60:2 Extract air fan no. 3B motor controller over current | Read | |||
| BI | 1388 | Alarm 60:3 Extract air fan no. 3B motor controller under voltage | Read | |||
| BI | 1389 | Alarm 60:4 Extract air fan no. 3B motor controller over voltage | Read | |||
| BI | 1390 | Alarm 60:5 Extract air fan no. 3B motor controller over temperature | Read | |||
| BI | 1391 | Alarm 60:6 Extract air fan no. 3B motor controller start error | Read | |||
| BI | 1392 | Alarm 60:7 Extract air fan no. 3B motor controller ripple error | Read | |||
| BI | 1393 | Alarm 60:8 Extract air fan no. 3B motor controller phase error | Read | |||
| BI | 1394 | Alarm 60:9 Extract air fan no. 3B motor controller internal memory error | Read | |||
| BI | 1395 | Alarm 60:10 Extract air fan no. 3B motor controller current reduction | Read | |||
| BI | 1952 | Info 97:12 Plate heat exchanger bypass optimization not performed | Read | |||
| BI | 1953 | Info 97:13 Plate heat exchanger bypass optimization not approved | Read | |||
| BI | 1954 | Info 97:14 Plate heat exchanger defrost calibration not performed | Read | |||
| BI | 1955 | Info 97:15 Plate heat exchanger defrost calibration not approved | Read | |||
| BI | 1956 | Info 98:1 Supply air pre-filter calibration not performed | Read | |||
| BI | 1957 | Info 98:2 Supply air pre-filter calibration not approved | Read | |||
| BI | 1958 | Info 98:3 Extract air pre-filter calibration not performed | Read | |||
| BI | 1959 | Info 98:4 Extract air pre-filter calibration not approved | Read | |||
| BI | 1960 | Info 98:5 Supply air air handling unit filter calibration not performed | Read | |||
| BI | 1961 | Info 98:6 Supply air air handling unit filter calibration not approved | Read | |||
| BI | 1962 | Info 98:7 Extract air air handling unit filter calibration not performed | Read | |||
| BI | 1963 | Info 98:8 Extract air air handling unit filter calibration not approved | Read | |||
| BI | 1964 | Info 98:9 Supply air end filter calibration not performed | Read | |||
| BI | 1965 | Info 98:10 Supply air end filter calibration not approved | Read | |||
| BI | 1966 | Info 98:11 Rotary heat exchanger defrost calibration not performed | Read | |||
| BI | 1967 | Info 98:12 Rotary heat exchanger defrost calibration not approved | Read | |||
| BI | 1968 | Info 98:13 ReCO2 calibration not performed | Read | |||
| BI | 1969 | Info 98:14 ReCO2 calibration not approved | Read | |||
| BI | 1970 | Info 98:15 ReCO2 incorrect setting | Read | |||
| BI | 1971 | Info 99:1 E-mail error | Read | |||
| BI | 1977 | Info 99:7 SD card memory soon full. Oldest log data will soon be deleted | Read | |||
| BI | 1978 | Info 99:8 SD card memory full. Oldest log data deleted | Read | |||
| BI | 1984 | Info 99:14 Internal serial memory error CPU 1 | Read | |||
| BI | 1985 | Info 99:15 Clock circuit defective | Read | |||
| BI | 2001 | Active alarm group 1 | Read | |||
| BI | 2002 | Active alarm group 2 | Read | |||
| BI | 2003 | Active alarm group 3 | Read | |||
| BI | 2004 | Active alarm group 4 | Read | |||
| BI | 2005 | Active alarm group 5 | Read | |||
| BI | 2006 | Active alarm group 6 | Read | |||
| BI | 2007 | Active alarm group 7 | Read | |||
| BI | 2008 | Active alarm group 8 | Read | |||
| BI | 2009 | Active alarm group 9 | Read | |||
| BI | 2010 | Active alarm group 10 | Read | |||
| BI | 2011 | Active alarm group 11 | Read | |||
| BI | 2012 | Active alarm group 12 | Read | |||
| BI | 2013 | Active alarm group 13 | Read | |||
| BI | 2014 | Active alarm group 14 | Read | |||
| BI | 2015 | Active alarm group 15 | Read | |||
| BI | 2016 | Active alarm group 16 | Read | |||
| BI | 2017 | Active alarm group 17 | Read | |||
| BI | 2018 | Active alarm group 18 | Read | |||
| BI | 2019 | Active alarm group 19 | Read | |||
| BI | 2020 | Active alarm group 20 | Read | |||
| BI | 2021 | Active alarm group 21 | Read | |||
| BI | 2022 | Active alarm group 22 | Read | |||
| BI | 2023 | Active alarm group 23 | Read | |||
| BI | 2024 | Active alarm group 24 | Read | |||
| BI | 2025 | Active alarm group 25 | Read | |||
| BI | 2026 | Active alarm group 26 | Read | |||
| BI | 2027 | Active alarm group 27 | Read | |||
| BI | 2028 | Active alarm group 28 | Read | |||
| BI | 2029 | Active alarm group 29 | Read | |||
| BI | 2030 | Active alarm group 30 | Read | |||
| BI | 2031 | Active alarm group 31 | Read | |||
| BI | 2032 | Active alarm group 32 | Read | |||
| BI | 2033 | Active alarm group 33 | Read | |||
| BI | 2034 | Active alarm group 34 | Read | |||
| BI | 2035 | Active alarm group 35 | Read | |||
| BI | 2036 | Active alarm group 36 | Read | |||
| BI | 2037 | Active alarm group 37 | Read | |||
| BI | 2038 | Active alarm group 38 | Read | |||
| BI | 2039 | Active alarm group 39 | Read | |||
| BI | 2040 | Active alarm group 40 | Read | |||
| BI | 2041 | Active alarm group 41 | Read | |||
| BI | 2042 | Active alarm group 42 | Read | |||
| BI | 2043 | Active alarm group 43 | Read | |||
| BI | 2044 | Active alarm group 44 | Read | |||
| BI | 2045 | Active alarm group 45 | Read | |||
| BI | 2046 | Active alarm group 46 | Read | |||
| BI | 2047 | Active alarm group 47 | Read | |||
| BI | 2048 | Active alarm group 48 | Read | |||
| BI | 2049 | Active alarm group 49 | Read | |||
| BI | 2050 | Active alarm group 50 | Read | |||
| BI | 2051 | Active alarm group 51 | Read | |||
| BI | 2052 | Active alarm group 52 | Read | |||
| BI | 2053 | Active alarm group 53 | Read | |||
| BI | 2054 | Active alarm group 54 | Read | |||
| BI | 2055 | Active alarm group 55 | Read | |||
| BI | 2056 | Active alarm group 56 | Read | |||
| BI | 2057 | Active alarm group 57 | Read | |||
| BI | 2058 | Active alarm group 58 | Read | |||
| BI | 2059 | Active alarm group 59 | Read | |||
| BI | 2060 | Active alarm group 60 | Read | |||
| BI | 2061 | Active alarm group 61 | Read | |||
| BI | 2062 | Active alarm group 62 | Read | |||
| BI | 2063 | Active alarm group 63 | Read | |||
| BI | 2064 | Active alarm group 64 | Read | |||
| BI | 2065 | Active alarm group 65 | Read | |||
| BI | 2066 | Active alarm group 66 | Read | |||
| BI | 2067 | Active alarm group 67 | Read | |||
| BI | 2068 | Active alarm group 68 | Read | |||
| BI | 2069 | Active alarm group 69 | Read | |||
| BI | 2070 | Active alarm group 70 | Read | |||
| BI | 2071 | Active alarm group 71 | Read | |||
| BI | 2072 | Active alarm group 72 | Read | |||
| BI | 2073 | Active alarm group 73 | Read | |||
| BI | 2074 | Active alarm group 74 | Read | |||
| BI | 2075 | Active alarm group 75 | Read | |||
| BI | 2076 | Active alarm group 76 | Read | |||
| BI | 2077 | Active alarm group 77 | Read | |||
| BI | 2078 | Active alarm group 78 | Read | |||
| BI | 2079 | Active alarm group 79 | Read | |||
| BI | 2080 | Active alarm group 80 | Read | |||
| BI | 2081 | Active alarm group 81 | Read | |||
| BI | 2082 | Active alarm group 82 | Read | |||
| BI | 2083 | Active alarm group 83 | Read | |||
| BI | 2084 | Active alarm group 84 | Read | |||
| BI | 2085 | Active alarm group 85 | Read | |||
| BI | 2086 | Active alarm group 86 | Read | |||
| BI | 2087 | Active alarm group 87 | Read | |||
| BI | 2088 | Active alarm group 88 | Read | |||
| BI | 2089 | Active alarm group 89 | Read | |||
| BI | 2090 | Active alarm group 90 | Read | |||
| BI | 2091 | Active alarm group 91 | Read | |||
| BI | 2092 | Active alarm group 92 | Read | |||
| BI | 2093 | Active alarm group 93 | Read | |||
| BI | 2094 | Active alarm group 94 | Read | |||
| BI | 2095 | Active alarm group 95 | Read | |||
| BI | 2096 | Active alarm group 96 | Read | |||
| BI | 2097 | Active alarm group 97 | Read | |||
| BI | 2098 | Active alarm group 98 | Read | |||
| BI | 2099 | Active alarm group 99 | Read | |||
| BO | 1 | Booster diffusers | Booster diffusers function. | Write | ||
| BVmin | 1 | Alarm reset | Resets all active alarms | Write | ||
| BV | 3 | Internal fire alarm function | Write | |||
| BV | 29 | SA flow pressure sensor auto zero calibration | Write | |||
| BV | 30 | EA flow pressure sensor auto zero calibration | Write | |||
| BV | 31 | SA duct pressure sensor auto zero calibration | Write | |||
| BV | 32 | EA duct pressure sensor auto zero calibration | Write | |||
| BV | 33 | ReCO2 pressure sensor auto zero calibration | Write | |||
| BV | 34 | RHX defrost pressure sensor auto calibration | Write | |||
| BV | 35 | Carry over control pressure sensor auto calibration | Write | |||
| BV | 36 | SA filter pressure sensor auto zero calibration | Write | |||
| BV | 37 | EA filter pressure sensor auto zero calibration | Write | |||
| BV | 38 | SA pre-filter pressure sensor auto zero calibration | Write | |||
| BV | 39 | EA pre-filter pressure sensor auto zero calibration | Write | |||
| BV | 40 | SA end-filter pressure sensor auto zero calibration | Write | |||
| BV | 46 | SA flow pressure sensor activate zero calibration | If value is set to 1 for min 1s calibration will be | Write | ||
| BV | 47 | EA flow pressure sensor activate zero calibration | Write | |||
| BV | 48 | SA duct pressure sensor activate zero calibration | Write | |||
| BV | 49 | EA duct pressure sensor activate zero calibration | Write | |||
| BV | 50 | ReCO2 pressure sensor activate calibration | Write | |||
| BV | 51 | RHX Defrost pressure sensor activate calibration | Write | |||
| BV | 52 | Carry over control pressure sensor activate zero calibration | Write | |||
| BV | 53 | SA filter pressure sensor activate zero calibration | Write | |||
| BV | 54 | EA filter pressure sensor activate zero calibration | Write | |||
| BV | 55 | SA pre-filter pressure sensor activate zero calibration | Write | |||
| BV | 56 | EA pre-filter pressure sensor activate zero calibration | Write | |||
| BV | 57 | SA end-filter pressure sensor activate zero calibration | Write | |||
| BV | 162 | External room sensor 1 function | Write | |||
| BV | 163 | External room sensor 2 function | Write | |||
| BV | 164 | External room sensor 3 function | Write | |||
| BV | 165 | External room sensor 4 function | Write | |||
| BV | 167 | External room temp from BMS function | Write | |||
| BV | 172 | External OA sensor 1 function | Write | |||
| BV | 173 | External OA sensor 2 function | Write | |||
| BV | 174 | External OA sensor 3 function | Write | |||
| BV | 175 | External OA sensor 4 function | Write | |||
| BV | 177 | External OA temp from BMS function | Write | |||
| BV | 182 | RHX defrost function | Setting for activating the defrost function for the rotary heat | Write | ||
| BV | 183 | RHX defrost calibration | Write | |||
| BV | 187 | RHX carry over control function | Setting for activating the carry over control function for the rotary heat | Write | ||
| BV | 190 | RHX min exhaust air temp function | Write | |||
| BV | 198 | PHX periodic operation of bypass damper function | Write | |||
| BV | 201 | PX bypass optimize | Write | |||
| BV | 205 | CHX periodic operation of pump function | Write | |||
| BV | 206 | CHX periodic operation of valve function | Write | |||
| BV | 228 | Re-heat periodic operation of pump function | Write | |||
| BV | 229 | Re-heat periodic operation of valve function | Write | |||
| BV | 245 | Extra regulation 1 periodic operation of pump function | Write | |||
| BV | 246 | Extra regulation 1 periodic operation of valve function | Write | |||
| BV | 274 | Cool relay 1 periodic operation of pump function | Write | |||
| BV | 275 | Cool relay 2 periodic operation of pump function | Write | |||
| BV | 276 | Cool periodic operation of valve function | Write | |||
| BV | 284 | Summer night cool function | Write | |||
| BV | 296 | Intermittent night heat function | Write | |||
| BV | 302 | Intermittent night heat recirculation function | Write | |||
| BV | 305 | Morning boost function | Write | |||
| BV | 320 | Heating boost function | Write | |||
| BV | 325 | Xzone heat function | Write | |||
| BV | 327 | Xzone cool function | Write | |||
| BV | 374 | Xzone external room sensor 1 function | Write | |||
| BV | 375 | Xzone external room sensor 2 function | Write | |||
| BV | 376 | Xzone external room sensor 3 function | Write | |||
| BV | 377 | Xzone external room sensor 4 function | Write | |||
| BV | 379 | Xzone external room temp from BMS function | Write | |||
| BV | 386 | Xzone reheat periodic operation of pump function | Write | |||
| BV | 387 | Xzone reheat periodic operation of valve function | Write | |||
| BV | 400 | Xzone Cool relay 1 periodic operation of pump function | Write | |||
| BV | 401 | Xzone Cool relay 2 periodic operation of pump function | Write | |||
