Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet points list
Updated 28 October 2026
The SSB boilers reach a BMS through a ProtoNode FPC-N38, which reads the D_Platform boiler control over a serial Modbus RTU link and serves BACnet MS/TP or BACnet IP (Metasys N2 and Modbus TCP also selectable). The list has 147 objects: cascade/system values, per-boiler and per-burner status, temperatures, power level, flow, fan speed, burn hours and error data for up to four boilers. Only the reset-curve, warm weather shutdown, night setback, cascade setpoint and boiler address objects are writable.
This page lists 147 BACnet objects for the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bosch’s own free documentation, linked below.
- Manufacturer
- Bosch
- Model
- Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)
- Equipment
- Condensing boiler gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 147 (10 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + boiler station address (station address 1 gives 50001)
- Also known as
- SSB800, SSB1000, SSB1000TL, Buderus SSB, Bosch SSB, ProtoNode FPC-N38, D_Platform
Instance calculator. This list prints one unit; the other units follow a formula. ProtoNode boiler gateways (Laars, Peerless, Raypak, AERCO and more) instance calculator →
Reference only, provided as-is: verify against Bosch’s current documentation and the live device before use. Not official Bosch information. Terms of use.
BMS integration notes: Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)
Set the boiler station address to 1, pick BACnet MS/TP or BACnet IP on the ProtoNode S DIP switches, set the MS/TP MAC and baud rate, then select the boiler profile in the ProtoNode web configurator. The list is mostly monitoring: system supply setpoint and temperature, outdoor temperature, power level, per-boiler active/error/service flags and the error number. The writable objects are the cascade setpoint and heating-curve settings; the guide describes no enable or start/stop command.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 10 | Cascade Ch Mode X SP | Cascade central-heating mode setpoint | Write |
| AI 11 | System Supply SP | Active system supply setpoint | Read |
| AI 12 | System Supply Sensor Temp | System supply water temperature | Read |
| AI 13 | Outdoor Sensor Temp | Outdoor air temperature | Read |
| AI 9 | Power Level For Entire System | System power level, % | Read |
| BI 19 | Boiler 1 Is Active / Heating | Boiler 1 firing | Read |
| BI 23 | Boiler 1 Has Error | Boiler 1 in error | Read |
| AI 136 | Error Number | Active error code | Read |
Network setup
- Boiler side: Modbus RTU at 9600 baud; set the station address of the device attached to the ProtoNode to 1.
- S bank DIP switches S0-S3 select BACnet IP, BACnet MS/TP, Metasys N2, Modbus TCP or single-node BACnet MS/TP (power off when changing them).
- BACnet MS/TP: MAC address 1-127 on the A bank DIP switches; baud rate on B0-B3 (9600-76800, factory default 38400).
- Device instance = station address + Node_Offset (default 50,000); Node_Offset can be changed in the web configurator.
- The ProtoNode web configurator defaults to 192.168.1.24 / 255.255.255.0; change the IP address there for BACnet IP.
Watch out for
- Point count follows the selected profile (1-4 boilers); objects for missing boilers or burners will not be present.
- Most writable objects are boiler heating-curve settings (reset curve, warm weather shutdown, night setback), not run commands.
Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 9 | Power Level For Entire System | Read | |||
| AImin | 11 | System Supply SP | Read | |||
| AImin | 12 | System Supply Sensor Temp | Read | |||
| AImin | 13 | Outdoor Sensor Temp | Read | |||
| AI | 32 | Power Level For The Boiler | Read | |||
| AI | 33 | Boiler Supply SP | Read | |||
| AI | 34 | Heat Demand Type | Read | |||
| AI | 35 | System Sensor Temp | Read | |||
| AI | 36 | Dhw Temp | Read | |||
| AI | 39 | Total Burn Hours | Read | |||
| AI | 48 | Blr 1 - Burner 1 Current State | Read | |||
| AI | 49 | Blr 1 - Burner 1 Error | Read | |||
| AI | 50 | Blr 1 - Burner 1 Supply SP | Read | |||
| AI | 51 | Blr 1 - Burner 1 Power Level | Read | |||
| AI | 53 | Blr 1 - Burner 1 CH Flow Rate | Read | |||
| AI | 54 | Blr 1 - Burner 1 Actual Fan Speed | Read | |||
| AI | 55 | Blr 1 - Burner 1 Supply Sensor Temp | Read | |||
| AI | 56 | Blr 1 - Burner 1 Return Sensor Temp | Read | |||
| AI | 57 | Blr 1 - Burner 1 Flue Sensor Temp | Read | |||
| AI | 58 | Blr 1 - Burner 1 Total Burn Hours | Read | |||
| AI | 59 | Blr 1 - Burner 2 Current State | Read | |||
| AI | 60 | Blr 1 - Burner 2 Error | Read | |||
| AI | 61 | Blr 1 - Burner 2 Supply SP | Read | |||
| AI | 62 | Blr 1 - Burner 2 Power Level | Read | |||
| AI | 64 | Blr 1 - Burner 2 CH Flow Rate | Read | |||
| AI | 65 | Blr 1 - Burner 2 Actual Fan Speed | Read | |||
| AI | 66 | Blr 1 - Burner 2 Supply Sensor Temp | Read | |||
| AI | 67 | Blr 1 - Burner 2 Return Sensor Temp | Read | |||
| AI | 68 | Blr 1 - Burner 2 Flue Sensor Temp | Read | |||
| AI | 69 | Blr 1 - Burner 2 Total Burn Hours | Read | |||
| AI | 70 | Blr 2 - Burner 1 Current State | Read | |||
| AI | 71 | Blr 2 - Burner 1 Error | Read | |||
| AI | 72 | Blr 2 - Burner 1 Supply SP | Read | |||
| AI | 73 | Blr 2 - Burner 1 Power Level | Read | |||
| AI | 75 | Blr 2 - Burner 1 CH Flow Rate | Read | |||
| AI | 76 | Blr 2 - Burner 1 Actual Fan Speed | Read | |||
| AI | 77 | Blr 2 - Burner 1 Supply Sensor Temp | Read | |||
| AI | 78 | Blr 2 - Burner 1 Return Sensor Temp | Read | |||
| AI | 79 | Blr 2 - Burner 1 Flue Sensor Temp | Read | |||
| AI | 80 | Blr 2 - Burner 1 Total Burn Hours | Read | |||
| AI | 81 | Blr 2 - Burner 2 Current State | Read | |||
| AI | 82 | Blr 2 - Burner 2 Error | Read | |||
| AI | 83 | Blr 2 - Burner 2 Supply SP | Read | |||
| AI | 84 | Blr 2 - Burner 2 Power Level | Read | |||
| AI | 86 | Blr 2 - Burner 2 CH Flow Rate | Read | |||
| AI | 87 | Blr 2 - Burner 2 Actual Fan Speed | Read | |||
| AI | 88 | Blr 2 - Burner 2 Supply Sensor Temp | Read | |||
| AI | 89 | Blr 2 - Burner 2 Return Sensor Temp | Read | |||
| AI | 90 | Blr 2 - Burner 2 Flue Sensor Temp | Read | |||
