 "manufacturer": "York",
 "manufacturer_slug": "york",
 "model": "YVWH / YVWE / YGWH Water-Cooled Screw (SC-EQ)",
 "model_slug": "yvwh-yvwe-ygwh-sc-eq",
 "aliases": [
  "YORK YVWH",
  "YVWH-200",
  "YORK YVWE",
  "YORK YGWH",
  "SC-EQ",
  "water-to-water screw heat pump"
 ],
 "equipment_type": "Water-cooled screw chiller / water-to-water heat pump (via SC-EQ card)",
 "applies_to": "YORK YVWH and YGWH water-to-water screw heat pumps and YVWE water-cooled screw chillers fitted with the SC-EQ communication card.",
 "summary": "YORK by Johnson Controls YVWH, YVWE and YGWH water-cooled screw units share one SC-EQ list on BACnet MS/TP (or Modbus RTU / N2). A Read/Write block holds start/stop, run mode (cool, ice storage, heat pump, remote), leaving water setpoints per mode and over-current percentages per mode. Read points cover water temperatures, pressures, per-system motor and VSD values, and bit-coded digital I/O and fault words.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "SC-EQ software 3.5.0.11",
 "default_device_instance": "5000 + MAC address",
 "access_inferred": false,
 "notes": [
  "Access comes from the sheet's Read/Write and Read sections.",
  "Several AVs are bit-coded words (digital inputs/outputs and faults); the states list the bits. The sheet only gives bit tables written for system 1, so AV 57-59 have none.",
  "All MV enums are printed in the points table (the sheet has no add-1 note). Multistate states with their own enum in the points table are shown as printed, from 0. BACnet multistate values start at 1, so the device may report the printed number + 1; confirm by discovery (read the state text).",
  "Units shown are the IP units; with MV 65001 set to SI on the SC-EQ the card reports °C, kPa and so on.",
  "System 2 points apply to dual-compressor units."
 ],
 "source": {
  "title": "YVWH YVWE YGWH SC-EQ BAS Points List",
  "doc_number": null,
  "revision_date": "Rev 1.0, 2021-03-15",
  "url": "https://docs.johnsoncontrols.com/chillers/api/khub/documents/TWAOtmjMD~xxMBlTMLA2QQ/content"
 },
 "integration": {
  "summary": "Select the run mode with MV 1, start/stop with BV 1, and write the setpoint for the active mode (AV 1 cooling, AV 3 heat pump). MV 2 shows whether the unit is under local, remote or communication control. Read leaving water temperatures, % FLA and VSD run status, and alarm on BV 2.",
  "minimum_points": [
   {
    "ref": "BV 1",
    "name": "START|STOP",
    "why": "Start/stop command (1 = start)"
   },
   {
    "ref": "MV 1",
    "name": "RUN MODE",
    "why": "Mode: cool, ice storage, heat pump, remote"
   },
   {
    "ref": "AV 1",
    "name": "LEAVING CHILLED LIQUID SETPOINT AC",
    "why": "Leaving chilled liquid setpoint, cooling mode"
   },
   {
    "ref": "AV 3",
    "name": "LEAVING HEAT LIQUID SETPOINT HP",
    "why": "Leaving hot liquid setpoint, heat pump mode"
   },
   {
    "ref": "AV 21",
    "name": "OVER CURRENT PERCENT AC",
    "why": "Over-current setting, %, cooling mode (no detail in sheet)"
   },
   {
    "ref": "MV 2",
    "name": "CONTROL MODE",
    "why": "Control mode: local, remote or communication"
   },
   {
    "ref": "MV 3",
    "name": "SYS 1 VSD RUN STATUS",
    "why": "Compressor 1 VSD running, stopped or fault"
   },
   {
    "ref": "AV 9",
    "name": "LEAVING CHILLED LIQUID TEMPERATURE",
    "why": "Leaving chilled liquid temperature"
   },
   {
    "ref": "AV 24",
    "name": "SYS 1 PERCENT FLA",
    "why": "Compressor 1 current, % FLA"
   },
   {
    "ref": "BV 2",
    "name": "FAULT",
    "why": "Unit fault (1 = fault)"
   }
  ],
  "enable": "MV 2 reports the control mode (local, remote, communication). The sheet does not say how to select it and gives no write-enable point.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The BAS connects to the SC-EQ J12 port (RS-485: +, -, COM/REF, SHLD). The card detects BACnet MS/TP, Modbus RTU or N2 and the baud rate by itself; allow up to 120 seconds after power-up.",
   "The MAC address (1-127) is set on DIP switch SW1 (switch 8 unused). Cycle the card's power after changing it.",
   "The device instance defaults to 5000 + the MAC address (MAC 6 gives 5006). To use another number, set Device Instance Mode to Manual and enter the instance with the SC-AP / MAP tool, or write BV 65000 (mode) and AV 65000 (instance ID).",
   "MV 65001 Units sets whether the BAS sees IP or SI values, independent of the chiller display; set it to match the chiller."
