Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet points list
Updated 28 October 2026
The ProtoNode RER reads one or more Raypak VERSA IC controls over Modbus RTU and makes each one a separate BACnet IP or BACnet MS/TP device. The Master profile used for single boilers and cascade masters has 173 objects: system temperatures and calls, a 29-point block for each of up to 4 boilers, writable setpoint, outdoor reset, DHW, tank and pool settings, and on/off commands per boiler. Cascade followers use a smaller Follower profile.
This page lists 173 BACnet objects for the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Raypak’s own free documentation, linked below.
- Manufacturer
- Raypak
- Model
- VERSA IC - ProtoNode RER/LER (B-85 / B-86)
- Equipment
- Boiler controller gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 173 (32 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 50000 + VERSA IC Modbus node ID (BN_Node_Offset default 50000)
- Also known as
- VERSA IC, Versa IC, ProtoNode RER, ProtoNode LER, FPC-N34, FPC-N35, B-85, B-86, 241515
Instance calculator. This list prints one unit; the other units follow a formula. ProtoNode boiler gateways (Laars, Peerless, Raypak, AERCO and more) instance calculator →
Reference only, provided as-is: verify against Raypak’s current documentation and the live device before use. Not official Raypak information. Terms of use.
BMS integration notes: Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86)
Add a Master profile in the ProtoNode Web Configurator for each VERSA IC (Follower profile for cascade followers) with its Modbus node ID, then find each one as its own BACnet device. Turn boilers on with the Blr On/Off BVs and set the target with Target Mode plus Setpoint Target or Target Mod Rate; read supply temperature, boiler outlet temperature, modulation rate, ignition status and error code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 162 | Blr 1 On/Off | Boiler 1 on/off command (BV 163-165 for 2-4) | Write |
| BV 134 | Target Mode | Selects which target applies (values not documented) | Write |
| AV 135 | Setpoint Target | Target water setpoint | Write |
| AV 160 | Target Mod Rate | Target modulation rate | Write |
| AI 25 | Blr 1 Ignition Status | Boiler 1 ignition state code | Read |
| AI 2 | System Supply Temperature | System supply water temperature | Read |
| AI 18 | Blr 1 Outlet temperature | Boiler 1 outlet water temperature | Read |
| AI 23 | Blr 1 Mod Rate | Boiler 1 modulation rate | Read |
| AI 30 | Blr 1 Error Code | Boiler 1 active error code | Read |
Enable & remote start
The Master profile has writable on/off BVs per boiler (BV 162-165) and a Target Mode BV with Setpoint Target (AV 135), Target temperature (AV 158) and Target Mod Rate (AV 160). The manual does not explain the Target Mode values or which target applies in each mode.
Network setup
- Device instance = BN_Node_Offset + Modbus node ID; the offset defaults to 50000 and is changed in the Web Configurator (node 10 -> 50010).
- S-bank DIP switches pick the protocol: all off = BACnet IP (default), S0 on = BACnet MS/TP.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A-bank switches; baud on B0-B3 (9600, 19200, 38400, 57600 or 76800).
- VERSA IC side: Modbus RTU at 19200 baud, each unit with a unique node ID; up to 8 Master units (1400 registers) per ProtoNode RER.
- Default ProtoNode IP address 192.168.1.24; the Web Configurator is used to add profiles and set the offset.
Watch out for
- Use the Master profile only for single boilers or the cascade master; followers on the Ft-bus/TN-bus need the Follower profile.
- The ProtoNode connects only to a master unit, not directly to a follower.
- Never set an MS/TP MAC address above 127; 128-255 cannot be auto-discovered.
- Writable AVs are boiler settings; avoid rewriting them cyclically.
Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | MODBUS | Read | |||
| AImin | 2 | System Supply Temperature | System supply water temperature | Read | ||
| AI | 3 | Outdoor Temperature | Outdoor air temperature | Read | ||
| AI | 4 | DHW Temperature | DHW tank temperature | Read | ||
| AI | 5 | Aux 1 Temperature | Auxiliary sensor 1 temperature | Read | ||
| AI | 6 | Aux 2 Temperature | Auxiliary sensor 2 temperature | Read | ||
| AI | 7 | System Pump | System pump state | Read | ||
| AI | 8 | System Pump Runtime | System pump run time | Read | ||
| AI | 9 | DHW Pump | DHW pump state | Read | ||
| AI | 10 | DHW Pump Runtime | DHW pump run time | Read | ||
| AI | 11 | Setback | Setback state | Read | ||
| AI | 12 | CH Call | Central heat call | Read | ||
| AI | 13 | DHW Call | DHW call | Read | ||
| AI | 14 | Target temperature | Current target water temperature | Read | ||
| AI | 15 | Target rate | Current target firing rate | Read | ||
| BI | 16 | Auto Diff | Read | |||
| BI | 17 | Blr 1 detected | Boiler 1 detected on the bus | Read | ||
| AImin | 18 | Blr 1 Outlet temperature | Boiler 1 outlet water temperature | Read | ||
| AI | 19 | Blr 1 Inlet temperature | Boiler 1 inlet water temperature | Read | ||
| AI | 20 | Blr 1 Vent temperature | Boiler 1 vent (flue) temperature | Read | ||
| AI | 21 | Blr 1 High Limit temperature | Boiler 1 high limit sensor temperature | Read | ||
| AI | 22 | Blr 1 Operator temperature | Boiler 1 operator sensor temperature | Read | ||
| AImin | 23 | Blr 1 Mod Rate | Boiler 1 modulation rate | Read | ||
| AI | 24 | Blr 1 Mix Rate | Boiler 1 mix rate | Read | ||
| AImin | 25 | Blr 1 Ignition Status | Boiler 1 ignition status code | Read | ||
| AI | 26 | Blr 1 Runtime | Boiler 1 burner run time | Read | ||
| AI | 27 | Blr 1 Cycles | Boiler 1 burner cycles | Read | ||
| AI | 28 | Blr 1 Pump | Boiler 1 pump state | Read | ||
| AI | 29 | Blr 1 Pump Runtime | Boiler 1 pump run time | Read | ||
| AImin | 30 | Blr 1 Error Code | Boiler 1 active error code | Read | ||
| AI | 31 | Blr 1 Error History 1 | Boiler 1 error history entry 1 | Read | ||
| AI | 32 | Blr 1 Error History 2 | Boiler 1 error history entry 2 | Read | ||
| AI | 33 | Blr 1 Error History 3 | Boiler 1 error history entry 3 | Read | ||
| AI | 34 | Blr 1 Error History 4 | Boiler 1 error history entry 4 | Read | ||
| AI | 35 | Blr 1 Error History 5 | Boiler 1 error history entry 5 | Read | ||
| AI | 36 | Blr 1 Error History 6 | Boiler 1 error history entry 6 | Read | ||
| AI | 37 | Blr 1 Error History 7 | Boiler 1 error history entry 7 | Read | ||
| AI | 38 | Blr 1 Error History 8 | Boiler 1 error history entry 8 | Read | ||
| AI | 39 | Blr 1 Error History 9 | Boiler 1 error history entry 9 | Read | ||
| AI | 40 | Blr 1 Error History 10 | Boiler 1 error history entry 10 | Read | ||
| AI | 41 | Blr 1 Error History 11 | Boiler 1 error history entry 11 | Read | ||
| AI | 42 | Blr 1 Error History 12 | Boiler 1 error history entry 12 | Read | ||
| AI | 43 | Blr 1 Error History 13 | Boiler 1 error history entry 13 | Read | ||
| AI | 44 | Blr 1 Error History 14 | Boiler 1 error history entry 14 | Read | ||
| AI | 45 | Blr 1 Error History 15 | Boiler 1 error history entry 15 | Read | ||