| AI | 91 | Blr 2 - Burner 2 Total Burn Hours | Read | |||
| AI | 92 | Blr 3 - Burner 1 Current State | Read | |||
| AI | 93 | Blr 3 - Burner 1 Error | Read | |||
| AI | 94 | Blr 3 - Burner 1 Supply SP | Read | |||
| AI | 95 | Blr 3 - Burner 1 Power Level | Read | |||
| AI | 97 | Blr 3 - Burner 1 CH Flow Rate | Read | |||
| AI | 98 | Blr 3 - Burner 1 Actual Fan Speed | Read | |||
| AI | 99 | Blr 3 - Burner 1 Supply Sensor Temp | Read | |||
| AI | 100 | Blr 3 - Burner 1 Return Sensor Temp | Read | |||
| AI | 101 | Blr 3 - Burner 1 Flue Sensor Temp | Read | |||
| AI | 102 | Blr 3 - Burner 1 Total Burn Hours | Read | |||
| AI | 103 | Blr 3 - Burner 2 Current State | Read | |||
| AI | 104 | Blr 3 - Burner 2 Error | Read | |||
| AI | 105 | Blr 3 - Burner 2 Supply SP | Read | |||
| AI | 106 | Blr 3 - Burner 2 Power Level | Read | |||
| AI | 108 | Blr 3 - Burner 2 CH Flow Rate | Read | |||
| AI | 109 | Blr 3 - Burner 2 Actual Fan Speed | Read | |||
| AI | 110 | Blr 3 - Burner 2 Supply Sensor Temp | Read | |||
| AI | 111 | Blr 3 - Burner 2 Return Sensor Temp | Read | |||
| AI | 112 | Blr 3 - Burner 2 Flue Sensor Temp | Read | |||
| AI | 113 | Blr 3 - Burner 2 Total Burn Hours | Read | |||
| AI | 114 | Blr 4 - Burner 1 Current State | Read | |||
| AI | 115 | Blr 4 - Burner 1 Error | Read | |||
| AI | 116 | Blr 4 - Burner 1 Supply SP | Read | |||
| AI | 117 | Blr 4 - Burner 1 Power Level | Read | |||
| AI | 119 | Blr 4 - Burner 1 CH Flow Rate | Read | |||
| AI | 120 | Blr 4 - Burner 1 Actual Fan Speed | Read | |||
| AI | 121 | Blr 4 - Burner 1 Supply Sensor Temp | Read | |||
| AI | 122 | Blr 4 - Burner 1 Return Sensor Temp | Read | |||
| AI | 123 | Blr 4 - Burner 1 Flue Sensor Temp | Read | |||
| AI | 124 | Blr 4 - Burner 1 Total Burn Hours | Read | |||
| AI | 125 | Blr 4 - Burner 2 Current State | Read | |||
| AI | 126 | Blr 4 - Burner 2 Error | Read | |||
| AI | 127 | Blr 4 - Burner 2 Supply SP | Read | |||
| AI | 128 | Blr 4 - Burner 2 Power Level | Read | |||
| AI | 130 | Blr 4 - Burner 2 CH Flow Rate | Read | |||
| AI | 131 | Blr 4 - Burner 2 Actual Fan Speed | Read | |||
| AI | 132 | Blr 4 - Burner 2 Supply Sensor Temp | Read | |||
| AI | 133 | Blr 4 - Burner 2 Return Sensor Temp | Read | |||
| AI | 134 | Blr 4 - Burner 2 Flue Sensor Temp | Read | |||
| AI | 135 | Blr 4 - Burner 2 Total Burn Hours | Read | |||
| AImin | 136 | Error Number | Read | |||
| AI | 137 | Boiler ID | Read | |||
| AI | 138 | Timestamp: Day Of Week | Read | |||
| AI | 139 | Timestamp: Day Of Month | Read | |||
| AI | 140 | Timestamp: Month | Read | |||
| AI | 141 | Timestamp: Year | Read | |||
| AI | 142 | Timestamp: Hour | Read | |||
