Rooftop unit controller · BACnet points list
Johnson Controls Premier Rooftop Units 25-50 Ton BACnet points list
Updated 28 October 2026
The Premier 25-50 ton rooftop units use the Applied Smart Equipment controller, which has BACnet MS/TP (plus Modbus and N2) on its FC bus and BACnet IP through an optional plug-in card. The points list is all AV, MV and CSV objects in the 29501-30079 range: occupancy and unit enable commands, heating and cooling setpoints, network override inputs for zone and outdoor sensors, unit, fan, cooling and heating status, refrigerant circuit values, runtimes and fault flags. Many points belong to options and stay unused on units without them.
This page lists 322 BACnet objects for the Johnson Controls Premier Rooftop Units 25-50 Ton — 115 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- Premier Rooftop Units 25-50 Ton
- Equipment
- Rooftop unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 322 (115 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls Premier Rooftop Units 25-50 Ton
Pick the field bus mode (BACnet MS/TP on the FC bus, or BACnet IP with the optional card) and set the device OID in Controller > Network. Set OccMode (MV 29518) to External so the BAS occupancy request on NetOcc (MV 29520) is used, keep UnitEn (MV 29896) at Enable, and write the occupied heating and cooling setpoints. Read Unit-S, Fan-S, the zone temperature in use and DAT for status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 29896 | UnitEn | Unit enable (0 = shutdown, 1 = enable) | Write |
| MV 29520 | NetOcc | BAS occupancy: occupied, unoccupied or not set | Write |
| MV 29518 | OccMode | Must be External for BAS occupancy | Write |
| AV 29608 | ClgOcc-Sp | Occupied cooling setpoint, 45-98 °F | Write |
| AV 29723 | HtgOcc-Sp | Occupied heating setpoint, 40-85 °F | Write |
| MV 29803 | Unit-S | Unit state: idle, SD alarm, purge, start-up wizard | Read |
| MV 29550 | Fan-S | Fan state: off/idle, on/purge, on/valve or limit fault, on | Read |
| AV 29522 | OprZT | Zone temperature in use | Read |
| AV 29564 | DAT | Discharge air temperature | Read |
| MV 29969 | DownInOccAlm | Unit down during occupied mode (1 = alarm) | Read |
Enable & remote start
UnitEn (MV 29896) enables or shuts down the unit; the default is Enable. With OccMode (MV 29518) at Schedule the unit follows its internal schedule. With OccMode at External, an occupied command from the BAS (NetOcc, MV 29520), a zone sensor override or the hard-wired occupancy input makes the unit occupied.
Heartbeat & communication loss
No unit-level heartbeat point is listed. A zone temperature written by the BAS times out after 15 minutes without an update; the controller then falls back to a NetSensor, the wired zone sensor, then return air temperature.
Sensors & values from the BMS
Write zone temperature to NetZT (AV 29526), setpoint offset to NetSSO (AV 29540), zone humidity to NetSH (AV 29533), indoor CO2 to NetIAQ (AV 29530), and outdoor air temperature, humidity and CO2 to NetOAT, NetOAH and NetOAQ. A BAS zone temperature has top priority over local sensors. ZTSrc, IAQSrc, SHSrc and OATSrc show which source is in use.
Network setup
- BACnet MS/TP: set FCBusMode to Wired Field Bus; default MAC address 4 (range 4-255), default baud 38400.
- BACnet IP needs the optional BACnet IP card; with it installed, BACnet MS/TP, Modbus and N2 on the FC bus do not work. Choose DHCP or a static IP, mask and router in Controller > Network.
- Device OID range 0-4194302, set from the local display or a MAP gateway; it is also writable as DeviceId (AV 29897).
- FC bus cable: 22 AWG 3-wire twisted shielded; set the EOL switch ON at each end of a bus segment. Use Cat 5/5e/6 for BACnet IP.
- SZVAV must be enabled at commissioning (SZVAVEn); MZVAV is the default unit type.
Watch out for
- Multistate values in the table start at 0; confirm the numbering on the device before writing NetOcc, OccMode or UnitEn.
- NetOcc only acts when OccMode is External.
- DctShutdownSp (AV 29567) is a high duct static limit; exceeding it locks the unit out as a critical fault. ResetLO (MV 29826) resets lockouts.
- Unit name, serial number and device name are writable CSVs; do not write them cyclically.
Johnson Controls Premier Rooftop Units 25-50 Ton BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 29521 | TempOccTimeout | Temporary Occupancy Timeout, 30-480 minutes | minutes | Write | |
| AVmin | 29522 | OprZT | Operational Zone Temperature | °F | Read | |
| AV | 29524 | ZTAlarmOffset | ZT Alarm Setpoint Offset, 0.0-25.0 °F | °F | Write | |
| AV | 29525 | ZTAlarmDelay | ZT Alarm Time Delay, 0-120 minutes | minutes | Write | |
| AV | 29526 | NetZT | Network Override ZT, 0.0-100.0 °F | °F | Write | |
| AV | 29527 | OprIAQ | Operational IAQ | ppm | Read | |
| AV | 29530 | NetIAQ | Network Override IAQ, 0-5,000 ppm | ppm | Write | |
| AV | 29531 | OprZH | Operational Space Humidity | %RH | Read | |
| AV | 29533 | NetSH | Network Override Zone Humidity, 0-100 %RH | %RH | Write | |
| AV | 29537 | OprSSO | Operational Zone Temperature Setpoint Offset | Δ°F | Read | |
| AV | 29540 | NetSSO | Network Override Space Setpoint Offset, -5.0 to 5.0 Δ°F | Δ°F | Write | |
| AV | 29541 | OprOAT | Operational OAT | °F | Read | |
