Room pressure monitor and controller · BACnet points list
Setra FLEX Room Pressure Monitor BACnet points list
Updated 28 October 2026
The Setra FLEX is a touch-screen room pressure and environmental monitor that watches up to three rooms with six parameters each (pressure, temperature, humidity, ACH and two user-defined). It talks BACnet IP or BACnet MS/TP and exposes the room readings, alarm states, limits and almost all setup as objects; each room parameter can come from an on-board input or be read from another BACnet device. The FLEX-RC version can also control equipment with PI loops or BACnet setpoint overrides.
This page lists 513 BACnet objects for the Setra FLEX Room Pressure Monitor — 455 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Setra’s own free documentation, linked below.
- Manufacturer
- Setra
- Model
- Setra FLEX Room Pressure Monitor
- Equipment
- Room pressure monitor and controller
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 513 (455 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- SetraFLEX, Setra FLEX, FLEX-RM, FLEX-RC, Setra FLEX Environmental Monitor
Reference only, provided as-is: verify against Setra’s current documentation and the live device before use. Not official Setra information. Terms of use.
BMS integration notes: Setra FLEX Room Pressure Monitor
Read the room pressure, temperature and humidity AIs and the per-room and system alarm state MIs; map the door inputs if used. Room standby (BV 72-74) and the active room profile (MV 19-21) can be written from the BMS to switch modes such as occupied and unoccupied. On FLEX-RC units the four setpoint controls have preset A/B setpoints and limits in AV 177-206.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 72 | Room 1 Standby | Room 1 standby: 1 = Standby, 0 = Active | Write |
| MV 19 | Room 1 Room Profile | Active room profile 1-4 (e.g. occupied/unoccupied) | Write |
| AV 177 | Setpoint Control 1 - Preset A Setpoint | Control 1 setpoint, preset A (FLEX-RC) | Write |
| AI 13 | Room 1 Pressure | Room 1 differential pressure | Read |
| AI 14 | Room 1 Temperature | Room 1 temperature, from its configured source | Read |
| AI 15 | Room 1 Humidity | Room 1 humidity, from its configured source | Read |
| BI 13 | Room 1 Door Input | Room 1 door switch | Read |
| MI 19 | Room 1 Alarm State | Room 1: 1 Normal, 2 Warning, 3 Alarm, 4 Standby | Read |
| MI 22 | System Alarm State | Whole-unit alarm state, same states | Read |
Enable & remote start
Room 1-3 Standby (BV 72-74) put a room in standby, and Room 1-3 Room Profile (MV 19-21) pick which of the four profiles (alarm limits and control presets) is active.
Sensors & values from the BMS
Each room parameter has a source selector (MV 1-18, 6 = BACnet). With BACnet selected, the FLEX reads the value from another device set by the matching device instance, object instance and object type objects (AV 141-176, MV 55-72). The four setpoint controls point at external BACnet setpoint objects set by AV 183/184, 191/192, 199/200 and 207/208 (device and object instance).
Network setup
- BACnet IP uses IPv4 with static IP or DHCP; BACnet MS/TP runs at up to 76.8 kbps (Setra data sheet and specification guide).
- The device object is listed as Device-4194302 with an instance range of 0-4194303, where 4194303 means unconfigured.
- Setra states that anything set up on the touch screen can also be set over BACnet, except passwords, the device ID and read-only items.
Watch out for
- Most of the list is configuration (limits, delays, display, sources); avoid writing those objects cyclically from the BMS.
- MV 90-93 set the BACnet priority used for the setpoint overrides; check they do not clash with the BMS command priority.
- Execute BACnet Time Sync? (BV 7) must be 1 for the unit to accept BACnet time synchronization.
- Operator Password (CSV 18) is writable over BACnet; restrict write access on the BMS side.
