- TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Fan coil unit controller (room thermostat) · BACnet points list
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP) BACnet points list
Updated 29 October 2026
The TEC3610-TEC3613 are field-selectable BACnet MS/TP or N2 networked thermostats for on/off or floating fan coil and zoning equipment. The point table covers modes, occupied/unoccupied/standby setpoints, network overrides for supply air temperature and humidity, loop outputs, valve and fan outputs, tuning values and the internal schedule. TEC3611 and TEC3613 have an onboard occupancy sensor; TEC3612 and TEC3613 support dehumidification.
This page lists 97 BACnet objects for the Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP) — 68 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
- Equipment
- Fan coil unit controller (room thermostat)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 97 (68 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1
- Also known as
- TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Put the TEC on the MS/TP trunk with a unique address and instance, set OCC-CONFIG to External and command NET-OCC from the BAS. Write the occupied setpoints, control mode and fan mode, and read the operational zone temperature, unit status and the critical event MV.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 29501 | Unit Enable (UNITEN-MODE) | Shutdown or enable the unit | Write |
| MV 29500 | Control Mode (SYSTEM-MODE) | Auto, cooling or heating | Write |
| MV 29519 | Supervisor Occupancy (NET-OCC) | BAS occupancy: occupied, unoccupied, standby | Write |
| MV 29520 | Occupancy Configuration Source (OCC-CONFIG) | Must be External for NET-OCC to take effect | Write |
| MV 29524 | Fan Mode (FAN-MODE) | Fan mode: on, auto or smart | Write |
| AV 29502 | Occupied Cooling Setpoint (CLGOCC-SP) | Occupied cooling setpoint, °F | Write |
| AV 29503 | Occupied Heating Setpoint (HTGOCC-SP) | Occupied heating setpoint, °F | Write |
| MV 29700 | Unit Status (UNIT-S) | Detailed unit status | Read |
| AV 29701 | Operational Space Temperature (EFF-ZNT) | Zone temperature used for control | Read |
| MV 30000 | MV Critical Active Event | Active critical faults | Read |
Enable & remote start
Set Occupancy Configuration Source (OCC-CONFIG, MV 29520) to External, then command Supervisor Occupancy (NET-OCC, MV 29519) occupied, unoccupied or standby. With OCC-CONFIG = Schedule the internal schedule writes LOCAL-OCC instead. Unit Enable (MV 29501) shuts the unit down or enables it, and Control Mode (MV 29500) picks auto, cooling or heating. A manual override at the display, an occupancy input or the motion sensor can still change the effective occupancy.
Sensors & values from the BMS
Network Override Supply Air Temperature (NET-SAT, AV 29515) lets the BAS supply a supply air temperature, which the thermostat combines with its local sensor into EFF-SAT, and NET-ZNH (MV 29516) supplies zone humidity on units without a humidity sensor. The guide gives no timeout for these values.
Network setup
- Out of the box the thermostat runs BACnet MS/TP; N2 is chosen with FC Comm Mode in the Network Setup menu (the unit reboots).
- BACnet Instance ID: 1 to 4,194,302, default 1. MS/TP address: 4 to 127, default 4.
- MS/TP baud rate default is Auto; fixed choices are 1200, 9600, 19200, 38400 and 76800.
- Character encoding defaults to ISO 10646 (UCS-2) for Metasys; a third-party BAS may need a different setting.
Watch out for
- The guide says AV and MV objects are written without a priority (Metasys Change Default); the last such write received is the one executed.
- The passcode cannot be changed from the BAS, only at the display or through the Mobile Access Portal.
- LOCK-LVL (MV 29531) can hide the menu or most display functions; State 0 gives full access.
