Variable frequency drive · BACnet points list
WEG CFW503 (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The CFW503 runs BACnet MS/TP on its RS-485 port and maps drive parameters to fixed objects: AVs for readings, ramps, PID values and the network speed reference, BVs for the status word (P0680) and control word (P0682), plus digital and analog I/O. A mailbox (AV 100/101, BV 100/101) reads or writes any parameter by number.
This page lists 77 BACnet objects for the WEG CFW503 (BACnet MS/TP) — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WEG’s own free documentation, linked below.
- Manufacturer
- WEG
- Model
- CFW503 (BACnet MS/TP)
- Equipment
- Variable frequency drive
- Equipment type
- VFDs & pumps
- BACnet objects
- 77 (41 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 359000 + serial address (P0308) when P0760 and P0761 are 0
- Also known as
- CFW503, WEG CFW503, CFW503 BACnet, 10012735607, CFW500
Reference only, provided as-is: verify against WEG’s current documentation and the live device before use. Not official WEG information. Terms of use.
BMS integration notes: WEG CFW503 (BACnet MS/TP)
Set P0312 to BACnet, the address in P0308 and the baud rate in P0310, then set P0220-P0228 so run/stop, direction and reference come from Serial/USB. Write BV 16 run/stop with BV 17 general enable and the speed reference to AV 17 (8192 = motor rated frequency). Read BV 8, AV 3, AV 1 and BV 15, and reset faults with BV 23.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 16 | Run/Stop | Start/stop from the BMS | Command |
| BV 17 | General Enable | General enable; must be on to run | Command |
| BV 20 | Remote | Remote mode when P0220 selects Serial/USB | Command |
| AV 17 | Serial/USB Speed Ref. | Speed reference, 8192 = rated frequency | Command |
| BV 23 | Fault Reset | Reset a tripped drive | Command |
| BV 8 | Running | Running status | Read |
| AV 3 | Motor Frequency | Output frequency in Hz | Read |
| AV 1 | Motor Current | Motor amps | Read |
| BV 15 | Fault | Any active drive fault | Read |
| AV 13 | Present Fault | Active fault number | Command |
Enable & remote start
Network commands only act when P0220-P0228 select Serial/USB: P0220 = 5/6 lets the control word set local/remote (BV 20), P0222 = 9 takes the reference from P0683 (AV 17), P0227 = 2 takes run/stop from the control word and P0226 = 5/6 sets direction. The drive needs both BV 17 General Enable and BV 16 Run/Stop.
Heartbeat & communication loss
P0314 Serial Watchdog (time limit 0-999, the manual gives no unit; 0 = off, factory 0): if no valid telegram arrives within that time the drive shows alarm A0128 (or fault F0228) and runs the P0313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.
Sensors & values from the BMS
AV 21/AV 25 take the main and external PID automatic setpoints and AV 23/AV 27 the PID feedbacks when the drive's PID is used.
Network setup
- P0312 = 3 (BACnet-1) for the standard port, or 9 for the second port of a plug-in module; reinitialize after changing.
- P0308 MS/TP address 0-254 (factory 1); P0310 baud 9600, 19200 (factory) or 38400; P0311 must be 8N1.
- Device instance: P0760 x 10000 + P0761; with both at 0 the drive uses 359000 + P0308 (WEG vendor ID 359).
- P0762 max master (factory 127), P0763 max info frames (factory 1), P0764 sends I-Am at power-up only (factory) or continuously.
Watch out for
- Speed reference AV 17 is a 13-bit value, not Hz or %: 8192 = motor rated frequency (P0403); negative values reverse.
- Unit column in the manual is shifted for AV 6-11; see notes.
- Ramp times AV 14/15 and the mailbox write change drive parameters; don't write them cyclically.
- P0313 = 0 keeps the drive running at the last command after a comm loss.