Setra FLEX Room Pressure Monitor BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | 4194302 | Setra FLEX | Device object | Write | ||
| AI | 1 | On-Board Analog Input | On-board input value | Read | ||
| AI | 2 | On-Board Universal Input 1 | On-board input value | Read | ||
| AI | 3 | On-Board Universal Input 2 | On-board input value | Read | ||
| AI | 4 | On-Board Universal Input 3 | On-board input value | Read | ||
| AImin | 13 | Room 1 Pressure | Room 1 pressure value from its configured source | Read | ||
| AImin | 14 | Room 1 Temperature | Room 1 temperature value from its configured source | Read | ||
| AImin | 15 | Room 1 Humidity | Room 1 humidity value from its configured source | Read | ||
| AI | 16 | Room 1 ACH | Room 1 ACH value from its configured source | Read | ||
| AI | 17 | Room 1 User Defined 1 | Room 1 user defined 1 value from its configured source | Read | ||
| AI | 18 | Room 1 User Defined 2 | Room 1 user defined 2 value from its configured source | Read | ||
| AI | 19 | Room 2 Pressure | Room 2 pressure value from its configured source | Read | ||
| AI | 20 | Room 2 Temperature | Room 2 temperature value from its configured source | Read | ||
| AI | 21 | Room 2 Humidity | Room 2 humidity value from its configured source | Read | ||
| AI | 22 | Room 2 ACH | Room 2 ACH value from its configured source | Read | ||
| AI | 23 | Room 2 User Defined 1 | Room 2 user defined 1 value from its configured source | Read | ||
| AI | 24 | Room 2 User Defined 2 | Room 2 user defined 2 value from its configured source | Read | ||
| AI | 25 | Room 3 Pressure | Room 3 pressure value from its configured source | Read | ||
| AI | 26 | Room 3 Temperature | Room 3 temperature value from its configured source | Read | ||
| AI | 27 | Room 3 Humidity | Room 3 humidity value from its configured source | Read | ||
| AI | 28 | Room 3 ACH | Room 3 ACH value from its configured source | Read | ||
| AI | 29 | Room 3 User Defined 1 | Room 3 user defined 1 value from its configured source | Read | ||
| AI | 30 | Room 3 User Defined 2 | Room 3 user defined 2 value from its configured source | Read | ||
| AO | 1 | On-Board Analog Output | On-board analog output value | Command | ||
| AV | 1 | Room 1 Pressure Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 2 | Room 1 Pressure High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 3 | Room 1 Pressure Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 4 | Room 1 Pressure High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 5 | Room 1 Pressure Deadband | Alarm deadband | Write | ||
| AV | 6 | Room 1 Pressure To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 7 | Room 1 Pressure Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 8 | Room 1 Temperature Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 9 | Room 1 Temperature High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 10 | Room 1 Temperature Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 11 | Room 1 Temperature High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 12 | Room 1 Temperature Deadband | Alarm deadband | Write | ||
| AV | 13 | Room 1 Temperature To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 14 | Room 1 Temperature Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 15 | Room 1 Humidity Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 16 | Room 1 Humidity High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 17 | Room 1 Humidity Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 18 | Room 1 Humidity High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 19 | Room 1 Humidity Deadband | Alarm deadband | Write | ||
| AV | 20 | Room 1 Humidity To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 21 | Room 1 Humidity Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 22 | Room 1 ACH Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 23 | Room 1 ACH High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 24 | Room 1 ACH Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 25 | Room 1 ACH High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 26 | Room 1 ACH Deadband | Alarm deadband | Write | ||
| AV | 27 | Room 1 ACH To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 28 | Room 1 ACH Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 29 | Room 1 User Defined 1 Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 30 | Room 1 User Defined 1 High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 31 | Room 1 User Defined 1 Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 32 | Room 1 User Defined 1 High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 33 | Room 1 User Defined 1 Deadband | Alarm deadband | Write | ||
| AV | 34 | Room 1 User Defined 1 To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 35 | Room 1 User Defined 1 Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 36 | Room 1 User Defined 2 Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 37 | Room 1 User Defined 2 High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 38 | Room 1 User Defined 2 Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 39 | Room 1 User Defined 2 High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 40 | Room 1 User Defined 2 Deadband | Alarm deadband | Write | ||
| AV | 41 | Room 1 User Defined 2 To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 42 | Room 1 User Defined 2 Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 43 | Room 2 Pressure Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 44 | Room 2 Pressure High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 45 | Room 2 Pressure Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 46 | Room 2 Pressure High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 47 | Room 2 Pressure Deadband | Alarm deadband | Write | ||