| BI | 46 | Blr 2 detected | Boiler 2 detected on the bus | Read | ||
| AI | 47 | Blr 2 Outlet temperature | Boiler 2 outlet water temperature | Read | ||
| AI | 48 | Blr 2 Inlet temperature | Boiler 2 inlet water temperature | Read | ||
| AI | 49 | Blr 2 Vent temperature | Boiler 2 vent (flue) temperature | Read | ||
| AI | 50 | Blr 2 High Limit temperature | Boiler 2 high limit sensor temperature | Read | ||
| AI | 51 | Blr 2 Operator temperature | Boiler 2 operator sensor temperature | Read | ||
| AI | 52 | Blr 2 Mod Rate | Boiler 2 modulation rate | Read | ||
| AI | 53 | Blr 2 Mix Rate | Boiler 2 mix rate | Read | ||
| AI | 54 | Blr 2 Ignition Status | Boiler 2 ignition status code | Read | ||
| AI | 55 | Blr 2 Runtime | Boiler 2 burner run time | Read | ||
| AI | 56 | Blr 2 Cycles | Boiler 2 burner cycles | Read | ||
| AI | 57 | Blr 2 Pump | Boiler 2 pump state | Read | ||
| AI | 58 | Blr 2 Pump Runtime | Boiler 2 pump run time | Read | ||
| AI | 59 | Blr 2 Error Code | Boiler 2 active error code | Read | ||
| AI | 60 | Blr 2 Error History 1 | Boiler 2 error history entry 1 | Read | ||
| AI | 61 | Blr 2 Error History 2 | Boiler 2 error history entry 2 | Read | ||
| AI | 62 | Blr 2 Error History 3 | Boiler 2 error history entry 3 | Read | ||
| AI | 63 | Blr 2 Error History 4 | Boiler 2 error history entry 4 | Read | ||
| AI | 64 | Blr 2 Error History 5 | Boiler 2 error history entry 5 | Read | ||
| AI | 65 | Blr 2 Error History 6 | Boiler 2 error history entry 6 | Read | ||
| AI | 66 | Blr 2 Error History 7 | Boiler 2 error history entry 7 | Read | ||
| AI | 67 | Blr 2 Error History 8 | Boiler 2 error history entry 8 | Read | ||
| AI | 68 | Blr 2 Error History 9 | Boiler 2 error history entry 9 | Read | ||
| AI | 69 | Blr 2 Error History 10 | Boiler 2 error history entry 10 | Read | ||
| AI | 70 | Blr 2 Error History 11 | Boiler 2 error history entry 11 | Read | ||
| AI | 71 | Blr 2 Error History 12 | Boiler 2 error history entry 12 | Read | ||
| AI | 72 | Blr 2 Error History 13 | Boiler 2 error history entry 13 | Read | ||
| AI | 73 | Blr 2 Error History 14 | Boiler 2 error history entry 14 | Read | ||
| AI | 74 | Blr 2 Error History 15 | Boiler 2 error history entry 15 | Read | ||
| BI | 75 | Blr 3 detected | Boiler 3 detected on the bus | Read | ||
| AI | 76 | Blr 3 Outlet temperature | Boiler 3 outlet water temperature | Read | ||
| AI | 77 | Blr 3 Inlet temperature | Boiler 3 inlet water temperature | Read | ||
| AI | 78 | Blr 3 Vent temperature | Boiler 3 vent (flue) temperature | Read | ||
| AI | 79 | Blr 3 High Limit temperature | Boiler 3 high limit sensor temperature | Read | ||
| AI | 80 | Blr 3 Operator temperature | Boiler 3 operator sensor temperature | Read | ||
| AI | 81 | Blr 3 Mod Rate | Boiler 3 modulation rate | Read | ||
| AI | 82 | Blr 3 Mix Rate | Boiler 3 mix rate | Read | ||
| AI | 83 | Blr 3 Ignition Status | Boiler 3 ignition status code | Read | ||
| AI | 84 | Blr 3 Runtime | Boiler 3 burner run time | Read | ||
| AI | 85 | Blr 3 Cycles | Boiler 3 burner cycles | Read | ||
| AI | 86 | Blr 3 Pump | Boiler 3 pump state | Read | ||
| AI | 87 | Blr 3 Pump Runtime | Boiler 3 pump run time | Read | ||