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 29500 | Control Mode (SYSTEM-MODE) | Unit control mode: auto, cooling or heating | Write | 1=Auto, 2=Cooling, 3=Heating | |
| MVmin | 29501 | Unit Enable (UNITEN-MODE) | Unit shutdown or enable | Write | 1=Shutdown, 2=Enable | |
| AV | 29567 | Common Setpoint (COMMON-SP) | Single common setpoint (common setpoint mode) | °F | Read | |
| AVmin | 29502 | Occupied Cooling Setpoint (CLGOCC-SP) | Occupied cooling setpoint | °F | Write | |
| AVmin | 29503 | Occupied Heating Setpoint (HTGOCC-SP) | Occupied heating setpoint | °F | Write | |
| AV | 29504 | Unoccupied Cooling Setpoint (CLGUNOCC-SP) | Unoccupied cooling setpoint | °F | Write | |
| AV | 29505 | Unoccupied Heating Setpoint (HTGUNOCC-SP) | Unoccupied heating setpoint | °F | Write | |
| AV | 29506 | Standby Cooling Setpoint (CLGSTBY-SP) | Standby cooling setpoint | °F | Write | |
| AV | 29507 | Standby Heating Setpoint (HTGSTBY-SP) | Standby heating setpoint | °F | Write | |
| AV | 29508 | Setpoint Offset (WC-ADJ) | Warmer/cooler offset added to the setpoint | Write | ||
| MV | 29509 | Hold/Run (HOLDRUN-MD) | Hold or run the schedule | Write | 1=Hold, 2=Run | |
| AV | 29510 | Humidity Setpoint (ZNH-SP) | Zone humidity (dehumidification) setpoint | %RH | Write | |
| AV | 29515 | Network Override Supply Air Temperature (NET-SAT) | Supply air temperature written by the BAS | °F | Write | |
| MV | 29516 | Network Override Zone Humidity (NET-ZNH) | Zone humidity written by the BAS | %RH | Write | |
| MV | 29517 | Reset PID Tuning (TUNING-RESET) | Reset the PID auto-tuning | Write | 1=No, 2=Yes | |
| MV | 29518 | Manual Occupancy Override (OCCOVRD-MODE) | Manual occupancy override from the display | Write | 1=No Override, 2=Occupied, 3=Unoccupied | |
| MVmin | 29519 | Supervisor Occupancy (NET-OCC) | Occupancy command from the BAS (OCC-CONFIG = External) | Write | 1=Occupied, 2=Unoccupied, 3=Standby | |
| MVmin | 29520 | Occupancy Configuration Source (OCC-CONFIG) | Occupancy source: internal schedule or external (BAS) | Write | 1=Schedule, 2=External | |
| AV | 29522 | Passcode (PASSCODE) | Display passcode (cannot be changed from the BAS) | Read | ||
| MV | 29523 | Changeover Mode (CGOVR-MODE) | Changeover mode: auto, cooling or heating | Write | 1=Auto, 2=Cooling, 3=Heating | |
| MVmin | 29524 | Fan Mode (FAN-MODE) | Fan mode (single- or variable-speed fan) | Write | 1=On, 2=Auto, 3=Smart | |
| MV | 29525 | Fan Override (FANOVRD-MODE) | Fan override from the display | Write | 1=On, 2=Auto, 3=Quiet | |
| MV | 29568 | Fan Mode 2 (FAN-MODE2) | Fan mode (multi-speed fan) | Write | 1=Auto, 2=Smart, 3=Low, 4=Medium, 5=High | |
| MV | 29569 | Fan Override Mode 2 (FAN-OVRD2) | Fan override from the display (multi-speed fan) | Write | 1=Auto, 2=Quiet, 3=Low, 4=Medium, 5=High | |
| MV | 29527 | Aux Mode (AUX-MODE) | Auxiliary output function | Write | 1=Not Used, 2=Occupied NO, 3=Occupied NC, 4=Occupied Fan NO, 5=Occupied Fan NC, 6=On, 7=Off | |
| MV | 29528 | Temperature Units (TEMP-UNITS) | Display units: IP or SI | Write | 1=IP, 2=SI | |
| AV | 29529 | Max Setpoint Offset (MAXSP-OFFSET) | Largest warmer/cooler offset allowed | °F | Write | |
| MVmin | 29700 | Unit Status (UNIT-S) | Detailed unit status | Read | 1=System Fault, 2=Airflow Fault, 3=Open Window, 4=Control Off, 5=Unreliable Temperature, 6=Dehumidification, 7=Idle, 8=Cooling, 9=Heating, 10=Cooling Unavailable, 11=Heating Unavailable, 12=Cooling Unavailable due to Changeover, 13=Cooling Unavailable due to OA Temp, 14=Cooling Unavailable due to Control Mode, 15=Heating Unavailable due to Changeover, 16=Heating Unavailable due to OA Temp, 17=Heating Unavailable due to Control Mode, 18=Load Shed Active | |
