- VT8650 Rooftop Unit and Heat Pump Controller
Rooftop unit controller (room thermostat, conventional or heat-pump RTUs) · BACnet points list
Viconics VT8650 Rooftop Unit and Heat Pump Controller BACnet points list
Updated 7 November 2026
The VT8650 is the rooftop unit and heat pump version of the Viconics VT8000 room controller. It is a BACnet application-specific controller (B-ASC) on BACnet MS/TP, with BACnet IP and Wi-Fi status objects for units set up through the Wi-Fi configuration web page. MV 119 Application selects rooftop or heat pump; the objects cover G/Y1/Y2/W1/W2-OB stage outputs, economizer and fresh-air limits, CO2-based IAQ control, supply and mixed air temperatures, and the common VT8000 display, Lua and ZigBee wireless sensor objects.
This page lists 456 BACnet objects for the Viconics VT8650 Rooftop Unit and Heat Pump Controller — 280 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Viconics’s own free documentation, linked below.
- Manufacturer
- Viconics
- Model
- VT8650 Rooftop Unit and Heat Pump Controller
- Equipment
- Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 456 (280 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- 2.6
- Also known as
- VT8650, Viconics VT8650, VT8000 VT8650, Schneider Electric VT8650, Schneider Electric SpaceLogic SE8650
Reference only, provided as-is: verify against Viconics’s current documentation and the live device before use. Not official Viconics information. Terms of use.
BMS integration notes: Viconics VT8650 Rooftop Unit and Heat Pump Controller
Command occupancy with MV 10, mode with MV 16 and fan mode with MV 17, and write the occupied setpoints AV 39/AV 40. Read AV 100 room temperature, MI 33 effective occupancy, MV 112 control status, the G fan output BO 25 and the fan lock alarm BV 39. Write at priorities 4-16 for live control; avoid 1-3.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 10 | Occupancy Command | BMS occupancy: local, occupied or unoccupied | Command |
| MV 16 | System Mode | Off / auto / cool / heat | Command |
| MV 17 | Fan Mode | Fan mode: on / auto / smart | Command |
| AV 39 | Occupied Heat Setpoint | Occupied heating setpoint | Command |
| AV 40 | Occupied Cool Setpoint | Occupied cooling setpoint | Command |
| MV 112 | Control Status | Current state: off, cooling or heating | Command |
| BO 25 | G Fan Status | Fan (G) output state | Command |
| MI 33 | Effective Occupancy | Actual occupancy state | Read |
| AV 100 | Room Temperature | Space temperature used for control | Command |
| BV 39 | Fan Lock Alarm | Fan lock alarm (1 = on) | Command |
Enable & remote start
No enable switch is needed. The BMS writes MV 10 Occupancy Command (1 = Loc. occ, the controller decides locally; 2 = Occupied; 3 = Unoccupied) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.
Sensors & values from the BMS
The guide has no BMS-written room temperature object: MV 145 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.
Network setup
- The Device Object_Identifier and Object_Name are writable; no default device instance is printed in the guide.
- BACnet MS/TP baud rate is MV 8 (9600, 19200, 38400, 57600, 76800, 115200 or Auto; default Auto). Max_Master is writable, 0-127, default 127.
- MI 317 shows whether BACnet IP is enabled; it is set from the BACnet/IP page of the Wi-Fi configuration web page.
- COV subscriptions are supported (DS-COV-B), along with an internal schedule (SCHED-I-B) and time synchronization.
Watch out for
- Priorities 1-3 are stored in EEPROM and lock the value at the thermostat, even after a power cycle, until it is released at the same priority or factory defaults are restored. Use them only for fixed configuration.
- Priorities 4-16 are held in RAM and are lost on a power cycle, so the BMS has to write them again after the controller restarts.
- The relinquish default (priority 17) is the value the occupant changes at the thermostat, which is kept through power cycles. Writes at 4-16 override local changes to setpoints and modes.
- The controller does not support segmented requests or responses; keep Read Property Multiple requests small.
- MV 119 Application, the stage counts (AV 75, AV 87) and MV 117 reversing valve setting are commissioning settings; do not write them cyclically.
Viconics VT8650 Rooftop Unit and Heat Pump Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 2 | Light Sensor Level | Range 0 to 30000 | Read | ||
| AI | 4 | Relative Humidity Raw Value | Range 0 to 1000 | Read | ||
| AI | 5 | UI20 Raw Value | Range 0 to 4095 | Read | ||
| AI | 7 | UI23 Raw Value | Range 0 to 4095 | Read | ||
| AI | 8 | UI22 Raw Value | Range 0 to 4095 | Read | ||
| AI | 9 | UI24 Raw Value | Range 0 to 4095 | Read | ||
| AI | 31 | UI19 Raw Value | Range 0 to 4095 | Read | ||
| AI | 32 | Temperature Raw Value | Range -400 to 1220 | Read | ||
| AI | 33 | UI16 Raw Value | Range 0 to 4095 | Read | ||
| AI | 34 | UI17 Raw Value | Range 0 to 4095 | Read | ||
| AI | 315 | Wireless Device 1 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 316 | Wireless Device 2 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 317 | Wireless Device 3 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 318 | Wireless Device 4 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 319 | Wireless Device 5 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 320 | Wireless Device 6 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 321 | Wireless Device 7 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 322 | Wireless Device 8 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 323 | Wireless Device 9 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 324 | Wireless Device 10 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 329 | Effective Setpoint | Range 40°F (4°C) to 100°F (38°C) | °F/°C | Read | |
| AI | 330 | Paired ZigBee Devices | Range 0 to 20 | Read | ||
| AI | 340 | Therm. Raw Value | Range -400 to 1220 | Read | ||
| AI | 341 | SH Therm. Raw Value | Range -400 to 1220 | Read | ||
| AI | 343 | Wi-Fi Module Boot Count | Range 0 to 32767 | Read | ||
| AI | 355 | Wireless Device 11 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 356 | Wireless Device 12 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 357 | Wireless Device 13 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 358 | Wireless Device 14 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 359 | Wireless Device 15 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 360 | Wireless Device 16 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 361 | Wireless Device 17 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 362 | Wireless Device 18 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 363 | Wireless Device 19 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 364 | Wireless Device 20 - Temperature | Range -40°F (-40°C) to 185°F (85°C) | °F/°C | Read | |
| AI | 365 | Wireless Device 1 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 366 | Wireless Device 2 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 367 | Wireless Device 3 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 368 | Wireless Device 4 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 369 | Wireless Device 5 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 370 | Wireless Device 6 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 371 | Wireless Device 7 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 372 | Wireless Device 8 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 373 | Wireless Device 9 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 374 | Wireless Device 10 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 375 | Wireless Device 11 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 376 | Wireless Device 12 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 377 | Wireless Device 13 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 378 | Wireless Device 14 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 379 | Wireless Device 15 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 380 | Wireless Device 16 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 381 | Wireless Device 17 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 382 | Wireless Device 18 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 383 | Wireless Device 19 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 384 | Wireless Device 20 - Humidity | Range 0 to 100 | %RH | Read | |