| AI | 88 | Blr 3 Error Code | Boiler 3 active error code | Read | ||
| AI | 89 | Blr 3 Error History 1 | Boiler 3 error history entry 1 | Read | ||
| AI | 90 | Blr 3 Error History 2 | Boiler 3 error history entry 2 | Read | ||
| AI | 91 | Blr 3 Error History 3 | Boiler 3 error history entry 3 | Read | ||
| AI | 92 | Blr 3 Error History 4 | Boiler 3 error history entry 4 | Read | ||
| AI | 93 | Blr 3 Error History 5 | Boiler 3 error history entry 5 | Read | ||
| AI | 94 | Blr 3 Error History 6 | Boiler 3 error history entry 6 | Read | ||
| AI | 95 | Blr 3 Error History 7 | Boiler 3 error history entry 7 | Read | ||
| AI | 96 | Blr 3 Error History 8 | Boiler 3 error history entry 8 | Read | ||
| AI | 97 | Blr 3 Error History 9 | Boiler 3 error history entry 9 | Read | ||
| AI | 98 | Blr 3 Error History 10 | Boiler 3 error history entry 10 | Read | ||
| AI | 99 | Blr 3 Error History 11 | Boiler 3 error history entry 11 | Read | ||
| AI | 100 | Blr 3 Error History 12 | Boiler 3 error history entry 12 | Read | ||
| AI | 101 | Blr 3 Error History 13 | Boiler 3 error history entry 13 | Read | ||
| AI | 102 | Blr 3 Error History 14 | Boiler 3 error history entry 14 | Read | ||
| AI | 103 | Blr 3 Error History 15 | Boiler 3 error history entry 15 | Read | ||
| BI | 104 | Blr 4 detected | Boiler 4 detected on the bus | Read | ||
| AI | 105 | Blr 4 Outlet temperature | Boiler 4 outlet water temperature | Read | ||
| AI | 106 | Blr 4 Inlet temperature | Boiler 4 inlet water temperature | Read | ||
| AI | 107 | Blr 4 Vent temperature | Boiler 4 vent (flue) temperature | Read | ||
| AI | 108 | Blr 4 High Limit temperature | Boiler 4 high limit sensor temperature | Read | ||
| AI | 109 | Blr 4 Operator temperature | Boiler 4 operator sensor temperature | Read | ||
| AI | 110 | Blr 4 Mod Rate | Boiler 4 modulation rate | Read | ||
| AI | 111 | Blr 4 Mix Rate | Boiler 4 mix rate | Read | ||
| AI | 112 | Blr 4 Ignition Status | Boiler 4 ignition status code | Read | ||
| AI | 113 | Blr 4 Runtime | Boiler 4 burner run time | Read | ||
| AI | 114 | Blr 4 Cycles | Boiler 4 burner cycles | Read | ||
| AI | 115 | Blr 4 Pump | Boiler 4 pump state | Read | ||
| AI | 116 | Blr 4 Pump Runtime | Boiler 4 pump run time | Read | ||
| AI | 117 | Blr 4 Error Code | Boiler 4 active error code | Read | ||
| AI | 118 | Blr 4 Error History 1 | Boiler 4 error history entry 1 | Read | ||
| AI | 119 | Blr 4 Error History 2 | Boiler 4 error history entry 2 | Read | ||
| AI | 120 | Blr 4 Error History 3 | Boiler 4 error history entry 3 | Read | ||
| AI | 121 | Blr 4 Error History 4 | Boiler 4 error history entry 4 | Read | ||
| AI | 122 | Blr 4 Error History 5 | Boiler 4 error history entry 5 | Read | ||
| AI | 123 | Blr 4 Error History 6 | Boiler 4 error history entry 6 | Read | ||
| AI | 124 | Blr 4 Error History 7 | Boiler 4 error history entry 7 | Read | ||
| AI | 125 | Blr 4 Error History 8 | Boiler 4 error history entry 8 | Read | ||
| AI | 126 | Blr 4 Error History 9 | Boiler 4 error history entry 9 | Read | ||
| AI | 127 | Blr 4 Error History 10 | Boiler 4 error history entry 10 | Read | ||
| AI | 128 | Blr 4 Error History 11 | Boiler 4 error history entry 11 | Read | ||