| BV | 402 | Xzone Cool periodic operation of valve function | Write | |||
| BV | 410 | Pre-heat function | Write | |||
| BV | 414 | Pre-heat periodic operation of pump function | Write | |||
| BV | 415 | Pre-heat periodic operation of valve function | Write | |||
| BV | 425 | ReCO2 Calibration | Write | |||
| BV | 457 | Dehumidifying function | Moved to Multistate Value 457 | Write | ||
| BV | 459 | Heat exchange active in dehumidifying sequence | Write | |||
| BV | 465 | VOC sensor function | Write | |||
| BV | 490 | SMART Link WB Optimize function | Write | |||
| BV | 504 | AQUA Link Function | Write | |||
| BV | 530 | AYC Heated water periodic operation of pump | Write | |||
| BV | 531 | AYC Heated water periodic operation of valve | Write | |||
| BV | 536 | AYC Heated water OA temp compensation | Write | |||
| BV | 547 | AYC Heated water room temp compensation function | Write | |||
| BV | 548 | AYC Heated water room temp compensation at night | Write | 0=Enabled during night, 1=Disabled during night | ||
| BV | 553 | AYC Heated water night temp compensation function | Write | |||
| BV | 579 | AYC Chilled water periodic operation of pump | Write | |||
| BV | 580 | AYC Chilled water periodic operation of valve | Write | |||
| BV | 585 | AYC Chilled water OA temp compensation | Write | |||
| BV | 596 | AYC Chilled water room temp compensation function | Write | |||
| BV | 597 | AYC Chilled water room temp compensation at night | Write | 0=Enabled during night, 1=Disabled during night | ||
| BV | 602 | AYC Chilled water night temp compensation function | Write | |||
| BV | 618 | AYC Chilled water dew point compensation air flow boost | Write | |||
| BV | 637 | Optimize function | Write | |||
| MI | 2 | Application id/AHU Type | Read | 1=GOLD RX, 2=GOLD PX, 3=GOLD CX, 4=GOLD SD/SA, 5=GOLD SD/EA, 6=GOLD SD/SA+CX, 7=GOLD SD/SA+EA, 8=GOLD SD/SA+EA+CX | ||
| MI | 3 | Air flow direction | Read | 1=Fan no.2 as SA, 2=Fan no.1 as SA | ||
| MI | 115 | PHX type | Read | 1=PHX-1 1D HS (one damper and humidity sensor), 2=PHX-2 3D (three dampers), 3=PHX-3 1D 1PS (one damper and pressure sensor) | ||
| MI | 140 | Extra regulation sequence 1 coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 142 | Extra regulation sequence 2 coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 152 | Re-heat coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 163 | Cool coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 198 | Xzone heat, coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 209 | Xzone cool, coil type | Read | 1=None, 2=1 Not used, 3=2 Not used, 4=3 Not used, 5=4 Not used, 6=5 Not used, 7=6 Not used, 8=7 Not used, 9=8 Not used, 10=9 Water, 11=10 Water, 12=11 Not used, 13=12 Not used, 14=13 Not used, 15=14 Not used, 16=15 Not used | ||
| MI | 224 | Pre-heat coil type | Read | 1=None, 2=1 Electric, 3=2 Electric, 4=3 Electric, 5=4 Electric, 6=5 Electric, 7=6 Electric, 8=7 Electric, 9=8 Electric, 10=9 Water, 11=10 Water, 12=11 Electric, 13=12 Electric, 14=13 Electric, 15=14 Electric, 16=15 Electric | ||
| MI | 320 | SMART Link, DX cool mode | Read | 1=Heat, 2=Cool | ||
| MImin | 592 | Operation level | Read | 1=Fan not available, 2=Alarm stop, 3=Manual total stop (on hand terminal), 4=External total stop (digital input), 5=Communication total stop, 6=Communication normal stop, 7=Communication extended normal stop, 8=Time channel total stop, 9=Time channel normal stop, 10=Time channel extended normal stop, 11=Low speed=normal stop, 12=SA Fan starting up, 13=Fan regulation blocked, 14=ReCO2 100% recirculation(1.11), 15=Morning boost stop(1.11), 16=Intermittent night heat stop(1.11), 17=After cooling electric heater, 18=COOL DX switch off delay, 19=Damper switch off delay, 20=Manual low speed (on hand terminal), 21=External low speed (digital input), 22=Extended external low speed, 23=Communication low speed, 24=Time channel low speed, 25=Morning boost low speed, 26=Intermittent night heat low speed, 27=Manual high speed (on hand terminal), 28=External high speed (digital input), 29=Extended external high speed, 30=Communication high speed, 31=Time channel high speed, 32=Summer night cooling high speed, 33=Filter calibration, 34=RHX Defrost calibration, 35=ReCO2 calibration, 36=AHU start up, 37=Re-heat ramp down, 38=HX ramp down, 39=Air adjustment, 40=Fans in operation with active fire alarm, 41=PX bypass damper adjustment(1.12) | ||
| MO | 1 | Boost Supply air | Write | 1=Off, 2=On | ||
| MO | 2 | Boost Extract air | Write | 1=Off, 2=On | ||
| MV | 1 | SA Fan regulation mode | Setting of regulation type for the supply air fan. | Write | 1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by EA fan | |
| MV | 2 | EA Fan regulation mode | Setting of regulation type for the extract air fan. | Write | 1=Air flow reg., 2=Pressure reg., 3=Demand reg., 4=Slave controlled by SA fan | |
| MV | 4 | Internal fire alarm reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 7 | External fire alarm no. 1 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 8 | External fire alarm no. 2 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 11 | External alarm no. 1 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 12 | External alarm no. 2 reset function | Write | 1=Manual reset, 2=Auto reset | ||
| MV | 15 | External alarm no. 1 input function | Write | 1=Alarm at closed contact, 2=Alarm at open contact | ||
| MV | 16 | External alarm no. 2 input function | Write | 1=Alarm at closed contact, 2=Alarm at open contact | ||
| MV | 53 | Outdoor temp compensation function | Write | 1=Inactive, 2=Active at low speed, 3=Active at high speed, 4=Active at low and high speed | ||
| MV | 78 | Down regulation function | Write | 1=Inactive, 2=SA, 3=SA and EA | ||
| MV | 84 | Fans in operation at fire alarm 1 function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 87 | Fans in operation at fire alarm 2 function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 90 | Fans in operation at internal fire alarm function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 95 | Pre-filter function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 96 | Pre-filter calibration | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 101 | AHU filter function | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 102 | AHU filter calibration | Write | 1=Inactive, 2=SA, 3=EA, 4=SA and EA | ||
| MV | 107 | SA end filter function | Write | 1=Inactive, 2=SA | ||
| MV | 108 | SA end filter calibration | Write | 1=Inactive, 2=SA | ||
| MV | 115 | Temperature regulation mode | Write | 1=Inactive, 2=ERS-1, 3=ERS-2, 4=SA, 5=EA, 6=ORS, 7=ORE | ||
| MV | 166 | External room sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 176 | External OA sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 188 | RHX sorption rotor function | Setting for activating the sorption rotor control function for the rotary heat | Write | 1=Inactive, 2=Sorption max at cool, 3=Sorption always max | |
| MV | 237 | Extra regulation sequence 1 function | State text | Write | 1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool | |
| MV | 238 | Extra regulation sequence 1 output function | Write | 1=0-10V, 2=10-0V | ||
| MV | 251 | Extra regulation 1 temperature protection function | Write | 1=Inactive, 2=Active | ||
| MV | 254 | Season heat function | Write | 1=Inactive, 2=Extra regulation sequence at closed input, 3=Extra regulation sequence at open input, 4=Manual mode | ||
| MV | 255 | Season heat manual setting | Write | 1=Re-heat, 2=Extra regulation sequence | ||
| MV | 261 | Cool on/off regulation function | Write | 1=Inactive, 2=1 step, 3=2 steps, 4=3 steps | ||
| MV | 313 | Cooling boost function | Write | 1=Inactive, 2=Comfort, 3=Economy, 4=Sequence, 5=Comfort and Economy, 6=Economy and Sequence | ||
| MV | 329 | Xzone temperature regulation mode | Write | 1=Inactive, 2=ERS-1, 3=ERS-2, 4=SA, 5=EA, 6=ORS, 7=ORE | ||
| MV | 378 | Xzone external room sensors measurement function | Write | 1=Average, 2=Min, 3=Max | ||
| MV | 395 | Xzone Cool on/off regulation function | Write | 1=Inactive, 2=1 step, 3=2 steps, 4=3 steps | ||
| MV | 423 | ReCO2-CO2 function | Write | 1=Inactive, 2=CO2, 3=CO2 and air flow boost | ||
| MV | 424 | ReCO2 temperature regulation sequence function | Write | 1=Inactive, 2=Heat, 3=Cool, 4=Heat and Cool | ||
| MV | 441 | Humidifying function | Write | 1=Inactive, 2=On/Off, 3=0-10V | ||
| MV | 442 | Humidifying sensor | Write | 1=SA, 2=EA | ||
| MV | 457 | DeHumidifying function | Write | 0=Inactive, 1=SA, 2=EA | ||
| MV | 469 | COOL DX Function | Write | 1=Inactive, 2=Economy, 3=Comfort, 4=Top | ||
| MV | 481 | SMART Link Function | Write | 1=Inactive, 2=Water based heat pump, 3=Water based chiller, 4=Water based reversible, 5=DX based heat pump, 6=DX based chiller, 7=DX based reversible | ||
| MV | 505 | AQUA Link Pump alarm function | Write | 1=Inactive, 2=Alarm at closed contact, 3=Alarm at open contact, 4=Alarm when in -and output are unequal (contactor function) | ||
| MV | 521 | AYC Function | Write | 1=Inactive, 2=Chilled water, 3=Heated water, 4=Chilled and heated water | ||
| MV | 528 | AYC Heated water signal monitor function for pump | Write | 1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function | ||
| MV | 555 | AYC Heated water night temp compensation time 1 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 562 | AYC Heated water night temp compensation time 2 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 577 | AYC Chilled water signal monitor function for pump | Write | 1=Inactive, 2=Alarm at open contact, 3=Alarm at closed contact, 4=Contactor function | ||
| MV | 604 | AYC Chilled water night temp compensation time 1 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 611 | AYC Chilled water night temp compensation time 2 (days) | Write | 1=Inactive, 2=Monday, 3=Tuesday, 4=Wednesday, 5=Thursday, 6=Friday, 7=Saturday, 8=Sunday, 9=Monday to Friday, 10= Monday to Sunday, 11=Saturday to Sunday | ||
| MV | 660 | MIRU Control 1 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 661 | MIRU Control 2 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 662 | MIRU Control 3 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 663 | MIRU Control 4 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 664 | MIRU Control 5 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 665 | MIRU Control 6 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 666 | MIRU Control 7 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 667 | MIRU Control 8 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 668 | MIRU Control 9 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 669 | MIRU Control 10 function | Write | 1=Inactive, 2=Parallel start, 3=Parallel low / high speed, 4=Parallel start and Low / high speed | ||
| MV | 671 | MIRU Control 1 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 679 | MIRU Control 2 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 687 | MIRU Control 3 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 695 | MIRU Control 4 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 703 | MIRU Control 5 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 711 | MIRU Control 6 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 719 | MIRU Control 7 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 727 | MIRU Control 8 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 735 | MIRU Control 9 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MV | 743 | MIRU Control 10 Balanced air flow function | Write | 1=Inactive, 2=SA, 3=EA | ||
| MVmin | 793 | Communication operation level | Write | 1=Auto, 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop | ||
| CAL | 0 | Calendar #1 | Date list, up to 10 dates | Write | ||
| CAL | 1 | Calendar #2 | Date list, up to 10 dates | Write | ||
| NC | 0 | NC 00 A-Alarm | Notification class for AHU A-alarms | Read | ||
| NC | 1 | NC 01 B-Alarm | Notification class for AHU B-alarms | Read | ||
| NC | 3 | NC 03 Alarms specified in BACnet | Notification class for alarms set in BACnet objects | Read | ||
| NC | 10 | NC 10 Info message | Notification class for AHU info messages | Read | ||
| NC | 11 | NC 11 Events specified in BACnet | Notification class for events set in BACnet objects | Read | ||
| SCH | 0 | Schedule #1 | Weekly schedule, 6 time-values per day, 2 exceptions | Write | 1=Total stop, 2=Low speed, 3=High speed, 4=Normal stop, 5=Extended normal stop |
No points match these filters.