| AVmin | 29701 | Operational Space Temperature (EFF-ZNT) | Zone temperature used for control | Read | ||
| AV | 29702 | Return Air Humidity (EFF-ZNH) | Zone humidity used for control | Read | ||
| AV | 29703 | Supply Air Temperature (EFF-SAT) | Supply air temperature used for control | Read | ||
| AV | 29705 | Active Setpoint (EFF-SETPOINT) | Active setpoint | Read | ||
| AV | 29706 | CV Operating Cooling Setpoint (EFFCLG-SP) | Active cooling setpoint | Read | ||
| AV | 29707 | CV Operating Heating Setpoint (EFFHTG-SP) | Active heating setpoint | Read | ||
| MV | 29708 | Occupancy Status (EFF-OCC) | Effective occupancy status | Read | 1=Occupied, 2=Temp Occupancy, 3=Unoccupied, 4=Standby, 5=Occupied-Override, 6=Unoccupied-Override | |
| MV | 29709 | Occupancy Input Source (OCCSOURCE-S) | What set the current occupancy | Read | 1=Occupancy BI, 2=Temp Occ BI, 3=Temp Occ, 4=Occ Override, 5=Local Schedule, 6=BAS Schedule, 7=Occupancy Sensor | |
| AV | 29714 | Cool/Dehum PID Cmd (CLGPID-%) | Cooling/dehumidification loop output | % | Write | |
| AV | 29717 | Heat PID Command (HTGPID-%) | Heating loop output | % | Write | |
| AV | 29720 | Reheat PID Command (RHPID-%) | Reheat loop output | % | Read | |
| AO | 86907 | Cooling Valve % Command (CLG-O) | Cooling valve output, percent | % | Write | |
| BO | 86908 | BO1 Command (CLGO-C) | Cooling output, N.O. terminal | Write | Inactive/Active | |
| BO | 87101 | BO6 Command (CLGC-C) | Cooling output, N.C. terminal | Write | Inactive/Active | |
| MV | 29728 | Load Shed Active (LOADSHED-EN) | Load shed active | Write | 0=No, 1=Yes | |
| AV | 29725 | Load Shed Rate limit (LOADSHED-RL) | Load shed setpoint rate limit | °F | Write | |
| AV | 29726 | Load Shed Adjust (LOADSHED-ADJ) | Load shed setpoint adjustment | °F | Write | |
| BO | 86909 | Fan Low Command (FANL-C) | Fan low speed output | Write | Inactive/Active | |
| BO | 86910 | Fan Medium Command (FANM-C) | Fan medium speed output | Write | Inactive/Active | |
| BO | 86912 | Fan High Command (FANH-C) | Fan high speed output | Write | Inactive/Active | |
| BO | 87102 | BO5 Command (HTGO-C) | Heating output, N.O. terminal | Write | Inactive/Active | |
| AV | 86905 | Fan Speed % Command (FANSPD-%) | Fan speed command, percent | % | Write | |
| MV | 29712 | Fan Speed Status (FANSPD-S) | Supply fan status | Read | 1=Off, 2=On, 3=Low, 4=Medium, 5=High | |
| BI | 30827 | B1 Sensor (BI1-S) | Binary input 1 state | Read | Inactive/Active | |
| BI | 30828 | B2 Sensor (BI2-S) | Binary input 2 state | Read | Inactive/Active | |
| MV | 6 | Local Occupancy (LOCAL-OCC) | Occupancy from the internal schedule | Read | 1=Occupied, 2=Unoccupied, 3=Standby, 4=Not Set | |
| AV | 29727 | Temporary Occupancy Duration (TEMPOCC-LEN) | Temporary occupancy duration | min | Write | |
| AV | 29530 | Changeover Setpoint (CGOVR-SP) | Supply temperature changeover setpoint | °F | Read | |
| AV | 29534 | Unoccupied Off Delay (UNOCC-OFF-DELAY) | Delay before unoccupied off | min | Write | |
| MV | 29563 | Occ Setpoint Select (OCCSP-SEL) | Setpoint adjust method: offset or min/max | Write | 0=Setpoint Offset, 1=Min and Max Setpoint | |
| MV | 29566 | Heat Cool Setpoint Mode (HTGCLGSP-MODE) | Common or individual heat/cool setpoints | Write | 0=Common Setpoint, 1=Individual Setpoint | |
| AV | 29560 | Max Heating Setpoint (MAXHTG-SP) | Highest heating setpoint allowed | Write | ||
| AV | 29559 | Min Heating Setpoint (MINHTG-SP) | Lowest heating setpoint allowed | °F | Write | |