| AI | 129 | Blr 4 Error History 12 | Boiler 4 error history entry 12 | Read | ||
| AI | 130 | Blr 4 Error History 13 | Boiler 4 error history entry 13 | Read | ||
| AI | 131 | Blr 4 Error History 14 | Boiler 4 error history entry 14 | Read | ||
| AI | 132 | Blr 4 Error History 15 | Boiler 4 error history entry 15 | Read | ||
| BVmin | 134 | Target Mode | Target mode selection | Write | ||
| AVmin | 135 | Setpoint Target | Target setpoint | Write | ||
| AV | 136 | Outdoor Start | Outdoor reset: outdoor start temperature | Write | ||
| AV | 137 | Outdoor Design | Outdoor reset: outdoor design temperature | Write | ||
| AV | 138 | Boil Start | Outdoor reset: boiler water start temperature | Write | ||
| AV | 139 | Boil Design | Outdoor reset: boiler water design temperature | Write | ||
| AV | 140 | Manual Differential | Differential setting | Write | ||
| AV | 141 | DHW Exchange | DHW exchange temperature | Write | ||
| AV | 142 | DHW Tank | DHW tank setting | Write | ||
| AV | 143 | DHW Differential | DHW differential | Write | ||
| BV | 144 | DHW Priority | DHW priority on/off | Write | ||
| BV | 145 | DHW During UnOcc | DHW during unoccupied on/off | Write | ||
| AV | 146 | WWSD During Occ | Warm weather shutdown temperature, occupied | Write | ||
| AV | 147 | WWSD During UnOcc | Warm weather shutdown temperature, unoccupied | Write | ||
| AV | 148 | Tank Setpoint | Tank setpoint | Write | ||
| AV | 149 | Tank Differential | Tank differential | Write | ||
| BV | 150 | Tank During UnOcc | Tank heating during unoccupied on/off | Write | ||
| AV | 151 | Pool Setpoint | Pool setpoint | Write | ||
| AV | 152 | Pool Differential | Pool differential | Write | ||
| AV | 153 | Pool Supply Max | Pool maximum supply temperature | Write | ||
| BV | 154 | Pool During UnOcc | Pool heating during unoccupied on/off | Write | ||
| AV | 155 | System Pump | System pump setting | Write | ||
| AV | 156 | DHW Pump | DHW pump setting | Write | ||
| AV | 157 | Boiler Pump | Boiler pump setting | Write | ||
| AV | 158 | Target temperature | Target water temperature (writable) | Write | ||
| AV | 159 | Manual Differential | Temperature differential setting | Write | ||
| AVmin | 160 | Target Mod Rate | Target modulation rate | Write | ||
| AV | 161 | Target Mix Rate | Target mix rate | Write | ||
| BVmin | 162 | Blr 1 On/Off | Boiler 1 on/off command | Write | ||
| BV | 163 | Blr 2 On/Off | Boiler 2 on/off command | Write | ||
| BV | 164 | Blr 3 On/Off | Boiler 3 on/off command | Write | ||
| BV | 165 | Blr 4 On/Off | Boiler 4 on/off command | Write | ||
| AI | 166 | Blr 1 Flow Sensor | Boiler 1 flow sensor value | Read | ||
| AI | 167 | Blr 2 Flow Sensor | Boiler 2 flow sensor value | Read | ||
| AI | 168 | Blr 3 Flow Sensor | Boiler 3 flow sensor value | Read | ||
| AI | 169 | Blr 4 Flow Sensor | Boiler 4 flow sensor value | Read | ||
| AI | 170 | Override Governor | Read | |||
| AI | 171 | Blr 1 Flame Current | Boiler 1 flame current | Read | ||
| AI | 172 | Blr 2 Flame Current | Boiler 2 flame current | Read | ||
| AI | 173 | Blr 3 Flame Current | Boiler 3 flame current | Read | ||
| AI | 174 | Blr 4 Flame Current | Boiler 4 flame current | Read |
No points match these filters.
