WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10) BACnet points list
Updated 28 October 2026
These are the BACnet objects WaterFurnace publishes for its dual-compressor water-to-air heat pumps running the FX10 DDC controller. A BAS can read space, discharge and coil temperatures, occupancy and compressor/fan states, and can command occupancy, fan, compressor stages, the reversing valve and spare outputs directly. Setpoints and configuration live in flash-backed Analog/Multistate Values, so they should only be written occasionally.
This page lists 43 BACnet objects for the WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10) — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.
- Manufacturer
- WaterFurnace
- Model
- Dual Compressor Water-to-Air Heat Pump (FX10)
- Equipment
- Water-source heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 43 (25 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- PRODCWA-05, PRODCWA, WaterFurnace FX10
Reference only, provided as-is: verify against WaterFurnace’s current documentation and the live device before use. Not official WaterFurnace information. Terms of use.
BMS integration notes: WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)
The BAS can run this heat pump in two ways: command occupancy (MO1) and let the FX10 hold its occupied/unoccupied setpoints, or act as the thermostat and send fan, Y1, Y2 and O calls directly (MO2-MO5). Space temperature can be overridden from the network on AO2, and MO6 forces an emergency shutdown. Keep frequent writes on the volatile AO/MO points, not the flash-backed AV/MV setpoints.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MO 1 | Occupancy Command | Occupied/unoccupied/bypass/standby command | Write |
| MO 6 | Emergency Override | Network emergency shutdown | Write |
| AV 1 | Occupied Cool | Occupied cooling setpoint (flash; write rarely) | Write |
| AV 2 | Occupied Heat | Occupied heating setpoint (flash; write rarely) | Write |
| MO 7 | Alarm Reset | Reset manual-reset alarms | Write |
| MI 2 | Mode | Auto or shutdown status | Read |
| MI 5 | Comp1 Cmd Status | Compressor 1 commanded on/off | Read |
| AI 1 | Space Temp | Space sensor temperature (terminals RS/AIC) | Read |
| AI 2 | Discharge Air | Discharge (supply) air temperature | Read |
| AI 8 | nvoAlarms | Active alarm code | Read |
Enable & remote start
The sheet has no separate BAS-enable point. MO6 Emergency Override puts the unit in shutdown (5) or back to auto (1). MO2-MO5 let the BAS send fan, compressor and reversing-valve calls directly.
Sensors & values from the BMS
AO2 Space Temp Ovrd overrides the space temperature reading from the network. It is a volatile output, so it reverts to uncommanded after a power cycle. The sheet does not mention a network outdoor-air input.
Watch out for
- AV/MV points are stored in flash (about 2,000,000 writes); write them only manually or by schedule, never from automatic reset logic.
- Output points (AO/MO) are volatile and go back to uncommanded after a power cycle, so rewrite them after power is restored.
- If the BAS shows 254 as uncommanded instead of 255, every multistate value is one lower (0=Off, 1=On).
- MO8 (BO5 electric heat) is interlocked with BI4. The sheet says it needs MV2 Electric Heat Mode set to EmgHeat, which seems to conflict with MV2's own description, so confirm on site.
- Alarm Reset needs a write of 2 followed by 1.
WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Space Temp | Space sensor reading (terminals RS/AIC) | Read | ||
| AImin | 2 | Discharge Air | Discharge air sensor | Read | ||
| AI | 3 | Freeze Temp 1 | Water coil refrigerant temperature, circuit 1 | Read | ||
| AI | 4 | Freeze Temp 2 | Water coil refrigerant temperature, circuit 2 | Read | ||
| AI | 5 | Active Clg Setpt | Effective cooling setpoint | Read | ||
| AI | 6 | Active Hgt Setpt | Effective heating setpoint | Read | ||
| AI | 7 | Freeze Temp Limit | Low temperature limit for the water coil | Read | ||
| AImin | 8 | nvoAlarms | Active alarm code (see alarm table) | Read | 0=No Alarm; 1=Condensate Detected; 2=Comp 1 High Discharge Pressure; 3=Comp 1 Low Suction Pressure; 4=Circuit 1 Low Temp Limit on Coax; 5=Comp 2 High Discharge Pressure; 6=Comp 2 Low Suction Pressure; 7=Circuit 2 Low Temp Limit on Coax; 8=Circuit 1 Bad Refrigerant Temp Sensor; 9=Circuit 2 Bad Refrigerant Temp Sensor | |
| AI | 9 | Economizer Temp | Economizer water temperature sensor | Read | ||
| AO | 1 | Common Setpoint | Midpoint setpoint; moves heating and cooling setpoints together | Write | ||
| AO | 2 | Space Temp Ovrd | Network override of the space temperature reading | Write | ||
| AVmin | 1 | Occupied Cool | Occupied cooling setpoint (flash) | Write | ||
| AVmin | 2 | Occupied Heat | Occupied heating setpoint (flash) | Write | ||
| AV | 3 | Unoccupied Cool | Unoccupied cooling setpoint (flash) | Write | ||
| AV | 4 | Unoccupied Heat | Unoccupied heating setpoint (flash) | Write | ||
| AV | 5 | Economizer Setpt | Water temperature threshold for economizer operation | Write | ||
| AV | 6 | Max Hgt Setpt | Upper limit for the heating setpoint | Write | ||
| AV | 7 | Min Clg Setpt | Lower limit for the cooling setpoint | Write | ||
| AV | 8 | Remote Setpt Max | Maximum positive setpoint shift from the sensor | Write | ||
| AV | 9 | Remote Setpt Min | Maximum negative setpoint shift from the sensor | Write | ||
| AV | 10 | Zone Temp Offset | Calibration offset for the zone sensor | Write | ||
| AV | 11 | Econo Temp Offset | Calibration offset for the economizer water sensor | Write | ||
| MI | 1 | Effective Occupancy | Current occupancy status | Read | 1=Occupied; 2=Unoccupied; 3=Bypass (temporary occupancy) | |
| MImin | 2 | Mode | Current unit mode | Read | 1=Auto (Normal); 7=Off (Shutdown) | |
| MI | 3 | Comp/Fan Prove | DI4 proving contact; needs field current relay(s) | Read | 1=Off; 2=On | |
| MI | 4 | Fan Cmd Status | Commanded fan status | Read | 1=Off; 2=On | |
| MImin | 5 | Comp1 Cmd Status | Commanded compressor 1 status | Read | 1=Off; 2=On | |
| MI | 6 | Comp2 Cmd Status | Commanded compressor 2 status | Read | 1=Off; 2=On | |
| MI | 7 | Rev Valve Status | Commanded reversing valve position | Read | 1=Heating; 2=Cooling | |
| MI | 8 | BO-5/Elect Heat | Commanded state of BO5 (electric heat) | Read | 1=Off; 2=On | |
| MI | 9 | BO-9 Spare | Commanded state of spare BO9 | Read | 1=Off; 2=On | |
| MOmin | 1 | Occupancy Command | Network occupancy command | Write | 1=Occupied; 2=Unoccupied; 3=Bypass; 4=Standby | |
| MO | 2 | Fan Command | Network fan call (thermostat G) | Write | 1=Off; 2=On | |
| MO | 3 | Comp1 Command (Y1) | Network compressor 1 call (thermostat Y1) | Write | 1=Off; 2=On | |
| MO | 4 | Comp2 Command (Y2) | Network compressor 2 call (thermostat Y2) | Write | 1=Off; 2=On | |
| MO | 5 | Rev Vlv Cmd | Network reversing valve call (thermostat O) | Write | 1=Heat; 2=Cooling | |
| MOmin | 6 | Emergency Override | Network emergency shutdown | Write | 1=Auto; 5=Shutdown | |
| MOmin | 7 | Alarm Reset | Reset manual-reset alarms: write 2, then back to 1 | Write | ||
| MO | 8 | BO5 Elect Heat | Network control of BO5 electric heat (see MV2) | Write | 1=Off; 2=On | |
| MO | 9 | BO9 Spare | Network control of spare output BO9 | Write | 1=Off; 2=On | |
| MV | 1 | Economizer Enable | Enable economizer logic (flash) | Write | 1=Off; 2=On | |
| MV | 2 | Electric Heat Mode | BO5 as emergency heat or network-controlled (flash) | Write | 1=EmgHeat; 2=Network Control | |
| MV | 3 | Fan Operation | Continuous or cycled fan (flash) | Write | 1=Continuous; 2=Cycled |
No points match these filters.