| AV | 29562 | Max Cooling Setpoint (MAXCLG-SP) | Highest cooling setpoint allowed | °F | Write | |
| AV | 29561 | Min Cooling Setpoint (MINCLG-SP) | Lowest cooling setpoint allowed | Write | ||
| AV | 29565 | Max Setpoint (MAX-SP) | Highest common setpoint allowed | °F | Write | |
| AV | 29564 | Min Setpoint (MIN-SP) | Lowest common setpoint allowed | °F | Write | |
| MV | 29533 | Temp Control Setup (TEMPCTRL-SETUP) | Temperature control tuning method | Write | 0=Automatic PID Tuning, 1=Deadband Override, 2=Manual PID Tuning, 3=On/Off Control (single-speed fan only) | |
| MV | 29558 | Temp Control Setup 2 (TEMPCTRL-SETUP2) | Tuning method (multi- or variable-speed fan units) | Write | 0=Automatic PID Tuning, 1=Deadband Override, 2=Manual PID Tuning | |
| AV | 29556 | Deadband (DEADBAND) | Control deadband | delta °F | Write | |
| AV | 29535 | Heat Prop band (HTG-PROP-BAND) | Heating loop proportional band | delta °F | Write | |
| AV | 29536 | Heat Integral Time (HTG-INT-TIME) | Heating loop integral time | s | Write | |
| AV | 29537 | Heat Process Range (HTG-PROC-RANGE) | Heating loop process range | delta °F | Write | |
| AV | 29538 | Heat Saturation Time (HTG-SAT-TIME) | Heating loop saturation time | s | Write | |
| AV | 29539 | Heat Time Constant (HTG-TIME-CONST) | Heating loop time constant | s | Write | |
| AV | 29540 | Heat Process Dead Time (HTG-DEAD-TIME) | Heating loop process dead time | s | Write | |
| AV | 29541 | Heat Period (HTG-PERIOD) | Heating loop period | s | Write | |
| AV | 29542 | Cool Prop Band (CLG-PROP-BAND) | Cooling loop proportional band | delta °F | Write | |
| AV | 29543 | Cool Integral Time (CLG-INT-TIME) | Cooling loop integral time | s | Write | |
| AV | 29544 | Cool Process Range (CLG-PROC-RANGE) | Cooling loop process range | delta °F | Write | |
| AV | 29545 | Cool Saturation Time (CLG-SAT-TIME) | Cooling loop saturation time | s | Write | |
| AV | 29546 | Cool Time Constant (CLG-TIME-CONST) | Cooling loop time constant | s | Write | |
| AV | 29547 | Cool Process Dead Time (CLG-DEAD-TIME) | Cooling loop process dead time | s | Write | |
| AV | 29548 | Cool Period (CLG-PERIOD) | Cooling loop period | s | Write | |
| MV | 29531 | LOCK-LVL | Display user lockout level | Write | 0=State 0, 1=State 1, 2=State 2 | |
| SCH | 10133 | Schedule | Internal occupancy schedule | Write | ||
| CAL | 10019 | Calendar | Holiday calendar for the schedule | Write | ||
| MVmin | 30000 | MV Critical Active Event | Active critical faults (bit list) | Read | ||
| NC | 10 | Critical Active Event NTF | Notification class for critical active events | Read | ||
| MV | 29999 | MV Critical Inactive Event | Critical faults returned to normal | Read | ||
| NC | 11 | Critical Inactive Event NTF | Notification class for critical inactive events | Read | ||
| MV | 29998 | MV Service Priority Active Event | Active service-priority faults | Read | ||
| NC | 12 | Service Priority Active Event NTF | Notification class for service-priority events | Read | ||
| MV | 29997 | MV Service Priority Inactive Event | Service-priority faults returned to normal | Read | ||
| NC | 13 | Service Priority Inactive Event NTF | Notification class for service-priority events | Read | ||
| MV | 29996 | MV Service Active Event | Active service faults | Read | ||
| NC | 14 | Service Active Event NTF | Notification class for service events | Read | ||
| MV | 29995 | MV Service Inactive Event | Service faults returned to normal | Read | ||
| NC | 15 | Service Inactive Event NTF | Notification class for service events | Read |
No points match these filters.