| AV | 29543 | NetOAT | Network Override OAT, -50.0 to 125.0 °F | °F | Write | |
| AV | 29544 | OprOAH | Operational Outdoor Air Humidity | %RH | Read | |
| AV | 29545 | OA-Enth | Outdoor Air Enthalpy | BTU/lb | Read | |
| AV | 29546 | NetOAH | Network Override Outdoor Air Humidity, 0-100 %RH | %RH | Write | |
| AV | 29547 | OprOAQ | Operational Outdoor Air Quality | ppm | Read | |
| AV | 29549 | NetOAQ | Network Override Outdoor Air Quality | ppm | Write | |
| AV | 29551 | FanVFD | Fan % Command | % | Read | |
| AV | 29554 | Fan-RT | Supply Fan Accumulated Runtime | hours | Read | |
| AV | 29559 | FanOffDlyCool | Fan Off Delay for Cool, 0-255 seconds | seconds | Write | |
| AV | 29561 | FanOffDlyHeat | Fan Off Delay for Heat, 0-30 seconds | seconds | Write | |
| AVmin | 29564 | DAT | DAT | °F | Read | |
| AV | 29565 | DctPrs | Discharge Air Static Pressure | iwg | Read | |
| AV | 29566 | DctPrs-Sp | Duct Pressure Setpoint | iwg | Write | |
| AV | 29567 | DctShutdownSp | Duct Pressure Shutdown Setpoint | iwg | Write | |
| AV | 29576 | #ClgStgs | Number of Cooling Stages Installed | Read | ||
| AV | 29578 | MinRtCoolStg | Minimum Runtime for a Cooling Stage | minutes | Read | |
| AV | 29581 | Circ1ClgOATCutout | Circuit 1 OAT Cooling Cutout | °F | Write | |
| AV | 29582 | Circ2ClgOATCutout | Circuit 2 OAT Cooling Cutout | °F | Write | |
| AV | 29592 | Freeze-Sp | Freeze Condition Setpoint, 20.0-32.0 °F | °F | Write | |
| AV | 29604 | ClgDATUp-SP | Cooling DAT Upper Setpoint, 41.0-80.0 °F | °F | Write | |
| AV | 29605 | ClgDATLo-SP | Cooling DAT Lower Setpoint, 40.0-79.0 °F | °F | Write | |
| AV | 29607 | OprClgDAT-SP | Operating Cooling DAT Setpoint | °F | Read | |
| AVmin | 29608 | ClgOcc-Sp | OCC Cooling Setpoint, 45.0-98.0 °F | °F | Write | |
| AV | 29609 | ClgUnocc-Sp | UNOCC Cooling Setpoint, 46.0-99.0 °F | °F | Write | |
| AV | 29610 | OprClg-Sp | Operating Cooling Setpoint | °F | Read | |
| AV | 29627 | C1A-RunTime | Compressor Accumulated Runtime 1A | hours | Read | |
| AV | 29628 | C1B-RunTime | Compressor Accumulated Runtime 1B | hours | Read | |
| AV | 29630 | C2A-RunTime | Compressor Accumulated Runtime 2A | hours | Read | |
| AV | 29631 | C1AOnTimer | Min. ON Time Remaining 1A | seconds | Read | |
| AV | 29632 | C1BOnTimer | Min. ON Time Remaining 1B | seconds | Read | |
| AV | 29634 | C2AOnTimer | Min. ON Time Remaining 2A | seconds | Read | |
| AV | 29635 | C1A-ASCDTmr | Anti-Short Cycle Delay Time Remaining 1A | seconds | Read | |
| AV | 29636 | C1B-ASCDTmr | Anti-Short Cycle Delay Time Remaining 1B | seconds | Read | |
| AV | 29638 | C2A-ASCDTmr | Anti-Short Cycle Delay Time Remaining 2A | seconds | Read | |
| AV | 29671 | SLP-1 | Suction Line Pressure 1 | psi | Read | |
| AV | 29672 | SLP-2 | Suction Line Pressure 2 | psi | Read | |
| AV | 29675 | LLP-1 | Liquid Line Pressure 1 | psi | Read | |
| AV | 29676 | LLP-2 | Liquid Line Pressure 2 | psi | Read | |
| AV | 29679 | SLT-1 | Suction Line Temperature 1 | °F | Read | |
| AV | 29680 | SLT-2 | Suction Line Temperature 2 | °F | Read | |
| AV | 29683 | LLT-1 | Liquid Line Temperature 1 | °F | Read | |
| AV | 29684 | LLT-2 | Liquid Line Temperature 2 | °F | Read | |
| AV | 29711 | HtgOATCutout-Sp | OAT Heating Cutout Setpoint, 0.0-100.0 °F | °F | Write | |
| AVmin | 29723 | HtgOcc-Sp | OCC Heating Setpoint, 40.0-85.0 °F | °F | Write | |
| AV | 29725 | HtgUnocc-Sp | UNOCC Heating Setpoint, 45.0-98.0 °F | °F | Write | |
| AV | 29726 | OprHtg-Sp | Operating Heating Setpoint | °F | Read | |
| AV | 29731 | #HtgStgs | Number of Heating Stages Installed | Read | ||
| AV | 29738 | H1-Runtime | Heating Stage 1 Accumulated Runtime | hours | Read | |
| AV | 29739 | H2-Runtime | Heating Stage 2 Accumulated Runtime | hours | Read | |
| AV | 29740 | H3-Runtime | Heating Stage 3 Accumulated Runtime | hours | Read | |
| AV | 29741 | HWV | Hydronic Heat Valve % Command | % | Read | |
| AV | 29746 | DATTemper-Sp | DAT Tempering Setpoint, 40.0-60.0 °F | °F | Write | |
| AV | 29748 | Econ | Economizer Damper % Command | % | Read | |
| AV | 29753 | EconOAT-SpEn | Economizer OAT Enable Setpoint, 40.0-80.0 °F | °F | Write | |
| AV | 29754 | EconOAEnth-Sp | Economizer Outside Air Enthalpy Setpoint, 10-50 BTU/lb | BTU/lb | Write | |
| AV | 29755 | MATClgLim | Mixed Air Temperature Cooling Limit, 0.0-100.0 °F | °F | Write | |
| AV | 29759 | Econ-MinPos | Economizer Minimum Position Setpoint, 0-100 % | % | Write | |
| AV | 29760 | MAT | Mixed Air Temperature | °F | Read | |
| AV | 29762 | DAH | Discharge Air Humidity | %RH | Read | |
| AV | 29763 | RA-Enth | Return Air Enthalpy | BTU/lb | Read | |
| AV | 29764 | RAT | Return Air Temperature | °F | Read | |
| AV | 29766 | DVentMaxEconPos | Demand Ventilation Maximum Economizer Position | % | Write | |
| AV | 29767 | DVentIAQ-Sp | Demand Ventilation IAQ Setpoint, 0-5,000 ppm | ppm | Write | |
| AV | 29768 | DVentDiff-Sp | Demand Ventilation Differential Setpoint, 0-5,000 ppm | ppm | Write | |
| AV | 29776 | ExFanVFD | Exhaust Fan VFD % Command | % | Read | |
| AV | 29779 | ExF-RunTim | Exhaust Fan Accumulated Runtime | hours | Read | |
| AV | 29780 | Bldg-Sp | Building Pressure Setpoint, -0.25 to 0.25 iwg | iwg | Write | |
| AV | 29781 | BldgPres | Building Static Pressure | iwg | Read | |