| AI | 143 | Timestamp: Minute | Read | |||
| AI | 144 | Burn Hours Since Last Service | Read | |||
| AI | 145 | Burn Hours Till Service Is Required | Read | |||
| AI | 146 | Overdue Counter 0 | Read | |||
| AI | 147 | Service Interval | Read | |||
| AV | 1 | Reset Curve Boiler Design | Write | |||
| AV | 2 | Reset Curve Boiler Mild Weather | Write | |||
| AV | 3 | Reset Curve Outdoor Mild Weather | Write | |||
| AV | 4 | Reset Curve Outdoor Design | Write | |||
| AV | 5 | Warm Weather Shutdown | Write | |||
| AV | 6 | Reset Curve Boiler Maximum | Write | |||
| AV | 7 | Reset Curve Boiler Minimum | Write | |||
| AV | 8 | Night Setback | Write | |||
| AVmin | 10 | Cascade Ch Mode X SP | Write | |||
| AV | 31 | Boiler Address | Write | |||
| BI | 14 | Cascade Pump Status | Read | |||
| BI | 15 | Boiler 1 Available / Present | Read | |||
| BI | 16 | Boiler 2 Available / Present | Read | |||
| BI | 17 | Boiler 3 Available / Present | Read | |||
| BI | 18 | Boiler 4 Available / Present | Read | |||
| BImin | 19 | Boiler 1 Is Active / Heating | Read | |||
| BI | 20 | Boiler 2 Is Active / Heating | Read | |||
| BI | 21 | Boiler 3 Is Active / Heating | Read | |||
| BI | 22 | Boiler 4 Is Active / Heating | Read | |||
| BImin | 23 | Boiler 1 Has Error | Read | |||
| BI | 24 | Boiler 2 Has Error | Read | |||
| BI | 25 | Boiler 3 Has Error | Read | |||
| BI | 26 | Boiler 4 Has Error | Read | |||
| BI | 27 | Boiler 1 Requires Service | Read | |||
| BI | 28 | Boiler 2 Requires Service | Read | |||
| BI | 29 | Boiler 3 Requires Service | Read | |||
| BI | 30 | Boiler 4 Requires Service | Read | |||
| BI | 37 | Ch Pump Running | Read | |||
| BI | 38 | Dhw Pump Status | Read | |||
| BI | 40 | Blr 1 - Burner 1 Available/Present | Read | |||
| BI | 41 | Blr 1 - Burner 2 Available/Present | Read | |||
| BI | 42 | Blr 2 - Burner 1 Available/Present | Read | |||
| BI | 43 | Blr 2 - Burner 2 Available/Present | Read | |||
| BI | 44 | Blr 3 - Burner 1 Available/Present | Read | |||
| BI | 45 | Blr 3 - Burner 2 Available/Present | Read | |||
| BI | 46 | Blr 4 - Burner 1 Available/Present | Read | |||
| BI | 47 | Blr 4 - Burner 2 Available/Present | Read | |||
| BI | 52 | Blr 1 - Burner 1 Gen Pump Status | Read | |||
| BI | 63 | Blr 1 - Burner 2 Gen Pump Status | Read | |||
| BI | 74 | Blr 2 - Burner 1 Gen Pump Status | Read | |||
| BI | 85 | Blr 2 - Burner 2 Gen Pump Status | Read | |||
| BI | 96 | Blr 3 - Burner 1 Gen Pump Status | Read | |||
| BI | 107 | Blr 3 - Burner 2 Gen Pump Status | Read | |||
| BI | 118 | Blr 4 - Burner 1 Gen Pump Status | Read | |||
| BI | 129 | Blr 4 - Burner 2 Gen Pump Status | Read |
No points match these filters.
