Air handling unit controller · BACnet points list
Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet points list
Updated 28 October 2026
Swegon's Compact and GOLD LP air handlers have a built-in BACnet IP interface (B-ASC profile) on the unit controller. The list has 600 objects of four types: analog inputs for airflows, pressures, temperatures and operating modes, analog values for setpoints, regulator tuning, clock and time/year channels, plus binary inputs and values for outputs, alarms and functions. Several numbered 'Reserve' objects are placeholders.
This page lists 600 BACnet objects for the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) — 401 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Swegon’s own free documentation, linked below.
- Manufacturer
- Swegon
- Model
- Compact / GOLD LP BACnet IP (PV 2.01+)
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 600 (401 writable)
- Transport
- BACnet IP
- Firmware
- Program version 2.01 or later
- Also known as
- COMPACT Air, GOLD LP, Compact/GOLD LP, GB.BACnet480.100129, BACnet480
Reference only, provided as-is: verify against Swegon’s current documentation and the live device before use. Not official Swegon information. Terms of use.
BMS integration notes: Swegon Compact / GOLD LP BACnet IP (PV 2.01+)
Write AV-174 Communication operation mode to run the unit from the BMS (0 hands control back to the unit's own time channels) and read AI-84 Operation mode 1 to see why it is running or stopped. Map supply and extract air temperature, the EA/room setpoint and the low/high speed airflow or pressure setpoints, plus BI-5/BI-6 A/B alarms and BV-0 alarm reset. These are the objects the source's overview page highlights.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 174 | Communication operation mode | BMS stop / low / high / auto command | Write |
| AV 40 | SA Temperature setpoint | Supply air temperature setpoint | Write |
| AV 41 | EA/Room Temperature setpoint | Extract/room temperature setpoint | Write |
| BV 0 | Alarm reset | Resets tripped alarms | Write |
| AI 84 | Operation mode 1 | Current operating reason (stop, speed, channel) | Read |
| AI 27 | SA Temperature | Supply air temperature | Read |
| AI 28 | EA/Room temperature | Extract/room temperature | Read |
| AI 29 | Outdoor temperatur | Outdoor air temp measured by the unit, °C | Read |
| BI 5 | A-alarm. | A-class alarm active | Read |
| BI 6 | B-alarm. | B-class alarm active | Read |
Enable & remote start
AV-174 Communication operation mode: 0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2. Summer night cool, intermittent night heat and morning boost still run at stop 2.
Heartbeat & communication loss
Only for BMS-supplied temperatures: AV-204 'Timeout temperature com.' (0-9999 min) sets the timeout for room and outdoor temperatures written over communication. The document does not describe a timeout for the operation mode command.
Sensors & values from the BMS
Set AV-200 EA/Room temperature (external) func. to 2 (Communication) and write AV-201; set AV-202 Outdoor temperature (external) func. to 2 and write AV-203. AV-204 is the timeout for those written values.
Network setup
- BACnet IP only; the device is a B-ASC supporting read/write property, COV and dynamic device/object binding.
- Swegon refers to a separate BACnet PICS and EDE file; device instance and IP settings are not in this document.
Watch out for
- Setpoints exist separately for low and high speed (e.g. AV-0/1 SA airflow, AV-8/9 SA duct pressure).
- Fan regulation mode (AV-97 SA, EA equivalent) decides whether airflow, pressure or demand setpoints are used.
- Clock, time-channel and year-channel AVs (around 120-290) are configuration settings.
- Reserve objects return no meaningful data.
Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | SA Airflow | Present supply airflow. | l/s | Read | |
| AI | 1 | SA Airflow regulator | Present supply airflow regulator setpoint. | l/s | Read | |
| AI | 2 | EA Airflow | Present extract airflow. | l/s | Read | |
| AI | 3 | EA Airflow regulator | Present extract airflow regulator setpoint. | l/s | Read | |
| AI | 4 | SA Duct pressure | Present supply air duct pressure. | Pa | Read | |
| AI | 5 | SA Duct pressure regulator | Present supply air duct pressure regulator setpoint. | Pa | Read | |
| AI | 6 | EA Duct pressure | Present extract air duct pressure. | Pa | Read | |
| AI | 7 | EA Duct pressure regulator | Present extract air duct pressure regulator setpoint. | Pa | Read | |
| AI | 8 | Reserve | Read | |||
| AI | 9 | SA VAV demand regulator | Present supply air VAV demand regulator setpoint. | % | Read | |
| AI | 10 | Reserve | Read | |||
| AI | 11 | EA VAV demand regulator | Present extract air VAV demand regulator setpoint. | % | Read | |
| AI | 12 | SA Fan level | Present running level for the supply air fan. | % | Read | |
| AI | 13 | EA Fan level | Present running level for the extract air fan. | % | Read | |
| AI | 14 | SA Fan effect | Present power consumption level for the supply air fan. | W | Read | |
| AI | 15 | EA Fan effect | Present power consumption level for the extract air fan. | W | Read | |
| AI | 16 | SFP | SFP supply air + extract air. | Read | ||
| AI | 17 | Reserve | Read | |||
| AI | 18 | Reserve | Read | |||
| AI | 19 | SA Voltage | Present voltage level for the supply air fan. | V | Read | |
| AI | 20 | EA Voltage | Present voltage level for the extract air fan. | V | Read | |
| AI | 21 | SA Current | Present current level for the supply air fan. | A | Read | |
| AI | 22 | EA Current | Present current level for the extract air fan. | A | Read | |
| AI | 23 | SA Airflow pressure | Present airflow pressure in the supply air fan inlet. | Pa | Read | |
| AI | 24 | EA Airflow pressure | Present airflow pressure in the extract air fan inlet. | Pa | Read | |
| AI | 25 | SA Temp regulator | Present supply air temperature regulator setpoint. | °C | Read | |
| AI | 26 | EA Temp regulator | Present extract air temperature regulator setpoint. | °C | Read | |
| AImin | 27 | SA Temperature | Present supply air temperature. | °C | Read | |
| AImin | 28 | EA/Room temperature | Present extract air/room temperature in the unit. | °C | Read | |
| AImin | 29 | Outdoor temperatur | Present outdoor air temperature in the unit. | °C | Read | |
| AI | 30 | EA/Room temperature (external) | Present room temperature external from the unit. | °C | Read | |
| AI | 31 | Outdoor temperatur (external) | Present outdoor air temperature external from the unit. | °C | Read | |
| AI | 32 | Anti frost temperature | Present anti frost temperature for water reheating coils. | °C | Read | |
| AI | 33 | Reserve | Read | |||
| AI | 34 | Reserve | Read | |||
| AI | 35 | Rotary heat exchanger level | Present operation level from rotary heat exchanger. | % | Read | |
| AI | 36 | Reheat level | Present level of reheat. | % | Read | |
| AI | 37 | SA Down regulation level | Present level of supply airflow down regulation. | % | Read | |
| AI | 38 | Reserve | Read | |||
| AI | 39 | Cooling level | Present level of cooling. | % | Read | |
| AI | 40 | Heating boost level | Present level of heating boost. | % | Read | |
| AI | 41 | Cooling boost level | Present level of cooling boost. | % | Read | |
| AI | 42 | HX pressure level | Present pressure drop for the rotary heat exchanger. | Pa | Read | |
| AI | 43 | HX pressure alarm limit | Present pressure drop alarm limit for the rotary heat exchanger. | Pa | Read | |
| AI | 44 | HX temperature | Present temperature inside the control unit for the rotary heat exchanger. | °C | Read | |
| AI | 45 | Effect reduction level | Present level of max output signal for electrical reheaters, active during low | % | Read | |
| AI | 46 | Anti frost temp setpoint/operation | Present anti frost temperature setpoint for water reheating coils during unit operation. | °C | Read | |
| AI | 47 | Anti frost temp setpoint/stop | Present anti frost temperature setpoint for water reheating coils when the unit | °C | Read | |
| AI | 48 | Anti frost temp alarm limit | Setting of antifrost temperature alarm limit. | °C | Read | |
| AI | 49 | Supply air filter pressure level | Present supply air filter pressure drop. | Pa | Read | |
| AI | 50 | Supply air filter pressure alarm limit. | Present supply air filter pressure alarm limit. | Pa | Read | |
| AI | 51 | Supply air filter pressure level, new | Supply air filter pressure saved from calibration. | Pa | Read | |
| AI | 52 | Extract air filter pressure level | Present extract air filter pressure drop. | Pa | Read | |
| AI | 53 | Extract air filter pressure alarm limit. | Present extract air filter pressure alarm limit. | Pa | Read | |
| AI | 54 | Extract air filter pressure level, new | Extract air filter pressure saved from calibration. | Pa | Read | |
| AI | 55 | Reserve | Read | |||
| AI | 56 | Coil type | Present connected reheat coil type. | Read | ||
| AI | 57 | Cool step time | Present time between cool step shift. | s | Read | |
| AI | 58 | Cool relay 1 restart time | Present time between two starts of cool relay 1. | s | Read | |
| AI | 59 | Cool relay 2 restart time | Present time between two starts of cool relay 2. | s | Read | |
| AI | 60 | Programversion, HMI | Present programversion for the handterminal. | Read | ||
| AI | 61 | Programversion, HMI-slave | Present programversion for the extra handterminal. | Read | ||
| AI | 62 | Programversion, main controller. | Present programversion for the main control unit. | Read | ||
| AI | 63 | Programversion, SA FC-1. | Present programversion for the supply air frequency converter no.1. | Read | ||
| AI | 64 | Programversion, SA FC-2. | Present programversion for the supply air frequency converter no.2. | Read | ||
| AI | 65 | Programversion, EA FC-1. | Present programversion for the extract air frequency converter no.1. | Read | ||