| AI | 385 | Wireless Device 1 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 386 | Wireless Device 2 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 387 | Wireless Device 3 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 388 | Wireless Device 4 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 389 | Wireless Device 5 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 390 | Wireless Device 6 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 391 | Wireless Device 7 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 392 | Wireless Device 8 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 393 | Wireless Device 9 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 394 | Wireless Device 10 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 395 | Wireless Device 11 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 396 | Wireless Device 12 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 397 | Wireless Device 13 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 398 | Wireless Device 14 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 399 | Wireless Device 15 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 400 | Wireless Device 16 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 401 | Wireless Device 17 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 402 | Wireless Device 18 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 403 | Wireless Device 19 - CO2 | Range 0 to 5000 | ppm | Read | |
| AI | 404 | Wireless Device 20 - CO2 | Range 0 to 5000 | ppm | Read | |
| AO | 21 | PI Heating Demand | Default 0, range 0 to 100 | % | Command | |
| AO | 22 | PI Cooling Demand | Default 0, range 0 to 100 | % | Command | |
| AO | 23 | Economizer Demand | Default 0, range 0 to 100 | % | Command | |
| AO | 24 | Analog Output Heat Demand | Default 0, range 0 to 100 | % | Command | |
| AO | 123 | UO11 Analog Output | Default 0, range 0 to 10 | V | Command | |
| AO | 124 | UO12 Analog Output | Default 0, range 0 to 10 | V | Command | |
| AO | 125 | UO9 Analog Output | Default 0, range 0 to 10 | V | Command | |
| AO | 126 | UO10 Analog Output | Default 0, range 0 to 10 | V | Command | |
| AV | 2 | User HMI | Default 0, range 0 to 12 | Command | ||
| AV | 3 | Low Backlight | Default 60, range 0 to 100 | % | Command | |
| AV | 4 | Night Backlight | Default 5, range 0 to 100 | % | Command | |
| AV | 7 | Calibrate Room Temperature Sensor | Default 0°F (0.0°C), range -5°F (-2.5°C) to 5°F (2.5°C) | Δ°F/Δ°C | Command | |
| AV | 8 | Calibrate Humidity Sensor | Default 0, range -15 to 15 | %RH | Command | |
| AV | 10 | COM Address | Default 254, range 0 to 254 | Command | ||
| AV | 16 | BACnet Stack Poll Rate | Default 4, range 1 to 5 | Command | ||
| AV | 20 | Discharge Low Limit | Default 45°F (7°C), range 35°F (2°C) to 65°F (18°C) | °F/°C | Command | |
| AV | 21 | Minimum Fresh Air | Default 0, range 0 to 20000 | CFM | Command | |
| AV | 22 | Maximum Fresh Air | Default 0, range 0 to 20000 | CFM | Command | |
| AV | 23 | Minimum CO2 | Default 800, range 0 to 5000 | ppm | Command | |
| AV | 24 | Maximum CO2 | Default 1200, range 0 to 5000 | ppm | Command | |
| AV | 25 | Lua Parameter A (AV25) | Default 0, range -32768 to 32767 | Command | ||
| AV | 26 | Lua Parameter B (AV26) | Default 0, range -32768 to 32767 | Command | ||
| AV | 27 | Lua Parameter C (AV27) | Default 0, range -32768 to 32767 | Command | ||
| AV | 28 | Lua Parameter D (AV28) | Default 0, range -32768 to 32767 | Command | ||
| AV | 29 | Lua Parameter E (AV29) | Default 0, range -32768 to 32767 | Command | ||
| AV | 30 | Lua Parameter F (AV30) | Default 0, range -32768 to 32767 | Command | ||
| AVmin | 39 | Occupied Heat Setpoint | Default 72°F (22°C), range 40°F (4.5°C) to 90°F (32°C) | °F/°C | Command | |
| AVmin | 40 | Occupied Cool Setpoint | Default 75°F (24°C), range 54°F (12°C) to 100°F (38°C) | °F/°C | Command | |
| AV | 41 | Standby Heat Setpoint | Default 69°F (21°C), range 40°F (4.5°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 42 | Standby Cool Setpoint | Default 78°F (21°C), range 54°F (12°C) to 100°F (38°C) | °F/°C | Command | |
| AV | 43 | Unoccupied Heat Setpoint | Default 62°F (17°C), range 40°F (4.5°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 44 | Unoccupied Cool Setpoint | Default 80°F (27°C), range 54°F (12°C) to 100°F (38°C) | °F/°C | Command | |
| AV | 45 | Default Heating Setpoint | Default 72°F (22°C), range 65°F (18°C) to 80°F (27°C) | °F/°C | Command | |
| AV | 46 | Standby Temperature Differential | Default 4°F (2.0°C), range 1°F (0.5°C) to 5°F (2.5°C) | Δ°F/Δ°C | Command | |
| AV | 56 | Main Password | Default 0, range 0 to 9999 | Command | ||
| AV | 57 | User Password | Default 0, range 0 to 9999 | Command | ||
| AV | 58 | Heating Setpoint Limit | Default 90°F (32°C), range 40°F (4.5°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 59 | Cooling Setpoint Limit | Default 54°F (12°C), range 54°F (12°C) to 100°F (38°C) | °F/°C | Command | |
| AV | 62 | Temporary Occupancy Time | Default 2, range 0 to 24 | h | Command | |
| AV | 63 | Minimum Deadband | Default 3°F (1.5°C), range 2°F (1.0°C) to 5°F (2.5°C) | Δ°F/Δ°C | Command | |
| AV | 65 | Proportional Band | Default 3, range 3 to 10 | Command | ||
| AV | 67 | Standby Time | Default 0.5, range 0.5 to 24 | h | Command | |
| AV | 68 | Unoccupied Time | Default 0, range 0 to 24 | h | Command | |
| AV | 71 | Dehumidification Setpoint | Default 50, range 30 to 95 | %RH | Command | |
| AV | 72 | Dehumidification Hysteresis | Default 5, range 2 to 20 | %RH | Command | |
| AV | 74 | Calibrate Outside Temperature Sensor | Default 0°F (0°C), range -5°F (-2.5°C) to 5°F (2.5°C) | Δ°F/Δ°C | Command | |
| AV | 75 | Number of Cooling Stages | Default 2, range 1 to 2 | Command | ||
| AV | 76 | Power-up Delay | Default 10, range 10 to 120 | s | Command | |
| AV | 78 | Economizer Minimum Position | Default 0, range 0 to 100 | % | Command | |
| AV | 81 | Economizer Maximum Position | Default 100, range 0 to 100 | % | Command | |
| AV | 82 | High balance point | Default 90°F (32°C), range 34°F (1°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 83 | Low balance point | Default -12°F (-24°C), range -40°F (-40°C) to 30°F (-1°C) | °F/°C | Command | |
| AV | 84 | Heating CPH | Default 4, range 3 to 8 | cycles/h | Command | |
| AV | 85 | Cooling CPH | Default 4, range 3 to 4 | cycles/h | Command | |
| AV | 86 | Anti Short Cycle Time | Default 2, range 0 to 5 | min | Command | |
| AV | 87 | Number of Heating Stages | Default 2, range 0 to 2 | Command | ||
| AV | 88 | Heating Demand Limit | Default 0, range 0 to 100 | % | Command | |
| AV | 89 | Cooling Demand Limit | Default 0, range 0 to 100 | % | Command | |
| AV | 91 | Heating Lockout from Outside Air Temperature | Default 120°F (49°C), range -15°F (-26°C) to 120°F (49°C) | °F/°C | Command | |
| AV | 92 | Keyboard Value | Default 0, range 0 to 35 | Command | ||
| AV | 93 | Cooling Lockout | Default -40°F (-40°C), range -40°F (-40°C) to 95°F (35°C) | °F/°C | Command | |
| AV | 94 | Supply Air Setpoint | Default 55°F (13°C), range 50°F (10°C) to 90°F (32°C) | °F/°C | Command | |
| AV | 95 | Changeover Setpoint | Default 55°F (13°C), range 14°F (10°C) to 70°F (21°C) | °F/°C | Command | |
| AV | 96 | Fresh Air Range Upper Limit | Default 0, range 0 to 20,000 | CFM | Command | |
| AV | 97 | Minimum Supply Heat | Default 64°F (18°C), range 50°F (10°C) to 72°F (22°C) | °F/°C | Command | |
| AV | 98 | Supply Heat Lockout | Default 32°F (0°C), range -15°F (-26°C) to 120°F (49°C) | °F/°C | Command | |
| AV | 99 | Discharge High Limit | Default 120°F (49°C), range 70°F (21°C) to 150°F (65.5°C) | °F/°C | Command | |
| AVmin | 100 | Room Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 122°F (50°C) | °F/°C | Command | |
| AV | 101 | Outdoor Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 102 | UI22 Supply Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 103 | Room Humidity | Default 0, range 0 to 100 | %RH | Command | |
| AV | 104 | UI19 Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 105 | UI20 Remote Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 106 | CO2 Level | Default 0, range 0 to 5000 | ppm | Command | |
| AV | 107 | Airflow Level | Default 0, range 0 to 20,000 | CFM | Command | |
| AV | 108 | UI19 Analog Input | Default 0, range 0 to 10 | V | Command | |
| AV | 109 | UI24 Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 111 | UI16 Analog Input | Default 0, range 0 to 10 | V | Command | |
| AV | 112 | UI17 Analog Input | Default 0, range 0 to 10 | V | Command | |