| AV | 29782 | EAD-O | Exhaust Damper % Command | % | Read | |
| AV | 29783 | ExDmpPosFanOn | Exhaust Damper Position for Exhaust Fan to Turn ON, 20-99 % | % | Write | |
| AV | 29784 | ExDmpPosFanOff | Exhaust Damper Position for Exhaust Fan to Turn OFF, 20-99 % | % | Write | |
| AV | 29790 | HGR | HGRH Command | % | Read | |
| AV | 29792 | Dehum-SP | Dehumidification Setpoint, 0-100 %RH | %RH | Write | |
| AV | 29795 | MOAFlow-Sp | Min Outside Airflow Setpoint, 0-5,000 CFM | CFM | Write | |
| AV | 29796 | Fr Air | Fresh Air Intake Value | CFM | Read | |
| AV | 29808 | LowSpeedFan-MinPos | Economizer Damper Minimum Position Low Speed Fan, 0-100 % | % | Write | |
| AV | 29823 | MornWRAT-Sp | Morning Warm-up/RAT Setpoint, 50.0-85.0 °F | °F | Write | |
| AV | 29824 | EconDampPos | Economizer Damper Position | % | Read | |
| AV | 29828 | RAH | Return Air Humidity | %RH | Read | |
| AV | 29833 | EVAP-T | Evaporating Temperature Value Circuit 1 | °F | Read | |
| AV | 29885 | LoadShedAdjust | Load Shed Adjust, 0-8 Δ°F | Δ°F | Write | |
| AV | 29889 | Altitude | Altitude, -1,500 to 30,000 feet | feet | Write | |
| AV | 29892 | MornCRAT-Sp | Morning Cool Down/RAT Setpoint, 50-85 °F | °F | Write | |
| AV | 29895 | EarlyStrtPeriod | Early Start Period, 0-120 minutes | minutes | Write | |
| AV | 29897 | DeviceId | Device OID, 0-4194302 | Write | ||
| AV | 29903 | UnoccDehumSP | HGRH UNOCC Humidity Setpoint, 0-100 % | %RH | Write | |
| AV | 29913 | SZVAVMinFanSpd | SZVAV Minimum Fan Speed, 20-67 % | % | Write | |
| AV | 29916 | EconAlrmDly | FDD Economizer Alarm Delay, 1-3,600 seconds | seconds | Write | |
| AV | 29917 | EconPosErr | FDD Economizer Damper Allowed Error, 0-100 % | % | Write | |
| AV | 29918 | EconMinErr | FDD Damper Min Position Tolerance, 0-10 % | % | Write | |
| AV | 29922 | StgClgCmd | Staged Cooling Command | % | Read | |
| AV | 29923 | StgHtgCmd | Staged Heating Command | % | Read | |
| AV | 29924 | PropHtgCmd | Proportional Heating Command | % | Read | |
| AV | 29941 | C1A-Starts | Compressor Number Times ON 1A | Read | ||
| AV | 29942 | C1B-Starts | Compressor Number Times ON 1B | Read | ||
| AV | 29944 | C2A-Starts | Compressor Number Times ON 2A | Read | ||
| AV | 29945 | C2B-ASCDTmr | Anti-Short Cycle Delay Time Remaining 2B | seconds | Read | |
| AV | 29947 | C2BOnTimer | Min. ON Time Remaining 2B | seconds | Read | |
| AV | 29948 | C2B-RunTime | Compressor Accumulated Runtime 2B | hours | Read | |
| AV | 29950 | C2B-Starts | Compressor Number Times ON 2B | Read | ||
| AV | 29964 | ClgCapLim | Cooling Capacity Limit, 0-100 % | % | Write | |
| AV | 29966 | CoastTime | Coast Time, 0-120 minutes | minutes | Write | |
| AV | 29967 | DATCapAlmOffset | DAT Capability Alarm Offset, 1.0-10.0 °F | °F | Write | |
| AV | 29970 | EAHR-T | Exhaust Air Heat Recovery Temp | °F | Read | |
| AV | 29971 | EF-Flow | Exhaust Flow Value | CFM | Read | |
| AV | 29972 | FFILT-DP | Final Filter Differential Pressure | iwg | Read | |
| AV | 29973 | H1-Starts | Heating Number Times ON 1 | Read | ||
| AV | 29974 | H2-Starts | Heating Number Times ON 2 | Read | ||
| AV | 29975 | H3-Starts | Heating Number Times ON 3 | Read | ||
| AV | 29977 | H4-Runtime | Heating Stage 4 Accumulated Runtime | hours | Read | |
| AV | 29979 | H4-Starts | Heating Number Times ON 4 | Read | ||
| AV | 29981 | H5-Runtime | Heating Stage 5 Accumulated Runtime | hours | Read | |
| AV | 29983 | H5-Starts | Heating Number Times ON 5 | Read | ||
| AV | 29985 | H6-Runtime | Heating Stage 6 Accumulated Runtime | hours | Read | |
| AV | 29987 | H6-Starts | Heating Number Times ON 6 | Read | ||
| AV | 29989 | H7-Runtime | Heating Stage 7 Accumulated Runtime | hours | Read | |
| AV | 29991 | H7-Starts | Heating Number Times ON 7 | Read | ||
| AV | 29993 | H8-Runtime | Heating Stage 8 Accumulated Runtime | hours | Read | |
| AV | 30004 | HE-T | Heat Entering Temperature | °F | Read | |
| AV | 30006 | HighSpeedFan-MinPos | Economizer Damper Minimum Position High Speed Fan, 0-100 % | % | Write | |
| AV | 30008 | HRW-O | Heat Recovery Wheel Output | % | Read | |
| AV | 30010 | HtgCapLim | Heating Capacity Limit, 0-100 % | % | Write | |
| AV | 30011 | HtgDATLo-SP | Heating DAT Lower Setpoint, 85.0-134.0 °F | °F | Write | |
| AV | 30012 | HtgDATUp-SP | Heating DAT Upper Setpoint, 85.0-134.0 °F | °F | Write | |
| AV | 30014 | Hum-SP | Humidification Setpoint, 0-100 %RH | %RH | Write | |
| AV | 30017 | ModCompOut | Modulating Compressor Output | % | Read | |
| AV | 30018 | ModCondFan1Out | Modulating Condenser Fan 1 Output | % | Read | |
| AV | 30019 | ModCondFan2Out | Modulating Condenser Fan 2 Output | % | Read | |
| AV | 30020 | ModHtgOut | Modulating Heat Output | % | Read | |
| AV | 30021 | OprHtgDAT-SP | Operating Heating DAT Setpoint | °F | Read | |
| AV | 30022 | PFILT-DP | Pre-Filter Differential Pressure | iwg | Read | |
| AV | 30025 | RAD-O | Return Air Damper Command | % | Read | |
| AV | 30026 | RAD-POS | Return Air Damper Position | % | Read | |
| AV | 30028 | RunContAlmDly | Unit Running Continuously Alarm Delay, 1-99 hours | hours | Write | |
| AV | 30029 | SF-DAT-SpHighThresh | Supply Fan DAT Setpoint High Threshold, 0-100 % | % | Write | |