| AI | 66 | Programversion, EA FC-2. | Present programversion for the extract air frequency converter no.2. | Read | ||
| AI | 67 | Programversion, HX control unit | Present programversion for the rotary heat exchange control unit. | Read | ||
| AI | 68 | Weekday | Present weekday for the unit's internal clock. | Read | ||
| AI | 69 | Extended low speed op. Hours | Present time for extended low speed operation. | Read | ||
| AI | 70 | Extended low speed op. Minutes | Present time for extended low speed operation. | Read | ||
| AI | 71 | Extended high speed op. Hours | Present time for extended high speed operation. | Read | ||
| AI | 72 | Extended high speed op. Minutes | Present time for extended high speed operation. | Read | ||
| AI | 73 | SA Fan operation time | Present operation time for the supply air fan, measured in minutes and | Read | ||
| AI | 74 | EA Fan operation time | Present operation time for the extract air fan, measured in minutes and | Read | ||
| AI | 75 | Cool operation time | Present operation time for cooling, measured in minutes and present in days | Read | ||
| AI | 76 | Heat exchange operation time | Present operation time for heat exchange, measured in minutes and present in | Read | ||
| AI | 77 | Reheat operation time | Present operation time for reheat, measured in minutes and present in days | Read | ||
| AI | 78 | Present tripped alarm | Present tripped alarm number with highest priority. | Read | ||
| AI | 79 | Active not tripped alarm no.1 | Present active alarm in delay. | Read | ||
| AI | 80 | Active not tripped alarm no.2 | Present active alarm in delay. | Read | ||
| AI | 81 | Active not tripped alarm no.3 | Present active alarm in delay. | Read | ||
| AI | 82 | SA Fan size | Present supply air fan size. | Read | ||
| AI | 83 | EA Fan size | Present extract air fan size. | Read | ||
| AImin | 84 | Operation mode 1 | Read | 0=Manual stop, 1=Ext. stop, 2=Com. stop 1, 3=Manual high speed, 4=Summer night cooling, 5=Int. night heat, 6=Manual low speed, 7=Ext. high speed, 8=Com. high speed, 9=Year channel stop, 10=Year channel high speed, 11=Year channel low speed, 12=Time channel high speed, 13=Ext. low speed, 14=Com. low speed, 15=Time channel low speed, 16=Time channel stop, 17=Low speed=stop, 18=Com. stop 2 | ||
| AI | 85 | Operation mode 2 | Read | 0=, 1=Coold air recovery, 2=Cooling boost, 3=SA down regulation, 4=HX defrosting, 5=Anti frost func. active, 6=Effect reduction, 7=Startup, 8=Zero calibration, 9=Extended low speed, 10=Extended high speed, 11=Air adjustment, 12=Cooling off, 13=Purging R.HX, 14=Extended R.HX. op, 15=Filter calibration, 16=R.HX. calibration, 17=Morning boost, 18=Heating boost, 19=Alarm, 20=Cooling pressure reduction, 21=Startup extract air fan, 22=Reserve, 23=Airing, 24=Heating | ||
| AI | 86 | Operation mode, manual | Present manual operation set on the unit's handterminal. | Read | 0=Stop, 1=Auto operation, 2=Manual low speed, 3=Manual high speed | |
| AI | 87 | Copy of Input Status 1-16. | Bit 0=1x0001 Bit 1=1x0002 Bit 15=1x0016 | Read | ||
| AI | 88 | Copy of Input Status 17-32. | Bit 0=1x00017 Bit 1=1x00018 Bit 15=1x0032 | Read | ||
| AI | 89 | Copy of Input Status 33-48. | Bit 0=1x00033 Bit 1=1x00034 Bit 15=1x0048 | Read | ||
| AI | 90 | Heat exchanger regulator | Present level of heat exchanger regulator. | % | Read | |
| AI | 91 | Extract air-humidity | Present level of extract air-humidity. | % | Read | |
| AI | 92 | Extract air-humidity temperature | Present temperature inside extract air-humidity sensor. | °C | Read | |
| AI | 93 | Extract air-dewpoint | Calculated extract air-dewpoint. | °C | Read | |
| AI | 94 | AYC chilled water temperature | Present AYC chilled water temperature. | °C | Read | |
| AI | 95 | AYC chilled water temperature regulator | Present AYC chilled water temperature regulator setpoint. | °C | Read | |
| AI | 96 | AYC chilled water output | Present level of AYC chilled water valve output. | % | Read | |
| AI | 97 | Supply air-dewpoint regulator | Present supply air-dewpoint regulator setpoint. | °C | Read | |
| AI | 98 | Supply air-humidity | Present level of supply air-humidity | % | Read | |
| AI | 99 | Supply air-humidity temperature | Present temperature inside supply air-humidity sensor. | °C | Read | |
| AI | 100 | Supply air-dewpoint | Calculated supply air-dewpoint. | °C | Read | |
| AI | 101 | Reserve | Read | |||
| AI | 102 | Reserve | Read | |||
| AI | 103 | Reserve | Read | |||
| AI | 104 | Reserve | Read | |||
| AI | 105 | R.HX. Efficiency | Calculated level of rotary heat exchanger efficiency. | % | Read | |
| AI | 106 | Reserve | Read | |||
| AI | 107 | Reserve | Read | |||
| AI | 108 | Supply air prefilter pressure level | Present supply air prefilter pressure drop. | Pa | Read | |
| AI | 109 | Supply air prefilter pressure alarm limit. | Present supply air prefilter pressure alarm limit. | Pa | Read | |
| AI | 110 | Supply air prefilter pressure level, new | Supply air prefilter pressure saved from calibration. | Pa | Read | |
| AI | 111 | Extract air prefilter pressure level | Present extract air prefilter pressure drop. | Pa | Read | |
| AI | 112 | Extract air prefilter pressure alarm limit. | Present extract air prefilter pressure alarm limit. | Pa | Read | |
| AI | 113 | Extract air prefilter pressure level, new | Extract air prefilter pressure saved from calibration. | Pa | Read | |
| AI | 114 | Reserve | Read | |||
| AI | 115 | Reserve | Read | |||
| AI | 116 | Reserve | Read | |||
| AI | 117 | Reserve | Read | |||
| AI | 118 | Reserve | Read | |||
| AI | 119 | Reserve | Read | |||
| AI | 120 | Reserve | Read | |||
| AI | 121 | Reserve | Read | |||
| AI | 122 | Reserve | Read | |||
| AI | 123 | Reserve | Read | |||
| AI | 124 | Pre-heating air temperature | Present pre-heating air temperature. | °C | Read | |
| AI | 125 | Pre-heating level | Present level of pre-heating. | % | Read | |
| AI | 126 | Pre-heating anti frost temperature | Present anti frost temperature for water pre-heating coils. | °C | Read | |
| AI | 127 | Reserve | Read | |||
| AI | 128 | Reserve | Read | |||
| AI | 129 | Reserve | Read | |||
| AI | 130 | Reserve | Read | |||
| AI | 131 | Reserve | Read | |||
| AI | 132 | Reserve | Read | |||
| AI | 133 | Preheat operation time | Present operation time for preheat, measured in minutes and present in days | Read | ||
| AI | 134 | Reserve | Read | |||
| AI | 135 | Reserve | Read | |||
| AI | 136 | Demand VOC Level | Present level of demand VOC input. | % | Read | |
| AI | 137 | Demand Vin Level | Present level of demand 0-10VDC input. | % | Read | |
| AI | 138 | SA Filter level calculated | Present level of calculated supply air filter. | % | Read | |
| AI | 139 | EA Filter level calculated | Present level of calculated extract air filter. | % | Read | |
| AI | 140 | AYC heat temperature | Present AYC heat temperature. | °C | Read | |
| AI | 141 | AYC heat temp regulator | Present AYC heat temperature regulator setpoint. | °C | Read | |
| AI | 142 | AYC heat valve output | Present level of AYC heat valve output. | % | Read | |
| AV | 0 | SA Low speed airflow setpoint | Supply airflow setpoint for the unit when running in low speed operation. | l/s | Write | |
| AV | 1 | SA High speed airflow setpoint | Supply airflow setpoint for the unit when running in high speed operation. | l/s | Write | |
| AV | 2 | SA Max speed airflow setpoint | Supply airflow max. limit for the unit when the low/high speed operation | l/s | Write | |
| AV | 3 | SA Min speed airflow setpoint | Supply airflow min. limit for the unit when the low/high speed operation | l/s | Write | |
| AV | 4 | EA Low speed airflow setpoint | Extract airflow setpoint for the unit when running in low speed operation. | l/s | Write | |
| AV | 5 | EA High speed airflow setpoint | Extract airflow setpoint for the unit when running in high speed operation. | l/s | Write | |
| AV | 6 | EA Max speed airflow setpoint | Extract airflow max. limit for the unit when the low/high speed operation | l/s | Write | |
| AV | 7 | EA Min speed airflow setpoint | Extract airflow min. limit for the unit when the low/high speed operation | l/s | Write | |
| AV | 8 | SA Low speed pressure setpoint | Supply air duct pressure setpoint for the unit when running in low | Pa | Write | |
| AV | 9 | SA High speed pressure setpoint | Supply air duct pressure for the unit when running in high speed | Pa | Write | |
| AV | 10 | SA Max speed output signal | Max. limit for the supply air fan speed when running in pressure | % | Write | |
| AV | 11 | SA Max speed pressure setpoint | Supply air duct pressure max. limit for the unit when the low/high | Pa | Write | |
| AV | 12 | EA Low speed pressure setpoint | Extract air duct pressure setpoint for the unit when running in low | Pa | Write | |
| AV | 13 | EA High speed pressure setpoint | Extract air duct pressure setpoint for the unit when running in high | Pa | Write | |
| AV | 14 | EA Max speed output signal | Max. limit for the extract air fan speed when running in pressure | % | Write | |
| AV | 15 | EA Max speed pressure setpoint | Extract air duct pressure max. limit for the unit when the low/high | Pa | Write | |
| AV | 16 | SA Low speed demand setpoint | Supply air setpoint for the 0-10V input signal on terminal 35..37 for | % | Write | |
| AV | 17 | SA High speed demand setpoint | Supply air setpoint for the 0-10V input signal on terminal 35..37 for | % | Write | |
| AV | 18 | EA Low speed demand setpoint | Extract air setpoint for the 0-10V input signal on terminal 35..37 for | % | Write | |
| AV | 19 | EA High speed demand setpoint | Extract air setpoint for the 0-10V input signal on terminal 35..37 for | % | Write | |
| AV | 20 | SA Airflow regulation zone | Supply airflow regulation zone setting in % of the present airflow setpoint | Write | ||