Object ID lookup: Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler point IDs by name
AI9Power Level For Entire SystemAI11System Supply SPAI12System Supply Sensor TempAI13Outdoor Sensor TempAI32Power Level For The BoilerAI33Boiler Supply SPAI34Heat Demand TypeAI35System Sensor TempAI36Dhw TempAI39Total Burn HoursAI48Blr 1 - Burner 1 Current StateAI49Blr 1 - Burner 1 ErrorAI50Blr 1 - Burner 1 Supply SPAI51Blr 1 - Burner 1 Power LevelAI53Blr 1 - Burner 1 CH Flow RateAI54Blr 1 - Burner 1 Actual Fan SpeedAI55Blr 1 - Burner 1 Supply Sensor TempAI56Blr 1 - Burner 1 Return Sensor TempAI57Blr 1 - Burner 1 Flue Sensor TempAI58Blr 1 - Burner 1 Total Burn HoursAI59Blr 1 - Burner 2 Current StateAI60Blr 1 - Burner 2 ErrorAI61Blr 1 - Burner 2 Supply SPAI62Blr 1 - Burner 2 Power LevelAI64Blr 1 - Burner 2 CH Flow RateAI65Blr 1 - Burner 2 Actual Fan SpeedAI66Blr 1 - Burner 2 Supply Sensor TempAI67Blr 1 - Burner 2 Return Sensor TempAI68Blr 1 - Burner 2 Flue Sensor TempAI69Blr 1 - Burner 2 Total Burn HoursAI70Blr 2 - Burner 1 Current StateAI71Blr 2 - Burner 1 ErrorAI72Blr 2 - Burner 1 Supply SPAI73Blr 2 - Burner 1 Power LevelAI75Blr 2 - Burner 1 CH Flow RateAI76Blr 2 - Burner 1 Actual Fan SpeedAI77Blr 2 - Burner 1 Supply Sensor TempAI78Blr 2 - Burner 1 Return Sensor TempAI79Blr 2 - Burner 1 Flue Sensor TempAI80Blr 2 - Burner 1 Total Burn HoursAI81Blr 2 - Burner 2 Current StateAI82Blr 2 - Burner 2 ErrorAI83Blr 2 - Burner 2 Supply SPAI84Blr 2 - Burner 2 Power LevelAI86Blr 2 - Burner 2 CH Flow RateAI87Blr 2 - Burner 2 Actual Fan SpeedAI88Blr 2 - Burner 2 Supply Sensor TempAI89Blr 2 - Burner 2 Return Sensor TempAI90Blr 2 - Burner 2 Flue Sensor TempAI91Blr 2 - Burner 2 Total Burn HoursAI92Blr 3 - Burner 1 Current StateAI93Blr 3 - Burner 1 ErrorAI94Blr 3 - Burner 1 Supply SPAI95Blr 3 - Burner 1 Power LevelAI97Blr 3 - Burner 1 CH Flow RateAI98Blr 3 - Burner 1 Actual Fan SpeedAI99Blr 3 - Burner 1 Supply Sensor TempAI100Blr 3 - Burner 1 Return Sensor TempAI101Blr 3 - Burner 1 Flue Sensor TempAI102Blr 3 - Burner 1 Total Burn HoursAI103Blr 3 - Burner 2 Current StateAI104Blr 3 - Burner 2 ErrorAI105Blr 3 - Burner 2 Supply SPAI106Blr 3 - Burner 2 Power LevelAI108Blr 3 - Burner 2 CH Flow RateAI109Blr 3 - Burner 2 Actual Fan SpeedAI110Blr 3 - Burner 2 Supply Sensor TempAI111Blr 3 - Burner 2 Return Sensor TempAI112Blr 3 - Burner 2 Flue Sensor TempAI113Blr 3 - Burner 2 Total Burn HoursAI114Blr 4 - Burner 1 Current StateAI115Blr 4 - Burner 1 ErrorAI116Blr 4 - Burner 1 Supply SPAI117Blr 4 - Burner 1 Power LevelAI119Blr 4 - Burner 1 CH Flow RateAI120Blr 4 - Burner 1 Actual Fan SpeedAI121Blr 4 - Burner 1 Supply Sensor TempAI122Blr 4 - Burner 1 Return Sensor TempAI123Blr 4 - Burner 1 Flue Sensor TempAI124Blr 4 - Burner 1 Total Burn HoursAI125Blr 4 - Burner 2 Current StateAI126Blr 4 - Burner 2 ErrorAI127Blr 4 - Burner 2 Supply SPAI128Blr 4 - Burner 2 Power LevelAI130Blr 4 - Burner 2 CH Flow RateAI131Blr 4 - Burner 2 Actual Fan SpeedAI132Blr 4 - Burner 2 Supply Sensor TempAI133Blr 4 - Burner 2 Return Sensor TempAI134Blr 4 - Burner 2 Flue Sensor TempAI135Blr 4 - Burner 2 Total Burn HoursAI136Error NumberAI137Boiler IDAI138Timestamp: Day Of WeekAI139Timestamp: Day Of MonthAI140Timestamp: MonthAI141Timestamp: YearAI142Timestamp: HourAI143Timestamp: MinuteAI144Burn Hours Since Last ServiceAI145Burn Hours Till Service Is RequiredAI146Overdue Counter 0AI147Service IntervalAV1Reset Curve Boiler DesignAV2Reset Curve Boiler Mild WeatherAV3Reset Curve Outdoor Mild WeatherAV4Reset Curve Outdoor DesignAV5Warm Weather ShutdownAV6Reset Curve Boiler MaximumAV7Reset Curve Boiler MinimumAV8Night SetbackAV10Cascade Ch Mode X SPAV31Boiler AddressBI14Cascade Pump StatusBI15Boiler 1 Available / PresentBI16Boiler 2 Available / PresentBI17Boiler 3 Available / PresentBI18Boiler 4 Available / PresentBI19Boiler 1 Is Active / HeatingBI20Boiler 2 Is Active / HeatingBI21Boiler 3 Is Active / HeatingBI22Boiler 4 Is Active / HeatingBI23Boiler 1 Has ErrorBI24Boiler 2 Has ErrorBI25Boiler 3 Has ErrorBI26Boiler 4 Has ErrorBI27Boiler 1 Requires ServiceBI28Boiler 2 Requires ServiceBI29Boiler 3 Requires ServiceBI30Boiler 4 Requires ServiceBI37Ch Pump RunningBI38Dhw Pump StatusBI40Blr 1 - Burner 1 Available/PresentBI41Blr 1 - Burner 2 Available/PresentBI42Blr 2 - Burner 1 Available/PresentBI43Blr 2 - Burner 2 Available/PresentBI44Blr 3 - Burner 1 Available/PresentBI45Blr 3 - Burner 2 Available/PresentBI46Blr 4 - Burner 1 Available/PresentBI47Blr 4 - Burner 2 Available/PresentBI52Blr 1 - Burner 1 Gen Pump StatusBI63Blr 1 - Burner 2 Gen Pump StatusBI74Blr 2 - Burner 1 Gen Pump StatusBI85Blr 2 - Burner 2 Gen Pump StatusBI96Blr 3 - Burner 1 Gen Pump StatusBI107Blr 3 - Burner 2 Gen Pump StatusBI118Blr 4 - Burner 1 Gen Pump StatusBI129Blr 4 - Burner 2 Gen Pump Status
Integration notes
- The table has no read/write column. Objects whose LonWorks variable is an input/output pair (nvi/nvo) and that map to N2 AO are marked writable; the rest are read-only.
- The gateway profile depends on how many boilers the managing D_Platform runs: 63 points for one boiler, 91 for two, 119 for three and 147 for four. This file lists the full four-boiler table.
- Blr 1-4 / Burner 1-2 objects only exist for boilers and burners that are present.
- The table gives no engineering units; the LonWorks types (temperature, percent, hours, count) hint at the value type.
- The same table also maps Metasys N2 and LonWorks (FPC-N39); only the BACnet side is listed here.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)
How many BACnet points does the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) have?
This list has 147 BACnet objects: 102 analog inputs, 10 analog values, 35 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet points are writable?
10 of the 147 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38) BACnet documentation?
The source is ProtoNode FPC-N38 and ProtoNode FPC-N39 Start-up Guide for Interfacing Bosch Products: Bosch Buderus SSB800, SSB1000, SSB1000TL (Appendix B.1 D_Platform Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks) (Document Revision 4.B (Web Configurator Template Revision 70)), revision 2018-03, published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ssb800-1000-1000tl_bacnet_and_lonworks_start-up_guide_03.2018_us_1.pdf.