WEG CFW503 (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | AI1 Value | Analog input 1 level (P018) | % | Read | |
| AI | 1 | AI2 Value | Analog input 2 level (P019) | % | Read | |
| AI | 2 | AI3 Value | Analog input 3 level (P020) | % | Read | |
| AO | 0 | AOx Value 1 | Network value for an analog output (P0696) | Command | ||
| AO | 1 | AOx Value 2 | Network value for an analog output (P0697) | Command | ||
| AO | 2 | AOx Value 3 | Network value for an analog output (P0698) | Command | ||
| AV | 0 | Motor Speed | Motor speed (P0002) | rpm | Read | |
| AVmin | 1 | Motor Current | Motor current (P0003) | A | Read | |
| AV | 2 | DC Link Voltage (Ud) | DC bus voltage (P0004) | V | Read | |
| AVmin | 3 | Motor Frequency | Output frequency (P0005) | Hz | Read | |
| AV | 4 | Motor Voltage | Output voltage (P0007) | V | Read | |
| AV | 5 | Motor Torque | Motor torque (P0009) | % | Read | |
| AV | 6 | Output Power | Output power; unit cell blank in the shifted table (P0010) | Read | ||
| AV | 7 | Heatsink Temperature | Heatsink temperature (P0030) | °C | Read | |
| AV | 9 | Time Powered | Powered hours counter (P0042) | h | Command | |
| AV | 10 | Time Enabled | Enabled hours counter (P0043) | h | Command | |
| AV | 11 | kWh Output Energy | Energy counter (P0044) | kWh | Read | |
| AV | 12 | Present Alarm | Active alarm number (P0048) | Command | ||
| AVmin | 13 | Present Fault | Active fault number (P0049) | Command | ||
| AV | 14 | Acceleration Time | Acceleration ramp time (P0100) | s | Command | |
| AV | 15 | Deceleration Time | Deceleration ramp time (P0101) | s | Command | |
| AV | 16 | Speed in 13 bits | Motor speed, 13-bit scale (8192 = rated frequency) (P0681) | Command | ||
| AVmin | 17 | Serial/USB Speed Ref. | Speed reference, 13-bit scale (8192 = rated frequency) (P0683) | Command | ||
| AV | 18 | SoftPLC Parameter 3 | SoftPLC user parameter (P1012) | Command | ||
| AV | 19 | SoftPLC Parameter 4 | SoftPLC user parameter (P1013) | Command | ||
| AV | 20 | SoftPLC Parameter 16 | SoftPLC user parameter (P1025) | Command | ||
| AV | 21 | Main PID Aut. Setpoint | Main PID automatic setpoint (P1011) | Command | ||
| AV | 22 | Main PID Man. Setpoint | Main PID manual setpoint (P1014) | % | Command | |
| AV | 23 | Main PID Feedback | Main PID feedback (P1015) | Command | ||
| AV | 24 | Main PID Output | Main PID output (P1016) | % | Command | |
| AV | 25 | External PID Auto Setpoint | External PID automatic setpoint (P1060) | Command | ||
| AV | 26 | External PID Man. Setpoint | External PID manual setpoint (P1061) | % | Command | |
| AV | 27 | External PID Feedback | External PID feedback (P1062) | Command | ||
| AV | 28 | External PID Output | External PID output (P1063) | % | Command | |
| AV | 100 | Mailbox: param. number | Parameter number for mailbox access | Write | ||
| AV | 101 | Mailbox: param. value | Value read from or to write to the parameter | Write | ||
| BI | 0 | DI1 | Digital input 1 (P012 bit 0) | Read | 0=Off, 1=On | |
| BI | 1 | DI2 | Digital input 2 (P012 bit 1) | Read | 0=Off, 1=On | |
| BI | 2 | DI3 | Digital input 3 (P012 bit 2) | Read | 0=Off, 1=On | |
| BI | 3 | DI4 | Digital input 4 (P012 bit 3) | Read | 0=Off, 1=On | |
| BI | 4 | DI5 | Digital input 5 (P012 bit 4) | Read | 0=Off, 1=On | |
| BI | 5 | DI6 | Digital input 6 (P012 bit 5) | Read | 0=Off, 1=On | |
| BI | 6 | DI7 | Digital input 7 (P012 bit 6) | Read | 0=Off, 1=On | |
| BI | 7 | DI8 | Digital input 8 (P012 bit 7) | Read | 0=Off, 1=On | |
| BO | 0 | DO1 | Digital output 1 (P695 bit 0) | Command | 0=Off, 1=On | |
| BO | 1 | DO2 | Digital output 2 (P695 bit 1) | Command | 0=Off, 1=On | |
| BO | 2 | DO3 | Digital output 3 (P695 bit 2) | Command | 0=Off, 1=On | |
| BO | 3 | DO4 | Digital output 4 (P695 bit 3) | Command | 0=Off, 1=On | |
| BO | 4 | DO5 | Digital output 5 (P695 bit 4) | Command | 0=Off, 1=On | |
| BV | 0 | Reserved | Status word bit, reserved (P680 bit 0) | Read | ||