Object ID lookup: Swegon GOLD generation E point IDs by name
AI1Component nameAI4SA Air flowAI5SA Air flow regulatorAI6EA Air flowAI7EA Air flow regulatorAI8SA Duct pressureAI9SA Duct pressure regulatorAI10EA Duct pressureAI11EA Duct pressure regulatorAI12Demand input levelAI13Demand regulatorAI14SA Air flow pressureAI15EA Air flow pressureAI23SA Pre-filter pressure levelAI24SA Pre-filter pressure alarm limitAI25EA Pre-filter pressure levelAI26EA Pre-filter pressure alarm limitAI27SA AHU filter pressure levelAI28SA AHU filter pressure alarm limitAI29EA AHU filter pressure levelAI30EA AHU filter pressure alarm limitAI31SA End-filter pressure levelAI32SA End-filter pressure alarm limitAI37SA Fan levelAI38EA Fan levelAI39SA Fan speedAI40EA Fan speedAI41SA VoltageAI42EA VoltageAI43SA Fan currentAI44EA Fan currentAI45SA Fan powerAI46EA Fan powerAI47SA Fan kWhAI48EA Fan kWhAI49SA Fan MWhAI50EA Fan MWhAI51SA Fan operation timeAI52EA Fan operation timeAI55SA Fan min air flowAI56EA Fan min air flowAI57SA Fan max air flowAI58EA Fan max air flowAI63SFPAI64SA TemperatureAI65SA-D TemperatureAI66EA TemperatureAI67EA-D TemperatureAI68EA Regulation temperatureAI69EA Temperature PX/CXAI70EA Temperature SDAI72Outdoor temperature COOL DXAI73Outdoor temperatureAI74Outdoor regulation temperatureAI75External outdoor temperature 1AI76External outdoor temperature 2AI77External outdoor temperature 3AI78External outdoor temperature 4AI79External outdoor temperature min/max/averageAI80EA Duct temperatureAI81Room temperature 1AI82Room temperature 2AI83Room temperature 3AI84Room temperature 4AI85Room temperature min/max/averageAI87SA Temp regulatorAI88EA Temp regulatorAI90Cool exchanger regulator levelAI91Heat exchanger regulator levelAI92Extra regulation sequence 1 heat regulator levelAI93Extra regulation sequence 1 heat output levelAI94Reheat regulator levelAI95Reheat output levelAI96ReCO2 heat levelAI97Down regulation levelAI98Heating boost levelAI99Extra regulation sequence 1 cool regulator levelAI100Extra regulation sequence 1 cool output levelAI101Cool regulator levelAI102Cool output levelAI103ReCO2 cool levelAI104Cooling boost levelAI105RHX operation levelAI106RHX efficiencyAI107RHX defrost pressure levelAI108RHX defrost pressure alarm limitAI109RHX carry over control pressure levelAI111RHX operation timeAI116PX defrost pressure levelAI117PHX-3D Bypass outputAI118PHX-3D Bypass inputAI119PHX-3D Bypass temperature 1AI120PHX-3D Bypass temperature 2AI121PX exchanger damper 1 outputAI122PHX-2 Damper 1 inputAI123PX exchanger damper 2 outputAI124PHX-2 Damper 2 inputAI125PX exchanger bypass outputAI126PX exchanger bypass feedbackAI127CHX Valve outputAI128CHX Valve inputAI129CHX Return water temperatureAI130PHX/CHX operation timeAI132PHX-1D Bypass outputAI133PHX-1D Bypass inputAI136PHX/CHX Humidity levelAI141Extra regulation sequence 1 anti frost temp/overheat inputAI143Extra regulation sequence 2 anti frost temp/overheat inputAI146Extra regulation sequence 1 input levelAI147Extra regulation sequence 1 heat operation timeAI148Extra regulation sequence 1 cool operation timeAI149Extra regulation sequence 2 input levelAI150Extra regulation sequence 2 heat operation timeAI151Extra regulation sequence 2 cool operation timeAI153Re-heat anti frost temp/overheat inputAI158Re-heat input levelAI159Re-heat operation timeAI164Cool water temperatureAI168Cool input levelAI169Cool operation timeAI174Xzone SA temperatureAI175Xzone EA temperatureAI176Xzone EA regulation temperatureAI177Xzone Room temperature 1AI178Xzone Room temperature 2AI179Xzone Room temperature 3AI180Xzone Room temperature 4AI181Xzone Room temperature min/max/averageAI186Xzone SA Temp regulatorAI187Xzone EA Temp regulatorAI190Xzone re-heat regulator levelAI193Xzone cool regulator levelAI199Xzone heat, anti frost temp/overheat inputAI203Xzone heat, output levelAI204Xzone heat, input levelAI205Xzone heat, operation timeAI210Xzone cool, water temperatureAI214Xzone cool, output levelAI215Xzone cool, input levelAI216Xzone cool, operation timeAI220Pre-heat temperatureAI221Pre-heat temp regulator set pointAI222Pre-heat temp regulator levelAI225Pre-heat anti frost temp/overheat inputAI228Pre-heat output levelAI229Pre-heat input levelAI230Pre-heat operation timeAI233ReCO2 recirculation damper outputAI234ReCO2 recirculation damper inputAI235ReCO2 outdoor damper outputAI236ReCO2 outdoor damper inputAI237ReCO2 outdoor air flowAI238ReCO2 outdoor air flow regulator set pointAI244SA humidity levelAI245SA humidity temperatureAI246SA dew pointAI247EA humidity levelAI248EA humidity temperatureAI249EA dew pointAI251Dehumidifying SA dew point regulator set pointAI252Dehumidifying output levelAI254Humidifying SA regulator set pointAI255Humidifying output levelAI266VOC levelAI271COOL DX, unit power sizeAI274COOL DX, compressor 1 low pressure levelAI275COOL DX, compressor 1 high pressure levelAI276COOL DX, compressor 2 low pressure levelAI277COOL DX, compressor 2 high pressure levelAI289SMART Link, WB outlet water 1AI290SMART Link, WB outlet water 2AI291SMART Link, WB outlet water 3AI292SMART Link, WB outlet water 4AI293SMART Link, WB outlet water averageAI294SMART Link, WB return waterAI297SMART Link WB, heated water set pointAI298SMART Link WB, chilled water set pointAI299SMART Link WB, Min heated water set pointAI300SMART Link WB, Max heated water set pointAI301SMART Link WB, Min chilled water set pointAI302SMART Link WB, Max chilled water set pointAI327SMART Link, DX unit 1 power level set pointAI328SMART Link, DX unit 1 power levelAI329SMART Link, DX unit 1 operation timeAI338SMART Link, DX unit 2 power level set pointAI339SMART Link, DX unit 2 power levelAI340SMART Link, DX unit 2 operation timeAI349SMART Link, DX unit 3 power level set pointAI350SMART Link, DX unit 3 power levelAI351SMART Link, DX unit 3 operation timeAI360SMART Link, DX unit 4 power level set pointAI361SMART Link, DX unit 4 power levelAI362SMART Link, DX unit 4 operation timeAI374AYC Heat, heated waterAI375AYC Heated water set pointAI376AYC Heat, valve outputAI377AYC Heat, valve inputAI378AYC Heat, operation timeAI379AYC Heated water heat demandAI387AYC Cool, chilled waterAI388AYC Chilled water set pointAI389AYC Cool, valve outputAI390AYC Cool, valve inputAI391AYC Cool, operation timeAI392AYC Chilled water cool demandAI400MIRU Control 1 Min air flowAI401MIRU Control 1 Max air flowAI402MIRU Control 1 Air flowAI403MIRU Control 1 Air flow set pointAI404MIRU Control 1 PressureAI405MIRU Control 1 Pressure set pointAI406MIRU Control 1 External temperatureAI407MIRU Control 1 Operation timeAI408MIRU Control 1 Fan levelAI409MIRU Control 1 Fan powerAI410MIRU Control 1 SFPAI411MIRU Control 1 kWhAI412MIRU Control 1 MWhAI417MIRU Control 2 Min air flowAI418MIRU Control 2 Max air flowAI419MIRU Control 2 Air flowAI420MIRU Control 2 Air flow set pointAI421MIRU Control 2 PressureAI422MIRU Control 2 Pressure set pointAI423MIRU Control 2 External temperatureAI424MIRU Control 2 Operation timeAI425MIRU Control 2 Fan levelAI426MIRU Control 2 Fan powerAI427MIRU Control 2 SFPAI428MIRU Control 2 kWhAI429MIRU Control 2 MWhAI434MIRU Control 3 Min air flowAI435MIRU Control 3 Max air flowAI436MIRU Control 3 Air flowAI437MIRU Control 3 Air flow set pointAI438MIRU Control 3 PressureAI439MIRU Control 3 Pressure set pointAI440MIRU Control 3 External temperatureAI441MIRU Control 3 Operation timeAI442MIRU Control 3 Fan levelAI443MIRU Control 3 Fan powerAI444MIRU Control 3 SFPAI445MIRU Control 3 kWhAI446MIRU Control 3 MWhAI451MIRU Control 4 Min air flowAI452MIRU Control 4 Max air flowAI453MIRU Control 4 Air flowAI454MIRU Control 4 Air flow set pointAI455MIRU Control 4 PressureAI456MIRU Control 4 Pressure set pointAI457MIRU Control 4 External temperatureAI458MIRU Control 4 Operation timeAI459MIRU Control 4 Fan levelAI460MIRU Control 4 Fan powerAI461MIRU Control 4 SFPAI462MIRU Control 4 kWhAI463MIRU Control 4 MWhAI468MIRU Control 5 Min air flowAI469MIRU Control 5 Max air flowAI470MIRU Control 5 Air flowAI471MIRU Control 5 Air flow set pointAI472MIRU Control 5 PressureAI473MIRU Control 5 Pressure set pointAI474MIRU Control 5 External temperatureAI475MIRU Control 5 Operation timeAI476MIRU Control 5 Fan levelAI477MIRU Control 5 Fan powerAI478MIRU Control 5 SFPAI479MIRU Control 5 kWhAI480MIRU Control 5 MWhAI485MIRU Control 6 Min air flowAI486MIRU Control 6 Max air flowAI487MIRU Control 6 Air flowAI488MIRU Control 6 Air flow set pointAI489MIRU Control 6 PressureAI490MIRU Control 6 Pressure set pointAI491MIRU Control 6 External temperatureAI492MIRU Control 6 Operation timeAI493MIRU Control 6 Fan levelAI494MIRU Control 6 Fan powerAI495MIRU Control 6 SFPAI496MIRU Control 6 kWhAI497MIRU Control 6 MWhAI502MIRU Control 7 Min air flowAI503MIRU Control 7 Max air flowAI504MIRU Control 7 Air flowAI505MIRU Control 7 Air flow set pointAI506MIRU Control 7 PressureAI507MIRU Control 7 Pressure set pointAI508MIRU Control 7 External temperatureAI509MIRU Control 7 Operation timeAI510MIRU Control 7 Fan levelAI511MIRU Control 7 Fan powerAI512MIRU Control 7 SFPAI513MIRU Control 7 kWhAI514MIRU Control 7 MWhAI519MIRU Control 8 Min air flowAI520MIRU Control 8 Max air flowAI521MIRU Control 8 Air flowAI522MIRU Control 8 Air flow set pointAI523MIRU Control 8 PressureAI524MIRU Control 8 Pressure set pointAI525MIRU Control 8 External temperatureAI526MIRU Control 8 Operation timeAI527MIRU Control 8 Fan levelAI528MIRU Control 8 Fan powerAI529MIRU Control 8 SFPAI530MIRU Control 8 kWhAI531MIRU Control 8 MWhAI536MIRU Control 9 Min air flowAI537MIRU Control 9 Max air flowAI538MIRU Control 9 Air flowAI539MIRU Control 9 Air flow set pointAI540MIRU Control 9 PressureAI541MIRU Control 9 Pressure set pointAI542MIRU Control 9 External temperatureAI543MIRU Control 9 Operation timeAI544MIRU Control 9 Fan levelAI545MIRU Control 9 Fan powerAI546MIRU Control 9 SFPAI547MIRU Control 9 kWhAI548MIRU Control 9 MWhAI553MIRU Control 10 Min air flowAI554MIRU Control 10 Max air flowAI555MIRU Control 10 Air flowAI556MIRU Control 10 Air flow set pointAI557MIRU Control 10 PressureAI558MIRU Control 10 Pressure set pointAI559MIRU Control 10 External temperatureAI560MIRU Control 10 Operation timeAI561MIRU Control 10 Fan levelAI562MIRU Control 10 Fan powerAI563MIRU Control 10 SFPAI564MIRU Control 10 kWhAI565MIRU Control 10 MWhAI570IQlogic software versionAI604Triggered alarm #1AI605Triggered alarm #2AI606Triggered alarm #3AI607Triggered alarm #4AI608Triggered alarm #5AI609Triggered alarm #6AI610Triggered alarm #7AI611Triggered alarm #8AI612Triggered alarm #9AI613Triggered alarm #10AI614Triggered alarm group #1AI615Triggered alarm group #2AI616Triggered alarm group #3AI617Triggered alarm group #4AI618Triggered alarm group #5AI619Triggered alarm group #6AI620Triggered alarm group #7AI621Triggered alarm group #8AI622Triggered alarm group #9AI623Triggered alarm group #10AO1Extract air start upAV3SA low speed air flow set pointAV4EA