| AV | 30030 | SF-DAT-SpLowThresh | Supply Fan DAT Setpoint Low Threshold, 0-100 % | % | Write | |
| AV | 30034 | SZVAVClgMinFan | SZVAV Cooling Minimum Fan Speed, 20-67 % | % | Write | |
| AV | 30035 | SZVAVHtgMinFan | SZVAV Heating Minimum Fan Speed, 20-67 % | % | Write | |
| AV | 30038 | UVLight-Rt | UV Light Runtime | hours | Read | |
| AV | 30040 | DLP1 | Discharge Line Pressure 1 | psi | Read | |
| AV | 30041 | DLT1 | Discharge Line Temperature 1 | °F | Read | |
| AV | 30042 | DLP2 | Discharge Line Pressure 2 | psi | Read | |
| AV | 30043 | DLT2 | Discharge Line Temperature 2 | °F | Read | |
| AV | 30044 | DischSuperheat1 | Discharge Superheat 1 | °F | Read | |
| AV | 30045 | DischSuperheat2 | Discharge Superheat 2 | °F | Read | |
| AV | 30046 | SucSuperheat1 | Suction Superheat 1 | °F | Read | |
| AV | 30047 | SucSuperheat2 | Suction Superheat 2 | °F | Read | |
| AV | 30048 | LLSubcool1 | Liquid Line Sub-Cooling 1 | °F | Read | |
| AV | 30049 | LLSubcool2 | Liquid Line Sub-Cooling 2 | °F | Read | |
| AV | 30050 | SatDischTemp1 | Saturated DAT 1 | °F | Read | |
| AV | 30051 | SatDischTemp2 | Saturated DAT 2 | °F | Read | |
| AV | 30052 | SatLLTemp1 | Saturated Liquid Line Temperature 1 | °F | Read | |
| AV | 30053 | SatLLTemp2 | Saturated Liquid Line Temperature 2 | °F | Read | |
| AV | 30054 | SatSucTemp1 | Saturated Suction Temperature 1 | °F | Read | |
| AV | 30055 | SatSucTemp2 | Saturated Suction Temperature 2 | °F | Read | |
| AV | 30056 | H8-Starts | Heating Number Times ON 8 | Read | ||
| AV | 30061 | DehumEvapLowSp | Dehum Evap Low Setpoint | °F | Write | |
| CSV | 29804 | Name | Unit Name | Write | ||
| CSV | 29806 | Serial# | Unit Serial Number | Write | ||
| CSV | 29807 | FirmVer | Firmware Version | Read | ||
| CSV | 29818 | DevName | Device Name | Write | ||
| MV | 29501 | Htg-Type | Heating Control Type | Write | 0=none, 1=gas, 2=electric, 3=hot water, 4=steam | |
| MV | 29503 | ExFType | Exhaust Type | Write | 0=none, 1=barometric, 2=modulating damper, 3=VFD | |
| MV | 29504 | Y1-Tstat | Y1 - Thermostat | Read | 0=OFF, 1=ON | |
| MV | 29505 | Y2-Tstat | Y2 - Thermostat | Read | 0=OFF, 1=ON | |
| MV | 29508 | W1-Tstat | W1 - Thermostat | Read | 0=OFF, 1=ON | |
| MV | 29509 | W2-Tstat | W2 - Thermostat | Read | 0=OFF, 1=ON | |
| MV | 29511 | G-Tstat | G - Thermostat | Read | 0=OFF, 1=ON | |
| MV | 29512 | Occ-Tstat | Occupancy Input | Read | 0=disabled/UNOCC, 1=enabled/OCC | |
| MV | 29514 | Tstat-Only | Thermostat Only Control Enabled | Write | 0=NO, 1=YES | |
| MV | 29515 | OccSrc | Occupancy Input Source | Read | 0=local input, 1=local network sensor, 2=BAS network request, 3=local schedule, 4=temporary occupancy | |
| MV | 29517 | OprOcc | Operational Occupancy | Read | 0=OCC, 1=UNOCC, 2=bypass, 3=standby | |
| MVmin | 29518 | OccMode | Occupancy Mode | Write | 0=schedule, 1=external | |
| MV | 29519 | NetTempOcc | Network Temporary Occupancy Request | Write | 0=false, 1=true | |
| MVmin | 29520 | NetOcc | Network Occupancy Request | Write | 0=OCC, 1=UNOCC, 2=not set | |
| MV | 29523 | ZTSrc | ZT Source | Read | 0=unreliable, 1=local input, 2=network sensor, 3=high priority | |
| MV | 29528 | IAQSrc | IAQ Source | Read | 0=unreliable, 1=local input, 2=network sensor, 3=high priority | |
| MV | 29532 | SHSrc | Space Humidity Source | Read | 0=unreliable, 1=local input, 2=network sensor, 3=high priority | |
| MV | 29534 | OprFanReq | Operating Fan Request | Read | 0=OFF, 1=ON | |
| MV | 29535 | FanReqSrc | Fan Request Source | Read | 0=unreliable, 1=local input, 2=network sensor, 3=high priority | |
| MV | 29536 | NetFanReq | Network Override Fan Request | Write | 0=OFF, 1=ON | |
| MV | 29542 | OATSrc | OAT Source | Read | 0=unreliable, 1=local input, 2=network sensor, 3=high priority | |
| MV | 29548 | OAQSrc | Source of outdoor air CO2 input | Read | 0=unreliable, 1=local input, 2=network sensor, 3=high priority | |
| MVmin | 29550 | Fan-S | Supply Fan Status | Read | 0=OFF/idle, 1=ON/purge, 2=ON/gas valve or limit fault, 3=ON | |
| MV | 29552 | SFVFD1Flt | Supply Fan VFD 1 Fault | Read | 0=normal, 1=alarm | |
| MV | 29557 | APS | Air Proving Switch | Read | 0=OFF, 1=ON | |
| MV | 29563 | Fan | Supply Fan Command | Read | 0=OFF, 1=ON | |
| MV | 29568 | FanOnOcc | Continuous Fan Operation in Occupied Mode | Write | 0=YES, 1=NO | |
| MV | 29575 | Clg-En | Cooling Mode Enabled For Operation | Write | 0=NO, 1=YES | |
| MV | 29577 | Clg-S | Cooling Status | Read | 0=OFF/idle, 1=thermostat cooling, 2=UNOCC cooling, 3=OCC cooling | |
| MV | 29584 | AllCompOff-Econ | All Compressors OFF in Free Cooling | Write | 0=NO, 1=YES | |
| MV | 29611 | C1A | Compressor 1A Command | Read | 0=OFF, 1=ON | |
| MV | 29612 | C1B | Compressor 1B Command | Read | 0=OFF, 1=ON | |
| MV | 29614 | C2A | Compressor 2A Command | Read | 0=OFF, 1=ON | |
| MV | 29615 | C1A-S | Compressor 1A Status | Read | 0=OFF/idle, 1=ON/minimum ON time, 2=ON/normal command, 3=OFF/cooling is disabled | |
| MV | 29616 | C1B-S | Compressor 1B Status | Read | 0=OFF/idle, 1=ON/minimum ON time, 2=ON/normal command, 3=OFF/cooling is disabled | |
| MV | 29618 | C2A-S | Compressor 2A Status | Read | 0=OFF/idle, 1=ON/minimum ON time, 2=ON/normal command, 3=OFF/cooling is disabled | |
| MV | 29619 | C1A-En | Compressor 1A Enabled | Write | 0=YES, 1=NO | |