| AV | 21 | SA Airflow C-factor | Supply airflow regulator affection setting. | Write | ||
| AV | 22 | EA Airflow regulation zone | Extract airflow regulation zone setting in % of the present airflow setpoint | Write | ||
| AV | 23 | EA Airflow C-factor | Extract airflow regulator affection setting. | Write | ||
| AV | 24 | SA Pressure regulation zone | Supply air pressure regulation zone setting in % of the present duct | Write | ||
| AV | 25 | SA Pressure C-factor | Supply air pressure regulator affection setting. | Write | ||
| AV | 26 | EA Pressure regulation zone | Extract air pressure regulation zone setting in % of the present duct | Write | ||
| AV | 27 | EA Pressure C-factor | Extract air pressure regulator affection setting. | Write | ||
| AV | 28 | SA Demand P-band. | Supply air demand regulator P-band setting. | Write | ||
| AV | 29 | SA Demand C-factor | Supply air demand regulator affection setting. | Write | ||
| AV | 30 | EA Demand P-band. | Extract air demand regulator P-band setting. | Write | ||
| AV | 31 | EA Demand C-factor | Extract air demand regulator affection setting. | Write | ||
| AV | 32 | ERS 1 Diff | Supply air temperature difference setting accordning to the diagram for ERS 1. | °C | Write | |
| AV | 33 | ERS 1 Breakpoint | Breakpoint setting accordning to the diagram for ERS 1. | °C | Write | |
| AV | 34 | ERS 2 Breakpoint X1 | Breakpoint X1 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 35 | ERS 2 Breakpoint Y1 | Breakpoint Y1 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 36 | ERS 2 Breakpoint X2 | Breakpoint X2 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 37 | ERS 2 Breakpoint Y2 | Breakpoint Y2 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 38 | ERS 2 Breakpoint X3 | Breakpoint X3 setting accordning to the diagram for ERS 2. | °C | Write | |
| AV | 39 | ERS 2 Breakpoint Y3 | Breakpoint Y3 setting accordning to the diagram for ERS 2. | °C | Write | |
| AVmin | 40 | SA Temperature setpoint | Supply air temperature setting, for supply air temp regulation mode. | °C | Write | |
| AVmin | 41 | EA/Room Temperature setpoint | Extract air/room temperature setting, for Extract air/room temp regulation mode. | °C | Write | |
| AV | 42 | SA Min temp setpoint | Supply air min.setpoint during EA/room regulation mode. | °C | Write | |
| AV | 43 | SA Max temp setpoint | Supply air max.setpoint during EA/room regulation mode. | °C | Write | |
| AV | 44 | SA Temperature P-band | Supply air temperature regulator P-band setting. | Write | ||
| AV | 45 | EA/Room Temperature P-band | Extract air/room temperature regulator P-band setting. | Write | ||
| AV | 46 | SA HX. Reg C-factor | Supply air heat exchange regulator affection setting. | Write | ||
| AV | 47 | EA/Room HX. Reg C-factor | Extract air/room heat exchange regulator affection setting. | Write | ||
| AV | 48 | SA Heat Reg C-factor | Supply air reheat regulator affection setting. | Write | ||
| AV | 49 | EA/Room Heat Reg C-factor | Extract air/room reheat regulator affection setting. | Write | ||
| AV | 50 | Reserve | Write | |||
| AV | 51 | Reserve | Write | |||
| AV | 52 | Reserve | Write | |||
| AV | 53 | Reserve | Write | |||
| AV | 54 | SA Down regulation Reg C-factor | Supply air reheat regulator affection setting. | Write | ||
| AV | 55 | Reserve | Write | |||
| AV | 56 | SA Cool reg C-factor | Supply air cool regulator affection setting. | Write | ||
| AV | 57 | EA/Room Cool reg C-factor | Extract air/room cool regulator affection setting. | Write | ||
| AV | 58 | SA Cooling boost C-factor | Supply air cooling boost affection setting. | Write | ||
| AV | 59 | EA/Room Cooling boost reg C-factor | Extract air/room cooling boost regulator affection setting. | Write | ||
| AV | 60 | HX Pressure alarm set. | Heat exchange pressure alarm limit setting (alarm no.38). | Pa | Write | |
| AV | 61 | Reserve | Write | |||
| AV | 62 | Reserve | Write | |||
| AV | 63 | Cooling off set. | Cooling off airflow setting in % of max. airflow. | % | Write | |
| AV | 64 | SA Down regulation neautral zone | Neutral zone setting before downregulation is permitted. | °C | Write | |
| AV | 65 | Cool Outdoor temp limit.1 | Outdoor temperature limit setting for cooling stage 1. | °C | Write | |
| AV | 66 | Cool Outdoor temp limit.2 | Outdoor temperature limit setting for cooling stage 2. | °C | Write | |
| AV | 67 | Cool Outdoor temp limit.3 | Outdoor temperature limit setting for cooling stage 3. | °C | Write | |
| AV | 68 | Temperature reg. Neutral zone | Neutral zone setting before shift between heating and cooling. | °C | Write | |
| AV | 69 | SA Cool min air flow | Supply air min. air flow setting for cooling. | l/s | Write | |
| AV | 70 | EA Cool min air flow | Extract air min. air flow setting for cooling. | l/s | Write | |
| AV | 71 | Heating boost start limit | Heating boost start temperature limit. | °C | Write | |
| AV | 72 | Cooling boost start limit | Cooling boost (comfort) start temperature limit. | °C | Write | |
| AV | 73 | SA Filter alarm limit | Supply air filter pressure alarm limit setting. | Pa | Write | |
| AV | 74 | EA Filter alarm limit | Extract air filter pressure alarm limit setting. | Pa | Write | |
| AV | 75 | Int. Night heat room start temp | Intermittent night heat function, extract air temperature setting for start. | °C | Write | |
| AV | 76 | Int. Night heat room stop temp | Intermittent night heat function, extract air temperature setting for stop. | °C | Write | |
| AV | 77 | Int. Night heat SA temp setpoint | Intermittent night heat function, supply air temperature setpoint during night heat. | °C | Write | |
| AV | 78 | Int. Night heat SA airflow setpoint | Intermittent night heat function, supply airflow setpoint during night heat. | l/s | Write | |
| AV | 79 | Int. Night heat EA airflow setpoint | Intermittent night heat function, extract airflow setpoint during night heat. | l/s | Write | |
| AV | 80 | Summer night cool EA start temp | Summer night cool function, extract air temperature setting for start. | °C | Write | |
| AV | 81 | Summer night cool EA stop temp | Summer night cool function, extract air temperature setting for stop. | °C | Write | |
| AV | 82 | Summer night cool outdoor temp limit | Summer night cool function, outdoor temperature limit. | °C | Write | |
| AV | 83 | Summer night cool SA temp setpoint | Summer night cool function, supply air temperature setpoint during summer night cool. | °C | Write | |
| AV | 84 | Outdoor temp comp. Winter X1. | Endpoint of winter compensation. | (-10.00)°C | Write | |
| AV | 85 | Outdoor temp comp. Winter X2. | Startpoint of winter compensation. | °C | Write | |
| AV | 86 | Outdoor temp comp. Winter Y1. | Level of winter compensation at X1. | °C | Write | |
| AV | 87 | Outdoor temp comp. Summer X3. | Startpoint of summer compensation. | °C | Write | |
| AV | 88 | Outdoor temp comp. Summer X4. | Endpoint of summer compensation. | °C | Write | |
| AV | 89 | Outdoor temp comp. Summer Y2. | Level of summer compensation at X4. | °C | Write | |
| AV | 90 | Outdoor airflow comp. Winter X1. | Endpoint of winter compensation. | (-10.00)°C | Write | |
| AV | 91 | Outdoor airflow comp. Winter X2. | Startpoint of winter compensation. | °C | Write | |
| AV | 92 | Outdoor airflow comp. Winter Y1. | Level of airflow compensation at X1. | % | Write | |
| AV | 93 | Reserve | Write | |||
| AV | 94 | EA/Room min temp alarm limit | Setting for min extract air /room temp alarm no.40. | °C | Write | |
| AV | 95 | SA Deviation alarm limit | Setting for supply air temperature below present setpoint, alarm no.41. | °C | Write | |
| AV | 96 | Reserve | Write | |||
| AV | 97 | SA Fan regulation mode | Setting of regulation type for the supply air fan. | Write | 0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by EA fan | |
| AV | 98 | EA Fan regulation mode | Setting of regulation type for the extract air fan. | Write | 0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by SA fan | |
| AV | 99 | ERS Step | Setting of curve when temperature is above breakpoint. | Write | ||
| AV | 100 | Temperature regulation mode. | Setting of temperature regulation type. | Write | 0=ERS 1 reg, 1=ERS 2 reg, 2=SA reg, 3=EA/Room reg | |
| AV | 101 | Cooling off periode | Time setting for cooling off electrical heating coil. | s | Write | |
| AV | 102 | Cool step time | Time setting between cool step shift. | s | Write | |
| AV | 103 | Cool restart time | Setting of time between two starts of the cool relays. | s | Write | |
| AV | 104 | Cool regulation mode | Setting of cool regulation type | Write | 0=Controlled 0-10V, 1=Controlled 10-0V, 2=On/Off 1-step, 3=On/Off 2-steps, 4=On/Off 3-steps binary | |
| AV | 105 | Heating boost regulation mode. | Setting for heating boost function. | Write | 0=Inactive, 1=Active | |
| AV | 106 | Cooling boost regulation mode. | Setting of cooling boost regulation type. | Write | 0=Inactive, 1=Comfort, 2=Economy, 3=Sequence, 4=Comfort+economy, 5=Economy+sequence | |
| AV | 107 | Filter calibration mode | Setting for required filter calibration. | Write | 0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter, 4=HX | |
| AV | 108 | Air adjustment time, minutes | Setting for amount of minutes to air adjustment function. | Write | ||
| AV | 109 | Air adjustment time, hours | Setting for amount of hours to air adjustment function. | Write | ||
| AV | 110 | Handterminal language | Write | 0=Svenska, 1=Norsk, 2=Dansk, 3=Suomi, 4=English, 5=Français, 6=Deutsch, 7=Polski, 8=Český, 9=Italiano, 10=Español, 11=Português, 12=Pycckий, 13=Eesti, 14=Latviesu, 15=Lietiviu, 16=Nederlands, 17=Magyar, 18=Türkçe | ||
| AV | 111 | Summer night cool start, hour | Setting for start time of summer night cooling function. | Write | ||