Object ID lookup: Raypak VERSA IC point IDs by name
AI1MODBUSAI2System Supply TemperatureAI3Outdoor TemperatureAI4DHW TemperatureAI5Aux 1 TemperatureAI6Aux 2 TemperatureAI7System PumpAI8System Pump RuntimeAI9DHW PumpAI10DHW Pump RuntimeAI11SetbackAI12CH CallAI13DHW CallAI14Target temperatureAI15Target rateBI16Auto DiffBI17Blr 1 detectedAI18Blr 1 Outlet temperatureAI19Blr 1 Inlet temperatureAI20Blr 1 Vent temperatureAI21Blr 1 High Limit temperatureAI22Blr 1 Operator temperatureAI23Blr 1 Mod RateAI24Blr 1 Mix RateAI25Blr 1 Ignition StatusAI26Blr 1 RuntimeAI27Blr 1 CyclesAI28Blr 1 PumpAI29Blr 1 Pump RuntimeAI30Blr 1 Error CodeAI31Blr 1 Error History 1AI32Blr 1 Error History 2AI33Blr 1 Error History 3AI34Blr 1 Error History 4AI35Blr 1 Error History 5AI36Blr 1 Error History 6AI37Blr 1 Error History 7AI38Blr 1 Error History 8AI39Blr 1 Error History 9AI40Blr 1 Error History 10AI41Blr 1 Error History 11AI42Blr 1 Error History 12AI43Blr 1 Error History 13AI44Blr 1 Error History 14AI45Blr 1 Error History 15BI46Blr 2 detectedAI47Blr 2 Outlet temperatureAI48Blr 2 Inlet temperatureAI49Blr 2 Vent temperatureAI50Blr 2 High Limit temperatureAI51Blr 2 Operator temperatureAI52Blr 2 Mod RateAI53Blr 2 Mix RateAI54Blr 2 Ignition StatusAI55Blr 2 RuntimeAI56Blr 2 CyclesAI57Blr 2 PumpAI58Blr 2 Pump RuntimeAI59Blr 2 Error CodeAI60Blr 2 Error History 1AI61Blr 2 Error History 2AI62Blr 2 Error History 3AI63Blr 2 Error History 4AI64Blr 2 Error History 5AI65Blr 2 Error History 6AI66Blr 2 Error History 7AI67Blr 2 Error History 8AI68Blr 2 Error History 9AI69Blr 2 Error History 10AI70Blr 2 Error History 11AI71Blr 2 Error History 12AI72Blr 2 Error History 13AI73Blr 2 Error History 14AI74Blr 2 Error History 15BI75Blr 3 detectedAI76Blr 3 Outlet temperatureAI77Blr 3 Inlet temperatureAI78Blr 3 Vent temperatureAI79Blr 3 High Limit temperatureAI80Blr 3 Operator temperatureAI81Blr 3 Mod RateAI82Blr 3 Mix RateAI83Blr 3 Ignition StatusAI84Blr 3 RuntimeAI85Blr 3 CyclesAI86Blr 3 PumpAI87Blr 3 Pump RuntimeAI88Blr 3 Error CodeAI89Blr 3 Error History 1AI90Blr 3 Error History 2AI91Blr 3 Error History 3AI92Blr 3 Error History 4AI93Blr 3 Error History 5AI94Blr 3 Error History 6AI95Blr 3 Error History 7AI96Blr 3 Error History 8AI97Blr 3 Error History 9AI98Blr 3 Error History 10AI99Blr 3 Error History 11AI100Blr 3 Error History 12AI101Blr 3 Error History 13AI102Blr 3 Error History 14AI103Blr 3 Error History 15BI104Blr 4 detectedAI105Blr 4 Outlet temperatureAI106Blr 4 Inlet temperatureAI107Blr 4 Vent temperatureAI108Blr 4 High Limit temperatureAI109Blr 4 Operator temperatureAI110Blr 4 Mod RateAI111Blr 4 Mix RateAI112Blr 4 Ignition StatusAI113Blr 4 RuntimeAI114Blr 4 CyclesAI115Blr 4 PumpAI116Blr 4 Pump RuntimeAI117Blr 4 Error CodeAI118Blr 4 Error History 1AI119Blr 4 Error History 2AI120Blr 4 Error History 3AI121Blr 4 Error History 4AI122Blr 4 Error History 5AI123Blr 4 Error History 6AI124Blr 4 Error History 7AI125Blr 4 Error History 8AI126Blr 4 Error History 9AI127Blr 4 Error History 10AI128Blr 4 Error History 11AI129Blr 4 Error History 12AI130Blr 4 Error History 13AI131Blr 4 Error History 14AI132Blr 4 Error History 15BV134Target ModeAV135Setpoint TargetAV136Outdoor StartAV137Outdoor DesignAV138Boil StartAV139Boil DesignAV140Manual DifferentialAV141DHW ExchangeAV142DHW TankAV143DHW DifferentialBV144DHW PriorityBV145DHW During UnOccAV146WWSD During OccAV147WWSD During