| AV | 48 | Room 2 Pressure To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 49 | Room 2 Pressure Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 50 | Room 2 Temperature Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 51 | Room 2 Temperature High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 52 | Room 2 Temperature Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 53 | Room 2 Temperature High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 54 | Room 2 Temperature Deadband | Alarm deadband | Write | ||
| AV | 55 | Room 2 Temperature To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 56 | Room 2 Temperature Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 57 | Room 2 Humidity Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 58 | Room 2 Humidity High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 59 | Room 2 Humidity Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 60 | Room 2 Humidity High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 61 | Room 2 Humidity Deadband | Alarm deadband | Write | ||
| AV | 62 | Room 2 Humidity To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 63 | Room 2 Humidity Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 64 | Room 2 ACH Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 65 | Room 2 ACH High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 66 | Room 2 ACH Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 67 | Room 2 ACH High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 68 | Room 2 ACH Deadband | Alarm deadband | Write | ||
| AV | 69 | Room 2 ACH To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 70 | Room 2 ACH Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 71 | Room 2 User Defined 1 Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 72 | Room 2 User Defined 1 High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 73 | Room 2 User Defined 1 Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 74 | Room 2 User Defined 1 High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 75 | Room 2 User Defined 1 Deadband | Alarm deadband | Write | ||
| AV | 76 | Room 2 User Defined 1 To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 77 | Room 2 User Defined 1 Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 78 | Room 2 User Defined 2 Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 79 | Room 2 User Defined 2 High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 80 | Room 2 User Defined 2 Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 81 | Room 2 User Defined 2 High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 82 | Room 2 User Defined 2 Deadband | Alarm deadband | Write | ||
| AV | 83 | Room 2 User Defined 2 To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 84 | Room 2 User Defined 2 Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 85 | Room 3 Pressure Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 86 | Room 3 Pressure High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 87 | Room 3 Pressure Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 88 | Room 3 Pressure High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 89 | Room 3 Pressure Deadband | Alarm deadband | Write | ||
| AV | 90 | Room 3 Pressure To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 91 | Room 3 Pressure Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 92 | Room 3 Temperature Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 93 | Room 3 Temperature High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 94 | Room 3 Temperature Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 95 | Room 3 Temperature High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 96 | Room 3 Temperature Deadband | Alarm deadband | Write | ||
| AV | 97 | Room 3 Temperature To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 98 | Room 3 Temperature Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 99 | Room 3 Humidity Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 100 | Room 3 Humidity High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 101 | Room 3 Humidity Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 102 | Room 3 Humidity High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 103 | Room 3 Humidity Deadband | Alarm deadband | Write | ||
| AV | 104 | Room 3 Humidity To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 105 | Room 3 Humidity Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 106 | Room 3 ACH Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 107 | Room 3 ACH High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 108 | Room 3 ACH Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 109 | Room 3 ACH High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 110 | Room 3 ACH Deadband | Alarm deadband | Write | ||
| AV | 111 | Room 3 ACH To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 112 | Room 3 ACH Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 113 | Room 3 User Defined 1 Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 114 | Room 3 User Defined 1 High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 115 | Room 3 User Defined 1 Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 116 | Room 3 User Defined 1 High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 117 | Room 3 User Defined 1 Deadband | Alarm deadband | Write | ||
| AV | 118 | Room 3 User Defined 1 To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 119 | Room 3 User Defined 1 Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 120 | Room 3 User Defined 2 Low Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 121 | Room 3 User Defined 2 High Limit - Monitor Preset A | Alarm limit for monitor preset A | Write | ||