| AV | 112 | Summer night cool start, minute | Setting for start time of summer night cooling function. | Write | ||
| AV | 113 | Summer night cool stop, hour | Setting for stop time of summer night cooling function. | Write | ||
| AV | 114 | Summer night cool stop, minute | Setting for stop time of summer night cooling function. | Write | ||
| AV | 115 | Reserve | Write | |||
| AV | 116 | Reserve | Write | |||
| AV | 117 | Morning boost time, hours | Setting of morning boost time before normal operation. | Write | ||
| AV | 118 | Morning boost time, minutes | Setting of morning boost time before normal operation. | Write | ||
| AV | 119 | Startup time | Setting of time for startup when the unit regulator is running with | s | Write | |
| AV | 120 | Start delay SA fan. | Setting of start delay time for the supply air fan. | s | Write | |
| AV | 121 | Start delay EA fan. | Setting of start delay time for the extract air fan after supply | s | Write | |
| AV | 122 | Air flow unit | Setting of air flow unit presented in the unit's handterminal and WEB. | Write | 0=l/s, 1=m3/s, 2=m3/h | |
| AV | 123 | Reserve | Write | |||
| AV | 124 | Year | Setting for the unit's internal clock. | Write | ||
| AV | 125 | Month | Setting for the unit's internal clock. | Write | ||
| AV | 126 | Date | Setting for the unit's internal clock. | Write | ||
| AV | 127 | Hour | Setting for the unit's internal clock. | Write | ||
| AV | 128 | Minute | Setting for the unit's internal clock. | Write | ||
| AV | 129 | Second | Setting for the unit's internal clock. | Write | ||
| AV | 130 | Time channel 1 status | Low speed High speed | Write | 0=Inactive 16=Inactive, 1=Monday 17=Monday, 2=Tuesday 18=Tuesday, 3=Wednesday 19=Wednesday, 4=Thursday 20=Thursday, 5=Friday 21=Friday, 6=Saturday 22=Saturday, 7=Sunday 23=Sunday, 8=Monday..Friday 24=Monday..Friday, 9=Monday..Sunday 25=Monday..Sunday, 10=Saturday..Sunday 26=Saturday..Sunday | |
| AV | 131 | Time channel 1 start hour | Write | |||
| AV | 132 | Time channel 1 start minute | Write | |||
| AV | 133 | Time channel 1 stop hour | Write | |||
| AV | 134 | Time channel 1 stop minute | Write | |||
| AV | 135 | Time channel 2 status | Write | |||
| AV | 136 | Time channel 2 start hour | Write | |||
| AV | 137 | Time channel 2 start minute | Write | |||
| AV | 138 | Time channel 2 stop hour | Write | |||
| AV | 139 | Time channel 2 stop minute | Write | |||
| AV | 140 | Time channel 3 status | Write | |||
| AV | 141 | Time channel 3 start hour | Write | |||
| AV | 142 | Time channel 3 start minute | Write | |||
| AV | 143 | Time channel 3 stop hour | Write | |||
| AV | 144 | Time channel 3 stop minute | Write | |||
| AV | 145 | Time channel 4 status | Write | |||
| AV | 146 | Time channel 4 start hour | Write | |||
| AV | 147 | Time channel 4 start minute | Write | |||
| AV | 148 | Time channel 4 stop hour | Write | |||
| AV | 149 | Time channel 4 stop minute | Write | |||
| AV | 150 | Time channel 5 status | Write | |||
| AV | 151 | Time channel 5 start hour | Write | |||
| AV | 152 | Time channel 5 start minute | Write | |||
| AV | 153 | Time channel 5 stop hour | Write | |||
| AV | 154 | Time channel 5 stop minute | Write | |||
| AV | 155 | Time channel 6 status | Write | |||
| AV | 156 | Time channel 6 start hour | Write | |||
| AV | 157 | Time channel 6 start minute | Write | |||
| AV | 158 | Time channel 6 stop hour | Write | |||
| AV | 159 | Time channel 6 stop minute | Write | |||
| AV | 160 | Time channel 7 status | Write | |||
| AV | 161 | Time channel 7 start hour | Write | |||
| AV | 162 | Time channel 7 start minute | Write | |||
| AV | 163 | Time channel 7 stop hour | Write | |||
| AV | 164 | Time channel 7 stop minute | Write | |||
| AV | 165 | Time channel 8 status | Write | |||
| AV | 166 | Time channel 8 start hour | Write | |||
| AV | 167 | Time channel 8 start minute | Write | |||
| AV | 168 | Time channel 8 stop hour | Write | |||
| AV | 169 | Time channel 8 stop minute | Write | |||
| AV | 170 | Extended low speed op. Hours | Setting for extended low speed operation. | Write | ||
| AV | 171 | Extended low speed op. Minutes | Setting for extended low speed operation. | Write | ||
| AV | 172 | Extended high speed op. Hours | Setting for extended low speed operation. | Write | ||
| AV | 173 | Extended high speed op. Minutes | Setting for extended low speed operation. | Write | ||
| AVmin | 174 | Communication operation mode | Setting of unit operation mode from communication. Summer night cool, intermittent night | Write | 0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2 | |
| AV | 175 | Service periode alarm. | Setting for delay time in months before service alarm. | Write | ||
| AV | 176 | External alarm 1 delay | Setting of delay time for external alarm no 1 | s | Write | |
| AV | 177 | External alarm 2 delay | Setting of delay time for external alarm no 2 | s | Write | |
| AV | 178 | Int. Night heat SA pressure setpoint | Intermittent night heat function, supply pressure setpoint during night heat. | Pa | Write | |
| AV | 179 | Int. Night heat EA pressure setpoint | Intermittent night heat function, extract pressure setpoint during night heat. | Pa | Write | |
| AV | 180 | Copy of Coil Status 1-16 | Bit 0=1x0001 Bit 1=1x0002 Bit 15=1x0016 | Write | ||
| AV | 181 | Copy of Coil Statust 17-32 | Bit 0=1x00017 Bit 1=1x00018 Bit 15=1x0032 | Write | ||
| AV | 182 | Copy of Coil Status 33-48 | Bit 0=1x00033 Bit 1=1x00034 Bit 15=1x0048 | Write | ||
| AV | 183 | Heat relay periodic func. | Setting of periodic operation. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 184 | Cool relay 1 periodic func. | Setting of periodic operation. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 185 | Cool relay 2 periodic func. | Setting of periodic operation. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve (PV 2.02) | |
| AV | 186 | Slave control C-factor | Slave regulator affection setting. | Write | ||
| AV | 187 | SA dehumid P-band | SA dehumid regulator P-band setting. | Write | ||
| AV | 188 | SA dehumid C-factor | SA dehumid regulator affection setting. | Write | ||
| AV | 189 | Dewpoint reg. P-band | Dewpoint regulator P-band setting. | Write | ||
| AV | 190 | Dewpoint reg. C-factor | Dewpoint regulator affection setting. | Write | ||
| AV | 191 | AYC chilled water temperature | Setting of AYC chilled water temperature setpoint. | °C | Write | |
| AV | 192 | Dewpoint neutralzone | Dewpoint neutralzone setting. | °C | Write | |
| AV | 193 | Comp. airflow | Setting of comp. airflow. | % | Write | |
| AV | 194 | Supply air-humidity | Setting of supply air-humidity. | % | Write | |
| AV | 195 | Water heating periodic op. time | Setting of periodic op. time (minute). | min | Write | |
| AV | 196 | Water heating interval | Setting of water heating interval time (hour). | h | Write | |
| AV | 197 | Cool periodic op. time | Setting of periodic op. time (minute). | min | Write | |
| AV | 198 | Cool interval | Setting of cool interval time (hour). | h | Write | |
| AV | 199 | Reserve | Write | |||
| AV | 200 | EA/Room temperature (external) func. | Setting of EA/Room temperature (external) function. | Write | 0=Inactive, 1=IQnomic, 2=Communication (4x0202) | |
| AV | 201 | EA/Room temperature com. | Setting of EA/Room temperature via communication. | °C | Write | |
| AV | 202 | Outdoor temperature (external) func. | Setting of outdoor temperature (external) function. | Write | 0=Inactive, 1=IQnomic, 2=Communication (4x0204) | |
| AV | 203 | Outdoor temperature com. | Setting of outdoor temperature via communication. | °C | Write | |
| AV | 204 | Timeout temperature com. | Setting of timeout for temperature via communication (4x0202, 4x0204). | min | Write | |
| AV | 205 | Flow at fire function. | Setting for activating the air fan operation at fire function | Write | 0=Inactive, 1=SA, 2=EA, 3=SA+EA | |
| AV | 206 | Air fan down regulation func. | Setting for activating the air fan down regulation function | Write | 0=Inactive, 1=SA, 2=SA+EA | |
| AV | 207 | SA speed at fire. | Setting of supply air speed at fire. | % | Write | |
| AV | 208 | EA speed at fire. | Setting of extract air speed at fire. | % | Write | |
| AV | 209 | Reserve | Write | |||
| AV | 210 | Reserve | Write | |||
| AV | 211 | Supply air min P-band. | Supply air min regulator P-band setting. | Write | ||
| AV | 212 | Supply air min C-factor. | Supply air min regulator affection setting. | Write | ||
| AV | 213 | Supply air max P-band. | Supply air max regulator P-band setting. | Write | ||
| AV | 214 | Supply air max C-factor. | Supply air max regulator affection setting. | Write | ||
| AV | 215 | Year channel 1 function. | Write | 0=Inactive, 1=Stop, 2=Low speed, 3=High speed | ||
| AV | 216 | Year channel 1 start year. | Write | |||
| AV | 217 | Year channel 1 start month. | Write | |||
| AV | 218 | Year channel 1 start date. | Write | |||
| AV | 219 | Year channel 1 start hour. | Write | |||
| AV | 220 | Year channel 1 start minute. | Write | |||
| AV | 221 | Year channel 1 stop year. | Write | |||
| AV | 222 | Year channel 1 stop month. | Write | |||
| AV | 223 | Year channel 1 stop date. | Write | |||
| AV | 224 | Year channel 1 stop hour. | Write | |||
| AV | 225 | Year channel 1 stop minute. | Write | |||
| AV | 226 | Year channel 2 function. | Write | |||
| AV | 227 | Year channel 2 start year. | Write | |||
| AV | 228 | Year channel 2 start month. | Write | |||
| AV | 229 | Year channel 2 start date. | Write | |||
| AV | 230 | Year channel 2 start hour. | Write | |||
| AV | 231 | Year channel 2 start minute. | Write | |||
| AV | 232 | Year channel 2 stop year. | Write | |||
| AV | 233 | Year channel 2 stop month. | Write | |||
| AV | 234 | Year channel 2 stop date. | Write | |||
| AV | 235 | Year channel 2 stop hour. | Write | |||
| AV | 236 | Year channel 2 stop minute. | Write | |||