| MV | 29620 | C1B-En | Compressor 1B Enabled | Write | 0=YES, 1=NO | |
| MV | 29622 | C2A-En | Compressor 2A Enabled | Write | 0=YES, 1=NO | |
| MV | 29639 | COMP1-A | Compressor Safety Chain 1 | Read | 0=normal, 1=alarm | |
| MV | 29640 | COMP2-A | Compressor Safety Chain 2 | Read | 0=normal, 1=alarm | |
| MV | 29643 | COMP1-LO | Compressor Safety Chain Lockout 1 | Read | 0=normal, 1=lockout | |
| MV | 29644 | COMP2-LO | Compressor Safety Chain Lockout 2 | Read | 0=normal, 1=lockout | |
| MV | 29647 | LPS1 | Low Pressure Safety 1 | Read | 0=normal, 1=alarm | |
| MV | 29648 | LPS2 | Low Pressure Safety 2 | Read | 0=normal, 1=alarm | |
| MV | 29651 | LPS1-LO | Low Pressure Lockout 1 | Read | 0=normal, 1=lockout | |
| MV | 29652 | LPS2-LO | Low Pressure Lockout 2 | Read | 0=normal, 1=lockout | |
| MV | 29707 | Htg-En | Heating Mode Enabled For Operation | Write | 0=OFF, 1=ON | |
| MV | 29708 | Htg-S | Heating Status | Read | 0=OFF/idle, 1=ON, 2=SAT tempering, 3=morning warm-up | |
| MV | 29712 | FSHW | Low Temp Water Coil Freeze Stat | Read | 0=normal, 1=alarm | |
| MV | 29724 | HtgUnocc-En | Unoccupied Heating Enabled | Write | 0=NO, 1=YES | |
| MV | 29727 | VAV Box | MZ VAV Box Heat Command | Read | 0=OFF, 1=ON | |
| MV | 29732 | H1 | Heating Stage Command 1 | Read | 0=OFF, 1=ON | |
| MV | 29733 | H2 | Heating Stage Command 2 | Read | 0=OFF, 1=ON | |
| MV | 29734 | H3 | Heating Stage Command 3 | Read | 0=OFF, 1=ON | |
| MV | 29735 | H1-S | Heating Stage 1 Status | Read | 0=OFF/idle, 1=ON/minimum runtime timer, 2=ON/normal command, 3=OFF/heating is disabled | |
| MV | 29736 | H2-S | Heating Stage 2 Status | Read | 0=OFF/idle, 1=ON/minimum runtime timer, 2=ON/normal command, 3=OFF/heating is disabled | |
| MV | 29737 | H3-S | Heating Stage 3 Status | Read | 0=OFF/idle, 1=ON/minimum runtime timer, 2=ON/normal command, 3=OFF/heating is disabled | |
| MV | 29742 | HydReverse | Hydronic Heat Valve Reverse Acting | Write | 0=NO, 1=YES | |
| MV | 29745 | DATTemper-En | DAT Tempering Enable | Write | 0=NO, 1=YES | |
| MV | 29747 | Econ-En | Economizer Enabled For Operation | Write | 0=NO, 1=YES | |
| MV | 29749 | Econ-Free | Economizer Free Cooling Available | Read | 0=NO, 1=YES | |
| MV | 29750 | Econ-S | Economizer Status | Read | 0=disabled, 1=damper not functional, 2=purge, 3=unavailable sensor fault | |
| MV | 29751 | FreeClg-Mode | Free Cooling Current Mode | Read | 0=dry bulb temperature, 1=differential dry bulb temperature, 2=single enthalpy, 3=dual enthalpy, 4=unreliable | |
| MV | 29752 | FreeClg-Sel | Free Cooling Selection | Write | 0=dry bulb temperature, 1=differential dry bulb temperature, 2=single enthalpy, 3=dual enthalpy, 4=unreliable | |
| MV | 29765 | DVent-Mode | Demand Ventilation Mode of Operation | Write | 0=disabled, 1=controlled by IAQ, 2=difference between IAQ and OAQ | |
| MV | 29775 | ExFan | Exhaust Fan Command | Read | 0=OFF, 1=ON | |
| MV | 29777 | ExF-S | Exhaust Return Fan Status | Read | 0=OFF/idle, 1=ON/normal command, 2=OFF/disabled, 3=OFF/VFD fault | |
| MV | 29778 | ExFanVFDFlt | Exhaust Fan VFD Fault | Read | 0=normal, 1=alarm | |
| MV | 29787 | ERV-En | ERV Enabled | Write | 0=NO, 1=YES | |
| MV | 29789 | HGR-En | HGRH Enabled For Operation | Write | 0=none, 1=normal, 2=alternate | |
| MV | 29791 | HGR-S | HGRH Status | Read | 0=OFF/idle, 1=ON/normal command, 2=ON/alternate operation command, 3=OFF/disabled | |
| MV | 29798 | OprSafetyCmd | Operating Safety Command | Read | 0=normal, 1=pressurize, 2=depressurize, 3=purge | |
| MV | 29799 | SafetyCmdSrc | Safety Command Source | Read | 0=unreliable, 1=local input, 2=network sensor, 3=high priority | |
| MV | 29800 | Safety1 | Local Safety Command Input 1 | Read | 0=false, 1=true | |
| MV | 29801 | NetSafety | Network Override Safety Command | Write | 0=false, 1=true | |
| MV | 29802 | SS-S | Safety Switch Status | Read | 0=normal, 1=alarm | |
| MVmin | 29803 | Unit-S | Unit Status | Read | 0=idle, 1=SD alarm, 2=purge command, 3=start-up wizard | |
| MV | 29809 | ExcessOutAirFlt | Excess outside air fault (economizer FDD) | Read | 0=normal, 1=alarm | |
| MV | 29810 | NotEconFlt | Economizer not economizing when conditions suit (FDD) | Read | 0=normal, 1=alarm | |
| MV | 29811 | EconDampFlt | Economizer damper fault (FDD) | Read | 0=normal, 1=alarm | |
| MV | 29812 | EconWhenShouldNotFlt | Economizing when outside air is unsuitable (FDD) | Read | 0=normal, 1=alarm | |
| MV | 29822 | MornW-En | Morning Warm-Up Enabled | Write | 0=NO, 1=YES | |
| MV | 29825 | TempOCC | Temporary Occupancy Input | Write | 0=disable, 1=enable | |
| MV | 29826 | ResetLO | Reset Lockouts | Write | 0=OFF, 1=ON | |
| MV | 29881 | HtgAdapTunEn | Heating Adaptive Tuning Enable | Write | 0=NO, 1=YES | |
| MV | 29882 | ClgAdapTunEn | Cooling Adaptive Tuning Enable | Write | 0=NO, 1=YES | |
| MV | 29883 | LoadShedEnable | Load Shed Active | Write | 0=NO, 1=YES | |
| MV | 29891 | MornC-En | Morning Cool Down Enabled | Write | 0=NO, 1=YES | |
| MV | 29893 | OptStrt-En | Optimal Start Enabled | Write | 0=NO, 1=YES | |
| MVmin | 29896 | UnitEn | Unit Enable | Write | 0=shutdown, 1=enable | |
| MV | 29904 | HGRUnocc-En | HGRH Enabled for UNOCC Operation | Write | 0=NO, 1=YES | |