| AV | 113 | UI20 Analog Input | Default 0, range 0 to 10 | V | Command | |
| AV | 114 | UI22 Analog Input | Default 0, range 0 to 10 | V | Command | |
| AV | 115 | UI23 Analog Input | Default 0, range 0 to 10 | V | Command | |
| AV | 116 | UI24 Analog Input | Default 0, range 0 to 10 | V | Command | |
| AV | 117 | UI16 Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 118 | UI17 Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 120 | UI20 Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 121 | UI22 Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 122 | UI23 Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 125 | Mixed Air Temperature | Default -40°F (-40°C), range -40°F (-40°C) to 180°F (82°C) | °F/°C | Command | |
| AV | 202 | UI19 Lua | Default 0, range -32768 to 32767 | Command | ||
| AV | 203 | UI20 Lua | Default 0, range -32768 to 32767 | Command | ||
| AV | 204 | UI22 Lua | Default 0, range -32768 to 32767 | Command | ||
| AV | 205 | UI23 Lua | Default 0, range -32768 to 32767 | Command | ||
| AV | 206 | UI24 Lua | Default 0, range -32768 to 32767 | Command | ||
| AV | 209 | Ambient Low Temperature Threshold | Default 40°F (4°C), range 32°F (0°C) to 50°F (10°C) | °F/°C | Command | |
| AV | 210 | Temperature Alarm Hysteresis | Default 2°F (1°C), range 0°F (0°C) to 10°F (5.5°C) | Δ°F/Δ°C | Command | |
| AV | 211 | Load Shedding Offset | Default 4°F (2°C), range 4°F (2°C) to 10°F (5.5°C) | Δ°F/Δ°C | Command | |
| AV | 225 | Lua Parameter G (AV225) | Default 0, range -32768 to 32767 | Command | ||
| AV | 226 | Lua Parameter H (AV226) | Default 0, range -32768 to 32767 | Command | ||
| AV | 227 | Lua Parameter I (AV227) | Default 0, range -32768 to 32767 | Command | ||
| AV | 228 | Lua Parameter J (AV228) | Default 0, range -32768 to 32767 | Command | ||
| AV | 229 | Lua Parameter K (AV229) | Default 0, range -32768 to 32767 | Command | ||
| AV | 230 | Lua Parameter L (AV230) | Default 0, range -32768 to 32767 | Command | ||
| AV | 270 | Standby Screen Delay | Default 150, range 5 to 300 | s | Command | |
| AV | 275 | Ambient High Temperature Threshold | Default 86°F (30°C), range 32°F (0°C) to 122°F (50°C) | °F/°C | Command | |
| AV | 276 | Refrigeration High Temperature Threshold | Default 40°F (4°C), range 32°F (0°C) to 60°F (16°C) | °F/°C | Command | |
| AV | 277 | Refrigeration Low Temperature Threshold | Default 32°F (0°C), range 32°F (0°C) to 50°F (10°C) | °F/°C | Command | |
| AV | 278 | Freezer High Temperature Threshold | Default 0°F (-18°C), range -40°F (-40°C) to 32°F (0°C) | °F/°C | Command | |
| BI | 29 | UI16 Binary Input | Read | 0=Activated, 1=Not Activated | ||
| BI | 30 | UI17 Binary Input | Read | 0=Activated, 1=Not Activated | ||
| BI | 91 | UI19 Binary Input | Read | 0=Activated, 1=Not Activated | ||
| BI | 94 | UI20 Binary Input | Read | 0=Activated, 1=Not Activated | ||
| BI | 95 | UI22 Binary Input | Read | 0=Activated, 1=Not Activated | ||
| BI | 96 | UI23 Binary Input | Read | 0=Activated, 1=Not Activated | ||
| BI | 97 | UI24 Binary Input | Read | 0=Activated, 1=Not Activated | ||
| BOmin | 25 | G Fan Status | Default 0 | Command | 0=Off, 1=On | |
| BO | 26 | Y1 Status | Default 0 | Command | 0=Off, 1=On | |
| BO | 27 | Y2 Status | Default 0 | Command | 0=Off, 1=On | |
| BO | 28 | W1 Status | Default 0 | Command | 0=Off, 1=On | |
| BO | 29 | W2/OB Status | Default 0 | Command | 0=Off, 1=On | |
| BO | 94 | UO10 Binary Output | Default 0 | Command | 0=Off, 1=On | |
| BO | 98 | BO1 Auxiliary Binary Output | Default 0 | Command | 0=Off, 1=On | |
| BO | 101 | UO11 Binary Output | Default 0 | Command | 0=Off, 1=On | |
| BO | 102 | UO12 Binary Output | Default 0 | Command | 0=Off, 1=On | |
| BV | 1 | Door Contact Status | Default 0 | Command | 0=Closed, 1=Open | |
| BV | 2 | Door Contact Installed | Default 0 | Command | 0=No, 1=Yes | |
| BV | 3 | Window Contact Status | Default 0 | Command | 0=Closed, 1=Open | |
| BV | 4 | Window Contact Installed | Default 0 | Command | 0=No, 1=Yes | |
| BV | 5 | Low Battery Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 6 | Force High Backlight | Default 0 | Command | 0=Off, 1=On | |
| BV | 7 | Display Long Screen Message | Default 0 | Command | 0=Off, 1=On | |
| BV | 8 | Clock Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 10 | Exception Status | Default 0 | Command | 0=Off, 1=On | |
| BV | 32 | PIR Local Motion | Default 0 | Command | 0=No motion, 1=Motion | |
| BV | 35 | Window Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 36 | Filter Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 37 | Service Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 38 | Dehumidification Status | Default 0 | Command | 0=Off, 1=On | |
| BVmin | 39 | Fan Lock Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 40 | Smart Recovery Status | Default 0 | Command | 0=Off, 1=On | |
| BV | 41 | CO2 Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 42 | Low Fresh Air Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 43 | Frost Protection Alarm | Default 0 | Command | 0=Off, 1=On | |
| BV | 44 | Water Leak | Default 0 | Command | 0=Off, 1=On | |
| BV | 45 | Water Leak Sensor Installed | Default 0 | Command | 0=No, 1=Yes | |
| BV | 46 | Water leak sensor status | Default 0 | Command | 0=Normal, 1=Leak | |
| BV | 47 | Low Temperature | Default 0 | Command | 0=Off, 1=On | |
| BV | 48 | Load Shedding Demand | Default 0 | Command | 0=Off, 1=On | |
| BV | 49 | Load Shedding Status | Default 0 | Command | 0=Off, 1=On | |
| BV | 50 | Load Shedding Override | Default 0 | Command | 0=Off, 1=On | |
| BV | 53 | High Temperature | Default 0 | Command | 0=Off, 1=On | |
| BV | 200 | ZigBee PIR Sensor Installed | Default 0 | Command | 0=Off, 1=On | |
| BV | 201 | ZigBee Sensor Motion | Default 0 | Command | 0=No motion, 1=Motion | |
| CSV | 1 | Short Screen Message Text | Text, up to 26 characters | Write | ||
| CSV | 2 | Long Screen Message Text | Text, up to 480 characters | Write | ||
| CSV | 3 | External Memory Revision | Text | Write | ||
| CSV | 4 | Wi-Fi Device Name | Text | Write | ||
| CSV | 5 | Wi-Fi Firmware Version | Text | Write | ||
| CSV | 6 | MAC Address | Text | Write | ||
| CSV | 7 | Wi-Fi Network SSID | Text | Write | ||
| CSV | 8 | Wi-Fi Network IP Address | Text | Write | ||
| CSV | 9 | ZigBee Firmware Revision | Text | Write | ||
| CSV | 10 | Zigbee IEEE Address | Text | Write | ||
| CSV | 11 | Wireless Device 1 - Address | Text | Write | ||
| CSV | 12 | Wireless Device 2 - Address | Text | Write | ||
| CSV | 13 | Wireless Device 3 - Address | Text | Write | ||
| CSV | 14 | Wireless Device 4 - Address | Text | Write | ||
| CSV | 15 | Wireless Device 5 - Address | Text | Write | ||
| CSV | 16 | Wireless Device 6 - Address | Text | Write | ||
| CSV | 17 | Wireless Device 7 - Address | Text | Write | ||
| CSV | 18 | Wireless Device 8 - Address | Text | Write | ||
| CSV | 19 | Wireless Device 9 - Address | Text | Write | ||
| CSV | 20 | Wireless Device 10 - Address | Text | Write | ||
| CSV | 21 | Wireless Device 11 - Address | Text | Write | ||
| CSV | 22 | Wireless Device 12 - Address | Text | Write | ||
| CSV | 23 | Wireless Device 13 - Address | Text | Write | ||
| CSV | 24 | Wireless Device 14 - Address | Text | Write | ||
| CSV | 25 | Wireless Device 15 - Address | Text | Write | ||
| CSV | 26 | Wireless Device 16 - Address | Text | Write | ||
| CSV | 27 | Wireless Device 17 - Address | Text | Write | ||
| CSV | 28 | Wireless Device 18 - Address | Text | Write | ||
| CSV | 29 | Wireless Device 19 - Address | Text | Write | ||
| CSV | 30 | Wireless Device 20 - Address | Text | Write | ||
| MI | 2 | ZigBee Network Status | Read | 1=Not det., 2=Pwr on, 3=No NWK, 4=Joined, 5=Online | ||
| MImin | 33 | Effective Occupancy | Read | 1=Occupied, 2=Unoccupied, 3=Override, 4=Standby | ||
