Boiler plant sequencer · BACnet points list
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet points list
Updated 28 October 2026
The ModSync SE sequences up to eight hydronic boilers, and Fulton's N54 ProtoNode publishes its data as one flat list of 164 objects. Plant points cover enable, setpoint source and value, supply/return temperatures and the alarm code; each boiler then has a 12-point block of status, temperature and firing rate, followed by optional valve, pump and pressure points.
This page lists 164 BACnet objects for the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.
- Manufacturer
- Fulton
- Model
- Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
- Equipment
- Boiler plant sequencer
- Equipment type
- Boilers & water heaters
- BACnet objects
- 164 (11 writable)
- Transport
- —
- Firmware
- ModSync SE 6.6.1.X
- Also known as
- ModSync, ModSync SE, Fulton ModSync, ModSync sequencer, N54 ProtoNode
Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.
BMS integration notes: Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
Enable the plant with Remote Enable/Disable, set ModSync Setpoint Mode to BMS and write the supply setpoint to BMS Setpoint Input. Read back the active ModSync setpoint, supply temperature, each boiler's run and alarm status and the ModSync alarm code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 7 | Remote Enable/Disable | Plant enable (1 = enable) | Write |
| AV 9 | BMS Setpoint Input (Note 2) | Supply setpoint from the BMS, °F | Write |
| AV 10 | ModSync Setpoint Mode | Must be 2 = BMS to use the BMS setpoint | Write |
| BI 16 | Boiler 1 Run Status | Boiler 1 running (repeat per boiler) | Read |
| AI 11 | ModSync Setpoint | Active plant setpoint, °F | Read |
| AV 3 | Supply Temperature | System supply water temperature, °F | Write |
| AI 22 | Boiler 1 Firing Rate | Boiler 1 firing rate, % (repeat per boiler) | Read |
| BI 17 | Boiler 1 Alarm Status | Boiler 1 alarm (repeat per boiler) | Read |
| AI 12 | ModSync Alarm Code | Plant alarm code from Fulton's alarm chart | Read |
Enable & remote start
BV 7 Remote Enable/Disable enables the plant from the BMS. For a BMS setpoint, set AV 10 ModSync Setpoint Mode = 2 (BMS) and write AV 9 BMS Setpoint Input; AV 9 is an optional point that has to be enabled at the ModSync.
Sensors & values from the BMS
Outdoor air (AV 2), return (AV 4), differential (AV 5) and the system pressures (AV 149-151) are read/write analog values, available when the matching option is enabled at the ModSync. The sheet does not say when the BMS must write them.
Network setup
- Object IDs 1-164 are fixed; boiler 1 data is 13-24, each further boiler adds 12 (boiler 8 = 97-108).
- The sheet gives no device instance, MAC address or baud rate; those are set on the ProtoNode gateway.
Watch out for
- Points marked (Note 2) stay inactive unless the option is enabled at the ModSync.
- Status, Lead Lag Position and alarm codes are analog values carrying a code; see the states.