| MV | 29908 | SZVAVEn | SZ VAV Enabled | Write | 0=OFF, 1=ON | |
| MV | 29910 | ADR-S | Automated Demand Response | Read | 0=NO, 1=YES | |
| MV | 29914 | OffDurUnocc | OFF During UNOCC | Write | 0=NO, 1=YES | |
| MV | 29915 | EconFltDetectEn | Economizer Fault Detection Enabled | Write | 0=disable, 1=enable | |
| MV | 29919 | PIDTunRst | PID Tuning Reset | Write | 0=false, 1=true | |
| MV | 29933 | FrAir-En | Min Outside Air Enabled | Write | 0=disable, 1=enable | |
| MV | 29934 | EncodeType | BACnet Encoding Type | Write | 0=ISO 10646 (UCS-2), 1=ANSI X3.4 (US-ASCII), 2=Microsoft DBCS code page 932 (Japanese Shift JIS), 3=ISO 10646 (UTF-8) | |
| MV | 29935 | CF-1A | Condenser Fan 1A | Read | 0=OFF, 1=ON | |
| MV | 29936 | CF-1B | Condenser Fan 1B | Read | 0=OFF, 1=ON | |
| MV | 29937 | CF-2A | Condenser Fan 2A | Read | 0=OFF, 1=ON | |
| MV | 29938 | CF-2B | Condenser Fan 2B | Read | 0=OFF, 1=ON | |
| MV | 29939 | C2B | Compressor 2B Command | Read | 0=OFF, 1=ON | |
| MV | 29946 | C2B-En | Compressor 2B Enabled | Write | 0=NO, 1=YES | |
| MV | 29949 | C2B-S | Compressor 2B Status | Read | 0=OFF/idle, 1=ON/minimum ON time, 2=ON/normal command, 3=OFF/cooling is disabled | |
| MV | 29965 | Coast-En | Coast Enable | Write | 0=disable, 1=enable | |
| MV | 29968 | DAT-SPconfig | DAT Setpoint Configuration | Write | 0=fixed, 1=OAT reset, 2=supply fan reset, 3=ZT reset, 4=external mode | |
| MVmin | 29969 | DownInOccAlm | Unit Down in OCC Alarm | Read | 0=normal, 1=alarm | |
| MV | 29976 | H4 | Heating Stage Command 4 | Read | 0=OFF, 1=ON | |
| MV | 29978 | H4-S | Heating Stage 4 Status | Read | 0=OFF/idle, 1=ON/minimum ON time, 2=ON/normal command, 3=OFF/heating is disabled | |
| MV | 29980 | H5 | Heating Stage Command 5 | Read | 0=OFF, 1=ON | |
| MV | 29982 | H5-S | Heating Stage 5 Status | Read | 0=OFF/idle, 1=ON/minimum runtime timer, 2=ON/normal command, 3=OFF/heating is disabled | |
| MV | 29984 | H6 | Heating Stage Command 6 | Read | 0=OFF, 1=ON | |
| MV | 29986 | H6-S | Heating Stage 6 Status | Read | 0=OFF/idle, 1=ON/minimum runtime timer, 2=ON/normal command, 3=OFF/heating is disabled | |
| MV | 29988 | H7 | Heating Stage Command 7 | Read | 0=OFF, 1=ON | |
| MV | 29990 | H7-S | Heating Stage 7 Status | Read | 0=OFF/idle, 1=ON/minimum runtime timer, 2=ON/normal command, 3=OFF/heating is disabled | |
| MV | 29992 | H8 | Heating Stage Command 8 | Read | 0=OFF, 1=ON | |
| MV | 29994 | H8-S | Heating Stage 8 Status | Read | 0=OFF/idle, 1=ON/minimum runtime timer, 2=ON/normal command, 3=OFF/heating is disabled | |
| MV | 30005 | HGRB-C | HGRH Bleed Valve Command | Read | 0=OFF, 1=ON | |
| MV | 30007 | HRW-C | Heat Recovery Wheel Command | Read | 0=OFF, 1=ON | |
| MV | 30009 | HRW-S | Heat Recovery Wheel Status | Read | 0=OFF, 1=max cooling, 2=max heating, 3=blocking protection | |
| MV | 30013 | Hum-En | Humidification Enabled | Write | 0=disable, 1=enable | |
| MV | 30015 | LowCoolCapAlm | Insufficient Cooling Capability Alarm | Read | 0=normal, 1=alarm | |
| MV | 30016 | LowHeatCapAlm | Insufficient Heating Capability Alarm | Read | 0=normal, 1=alarm | |
| MV | 30023 | Safety2 | Local Safety Command Input 2 | Read | 0=false, 1=true | |
| MV | 30024 | Safety3 | Local Safety Command Input 3 | Read | 0=false, 1=true | |
| MV | 30027 | RunContAlm | Unit Running Continuously Alarm | Read | 0=normal, 1=alarm | |
| MV | 30031 | SFVFD2Flt | Supply Fan VFD 2 Fault | Read | 0=normal, 1=alarm | |
| MV | 30032 | SMOKE-A | Smoke Detector | Read | 0=normal, 1=alarm | |
| MV | 30033 | SPNoChangeAlm | Setpoint Not Changing Alarm | Read | 0=normal, 1=alarm | |
| MV | 30036 | UVLight-En | UV Light Installed | Write | 0=NO, 1=YES | |
| MV | 30037 | UVLight-Reset | UV Light Runtime Reset | Write | 0=OFF, 1=reset | |
| MV | 30039 | UVLight-Service | UV Light Needs Service | Read | 0=normal, 1=alarm | |
| MV | 30062 | Condensate Alarm | Condensate Alarm | Read | ||
| MV | 30063 | Humidistat | Humidistat | Read | 0=OFF, 1=ON | |
| MV | 29722 | HtgOcc-En | MZVAV Occupied Heating Enabled | Write | 0=NO, 1=YES | |
| MV | 30064 | HtgClgSP-Mode | Heat Cool Setpoint Mode | Write | 0=NO, 1=YES | |
| AV | 30065 | Common-SP | Common Setpoint, 45.0-98.0 °F | °F | Write | |
| AV | 30066 | OprEvapTempSp | Operational Evap Temperature Setpoint | °F | Read | |
| AV | 30067 | OprHGRTempSp | Operational HGRH Temperature Setpoint | °F | Read | |
| MV | 30075 | DemLoadshd | Demand Loadshed | Read | 0=NO, 1=YES | |
| MV | 30079 | SafetySetupNI | Safety Setup Network Input | Write | 0=Normal, 1=Pressurize, 2=Depressurize, 3=Purge, 4=Shutdown | |
| Other | 30000 | MVCriticalActiveEvent | Critical event (active), no description given | Read | ||
| Other | 29999 | MVCriticalInactiveEvent | Critical event (inactive), no description given | Read | ||
| Other | 29998 | MVServicePriorityActiveEvent | Service priority event (active), no description given | Read | ||
| Other | 29997 | MVServicePriorityInactiveEvent | Service priority event (inactive), no description given | Read | ||
| Other | 29996 | MVServiceActiveEvent | Service event (active), no description given | Read | ||
| Other | 29995 | MVServiceInactiveEvent | Service event (inactive), no description given | Read |
No points match these filters.