| AV | 237 | Year channel 3 function. | Write | |||
| AV | 238 | Year channel 3 start year. | Write | |||
| AV | 239 | Year channel 3 start month. | Write | |||
| AV | 240 | Year channel 3 start date. | Write | |||
| AV | 241 | Year channel 3 start hour. | Write | |||
| AV | 242 | Year channel 3 start minute. | Write | |||
| AV | 243 | Year channel 3 stop year. | Write | |||
| AV | 244 | Year channel 3 stop month. | Write | |||
| AV | 245 | Year channel 3 stop date. | Write | |||
| AV | 246 | Year channel 3 stop hour. | Write | |||
| AV | 247 | Year channel 3 stop minute. | Write | |||
| AV | 248 | Year channel 4 function. | Write | |||
| AV | 249 | Year channel 4 start year. | Write | |||
| AV | 250 | Year channel 4 start month. | Write | |||
| AV | 251 | Year channel 4 start date. | Write | |||
| AV | 252 | Year channel 4 start hour. | Write | |||
| AV | 253 | Year channel 4 start minute. | Write | |||
| AV | 254 | Year channel 4 stop year. | Write | |||
| AV | 255 | Year channel 4 stop month. | Write | |||
| AV | 256 | Year channel 4 stop date. | Write | |||
| AV | 257 | Year channel 4 stop hour. | Write | |||
| AV | 258 | Year channel 4 stop minute. | Write | |||
| AV | 259 | Year channel 5 function. | Write | |||
| AV | 260 | Year channel 5 start year. | Write | |||
| AV | 261 | Year channel 5 start month. | Write | |||
| AV | 262 | Year channel 5 start date. | Write | |||
| AV | 263 | Year channel 5 start hour. | Write | |||
| AV | 264 | Year channel 5 start minute. | Write | |||
| AV | 265 | Year channel 5 stop year. | Write | |||
| AV | 266 | Year channel 5 stop month. | Write | |||
| AV | 267 | Year channel 5 stop date. | Write | |||
| AV | 268 | Year channel 5 stop hour. | Write | |||
| AV | 269 | Year channel 5 stop minute. | Write | |||
| AV | 270 | Year channel 6 function. | Write | |||
| AV | 271 | Year channel 6 start year. | Write | |||
| AV | 272 | Year channel 6 start month. | Write | |||
| AV | 273 | Year channel 6 start date. | Write | |||
| AV | 274 | Year channel 6 start hour. | Write | |||
| AV | 275 | Year channel 6 start minute. | Write | |||
| AV | 276 | Year channel 6 stop year. | Write | |||
| AV | 277 | Year channel 6 stop month. | Write | |||
| AV | 278 | Year channel 6 stop date. | Write | |||
| AV | 279 | Year channel 6 stop hour. | Write | |||
| AV | 280 | Year channel 6 stop minute. | Write | |||
| AV | 281 | Year channel 7 function. | Write | |||
| AV | 282 | Year channel 7 start year. | Write | |||
| AV | 283 | Year channel 7 start month. | Write | |||
| AV | 284 | Year channel 7 start date. | Write | |||
| AV | 285 | Year channel 7 start hour. | Write | |||
| AV | 286 | Year channel 7 start minute. | Write | |||
| AV | 287 | Year channel 7 stop year. | Write | |||
| AV | 288 | Year channel 7 stop month. | Write | |||
| AV | 289 | Year channel 7 stop date. | Write | |||
| AV | 290 | Year channel 7 stop hour. | Write | |||
| AV | 291 | Year channel 7 stop minute. | Write | |||
| AV | 292 | Year channel 8 function. | Write | |||
| AV | 293 | Year channel 8 start year. | Write | |||
| AV | 294 | Year channel 8 start month. | Write | |||
| AV | 295 | Year channel 8 start date. | Write | |||
| AV | 296 | Year channel 8 start hour. | Write | |||
| AV | 297 | Year channel 8 start minute. | Write | |||
| AV | 298 | Year channel 8 stop year. | Write | |||
| AV | 299 | Year channel 8 stop month. | Write | |||
| AV | 300 | Year channel 8 stop date. | Write | |||
| AV | 301 | Year channel 8 stop hour. | Write | |||
| AV | 302 | Year channel 8 stop minute. | Write | |||
| AV | 303 | Filter select. | Setting for filter select function. | Write | 0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA | |
| AV | 304 | Prefilter select. | Setting for prefilter select function. | Write | 0=Inactive, 1=Supply air, 2=Extract air, 3=SA+EA | |
| AV | 305 | SA prefilter alarm limit. | Supply air prefilter pressure alarm limit setting. | Pa | Write | |
| AV | 306 | EA prefilter alarm limit. | Extract air prefilter pressure alarm limit setting. | Pa | Write | |
| AV | 307 | Prefilter calibration mode. | Setting for requiered filtercalibration. | Write | 0=Inactive, 1=SA+EA-Filter, 2=SA-Filter, 3=EA-Filter | |
| AV | 308 | Preheating function. | Setting of preheating function. | Write | 0=Inactive, 1=El. coil P/P, 2=El. coil 0-10V, 3=Water coil with FP, 4=Water coil without FP | |
| AV | 309 | Preheating setpoint. | Setting of preheating temperature setpoint. | °C | Write | |
| AV | 310 | Preheat P-band. | Preheat regulator P-band setting. | Write | ||
| AV | 311 | Preheat C-factor. | Preheat regulator affection setting. | Write | ||
| AV | 312 | SA Filter calculated alarm level | Supply air filter calculated alarm limit setting. | % | Write | |
| AV | 313 | EA Filter calculated alarm level | Extract air filter calculated alarm limit setting. | % | Write | |
| AV | 314 | Mode digital output relay 1 | Setting of mode output relay 1 function. | Write | 0=Damper, 1=Operation, 2=Low speed, 3=High speed, 4=Alarm A, 5=Alarm B, 6=Heating, 7=Cooling 1, 8=Cooling 2 | |
| AV | 315 | Mode digital output relay 2 | Setting of mode output relay 2 function. | Write | 0=Damper, 1=Operation, 2=Low speed, 3=High speed, 4=Alarm A, 5=Alarm B, 6=Heating, 7=Cooling 1, 8=Cooling 2 | |
| AV | 316 | Mode digital input 1 | Setting of mode input 1 function. | Write | 0=Stop, 1=Low speed, 2=High speed, 3=Alarm 1, 4=Alarm 2, 5=Reset, 6=Fire | |
| AV | 317 | Mode digital input 2 | Setting of mode input 2 function. | Write | 0=Stop, 1=Low speed, 2=High speed, 3=Alarm 1, 4=Alarm 2, 5=Reset, 6=Fire | |
| AV | 318 | Manual morning boost time hour | Setting of manual morning boost time before normal operation. | Write | ||
| AV | 319 | Manual morning boost time minutes | Setting of manual morning boost time before normal operation. | Write | ||
| AV | 320 | Airing temp set | Setting of airing temperature setpoint. | °C | Write | |
| AV | 321 | Airing time set | Setting of airing time in minutes. | Write | ||
| AV | 322 | Manual operation drift mode | Setting of manual operation drift mode. | Write | 0=Normal operation, 1=Extended operation, 2=Airing, 3=Heating, 4=Heating+Recirc | |
| AV | 323 | AYC function. | Setting of AYC function. | Write | 0=Inactive, 1=Cool, 2=Heat, 3=Cool+heat | |
| AV | 324 | AYC heat temp set. | Setting of AYC heated water temperature setpoint. | °C | Write | |
| AV | 325 | AYC night comp. channel. | Setting of AYC night compensation channel. | Write | 1=Channel 1, 2=Channel 2 | |
| AV | 326 | AYC channel start hour. | Setting of AYC channel start time (hour). | h | Write | |
| AV | 327 | AYC channel start minute. | Setting of AYC channel start time (minute). | min | Write | |
| AV | 328 | AYC channel stop hour. | Setting of AYC channel stop time (hour). | h | Write | |
| AV | 329 | AYC channel stop minute. | Setting of AYC channel stop time (minute). | min | Write | |
| AV | 330 | AYC channel period. | Setting of AYC channel period. | Write | 0=Inactive, 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday, 5=Friday, 6=Saturday, 7=Sunday, 8=Monday..Friday, 9=Monday..Sunday, 10=Saturday..Sunday | |
| AV | 331 | AYC heat P-band. | AYC heat regulator P-band setting. | Write | ||
| AV | 332 | AYC heat C-factor. | AYC heat regulator affection setting. | Write | ||
| AV | 333 | AYC cool P-band. | AYC cool regulator P-band setting. | Write | ||
| AV | 334 | AYC cool C-factor. | AYC cool regulator affection setting. | Write | ||
| AV | 335 | AYC heat out comp. X1. | AYC outdoor compensation of heated water, outdoor temp X1 setting. | °C | Write | |
| AV | 336 | AYC heat out comp. Y1. | AYC outdoor compensation of heated water, heated water temp Y1 setting. | °C | Write | |
| AV | 337 | AYC heat out comp. X2. | AYC outdoor compensation of heated water, outdoor temp X2 setting. | °C | Write | |
| AV | 338 | AYC heat out comp. Y2. | AYC outdoor compensation of heated water, heated water temp Y2 setting. | °C | Write | |
| AV | 339 | AYC heat out comp. X3. | AYC outdoor compensation of heated water, outdoor temp X3 setting. | °C | Write | |
| AV | 340 | AYC heat out comp. Y3. | AYC outdoor compensation of heated water, heated water temp Y3 setting. | °C | Write | |
| AV | 341 | AYC heat room comp. temp limit. | AYC room compensation of heated water, heated water temp limit setting. | °C | Write | |
| AV | 342 | AYC heat room comp P-band. | AYC room compensation of heated water, heated water P-band setting. | °C | Write | |
| AV | 343 | AYC heat night comp temp. | AYC night compensation of heated water, heated water night setting. | °C | Write | |
| AV | 344 | AYC heat pump on temp. | AYC pump operation of heated water, outdoor temp start setting. | °C | Write | |
| AV | 345 | AYC heat pump off temp. | AYC pump operation of heated water, outdoor temp stop setting. | °C | Write | |
| AV | 346 | AYC heat pump alarm. | Setting for selecting the AYC heated water pump alarm function. | Write | 0=Inactive, 1=Open, 2=Closed, 3=Contactor | |
| AV | 347 | AYC heat per op function. | Setting for selecting the AYC heated water periodic operation function. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve | |
| AV | 348 | AYC heat per op time. | AYC periodic operation of heated water, time (minute) setting. | min | Write | |
| AV | 349 | AYC heat per op interval. | AYC periodic operation of heated water, interval time (hour) setting. | h | Write | |
| AV | 350 | AYC cool out comp. X1. | AYC outdoor compensation of chilled water, outdoor temp X1 setting. | °C | Write | |
| AV | 351 | AYC cool out comp. Y1. | AYC outdoor compensation of chilled water, chilled water temp Y1 setting. | °C | Write | |
| AV | 352 | AYC cool out comp. X2. | AYC outdoor compensation of chilled water, outdoor temp X2 setting. | °C | Write | |
| AV | 353 | AYC cool out comp. Y2. | AYC outdoor compensation of chilled water, chilled water temp Y2 setting. | °C | Write | |