| BV | 1 | Run Command | Status: run command active (P680 bit 1) | Read | ||
| BV | 2 | Fire mode | Status: fire mode (P680 bit 2) | Read | 0=Off, 1=On | |
| BV | 3 | Reserved | Status word bit, reserved (P680 bit 3) | Read | ||
| BV | 4 | Quick Stop | Status: quick stop (P680 bit 4) | Read | 0=Inactive, 1=Active | |
| BV | 5 | 2nd Ramp | Status: second ramp (P680 bit 5) | Read | 0=Off, 1=On | |
| BV | 6 | Config. Mode | Status: configuration mode (P680 bit 6) | Read | 0=Normal, 1=Config | |
| BV | 7 | Alarm | Status: alarm active (P680 bit 7) | Read | 0=No Alarm, 1=Alarm | |
| BVmin | 8 | Running | Status: motor running (P680 bit 8) | Read | 0=Stopped, 1=Running | |
| BV | 9 | Enabled | Status: general enable (P680 bit 9) | Read | 0=Disabled, 1=Enabled | |
| BV | 10 | Forward | Status: direction (P680 bit 10) | Read | 0=Reverse, 1=Forward | |
| BV | 11 | JOG | Status: JOG (P680 bit 11) | Read | 0=Off, 1=On | |
| BV | 12 | Remote | Status: remote or local (P680 bit 12) | Read | 0=Local, 1=Remote | |
| BV | 13 | Undervoltage | Status: undervoltage (P680 bit 13) | Read | 0=No, 1=Undervoltage | |
| BV | 14 | Automatic PID | Status: PID manual or auto (P680 bit 14) | Read | 0=Auto, 1=Manual | |
| BVmin | 15 | Fault | Status: fault active (P680 bit 15) | Read | 0=No Fault, 1=Fault | |
| BVmin | 16 | Run/Stop | Command: run/stop (P682 bit 0) | Command | 0=Stop, 1=Run | |
| BVmin | 17 | General Enable | Command: general enable (P682 bit 1) | Command | 0=Disable, 1=Enable | |
| BV | 18 | Run Forward | Command: direction (P682 bit 2) | Command | 0=Reverse, 1=Forward | |
| BV | 19 | JOG Enable | Command: JOG (P682 bit 3) | Command | 0=Off, 1=On | |
| BVmin | 20 | Remote | Command: remote/local select (P682 bit 4) | Command | 0=Local, 1=Remote | |
| BV | 21 | 2nd Ramp | Command: second ramp (P682 bit 5) | Command | 0=Off, 1=On | |
| BV | 22 | Quick Stop | Command: quick stop (P682 bit 6) | Command | 0=Off, 1=On | |
| BVmin | 23 | Fault Reset | Command: fault reset (P682 bit 7) | Command | 0=Off, 1=Reset | |
| BV | 29 | Intern PID | Command: internal PID manual/auto (P682 bit 13) | Command | 0=Auto, 1=Manual | |
| BV | 30 | Extern PID | Command: external PID manual/auto (P682 bit 14) | Command | 0=Auto, 1=Manual | |
| BV | 100 | Mailbox: exec. read | Mailbox read trigger | Write | 0=Off, 1=On | |
| BV | 101 | Mailbox: exec. write | Mailbox write trigger | Write | 0=Off, 1=On |
No points match these filters.
Object ID lookup: WEG CFW503 point IDs by name
AI0AI1 ValueAI1AI2 ValueAI2AI3 ValueAO0AOx Value 1AO1AOx Value 2AO2AOx Value 3AV0Motor SpeedAV1Motor CurrentAV2DC Link Voltage (Ud)AV3Motor FrequencyAV4Motor VoltageAV5Motor TorqueAV6Output PowerAV7Heatsink TemperatureAV9Time PoweredAV10Time EnabledAV11kWh Output EnergyAV12Present AlarmAV13Present FaultAV14Acceleration TimeAV15Deceleration TimeAV16Speed in 13 bitsAV17Serial/USB Speed Ref.AV18SoftPLC Parameter 3AV19SoftPLC Parameter 4AV20SoftPLC Parameter 16AV21Main PID Aut. SetpointAV22Main PID Man. SetpointAV23Main PID FeedbackAV24Main PID OutputAV25External PID Auto SetpointAV26External PID Man. SetpointAV27External PID FeedbackAV28External PID OutputAV100Mailbox: param. numberAV101Mailbox: param. valueBI0DI1BI1DI2BI2DI3BI3DI4BI4DI5BI5DI6BI6DI7BI7DI8BO0DO1BO1DO2BO2DO3BO3DO4BO4DO5BV0ReservedBV1Run CommandBV2Fire modeBV3ReservedBV4Quick StopBV52nd RampBV6Config. ModeBV7AlarmBV8RunningBV9EnabledBV10ForwardBV11JOGBV12RemoteBV13UndervoltageBV14Automatic PIDBV15FaultBV16Run/StopBV17General EnableBV18Run ForwardBV19JOG EnableBV20RemoteBV212nd RampBV22Quick StopBV23Fault ResetBV29Intern PIDBV30Extern PIDBV100Mailbox: exec. readBV101Mailbox: exec. write
Integration notes
- The manual's AV unit column is shifted one row from AV 6 to AV 11 (it prints °C for Output Power, h for Heatsink Temperature, kWh for Time Enabled). Units here follow the parameter: AV 6 is left blank, AV 7 °C, AV 9-10 h, AV 11 kWh.