| MI | 180 | Wireless Device 1 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 181 | Wireless Device 2 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 182 | Wireless Device 3 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 183 | Wireless Device 4 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 184 | Wireless Device 5 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 185 | Wireless Device 6 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 186 | Wireless Device 7 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 187 | Wireless Device 8 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 188 | Wireless Device 9 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 189 | Wireless Device 10 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 190 | Wireless Device 11 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 191 | Wireless Device 12 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 192 | Wireless Device 13 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 193 | Wireless Device 14 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 194 | Wireless Device 15 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 195 | Wireless Device 16 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 196 | Wireless Device 17 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 197 | Wireless Device 18 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 198 | Wireless Device 19 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 199 | Wireless Device 20 - Sensor Type | Read | 1=None, 2=Unknown, 3=Motion, 4=Contact, 5=Water, 6=Temp., 7=Temp./RH, 8=CO2 | ||
| MI | 210 | Wireless Device 1 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 211 | Wireless Device 1 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 212 | Wireless Device 1 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 220 | Wireless Device 2 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 221 | Wireless Device 2 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 222 | Wireless Device 2 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 230 | Wireless Device 3 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 231 | Wireless Device 3 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 232 | Wireless Device 3 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 240 | Wireless Device 4 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 241 | Wireless Device 4 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 242 | Wireless Device 4 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 250 | Wireless Device 5 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 251 | Wireless Device 5 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 252 | Wireless Device 5 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 260 | Wireless Device 6 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 261 | Wireless Device 6 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 262 | Wireless Device 6 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 270 | Wireless Device 7 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 271 | Wireless Device 7 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 272 | Wireless Device 7 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 280 | Wireless Device 8 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 281 | Wireless Device 8 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 282 | Wireless Device 8 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 290 | Wireless Device 9 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 291 | Wireless Device 9 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 292 | Wireless Device 9 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 300 | Wireless Device 10 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 301 | Wireless Device 10 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 302 | Wireless Device 10 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 309 | Effective Temperature Sensor | Read | 1=Wired, 2=Internal, 3=WL IO, 4=WL 1, 5=WL 2, 6=WL 3, 7=WL 4, 8=WL 5, 9=WL 6, 10=WL 7, 11=WL 8, 12=WL 9, 13=WL 10, 14=WL 11, 15=WL 12, 16=WL 13, 17=WL 14, 18=WL 15, 19=WL 16, 20=WL 17, 21=WL 18, 22=WL 19, 23=WL 20 | ||
| MI | 310 | Wireless Device 11 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 311 | Wireless Device 11 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 312 | Wireless Device 11 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 313 | Effective Relative Humidity Sensor | Read | 1=None, 2=Internal, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20 | ||
| MI | 314 | Effective System Mode | Read | 1=Cool, 2=Heat | ||
| MI | 315 | Wi-Fi Module Status | Read | 1=Offline, 2=Initializing, 3=Ready, 4=Booting, 5=Resetting, 6=Fail, 7=Testing | ||
| MI | 316 | Wi-Fi Status | Read | 1=Idle, 2=Associate, 3=Config., 4=Ready, 5=Online, 6=Disconn., 7=Failure | ||
| MI | 317 | BACnet IP Status | Read | 1=Disabled, 2=Enabled | ||
| MI | 318 | SMTP Server Status | Read | 1=Unkown, 2=Disabled, 3=Offline, 4=Online | ||
| MI | 319 | Facility Expert Enabled | Read | 1=Disabled, 2=Enabled | ||
| MI | 320 | Wireless Device 12 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 321 | Wireless Device 12 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 322 | Wireless Device 12 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 323 | Facility Expert Status | Read | 1=Disabled, 2=Offline, 3=Connect., 4=Online, 5=Failure, 6=Unknown | ||
| MI | 324 | CO2 Effective Source | Read | 1=None, 2=Internal, 3=Error, 4=Wired, 5=WL 1, 6=WL 2, 7=WL 3, 8=WL 4, 9=WL 5, 10=WL 6, 11=WL 7, 12=WL 8, 13=WL 9, 14=WL 10, 15=WL 11, 16=WL 12, 17=WL 13, 18=WL 14, 19=WL 15, 20=WL 16, 21=WL 17, 22=WL 18, 23=WL 19, 24=WL 20 | ||
| MI | 325 | Time source | Read | 1=None, 2=Local, 3=BACnet, 4=NTP, 5=Cloud | ||
| MI | 326 | Fan Speed Status | Read | 1=Off, 2=Low, 3=Medium, 4=High | ||
| MI | 330 | Wireless Device 13 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 331 | Wireless Device 13 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 332 | Wireless Device 13 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 340 | Wireless Device 14 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 341 | Wireless Device 14 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 342 | Wireless Device 14 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 350 | Wireless Device 15 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 351 | Wireless Device 15 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 352 | Wireless Device 15 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 360 | Wireless Device 16 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 361 | Wireless Device 16 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 362 | Wireless Device 16 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 370 | Wireless Device 17 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 371 | Wireless Device 17 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 372 | Wireless Device 17 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 380 | Wireless Device 18 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 381 | Wireless Device 18 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 382 | Wireless Device 18 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 390 | Wireless Device 19 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 391 | Wireless Device 19 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 392 | Wireless Device 19 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MI | 400 | Wireless Device 20 - Status | Read | 1=None, 2=Closed, 3=Opened, 4=No motion, 5=Motion, 6=Normal, 7=Leak | ||
| MI | 401 | Wireless Device 20 - Battery | Read | 1=None, 2=Normal, 3=Low | ||
| MI | 402 | Wireless Device 20 - Communication Status | Read | 1=Not paired, 2=Online, 3=Invalid, 4=Offline | ||
| MV | 1 | Long Message Background Color | Default 1 | Command | 1=White, 2=Green, 3=Blue, 4=Grey, 5=Dark grey, 6=Pink, 7=Purple, 8=Red, 9=Orange, 10=Black, 11=Default | |
| MV | 2 | HMI Color | Default 1 | Command | 1=White, 2=Green, 3=Blue, 4=Grey, 5=Dark grey, 6=Pink, 7=Purple, 8=Red, 9=Orange, 10=Black | |
| MV | 3 | Main Display | Default 1 | Command | 1=Temperature, 2=Setpoint | |
| MV | 4 | Display Language | Default 1 | Command | 1=English, 2=French, 3=Spanish, 4=Chinese, 5=Russian, 6=Arabic, 7=Bulgarian, 8=Czech, 9=Danish, 10=Dutch, 11=Finnish, 12=German, 13=Hungarian, 14=Indonesian, 15=Italian, 16=Norwegian, 17=Polish, 18=Portuguese, 19=Slovak, 20=Swedish, 21=Turkish, 22=Japanese, 23=Hebrew | |
| MV | 5 | Time Format | Default 1 | Command | 1=AM-PM, 2=24 Hours | |
| MV | 6 | Network Units | Default 1 | Command | 1=SI, 2=Imperial | |
| MV | 7 | Network Language | Default 1 | Command | 1=English, 2=French, 3=Spanish | |
| MV | 8 | BACnet Baud Rate | Default 7 | Command | 1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200, 7=Auto | |
| MVmin | 10 | Occupancy Command | Default 2 | Command | 1=Loc. occ, 2=Occupied, 3=Unocc. | |
| MV | 11 | Standby Mode Configuration | Default 1 | Command | 1=Absolute, 2=Offset | |
