 "manufacturer": "Siemens",
 "manufacturer_slug": "siemens",
 "model": "BACnet Room Pressure Monitor (RPM / SRCM)",
 "model_slug": "bacnet-room-pressure-monitor-rpm",
 "short_model": "BACnet Room Pressure Monitor",
 "aliases": [
  "Siemens RPM",
  "SRCM",
  "Setra SRCM",
  "Room Condition Monitor"
 ],
 "equipment_type": "Room pressure monitor",
 "applies_to": "The Siemens BACnet Room Pressure Monitor (SRCM device) for single-room differential pressure monitoring with door input and alarm relay.",
 "summary": "A single-room differential pressure monitor sold by Siemens as a standard BACnet device. Its point map has one pressure input, alarm limits and timers, a door input, an alarm-active flag, relay and alarm settings, and selectors for the analog output type, pressure unit and room type. It has no application point; the field panel assigns a project application number.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The point map has no access column; AI and BI are shown read-only and AV, BV and MV writable (the map lists them as logical outputs).",
  "Pressure units follow the pressure unit selector MV 2 (inWC, Pa or cmWC); inH2O is shown here. The map's footnote calls this point 18 (MV_3); point 18 is MV_2 in the table.",
  "The analog output units (mA or V) follow MV 1.",
  "Most binary objects print only placeholder state text (\"Inactive Text\" / \"Active Text\"); those states are left blank here.",
  "Besides the 19 points, the map lists event enrollments and notification classes 1-3 for alarm, pressure out of limit and door open.",
  "The point map does not name the data link. Setra's PICS for the SRCM (Room Condition Monitor, SS-SRCM-BAC-PICS Rev A) lists BACnet MS/TP master at 9600, 19200, 38400 and 76800 baud."
 ],
 "source": {
  "title": "BACnet Room Pressure Monitor Point Map",
  "doc_number": "140-1300",
  "revision_date": "2014-09-03",
  "url": "https://sid.siemens.com/api/khub/documents/mfqHydSg0AIgD_1KIpx8tg/content"
 },
 "integration": {
  "summary": "Read the room pressure (AI 1), the door input (BI 1) and the alarm-active flag (BV 2). Alarm limits, delay and the pressure unit can be set over BACnet. Event enrollments 1-3 can send alarm, out-of-limit and door-open notifications.",
  "minimum_points": [
   {
    "ref": "AI 1",
    "name": "AI_1",
    "why": "Room differential pressure"
   },
   {
    "ref": "BI 1",
    "name": "DOOR STATUS",
    "why": "Door open/closed input"
   },
   {
    "ref": "BV 2",
    "name": "ALARM ACTIVE",
    "why": "Pressure alarm active"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The device has no application point; the SRCM is set up at the field panel with a project-specific application number from 10000 to 11999."
  ],
  "gotchas": [
   "Changing the pressure unit (MV 2) changes the units of the pressure reading and the alarm limits."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "AI_1",
   "description": "Room differential pressure shown on the display",
   "units": "inH2O",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "AV_1",
   "description": "Analog output value (4-20 mA, 0-5 V or 0-10 V)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "AV_2",
   "description": "Pressure alarm low limit",
   "units": "inH2O",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "AV_3",
   "description": "Pressure alarm high limit",
   "units": "inH2O",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "AV_4",
   "description": "Alarm mute time-out",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "ALARM DELAY",
   "description": "Alarm delay",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "AV_6",
   "description": "Buzzer volume, 0-4",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "DOOR STATUS",
   "description": "Door status input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "BV_1",
   "description": "Relay operate",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "ALARM ACTIVE",
   "description": "Alarm active",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "BV_3",
   "description": "Enabled or disabled",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "BV_4",
   "description": "Audible alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "LATCH ALARM",
   "description": "Latch alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "DOOR CONTACT",
   "description": "Door contact",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "BV_7",
   "description": "Supervisor password",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "BV_8",
   "description": "Operator password",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "MV_1",
   "description": "Analog output signal type",
   "units": "",
   "access": "W",
   "states": "1=4-20mA, 2=0-5Vdc, 3=0-10Vdc"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "MV_2",
   "description": "Pressure unit",
   "units": "",
   "access": "W",
   "states": "1=inWC, 2=Pa, 3=CmWC"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "ROOM TYPE",
   "description": "Room pressurization type",
   "units": "",
   "access": "W",
   "states": "1=Positive, 2=Negative, 3=Neutral"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/siemens/bacnet-room-pressure-monitor-rpm",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}