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Lead Boiler Position | Which boiler is lead, 0-8 | Read | ||
| AV | 2 | Outdoor Air Temperature (Note 2) | Outdoor air temperature (optional) | °F | Write | |
| AVmin | 3 | Supply Temperature | System supply temperature | °F | Write | |
| AV | 4 | Return Temperature (Note 2) | System return temperature (optional) | °F | Write | |
| AV | 5 | Differential Temperature (Note 2) | Supply/return differential (optional) | °F | Write | |
| BI | 6 | Building Mode | Occupied or unoccupied | Read | 0=Unoccupied, 1=Occupied | |
| BVmin | 7 | Remote Enable/Disable | Plant enable from the BMS | Write | 0=Disable, 1=Enable | |
| BI | 8 | Domestic Hot Water Priority | DHW priority active | Read | 0=Disabled, 1=Enabled | |
| AVmin | 9 | BMS Setpoint Input (Note 2) | Supply setpoint written by the BMS | °F | Write | |
| AVmin | 10 | ModSync Setpoint Mode | Setpoint source selection | Write | 0=ModSync, 1=Remote SP, 2=BMS, 3=Manual | |
| AImin | 11 | ModSync Setpoint | Active plant setpoint | °F | Read | |
| AImin | 12 | ModSync Alarm Code | Plant alarm code (see Fulton alarm chart) | Read | ||
| BI | 13 | Boiler 1 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 14 | Boiler 1 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 15 | Boiler 1 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BImin | 16 | Boiler 1 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BImin | 17 | Boiler 1 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 18 | Boiler 1 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 19 | Boiler 1 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 20 | Boiler 1 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 21 | Boiler 1 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AImin | 22 | Boiler 1 Firing Rate | Boiler firing rate | % | Read | |
| AI | 23 | Boiler 1 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 24 | Boiler 1 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 25 | Boiler 2 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 26 | Boiler 2 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 27 | Boiler 2 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 28 | Boiler 2 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 29 | Boiler 2 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 30 | Boiler 2 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 31 | Boiler 2 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 32 | Boiler 2 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 33 | Boiler 2 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 34 | Boiler 2 Firing Rate | Boiler firing rate | % | Read | |
| AI | 35 | Boiler 2 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 36 | Boiler 2 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 37 | Boiler 3 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 38 | Boiler 3 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 39 | Boiler 3 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 40 | Boiler 3 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 41 | Boiler 3 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 42 | Boiler 3 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 43 | Boiler 3 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 44 | Boiler 3 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 45 | Boiler 3 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 46 | Boiler 3 Firing Rate | Boiler firing rate | % | Read | |
| AI | 47 | Boiler 3 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 48 | Boiler 3 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 49 | Boiler 4 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 50 | Boiler 4 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 51 | Boiler 4 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 52 | Boiler 4 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 53 | Boiler 4 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 54 | Boiler 4 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 55 | Boiler 4 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 56 | Boiler 4 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 57 | Boiler 4 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 58 | Boiler 4 Firing Rate | Boiler firing rate | % | Read | |
| AI | 59 | Boiler 4 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 60 | Boiler 4 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 61 | Boiler 5 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 62 | Boiler 5 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 63 | Boiler 5 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 64 | Boiler 5 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 65 | Boiler 5 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 66 | Boiler 5 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 67 | Boiler 5 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 68 | Boiler 5 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 69 | Boiler 5 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 70 | Boiler 5 Firing Rate | Boiler firing rate | % | Read | |