low speed air flow set pointAV5SA high speed air flow set pointAV6EA high speed air flow set pointAV7SA max speed air flow set pointAV8EA max speed air flow set pointAV9SA regulation zoneAV10EA regulation zoneAV11SA regulation I-timeAV12EA regulation I-timeAV19SA low speed pressure set pointAV20EA low speed pressure set pointAV21SA high speed pressure set pointAV22EA high speed pressure set pointAV23SA max speed pressure set pointAV24EA max speed pressure set pointAV25SA max speed output signalAV26EA max speed output signalAV27SA pressure regulation zoneAV28EA pressure regulation zoneAV29SA pressure I-timeAV30EA pressure I-timeAV37Demand low speed demand set pointAV38Demand high speed demand set pointAV39SA min speed air flow set pointAV40EA min speed air flow set pointAV41SA max speed air flow set pointAV42EA max speed air flow set pointAV43SA demand P-bandAV44SA demand I-timeAV50Slave offset factorAV54Outdoor temp compensation X1AV55Outdoor temp compensation X2AV56Outdoor temp compensation X3AV57Outdoor temp compensation X4AV58Outdoor temp compensation Y1 SA air flowAV59Outdoor temp compensation Y2 SA air flowAV60Outdoor temp compensation Y3 SA air flowAV61Outdoor temp compensation Y4 SA air flowAV62Outdoor temp compensation Y1 EA air flowAV63Outdoor temp compensation Y2 EA air flowAV64Outdoor temp compensation Y3 EA air flowAV65Outdoor temp compensation Y4 EA air flowAV66Outdoor temp compensation Y1 SA pressureAV67Outdoor temp compensation Y2 SA pressureAV68Outdoor temp compensation Y3 SA pressureAV69Outdoor temp compensation Y4 SA pressureAV70Outdoor temp compensation Y1 EA pressureAV71Outdoor temp compensation Y2 EA pressureAV72Outdoor temp compensation Y3 EA pressureAV73Outdoor temp compensation Y4 EA pressureAV79Down regulation neutralzoneAV80Down regulation P-bandAV81Down regulation I-timeAV85SA fan speed at fire alarm 1AV86EA fan speed at fire alarm 1AV88SA fan speed at fire alarm 2AV89EA fan speed at fire alarm 2AV91SA fan speed at internal fire alarmAV92EA fan speed at internal fire alarmAV97SA pre-filter alarm limitAV98EA pre-filter alarm limitAV103SA AHU-filter alarm limitAV104EA AHU-filter alarm limitAV109SA end-filter alarm limitAV117ERS 1 stepAV118ERS 1 diffAV119ERS 1 breakpointAV122ERS 2 breakpoint X1AV123ERS 2 breakpoint X2AV124ERS 2 breakpoint X3AV125ERS 2 breakpoint X4AV126ERS 2 breakpoint Y1AV127ERS 2 breakpoint Y2AV128ERS 2 breakpoint Y3AV129ERS 2 breakpoint Y4AV132SA temperature set pointAV135EA/Room temperature set pointAV136SA min temp set pointAV137SA max temp set pointAV138EA regultaion P-bandAV139EA regultaion I-timeAV142ORS breakpoint X1AV143ORS breakpoint X2AV144ORS breakpoint X3AV145ORS breakpoint X4AV146ORS breakpoint Y1AV147ORS breakpoint Y2AV148ORS breakpoint Y3AV149ORS breakpoint Y4AV152ORE breakpoint X1AV153ORE breakpoint X2AV154ORE breakpoint X3AV155ORE breakpoint X4AV156ORE breakpoint Y1AV157ORE breakpoint Y2AV158ORE breakpoint Y3AV159ORE breakpoint Y4AV168External room temp from BMSAV169External room temp from BMS alarm timeAV178External OA temp from BMSAV179External OA temp from BMS alarm timeAV184RHX defrost start limitAV188RHX sorption rotor functionAV191RHX min exhaust air temp set pointAV192RHX min exhaust air temp P-bandAV193RHX min exhaust air temp I-timeAV199PHX periodic operation intervalAV200PHX periodic operation timeAV207CHX periodic operation intervalAV208CHX periodic operation timeAV213PHX/CHX Bypass defrost limitAV214PHX/CHX Bypass defrost P-bandAV215PHX/CHX Bypass defrost I-timeAV220Heat exchange temperature regulation P-bandAV221Heat exchange temperature regulation I-timeAV222Cool exchange temperature regulation P-bandAV223Cool exchange temperature regulation I-timeAV226Re-heat P-bandAV227Re-heat I-timeAV230Re-heat periodic operation intervalAV231Re-heat periodic operation timeAV239Extra regulation sequence 1 heat max output signalAV240Extra regulation sequence 1 cool max output signalAV241Extra regulation sequence 1 heat P-bandAV242Extra regulation sequence 1 heat I-timeAV243Extra regulation sequence 1 cool P-bandAV244Extra regulation sequence 1 cool I-timeAV247Extra regulation 1 periodic operation intervalAV248Extra regulation 1 periodic operation timeAV252Extra regulation 1 temperature protection temperatureAV253Extra regulation 1 temperature protection alarm delayAV258Cool step 1 min supply air flow limitAV259Cool step 2 min supply air flow limitAV260Cool step 3 min supply air flow limitAV262Cool SA neutral zoneAV263Cool EA neutral zoneAV264Cool outdoor temp limit 1AV265Cool outdoor temp limit 2AV266Cool outdoor temp limit 3AV267Cool 0-10V min supply air flow limitAV268Cool 0-10V min extract air flow limitAV269Cool restart timeAV270Cool step up delay timeAV271Cool stand still timeAV272Cool P-bandAV273Cool I-timeAV277Cool periodic operation intervalAV278Cool periodic operation timeAV279Cool step 1 min extract air flow limitAV280Cool step 2 min extract air flow limitAV281Cool step 3 min extract air flow limitAV285Summer night cool start time (hour)AV286Summer night cool start time (minute)AV287Summer night cool stop time (hour)AV288Summer night cool stop time (minute)AV289Summer night cool OA temp start limitAV290Summer night cool EA temp start limitAV291Summer night cool EA temp stop limitAV292Summer night cool SA temp set pointAV297Intermittent night heat SA flow set pointAV298Intermittent night heat SA duct pressure set pointAV299Intermittent night heat EA temp start limitAV300Intermittent night heat EA temp stop limitAV301Intermittent night heat SA temp set pointAV303Intermittent night heat EA flow set pointAV304Intermittent night heat EA duct pressure set pointAV306Morning boost start time (hour)AV307Morning boost start time (minute)AV308Morning boost air flow set pointAV309Morning boost duct pressure set pointAV314Cooling boost comfort start limitAV315Cooling boost comfort regulation speedAV316Cooling boost economy P-bandAV317Cooling boost economy I-timeAV321Heating boost comfort start limitAV322Heating boost comfort regulation speedAV331Xzone ERS 1 stepAV332Xzone ERS 1 diffAV333Xzone ERS 1 breakpointAV336Xzone ERS 2 breakpoint X1AV337Xzone ERS 2 breakpoint X2AV338Xzone ERS 2 breakpoint X3AV339Xzone ERS 2 breakpoint X4AV340Xzone ERS 2 breakpoint Y1AV341Xzone ERS 2 breakpoint Y2AV342Xzone ERS 2 breakpoint Y3AV343Xzone ERS 2 breakpoint Y4AV346Xzone SA temperature set pointAV349Xzone EA/Room temperature set pointAV350Xzone SA min temp set pointAV351Xzone SA max temp set pointAV352Xzone EA regultaion P-bandAV353Xzone EA regultaion I-timeAV354Xzone ORS breakpoint X1AV355Xzone ORS breakpoint X2AV356Xzone ORS breakpoint X3AV357Xzone ORS breakpoint X4AV358Xzone ORS breakpoint Y1AV359Xzone ORS breakpoint Y2AV360Xzone ORS breakpoint Y3AV361Xzone ORS breakpoint Y4AV364Xzone ORE breakpoint X1AV365Xzone ORE breakpoint X2AV366Xzone ORE breakpoint X3AV367Xzone ORE breakpoint X4AV368Xzone ORE breakpoint Y1AV369Xzone ORE breakpoint Y2AV370Xzone ORE breakpoint Y3AV371Xzone ORE breakpoint Y4AV380Xzone external room temp from BMSAV381Xzone external room temp from BMS alarm timeAV384Xzone reheat P-bandAV385Xzone reheat I-timeAV388Xzone reheat periodic operation intervalAV389Xzone reheat periodic operation timeAV396Xzone Cool SA neutral zoneAV397Xzone Cool EA neutral zoneAV398Xzone Cool P-bandAV399Xzone Cool I-timeAV403Xzone Cool periodic operation intervalAV404Xzone Cool periodic operation timeAV411Pre-heat temperature set pointAV412Pre-heat P-bandAV413Pre-heat I-timeAV416Pre-heat periodic operation intervalAV417Pre-heat periodic operation timeAV426ReCO2-CO2 set pointAV427ReCO2 min. outdoor airAV428ReCO2 min. exhaust airAV429ReCO2-CO2 P-bandAV430ReCO2-CO2 I-timeAV431ReCO2-CO2 air flow boost reg. P-bandAV432ReCO2-CO2 air flow boost reg. I-timeAV433ReCO2 heat P-bandAV434ReCO2 heat I-timeAV435ReCO2 cool P-bandAV436ReCO2 cool I-timeAV443Humidifying on/off start levelAV444Humidifying on/off stop levelAV448Humidifying 0-10V set pointAV449Humidifying 0-10V SA max set pointAV450Humidifying 0-10V SA P-bandAV451Humidifying 0-10V SA I-timeAV452Humidifying 0-10V EA P-bandAV453Humidifying 0-10V EA I-timeAV458Dehumidifying set pointAV470COOL DX Low pressure stop limitAV471COOL DX High pressure stop limitAV472COOL DX Restart timeAV482SMART Link WB Heat temperature set pointAV483SMART Link WB Heat temperature heat zoneAV484SMART Link WB Cool temperature set pointAV485SMART Link WB Cool temperature heat zoneAV491SMART Link WB Optimize valve upper limitAV492SMART Link WB Optimize valve lower limitAV493SMART Link WB Optimize time delayAV494SMART Link WB Optimize heat regulation speedAV495SMART Link WB Optimize cool regulation speedAV510SMART Link DX Amount of unitsAV519SMART Link OA temp limitAV524AYC Heated water temp set pointAV526AYC Heated water OA temp for start of pumpAV527AYC Heated water OA temp for stop of pumpAV532AYC Heated water periodic operation intervalAV533AYC Heated water periodic operation timeAV537AYC Heated water OA temp compensation X1AV538AYC Heated water OA temp compensation X2AV539AYC Heated water OA temp compensation X3AV540AYC Heated water OA temp compensation X4AV541AYC Heated water OA temp compensation Y1AV542AYC Heated water OA temp compensation Y2AV543AYC Heated water OA temp compensation Y3AV544AYC Heated water OA temp compensation Y4AV549AYC Heated water room temp compensation temperatureAV550AYC Heated water room temp compensation P-bandAV554AYC Heated water night temp compensation tempAV556AYC Heated water night temp compensation start time 1 (hour)AV557AYC Heated water night temp compensation start time 1 (minutes)AV558AYC Heated water night temp compensation stop time 1 (hour)AV559AYC Heated water night temp compensation stop time 1 (minutes)AV563AYC Heated water night temp compensation start time 2 (hour)AV564AYC Heated water night temp compensation start time 2 (minutes)AV565AYC Heated water night temp compensation stop time 2 (hour)AV566AYC Heated water night temp compensation stop time 2 (minutes)AV569AYC Heated water P-bandAV570AYC Heated water I-timeAV572AYC Chilled water temp set pointAV575AYC Chilled water OA temp for start of pumpAV576AYC Chilled water OA temp for stop of pumpAV581AYC Chilled water periodic operation intervalAV582AYC Chilled water periodic operation timeAV586AYC Chilled water OA temp compensation X1AV587AYC Chilled water OA temp compensation X2AV588AYC Chilled water OA temp compensation X3AV589AYC Chilled water OA temp compensation X4AV590AYC Chilled water OA temp compensation Y1AV591AYC Chilled water OA temp compensation Y2AV592AYC Chilled water OA temp compensation Y3AV593AYC Chilled water OA temp compensation Y4AV598AYC Chilledwater room temp compensation temperatureAV599AYC Chilled water room temp compensation P-bandAV603AYC Chilled water night temp compensation tempAV605AYC Chilled water night temp compensation start time 1 (hour)AV606AYC Chilled water night temp compensation start time 1 (minutes)AV607AYC