 "manufacturer": "Thermal Solutions",
 "manufacturer_slug": "thermal-solutions",
 "model": "Apex with Panasonic display, 4109 software (Universal Gateway)",
 "model_slug": "apex-panasonic-4109-universal-gateway",
 "aliases": [
  "Apex",
  "Apex 4109",
  "Panasonic GT02",
  "Universal Gateway",
  "106417-01",
  "ProtoNode RER",
  "FPC-N34-0816"
 ],
 "equipment_type": "Boiler controller via ProtoNode gateway",
 "applies_to": "Thermal Solutions Apex boilers with the control and Panasonic GT02 display running 4109 software, connected through the Universal Gateway.",
 "summary": "Apex boilers with the Panasonic display and 4109 software are read over Modbus RTU by the Thermal Solutions Universal Gateway (a ProtoNode) and served as BACnet IP or BACnet MS/TP devices. The 28-object profile has a burner on/off command, writable CH, DHW, lead lag and CH time-of-day setpoints, setpoint sources, sensor temperatures, burner state, lockout and hold codes, and cycle counters.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "50000 + boiler Modbus address (BACnet IP and MS/TP multiple node); Node_Offset default 50,000",
 "access_inferred": false,
 "notes": [
  "The Universal Gateway is a ProtoNode (BACnet RER FPC-N34-0816, LonWorks LER FPC-N35-0817) that auto-discovers up to 8 boilers on its Modbus RS-485 port.",
  "Every boiler is its own BACnet device with the same object list; the instances here are for one boiler.",
  "Power all boilers and connect them before running auto-discovery; a boiler added later is not found until discovery is run again.",
  "All writable values on this control are stored in EEPROM; write only when a value has to change, never cyclically.",
  "Check the software version with the i button on the home screen: 4716 software uses a different list."
 ],
 "integration": {
  "summary": "Give each Apex a unique Boiler Address (Adjust > Sequencer Slave), disable Sequencer Master on every boiler, wire the RJ45 boiler-to-boiler port to the gateway, run auto-discovery, then use BV 1 Burner On Off and AV 3 CH Setpoint. Values go to EEPROM, so write them only when they change.",
  "minimum_points": [
   {
    "ref": "BV 1",
    "name": "Burner On Off",
    "why": "Burner enable from the BMS (1 = on)"
   },
   {
    "ref": "AV 3",
    "name": "CH Setpoint",
    "why": "CH setpoint, 79-191 °F; EEPROM, write on change"
   },
   {
    "ref": "AI 21",
    "name": "Burner Control State",
    "why": "Burner sequence state; 12 = Run, 14 = Lockout"
   },
   {
    "ref": "AI 13",
    "name": "Supply Sensor",
    "why": "Supply water temperature, °F"
   },
   {
    "ref": "AI 8",
    "name": "Active CH Setpoint",
    "why": "CH setpoint in use, °F"
   },
   {
    "ref": "AI 22",
    "name": "Lockout Code",
    "why": "Lockout reason; 0 = no lockout"
   }
  ],
  "enable": "BV 1 Burner On Off enables or disables the burner. If only BV 1 is used instead of the boiler's Enable/Disable contact, the boiler stops but the system pump may keep running. For lead/lag, Enable/Disable and the remote firing rate (4-20 mA) must be hard-wired to each boiler, and the Sequencer must be disabled (no master boiler) while the EMS is connected.",
  "heartbeat": null,
  "remote_sensors": "When the BMS writes AV 3 CH Setpoint it takes over the boiler's CH setpoint, so disable the boiler's outdoor air reset. There is no writable outdoor or header temperature input.",
  "setup": [
   "BACnet IP and MS/TP multiple node: each boiler is its own device, instance = Node_Offset (default 50,000) + boiler Modbus address, so address 1 = 50001.",
   "BACnet MS/TP single node (for front ends without virtual-node support): one device at Node_Offset + MAC, with boiler objects renumbered 1001, 1002... for address 1, 2001... for address 2.",
   "S-bank DIP switches pick the protocol (S0-S2 all Off = BACnet IP, S0 On = MS/TP multiple node, S2 On = MS/TP single node); S3 On at power-up runs auto-discovery (about 3 minutes), then set S3 Off to keep the configuration.",
   "MS/TP MAC address 1-127 on A-bank DIP switches (one MAC for the whole gateway); baud rate on B-bank switches.",
   "Change the IP address and Node_Offset in the ProtoNode web configurator (default IP 192.168.1.24).",
   "Apex with Panasonic GT02: set a unique Boiler Address under Adjust > Sequencer Slave and disable Sequencer Master on all boilers."
  ],
  "gotchas": [
   "All writable parameters live in EEPROM: avoid repeated or cyclic writes.",
   "Disable outdoor air reset on the boiler when the BMS writes the CH setpoint.",
   "Boiler sequencing (lead/lag) must be done outside the boiler controls when the EMS is connected."