| MV | 12 | Fan Delay | Default 2 | Command | 1=Off, 2=On | |
| MV | 13 | Dehumidification Lockout | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MVmin | 16 | System Mode | Default 4 | Command | 1=Off, 2=Auto, 3=Cool, 4=Heat | |
| MVmin | 17 | Fan Mode | Default 2 | Command | 1=On, 2=Auto, 3=Smart | |
| MV | 32 | Use Standby Screen | Default 1 | Command | 1=No, 2=Yes, 3=Occ. only, 4=Screen sav | |
| MV | 46 | UI16 Configuration | Default 1 | Command | 1=None, 2=Rem NSB, 3=Motion NO, 4=Motion NC, 5=Window, 6=Fan lock | |
| MV | 47 | UI17 Configuration | Default 1 | Command | 1=None, 2=Door dry, 3=Override, 4=Filter, 5=Service | |
| MV | 49 | UI19 Configuration | Default 1 | Command | 1=None, 2=CO2 | |
| MV | 51 | Temperature Scale | Default 1 | Command | 1=°C, 2=°F | |
| MV | 55 | Frost Protection | Default 1 | Command | 1=Off, 2=On | |
| MV | 58 | Setpoint Function | Default 2 | Command | 1=Dual SP, 2=Attach SP | |
| MV | 70 | Room Humidity Display | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 71 | Enable Smart Recovery | Default 1 | Command | 1=Off, 2=On | |
| MV | 72 | Economizer Configuration | Default 1 | Command | 1=Off, 2=On | |
| MV | 73 | Schedule Menu | Default 2 | Command | 1=Disabled, 2=Enabled, 3=Dis. no. clk., 4=En. no. clk. | |
| MV | 79 | Mechanical Cooling Allowed | Default 1 | Command | 1=Off, 2=On | |
| MV | 92 | BO1 Auxiliary Output Configuration | Default 1 | Command | 1=NO, 2=NC | |
| MV | 95 | Fan Control in Heating Mode | Default 2 | Command | 1=Off, 2=On | |
| MV | 96 | UO9 Configuration | Default 4 | Command | 1=Analog, 2=Binary, 3=Relay RC, 4=Relay RH | |
| MV | 97 | UO10 Configuration | Default 1 | Command | 1=Analog, 2=Binary, 3=Relay RC | |
| MV | 98 | UO11 Configuration | Default 1 | Command | 1=Analog, 2=Binary | |
| MV | 99 | UO12 Configuration | Default 2 | Command | 1=Analog, 2=Binary | |
| MV | 101 | French | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 102 | Spanish | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 103 | Chinese | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 104 | Russian | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 110 | Occupancy Source | Default 1 | Command | 1=Motion, 2=Schedule, 3=Mot. occ., 4=Mot. unoc. | |
| MV | 111 | Mode Button | Default 1 | Command | 1=Normal, 2=Off-Auto | |
| MVmin | 112 | Control Status | Default 1 | Command | 1=Off, 2=Cool, 3=Heat | |
| MV | 114 | Custom button icon | Default 1 | Command | 1=Default Button, 2=No Button, 3=System Mode Heat/Cool, 4=System Mode On/Off, 5=Fan mode, 6=Override Button, 7=Units Button, 8=Help Button, 9=Language Button, 10=Schedule Button, 11=Lighting Button, 12=Blind Button, 13=Lamp Button, 14=Energy Button, 15=Make Room Button, 16=Setting Button, 17=Timer Button | |
| MV | 115 | Custom button behavior | Default 1 | Command | 1=Default function, 2=No function, 3=System mode function, 4=Fan function, 5=Override function, 6=Schedule function, 7=Units function, 8=Help function, 9=Language function, 10=Configuration function, 11=Custom function, 12=Standby function | |
| MV | 116 | Comfort or economy mode | Default 1 | Command | 1=Comfort, 2=Economy | |
| MV | 117 | Reversing valve operation | Default 1 | Command | 1=O, 2=B | |
| MV | 118 | Compressor - auxiliary interlock | Default 1 | Command | 1=Off, 2=On | |
| MV | 119 | Application | Default 1 | Command | 1=Rooftop, 2=Heatpump | |
| MV | 120 | Arabic | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 122 | Czech | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 123 | Danish | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 124 | Dutch | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 125 | Finnish | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 126 | German | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 127 | Hungarian | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 128 | Indonesian | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 129 | Italian | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 130 | Norwegian | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 131 | Polish | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 132 | Portuguese | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 133 | Slovak | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 134 | Swedish | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 135 | Turkish | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 136 | Schedule Type | Default 1 | Command | 1=7 days, 2=5 + 2 days, 3=5 + 1 + 1 days | |
| MV | 138 | UI16 Input Type | Default 2 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 139 | UI17 Input Type | Default 2 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 140 | UI19 Input Type | Default 3 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 141 | UI20 Input Type | Default 1 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 142 | UI22 Input Type | Default 1 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 143 | UI23 Input Type | Default 1 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 144 | UI24 Input Type | Default 3 | Command | 1=Therm., 2=Binary, 3=Voltage | |
| MV | 145 | Room Temperature Sensor | Default 1 | Command | 1=Wired, 2=Internal, 3=WL IO, 4=WL 1, 5=WL 2, 6=WL 3, 7=WL 4, 8=WL 5, 9=WL 6, 10=WL 7, 11=WL 8, 12=WL 9, 13=WL 10, 14=WL 11, 15=WL 12, 16=WL 13, 17=WL 14, 18=WL 15, 19=WL 16, 20=WL 17, 21=WL 18, 22=WL 19, 23=WL 20 | |
| MV | 146 | CO2 Display | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 147 | CO2 Autocalibration | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 148 | Lock Screen | Default 1 | Command | 1=No, 2=Yes | |
| MV | 149 | Relative humidity sensor | Default 2 | Command | 1=None, 2=Internal, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20 | |
| MV | 150 | CO2 source | Default 2 | Command | 1=None, 2=Local, 3=WL 1, 4=WL 2, 5=WL 3, 6=WL 4, 7=WL 5, 8=WL 6, 9=WL 7, 10=WL 8, 11=WL 9, 12=WL 10, 13=WL 11, 14=WL 12, 15=WL 13, 16=WL 14, 17=WL 15, 18=WL 16, 19=WL 17, 20=WL 18, 21=WL 19, 22=WL 20 | |
| MV | 151 | Temperature Alarm Enabled | Default 1 | Command | 1=Off, 2=On | |
| MV | 152 | ADR Permission | Default 1 | Command | 1=Off, 2=On | |
| MV | 155 | Japanese | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 156 | Hebrew | Default 1 | Command | 1=Disabled, 2=Enabled | |
| MV | 180 | Display the Fan Status icon | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 181 | Display the System Status icon | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 182 | Display the Help button | Default 2 | Command | 1=Disabled, 2=Enabled | |
| MV | 185 | UI20 Configuration | Default 2 | Command | 1=None, 2=RS, 3=MAT | |
| MV | 210 | Wireless Device 1 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 220 | Wireless Device 2 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 230 | Wireless Device 3 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 240 | Wireless Device 4 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 250 | Wireless Device 5 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 260 | Wireless Device 6 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 270 | Wireless Device 7 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 280 | Wireless Device 8 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 290 | Wireless Device 9 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 300 | Wireless Device 10 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 310 | Wireless Device 11 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 320 | Wireless Device 12 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 330 | Wireless Device 13 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 340 | Wireless Device 14 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 350 | Wireless Device 15 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 360 | Wireless Device 16 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 370 | Wireless Device 17 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 380 | Wireless Device 18 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 390 | Wireless Device 19 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| MV | 400 | Wireless Device 20 - Function | Default 1 | Command | 1=None, 2=Window, 3=Door, 4=Motion, 5=Env. data, 6=Remove, 7=Water, 8=Refrig., 9=Freezer | |
| FILE | 1 | Custom Lua File | Lua script file (read/write the custom script) | Write | ||
| Other | 1 | Lua Program 1 | Monitors and controls the Lua script program | Write |
No points match these filters.