  ],
  "gotchas": [
   "The remote (commandable) setpoints read as unreliable until the BAS writes them the first time.",
   "The SC-EQ only exposes the points that apply to the chiller it detects; if it replaces an E-Link, re-discover the device so old non-applicable points don't sit offline.",
   "Leaving water setpoints are per mode (AC, ICS, HP, HTHP) and over-current percentages per mode (AC, ICS, HP); write the ones for the mode selected in MV 1."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "START|STOP",
   "description": "Start/Stop",
   "units": "",
   "access": "W",
   "states": "0=Stop, 1=Start"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "RUN MODE",
   "description": "Run Mode",
   "units": "",
   "access": "W",
   "states": "0=Cool, 1=ice storage, 2=heat pump, 3=remote"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "LEAVING CHILLED LIQUID SETPOINT AC",
   "description": "Leaving chilled liquid setpoint, cooling (AC) mode",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "LEAVING CHILLED LIQUID SETPOINT ICS",
   "description": "Leaving chilled liquid setpoint, ice storage (ICS) mode",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "LEAVING HEAT LIQUID SETPOINT HP",
   "description": "Leaving hot liquid setpoint, heat pump (HP) mode",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "LEAVING HEAT LIQUID SETPOINT HTHP",
   "description": "Leaving hot liquid setpoint, high-temperature heat pump mode",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "OVER CURRENT PERCENT AC",
   "description": "Over current percent, cooling (AC) mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "OVER CURRENT PERCENT ICS",
   "description": "Over current percent, ice storage (ICS) mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "OVER CURRENT PERCENT HP",
   "description": "Over current percent, heat pump (HP) mode",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "FAULT",
   "description": "Fault",
   "units": "",
   "access": "R",
   "states": "0=no fault, 1=fault exist"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "TIME LIMITATION",
   "description": "Time Limitation",
   "units": "",
   "access": "R",
   "states": "0=no time limitation, 1=time limitation"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "PREHEAT",
   "description": "Preheat",
   "units": "",
   "access": "R",
   "states": "0=no preheat, 1=preheat"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "CONTROL MODE",
   "description": "Control Mode",
   "units": "",
   "access": "R",
   "states": "0=local, 1=remote, 2=communication"
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "SYS 1 DIGITAL OUTPUT",
   "description": "System 1 digital outputs, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Liquid Pump, Bit 1=Compressor Y Contact, Bit 2=Compressor Δ Contact, Bit 3=Oil Heater, Bit 4=Hot Gas Bypass, Bit 5=Alarm, Bit 6=Liquid Injection Oil Cooling, Bit 7=DO18, Bit 8=Unit Running, Bit 9=Oil Supply Circuit, Bit 12=Slide Stop Load, Bit 13=Slide Stop Unload, Bit 14=Slide Valve Load, Bit 15=Slide Valve Unload (1=on)"
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "SYS 1 DIGITAL INPUT",
   "description": "System 1 digital inputs, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Chilled Liquid Flow Switch, Bit 1=Mode Switch, Bit 2=High Pressure Switch, Bit 3=Low Oil Level Switch, Bit 4=Motor Internal Protect, Bit 5=External Interlock/Power Protect, Bit 6=Starter Running Feedback, Bit 7=Remote Switch, Bit 8=EM Stop, Bit 9=Starter Fault Feedback, Bit 10=Condenser Liquid Flow Switch (1=closed)"
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "LEAVING CONDENSER LIQUID TEMPERATURE",
   "description": "Leaving Condenser Liquid Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "RETURN CONDENSER LIQUID TEMPERATURE",
   "description": "Return Condenser Liquid Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "LEAVING CHILLED LIQUID TEMPERATURE",
   "description": "Leaving Chilled Liquid Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "RETURN CHILLED LIQUID TEMPERATURE",
   "description": "Return Chilled Liquid Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "SYS 1 DISCHARGE TEMPERATURE",
   "description": "Sys 1 Discharge Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "EVAPORATOR PRESSURE",
   "description": "Evaporator Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "CONDENSER PRESSURE",
   "description": "Condenser Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "SYS 1 OIL PRESSURE",
   "description": "Sys 1 Oil Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "SYS 1 MOTOR CURRENT",
   "description": "Sys 1 Motor Current",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "SYS 1 DIGITAL INPUT FAULT",