  ]
 },
 "source": {
  "title": "Thermal Solutions Universal Gateway Instruction Manual",
  "doc_number": "106417-01 Rev. 13",
  "revision_date": "2017-08-21",
  "url": "https://boilers-water-heaters.thermalsolutions.com/Asset/106417-01%20Rev%2013%20TS%20Universal%20Gateway%20Instructions.pdf"
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "Burner On Off",
   "description": "Enable / disable the burner",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Demand Source",
   "description": "Source of the current heat demand",
   "units": "",
   "access": "R",
   "states": "0=Unknown, 1=No source demand, 2=Central heat, 3=Domestic hot water, 4=Lead Lag slave, 5=Lead Lag master, 6=CH frost protection, 7=DHW frost protection, 8=No demand (burner switch off), 9=DHW storage, 11=Warm weather shutdown"
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "CH Setpoint",
   "description": "Central heat setpoint (79 to 191)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "DHW Setpoint",
   "description": "Domestic hot water setpoint (79 to 191)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Lead Lag Setpoint",
   "description": "Lead lag setpoint (79 to 191)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "CH TOD Setpoint",
   "description": "Central heat time-of-day setpoint (79 to 191)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "CH Setpoint Source",
   "description": "What sets the active CH setpoint",
   "units": "",
   "access": "R",
   "states": "0=Unknown, 1=Normal setpoint, 2=TOD setpoint, 3=Outdoor reset, 4=Remote control (4-20 mA), 7=Outdoor reset time of day"
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Active CH Setpoint",
   "description": "CH setpoint in use",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "DHW Setpoint Source",
   "description": "What sets the active DHW setpoint",
   "units": "",
   "access": "R",
   "states": "0=Unknown, 1=Normal setpoint, 2=TOD setpoint, 5=DHW tap setpoint, 6=DHW preheat setpoint"
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Active DHW Setpoint",
   "description": "DHW setpoint in use",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "LL Master Setpoint Source",
   "description": "What sets the lead lag master setpoint",
   "units": "",
   "access": "R",
   "states": "0=Unknown, 1=CH setpoint, 2=CH TOD setpoint, 3=Outdoor reset, 4=Remote control (4-20 mA), 5=DHW setpoint, 6=DHW TOD setpoint, 7=Outdoor reset time of day, 8=Mix setpoint"
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Active LL Setpoint",
   "description": "Lead lag setpoint in use",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Supply Sensor",
   "description": "Supply water temperature (-40 to 266)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Return Sensor",
   "description": "Return water temperature (-40 to 266)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Header Sensor",
   "description": "Header temperature (-40 to 266)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Stack Sensor",
   "description": "Flue stack temperature (-40 to 266)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Outdoor Sensor",
   "description": "Outdoor air temperature (-40 to 266)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "4-20 mA Rem Control Input",
   "description": "4-20 mA remote setpoint/modulation input",
   "units": "mA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Fan Speed",
   "description": "Combustion blower speed",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Flame Signal",
   "description": "Flame signal (0.00-50.00)",
   "units": "V or µA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Burner Control State",
   "description": "Burner sequence state",
   "units": "",
   "access": "R",
   "states": "0=Initiate, 1=Standby Delay, 2=Standby, 3=Safe Startup, 4=Prepurge - Drive to Purge Rate, 5=Prepurge - Measured Purge Time, 6=Prepurge - Drive to Lightoff Rate, 7=Preignition Test, 8=Preignition Time, 9=Pilot Flame Establishing Period, 10=Main Flame Establishing Period, 11=Direct Burner Ignition, 12=Run, 13=Postpurge, 14=Lockout"
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Lockout Code",
   "description": "Reason for burner lockout",
   "units": "",
   "access": "R",
   "states": "0=No lockout, 4=Supply high limit, 5=DHW high limit, 6=Stack high limit, 12=Flame detected out of sequence, 18=Lightoff rate proving failed, 19=Purge rate proving failed, 20=Invalid safety parameters, 21=Invalid modulation parameter, 22=Safety data verification needed, 23=24VAC voltage low/high, 24=Fuel valve error, 25=Hardware fault, 26=Internal fault, 27=Ignition failure"
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Hold Code",
   "description": "Reason for burner hold",
   "units": "",
   "access": "R",
   "states": "0=None, 1=Anti short cycle, 2=Boiler safety limit open, 3=Boiler safety limit open (ILK off), 7=Return sensor fault, 8=Supply sensor fault, 9=DHW sensor fault, 10=Stack sensor fault, 11=Ignition failure, 13=Flame rod shorted to ground, 14=Delta T inlet/outlet high, 15=Return temp higher than supply, 16=Supply temp has risen too quickly, 17=Fan speed not proved, 23=24VAC voltage low/high, 25=Hardware fault, 27=Ignition failure"
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Burner Cycle Count",
   "description": "Burner cycle counter (0-999,999)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Burner Run Time",
   "description": "Burner run time counter",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "System Pum Cycle Count",
   "description": "System pump cycle counter",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "DHW Pump Cycle Count",
   "description": "DHW pump cycle counter",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Boiler Pump Cycle Count",
   "description": "Boiler pump cycle counter",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/thermal-solutions/apex-panasonic-4109-universal-gateway",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}