Chilled water night temp compensation stop time 1 (hour)AV608AYC Chilled water night temp compensation stop time 1 (minutes)AV612AYC Chilled water night temp compensation start time 2 (hour)AV613AYC Chilled water night temp compensation start time 2 (minutes)AV614AYC Chilledwater night temp compensation stop time 2 (hour)AV615AYC Chilled water night temp compensation stop time 2 (minutes)AV619AYC Chilled water dew point compensation neutral zoneAV620AYC Chilled water dew point compensation regulation speedAV623AYC Chilled water P-bandAV624AYC Chilled water I-timeAV638Optimize SA pressure set pointAV639Optimize EA pressure set pointAV672MIRU Control 1 Low speed duct pressure set pointAV673MIRU Control 1 High speed duct pressure set pointAV674MIRU Control 1 Low speed air flow set pointAV675MIRU Control 1 High speed air flow set pointAV680MIRU Control 2 Low speed duct pressure set pointAV681MIRU Control 2 High speed duct pressure set pointAV682MIRU Control 2 Low speed air flow set pointAV683MIRU Control 2 High speed air flow set pointAV688MIRU Control 3 Low speed duct pressure set pointAV689MIRU Control 3 High speed duct pressure set pointAV690MIRU Control 3 Low speed air flow set pointAV691MIRU Control 3 High speed air flow set pointAV696MIRU Control 4 Low speed duct pressure set pointAV697MIRU Control 4 High speed duct pressure set pointAV698MIRU Control 4 Low speed air flow set pointAV699MIRU Control 4 High speed air flow set pointAV704MIRU Control 5 Low speed duct pressure set pointAV705MIRU Control 5 High speed duct pressure set pointAV706MIRU Control 5 Low speed air flow set pointAV707MIRU Control 5 High speed air flow set pointAV712MIRU Control 6 Low speed duct pressure set pointAV713MIRU Control 6 High speed duct pressure set pointAV714MIRU Control 6 Low speed air flow set pointAV715MIRU Control 6 High speed air flow set pointAV720MIRU Control 7 Low speed duct pressure set pointAV721MIRU Control 7 High speed duct pressure set pointAV722MIRU Control 7 Low speed air flow set pointAV723MIRU Control 7 High speed air flow set pointAV728MIRU Control 8 Low speed duct pressure set pointAV729MIRU Control 8 High speed duct pressure set pointAV730MIRU Control 8 Low speed air flow set pointAV731MIRU Control 8 High speed air flow set pointAV736MIRU Control 9 Low speed duct pressure set pointAV737MIRU Control 9 High speed duct pressure set pointAV738MIRU Control 9 Low speed air flow set pointAV739MIRU Control 9 High speed air flow set pointAV744MIRU Control 10 Low speed duct pressure set pointAV745MIRU Control 10 High speed duct pressure set pointAV746MIRU Control 10 Low speed air flow set pointAV747MIRU Control 10 High speed air flow set pointBI1Operation activeBI2Damper operation activeBI3Low speed operation activeBI4High speed operation activeBI5Intermittent night heat activeBI6Morning boost activeBI7Heating boost activeBI8Cooling boost activeBI9Summer night cool activeBI13A-alarm activeBI14B-alarm activeBI17HX operation activeBI18HX cool recovery activeBI19HX defrost activeBI22RHX speed monitor signalBI27CHX pump outputBI28CHX pump inputBI31Season heat, extra regulation sequence allowedBI32Season heat, re-heat allowedBI33Extra regulation sequence 1, outputBI34Extra regulation sequence 1, power reduction activeBI35Extra regulation sequence 1, anti-frost regulation activeBI38Re-heat outputBI39Re-heat power reduction activeBI40Re-heat anti-frost regulation activeBI43Cool output 1BI44Cool output 2BI48Extra regulation sequence 2, outputBI49Extra regulation sequence 2, power reduction activeBI50Extra regulation sequence 2, anti-frost regulation activeBI51Pre-heat outputBI52Pre-heat power reduction activeBI53Pre-heat anti-frost regulation activeBI56Xzone heat outputBI57Xzone heat power reduction activeBI58Xzone heat anti-frost regulation activeBI63Xzone cool output 1BI64Xzone cool output 2BI99AYC heat pump outputBI100AYC heat pump inputBI104Max. limit for the supply air fan speed when running in pressure regulation moBI105AYC cool pump inputBI109COOL DX compressor 1 outputBI110COOL DX compressor 1 inputBI115COOL DX compressor 2 outputBI116COOL DX compressor 2 inputBI319SMART Link, DX operationBI323SMART Link, DX unit 1 operationBI324SMART Link, DX unit 1 cool modeBI325SMART Link, DX unit 1 defrost requestBI326SMART Link, DX unit 1 defrost activeBI334SMART Link, DX unit 2 operationBI335SMART Link, DX unit 2 cool modeBI336SMART Link, DX unit 2 defrost requestBI337SMART Link, DX unit 2 defrost activeBI345SMART Link, DX unit 3 operationBI346SMART Link, DX unit 3 cool modeBI347SMART Link, DX unit 3 defrost requestBI348SMART Link, DX unit 3 defrost activeBI356SMART Link, DX unit 4 operationBI357SMART Link, DX unit 4 cool modeBI358SMART Link, DX unit 4 defrost requestBI359SMART Link, DX unit 4 power defrost activeBI501Alarm 1:1 External fire alarm no. 1 trippedBI502Alarm 1:2 External fire alarm no. 2 trippedBI503Alarm 1:3 Internal fire alarm trippedBI516Alarm 2:1 External alarm no. 1 trippedBI517Alarm 2:2 External alarm no. 2 trippedBI531Alarm 3:1 Pre-heat I/O-module no. 9 com. errorBI532Alarm 3:2 Pre-heat electrical heater overheat protection trippedBI533Alarm 3:3 Pre-heat frost protection trippedBI534Alarm 3:4 Pre-heat frost protection temperature sensor defectiveBI535Alarm 3:5 Pre-heat temperature sensor defectiveBI536Alarm 3:6 Pre-heat valve monitoring trippedBI537Alarm 3:7 Pre-heat temperature below set point alarm limitBI538Alarm 3:8 Pre-heat alarm input trippedBI546Alarm 4:1 Extra reg. sequence 1 I/O-module no. E com. errorBI547Alarm 4:2 Extra reg. sequence 1 electrical heater overheat protection trippedBI548Alarm 4:3 Extra reg. sequence 1 frost protection trippedBI549Alarm 4:4 Extra reg. sequence 1 frost protection temperature sensor defectiveBI550Alarm 4:5 Extra reg. sequence 1 valve monitoring trippedBI551Alarm 4:6 Extra reg. sequence 1 alarm input trippedBI552Alarm 4:7 Extra reg. sequence 1 temperature protection from com. ErrorBI554Alarm 4:9 Extra reg. sequence 2 I/O-module no. F com. errorBI555Alarm 4:10 Extra reg. sequence 2 electrical heater overheat protection trippedBI556Alarm 4:11 Extra reg. sequence 2 frost protection trippedBI557Alarm 4:12 Extra reg. sequence 2 frost protection temperature sensor defectiveBI558Alarm 4:13 Extra reg. sequence 2 valve monitoring trippedBI559Alarm 4:14 Extra reg. sequence 2 alarm input trippedBI561Alarm 5:1 Re-heat electrical heater over heat protection trippedBI562Alarm 5:2 Re-heat frost protection trippedBI563Alarm 5:3 Re-heat frost protection temperature sensor defectiveBI564Alarm 5:4 Re-heat heat valve monitoring trippedBI576Alarm 6:1 Xzone I/O-module no. A com. errorBI577Alarm 6:2 Xzone electrical heater overheat protection trippedBI578Alarm 6:3 Xzone frost protection trippedBI579Alarm 6:4 Xzone frost protection temperature sensor defectiveBI580Alarm 6:5 Xzone supply air temperature sensor defectiveBI581Alarm 6:6 Xzone heat valve monitoring trippedBI582Alarm 6:7 Xzone supply air temperature below set point alarm limitBI583Alarm 6:8 Xzone supply air temperature above set point alarm limitBI584Alarm 6:9 Xzone heat alarm input trippedBI591Alarm 7:1 Xzone I/O-module no. B com. errorBI592Alarm 7:2 Xzone extract air temperature sensor defectiveBI593Alarm 7:3 Xzone cool valve monitoring trippedBI594Alarm 7:4 Xzone extract air temperature below set point alarm limitBI595Alarm 7:5 Xzone cool alarm input 1 trippedBI596Alarm 7:6 Xzone cool alarm input 2 trippedBI610Alarm 8:5 Cool valve monitoring trippedBI636Alarm 10:1 Supply air temperature sensor defectiveBI637Alarm 10:2 Supply air temperature sensor for density compensation defectiveBI638Alarm 10:3 Extract air temperature sensor defectiveBI639Alarm 10:4 Extract air temperature sensor for density compensation defectiveBI640Alarm 10:5 Extract air temperature sensor for heat exchanger defrosting def.BI641Alarm 10:6 Extract air temp. sensor for density compensation in SD AHU def.BI642Alarm 10:7 Extract air duct temperature sensor defectiveBI645Alarm 10:10 Outdoor air temperature sensor defectiveBI651Alarm 11:1 Room temperature sensor no. 1 defectiveBI652Alarm 11:2 Room temperature sensor no. 2 defectiveBI653Alarm 11:3 Room temperature sensor no. 3 defectiveBI654Alarm 11:4 Room temperature sensor no. 4 defectiveBI655Alarm 11:5 Xzone room temperature sensor no. 5 defectiveBI656Alarm 11:6 Xzone room temperature sensor no. 6 defectiveBI657Alarm 11:7 Xzone room temperature sensor no. 7 defectiveBI658Alarm 11:8 Xzone room temperature sensor no. 8 defectiveBI659Alarm 11:9 Outdoor temperature sensor no. A defectiveBI660Alarm 11:10 Outdoor temperature sensor no. B defectiveBI661Alarm 11:11 Outdoor temperature sensor no. C defectiveBI662Alarm 11:12 Outdoor temperature sensor no. D defectiveBI663Alarm 11:13 Room temperature from com. errorBI664Alarm 11:14 Xzone room temperature from com. errorBI665Alarm 11:15 Outdoor temperature from com. errorBI666Alarm 12:1 Supply air temperature below set point alarm limitBI667Alarm 12:2 Supply air temperature above set point alarm limitBI671Alarm 12:6 Extract air temperature below alarm limitBI676Alarm 12:11 Temperature guard below alarm limitBI681Alarm 13:1 Humidification I/O-module no. 4 com. errorBI682Alarm 13:2 Supply air humidity sensor defectiveBI683Alarm 13:3 Extract air humidity sensor defectiveBI689Alarm 13:9 Humidifier alarm output trippedBI691Alarm 13:11 VOC sensor com. errorBI692Alarm 13:12 VOC sensor internal com. errorBI693Alarm 13:13 VOC sensor internal errorBI694Alarm 13:14 VOC sensor level below/above set point alarm limitBI711Alarm 15:1 Plate heat exchanger I/O-module no. 2 com. errorBI712Alarm 15:2 Plate heat exchanger temperature sensor no. 1 defectiveBI713Alarm 15:3 Plate heat exchanger temperature sensor no. 2 defectiveBI714Alarm 15:4 Plate heat exchanger damper monitor trippedBI717Alarm 15:7 Plate heat exchanger I/O-module no. 3 com. errorBI718Alarm 15:8 Plate heat exchanger bypass damper monitor trippedBI719Alarm 15:9 Plate heat exchanger damper no. 1 monitor trippedBI720Alarm 15:10 Plate heat exchanger damper no. 2 monitor trippedBI721Alarm 15:11 Plate heat exchanger I/O-module no. 3 com. errorBI722Alarm 15:12 Plate heat exchanger bypass damper monitor trippedBI724Alarm 15:14 Plate heat exchanger defrost pressure sensor no. C com. errorBI725Alarm 15:15 Plate heat exchanger defrost pressure above alarm limitBI726Alarm 16:1 Coil heat exchanger I/O-module no. 1 com. errorBI727Alarm 16:2 Coil heat exchanger temperature sensor defectiveBI728Alarm 16:3 Coil heat exchanger valve monitor trippedBI729Alarm 16:4 Coil heat exchanger pump monitor trippedBI741Alarm 17:1 Rotary heat exchanger motor controller com. errorBI742Alarm 17:2 Rotary heat exchanger defrost pressure sensor no. 7 com. errorBI743Alarm 17:3 Rotary heat exchanger defrost pressure above alarm limitBI744Alarm 17:4 Rotary heat exchanger speed monitor trippedBI745Alarm 17:5 Rotary heat exchanger motor controller over