| AI | 71 | Boiler 5 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 72 | Boiler 5 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 73 | Boiler 6 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 74 | Boiler 6 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 75 | Boiler 6 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 76 | Boiler 6 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 77 | Boiler 6 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 78 | Boiler 6 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 79 | Boiler 6 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 80 | Boiler 6 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 81 | Boiler 6 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 82 | Boiler 6 Firing Rate | Boiler firing rate | % | Read | |
| AI | 83 | Boiler 6 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 84 | Boiler 6 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 85 | Boiler 7 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 86 | Boiler 7 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 87 | Boiler 7 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 88 | Boiler 7 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 89 | Boiler 7 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 90 | Boiler 7 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 91 | Boiler 7 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 92 | Boiler 7 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 93 | Boiler 7 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 94 | Boiler 7 Firing Rate | Boiler firing rate | % | Read | |
| AI | 95 | Boiler 7 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 96 | Boiler 7 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 97 | Boiler 8 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 98 | Boiler 8 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 99 | Boiler 8 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 100 | Boiler 8 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 101 | Boiler 8 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 102 | Boiler 8 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 103 | Boiler 8 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 104 | Boiler 8 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 105 | Boiler 8 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 106 | Boiler 8 Firing Rate | Boiler firing rate | % | Read | |
| AI | 107 | Boiler 8 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 108 | Boiler 8 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 109 | Boiler 1 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 110 | Boiler 2 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 111 | Boiler 3 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 112 | Boiler 4 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 113 | Boiler 5 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 114 | Boiler 6 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 115 | Boiler 7 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 116 | Boiler 8 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 117 | Boiler 1 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 118 | Boiler 2 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 119 | Boiler 3 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 120 | Boiler 4 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 121 | Boiler 5 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 122 | Boiler 6 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 123 | Boiler 7 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 124 | Boiler 8 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 125 | Boiler 1 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 126 | Boiler 2 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 127 | Boiler 3 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 128 | Boiler 4 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 129 | Boiler 5 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 130 | Boiler 6 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 131 | Boiler 7 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 132 | Boiler 8 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 133 | Boiler 1 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 134 | Boiler 2 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 135 | Boiler 3 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 136 | Boiler 4 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 137 | Boiler 5 