Object ID lookup: Viconics VT8650 Rooftop Unit and Heat Pump Controller point IDs by name
AI2Light Sensor LevelAI4Relative Humidity Raw ValueAI5UI20 Raw ValueAI7UI23 Raw ValueAI8UI22 Raw ValueAI9UI24 Raw ValueAI31UI19 Raw ValueAI32Temperature Raw ValueAI33UI16 Raw ValueAI34UI17 Raw ValueAI315Wireless Device 1 - TemperatureAI316Wireless Device 2 - TemperatureAI317Wireless Device 3 - TemperatureAI318Wireless Device 4 - TemperatureAI319Wireless Device 5 - TemperatureAI320Wireless Device 6 - TemperatureAI321Wireless Device 7 - TemperatureAI322Wireless Device 8 - TemperatureAI323Wireless Device 9 - TemperatureAI324Wireless Device 10 - TemperatureAI329Effective SetpointAI330Paired ZigBee DevicesAI340Therm. Raw ValueAI341SH Therm. Raw ValueAI343Wi-Fi Module Boot CountAI355Wireless Device 11 - TemperatureAI356Wireless Device 12 - TemperatureAI357Wireless Device 13 - TemperatureAI358Wireless Device 14 - TemperatureAI359Wireless Device 15 - TemperatureAI360Wireless Device 16 - TemperatureAI361Wireless Device 17 - TemperatureAI362Wireless Device 18 - TemperatureAI363Wireless Device 19 - TemperatureAI364Wireless Device 20 - TemperatureAI365Wireless Device 1 - HumidityAI366Wireless Device 2 - HumidityAI367Wireless Device 3 - HumidityAI368Wireless Device 4 - HumidityAI369Wireless Device 5 - HumidityAI370Wireless Device 6 - HumidityAI371Wireless Device 7 - HumidityAI372Wireless Device 8 - HumidityAI373Wireless Device 9 - HumidityAI374Wireless Device 10 - HumidityAI375Wireless Device 11 - HumidityAI376Wireless Device 12 - HumidityAI377Wireless Device 13 - HumidityAI378Wireless Device 14 - HumidityAI379Wireless Device 15 - HumidityAI380Wireless Device 16 - HumidityAI381Wireless Device 17 - HumidityAI382Wireless Device 18 - HumidityAI383Wireless Device 19 - HumidityAI384Wireless Device 20 - HumidityAI385Wireless Device 1 - CO2AI386Wireless Device 2 - CO2AI387Wireless Device 3 - CO2AI388Wireless Device 4 - CO2AI389Wireless Device 5 - CO2AI390Wireless Device 6 - CO2AI391Wireless Device 7 - CO2AI392Wireless Device 8 - CO2AI393Wireless Device 9 - CO2AI394Wireless Device 10 - CO2AI395Wireless Device 11 - CO2AI396Wireless Device 12 - CO2AI397Wireless Device 13 - CO2AI398Wireless Device 14 - CO2AI399Wireless Device 15 - CO2AI400Wireless Device 16 - CO2AI401Wireless Device 17 - CO2AI402Wireless Device 18 - CO2AI403Wireless Device 19 - CO2AI404Wireless Device 20 - CO2AO21PI Heating DemandAO22PI Cooling DemandAO23Economizer DemandAO24Analog Output Heat DemandAO123UO11 Analog OutputAO124UO12 Analog OutputAO125UO9 Analog OutputAO126UO10 Analog OutputAV2User HMIAV3Low BacklightAV4Night BacklightAV7Calibrate Room Temperature SensorAV8Calibrate Humidity SensorAV10COM AddressAV16BACnet Stack Poll RateAV20Discharge Low LimitAV21Minimum Fresh AirAV22Maximum Fresh AirAV23Minimum CO2AV24Maximum CO2AV25Lua Parameter A (AV25)AV26Lua Parameter B (AV26)AV27Lua Parameter C (AV27)AV28Lua Parameter D (AV28)AV29Lua Parameter E (AV29)AV30Lua Parameter F (AV30)AV39Occupied Heat SetpointAV40Occupied Cool SetpointAV41Standby Heat SetpointAV42Standby Cool SetpointAV43Unoccupied Heat SetpointAV44Unoccupied Cool SetpointAV45Default Heating SetpointAV46Standby Temperature DifferentialAV56Main PasswordAV57User PasswordAV58Heating Setpoint LimitAV59Cooling Setpoint LimitAV62Temporary Occupancy TimeAV63Minimum DeadbandAV65Proportional BandAV67Standby TimeAV68Unoccupied TimeAV71Dehumidification SetpointAV72Dehumidification HysteresisAV74Calibrate Outside Temperature SensorAV75Number of Cooling StagesAV76Power-up DelayAV78Economizer Minimum PositionAV81Economizer Maximum PositionAV82High balance pointAV83Low balance pointAV84Heating CPHAV85Cooling CPHAV86Anti Short Cycle TimeAV87Number of Heating StagesAV88Heating Demand LimitAV89Cooling Demand LimitAV91Heating Lockout from Outside Air TemperatureAV92Keyboard ValueAV93Cooling LockoutAV94Supply Air SetpointAV95Changeover SetpointAV96Fresh Air Range Upper LimitAV97Minimum Supply HeatAV98Supply Heat LockoutAV99Discharge High LimitAV100Room TemperatureAV101Outdoor TemperatureAV102UI22 Supply TemperatureAV103Room HumidityAV104UI19 TemperatureAV105UI20 Remote TemperatureAV106CO2 LevelAV107Airflow LevelAV108UI19 Analog InputAV109UI24 TemperatureAV111UI16 Analog InputAV112UI17 Analog InputAV113UI20 Analog InputAV114UI22 Analog InputAV115UI23 Analog InputAV116UI24 Analog InputAV117UI16 TemperatureAV118UI17 TemperatureAV120UI20 TemperatureAV121UI22 TemperatureAV122UI23 TemperatureAV125Mixed Air TemperatureAV202UI19 LuaAV203UI20 LuaAV204UI22 LuaAV205UI23 LuaAV206UI24 LuaAV209Ambient Low Temperature ThresholdAV210Temperature Alarm HysteresisAV211Load Shedding OffsetAV225Lua Parameter G (AV225)AV226Lua Parameter H (AV226)AV227Lua Parameter I (AV227)AV228Lua Parameter J (AV228)AV229Lua Parameter K (AV229)AV230Lua Parameter L (AV230)AV270Standby Screen DelayAV275Ambient High Temperature ThresholdAV276Refrigeration High Temperature ThresholdAV277Refrigeration Low Temperature ThresholdAV278Freezer High Temperature ThresholdBI29UI16 Binary InputBI30UI17 Binary InputBI91UI19 Binary InputBI94UI20 Binary InputBI95UI22 Binary InputBI96UI23 Binary InputBI97UI24 Binary InputBO25G Fan StatusBO26Y1 StatusBO27Y2 StatusBO28W1 StatusBO29W2/OB StatusBO94UO10 Binary OutputBO98BO1 Auxiliary Binary OutputBO101UO11 Binary OutputBO102UO12 Binary OutputBV1Door Contact StatusBV2Door Contact InstalledBV3Window Contact StatusBV4Window Contact InstalledBV5Low Battery AlarmBV6Force High BacklightBV7Display Long Screen MessageBV8Clock AlarmBV10Exception StatusBV32PIR Local MotionBV35Window AlarmBV36Filter AlarmBV37Service AlarmBV38Dehumidification StatusBV39Fan Lock AlarmBV40Smart Recovery StatusBV41CO2 AlarmBV42Low Fresh Air AlarmBV43Frost Protection AlarmBV44Water LeakBV45Water Leak Sensor InstalledBV46Water leak sensor statusBV47Low TemperatureBV48Load Shedding DemandBV49Load Shedding StatusBV50Load Shedding OverrideBV53High TemperatureBV200ZigBee PIR Sensor InstalledBV201ZigBee Sensor MotionCSV1Short Screen Message TextCSV2Long Screen Message TextCSV3External Memory RevisionCSV4Wi-Fi Device NameCSV5Wi-Fi Firmware VersionCSV6MAC AddressCSV7Wi-Fi Network SSIDCSV8Wi-Fi Network IP AddressCSV9ZigBee Firmware RevisionCSV10Zigbee IEEE AddressCSV11Wireless Device 1 - AddressCSV12Wireless Device 2 - AddressCSV13Wireless Device 3 - AddressCSV14Wireless Device 4 - AddressCSV15Wireless Device 5 - AddressCSV16Wireless Device 6 - AddressCSV17Wireless Device 7 - AddressCSV18Wireless Device 8 - AddressCSV19Wireless Device 9 - AddressCSV20Wireless Device 10 - AddressCSV21Wireless Device 11 - AddressCSV22Wireless Device 12 - AddressCSV23Wireless Device 13 - AddressCSV24Wireless Device 14 - AddressCSV25Wireless Device 15 - AddressCSV26Wireless Device 16 - AddressCSV27Wireless Device 17 - AddressCSV28Wireless Device 18 - AddressCSV29Wireless Device 19 - AddressCSV30Wireless Device 20 - AddressMI2ZigBee Network StatusMI33Effective OccupancyMI180Wireless Device 1 - Sensor TypeMI181Wireless Device 2 - Sensor TypeMI182Wireless Device 3 - Sensor TypeMI183Wireless Device 4 - Sensor TypeMI184Wireless Device 5 - Sensor TypeMI185Wireless Device 6 - Sensor TypeMI186Wireless Device 7 - Sensor TypeMI187Wireless Device 8 - Sensor TypeMI188Wireless Device 9 - Sensor TypeMI189Wireless Device 10 - Sensor TypeMI190Wireless Device 11 - Sensor TypeMI191Wireless Device 12 - Sensor TypeMI192Wireless Device 13 - Sensor TypeMI193Wireless Device 14 - Sensor TypeMI194Wireless Device 15 - Sensor TypeMI195Wireless Device 16 - Sensor TypeMI196Wireless Device 17 - Sensor TypeMI197Wireless Device 18 - Sensor TypeMI198Wireless Device 19 - Sensor TypeMI199Wireless Device 20 - Sensor TypeMI210Wireless Device 1 - StatusMI211Wireless Device 1 - BatteryMI212Wireless Device 1 - Communication StatusMI220Wireless Device 2 - StatusMI221Wireless Device 2 - BatteryMI222Wireless Device 2 - Communication StatusMI230Wireless Device 3 - StatusMI231Wireless Device 3 - BatteryMI232Wireless Device 3 - Communication StatusMI240Wireless Device 4 - StatusMI241Wireless Device 4 - BatteryMI242Wireless Device 4 - Communication StatusMI250Wireless Device 5 - StatusMI251Wireless Device 5 - BatteryMI252Wireless Device 5 - Communication StatusMI260Wireless Device 6 - StatusMI261Wireless Device 6 - BatteryMI262Wireless Device 6 - Communication StatusMI270Wireless Device 7 - StatusMI271Wireless Device 7 - BatteryMI272Wireless Device 7 - Communication StatusMI280Wireless Device 8 - StatusMI281Wireless Device 8 - BatteryMI282Wireless Device 8 - Communication StatusMI290Wireless Device 9 - StatusMI291Wireless Device 9 - BatteryMI292Wireless Device 9 - Communication StatusMI300Wireless Device 10 - StatusMI301Wireless Device 10 - BatteryMI302Wireless Device 10 - Communication StatusMI309Effective Temperature SensorMI310Wireless Device 11 - StatusMI311Wireless Device 11 - BatteryMI312Wireless Device 11 - Communication StatusMI313Effective Relative Humidity SensorMI314Effective System ModeMI315Wi-Fi Module StatusMI316Wi-Fi StatusMI317BACnet IP StatusMI318SMTP Server StatusMI319Facility Expert EnabledMI320Wireless Device 12 - StatusMI321Wireless Device 12 - BatteryMI322Wireless Device 12 - Communication StatusMI323Facility Expert StatusMI324CO2 Effective SourceMI325Time sourceMI326Fan Speed StatusMI330Wireless Device 13 - StatusMI331Wireless Device 13 - BatteryMI332Wireless Device 13 - Communication StatusMI340Wireless Device 14 - StatusMI341Wireless Device 14 - BatteryMI342Wireless Device 14 - Communication StatusMI350Wireless Device 15 - StatusMI351Wireless Device 15 - BatteryMI352Wireless Device 15 - Communication StatusMI360Wireless Device 16 - StatusMI361Wireless Device 16 - BatteryMI362Wireless Device 16 - Communication StatusMI370Wireless Device 17 - StatusMI371Wireless Device 17 - BatteryMI372Wireless Device 17 - Communication StatusMI380Wireless Device 18 - StatusMI381Wireless Device 18 - BatteryMI382Wireless Device 18 - Communication StatusMI390Wireless Device 19 - StatusMI391Wireless Device 19 - BatteryMI392Wireless Device 19 - Communication StatusMI400Wireless Device 20 - StatusMI401Wireless Device 20 - BatteryMI402Wireless Device 20 - Communication StatusMV1Long Message Background ColorMV2HMI ColorMV3Main DisplayMV4Display LanguageMV5Time FormatMV6Network UnitsMV7Network LanguageMV8BACnet Baud RateMV10Occupancy CommandMV11Standby Mode ConfigurationMV12Fan DelayMV13Dehumidification LockoutMV16System ModeMV17Fan ModeMV32Use Standby ScreenMV46UI16 ConfigurationMV47UI17 ConfigurationMV49UI19 ConfigurationMV51Temperature ScaleMV55Frost ProtectionMV58Setpoint FunctionMV70Room Humidity DisplayMV71Enable Smart RecoveryMV72Economizer ConfigurationMV73Schedule MenuMV79Mechanical Cooling AllowedMV92BO1 Auxiliary Output ConfigurationMV95Fan Control in Heating ModeMV96UO9 ConfigurationMV97UO10 ConfigurationMV98UO11 ConfigurationMV99UO12 ConfigurationMV101FrenchMV102SpanishMV103ChineseMV104RussianMV110Occupancy SourceMV111Mode ButtonMV112Control StatusMV114Custom button iconMV115Custom button behaviorMV116Comfort or economy modeMV117Reversing valve operationMV118Compressor - auxiliary interlockMV119ApplicationMV120ArabicMV122CzechMV123DanishMV124DutchMV125FinnishMV126GermanMV127HungarianMV128IndonesianMV129ItalianMV130NorwegianMV131PolishMV132PortugueseMV133SlovakMV134SwedishMV135TurkishMV136Schedule TypeMV138UI16 Input TypeMV139UI17 Input TypeMV140UI19 Input TypeMV141UI20 Input TypeMV142UI22 Input TypeMV143UI23 Input TypeMV144UI24 Input TypeMV145Room Temperature SensorMV146CO2 DisplayMV147CO2 AutocalibrationMV148Lock ScreenMV149Relative humidity sensorMV150CO2 sourceMV151Temperature Alarm EnabledMV152ADR PermissionMV155JapaneseMV156HebrewMV180Display the Fan Status iconMV181Display the System Status iconMV182Display the Help buttonMV185UI20 ConfigurationMV210Wireless Device 1 - FunctionMV220Wireless Device 2 - FunctionMV230Wireless Device 3 - FunctionMV240Wireless Device 4 - FunctionMV250Wireless Device 5 - FunctionMV260Wireless Device 6 - FunctionMV270Wireless Device 7 - FunctionMV280Wireless Device 8 - FunctionMV290Wireless Device 9 - FunctionMV300Wireless Device 10 - FunctionMV310Wireless Device 11 - FunctionMV320Wireless Device 12 - FunctionMV330Wireless Device 13 - FunctionMV340Wireless Device 14 - FunctionMV350Wireless Device 15 - FunctionMV360Wireless Device 16 - FunctionMV370Wireless Device 17 - FunctionMV380Wireless Device 18 - FunctionMV390Wireless Device 19 - FunctionMV400Wireless Device 20 - FunctionFILE1Custom Lua File
Integration notes
- Viconics is a Schneider Electric brand; the guide is published on veris.com.
