 "manufacturer": "Thermal Solutions",
 "manufacturer_slug": "thermal-solutions",
 "model": "EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)",
 "short_model": "EVA/EVO RM7800 ProtoNode",
 "model_slug": "eva-evo-rm7800",
 "aliases": [
  "RM7800",
  "Honeywell RM7800",
  "7800 Series",
  "EVA",
  "EVAW",
  "EVO",
  "EVOW",
  "FPC-N34-0643",
  "ProtoNode FPC-N34"
 ],
 "equipment_type": "Boiler flame safeguard (RM7800) via ProtoNode gateway",
 "applies_to": "Thermal Solutions EVA, EVAW, EVO and EVOW boilers with an RM7800 series burner control, connected through a ProtoNode FPC-N34.",
 "summary": "The RM7800 burner control on Thermal Solutions EVA/EVAW/EVO/EVOW boilers is read through a ProtoNode FPC-N34 gateway that polls it over Modbus RTU and serves it on BACnet IP or BACnet MS/TP. All 37 objects are read-only: flame signal, cycle and hour counters, fault and first-out codes, one flag per burner sequence state, and the limit and interlock inputs.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "50000 + the controller's Modbus Node-ID (Node_Offset default 50,000, changeable in the Web Configurator)",
 "access_inferred": true,
 "notes": [
  "Each connected controller shows up as its own BACnet device on the ProtoNode FPC-N34 gateway.",
  "Monitoring only: the RM7800 profile has no writable objects.",
  "The sequence-state points (Initiate to Lockout) are analog inputs that carry a 0/1 on/off value.",
  "The guide gives no fault-code or first-out-code tables; see the RM7800 documentation."
 ],
 "integration": {
  "summary": "Wire the RM7800 display module Modbus terminals to the ProtoNode, set it to 19200 8N1 with a unique Node-ID, add the RM7800 profile in the Web Configurator, and discover it at 50000 + Node-ID. It is a monitoring profile: read the run, alarm and lockout flags, the fault and first-out codes and the flame signal.",
  "minimum_points": [
   {
    "ref": "AI 58",
    "name": "Run",
    "why": "Burner in run (1 = on)"
   },
   {
    "ref": "AI 1",
    "name": "Flame Signal",
    "why": "Flame signal strength"
   },
   {
    "ref": "AI 4",
    "name": "Burner Fault Code",
    "why": "Current burner fault code"
   },
   {
    "ref": "AI 62",
    "name": "Alarm",
    "why": "Flame safeguard alarm (1 = on)"
   },
   {
    "ref": "AI 64",
    "name": "Lockout",
    "why": "Burner locked out (1 = on)"
   },
   {
    "ref": "BI 1",
    "name": "Com Status",
    "why": "Modbus link between ProtoNode and the RM7800"
   }
  ],
  "enable": "None: the RM7800 profile is read-only, so start/stop is not available over BACnet.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Device instance = Node_Offset (default 50,000) + the controller's Modbus Node-ID, so Node-ID 1 gives 50001.",
   "ProtoNode default IP is 192.168.1.24 (255.255.255.0); change it in the FS-GUI under Setup > Network Settings.",
   "FPC-N34 S-bank DIP switches pick the protocol: all Off = BACnet IP, S0 On = BACnet MS/TP, S2 On = BACnet MS/TP single node.",
   "BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on A-bank DIP switches; baud on B-bank switches, factory default 38400.",
   "Modbus side: every RWF40, RWF55 and RM7800 must run Modbus RTU at 19200, 8N1 with a unique Node-ID (1-255); add each one as a profile in the Web Configurator.",
   "With more than one controller on a ProtoNode set BACnet Virtual Server Nodes to Yes; give each ProtoNode on a subnet its own BACnet Network Number (default 50)."
  ],
  "gotchas": [
   "Sequence states are AI objects holding 0/1, not binary objects.",
   "RM7800 wiring: A to ProtoNode Tx+, B to Rx-, C to GND; a factory terminal strip (AO/BO/SO) may already combine it with the RWF controller."
  ]
 },
 "source": {
  "title": "ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls",
  "doc_number": "Document Revision 7.A (Web Configurator Template Revision 70)",
  "revision_date": "2018-08",
  "url": "https://boilers-water-heaters.thermalsolutions.com/Asset/Thermal%20Solutions%20EVA,%20EVAW,%20EVO%20&%20EVOW%20ProtoNode%20N34%20&%20N35%20Start-up%20Guide%202018-08.pdf"
 },
 "points": [
  {
   "type": "BI",
   "instance": 1,
   "name": "Com Status",
   "description": "ProtoNode-to-RM7800 Modbus link status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Flame Signal",
   "description": "Flame signal strength",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Burner Cycles",
   "description": "Burner cycle count",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Burner Hours",
   "description": "Burner run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Burner Fault Code",
   "description": "Current burner fault code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "Initiate",
   "description": "Sequence state: initiate",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "Standby",
   "description": "Sequence state: standby",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "Purge",
   "description": "Sequence state: purge",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "Pilot Ignition",
   "description": "Sequence state: pilot ignition",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "Main Ignition",
   "description": "Sequence state: main ignition",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "Run",
   "description": "Sequence state: run",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "Postpurge",
   "description": "Sequence state: postpurge",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "Pre-Ignition",
   "description": "Sequence state: pre-ignition",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "Valve Proving",
   "description": "Sequence state: valve proving",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "Alarm",
   "description": "Flame safeguard alarm active",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "Hold",
   "description": "Sequence on hold",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "Lockout",
   "description": "Flame safeguard in lockout",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "First Out Code",
   "description": "First-out annunciation code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 66,
   "name": "Main Valve Proof of Closure",
   "description": "Main valve proof-of-closure input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 67,
   "name": "Burner Switch",
   "description": "Burner switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 68,
   "name": "Operating Control",
   "description": "Operating control input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 69,
   "name": "Auxiliary Limit 1",
   "description": "Auxiliary limit 1 input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 70,
   "name": "Auxiliary Limit 2",
   "description": "Auxiliary limit 2 input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 71,
   "name": "Low Water Cutoff",
   "description": "Low water cutoff input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 72,
   "name": "High Limit",
   "description": "High limit input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 73,
   "name": "Auxiliary Limit 3",
   "description": "Auxiliary limit 3 input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 74,
   "name": "Oil Select Switch",
   "description": "Oil select switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 75,
   "name": "High Oil Pressure",
   "description": "High oil pressure switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 76,
   "name": "Low Oil Pressure",
   "description": "Low oil pressure switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 77,
   "name": "High Oil Temperature",
   "description": "High oil temperature switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 78,
   "name": "Low Oil Temperature",
   "description": "Low oil temperature switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 79,
   "name": "Gas Select Switch",
   "description": "Gas select switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 80,
   "name": "High Gas Pressure",
   "description": "High gas pressure switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 81,
   "name": "Low Gas Pressure",
   "description": "Low gas pressure switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 82,
   "name": "Air Flow Switch",
   "description": "Combustion air flow switch input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 83,
   "name": "Auxiliary Interlock 4",
   "description": "Auxiliary interlock 4 input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 84,
   "name": "Auxiliary Interlock 5",
   "description": "Auxiliary interlock 5 input",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/thermal-solutions/eva-evo-rm7800",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}