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 138 | Boiler 6 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 139 | Boiler 7 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 140 | Boiler 8 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| AI | 141 | Boiler 1 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 142 | Boiler 2 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 143 | Boiler 3 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 144 | Boiler 4 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 145 | Boiler 5 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 146 | Boiler 6 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 147 | Boiler 7 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 148 | Boiler 8 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AV | 149 | Supply Pressure (Note 2) | System supply pressure, 0-200 | psi | Write | |
| AV | 150 | Return Pressure (Note 2) | System return pressure, 0-200 | psi | Write | |
| AV | 151 | Differential Pressure (Note 2) | System differential pressure, 0-200 | psi | Write | |
| AV | 152 | Differential Setpoint (Note 2) | Differential setpoint; temperature or pressure per ModSync | Write | ||
| AI | 153 | System Pump 1 Status (Note 2) | System pump state | Read | 0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm | |
| AI | 154 | System Pump 2 Status (Note 2) | System pump state | Read | 0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm | |
| AI | 155 | System Pump 3 Status (Note 2) | System pump state | Read | 0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm | |
| AI | 156 | System Pump 4 Status (Note 2) | System pump state | Read | 0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm | |
| AI | 157 | System Pump 1 Speed (Note 2) | System pump speed | % | Read | |
| AI | 158 | System Pump 2 Speed (Note 2) | System pump speed | % | Read | |
| AI | 159 | System Pump 3 Speed (Note 2) | System pump speed | % | Read | |
| AI | 160 | System Pump 4 Speed (Note 2) | System pump speed | % | Read | |
| AI | 161 | System Pump 1 Lead Lag Position (Note 2) | System pump lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3 | |
| AI | 162 | System Pump 2 Lead Lag Position (Note 2) | System pump lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3 | |
| AI | 163 | System Pump 3 Lead Lag Position (Note 2) | System pump lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3 | |
| AI | 164 | System Pump 4 Lead Lag Position (Note 2) | System pump lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3 |
No points match these filters.
Object ID lookup: Fulton Hydronic ModSync SE v6.6.1.X point IDs by name
AI1Lead Boiler PositionAV2Outdoor Air Temperature (Note 2)AV3Supply TemperatureAV4Return Temperature (Note 2)AV5Differential Temperature (Note 2)BI6Building ModeBV7Remote Enable/DisableBI8Domestic Hot Water PriorityAV9BMS Setpoint Input (Note 2)AV10ModSync Setpoint ModeAI11ModSync SetpointAI12ModSync Alarm CodeBI13Boiler 1 Local/Remote StatusBI14Boiler 1 ModSync Enable/DisableBI15Boiler 1 Heat DemandBI16Boiler 1 Run StatusBI17Boiler 1 Alarm StatusBI18Boiler 1 Current Fuel (Note 3)AI19Boiler 1 StatusAI20Boiler 1 Lead Lag PositionAI21Boiler 1 Outlet TemperatureAI22Boiler 1 Firing RateAI23Boiler 1 ModSync CyclesAI24Boiler 1 ModSync Run HoursBI25Boiler 2 Local/Remote StatusBI26Boiler 2 ModSync Enable/DisableBI27Boiler 2 Heat DemandBI28Boiler 2 Run StatusBI29Boiler 2 Alarm StatusBI30Boiler 2 Current Fuel (Note 3)AI31Boiler 2 StatusAI32Boiler 2 Lead Lag PositionAI33Boiler 2 Outlet TemperatureAI34Boiler 2 Firing RateAI35Boiler 2 ModSync CyclesAI36Boiler 2 ModSync Run HoursBI37Boiler 3 Local/Remote StatusBI38Boiler 3 ModSync Enable/DisableBI39Boiler 3 Heat DemandBI40Boiler 3 Run StatusBI41Boiler 3 Alarm StatusBI42Boiler 3 Current Fuel (Note 3)AI43Boiler 3 StatusAI44Boiler 3 Lead Lag PositionAI45Boiler 3 Outlet TemperatureAI46Boiler 3 Firing RateAI47Boiler 3 ModSync CyclesAI48Boiler 3 ModSync Run HoursBI49Boiler 4 Local/Remote StatusBI50Boiler 4 ModSync Enable/DisableBI51Boiler 4 Heat DemandBI52Boiler 4 Run StatusBI53Boiler 4 Alarm StatusBI54Boiler 4 Current Fuel (Note 3)AI55Boiler 4 StatusAI56Boiler 4 Lead Lag PositionAI57Boiler 4 Outlet TemperatureAI58Boiler 4 Firing RateAI59Boiler 4 ModSync CyclesAI60Boiler 4 ModSync Run HoursBI61Boiler 5 Local/Remote StatusBI62Boiler 5 ModSync Enable/DisableBI63Boiler 5 Heat DemandBI64Boiler 5 Run StatusBI65Boiler 5 Alarm StatusBI66Boiler 5 Current Fuel (Note 3)AI67Boiler 5 StatusAI68Boiler 5 Lead Lag PositionAI69Boiler 5 Outlet TemperatureAI70Boiler 5 Firing RateAI71Boiler 5 ModSync CyclesAI72Boiler 5 ModSync Run HoursBI73Boiler 6 Local/Remote StatusBI74Boiler 6 ModSync Enable/DisableBI75Boiler 6 Heat DemandBI76Boiler 6 Run StatusBI77Boiler 6 Alarm StatusBI78Boiler 6 Current Fuel (Note 3)AI79Boiler 6 StatusAI80Boiler 6 Lead Lag PositionAI81Boiler 