- BV 1 Run Command and BV 0/3 have no state or access entry in the table; they are status-word bits and are listed here as read-only.
- BV 20 Remote (command) is printed with states 'Reset/Off' in the object table; the P0682 bit 4 description (0 = Local, 1 = Remote) is used here.
- Some digital outputs may be missing depending on the plug-in module; AO 2 drives the frequency output (FO).
- The table marks counters and fault/alarm codes (AV 9, 10, 12, 13) as commandable; treat them as readings.
- Mailbox: write the parameter number to AV 100, then 1 to BV 100 to read the value into AV 101, or set AV 101 and write 1 to BV 101 to write it.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CFW503 (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WEG CFW503 (BACnet MS/TP)
How many BACnet points does the WEG CFW503 (BACnet MS/TP) have?
This list has 77 BACnet objects: 3 analog inputs, 3 analog outputs, 30 analog values, 8 binary inputs, 5 binary outputs, 28 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WEG CFW503 (BACnet MS/TP) BACnet points are writable?
41 of the 77 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WEG CFW503 (BACnet MS/TP) BACnet documentation?
The source is CFW503 BACnet User's Guide (10012735607 Rev. 00), revision 2025-05, published free by WEG at https://static.weg.net/medias/downloadcenter/hed/h7a/WEG-CFW503-manual-bacnet-communication-manual-10012735607-en.pdf.
What are the minimum BACnet points to integrate the WEG CFW503 (BACnet MS/TP)?
Start with BV 16 Run/Stop (Start/stop from the BMS); BV 17 General Enable (General enable; must be on to run); BV 20 Remote (Remote mode when P0220 selects Serial/USB); AV 17 Serial/USB Speed Ref. (Speed reference, 8192 = rated frequency); BV 23 Fault Reset (Reset a tripped drive); BV 8 Running (Running status); AV 3 Motor Frequency (Output frequency in Hz); AV 1 Motor Current (Motor amps); BV 15 Fault (Any active drive fault); AV 13 Present Fault (Active fault number).
How do I enable BMS control of the WEG CFW503 (BACnet MS/TP)?
Network commands only act when P0220-P0228 select Serial/USB: P0220 = 5/6 lets the control word set local/remote (BV 20), P0222 = 9 takes the reference from P0683 (AV 17), P0227 = 2 takes run/stop from the control word and P0226 = 5/6 sets direction. The drive needs both BV 17 General Enable and BV 16 Run/Stop.
Does the WEG CFW503 (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
P0314 Serial Watchdog (time limit 0-999, the manual gives no unit; 0 = off, factory 0): if no valid telegram arrives within that time the drive shows alarm A0128 (or fault F0228) and runs the P0313 action: 0 none, 1 ramp stop (factory), 2 general disable, 3 go to local, 4 local keeping commands, 5 fault. Timing starts at the first valid telegram after power-up.
Can the BMS supply sensor values to the WEG CFW503 (BACnet MS/TP)?
AV 21/AV 25 take the main and external PID automatic setpoints and AV 23/AV 27 the PID feedbacks when the drive's PID is used.
How do I check these points on the real CFW503 (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More WEG BACnet points lists
- Variable frequency drive
WEG CFW-11 (BACnet MS/TP)
WEG CFW-11 frequency inverters using BACnet MS/TP on the RS-485 port.
Also known as: CFW-11, CFW11, WEG CFW-11, CFW-11 BACnet, 10000831662 - Variable frequency drive
WEG CFW100 (BACnet MS/TP)
WEG CFW100 mini frequency inverters using BACnet MS/TP on the RS-485 port (plug-in communication module).
Also known as: CFW100, WEG CFW100, CFW100 BACnet, 10007481001 - Variable frequency drive
WEG CFW300 (BACnet MS/TP)
WEG CFW300 micro frequency inverters using BACnet MS/TP on the RS-485 port (plug-in communication module).
Also known as: CFW300, WEG CFW300, CFW300 BACnet, 10006901889, CFW320 - Variable frequency drive (HVAC)
WEG CFW701 HVAC drive (BACnet MS/TP)
WEG CFW701 HVAC-R frequency inverters using BACnet MS/TP on the RS-485 port.
Also known as: CFW701, WEG CFW701, CFW701 HVAC-R, CFW701 BACnet, 10001538519
Source: CFW503 BACnet User's Guide · 10012735607 Rev. 00 · rev. 2025-05. Object names, instances and units are reproduced as published; descriptions are our own.