currentBI746Alarm 17:6 Rotary heat exchanger motor controller under voltageBI747Alarm 17:7 Rotary heat exchanger motor controller over voltageBI748Alarm 17:8 Rotary heat exchanger motor controller over temperatureBI749Alarm 17:9 Rotary heat exchanger motor controller start errorBI756Alarm 18:1 AYC I/O-module no. 7 com. errorBI757Alarm 18:2 AYC heat temperature sensor defectiveBI758Alarm 18:3 AYC heat valve monitor trippedBI759Alarm 18:4 AYC heat pump monitor trippedBI760Alarm 18:5 AYC heat temperature below set point alarm limitBI761Alarm 18:6 AYC heat temperature above set point alarm limitBI764Alarm 18:9 AYC cool temperature sensor defectiveBI765Alarm 18:10 AYC cool valve monitor trippedBI766Alarm 18:11 AYC cool pump monitor trippedBI767Alarm 18:12 AYC cool temperature below set point alarm limitBI768Alarm 18:13 AYC cool temperature above set point alarm limitBI801Alarm 21:1 COOL DX I/O-module no. 2 com. errorBI802Alarm 21:2 COOL DX compressor no. 1 low pressure sensor defectiveBI803Alarm 21:3 COOL DX compressor no. 1 low pressure below alarm limitBI804Alarm 21:4 COOL DX compressor no. 1 high pressure sensor defectiveBI805Alarm 21:5 COOL DX compressor no. 1 high pressure above alarm limitBI806Alarm 21:6 COOL DX compressor no. 1 monitor trippedBI807Alarm 21:7 COOL DX compressor no. 1 restart errorBI808Alarm 21:8 COOL DX compressor no. 2 low pressure sensor defectiveBI809Alarm 21:9 COOL DX compressor no. 2 low pressure below alarm limitBI810Alarm 21:10 COOL DX compressor no. 2 high pressure sensor defectiveBI811Alarm 21:11 COOL DX compressor no. 2 high pressure above alarm limitBI812Alarm 21:12 COOL DX compressor no. 2 monitor trippedBI813Alarm 21:13 COOL DX compressor no. 2 restart errorBI814Alarm 21:14 COOL DX outdoor air temperature sensor defectiveBI815Alarm 21:15 COOL DX phase sequence errorBI831Alarm 23:1 SMART Link com. errorBI832Alarm 23:2 SMART Link alarm level 1 trippedBI833Alarm 23:3 SMART Link alarm level 2 trippedBI834Alarm 23:4 SMART Link alarm level 3 trippedBI840Alarm 23:10 AQUA Link I/O-module no. 5 com. errorBI841Alarm 23:11 AQUA Link pump monitor trippedBI846Alarm 24:1 SMART Link no. 1 com. errorBI847Alarm 24:2 SMART Link no. 1 alarm trippedBI849Alarm 24:4 SMART Link no. 2 com. errorBI850Alarm 24:5 SMART Link no. 2 alarm trippedBI852Alarm 24:7 SMART Link no. 3 com. errorBI853Alarm 24:8 SMART Link no. 3 alarm trippedBI855Alarm 24:10 SMART Link no. 4 com. errorBI856Alarm 24:11 SMART Link no. 4 alarm trippedBI876Alarm 26:1 Pre-filter supply air pressure sensor no.8 com. errorBI877Alarm 26:2 Pre-filter supply air dirtyBI882Alarm 26:7 Pre-filter extract air pressure sensor no.9 com. errorBI883Alarm 26:8 Pre-filter extract air dirtyBI891Alarm 27:1 AHU filter supply air pressure sensor no. 3/4 com. errorBI892Alarm 27:2 AHU filter supply air dirtyBI897Alarm 27:7 AHU filter extract air pressure sensor no. 3/4 com. errorBI898Alarm 27:8 AHU filter extract air dirtyBI906Alarm 28:1 End filter supply air pressure sensor no. A com. errorBI907Alarm 28:2 End filter supply air dirtyBI936Alarm 30:1 Air flow measurement supply air pressure sensor no. 1/2 com. errorBI937Alarm 30:2 Air flow measurement supply air flow below set point alarm limitBI938Alarm 30:3 Air flow measurement supply air flow above set point alarm limitBI941Alarm 30:6 Air flow measurement extract air pressure sensor no. 1/2 com. errorBI942Alarm 30:7 Air flow measurement extract air flow below set point alarm limitBI943Alarm 30:8 Air flow measurement extract air flow above set point alarm limitBI946Alarm 30:11 Air flow meas. carry over control press. sensor no. B com. errorBI951Alarm 31:1 Pressure regulation supply air pressure sensor no. 5 com. errorBI952Alarm 31:2 Pressure regulation supply air pressure below set point alarm limitBI953Alarm 31:3 Pressure regulation supply air pressure above set point alarm limitBI956Alarm 31:6 Pressure regulation extract air pressure sensor no. 6 com. errorBI957Alarm 31:7 Pressure regulation extract air press. below set point alarm limitBI958Alarm 31:8 Pressure regulation extract air press. above set point alarm limitBI966Alarm 32:1 ReCO2 I/O-module no. 0 com. errorBI967Alarm 32:2 ReCO2 pressure sensor no. 0 com. errorBI968Alarm 32:3 ReCO2 recirculation damper monitoring trippedBI969Alarm 32:4 ReCO2 outdoor air damper monitoring trippedBI981Alarm 33:1 Service period above alarm limitBI995Alarm 33:15 Lock function trippedBI996Alarm 34:1 External control I/O-module no. 3 com. errorBI997Alarm 34:2 External control I/O-module no. 6 com. errorBI1011Alarm 35:1 Booster diffusers I/O-module no. 8 com. errorBI1056Alarm 38:1 MIRU 1 com. errorBI1057Alarm 38:2 MIRU 1 motor controller alarm trippedBI1058Alarm 38:3 MIRU 1 motor controller com. errorBI1059Alarm 38:4 MIRU 1 air flow pressure sensor no. 0 com. errorBI1060Alarm 38:5 MIRU 1 pressure regulation sensor no. 1 com. errorBI1061Alarm 38:6 MIRU 1 temperature sensor defectiveBI1062Alarm 38:7 MIRU 1 air flow/pressure set point deviation from alarm limitBI1071Alarm 39:1 MIRU 2 com. errorBI1072Alarm 39:2 MIRU 2 motor controller alarm trippedBI1073Alarm 39:3 MIRU 2 motor controller com. errorBI1074Alarm 39:4 MIRU 2 air flow pressure sensor no. 0 com. errorBI1075Alarm 39:5 MIRU 2 pressure regulation sensor no. 1 com. errorBI1076Alarm 39:6 MIRU 2 temperature sensor defectiveBI1077Alarm 39:7 MIRU 2 air flow/pressure set point deviation from alarm limitBI1086Alarm 40:1 MIRU 3 com. errorBI1087Alarm 40:2 MIRU 3 motor controller alarm trippedBI1088Alarm 40:3 MIRU 3 motor controller com. errorBI1089Alarm 40:4 MIRU 3 air flow pressure sensor no. 0 com. errorBI1090Alarm 40:5 MIRU 3 pressure regulation sensor no. 1 com. errorBI1091Alarm 40:6 MIRU 3 temperature sensor defectiveBI1092Alarm 40:7 MIRU 3 air flow/pressure set point deviation from alarm limitBI1101Alarm 41:1 MIRU 4 com. errorBI1102Alarm 41:2 MIRU 4 motor controller alarm trippedBI1103Alarm 41:3 MIRU 4 motor controller com. errorBI1104Alarm 41:4 MIRU 4 air flow pressure sensor no. 0 com. errorBI1105Alarm 41:5 MIRU 4 pressure regulation sensor no. 1 com. errorBI1106Alarm 41:6 MIRU 4 temperature sensor defectiveBI1107Alarm 41:7 MIRU 4 air flow/pressure set point deviation from alarm limitBI1116Alarm 42:1 MIRU 5 com. errorBI1117Alarm 42:2 MIRU 5 motor controller alarm trippedBI1118Alarm 42:3 MIRU 5 motor controller com. errorBI1119Alarm 42:4 MIRU 5 air flow pressure sensor no. 0 com. errorBI1120Alarm 42:5 MIRU 5 pressure regulation sensor no. 1 com. errorBI1121Alarm 42:6 MIRU 5 temperature sensor defectiveBI1122Alarm 42:7 MIRU 5 air flow/pressure set point deviation from alarm limitBI1131Alarm 43:1 MIRU 6 com. errorBI1132Alarm 43:2 MIRU 6 motor controller alarm trippedBI1133Alarm 43:3 MIRU 6 motor controller com. errorBI1134Alarm 43:4 MIRU 6 air flow pressure sensor no. 0 com. errorBI1135Alarm 43:5 MIRU 6 pressure regulation sensor no. 1 com. errorBI1136Alarm 43:6 MIRU 6 temperature sensor defectiveBI1137Alarm 43:7 MIRU 6 air flow/pressure set point deviation from alarm limitBI1146Alarm 44:1 MIRU 7 com. errorBI1147Alarm 44:2 MIRU 7 motor controller alarm trippedBI1148Alarm 44:3 MIRU 7 motor controller com. errorBI1149Alarm 44:4 MIRU 7 air flow pressure sensor no. 0 com. errorBI1150Alarm 44:5 MIRU 7 pressure regulation sensor no. 1 com. errorBI1151Alarm 44:6 MIRU 7 temperature sensor defectiveBI1152Alarm 44:7 MIRU 7 air flow/pressure set point deviation from alarm limitBI1161Alarm 45:1 MIRU 8 com. errorBI1162Alarm 45:2 MIRU 8 motor controller alarm trippedBI1163Alarm 45:3 MIRU 8 motor controller com. errorBI1164Alarm 45:4 MIRU 8 air flow pressure sensor no. 0 com. errorBI1165Alarm 45:5 MIRU 8 pressure regulation sensor no. 1 com. errorBI1166Alarm 45:6 MIRU 8 temperature sensor defectiveBI1167Alarm 45:7 MIRU 8 air flow/pressure set point deviation from alarm limitBI1176Alarm 46:1 MIRU 9 com. errorBI1177Alarm 46:2 MIRU 9 motor controller alarm trippedBI1178Alarm 46:3 MIRU 9 motor controller com. errorBI1179Alarm 46:4 MIRU 9 air flow pressure sensor no. 0 com. errorBI1180Alarm 46:5 MIRU 9 pressure regulation sensor no. 1 com. errorBI1181Alarm 46:6 MIRU 9 temperature sensor defectiveBI1182Alarm 46:7 MIRU 9 air flow/pressure set point deviation from alarm limitBI1191Alarm 47:1 MIRU 10 com. errorBI1192Alarm 47:2 MIRU 10 motor controller alarm trippedBI1193Alarm 47:3 MIRU 10 motor controller com. errorBI1194Alarm 47:4 MIRU 10 air flow pressure sensor no. 0 com. errorBI1195Alarm 47:5 MIRU 10 pressure regulation sensor no. 1 com. errorBI1196Alarm 47:6 MIRU 10 temperature sensor defectiveBI1197Alarm 47:7 MIRU 10 air flow/pressure set point deviation from alarm limitBI1221Alarm 49:1 Supply air fan no. 1A com. errorBI1222Alarm 49:2 Supply air fan no. 1A motor controller over currentBI1223Alarm 49:3 Supply air fan no. 1A motor controller under voltageBI1224Alarm 49:4 Supply air fan no. 1A motor controller over voltageBI1225Alarm 49:5 Supply air fan no. 1A motor controller over temperatureBI1226Alarm 49:6 Supply air fan no. 1A motor controller start errorBI1227Alarm 49:7 Supply air fan no. 1A motor controller ripple errorBI1228Alarm 49:8 Supply air fan no. 1A motor controller phase errorBI1229Alarm 49:9 Supply air fan no. 1A motor controller internal memory errorBI1230Alarm 49:10 Supply air fan no. 1A motor controller current reductionBI1236Alarm 50:1 Supply air fan no. 2A com. errorBI1237Alarm 50:2 Supply air fan no. 2A motor controller over currentBI1238Alarm 50:3 Supply air fan no. 2A motor controller under voltageBI1239Alarm 50:4 Supply air fan no. 2A motor controller over voltageBI1240Alarm 50:5 Supply air fan no. 2A motor controller over temperatureBI1241Alarm 50:6 Supply air fan no. 2A motor controller start errorBI1242Alarm 50:7 Supply air fan no. 2A motor controller ripple errorBI1243Alarm 50:8 Supply air fan no. 2A motor controller phase errorBI1244Alarm 50:9 Supply air fan no. 2A motor controller internal memory errorBI1245Alarm 50:10 Supply air fan no. 2A motor controller current reductionBI1251Alarm 51:1 Supply air fan no. 3A com. errorBI1252Alarm 51:2 Supply air fan no. 3A motor controller over currentBI1253Alarm 51:3 Supply air fan no. 3A motor controller under voltageBI1254Alarm 51:4 Supply air fan no. 3A motor controller over voltageBI1255Alarm 51:5 Supply air fan no. 3A motor controller over temperatureBI1256Alarm 51:6 Supply air fan no. 3A motor controller start errorBI1257Alarm 51:7 Supply air fan no. 3A motor controller ripple errorBI1258Alarm 51:8 Supply air fan no. 3A motor controller phase errorBI1259Alarm 51:9 Supply air fan no. 3A motor controller internal memory errorBI1260Alarm 51:10 Supply air fan no. 3A motor controller current reductionBI1266Alarm 52:1 Supply air fan no. 1B com. errorBI1267Alarm 52:2 Supply air fan no. 1B motor controller over currentBI1268Alarm 52:3 Supply air fan no. 1B motor controller under voltageBI1269Alarm 52:4 Supply air fan no. 1B motor controller over voltageBI1270Alarm 