6 Outlet TemperatureAI82Boiler 6 Firing RateAI83Boiler 6 ModSync CyclesAI84Boiler 6 ModSync Run HoursBI85Boiler 7 Local/Remote StatusBI86Boiler 7 ModSync Enable/DisableBI87Boiler 7 Heat DemandBI88Boiler 7 Run StatusBI89Boiler 7 Alarm StatusBI90Boiler 7 Current Fuel (Note 3)AI91Boiler 7 StatusAI92Boiler 7 Lead Lag PositionAI93Boiler 7 Outlet TemperatureAI94Boiler 7 Firing RateAI95Boiler 7 ModSync CyclesAI96Boiler 7 ModSync Run HoursBI97Boiler 8 Local/Remote StatusBI98Boiler 8 ModSync Enable/DisableBI99Boiler 8 Heat DemandBI100Boiler 8 Run StatusBI101Boiler 8 Alarm StatusBI102Boiler 8 Current Fuel (Note 3)AI103Boiler 8 StatusAI104Boiler 8 Lead Lag PositionAI105Boiler 8 Outlet TemperatureAI106Boiler 8 Firing RateAI107Boiler 8 ModSync CyclesAI108Boiler 8 ModSync Run HoursBI109Boiler 1 Isolation Valve Command (Note 2)BI110Boiler 2 Isolation Valve Command (Note 2)BI111Boiler 3 Isolation Valve Command (Note 2)BI112Boiler 4 Isolation Valve Command (Note 2)BI113Boiler 5 Isolation Valve Command (Note 2)BI114Boiler 6 Isolation Valve Command (Note 2)BI115Boiler 7 Isolation Valve Command (Note 2)BI116Boiler 8 Isolation Valve Command (Note 2)BI117Boiler 1 Isolation Valve Status Input (Note 2)BI118Boiler 2 Isolation Valve Status Input (Note 2)BI119Boiler 3 Isolation Valve Status Input (Note 2)BI120Boiler 4 Isolation Valve Status Input (Note 2)BI121Boiler 5 Isolation Valve Status Input (Note 2)BI122Boiler 6 Isolation Valve Status Input (Note 2)BI123Boiler 7 Isolation Valve Status Input (Note 2)BI124Boiler 8 Isolation Valve Status Input (Note 2)BI125Boiler 1 Pump Command (Note 2)BI126Boiler 2 Pump Command (Note 2)BI127Boiler 3 Pump Command (Note 2)BI128Boiler 4 Pump Command (Note 2)BI129Boiler 5 Pump Command (Note 2)BI130Boiler 6 Pump Command (Note 2)BI131Boiler 7 Pump Command (Note 2)BI132Boiler 8 Pump Command (Note 2)BI133Boiler 1 Pump Status Input (Note 2)BI134Boiler 2 Pump Status Input (Note 2)BI135Boiler 3 Pump Status Input (Note 2)BI136Boiler 4 Pump Status Input (Note 2)BI137Boiler 5 Pump Status Input (Note 2)BI138Boiler 6 Pump Status Input (Note 2)BI139Boiler 7 Pump Status Input (Note 2)BI140Boiler 8 Pump Status Input (Note 2)AI141Boiler 1 Pump Speed (Note 2)AI142Boiler 2 Pump Speed (Note 2)AI143Boiler 3 Pump Speed (Note 2)AI144Boiler 4 Pump Speed (Note 2)AI145Boiler 5 Pump Speed (Note 2)AI146Boiler 6 Pump Speed (Note 2)AI147Boiler 7 Pump Speed (Note 2)AI148Boiler 8 Pump Speed (Note 2)AV149Supply Pressure (Note 2)AV150Return Pressure (Note 2)AV151Differential Pressure (Note 2)AV152Differential Setpoint (Note 2)AI153System Pump 1 Status (Note 2)AI154System Pump 2 Status (Note 2)AI155System Pump 3 Status (Note 2)AI156System Pump 4 Status (Note 2)AI157System Pump 1 Speed (Note 2)AI158System Pump 2 Speed (Note 2)AI159System Pump 3 Speed (Note 2)AI160System Pump 4 Speed (Note 2)AI161System Pump 1 Lead Lag Position (Note 2)AI162System Pump 2 Lead Lag Position (Note 2)AI163System Pump 3 Lead Lag Position (Note 2)AI164System Pump 4 Lead Lag Position (Note 2)
Integration notes
- Object IDs are fixed (1-164) and do not depend on boiler addresses.
- The sheet does not say which BACnet transport the gateway is set to; ProtoNode gateways are normally configured for BACnet IP or BACnet MS/TP.
- Points marked (Note 2) only work if the matching option is enabled at the ModSync.
- Current Fuel points apply only to boilers with LMV burner controls.
- Differential Setpoint is a temperature or a pressure, depending on the selection at the ModSync.
- Per-boiler blocks: boiler 1 = 13-24, boiler 2 = 25-36 ... boiler 8 = 97-108.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
How many BACnet points does the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) have?
This list has 164 BACnet objects: 71 analog inputs, 10 analog values, 82 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet points are writable?
11 of the 164 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet documentation?
The source is Hydronic ModSync SE Version 6.6.1.X - Fulton N54 ProtoNode BACnet Network Addressing, published free by Fulton at https://fulton.com/app/uploads/2021/02/ModSync-SE-V661X-BACnet.pdf.
What are the minimum BACnet points to integrate the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?
Start with BV 7 Remote Enable/Disable (Plant enable (1 = enable)); AV 9 BMS Setpoint Input (Note 2) (Supply setpoint from the BMS, °F); AV 10 ModSync Setpoint Mode (Must be 2 = BMS to use the BMS setpoint); BI 16 Boiler 1 Run Status (Boiler 1 running (repeat per boiler)); AI 11 ModSync Setpoint (Active plant setpoint, °F); AV 3 Supply Temperature (System supply water temperature, °F); AI 22 Boiler 1 Firing Rate (Boiler 1 firing rate, % (repeat per boiler)); BI 17 Boiler 1 Alarm Status (Boiler 1 alarm (repeat per boiler)); AI 12 ModSync Alarm Code (Plant alarm code from Fulton's alarm chart).