What are the minimum BACnet points to integrate the Bosch Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)?
Start with AV 10 Cascade Ch Mode X SP (Cascade central-heating mode setpoint); AI 11 System Supply SP (Active system supply setpoint); AI 12 System Supply Sensor Temp (System supply water temperature); AI 13 Outdoor Sensor Temp (Outdoor air temperature); AI 9 Power Level For Entire System (System power level, %); BI 19 Boiler 1 Is Active / Heating (Boiler 1 firing); BI 23 Boiler 1 Has Error (Boiler 1 in error); AI 136 Error Number (Active error code).
How do I check these points on the real Buderus SSB800 / SSB1000 / SSB1000TL boiler (ProtoNode FPC-N38)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Bosch BACnet points lists
- Boiler cascade controller gateway
Bosch Buderus Cascade SSB 255 / 399 / 512 (ProtoAir FPA-W44, C_Platform)
Bosch/Buderus SSB 255, 399 and 512 condensing boilers in a cascade (C_Platform), read through the ProtoAir FPA-W44 gateway.
Also known as: SSB 255, SSB 399, SSB 512, Buderus SSB, C_Platform, ProtoAir FPA-W44, Bosch cascade - Water-source heat pump controller
Bosch Control Air 5600 - Water to Air (WAZ software)
Bosch water-to-air (water source) heat pumps fitted with the Control Air 5600 DDC controller running WAZ zone software.
Also known as: Control Air 5600, WAZ 1.03, Bosch WSHP DDC, Bosch water source heat pump BACnet, Bosch TT Water to Air - Water-to-water heat pump controller
Bosch Control Air 5600 - Water to Water (WWZ software)
Bosch water-to-water heat pumps fitted with the Control Air 5600 DDC controller running WWZ software.
Also known as: Control Air 5600, WWZ 1.03, Bosch water to water heat pump BACnet, Bosch TT Water to Water - Commercial water-source heat pump controller
Bosch Control Air 6120 - Water to Air (WAF software)
Bosch commercial water-to-air heat pumps (up to 4 compressor stages) with the Control Air 6120 DDC controller and WAF software.
Also known as: Control Air 6120, WAF 1.01, Bosch commercial WSHP DDC, Bosch TT Water to Air - Water source heat pump controller
Bosch FHP / Bosch ES 2-stage single-compressor water-to-air DDC (software 3.10)
Discontinued FHP / Bosch ES-series two-stage, single-compressor water-to-air heat pumps with the factory DDC controller running software 3.10.
Also known as: FHP ES, Florida Heat Pump ES BACnet, Bosch ES water source heat pump, FHP BACview 3.10, Integration Points List v3.10 - Boiler plant (multi-boiler) controller
Bosch Heatronic 4000 boiler plant control
Bosch Heatronic 4000 control that runs up to four boilers for heating and DHW loads (product now discontinued).
Also known as: Heatronic 4000, Bosch 4000, Heatronic, J1229A - Heat pump controller
Bosch REGO 5200 heat pump controller (Supraeco T)
Bosch REGO 5200 controller used in Bosch Supraeco T ground-source / water heat pumps, program 1.3-0-00 and later.
Also known as: REGO 5200, REGO5200, Supraeco T, Bosch Supraeco T BACnet, 6 720 821 165, Bosch ground source heat pump BACnet
Source: ProtoNode FPC-N38 and ProtoNode FPC-N39 Start-up Guide for Interfacing Bosch Products: Bosch Buderus SSB800, SSB1000, SSB1000TL (Appendix B.1 D_Platform Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks) · Document Revision 4.B (Web Configurator Template Revision 70) · rev. 2018-03. Object names, instances and units are reproduced as published; descriptions are our own.