52:5 Supply air fan no. 1B motor controller over temperatureBI1271Alarm 52:6 Supply air fan no. 1B motor controller start errorBI1272Alarm 52:7 Supply air fan no. 1B motor controller ripple errorBI1273Alarm 52:8 Supply air fan no. 1B motor controller phase errorBI1274Alarm 52:9 Supply air fan no. 1B motor controller internal memory errorBI1275Alarm 52:10 Supply air fan no. 1B motor controller current reductionBI1281Alarm 53:1 Supply air fan no. 2B com. errorBI1282Alarm 53:2 Supply air fan no. 2B motor controller over currentBI1283Alarm 53:3 Supply air fan no. 2B motor controller under voltageBI1284Alarm 53:4 Supply air fan no. 2B motor controller over voltageBI1285Alarm 53:5 Supply air fan no. 2B motor controller over temperatureBI1286Alarm 53:6 Supply air fan no. 2B motor controller start errorBI1287Alarm 53:7 Supply air fan no. 2B motor controller ripple errorBI1288Alarm 53:8 Supply air fan no. 2B motor controller phase errorBI1289Alarm 53:9 Supply air fan no. 2B motor controller internal memory errorBI1290Alarm 53:10 Supply air fan no. 2B motor controller current reductionBI1296Alarm 54:1 Supply air fan no. 3B com. errorBI1297Alarm 54:2 Supply air fan no. 3B motor controller over currentBI1298Alarm 54:3 Supply air fan no. 3B motor controller under voltageBI1299Alarm 54:4 Supply air fan no. 3B motor controller over voltageBI1300Alarm 54:5 Supply air fan no. 3B motor controller over temperatureBI1301Alarm 54:6 Supply air fan no. 3B motor controller start errorBI1302Alarm 54:7 Supply air fan no. 3B motor controller ripple errorBI1303Alarm 54:8 Supply air fan no. 3B motor controller phase errorBI1304Alarm 54:9 Supply air fan no. 3B motor controller internal memory errorBI1305Alarm 54:10 Supply air fan no. 3B motor controller current reductionBI1311Alarm 55:1 Extract air fan no. 1A com. errorBI1312Alarm 55:2 Extract air fan no. 1A motor controller over currentBI1313Alarm 55:3 Extract air fan no. 1A motor controller under voltageBI1314Alarm 55:4 Extract air fan no. 1A motor controller over voltageBI1315Alarm 55:5 Extract air fan no. 1A motor controller over temperatureBI1316Alarm 55:6 Extract air fan no. 1A motor controller start errorBI1317Alarm 55:7 Extract air fan no. 1A motor controller ripple errorBI1318Alarm 55:8 Extract air fan no. 1A motor controller phase errorBI1319Alarm 55:9 Extract air fan no. 1A motor controller internal memory errorBI1320Alarm 55:10 Extract air fan no. 1A motor controller current reductionBI1326Alarm 56:1 Extract air fan no. 2A com. errorBI1327Alarm 56:2 Extract air fan no. 2A motor controller over currentBI1328Alarm 56:3 Extract air fan no. 2A motor controller under voltageBI1329Alarm 56:4 Extract air fan no. 2A motor controller over voltageBI1330Alarm 56:5 Extract air fan no. 2A motor controller over temperatureBI1331Alarm 56:6 Extract air fan no. 2A motor controller start errorBI1332Alarm 56:7 Extract air fan no. 2A motor controller ripple errorBI1333Alarm 56:8 Extract air fan no. 2A motor controller phase errorBI1334Alarm 56:9 Extract air fan no. 2A motor controller internal memory errorBI1335Alarm 56:10 Extract air fan no. 2A motor controller current reductionBI1341Alarm 57:1 Extract air fan no. 3A com. errorBI1342Alarm 57:2 Extract air fan no. 3A motor controller over currentBI1343Alarm 57:3 Extract air fan no. 3A motor controller under voltageBI1344Alarm 57:4 Extract air fan no. 3A motor controller over voltageBI1345Alarm 57:5 Extract air fan no. 3A motor controller over temperatureBI1346Alarm 57:6 Extract air fan no. 3A motor controller start errorBI1347Alarm 57:7 Extract air fan no. 3A motor controller ripple errorBI1348Alarm 57:8 Extract air fan no. 3A motor controller phase errorBI1349Alarm 57:9 Extract air fan no. 3A motor controller internal memory errorBI1350Alarm 57:10 Extract air fan no. 3A motor controller current reductionBI1356Alarm 58:1 Extract air fan no. 1B com. errorBI1357Alarm 58:2 Extract air fan no. 1B motor controller over currentBI1358Alarm 58:3 Extract air fan no. 1B motor controller under voltageBI1359Alarm 58:4 Extract air fan no. 1B motor controller over voltageBI1360Alarm 58:5 Extract air fan no. 1B motor controller over temperatureBI1361Alarm 58:6 Extract air fan no. 1B motor controller start errorBI1362Alarm 58:7 Extract air fan no. 1B motor controller ripple errorBI1363Alarm 58:8 Extract air fan no. 1B motor controller phase errorBI1364Alarm 58:9 Extract air fan no. 1B motor controller internal memory errorBI1365Alarm 58:10 Extract air fan no. 1B motor controller current reductionBI1371Alarm 59:1 Extract air fan no. 2B com. errorBI1372Alarm 59:2 Extract air fan no. 2B motor controller over currentBI1373Alarm 59:3 Extract air fan no. 2B motor controller under voltageBI1374Alarm 59:4 Extract air fan no. 2B motor controller over voltageBI1375Alarm 59:5 Extract air fan no. 2B motor controller over temperatureBI1376Alarm 59:6 Extract air fan no. 2B motor controller start errorBI1377Alarm 59:7 Extract air fan no. 2B motor controller ripple errorBI1378Alarm 59:8 Extract air fan no. 2B motor controller phase errorBI1379Alarm 59:9 Extract air fan no. 2B motor controller internal memory errorBI1380Alarm 59:10 Extract air fan no. 2B motor controller current reductionBI1386Alarm 60:1 Extract air fan no. 3B com. errorBI1387Alarm 60:2 Extract air fan no. 3B motor controller over currentBI1388Alarm 60:3 Extract air fan no. 3B motor controller under voltageBI1389Alarm 60:4 Extract air fan no. 3B motor controller over voltageBI1390Alarm 60:5 Extract air fan no. 3B motor controller over temperatureBI1391Alarm 60:6 Extract air fan no. 3B motor controller start errorBI1392Alarm 60:7 Extract air fan no. 3B motor controller ripple errorBI1393Alarm 60:8 Extract air fan no. 3B motor controller phase errorBI1394Alarm 60:9 Extract air fan no. 3B motor controller internal memory errorBI1395Alarm 60:10 Extract air fan no. 3B motor controller current reductionBI1952Info 97:12 Plate heat exchanger bypass optimization not performedBI1953Info 97:13 Plate heat exchanger bypass optimization not approvedBI1954Info 97:14 Plate heat exchanger defrost calibration not performedBI1955Info 97:15 Plate heat exchanger defrost calibration not approvedBI1956Info 98:1 Supply air pre-filter calibration not performedBI1957Info 98:2 Supply air pre-filter calibration not approvedBI1958Info 98:3 Extract air pre-filter calibration not performedBI1959Info 98:4 Extract air pre-filter calibration not approvedBI1960Info 98:5 Supply air air handling unit filter calibration not performedBI1961Info 98:6 Supply air air handling unit filter calibration not approvedBI1962Info 98:7 Extract air air handling unit filter calibration not performedBI1963Info 98:8 Extract air air handling unit filter calibration not approvedBI1964Info 98:9 Supply air end filter calibration not performedBI1965Info 98:10 Supply air end filter calibration not approvedBI1966Info 98:11 Rotary heat exchanger defrost calibration not performedBI1967Info 98:12 Rotary heat exchanger defrost calibration not approvedBI1968Info 98:13 ReCO2 calibration not performedBI1969Info 98:14 ReCO2 calibration not approvedBI1970Info 98:15 ReCO2 incorrect settingBI1971Info 99:1 E-mail errorBI1977Info 99:7 SD card memory soon full. Oldest log data will soon be deletedBI1978Info 99:8 SD card memory full. Oldest log data deletedBI1984Info 99:14 Internal serial memory error CPU 1BI1985Info 99:15 Clock circuit defectiveBI2001Active alarm group 1BI2002Active alarm group 2BI2003Active alarm group 3BI2004Active alarm group 4BI2005Active alarm group 5BI2006Active alarm group 6BI2007Active alarm group 7BI2008Active alarm group 8BI2009Active alarm group 9BI2010Active alarm group 10BI2011Active alarm group 11BI2012Active alarm group 12BI2013Active alarm group 13BI2014Active alarm group 14BI2015Active alarm group 15BI2016Active alarm group 16BI2017Active alarm group 17BI2018Active alarm group 18BI2019Active alarm group 19BI2020Active alarm group 20BI2021Active alarm group 21BI2022Active alarm group 22BI2023Active alarm group 23BI2024Active alarm group 24BI2025Active alarm group 25BI2026Active alarm group 26BI2027Active alarm group 27BI2028Active alarm group 28BI2029Active alarm group 29BI2030Active alarm group 30BI2031Active alarm group 31BI2032Active alarm group 32BI2033Active alarm group 33BI2034Active alarm group 34BI2035Active alarm group 35BI2036Active alarm group 36BI2037Active alarm group 37BI2038Active alarm group 38BI2039Active alarm group 39BI2040Active alarm group 40BI2041Active alarm group 41BI2042Active alarm group 42BI2043Active alarm group 43BI2044Active alarm group 44BI2045Active alarm group 45BI2046Active alarm group 46BI2047Active alarm group 47BI2048Active alarm group 48BI2049Active alarm group 49BI2050Active alarm group 50BI2051Active alarm group 51BI2052Active alarm group 52BI2053Active alarm group 53BI2054Active alarm group 54BI2055Active alarm group 55BI2056Active alarm group 56BI2057Active alarm group 57BI2058Active alarm group 58BI2059Active alarm group 59BI2060Active alarm group 60BI2061Active alarm group 61BI2062Active alarm group 62BI2063Active alarm group 63BI2064Active alarm group 64BI2065Active alarm group 65BI2066Active alarm group 66BI2067Active alarm group 67BI2068Active alarm group 68BI2069Active alarm group 69BI2070Active alarm group 70BI2071Active alarm group 71BI2072Active alarm group 72BI2073Active alarm group 73BI2074Active alarm group 74BI2075Active alarm group 75BI2076Active alarm group 76BI2077Active alarm group 77BI2078Active alarm group 78BI2079Active alarm group 79BI2080Active alarm group 80BI2081Active alarm group 81BI2082Active alarm group 82BI2083Active alarm group 83BI2084Active alarm group 84BI2085Active alarm group 85BI2086Active alarm group 86BI2087Active alarm group 87BI2088Active alarm group 88BI2089Active alarm group 89BI2090Active alarm group 90BI2091Active alarm group 91BI2092Active alarm group 92BI2093Active alarm group 93BI2094Active alarm group 94BI2095Active alarm group 95BI2096Active alarm group 96BI2097Active alarm group 97BI2098Active alarm group 98BI2099Active alarm group 99BO1Booster diffusersBV1Alarm resetBV3Internal fire alarm functionBV29SA flow pressure sensor auto zero calibrationBV30EA flow pressure sensor auto zero calibrationBV31SA duct pressure sensor auto zero calibrationBV32EA duct pressure sensor auto zero calibrationBV33ReCO2 pressure sensor auto zero calibrationBV34RHX defrost pressure sensor auto calibrationBV35Carry over control pressure sensor auto calibrationBV36SA filter pressure sensor auto zero calibrationBV37EA filter pressure sensor auto zero calibrationBV38SA pre-filter pressure sensor auto zero calibrationBV39EA pre-filter pressure sensor auto zero calibrationBV40SA end-filter pressure sensor auto zero calibrationBV46SA flow pressure sensor activate zero calibrationBV47EA flow pressure sensor activate zero calibrationBV48SA duct pressure sensor activate zero