How do I enable BMS control of the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?
BV 7 Remote Enable/Disable enables the plant from the BMS. For a BMS setpoint, set AV 10 ModSync Setpoint Mode = 2 (BMS) and write AV 9 BMS Setpoint Input; AV 9 is an optional point that has to be enabled at the ModSync.
Can the BMS supply sensor values to the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?
Outdoor air (AV 2), return (AV 4), differential (AV 5) and the system pressures (AV 149-151) are read/write analog values, available when the matching option is enabled at the ModSync. The sheet does not say when the BMS must write them.
How do I check these points on the real Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Fulton BACnet points lists
- Boiler burner control gateway
Fulton Boiler with Siemens LMV3 (N54 ProtoNode)
Fulton boilers with a Siemens LMV3 burner management control, read through Fulton's N54 ProtoNode gateway.
Also known as: LMV3, LMV 3, Siemens LMV3, N54 ProtoNode, Fulton ProtoNode - Boiler burner control gateway
Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)
Fulton hydronic boilers with a Siemens LMV3 burner control and a Yokogawa UT32A temperature controller, read through the N54 ProtoNode.
Also known as: LMV3, Siemens LMV3, Yokogawa UT32A, UT32A, N54 ProtoNode - Boiler controller gateway
Fulton Hydronic SOLA Boiler (N54 ProtoNode)
Fulton hydronic boilers with the SOLA burner control, one block of objects per boiler on the N54 ProtoNode.
Also known as: SOLA, Fulton SOLA, Honeywell SOLA, N54 ProtoNode - Boiler plant controller gateway
Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)
The SOLA lead/lag master of a group of Fulton hydronic boilers (up to 8 slaves), read through the N54 ProtoNode.
Also known as: SOLA Master, Fulton SOLA lead lag, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) 750-2000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Single (N54 ProtoNode)
Fulton Endura (EDR) 750-2000 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura XE (EXE) 399-750 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Single (N54 ProtoNode)
Fulton Endura XE (EXE) 399-750 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) ZE lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Single (N54 ProtoNode)
Fulton Endura (EDR) ZE boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 (N54 ProtoNode)
Fulton hydronic boilers run by the PURE control (the file name points to Endura+ EDR+ 2500-6000 MBH sizes), read through the N54 ProtoNode.
Also known as: PURE, Fulton PURE, Endura+, EDR+, Endura Plus, Hydronic PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura+ (EDR+) 2500-6000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura+, EDR+, Endura Plus, EDR+ 2500, EDR+ 6000, Fulton PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton VSRT steam boiler lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)
Fulton VSRT steam boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE, Fulton PURE, N54 ProtoNode - Boiler burner control
Fulton Siemens LMV36 with BACnet Interface
Fulton boilers with a Siemens LMV36 burner control on a BACnet interface.
Also known as: LMV36, Siemens LMV36, LMV3, Fulton LMV36 - Steam boiler burner control
Fulton Siemens LMV5 Steam Boiler with BACnet Interface
Fulton steam boilers whose Siemens LMV5 burner management is given a BACnet interface (standard configurations).
Also known as: LMV5, Siemens LMV5, LMV52, Fulton LMV5 - Steam boiler plant sequencer
Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)
Fulton ModSync SE steam boiler sequencer (version 6.6.1.0) managing up to 8 steam boilers, read through a Sierra Monitor ProtoNode.
Also known as: ModSync SE, ModSync, Fulton ModSync steam, ProtoNode
Source: Hydronic ModSync SE Version 6.6.1.X - Fulton N54 ProtoNode BACnet Network Addressing. Object names, instances and units are reproduced as published; descriptions are our own.