- Stage outputs BO 25-29 are G Fan, Y1, Y2, W1 and W2/OB Status; MV 117 sets the reversing valve to O or B for heat pump use.
- Access follows the guide's generic property tables: AV, AO, BV, BO and MSV present values are commandable, CSVs are writable, and AI/MSI present values can only be written while Out_Of_Service is TRUE.
- Wireless Device 1-20 objects only report data for ZigBee sensors paired to the controller.
- Printed as in the guide: AV 42 default 78°F (21°C); AV 85 Cooling CPH max printed 4; MV 136 and MV 185 max printed 2 with three states.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VT8650 Rooftop Unit and Heat Pump Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Viconics VT8650 Rooftop Unit and Heat Pump Controller
How many BACnet points does the Viconics VT8650 Rooftop Unit and Heat Pump Controller have?
This list has 456 BACnet objects: 75 analog inputs, 8 analog outputs, 100 analog values, 7 binary inputs, 9 binary outputs, 29 binary values, 1 file, 94 multi-state inputs, 102 multi-state values, 30 characterstring values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Viconics VT8650 Rooftop Unit and Heat Pump Controller BACnet points are writable?
280 of the 456 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Viconics VT8650 Rooftop Unit and Heat Pump Controller BACnet documentation?
The source is VT8650 BACnet Integration Guide - Roof Top Unit (RTU), Heat Pump and Indoor Air Quality (IAQ) - Firmware Revision 2.6 (028-0437-07_IG-VT8650-BNET_A4_EN (Version 7)), revision 2022-07, published free by Viconics at https://www.veris.com/ASSETS/DOCUMENTS/CMS/EN/Static_Documents/DownloadCenter/028-0437-07_IG-VT8650-2.6-BNET_A4_EN_RH20220708.pdf.
What are the minimum BACnet points to integrate the Viconics VT8650 Rooftop Unit and Heat Pump Controller?
Start with MV 10 Occupancy Command (BMS occupancy: local, occupied or unoccupied); MV 16 System Mode (Off / auto / cool / heat); MV 17 Fan Mode (Fan mode: on / auto / smart); AV 39 Occupied Heat Setpoint (Occupied heating setpoint); AV 40 Occupied Cool Setpoint (Occupied cooling setpoint); MV 112 Control Status (Current state: off, cooling or heating); BO 25 G Fan Status (Fan (G) output state); MI 33 Effective Occupancy (Actual occupancy state); AV 100 Room Temperature (Space temperature used for control); BV 39 Fan Lock Alarm (Fan lock alarm (1 = on)).
How do I enable BMS control of the Viconics VT8650 Rooftop Unit and Heat Pump Controller?
No enable switch is needed. The BMS writes MV 10 Occupancy Command (1 = Loc. occ, the controller decides locally; 2 = Occupied; 3 = Unoccupied) and MV 16 System Mode. MV 110 Occupancy Source chooses whether local occupancy follows motion, the schedule or a mix.
Can the BMS supply sensor values to the Viconics VT8650 Rooftop Unit and Heat Pump Controller?
The guide has no BMS-written room temperature object: MV 145 Room Temperature Sensor selects the wired, internal or one of 20 paired ZigBee wireless sensors, and MI 309 shows which one is in use. Writing an AI present value only works with Out_Of_Service set TRUE.
How do I check these points on the real VT8650 Rooftop Unit and Heat Pump Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Viconics BACnet points lists
- Networked room controller (thermostat)
Viconics TRCVT 3.0 Room Controller
Viconics TRC room controllers running firmware 3.0: TRC3500 models for fan coils and TRC6500 models for packaged rooftop units and heat pumps, in wired and wireless versions.
Also known as: TRCVT, TRC3500, TRC6500, TRCn500nnnn-VC, Viconics Room Controller - Networked room thermostat
Viconics VT7200 / VT7300 Series PIR-Ready Thermostats
Viconics VT7200 zoning thermostats and VT73xx / VTR73xx fan coil and zoning thermostats (24 Vac, PIR-ready) with the BACnet MS/TP communication module.
Also known as: VT7200, VT7300, VT7305, VT7350, VT7355, VTR7300, VTR7305, VTR7350, VTR7355, VT72xx, VT73xx, Trane X13511543010, Trane Communicating Thermostat (fan coil), Honeywell TB7200, Honeywell TB7300 - Networked room thermostat
Viconics VT7600 Series PIR-Ready Rooftop / Heat Pump Thermostats
Viconics VT76xx thermostats (with and without scheduling) for packaged rooftop units and heat pumps, including economizer, dehumidification and humidification models, with the BACnet MS/TP communication module.
Also known as: VT7600, VT7605, VT7607, VT7652, VT7656, VT7657, VT7606, VT76xx, Trane X13511541010, Trane Communicating Thermostat (rooftop / heat pump / dehumidification), Schneider Electric SE7600, SE7652, SE7605, SE7656, SE7606, SE7607, SE7657, Honeywell TB7600, TB7652, TB7605, TB7656, TB7607, TB7657 - Fan coil unit controller (room thermostat)
Viconics VT8350 Fan Coil and Zone Controller
Viconics VT8000-series VT8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: VT8350, Viconics VT8350, VT8000 VT8350, Schneider Electric VT8350 - Fan coil unit controller (room thermostat)
Viconics VTR8350 Line Voltage Fan Coil Controller
Viconics VT8000-series VTR8350 room controllers for line-voltage fan coil units (used with a VC3000-series relay pack).
Also known as: VTR8350, Viconics VTR8350, VT8000 VTR8350, Schneider Electric VTR8350 - VAV zone controller (room thermostat)
Viconics VZ8250 VAV Zone Controller
Viconics VT8000-series VZ8250 room controllers for pressure-dependent or pressure-independent VAV boxes, with optional fan, duct heater and baseboard reheat.
Also known as: VZ8250, Viconics VZ8250, VT8000 VZ8250, Schneider Electric VZ8250, Schneider Electric SpaceLogic SEZ8250
Source: VT8650 BACnet Integration Guide - Roof Top Unit (RTU), Heat Pump and Indoor Air Quality (IAQ) - Firmware Revision 2.6 · 028-0437-07_IG-VT8650-BNET_A4_EN (Version 7) · rev. 2022-07. Object names, instances and units are reproduced as published; descriptions are our own.