Object ID lookup: Johnson Controls TEC3610-TEC3613 Fan Coil Thermostat point IDs by name
MV29500Control Mode (SYSTEM-MODE)MV29501Unit Enable (UNITEN-MODE)AV29567Common Setpoint (COMMON-SP)AV29502Occupied Cooling Setpoint (CLGOCC-SP)AV29503Occupied Heating Setpoint (HTGOCC-SP)AV29504Unoccupied Cooling Setpoint (CLGUNOCC-SP)AV29505Unoccupied Heating Setpoint (HTGUNOCC-SP)AV29506Standby Cooling Setpoint (CLGSTBY-SP)AV29507Standby Heating Setpoint (HTGSTBY-SP)AV29508Setpoint Offset (WC-ADJ)MV29509Hold/Run (HOLDRUN-MD)AV29510Humidity Setpoint (ZNH-SP)AV29515Network Override Supply Air Temperature (NET-SAT)MV29516Network Override Zone Humidity (NET-ZNH)MV29517Reset PID Tuning (TUNING-RESET)MV29518Manual Occupancy Override (OCCOVRD-MODE)MV29519Supervisor Occupancy (NET-OCC)MV29520Occupancy Configuration Source (OCC-CONFIG)AV29522Passcode (PASSCODE)MV29523Changeover Mode (CGOVR-MODE)MV29524Fan Mode (FAN-MODE)MV29525Fan Override (FANOVRD-MODE)MV29568Fan Mode 2 (FAN-MODE2)MV29569Fan Override Mode 2 (FAN-OVRD2)MV29527Aux Mode (AUX-MODE)MV29528Temperature Units (TEMP-UNITS)AV29529Max Setpoint Offset (MAXSP-OFFSET)MV29700Unit Status (UNIT-S)AV29701Operational Space Temperature (EFF-ZNT)AV29702Return Air Humidity (EFF-ZNH)AV29703Supply Air Temperature (EFF-SAT)AV29705Active Setpoint (EFF-SETPOINT)AV29706CV Operating Cooling Setpoint (EFFCLG-SP)AV29707CV Operating Heating Setpoint (EFFHTG-SP)MV29708Occupancy Status (EFF-OCC)MV29709Occupancy Input Source (OCCSOURCE-S)AV29714Cool/Dehum PID Cmd (CLGPID-%)AV29717Heat PID Command (HTGPID-%)AV29720Reheat PID Command (RHPID-%)AO86907Cooling Valve % Command (CLG-O)BO86908BO1 Command (CLGO-C)BO87101BO6 Command (CLGC-C)MV29728Load Shed Active (LOADSHED-EN)AV29725Load Shed Rate limit (LOADSHED-RL)AV29726Load Shed Adjust (LOADSHED-ADJ)BO86909Fan Low Command (FANL-C)BO86910Fan Medium Command (FANM-C)BO86912Fan High Command (FANH-C)BO87102BO5 Command (HTGO-C)AV86905Fan Speed % Command (FANSPD-%)MV29712Fan Speed Status (FANSPD-S)BI30827B1 Sensor (BI1-S)BI30828B2 Sensor (BI2-S)MV6Local Occupancy (LOCAL-OCC)AV29727Temporary Occupancy Duration (TEMPOCC-LEN)AV29530Changeover Setpoint (CGOVR-SP)AV29534Unoccupied Off Delay (UNOCC-OFF-DELAY)MV29563Occ Setpoint Select (OCCSP-SEL)MV29566Heat Cool Setpoint Mode (HTGCLGSP-MODE)AV29560Max Heating Setpoint (MAXHTG-SP)AV29559Min Heating Setpoint (MINHTG-SP)AV29562Max Cooling Setpoint (MAXCLG-SP)AV29561Min Cooling Setpoint (MINCLG-SP)AV29565Max Setpoint (MAX-SP)AV29564Min Setpoint (MIN-SP)MV29533Temp Control Setup (TEMPCTRL-SETUP)MV29558Temp Control Setup 2 (TEMPCTRL-SETUP2)AV29556Deadband (DEADBAND)AV29535Heat Prop band (HTG-PROP-BAND)AV29536Heat Integral Time (HTG-INT-TIME)AV29537Heat Process Range (HTG-PROC-RANGE)AV29538Heat Saturation Time (HTG-SAT-TIME)AV29539Heat Time Constant (HTG-TIME-CONST)AV29540Heat Process Dead Time (HTG-DEAD-TIME)AV29541Heat Period (HTG-PERIOD)AV29542Cool Prop Band (CLG-PROP-BAND)AV29543Cool Integral Time (CLG-INT-TIME)AV29544Cool Process Range (CLG-PROC-RANGE)AV29545Cool Saturation Time (CLG-SAT-TIME)AV29546Cool Time Constant (CLG-TIME-CONST)AV29547Cool Process Dead Time (CLG-DEAD-TIME)AV29548Cool Period (CLG-PERIOD)MV29531LOCK-LVLSCH10133ScheduleCAL10019CalendarMV30000MV Critical Active EventNC10Critical Active Event NTFMV29999MV Critical Inactive EventNC11Critical Inactive Event NTFMV29998MV Service Priority Active EventNC12Service Priority Active Event NTFMV29997MV Service Priority Inactive EventNC13Service Priority Inactive Event NTFMV29996MV Service Active EventNC14Service Active Event NTFMV29995MV Service Inactive EventNC15Service Inactive Event NTF