calibrationBV49EA duct pressure sensor activate zero calibrationBV50ReCO2 pressure sensor activate calibrationBV51RHX Defrost pressure sensor activate calibrationBV52Carry over control pressure sensor activate zero calibrationBV53SA filter pressure sensor activate zero calibrationBV54EA filter pressure sensor activate zero calibrationBV55SA pre-filter pressure sensor activate zero calibrationBV56EA pre-filter pressure sensor activate zero calibrationBV57SA end-filter pressure sensor activate zero calibrationBV162External room sensor 1 functionBV163External room sensor 2 functionBV164External room sensor 3 functionBV165External room sensor 4 functionBV167External room temp from BMS functionBV172External OA sensor 1 functionBV173External OA sensor 2 functionBV174External OA sensor 3 functionBV175External OA sensor 4 functionBV177External OA temp from BMS functionBV182RHX defrost functionBV183RHX defrost calibrationBV187RHX carry over control functionBV190RHX min exhaust air temp functionBV198PHX periodic operation of bypass damper functionBV201PX bypass optimizeBV205CHX periodic operation of pump functionBV206CHX periodic operation of valve functionBV228Re-heat periodic operation of pump functionBV229Re-heat periodic operation of valve functionBV245Extra regulation 1 periodic operation of pump functionBV246Extra regulation 1 periodic operation of valve functionBV274Cool relay 1 periodic operation of pump functionBV275Cool relay 2 periodic operation of pump functionBV276Cool periodic operation of valve functionBV284Summer night cool functionBV296Intermittent night heat functionBV302Intermittent night heat recirculation functionBV305Morning boost functionBV320Heating boost functionBV325Xzone heat functionBV327Xzone cool functionBV374Xzone external room sensor 1 functionBV375Xzone external room sensor 2 functionBV376Xzone external room sensor 3 functionBV377Xzone external room sensor 4 functionBV379Xzone external room temp from BMS functionBV386Xzone reheat periodic operation of pump functionBV387Xzone reheat periodic operation of valve functionBV400Xzone Cool relay 1 periodic operation of pump functionBV401Xzone Cool relay 2 periodic operation of pump functionBV402Xzone Cool periodic operation of valve functionBV410Pre-heat functionBV414Pre-heat periodic operation of pump functionBV415Pre-heat periodic operation of valve functionBV425ReCO2 CalibrationBV457Dehumidifying functionBV459Heat exchange active in dehumidifying sequenceBV465VOC sensor functionBV490SMART Link WB Optimize functionBV504AQUA Link FunctionBV530AYC Heated water periodic operation of pumpBV531AYC Heated water periodic operation of valveBV536AYC Heated water OA temp compensationBV547AYC Heated water room temp compensation functionBV548AYC Heated water room temp compensation at nightBV553AYC Heated water night temp compensation functionBV579AYC Chilled water periodic operation of pumpBV580AYC Chilled water periodic operation of valveBV585AYC Chilled water OA temp compensationBV596AYC Chilled water room temp compensation functionBV597AYC Chilled water room temp compensation at nightBV602AYC Chilled water night temp compensation functionBV618AYC Chilled water dew point compensation air flow boostBV637Optimize functionMI2Application id/AHU TypeMI3Air flow directionMI115PHX typeMI140Extra regulation sequence 1 coil typeMI142Extra regulation sequence 2 coil typeMI152Re-heat coil typeMI163Cool coil typeMI198Xzone heat, coil typeMI209Xzone cool, coil typeMI224Pre-heat coil typeMI320SMART Link, DX cool modeMI592Operation levelMO1Boost Supply airMO2Boost Extract airMV1SA Fan regulation modeMV2EA Fan regulation modeMV4Internal fire alarm reset functionMV7External fire alarm no. 1 reset functionMV8External fire alarm no. 2 reset functionMV11External alarm no. 1 reset functionMV12External alarm no. 2 reset functionMV15External alarm no. 1 input functionMV16External alarm no. 2 input functionMV53Outdoor temp compensation functionMV78Down regulation functionMV84Fans in operation at fire alarm 1 functionMV87Fans in operation at fire alarm 2 functionMV90Fans in operation at internal fire alarm functionMV95Pre-filter functionMV96Pre-filter calibrationMV101AHU filter functionMV102AHU filter calibrationMV107SA end filter functionMV108SA end filter calibrationMV115Temperature regulation modeMV166External room sensors measurement functionMV176External OA sensors measurement functionMV188RHX sorption rotor functionMV237Extra regulation sequence 1 functionMV238Extra regulation sequence 1 output functionMV251Extra regulation 1 temperature protection functionMV254Season heat functionMV255Season heat manual settingMV261Cool on/off regulation functionMV313Cooling boost functionMV329Xzone temperature regulation modeMV378Xzone external room sensors measurement functionMV395Xzone Cool on/off regulation functionMV423ReCO2-CO2 functionMV424ReCO2 temperature regulation sequence functionMV441Humidifying functionMV442Humidifying sensorMV457DeHumidifying functionMV469COOL DX FunctionMV481SMART Link FunctionMV505AQUA Link Pump alarm functionMV521AYC FunctionMV528AYC Heated water signal monitor function for pumpMV555AYC Heated water night temp compensation time 1 (days)MV562AYC Heated water night temp compensation time 2 (days)MV577AYC Chilled water signal monitor function for pumpMV604AYC Chilled water night temp compensation time 1 (days)MV611AYC Chilled water night temp compensation time 2 (days)MV660MIRU Control 1 functionMV661MIRU Control 2 functionMV662MIRU Control 3 functionMV663MIRU Control 4 functionMV664MIRU Control 5 functionMV665MIRU Control 6 functionMV666MIRU Control 7 functionMV667MIRU Control 8 functionMV668MIRU Control 9 functionMV669MIRU Control 10 functionMV671MIRU Control 1 Balanced air flow functionMV679MIRU Control 2 Balanced air flow functionMV687MIRU Control 3 Balanced air flow functionMV695MIRU Control 4 Balanced air flow functionMV703MIRU Control 5 Balanced air flow functionMV711MIRU Control 6 Balanced air flow functionMV719MIRU Control 7 Balanced air flow functionMV727MIRU Control 8 Balanced air flow functionMV735MIRU Control 9 Balanced air flow functionMV743MIRU Control 10 Balanced air flow functionMV793Communication operation levelCAL0Calendar #1CAL1Calendar #2NC0NC 00 A-AlarmNC1NC 01 B-AlarmNC3NC 03 Alarms specified in BACnetNC10NC 10 Info messageNC11NC 11 Events specified in BACnetSCH0Schedule #1
Integration notes
- Object tables are the same on every unit; points for accessories or heat-exchanger types not fitted read zero or inactive.
- The Misc column in the source marks the program version (1.11-1.13) that added some objects.
- Most alarms appear as individual BIs named 'Alarm <group>:<number> ...'; BI-13/14 summarize A- and B-class alarms.
- Airflows are in l/s and temperatures in °C as published.
- BI-104's object name is printed truncated in the source (a pressure-limit sentence) and is kept as printed.
- BV-457 Dehumidifying function is marked as moved to MV-457.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GOLD generation E (RX/PX/CX/SD) BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP
How many BACnet points does the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP have?
This list has 1452 BACnet objects: 356 analog inputs, 1 analog output, 357 analog values, 554 binary inputs, 1 binary output, 91 binary values, 2 calendars, 12 multi-state inputs, 2 multi-state outputs, 5 notification classs, 1 schedule, 70 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet points are writable?
525 of the 1452 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP BACnet documentation?
The source is BACnet IP GOLD RX/PX/CX/SD, Generation E (GOLD_E_BACnet_150316), revision 2015-03-16, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/air-handling-units/gold-version-e-2013-2017/functions/_en/gold_e_bacnet_150316.pdf.
What are the minimum BACnet points to integrate the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?
Start with MV 793 Communication operation level (BMS start/stop and speed command); AV 132 SA temperature set point (Supply air temperature setpoint); AV 135 EA/Room temperature set point (Extract/room temperature setpoint); BV 1 Alarm reset (Resets all active alarms); MI 592 Operation level (Actual operating state and who stopped the unit); AI 64 SA Temperature (Supply air temperature); AI 66 EA Temperature (Extract air temperature); AI 73 Outdoor temperature (Outdoor air temp measured by the unit, °C); BI 13 A-alarm active (Any A-class alarm); BI 14 B-alarm active (Any B-class alarm).
How do I enable BMS control of the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?
MV-793 Communication operation level: 1=Auto (unit follows its own time channel), 2=Total stop, 3=Low speed, 4=High speed, 5=Normal stop, 6=Extended normal stop. MI-592 shows whether a stop came from communication, the hand terminal, a digital input, the time channel or an alarm.
Can the BMS supply sensor values to the Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP?
Room temperature can come from the BMS by enabling BV-167 'External room temp from BMS function' and writing AV-168; outdoor temperature likewise via BV-177 and AV-178. Each has an 'alarm time' AV in minutes (AV-169, AV-179; AV-179 defaults to 5). Xzone has its own BMS room temperature (BV-379, AV-380, AV-381).
How do I check these points on the real GOLD generation E (RX/PX/CX/SD) BACnet IP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Swegon BACnet points lists
- Air handling unit controller
Swegon Compact / GOLD LP BACnet IP (PV 2.01+)
Swegon COMPACT and GOLD LP air handling units with controller program version 2.01 or later.
Also known as: COMPACT Air, GOLD LP, Compact/GOLD LP, GB.BACnet480.100129, BACnet480 - Air handling unit controller
Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP
Swegon GOLD air handling units of generation C and D (RX, PX, CX and SD versions, built about 2010-2013) running program version 6.08 or later.
Also known as: GOLD C, GOLD D, GOLD RX, GOLD PX, GOLD CX, GOLD SD, GOLD version D, GB.BACnet480.121017, BACnet480 - Air handling unit controller
Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48
Swegon GOLD air handling units of generations E and F (RX, PX, CX and SD versions) with program version 2.48.
Also known as: GOLD F, GOLD version F, GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_F_BACnet_251202 - Other equipment (demand-controlled ventilation system controller)
Swegon SuperWISE (generation 1) BACnet IP - system objects
Swegon SuperWISE (first generation) system controllers for WISE demand-controlled ventilation, program version 1.25.
Also known as: SuperWISE, Super WISE, WISE gen 1, GB.BACnetSuper WISE.140603, SuperWISE_BACnet_list_ver_1.3
Source: BACnet IP GOLD RX/PX/CX/SD, Generation E · GOLD_E_BACnet_150316 · rev. 2015-03-16. Object names, instances and units are reproduced as published; descriptions are our own.