| AV | 354 | AYC cool out comp. X3. | AYC outdoor compensation of chilled water, outdoor temp X3 setting. | °C | Write | |
| AV | 355 | AYC cool out comp. Y3. | AYC outdoor compensation of chilled water, chilled water temp Y3 setting. | °C | Write | |
| AV | 356 | AYC cool room comp. temp limit. | AYC room compensation of chilled water, chilled water temp limit setting. | °C | Write | |
| AV | 357 | AYC cool room comp. P-band. | AYC room compensation of chilled water, chilled water P-band setting. | °C | Write | |
| AV | 358 | AYC cool night comp temp. | AYC night compensation of chilled water, chilled water night setting. | °C | Write | |
| AV | 359 | AYC cool pump on temp. | AYC pump operation of chilled water, outdoor temp start setting. | °C | Write | |
| AV | 360 | AYC cool pump off temp. | AYC pump operation of chilled water, outdoor temp stop setting. | °C | Write | |
| AV | 361 | AYC cool pump alarm. | Setting for selecting the AYC chilled water pump alarm function. | Write | 0=Inactive, 1=Open, 2=Closed, 3=Contactor | |
| AV | 362 | AYC cool per op function. | Setting for selecting the AYC chilled water periodic operation function. | Write | 0=Inactive, 1=Pump, 2=Pump+valve, 3=Valve | |
| AV | 363 | AYC cool per op time. | AYC periodic operation of chilled water, time (minute) setting. | min | Write | |
| AV | 364 | AYC cool per op interval. | AYC periodic operation of chilled water, interval time (hour) setting. | h | Write | |
| AV | 365 | IO-mod 3 output 1 function. | Setting of I/O-module no. 3 relay 1 output. | Write | 0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost | |
| AV | 366 | IO-mod 3 output 2 function. | Setting of I/O-module no. 3 relay 2 output. | Write | 0=Cooling boost, 1=Heating boost, 2=Cooling, 3=Heat exchange, 4=Reheat, 5=Down regulation, 6=Effect reduction, 7=Intermittent night heat, 8=Summer night cooling, 9=Morning boost, 10=Heat exchange defrost | |
| BI | 0 | Heat output | Status for relay output. | Read | ||
| BI | 1 | Cool output 1 | Status for relay output. | Read | ||
| BI | 2 | Cool output 2 | Status for relay output. | Read | ||
| BI | 3 | Low speed output | Status for relay output. | Read | ||
| BI | 4 | High speed output | Status for relay output. | Read | ||
| BImin | 5 | A-alarm. | Status for relay output. | Read | ||
| BImin | 6 | B-alarm. | Status for relay output. | Read | ||
| BI | 7 | Operation output | Status for relay output. | Read | ||
| BI | 8 | Damper output | Status for relay output. | Read | ||
| BI | 9 | External low speed input | Status for digital input. | Read | ||
| BI | 10 | External high speed input | Status for digital input. | Read | ||
| BI | 11 | External alarm 1 input | Status for digital input. | Read | ||
| BI | 12 | External alarm 2 input | Status for digital input. | Read | ||
| BI | 13 | External fire alarm input. | Status for digital input. | Read | ||
| BI | 14 | External stop input | Status for digital input. | Read | ||
| BI | 15 | DIP Switch 1 | Status for dip switch setting. | Read | ||
| BI | 16 | DIP Switch 2 | Status for dip switch setting. | Read | ||
| BI | 17 | DIP Switch 3 | Status for dip switch setting. | Read | ||
| BI | 18 | DIP Switch 4 | Status for dip switch setting. | Read | ||
| BI | 19 | DIP Switch 5 | Status for dip switch setting. | Read | ||
| BI | 20 | DIP Switch 6 | Status for dip switch setting. | Read | ||
| BI | 21 | AYC heat pump output | Status for AYC heat pump output. | Read | ||
| BI | 22 | AYC cool pump output | Status for AYC cool pump output. | Read | ||
| BI | 23 | Reserve 9 | Read | |||
| BI | 24 | R.HX rotation monitor | Status from the rotation detector. | Read | ||
| BI | 25 | Reserve 10 | Read | |||
| BI | 26 | Reserve 11 | Read | |||
| BI | 27 | Reserve 12 | Read | |||
| BI | 28 | Pre-heat output | Status for relay output. | Read | ||
| BI | 29 | Recirculation output | Status for I/O-module no. 3 relay 1 output. | Read | ||
| BI | 30 | Booster output | Status for I/O-module no. 3 relay 2 output. | Read | ||
| BI | 31 | IO-mod 3 output 1 | Status for I/O-module no. 3 relay 1 output. | Read | ||
| BI | 32 | IO-mod 3 output 2 | Status for I/O-module no. 3 relay 2 output. | Read | ||
| BI | 33 | Reserve 13 | Read | |||
| BI | 34 | Reserve 14 | Read | |||
| BI | 35 | Reserve 15 | Read | |||
| BI | 36 | Reserve 16 | Read | |||
| BI | 37 | Reserve 17 | Read | |||
| BI | 38 | Reserve 18 | Read | |||
| BI | 39 | Reserve 19 | Read | |||
| BI | 40 | Reserve 20 | Read | |||
| BI | 41 | Reserve 21 | Read | |||
| BI | 42 | Reserve 22 | Read | |||
| BI | 43 | Reserve 23 | Read | |||
| BI | 44 | Reserve 24 | Read | |||
| BI | 45 | Reserve 25 | Read | |||
| BI | 46 | Reserve 26 | Read | |||
| BI | 47 | Reserve 27 | Read | |||
| BI | 48 | Alarm number 1 | Status if alarm number 1 is active. | Read | ||
| BI | 49 | Alarm number 2 | Status if alarm number 2 is active. | Read | ||
| BI | 50 | Alarm number 3 | Status if alarm number 3 is active. | Read | ||
| BI | 247 | Alarm number 200 | Status if alarm number 200 is active. | Read | ||
| BI | 248 | Info number 1 | Status if info number 1 is active. | Read | ||
| BI | 249 | Info number 2 | Status if info number 2 is active. | Read | ||
| BI | 250 | Info number 3 | Status if info number 3 is active. | Read | ||
| BI | 347 | Info number 100 | Status if info number 100 is active. | Read | ||
| BVmin | 0 | Alarm reset | Resets tripped alarms. | Write | ||
| BV | 1 | R.HX. Defrost func. | Setting for activating the defrost function for the rotary heat exchanger. | Write | ||
| BV | 2 | Cool operation mode | Setting for cooling between off and auto operation. | Write | ||
| BV | 3 | Int. Night heat func. | Setting for activating the intermittent night heat function. | Write | ||
| BV | 4 | Damper func. | Setting for activating the damper output relay during int. night heat. | Write | ||
| BV | 5 | Summer night cooling | Setting for activating the suumer night cool function. | Write | ||
| BV | 6 | Outdoor temp compensation | Setting for activating the outdoor temperature compensation function. | Write | ||
| BV | 7 | Outdoor airflow compensation | Setting for activating the outdoor airflow compensation function. | Write | ||
| BV | 8 | Auto. Summer/winter switch | Setting for activating the automatic switch between summer/winter time function. | Write | ||
| BV | 9 | Switch clock func. | Setting for switch clock function type. | Write | 0=Stop - low speed - high speed, 1=Low speed - high speed | |
| BV | 10 | Internal fire alarm func. | Setting for activating the internal fire alarm function. | Write | ||
| BV | 11 | External alarm 1 active at closure | Setting for external alarm number 1 condition to be activated. | Write | 0=Alarm at closed input, 1=Alarm at open input | |
| BV | 12 | External alarm 2 active at closure | Setting for external alarm number 2 condition to be activated. | Write | 0=Alarm at closed input, 1=Alarm at open input | |
| BV | 13 | Dewpoint reg. func. | Setting for activating the dewpoint regulator funktion. | Write | ||
| BV | 14 | Dehumid reg. func. | Setting for activating the dehumid regulator funktion. | Write | ||
| BV | 15 | External fire alarm func. | Setting for external fire resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 16 | External alarm 1 func. | Setting for external alarm 1 resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 17 | External alarm 2 func. | Setting for external alarm 2 resetting function. | Write | 0=Manual, 1=Automatic | |
| BV | 18 | Int. Night heat output func. | Setting for selecting the intermittent night heat output function. | Write | 0=IQnomic, 1=IQnomic+ | |
| BV | 19 | Morningboost damper func. | Setting for activating the morningboost damper function. | Write | 0=Inactive, 1=Active | |
| BV | 20 | Morningboost extract func. | Setting for activating the morningboost extract air fan function. | Write | 0=Inactive, 1=Active | |
| BV | 21 | Filter func. | Setting for filter between calculated and pressure sensors. | Write | 0=Calculated, 1=Pressure sensors | |
| BV | 22 | Iqnomic Plus module no.6 Cooling | Setting for activating Iqnomiq Plus no.6 Cooling module. | Write | 0=Inactive, 1=Active | |
| BV | 23 | Airing auto func. | Setting for activating the airing auto function. | Write | 0=Inactive, 1=Active | |
| BV | 24 | AYC heat out comp. func. | Setting for selecting the AYC outdoor comp. heated water function. | Write | 0=Inactive, 1=Active | |
| BV | 25 | AYC heat room comp. func. | Setting for selecting the AYC room comp. heated water function. | Write | 0=Inactive, 1=Active | |
| BV | 26 | AYC heat room comp. night block func. | Setting for selecting the AYC room comp. heated water night block function. | Write | 0=Inactive, 1=Active | |
| BV | 27 | AYC heat night comp. func. | Setting for selecting the AYC night comp. heated water function. | Write | 0=Inactive, 1=Active | |
| BV | 28 | AYC heat valve signal func. | Setting for selecting the AYC valve signal heated water alarm function. | Write | 0=Inactive, 1=Active | |
| BV | 29 | AYC cool out comp. func. | Setting for selecting the AYC outdoor comp. chilled water function. | Write | 0=Inactive, 1=Active | |
| BV | 30 | AYC cool room comp. func. | Setting for selecting the AYC room comp. chilled water function. | Write | 0=Inactive, 1=Active | |
| BV | 31 | AYC cool room comp. night block func. | Setting for selecting the AYC room comp. chilled water night block function. | Write | 0=Inactive, 1=Active | |
| BV | 32 | AYC cool night comp. func. | Setting for selecting the AYC night comp. chilled water function. | Write | 0=Inactive, 1=Active | |
| BV | 33 | AYC cool valve signal func. | Setting for selecting the AYC valve signal chilled water alarm function. | Write | 0=Inactive, 1=Active |
No points match these filters.