Integration notes
- The guide's BACnet table has no access column; access here is inferred from the N2 point type printed in the same row (AO/BO/MO writable, AI/BI/MI read-only). The network override points and the Schedule and Calendar objects (no N2 type) are marked writable.
- Multistate state numbers are copied from the guide's enum lists.
- The six MV event objects (MV 29995-30000) and their notification classes (10-15) come from the guide's separate multi-state event table, which applies to all three TEC36xx families on BACnet MS/TP.
- Some points only appear with matching configuration, e.g. Fan Mode for single/variable-speed fans and Fan Mode 2 for multi-speed fans.
- The guide prints instance 87102 for both BO5 Command (HTGO-C, heating output on the N.O. terminal) and BO7 Command (HTGC-C, heating output on the N.C. terminal); only BO5 is listed here. Read the device's object list to find BO7's real instance.
- Network Override Zone Humidity (NET-ZNH) is printed as an MV in this table and as an AV in the other two TEC3000 tables.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
How many BACnet points does the Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP) have?
This list has 97 BACnet objects: 1 analog output, 48 analog values, 2 binary inputs, 6 binary outputs, 1 calendar, 6 notification classs, 1 schedule, 32 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP) BACnet points are writable?
68 of the 97 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP) BACnet documentation?
The source is TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers Technical Bulletin (LIT-12011956), revision 2018-07, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/of4XABY6Cun_CHQyMfnYOw/content.
What are the minimum BACnet points to integrate the Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)?
Start with MV 29501 Unit Enable (UNITEN-MODE) (Shutdown or enable the unit); MV 29500 Control Mode (SYSTEM-MODE) (Auto, cooling or heating); MV 29519 Supervisor Occupancy (NET-OCC) (BAS occupancy: occupied, unoccupied, standby); MV 29520 Occupancy Configuration Source (OCC-CONFIG) (Must be External for NET-OCC to take effect); MV 29524 Fan Mode (FAN-MODE) (Fan mode: on, auto or smart); AV 29502 Occupied Cooling Setpoint (CLGOCC-SP) (Occupied cooling setpoint, °F); AV 29503 Occupied Heating Setpoint (HTGOCC-SP) (Occupied heating setpoint, °F); MV 29700 Unit Status (UNIT-S) (Detailed unit status); AV 29701 Operational Space Temperature (EFF-ZNT) (Zone temperature used for control); MV 30000 MV Critical Active Event (Active critical faults).
How do I enable BMS control of the Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)?
Set Occupancy Configuration Source (OCC-CONFIG, MV 29520) to External, then command Supervisor Occupancy (NET-OCC, MV 29519) occupied, unoccupied or standby. With OCC-CONFIG = Schedule the internal schedule writes LOCAL-OCC instead. Unit Enable (MV 29501) shuts the unit down or enables it, and Control Mode (MV 29500) picks auto, cooling or heating. A manual override at the display, an occupancy input or the motion sensor can still change the effective occupancy.