   "description": "System 1 digital input faults, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Cycling Stop-Chilled Liquid Flow Switch Open, Bit 1=Cycling Stop-Condenser Liquid Flow Switch Open, Bit 2=Safety Fault-SYS1 High Pressure Contact Open, Bit 3=Safety Fault-Low Level Switch Open, Bit 4=Safety Fault-SYS1 Compressor Motor Protection, Bit 5=Safety Fault-External Interlock Protection, Bit 6=Safety Fault-SYS1 Compressor Start Fail, Bit 7=Safety Fault-Emergency Stop Pressed, Bit 8=Start Inhibit-Oil Heat Over 5 Hour Before Start, Bit 9=Safety Fault-Evaporator Smart Freeze Protection (1=fault)"
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "SYS 1 ANALOG INPUT FAULT",
   "description": "System 1 analog input (sensor) faults, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Safety Fault-Leaving Condenser Temp. Sensor Fault, Bit 1=Safety Fault-Return Condenser Temp. Sensor Fault, Bit 2=Safety Fault-Leaving Chilled Sensor Fault, Bit 3=Safety Fault-Return Chilled Temp. Sensor Fault, Bit 4=Safety Fault-SYS1 Discharge Temp. Sensor Fault, Bit 10=Safety Fault-Leaving Hot Liquid Temp. Sensor Fault, Bit 11=Safety Fault-Return Hot Liquid Temp. Sensor Fault, Bit 12=Safety Fault-Evaporator Pressure Out Of Range Fault, Bit 13=Safety Fault-Condenser Pressure Sensor Fault, Bit 14=Safety Fault-SYS1 Oil Pressure Sensor Fault (1=fault)"
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "SYS 1 FAULT",
   "description": "System 1 faults, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 0=Safety Fault-Condenser High Pressure, Bit 1=Safety Fault-Evaporator Low Pressure, Bit 2=Safety Fault-SYS1 Discharge High Temp., Bit 3=Safety Fault-SYS1 Compressor Over Current, Bit 4=Safety Fault-SYS1 Compressor Low Current, Bit 5=Cycling Stop-Leaving Condenser High Temperature, Bit 6=Cycling Stop-Leaving Chilled Liquid Low Temperature, Bit 7=Safety Fault-SYS1 Oil Low Diff. Pressure, Bit 8=Safety Fault-SYS1 Oil Clogged Filter, Bit 9=Cycling Stop-SYS1 Anti-Recycle, Bit 10=Cycling Stop-Leaving Hot Liquid High Temperature, Bit 11=Safety Fault-SYS1 Oil Supply Fail, Bit 12=Safety Fault-SYS1 Discharge Low Superheat, Bit 13=Safety Fault-SYS1 Motor High Temperature, Bit 14=Cycling Stop-SYS1 Discharge High Temp. (1=fault)"
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "WATER PUMP WORK HOURS",
   "description": "Water Pump Work Hours",
   "units": "Hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "SYS 1 COMPRESSOR WORK HOURS",
   "description": "Sys 1 Compressor Work Hours",
   "units": "Hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "SYS 1 PERCENT FLA",
   "description": "Sys 1 Percent FLA",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "EVAPORATOR SATURATION TEMPERATURE",
   "description": "Evaporator Saturation Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "CONDENSER SATURATION TEMPERATURE",
   "description": "Condenser Saturation Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "DISCHARGE SUPERHEAT",
   "description": "Sys 1 Discharge Superheat",
   "units": "°F (diff)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "SYS 1 MOTOR TEMPERATURE A",
   "description": "Sys 1 Motor Temperature A",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "SYS 1 MOTOR TEMPERATURE B",
   "description": "Sys 1 Motor Temperature B",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "SYS 1 MOTOR TEMPERATURE C",
   "description": "Sys 1 Motor Temperature C",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "LIQUID LEVEL",
   "description": "Liquid Level",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "LEVEL CONTROL AO",
   "description": "Level Control AO",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "LEVEL SETPOINT",
   "description": "Level Setpoint",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "LEVEL CONTROL PB",
   "description": "Level Control Pb",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "LEVEL CONTROL TN",
   "description": "Level Control Tn",
   "units": "Sec",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "LEVEL CONTROL PERIOD",
   "description": "Level Control Period",
   "units": "Sec",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "SYS 1 VSD RUN STATUS",
   "description": "Sys 1 VSD Run Status",
   "units": "",
   "access": "R",
   "states": "0=No Communication, 1=Forward Running, 2=Reverse Running, 3=Stopped, 4=Tuned, 5=Fault"
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "SYS 1 FREQUENCY COMMAND",
   "description": "Sys 1 VSD Frequency Command",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "SYS 1 VSD FREQUENCY RUNNING",
   "description": "Sys 1 VSD Frequency Running",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "SYS 1 VSD BUS VOLTAGE",
   "description": "Sys 1 VSD BUS Voltage",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "SYS 1 VSD OUTPUT VOLTAGE",