Object ID lookup: Johnson Controls Premier Rooftop Units 25-50 Ton point IDs by name
AV29521TempOccTimeoutAV29522OprZTAV29524ZTAlarmOffsetAV29525ZTAlarmDelayAV29526NetZTAV29527OprIAQAV29530NetIAQAV29531OprZHAV29533NetSHAV29537OprSSOAV29540NetSSOAV29541OprOATAV29543NetOATAV29544OprOAHAV29545OA-EnthAV29546NetOAHAV29547OprOAQAV29549NetOAQAV29551FanVFDAV29554Fan-RTAV29559FanOffDlyCoolAV29561FanOffDlyHeatAV29564DATAV29565DctPrsAV29566DctPrs-SpAV29567DctShutdownSpAV29576#ClgStgsAV29578MinRtCoolStgAV29581Circ1ClgOATCutoutAV29582Circ2ClgOATCutoutAV29592Freeze-SpAV29604ClgDATUp-SPAV29605ClgDATLo-SPAV29607OprClgDAT-SPAV29608ClgOcc-SpAV29609ClgUnocc-SpAV29610OprClg-SpAV29627C1A-RunTimeAV29628C1B-RunTimeAV29630C2A-RunTimeAV29631C1AOnTimerAV29632C1BOnTimerAV29634C2AOnTimerAV29635C1A-ASCDTmrAV29636C1B-ASCDTmrAV29638C2A-ASCDTmrAV29671SLP-1AV29672SLP-2AV29675LLP-1AV29676LLP-2AV29679SLT-1AV29680SLT-2AV29683LLT-1AV29684LLT-2AV29711HtgOATCutout-SpAV29723HtgOcc-SpAV29725HtgUnocc-SpAV29726OprHtg-SpAV29731#HtgStgsAV29738H1-RuntimeAV29739H2-RuntimeAV29740H3-RuntimeAV29741HWVAV29746DATTemper-SpAV29748EconAV29753EconOAT-SpEnAV29754EconOAEnth-SpAV29755MATClgLimAV29759Econ-MinPosAV29760MATAV29762DAHAV29763RA-EnthAV29764RATAV29766DVentMaxEconPosAV29767DVentIAQ-SpAV29768DVentDiff-SpAV29776ExFanVFDAV29779ExF-RunTimAV29780Bldg-SpAV29781BldgPresAV29782EAD-OAV29783ExDmpPosFanOnAV29784ExDmpPosFanOffAV29790HGRAV29792Dehum-SPAV29795MOAFlow-SpAV29796Fr AirAV29808LowSpeedFan-MinPosAV29823MornWRAT-SpAV29824EconDampPosAV29828RAHAV29833EVAP-TAV29885LoadShedAdjustAV29889AltitudeAV29892MornCRAT-SpAV29895EarlyStrtPeriodAV29897DeviceIdAV29903UnoccDehumSPAV29913SZVAVMinFanSpdAV29916EconAlrmDlyAV29917EconPosErrAV29918EconMinErrAV29922StgClgCmdAV29923StgHtgCmdAV29924PropHtgCmdAV29941C1A-StartsAV29942C1B-StartsAV29944C2A-StartsAV29945C2B-ASCDTmrAV29947C2BOnTimerAV29948C2B-RunTimeAV29950C2B-StartsAV29964ClgCapLimAV29966CoastTimeAV29967DATCapAlmOffsetAV29970EAHR-TAV29971EF-FlowAV29972FFILT-DPAV29973H1-StartsAV29974H2-StartsAV29975H3-StartsAV29977H4-RuntimeAV29979H4-StartsAV29981H5-RuntimeAV29983H5-StartsAV29985H6-RuntimeAV29987H6-StartsAV29989H7-RuntimeAV29991H7-StartsAV29993H8-RuntimeAV30004HE-TAV30006HighSpeedFan-MinPosAV30008HRW-OAV30010HtgCapLimAV30011HtgDATLo-SPAV30012HtgDATUp-SPAV30014Hum-SPAV30017ModCompOutAV30018ModCondFan1OutAV30019ModCondFan2OutAV30020ModHtgOutAV30021OprHtgDAT-SPAV30022PFILT-DPAV30025RAD-OAV30026RAD-POSAV30028RunContAlmDlyAV30029SF-DAT-SpHighThreshAV30030SF-DAT-SpLowThreshAV30034SZVAVClgMinFanAV30035SZVAVHtgMinFanAV30038UVLight-RtAV30040DLP1AV30041DLT1AV30042DLP2AV30043DLT2AV30044DischSuperheat1AV30045DischSuperheat2AV30046SucSuperheat1AV30047SucSuperheat2AV30048LLSubcool1AV30049LLSubcool2AV30050SatDischTemp1AV30051SatDischTemp2AV30052SatLLTemp1AV30053SatLLTemp2AV30054SatSucTemp1AV30055SatSucTemp2AV30056H8-StartsAV30061DehumEvapLowSpCSV29804NameCSV29806Serial#CSV29807FirmVerCSV29818DevNameMV29501Htg-TypeMV29503ExFTypeMV29504Y1-TstatMV29505Y2-TstatMV29508W1-TstatMV29509W2-TstatMV29511G-TstatMV29512Occ-TstatMV29514Tstat-OnlyMV29515OccSrcMV29517OprOccMV29518OccModeMV29519NetTempOccMV29520NetOccMV29523ZTSrcMV29528IAQSrcMV29532SHSrcMV29534OprFanReqMV29535FanReqSrcMV29536NetFanReqMV29542OATSrcMV29548OAQSrcMV29550Fan-SMV29552SFVFD1FltMV29557APSMV29563FanMV29568FanOnOccMV29575Clg-EnMV29577Clg-SMV29584AllCompOff-EconMV29611C1AMV29612C1BMV29614C2AMV29615C1A-SMV29616C1B-SMV29618C2A-SMV29619C1A-EnMV29620C1B-EnMV29622C2A-EnMV29639COMP1-AMV29640COMP2-AMV29643COMP1-LOMV29644COMP2-LOMV29647LPS1MV29648LPS2MV29651LPS1-LOMV29652LPS2-LOMV29707Htg-EnMV29708Htg-SMV29712FSHWMV29724HtgUnocc-EnMV29727VAV BoxMV29732H1MV29733H2MV29734H3MV29735H1-SMV29736H2-SMV29737H3-SMV29742HydReverseMV29745DATTemper-EnMV29747Econ-EnMV29749Econ-FreeMV29750Econ-SMV29751FreeClg-ModeMV29752FreeClg-SelMV29765DVent-ModeMV29775ExFanMV29777ExF-SMV29778ExFanVFDFltMV29787ERV-EnMV29789HGR-EnMV29791HGR-SMV29798OprSafetyCmdMV29799SafetyCmdSrcMV29800Safety1MV29801NetSafetyMV29802SS-SMV29803Unit-SMV29809ExcessOutAirFltMV29810NotEconFltMV29811EconDampFltMV29812EconWhenShouldNotFltMV29822MornW-EnMV29825TempOCCMV29826ResetLOMV29881HtgAdapTunEnMV29882ClgAdapTunEnMV29883LoadShedEnableMV29891MornC-EnMV29893OptStrt-EnMV29896UnitEnMV29904HGRUnocc-EnMV29908SZVAVEnMV29910ADR-SMV29914OffDurUnoccMV29915EconFltDetectEnMV29919PIDTunRstMV29933FrAir-EnMV29934EncodeTypeMV29935CF-1AMV29936CF-1BMV29937CF-2AMV29938CF-2BMV29939C2BMV29946C2B-EnMV29949C2B-SMV29965Coast-EnMV29968DAT-SPconfigMV29969DownInOccAlmMV29976H4MV29978H4-SMV29980H5MV29982H5-SMV29984H6MV29986H6-SMV29988H7MV29990H7-SMV29992H8MV29994H8-SMV30005HGRB-CMV30007HRW-CMV30009HRW-SMV30013Hum-EnMV30015LowCoolCapAlmMV30016LowHeatCapAlmMV30023Safety2MV30024Safety3MV30027RunContAlmMV30031SFVFD2FltMV30032SMOKE-AMV30033SPNoChangeAlmMV30036UVLight-EnMV30037UVLight-ResetMV30039UVLight-ServiceMV30062Condensate AlarmMV30063HumidistatMV29722HtgOcc-EnMV30064HtgClgSP-ModeAV30065Common-SPAV30066OprEvapTempSpAV30067OprHGRTempSpMV30075DemLoadshdMV30079SafetySetupNI
Integration notes
- Taken from Table 32 (BACnet Points List) of the 25-50 ton Premier start-up and operation guide; the table has only AV, MV and CSV objects.
- Multistate states are printed from 0 in the table. BACnet multistate values start at 1, so the device may report the printed number + 1; check the state text on discovery.