Object ID lookup: WaterFurnace Dual Compressor Water-to-Air Heat Pump point IDs by name
AI1Space TempAI2Discharge AirAI3Freeze Temp 1AI4Freeze Temp 2AI5Active Clg SetptAI6Active Hgt SetptAI7Freeze Temp LimitAI8nvoAlarmsAI9Economizer TempAO1Common SetpointAO2Space Temp OvrdAV1Occupied CoolAV2Occupied HeatAV3Unoccupied CoolAV4Unoccupied HeatAV5Economizer SetptAV6Max Hgt SetptAV7Min Clg SetptAV8Remote Setpt MaxAV9Remote Setpt MinAV10Zone Temp OffsetAV11Econo Temp OffsetMI1Effective OccupancyMI2ModeMI3Comp/Fan ProveMI4Fan Cmd StatusMI5Comp1 Cmd StatusMI6Comp2 Cmd StatusMI7Rev Valve StatusMI8BO-5/Elect HeatMI9BO-9 SpareMO1Occupancy CommandMO2Fan CommandMO3Comp1 Command (Y1)MO4Comp2 Command (Y2)MO5Rev Vlv CmdMO6Emergency OverrideMO7Alarm ResetMO8BO5 Elect HeatMO9BO9 SpareMV1Economizer EnableMV2Electric Heat ModeMV3Fan Operation
Integration notes
- Output-type points are volatile and fall back to uncommanded after a power cycle; unlimited writes.
- Value-type points (AV/MV) are stored in flash (about 2,000,000 write life); never write them from automatic reset logic.
- Multistate numbers assume the BAS shows 255 as uncommanded; if yours shows 254, every state number is one lower (0=Off, 1=On).
- No engineering units are printed in the source; temperatures are presumably degrees F.
- The sheet does not state the BACnet transport.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Dual Compressor Water-to-Air Heat Pump (FX10) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)
How many BACnet points does the WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10) have?
This list has 43 BACnet objects: 9 analog inputs, 2 analog outputs, 11 analog values, 9 multi-state inputs, 9 multi-state outputs, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10) BACnet points are writable?
25 of the 43 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10) BACnet documentation?
The source is BACnet Points for Dual Compressor Water-to-Air Heat Pumps Utilizing the FX10 Controller (PRODCWA-05), revision 2013-02, published free by WaterFurnace at https://www.waterfurnace.com/downloads/ddc/BACnet-Resources/BACnet-points-pdfs/PRODCWA-05.pdf.
What are the minimum BACnet points to integrate the WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)?
Start with MO 1 Occupancy Command (Occupied/unoccupied/bypass/standby command); MO 6 Emergency Override (Network emergency shutdown); AV 1 Occupied Cool (Occupied cooling setpoint (flash; write rarely)); AV 2 Occupied Heat (Occupied heating setpoint (flash; write rarely)); MO 7 Alarm Reset (Reset manual-reset alarms); MI 2 Mode (Auto or shutdown status); MI 5 Comp1 Cmd Status (Compressor 1 commanded on/off); AI 1 Space Temp (Space sensor temperature (terminals RS/AIC)); AI 2 Discharge Air (Discharge (supply) air temperature); AI 8 nvoAlarms (Active alarm code).
How do I enable BMS control of the WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)?
The sheet has no separate BAS-enable point. MO6 Emergency Override puts the unit in shutdown (5) or back to auto (1). MO2-MO5 let the BAS send fan, compressor and reversing-valve calls directly.
Can the BMS supply sensor values to the WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)?
AO2 Space Temp Ovrd overrides the space temperature reading from the network. It is a volatile output, so it reverts to uncommanded after a power cycle. The sheet does not mention a network outdoor-air input.
How do I check these points on the real Dual Compressor Water-to-Air Heat Pump (FX10)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More WaterFurnace BACnet points lists
- Water-to-water heat pump controller
WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps
WaterFurnace NXW and SKW dual-scroll water-to-water heat pumps (including header rack arrangements) with the Aurora HydroLink controller.