Object ID lookup: Swegon Compact / GOLD LP point IDs by name
AI0SA AirflowAI1SA Airflow regulatorAI2EA AirflowAI3EA Airflow regulatorAI4SA Duct pressureAI5SA Duct pressure regulatorAI6EA Duct pressureAI7EA Duct pressure regulatorAI8ReserveAI9SA VAV demand regulatorAI10ReserveAI11EA VAV demand regulatorAI12SA Fan levelAI13EA Fan levelAI14SA Fan effectAI15EA Fan effectAI16SFPAI17ReserveAI18ReserveAI19SA VoltageAI20EA VoltageAI21SA CurrentAI22EA CurrentAI23SA Airflow pressureAI24EA Airflow pressureAI25SA Temp regulatorAI26EA Temp regulatorAI27SA TemperatureAI28EA/Room temperatureAI29Outdoor temperaturAI30EA/Room temperature (external)AI31Outdoor temperatur (external)AI32Anti frost temperatureAI33ReserveAI34ReserveAI35Rotary heat exchanger levelAI36Reheat levelAI37SA Down regulation levelAI38ReserveAI39Cooling levelAI40Heating boost levelAI41Cooling boost levelAI42HX pressure levelAI43HX pressure alarm limitAI44HX temperatureAI45Effect reduction levelAI46Anti frost temp setpoint/operationAI47Anti frost temp setpoint/stopAI48Anti frost temp alarm limitAI49Supply air filter pressure levelAI50Supply air filter pressure alarm limit.AI51Supply air filter pressure level, newAI52Extract air filter pressure levelAI53Extract air filter pressure alarm limit.AI54Extract air filter pressure level, newAI55ReserveAI56Coil typeAI57Cool step timeAI58Cool relay 1 restart timeAI59Cool relay 2 restart timeAI60Programversion, HMIAI61Programversion, HMI-slaveAI62Programversion, main controller.AI63Programversion, SA FC-1.AI64Programversion, SA FC-2.AI65Programversion, EA FC-1.AI66Programversion, EA FC-2.AI67Programversion, HX control unitAI68WeekdayAI69Extended low speed op. HoursAI70Extended low speed op. MinutesAI71Extended high speed op. HoursAI72Extended high speed op. MinutesAI73SA Fan operation timeAI74EA Fan operation timeAI75Cool operation timeAI76Heat exchange operation timeAI77Reheat operation timeAI78Present tripped alarmAI79Active not tripped alarm no.1AI80Active not tripped alarm no.2AI81Active not tripped alarm no.3AI82SA Fan sizeAI83EA Fan sizeAI84Operation mode 1AI85Operation mode 2AI86Operation mode, manualAI87Copy of Input Status 1-16.AI88Copy of Input Status 17-32.AI89Copy of Input Status 33-48.AI90Heat exchanger regulatorAI91Extract air-humidityAI92Extract air-humidity temperatureAI93Extract air-dewpointAI94AYC chilled water temperatureAI95AYC chilled water temperature regulatorAI96AYC chilled water outputAI97Supply air-dewpoint regulatorAI98Supply air-humidityAI99Supply air-humidity temperatureAI100Supply air-dewpointAI101ReserveAI102ReserveAI103ReserveAI104ReserveAI105R.HX. EfficiencyAI106ReserveAI107ReserveAI108Supply air prefilter pressure levelAI109Supply air prefilter pressure alarm limit.AI110Supply air prefilter pressure level, newAI111Extract air prefilter pressure levelAI112Extract air prefilter pressure alarm limit.AI113Extract air prefilter pressure level, newAI114ReserveAI115ReserveAI116ReserveAI117ReserveAI118ReserveAI119ReserveAI120ReserveAI121ReserveAI122ReserveAI123ReserveAI124Pre-heating air temperatureAI125Pre-heating levelAI126Pre-heating anti frost temperatureAI127ReserveAI128ReserveAI129ReserveAI130ReserveAI131ReserveAI132ReserveAI133Preheat operation timeAI134ReserveAI135ReserveAI136Demand VOC LevelAI137Demand Vin LevelAI138SA Filter level calculatedAI139EA Filter level calculatedAI140AYC heat temperatureAI141AYC heat temp regulatorAI142AYC heat valve outputAV0SA Low speed airflow setpointAV1SA High speed airflow setpointAV2SA Max speed airflow setpointAV3SA Min speed airflow setpointAV4EA Low speed airflow setpointAV5EA High speed airflow setpointAV6EA Max speed airflow setpointAV7EA Min speed airflow setpointAV8SA Low speed pressure setpointAV9SA High speed pressure setpointAV10SA Max speed output signalAV11SA Max speed pressure setpointAV12EA Low speed pressure setpointAV13EA High speed pressure setpointAV14EA Max speed output signalAV15EA Max speed pressure setpointAV16SA Low speed demand setpointAV17SA High speed demand setpointAV18EA Low speed demand setpointAV19EA High speed demand setpointAV20SA Airflow regulation zoneAV21SA Airflow C-factorAV22EA Airflow regulation zoneAV23EA Airflow C-factorAV24SA Pressure regulation zoneAV25SA Pressure C-factorAV26EA Pressure regulation zoneAV27EA Pressure C-factorAV28SA Demand P-band.AV29SA Demand C-factorAV30EA Demand P-band.AV31EA Demand C-factorAV32ERS 1 DiffAV33ERS 1 BreakpointAV34ERS 2 Breakpoint X1AV35ERS 2 Breakpoint Y1AV36ERS 2 Breakpoint X2AV37ERS 2 Breakpoint Y2AV38ERS 2 Breakpoint X3AV39ERS 2 Breakpoint Y3AV40SA Temperature setpointAV41EA/Room Temperature setpointAV42SA Min temp setpointAV43SA Max temp setpointAV44SA Temperature P-bandAV45EA/Room Temperature P-bandAV46SA HX. Reg C-factorAV47EA/Room HX. Reg C-factorAV48SA Heat Reg C-factorAV49EA/Room Heat Reg C-factorAV50ReserveAV51ReserveAV52ReserveAV53ReserveAV54SA Down regulation Reg C-factorAV55ReserveAV56SA Cool reg C-factorAV57EA/Room Cool reg C-factorAV58SA Cooling boost C-factorAV59EA/Room Cooling boost reg C-factorAV60HX Pressure alarm set.AV61ReserveAV62ReserveAV63Cooling off set.AV64SA Down regulation neautral zoneAV65Cool Outdoor temp limit.1AV66Cool Outdoor temp limit.2AV67Cool Outdoor temp limit.3AV68Temperature reg. Neutral zoneAV69SA Cool min air flowAV70EA Cool min air flowAV71Heating boost start limitAV72Cooling boost start limitAV73SA Filter alarm limitAV74EA Filter alarm limitAV75Int. Night heat room start tempAV76Int. Night heat room stop tempAV77Int. Night heat SA temp setpointAV78Int. Night heat SA airflow setpointAV79Int. Night heat EA airflow setpointAV80Summer night cool EA start tempAV81Summer night cool EA stop tempAV82Summer night cool outdoor temp limitAV83Summer night cool SA temp setpointAV84Outdoor temp comp. Winter X1.AV85Outdoor temp comp. Winter X2.AV86Outdoor temp comp. Winter Y1.AV87Outdoor temp comp. Summer X3.AV88Outdoor temp comp. Summer X4.AV89Outdoor temp comp. Summer Y2.AV90Outdoor airflow comp. Winter X1.AV91Outdoor airflow comp. Winter X2.AV92Outdoor airflow comp. Winter Y1.AV93ReserveAV94EA/Room min temp alarm limitAV95SA Deviation alarm limitAV96ReserveAV97SA Fan regulation modeAV98EA Fan regulation modeAV99ERS StepAV100Temperature regulation mode.AV101Cooling off periodeAV102Cool step timeAV103Cool restart timeAV104Cool regulation modeAV105Heating boost regulation mode.AV106Cooling boost regulation mode.AV107Filter calibration modeAV108Air adjustment time, minutesAV109Air adjustment time, hoursAV110Handterminal languageAV111Summer night cool start, hourAV112Summer night cool start, minuteAV113Summer night cool stop, hourAV114Summer night cool stop, minuteAV115ReserveAV116ReserveAV117Morning boost time, hoursAV118Morning boost time, minutesAV119Startup timeAV120Start delay SA fan.AV121Start delay EA fan.AV122Air flow unitAV123ReserveAV124YearAV125MonthAV126DateAV127HourAV128MinuteAV129SecondAV130Time channel 1 statusAV131Time channel 1 start hourAV132Time channel 1 start minuteAV133Time channel 1 stop hourAV134Time channel 1 stop minuteAV135Time channel 2 statusAV136Time channel 2 start hourAV137Time channel 2 start minuteAV138Time channel 2 stop hourAV139Time channel 2 stop minuteAV140Time channel 3 statusAV141Time channel 3 start hourAV142Time channel 3 start minuteAV143Time channel 3 stop hourAV144Time channel 3 stop minuteAV145Time channel 4 statusAV146Time channel 4 start hourAV147Time channel 4 start minuteAV148Time channel 4 stop hourAV149Time channel 4 stop minuteAV150Time channel 5 statusAV151Time channel 5 start hourAV152Time channel 5 start minuteAV153Time channel 5 stop hourAV154Time channel 5 stop minuteAV155Time channel 6 statusAV156Time channel 6 start hourAV157Time channel 6 start minuteAV158Time channel 6 stop hourAV159Time channel 6 stop minuteAV160Time channel 7 statusAV161Time channel 7 start hourAV162Time channel 7 start minuteAV163Time channel 7 stop hourAV164Time channel 7 stop minuteAV165Time channel 8 statusAV166Time channel 8 start hourAV167Time channel 8 start minuteAV168Time channel 8 stop hourAV169Time channel 8 stop minuteAV170Extended low speed op. HoursAV171Extended low speed op. MinutesAV172Extended high speed op. HoursAV173Extended high speed op. MinutesAV174Communication operation modeAV175Service periode alarm.AV176External alarm 1 delayAV177External alarm 2 delayAV178Int. Night heat SA pressure setpointAV179Int. Night heat EA pressure setpointAV180Copy of Coil Status 1-16AV181Copy of Coil Statust 17-32AV182Copy of Coil Status 33-48AV183Heat relay periodic func.AV184Cool relay 1 periodic func.AV185Cool relay 2 periodic func.AV186Slave control C-factorAV187SA dehumid P-bandAV188SA dehumid C-factorAV189Dewpoint reg. P-bandAV190Dewpoint reg. C-factorAV191AYC chilled water temperatureAV192Dewpoint neutralzoneAV193Comp. airflowAV194Supply air-humidityAV195Water heating periodic op. timeAV196Water heating intervalAV197Cool periodic op. timeAV198Cool intervalAV199ReserveAV200EA/Room temperature (external) func.AV201EA/Room temperature com.AV202Outdoor temperature (external) func.AV203Outdoor temperature com.AV204Timeout temperature com.AV205Flow at fire function.AV206Air fan down regulation func.AV207SA speed at fire.AV208EA speed at fire.AV209ReserveAV210ReserveAV211Supply air min P-band.AV212Supply air min C-factor.AV213Supply air max P-band.AV214Supply air max C-factor.AV215Year channel 1 function.AV216Year channel 1 start year.AV217Year channel 1 start month.AV218Year channel 1 start date.AV219Year channel 1 start hour.AV220Year channel 1 start minute.AV221Year channel 1 stop year.AV222Year channel 1 stop month.AV223Year channel 1 stop date.AV224Year channel 1 stop hour.AV225Year channel 1 stop minute.AV226Year channel 2 function.AV227Year channel 2 start year.AV228Year channel 2 start month.AV229Year channel 2 start date.AV230Year channel 2 start hour.AV231Year channel 2 start minute.AV232Year channel 2 stop year.AV233Year channel 2 stop month.AV234Year channel 2 stop date.AV235Year channel 2 stop hour.AV236Year channel 2 stop minute.AV237Year channel 3 function.AV238Year channel 3 start year.AV239Year channel 3 start