- Enable polarity is not consistent: FanOnOcc and C1A-En/C1B-En/C2A-En print 0 = YES, 1 = NO, while C2B-En and most other enables print 0 = NO, 1 = YES.
- The last six rows (MVCritical, MVServicePriority and MVService Active/Inactive Event, instances 29995-30000) give object type "0" and no description; they are listed here as type Other.
- Points for heat stages 4-8, the second circuit, exhaust, energy recovery wheel, HGRH, humidification and UV lights only carry data on units with those options.
- Writable setpoint ranges from the table are in the descriptions.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Premier Rooftop Units 25-50 Ton and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls Premier Rooftop Units 25-50 Ton
How many BACnet points does the Johnson Controls Premier Rooftop Units 25-50 Ton have?
This list has 322 BACnet objects: 172 analog values, 140 multi-state values, 4 characterstring values, 6 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls Premier Rooftop Units 25-50 Ton BACnet points are writable?
115 of the 322 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls Premier Rooftop Units 25-50 Ton BACnet documentation?
The source is Premier Rooftop Units 25-50 Tons Start-Up & Operation Guide (5586996-JSG-A-520), revision 2020-05, published free by Johnson Controls at https://docs.johnsoncontrols.com/ductedsystems/api/khub/documents/n3TN8DoIvhMOr21N5iDrIg/content.
What are the minimum BACnet points to integrate the Johnson Controls Premier Rooftop Units 25-50 Ton?
Start with MV 29896 UnitEn (Unit enable (0 = shutdown, 1 = enable)); MV 29520 NetOcc (BAS occupancy: occupied, unoccupied or not set); MV 29518 OccMode (Must be External for BAS occupancy); AV 29608 ClgOcc-Sp (Occupied cooling setpoint, 45-98 °F); AV 29723 HtgOcc-Sp (Occupied heating setpoint, 40-85 °F); MV 29803 Unit-S (Unit state: idle, SD alarm, purge, start-up wizard); MV 29550 Fan-S (Fan state: off/idle, on/purge, on/valve or limit fault, on); AV 29522 OprZT (Zone temperature in use); AV 29564 DAT (Discharge air temperature); MV 29969 DownInOccAlm (Unit down during occupied mode (1 = alarm)).
How do I enable BMS control of the Johnson Controls Premier Rooftop Units 25-50 Ton?
UnitEn (MV 29896) enables or shuts down the unit; the default is Enable. With OccMode (MV 29518) at Schedule the unit follows its internal schedule. With OccMode at External, an occupied command from the BAS (NetOcc, MV 29520), a zone sensor override or the hard-wired occupancy input makes the unit occupied.
Does the Johnson Controls Premier Rooftop Units 25-50 Ton need a BACnet heartbeat or have a communication timeout?
No unit-level heartbeat point is listed. A zone temperature written by the BAS times out after 15 minutes without an update; the controller then falls back to a NetSensor, the wired zone sensor, then return air temperature.
Can the BMS supply sensor values to the Johnson Controls Premier Rooftop Units 25-50 Ton?
Write zone temperature to NetZT (AV 29526), setpoint offset to NetSSO (AV 29540), zone humidity to NetSH (AV 29533), indoor CO2 to NetIAQ (AV 29530), and outdoor air temperature, humidity and CO2 to NetOAT, NetOAH and NetOAQ. A BAS zone temperature has top priority over local sensors. ZTSrc, IAQSrc, SHSrc and OATSrc show which source is in use.
How do I check these points on the real Premier Rooftop Units 25-50 Ton?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Refrigerated display case controller
Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)
PENN / Johnson Controls MR5 Series (MR534) panel-mount controllers for refrigerated display cases, with the ADPT-MR5-RS485 adapter for BACnet MS/TP or Verasys.
Also known as: MR5, MR534, MR534AFDV, MR534AFDN, PENN MR5, ADPT-MR5-RS485, LIT-12013019, JCI refrigeration case controller - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Room pressure controller (isolation room)
Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-1655 room pressure controllers for isolation rooms, labs and cleanrooms, with optional anteroom and flow inputs.
Also known as: FMS-1655, FMS1655, Triatek FMS-1655, Triatek room pressure controller, JCI room pressure controller, LIT-12013120 - Room pressure controller (critical environment)
Johnson Controls Triatek FMS-2000C Critical Environment Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000C critical environment controllers for isolation rooms, labs and cleanrooms (successor of the FMS-1655).
Also known as: FMS-2000C, FMS2000C, FMS-2000, Triatek FMS-2000C, LIT-12013504, JCI critical environment controller - Room pressure monitor (critical environment)
Johnson Controls Triatek FMS-2000M Critical Environment Monitor (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000M critical environment monitors with one to four differential pressure sensors (models FMS2M-Bx1x to Bx4x).
Also known as: FMS-2000M, FMS2000M, Triatek FMS-2000M, FMS2M, FMS2M-Bx1x, FMS2M-Bx2x, FMS2M-Bx3x, FMS2M-Bx4x, LIT-12013580 - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Bypass damper controller (Verasys zoning)
Johnson Controls Verasys BYP200 Bypass Controller
Verasys BYP200 bypass damper controllers that hold duct static pressure in a zoning system.
Also known as: BYP200, Verasys bypass controller - General purpose I/O controller (Verasys)
Johnson Controls Verasys generic IO controller
Verasys generic IO controllers with digital and analog inputs, outputs, NetSensors and energy meters on the system bus.
Also known as: Verasys generic IO, Verasys IO controller, Verasys GIO - Rooftop unit controller (Smart Equipment)
Johnson Controls Verasys SSE system bus (Smart Equipment rooftop board)
Rooftop units with the Simplicity SE / Smart Equipment (SSE) control board connected to a Verasys system bus.
Also known as: SSE, Simplicity SE, Verasys SSE - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC1000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC1000 Constant Volume Controller.
Also known as: VAC1000, Verasys VAC1000, Verasys constant volume controller - Lighting controller (Verasys)
Johnson Controls Verasys VAC1001 Lighting Controller
Verasys VAC1001 lighting controllers with up to 9 lighting circuits grouped into zones.
Also known as: VAC1001, Verasys lighting controller - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC3000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC3000 Constant Volume Controller.
Also known as: VAC3000, Verasys VAC3000, Verasys constant volume controller, Verasys CV controller - VAV / zone damper controller (Verasys)
Johnson Controls Verasys Zone Equipment Controller (ZEC)
Verasys Zone Equipment Controllers serving zone dampers and VAV boxes in a Verasys zoning system.
Also known as: ZEC, Verasys ZEC, Zone Equipment Controller - Rooftop unit controller (Verasys zoning)
Johnson Controls Verasys Zoning RTU (rooftop unit on the Verasys system bus)
Rooftop units integrated as the air source of a Verasys zoning system.
Also known as: Verasys Zoning RTU, Verasys RTU, Verasys zoning rooftop - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771 - Zoning system coordinator
Johnson Controls VZC100 Verasys Zone Coordinator
Verasys VZC100 zone coordinators that run a zoned rooftop system (zone voting, duct pressure and discharge air resets).
Also known as: VZC100, Verasys Zone Coordinator
Source: Premier Rooftop Units 25-50 Tons Start-Up & Operation Guide · 5586996-JSG-A-520 · rev. 2020-05. Object names, instances and units are reproduced as published; descriptions are our own.