Can the BMS supply sensor values to the Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)?
Network Override Supply Air Temperature (NET-SAT, AV 29515) lets the BAS supply a supply air temperature, which the thermostat combines with its local sensor into EFF-SAT, and NET-ZNH (MV 29516) supplies zone humidity on units without a humidity sensor. The guide gives no timeout for these values.
How do I check these points on the real TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Refrigerated display case controller
Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)
PENN / Johnson Controls MR5 Series (MR534) panel-mount controllers for refrigerated display cases, with the ADPT-MR5-RS485 adapter for BACnet MS/TP or Verasys.
Also known as: MR5, MR534, MR534AFDV, MR534AFDN, PENN MR5, ADPT-MR5-RS485, LIT-12013019, JCI refrigeration case controller - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Room pressure controller (isolation room)
Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-1655 room pressure controllers for isolation rooms, labs and cleanrooms, with optional anteroom and flow inputs.
Also known as: FMS-1655, FMS1655, Triatek FMS-1655, Triatek room pressure controller, JCI room pressure controller, LIT-12013120 - Room pressure controller (critical environment)
Johnson Controls Triatek FMS-2000C Critical Environment Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000C critical environment controllers for isolation rooms, labs and cleanrooms (successor of the FMS-1655).
Also known as: FMS-2000C, FMS2000C, FMS-2000, Triatek FMS-2000C, LIT-12013504, JCI critical environment controller - Room pressure monitor (critical environment)
Johnson Controls Triatek FMS-2000M Critical Environment Monitor (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000M critical environment monitors with one to four differential pressure sensors (models FMS2M-Bx1x to Bx4x).
Also known as: FMS-2000M, FMS2000M, Triatek FMS-2000M, FMS2M, FMS2M-Bx1x, FMS2M-Bx2x, FMS2M-Bx3x, FMS2M-Bx4x, LIT-12013580 - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Bypass damper controller (Verasys zoning)
Johnson Controls Verasys BYP200 Bypass Controller
Verasys BYP200 bypass damper controllers that hold duct static pressure in a zoning system.
Also known as: BYP200, Verasys bypass controller - General purpose I/O controller (Verasys)
Johnson Controls Verasys generic IO controller
Verasys generic IO controllers with digital and analog inputs, outputs, NetSensors and energy meters on the system bus.
Also known as: Verasys generic IO, Verasys IO controller, Verasys GIO - Rooftop unit controller (Smart Equipment)
Johnson Controls Verasys SSE system bus (Smart Equipment rooftop board)
Rooftop units with the Simplicity SE / Smart Equipment (SSE) control board connected to a Verasys system bus.
Also known as: SSE, Simplicity SE, Verasys SSE - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC1000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC1000 Constant Volume Controller.
Also known as: VAC1000, Verasys VAC1000, Verasys constant volume controller - Lighting controller (Verasys)
Johnson Controls Verasys VAC1001 Lighting Controller
Verasys VAC1001 lighting controllers with up to 9 lighting circuits grouped into zones.
Also known as: VAC1001, Verasys lighting controller - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC3000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC3000 Constant Volume Controller.
Also known as: VAC3000, Verasys VAC3000, Verasys constant volume controller, Verasys CV controller - VAV / zone damper controller (Verasys)
Johnson Controls Verasys Zone Equipment Controller (ZEC)
Verasys Zone Equipment Controllers serving zone dampers and VAV boxes in a Verasys zoning system.
Also known as: ZEC, Verasys ZEC, Zone Equipment Controller - Rooftop unit controller (Verasys zoning)
Johnson Controls Verasys Zoning RTU (rooftop unit on the Verasys system bus)
Rooftop units integrated as the air source of a Verasys zoning system.
Also known as: Verasys Zoning RTU, Verasys RTU, Verasys zoning rooftop - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771 - Zoning system coordinator
Johnson Controls VZC100 Verasys Zone Coordinator
Verasys VZC100 zone coordinators that run a zoned rooftop system (zone voting, duct pressure and discharge air resets).
Also known as: VZC100, Verasys Zone Coordinator
Source: TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers Technical Bulletin · LIT-12011956 · rev. 2018-07. Object names, instances and units are reproduced as published; descriptions are our own.