UnOccAV148Tank SetpointAV149Tank DifferentialBV150Tank During UnOccAV151Pool SetpointAV152Pool DifferentialAV153Pool Supply MaxBV154Pool During UnOccAV155System PumpAV156DHW PumpAV157Boiler PumpAV158Target temperatureAV159Manual DifferentialAV160Target Mod RateAV161Target Mix RateBV162Blr 1 On/OffBV163Blr 2 On/OffBV164Blr 3 On/OffBV165Blr 4 On/OffAI166Blr 1 Flow SensorAI167Blr 2 Flow SensorAI168Blr 3 Flow SensorAI169Blr 4 Flow SensorAI170Override GovernorAI171Blr 1 Flame CurrentAI172Blr 2 Flame CurrentAI173Blr 3 Flame CurrentAI174Blr 4 Flame Current
Integration notes
- Each VERSA IC unit is its own BACnet device: device instance = BN_Node_Offset (default 50000) + its Modbus node ID. Object IDs below are the same on every device.
- No read/write column is given. AVs and BVs map to LonWorks input variables and are marked writable; AIs and BIs are read-only.
- Object ID 133 is not used.
- Follower profile (cascade followers only): BI 1 Blr 1 detected, AI 2-29 the same Blr 1 values as AI 18-45 here, BV 30 Blr 1 On/Off, AI 31 Blr 1 Flow Sensor, AI 32 Blr 1 Flame Current.
- No units or state texts are given in the object table.
- The object table in the manual is not selectable text; it was keyed in by hand.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VERSA IC - ProtoNode RER/LER (B-85 / B-86) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86)
How many BACnet points does the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) have?
This list has 173 BACnet objects: 136 analog inputs, 23 analog values, 5 binary inputs, 9 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet points are writable?
32 of the 173 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86) BACnet documentation?
The source is Installation & Operating Instructions - ProtoNode RER and ProtoNode LER (FPC N34 / FPC N35) B-85 / B-86 (P/N 241515 Rev. 5), revision Effective 08-25-23, published free by Raypak at https://s3.amazonaws.com/AWSProd/sites/raypakcom/documents/241515.pdf.
What are the minimum BACnet points to integrate the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86)?
Start with BV 162 Blr 1 On/Off (Boiler 1 on/off command (BV 163-165 for 2-4)); BV 134 Target Mode (Selects which target applies (values not documented)); AV 135 Setpoint Target (Target water setpoint); AV 160 Target Mod Rate (Target modulation rate); AI 25 Blr 1 Ignition Status (Boiler 1 ignition state code); AI 2 System Supply Temperature (System supply water temperature); AI 18 Blr 1 Outlet temperature (Boiler 1 outlet water temperature); AI 23 Blr 1 Mod Rate (Boiler 1 modulation rate); AI 30 Blr 1 Error Code (Boiler 1 active error code).
How do I enable BMS control of the Raypak VERSA IC - ProtoNode RER/LER (B-85 / B-86)?
The Master profile has writable on/off BVs per boiler (BV 162-165) and a Target Mode BV with Setpoint Target (AV 135), Target temperature (AV 158) and Target Mod Rate (AV 160). The manual does not explain the Target Mode values or which target applies in each mode.
How do I check these points on the real VERSA IC - ProtoNode RER/LER (B-85 / B-86)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Installation & Operating Instructions - ProtoNode RER and ProtoNode LER (FPC N34 / FPC N35) B-85 / B-86 · P/N 241515 Rev. 5 · rev. Effective 08-25-23. Object names, instances and units are reproduced as published; descriptions are our own.