month.AV240Year channel 3 start date.AV241Year channel 3 start hour.AV242Year channel 3 start minute.AV243Year channel 3 stop year.AV244Year channel 3 stop month.AV245Year channel 3 stop date.AV246Year channel 3 stop hour.AV247Year channel 3 stop minute.AV248Year channel 4 function.AV249Year channel 4 start year.AV250Year channel 4 start month.AV251Year channel 4 start date.AV252Year channel 4 start hour.AV253Year channel 4 start minute.AV254Year channel 4 stop year.AV255Year channel 4 stop month.AV256Year channel 4 stop date.AV257Year channel 4 stop hour.AV258Year channel 4 stop minute.AV259Year channel 5 function.AV260Year channel 5 start year.AV261Year channel 5 start month.AV262Year channel 5 start date.AV263Year channel 5 start hour.AV264Year channel 5 start minute.AV265Year channel 5 stop year.AV266Year channel 5 stop month.AV267Year channel 5 stop date.AV268Year channel 5 stop hour.AV269Year channel 5 stop minute.AV270Year channel 6 function.AV271Year channel 6 start year.AV272Year channel 6 start month.AV273Year channel 6 start date.AV274Year channel 6 start hour.AV275Year channel 6 start minute.AV276Year channel 6 stop year.AV277Year channel 6 stop month.AV278Year channel 6 stop date.AV279Year channel 6 stop hour.AV280Year channel 6 stop minute.AV281Year channel 7 function.AV282Year channel 7 start year.AV283Year channel 7 start month.AV284Year channel 7 start date.AV285Year channel 7 start hour.AV286Year channel 7 start minute.AV287Year channel 7 stop year.AV288Year channel 7 stop month.AV289Year channel 7 stop date.AV290Year channel 7 stop hour.AV291Year channel 7 stop minute.AV292Year channel 8 function.AV293Year channel 8 start year.AV294Year channel 8 start month.AV295Year channel 8 start date.AV296Year channel 8 start hour.AV297Year channel 8 start minute.AV298Year channel 8 stop year.AV299Year channel 8 stop month.AV300Year channel 8 stop date.AV301Year channel 8 stop hour.AV302Year channel 8 stop minute.AV303Filter select.AV304Prefilter select.AV305SA prefilter alarm limit.AV306EA prefilter alarm limit.AV307Prefilter calibration mode.AV308Preheating function.AV309Preheating setpoint.AV310Preheat P-band.AV311Preheat C-factor.AV312SA Filter calculated alarm levelAV313EA Filter calculated alarm levelAV314Mode digital output relay 1AV315Mode digital output relay 2AV316Mode digital input 1AV317Mode digital input 2AV318Manual morning boost time hourAV319Manual morning boost time minutesAV320Airing temp setAV321Airing time setAV322Manual operation drift modeAV323AYC function.AV324AYC heat temp set.AV325AYC night comp. channel.AV326AYC channel start hour.AV327AYC channel start minute.AV328AYC channel stop hour.AV329AYC channel stop minute.AV330AYC channel period.AV331AYC heat P-band.AV332AYC heat C-factor.AV333AYC cool P-band.AV334AYC cool C-factor.AV335AYC heat out comp. X1.AV336AYC heat out comp. Y1.AV337AYC heat out comp. X2.AV338AYC heat out comp. Y2.AV339AYC heat out comp. X3.AV340AYC heat out comp. Y3.AV341AYC heat room comp. temp limit.AV342AYC heat room comp P-band.AV343AYC heat night comp temp.AV344AYC heat pump on temp.AV345AYC heat pump off temp.AV346AYC heat pump alarm.AV347AYC heat per op function.AV348AYC heat per op time.AV349AYC heat per op interval.AV350AYC cool out comp. X1.AV351AYC cool out comp. Y1.AV352AYC cool out comp. X2.AV353AYC cool out comp. Y2.AV354AYC cool out comp. X3.AV355AYC cool out comp. Y3.AV356AYC cool room comp. temp limit.AV357AYC cool room comp. P-band.AV358AYC cool night comp temp.AV359AYC cool pump on temp.AV360AYC cool pump off temp.AV361AYC cool pump alarm.AV362AYC cool per op function.AV363AYC cool per op time.AV364AYC cool per op interval.AV365IO-mod 3 output 1 function.AV366IO-mod 3 output 2 function.BI0Heat outputBI1Cool output 1BI2Cool output 2BI3Low speed outputBI4High speed outputBI5A-alarm.BI6B-alarm.BI7Operation outputBI8Damper outputBI9External low speed inputBI10External high speed inputBI11External alarm 1 inputBI12External alarm 2 inputBI13External fire alarm input.BI14External stop inputBI15DIP Switch 1BI16DIP Switch 2BI17DIP Switch 3BI18DIP Switch 4BI19DIP Switch 5BI20DIP Switch 6BI21AYC heat pump outputBI22AYC cool pump outputBI23Reserve 9BI24R.HX rotation monitorBI25Reserve 10BI26Reserve 11BI27Reserve 12BI28Pre-heat outputBI29Recirculation outputBI30Booster outputBI31IO-mod 3 output 1BI32IO-mod 3 output 2BI33Reserve 13BI34Reserve 14BI35Reserve 15BI36Reserve 16BI37Reserve 17BI38Reserve 18BI39Reserve 19BI40Reserve 20BI41Reserve 21BI42Reserve 22BI43Reserve 23BI44Reserve 24BI45Reserve 25BI46Reserve 26BI47Reserve 27BI48Alarm number 1BI49Alarm number 2BI50Alarm number 3BI247Alarm number 200BI248Info number 1BI249Info number 2BI250Info number 3BI347Info number 100BV0Alarm resetBV1R.HX. Defrost func.BV2Cool operation modeBV3Int. Night heat func.BV4Damper func.BV5Summer night coolingBV6Outdoor temp compensationBV7Outdoor airflow compensationBV8Auto. Summer/winter switchBV9Switch clock func.BV10Internal fire alarm func.BV11External alarm 1 active at closureBV12External alarm 2 active at closureBV13Dewpoint reg. func.BV14Dehumid reg. func.BV15External fire alarm func.BV16External alarm 1 func.BV17External alarm 2 func.BV18Int. Night heat output func.BV19Morningboost damper func.BV20Morningboost extract func.BV21Filter func.BV22Iqnomic Plus module no.6 CoolingBV23Airing auto func.BV24AYC heat out comp. func.BV25AYC heat room comp. func.BV26AYC heat room comp. night block func.BV27AYC heat night comp. func.BV28AYC heat valve signal func.BV29AYC cool out comp. func.BV30AYC cool room comp. func.BV31AYC cool room comp. night block func.BV32AYC cool night comp. func.BV33AYC cool valve signal func.
Integration notes
- Only AI, AV, BI and BV objects are used; modes and selections are AVs with numbered states.
- Instances are not contiguous and 'Reserve' objects carry no data.
- Units are taken from the Min/Max column (l/s, Pa, °C, %, s, min); unitless ranges are left blank.
- Operating state is reported as codes in AI-84 Operation mode 1 and AI-85 Operation mode 2.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Compact / GOLD LP BACnet IP (PV 2.01+) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)
How many BACnet points does the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) have?
This list has 600 BACnet objects: 143 analog inputs, 367 analog values, 56 binary inputs, 34 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet points are writable?
401 of the 600 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Swegon Compact / GOLD LP BACnet IP (PV 2.01+) BACnet documentation?
The source is BACnet IP Compact/GOLD LP, program version 2.01 and newer versions (GB.BACnet480.100129), revision 2010-01-29, published free by Swegon at https://www.swegon.com/globalassets/digizuite/11562-en-compactair_bacnet480_other_en.pdf.
What are the minimum BACnet points to integrate the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?
Start with AV 174 Communication operation mode (BMS stop / low / high / auto command); AV 40 SA Temperature setpoint (Supply air temperature setpoint); AV 41 EA/Room Temperature setpoint (Extract/room temperature setpoint); BV 0 Alarm reset (Resets tripped alarms); AI 84 Operation mode 1 (Current operating reason (stop, speed, channel)); AI 27 SA Temperature (Supply air temperature); AI 28 EA/Room temperature (Extract/room temperature); AI 29 Outdoor temperatur (Outdoor air temp measured by the unit, °C); BI 5 A-alarm. (A-class alarm active); BI 6 B-alarm. (B-class alarm active).
How do I enable BMS control of the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?
AV-174 Communication operation mode: 0=Auto operation, 1=Communication stop 1, 2=Communication low speed, 3=Communication high speed, 4=Communication stop 2. Summer night cool, intermittent night heat and morning boost still run at stop 2.
Does the Swegon Compact / GOLD LP BACnet IP (PV 2.01+) need a BACnet heartbeat or have a communication timeout?
Only for BMS-supplied temperatures: AV-204 'Timeout temperature com.' (0-9999 min) sets the timeout for room and outdoor temperatures written over communication. The document does not describe a timeout for the operation mode command.
Can the BMS supply sensor values to the Swegon Compact / GOLD LP BACnet IP (PV 2.01+)?
Set AV-200 EA/Room temperature (external) func. to 2 (Communication) and write AV-201; set AV-202 Outdoor temperature (external) func. to 2 and write AV-203. AV-204 is the timeout for those written values.
How do I check these points on the real Compact / GOLD LP BACnet IP (PV 2.01+)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Swegon BACnet points lists
- Air handling unit controller
Swegon GOLD generation C/D (RX/PX/CX/SD) BACnet IP
Swegon GOLD air handling units of generation C and D (RX, PX, CX and SD versions, built about 2010-2013) running program version 6.08 or later.
Also known as: GOLD C, GOLD D, GOLD RX, GOLD PX, GOLD CX, GOLD SD, GOLD version D, GB.BACnet480.121017, BACnet480 - Air handling unit controller
Swegon GOLD generation E (RX/PX/CX/SD) BACnet IP
Swegon GOLD air handling units of generation E (RX, PX, CX and SD versions) running program version 1.10 or later.
Also known as: GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_BACnet_150316 - Air handling unit controller
Swegon GOLD generation E/F (RX/PX/CX/SD) BACnet IP, PV 2.48
Swegon GOLD air handling units of generations E and F (RX, PX, CX and SD versions) with program version 2.48.
Also known as: GOLD F, GOLD version F, GOLD E, GOLD RX, GOLD PX, GOLD CX, GOLD SD, IQlogic, GOLD_E_F_BACnet_251202 - Other equipment (demand-controlled ventilation system controller)
Swegon SuperWISE (generation 1) BACnet IP - system objects
Swegon SuperWISE (first generation) system controllers for WISE demand-controlled ventilation, program version 1.25.
Also known as: SuperWISE, Super WISE, WISE gen 1, GB.BACnetSuper WISE.140603, SuperWISE_BACnet_list_ver_1.3
Source: BACnet IP Compact/GOLD LP, program version 2.01 and newer versions · GB.BACnet480.100129 · rev. 2010-01-29. Object names, instances and units are reproduced as published; descriptions are our own.