   "description": "Sys 1 VSD Output Voltage",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "SYS 1 VSD OUTPUT CURRENT",
   "description": "Sys 1 VSD Output Current",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "SYS 1 VSD OUTPUT POWER",
   "description": "Sys 1 VSD Output Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "SYS 1 VSD HEATSINK TEMPERATURE",
   "description": "Sys 1 VSD Heatsink Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "SYS 1 VSD FAULT CODE",
   "description": "Sys 1 VSD Fault Code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "SYS 1 FAIL RATE",
   "description": "Sys 1 Fail Rate",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "VSD COMMAND PERIOD",
   "description": "VSD Command Period",
   "units": "Sec",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "VSD PB",
   "description": "VSD Pb",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "VSD TN",
   "description": "VSD Tn",
   "units": "Sec",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "SYS 2 DIGITAL OUTPUT",
   "description": "System 2 digital outputs, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 1=Compressor Y Contact, Bit 2=Compressor Δ Contact, Bit 6=Liquid Injection Oil Cooling, Bit 9=Oil Supply Circuit, Bit 12=Slide Stop Load, Bit 13=Slide Stop Unload, Bit 14=Slide Valve Load, Bit 15=Slide Valve Unload (1=on)"
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "SYS 2 DIGITAL INPUT",
   "description": "System 2 digital inputs, bit-coded",
   "units": "",
   "access": "R",
   "states": "Bit 2=High Pressure Switch, Bit 4=Motor Internal Protect, Bit 6=Starter Running Feedback, Bit 9=Starter Fault Feedback (1=closed)"
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "SYS 2 DISCHARGE TEMPERATURE",
   "description": "Sys 2 Discharge Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "SYS 2 OIL PRESSURE",
   "description": "Sys 2 Oil Pressure",
   "units": "PSIG",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "SYS 2 MOTOR CURRENT",
   "description": "Sys 2 Motor Current",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "SYS 2 DIGITAL INPUT FAULT",
   "description": "System 2 digital input faults, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "SYS 2 ANALOG INPUT FAULT",
   "description": "System 2 analog input faults, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "SYS 2 FAULT",
   "description": "System 2 faults, bit-coded",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "SYS 2 COMPRESSOR WORK HOURS",
   "description": "Sys 2 Compressor Work Hours",
   "units": "Hours",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "SYS 2 PERCENT FLA",
   "description": "Sys 2 Percent FLA",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "SYS 2 DISCHARGE SUPERHEAT",
   "description": "Sys 2 Discharge Superheat",
   "units": "°F (diff)",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "SYS 2 MOTOR TEMPERATURE A",
   "description": "Sys 2 Motor Temperature A",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "SYS 2 MOTOR TEMPERATURE B",
   "description": "Sys 2 Motor Temperature B",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "SYS 2 MOTOR TEMPERATURE C",
   "description": "Sys 2 Motor Temperature C",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "SYS 2 VSD RUN STATUS",
   "description": "Sys 2 VSD Run Status",
   "units": "",
   "access": "R",
   "states": "0=No Communication, 1=Forward Running, 2=Reverse Running, 3=Stopped, 4=Tuned, 5=Fault"
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "SYS 2 VSD FREQUENCY COMMAND",
   "description": "Sys 2 VSD Frequency Command",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "SYS 2 VSD FREQUENCY RUNNING",
   "description": "Sys 2 VSD Frequency Running",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "SYS 2 VSD BUS VOLTAGE",
   "description": "Sys 2 VSD BUS Voltage",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "SYS 2 VSD OUTPUT VOLTAGE",
   "description": "Sys 2 VSD Output Voltage",
   "units": "Volts",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "SYS 2 VSD OUTPUT CURRENT",
   "description": "Sys 2 VSD Output Current",
   "units": "Amps",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "SYS 2 VSD OUTPUT POWER",
   "description": "Sys 2 VSD Output Power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "SYS 2 VSD HEATSINK TEMPERATURE",
   "description": "Sys 2 VSD Heatsink Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "SYS 2 VSD FAULT CODE",
   "description": "Sys 2 VSD Fault Code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "SYS 2 FAIL RATE",
   "description": "Sys 2 Fail Rate",
   "units": "%",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/york/yvwh-yvwe-ygwh-sc-eq",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}