Also known as: PL2500EW, HydroLink, NXW, SKW, WCHDM, HYDWWB01 - Modular chiller / water-to-water heat pump controller
WaterFurnace Aurora HydroLink2 for TruClimate 100 / TruClimate 500 Modular Chillers
WaterFurnace TruClimate 100 dual scroll (NXW) and TruClimate 500 modular chillers with the Aurora HydroLink2 controller, including 4-pipe and 6-pipe header rack builds and variable speed modules.
Also known as: HydroLink2, HydroLink 2, TruClimate 100, TruClimate 500, NXW, HydroLink2 BACnet Objects 3.04 - Water-cooled screw chiller / heat pump controller
WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller
WaterFurnace TruClimate 700 single screw water-to-water chillers with the Aurora HydroLink2 controller.
Also known as: HydroLink2 Single Screw, TruClimate 700, HydroLink2 - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Dual Compressor Rooftop Unit with Economizer
WaterFurnace dual-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump
WaterFurnace dual-compressor water-to-air heat pumps with two Aurora Base Controllers (ABC A and B) and the Aurora UPC.
Also known as: PL1500EW, Aurora Universal Protocol Converter, Aurora UPC dual compressor - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer
WaterFurnace single-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump
WaterFurnace single-compressor water-to-air heat pumps with the Aurora controls and the Aurora UPC protocol converter.
Also known as: AG1569EW, Aurora Universal Protocol Converter, Aurora UPC, UPCSWASTD01-01 - Water-source heat pump controller
WaterFurnace Aurora UPC, Variable Speed Water-Source Heat Pump
WaterFurnace variable speed water-to-air heat pumps with Aurora controls and the Aurora UPC.
Also known as: PL1700EW, Aurora Universal Protocol Converter, Aurora UPC variable speed - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace dual-compressor water-to-air heat pumps with hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PRODCWA-RH-03, PRODCWA-RH, WaterFurnace dual compressor reheat FX10, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Envision single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWWE-01, PROSSWWE, Envision Water-to-Water, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton
WaterFurnace Envision 1 to 6 ton water-to-air heat pumps with the DDC controller option.
Also known as: Envision BACnet Variables, Envision BACnet Variables with BI, Envision 1-6 Ton - Geothermal heat pump zoning controller
WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet
WaterFurnace geothermal heat pumps with Aurora controls and the IntelliZone2 zoning system (up to 6 zones), read through the Aurora BACnet controller.
Also known as: IZ2, IntelliZone2, IntelliZone 2, Aurora IZ2 - Water-to-water heat pump / reversible chiller controller
WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)
WaterFurnace dual-compressor reversible chiller (water-to-water) heat pumps with the FX10 controller.
Also known as: PRODCWWE-06B, PRODCWWE-07B, PRODCWWE-08B, PRODCWWE - Water-source heat pump controller (console)
WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)
WaterFurnace single-compressor water-to-air console heat pumps fitted with the FX10 DDC controller.
Also known as: PROSSWAC-02, PROSSWAC, WaterFurnace console heat pump FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace single-compressor water-to-air heat pumps without hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PROFXENV-00, PROFXENV, Envision FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace single-compressor water-to-air heat pumps with hot gas reheat and the FX10 DDC controller.
Also known as: PROFXENV-RH-00, PROFXENV-RH, Envision hot gas reheat, WaterFurnace FX10 - Water-source DOAS controller with energy recovery
WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)
WaterFurnace Versatec 700 indoor dedicated outdoor air systems: up to four variable speed water-source heat pump modules with an energy recovery wheel, economizers and DCV, on the Aurora UPC.
Also known as: Versatec 700, Versatec DOAS, WaterFurnace DOAS, DOAS BACnet Point List 1.00 - Water-to-water heat pump controller
WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec dual-compressor water-to-water heat pumps with the FX10 DDC controller and expansion board.
Also known as: PRODCWW-02, PRODCWW, Versatec Dual Compressor, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Versatec Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWW-03, PROSSWW, Versatec Water-to-Water, WaterFurnace FX10
Source: BACnet Points for Dual Compressor Water-to-Air Heat Pumps Utilizing the FX10 Controller · PRODCWA-05 · rev. 2013-02. Object names, instances and units are reproduced as published; descriptions are our own.