| AV | 122 | Room 3 User Defined 2 Low Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 123 | Room 3 User Defined 2 High Limit - Monitor Preset B | Alarm limit for monitor preset B | Write | ||
| AV | 124 | Room 3 User Defined 2 Deadband | Alarm deadband | Write | ||
| AV | 125 | Room 3 User Defined 2 To Off Normal Delay | Delay before the alarm is raised | Write | ||
| AV | 126 | Room 3 User Defined 2 Return To Normal Delay | Delay before the alarm clears | Write | ||
| AV | 127 | Room 1 Length | Room dimension for ACH calculation | Write | ||
| AV | 128 | Room 1 Width | Room dimension for ACH calculation | Write | ||
| AV | 129 | Room 1 Height | Room dimension for ACH calculation | Write | ||
| AV | 130 | Room 2 Length | Room dimension for ACH calculation | Write | ||
| AV | 131 | Room 2 Width | Room dimension for ACH calculation | Write | ||
| AV | 132 | Room 2 Height | Room dimension for ACH calculation | Write | ||
| AV | 133 | Room 3 Length | Room dimension for ACH calculation | Write | ||
| AV | 134 | Room 3 Width | Room dimension for ACH calculation | Write | ||
| AV | 135 | Room 3 Height | Room dimension for ACH calculation | Write | ||
| AV | 209 | Room 1 Duct Cross Sectional Area | Duct area for ACH from velocity | Write | ||
| AV | 210 | Room 2 Duct Cross Sectional Area | Duct area for ACH from velocity | Write | ||
| AV | 211 | Room 3 Duct Cross Sectional Area | Duct area for ACH from velocity | Write | ||
| AV | 136 | Mute Time Out | How long an alarm stays muted | Write | ||
| AV | 138 | Brightness Level | Display brightness level | Write | ||
| AV | 139 | Home Screen Timeout | Time before returning to the home screen | Write | ||
| AV | 140 | Room Carousel Interval | Time each room is shown in the carousel | Write | ||
| AV | 212 | Turn Off Display After Timeout | Time before the display turns off | Write | ||
| BV | 1 | Latch Alarm Enable | Alarms stay latched until acknowledged | Write | 0 = Latch Disabled, 1 = Latch Enabled | |
| BV | 2 | Audible Alarm Status | Audible alarm on/off | Write | 0 = Audible Alarm Disabled, 1 = Audible Alarm Enabled | |
| BV | 3 | Mute Alarm Enable | Allow alarm muting | Write | 0 = Mute Disabled, 1 = Mute Enabled | |
| BV | 4 | Default To Full Screen | Home screen view | Write | 0 = Show Single Room View, 1 = Show Full Screen View | |
| BV | 5 | Room Carousel | Cycle through rooms on the home screen | Write | 0 = Room Carousel Disabled, 1 = Room Carousel Enabled | |
| BV | 100 | Display Turn Off Enable | Allow the display to turn off | Write | 0 = Display turn off disabled, 1 = Display turn off enabled | |
| AV | 141 | Room 1 Pressure BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 142 | Room 1 Pressure BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 143 | Room 1 Temperature BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 144 | Room 1 Temperature BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 145 | Room 1 Humidity BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 146 | Room 1 Humidity BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 147 | Room 1 ACH BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 148 | Room 1 ACH BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 149 | Room 1 User Defined 1 BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 150 | Room 1 User Defined 1 BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 151 | Room 1 User Defined 2 BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 152 | Room 1 User Defined 2 BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 153 | Room 2 Pressure BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 154 | Room 2 Pressure BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 155 | Room 2 Temperature BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 156 | Room 2 Temperature BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 157 | Room 2 Humidity BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 158 | Room 2 Humidity BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 159 | Room 2 ACH BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 160 | Room 2 ACH BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 161 | Room 2 User Defined 1 BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 162 | Room 2 User Defined 1 BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 163 | Room 2 User Defined 2 BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 164 | Room 2 User Defined 2 BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 165 | Room 3 Pressure BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 166 | Room 3 Pressure BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 167 | Room 3 Temperature BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 168 | Room 3 Temperature BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 169 | Room 3 Humidity BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 170 | Room 3 Humidity BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 171 | Room 3 ACH BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 172 | Room 3 ACH BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 173 | Room 3 User Defined 1 BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 174 | Room 3 User Defined 1 BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AV | 175 | Room 3 User Defined 2 BACnet Device Instance | Device instance of the BACnet source | Write | ||
| AV | 176 | Room 3 User Defined 2 BACnet Object Instance | Object instance of the BACnet source | Write | ||
| AVmin | 177 | Setpoint Control 1 - Preset A Setpoint | Control setpoint for preset A | Write | ||
| AV | 178 | Setpoint Control 1 - Preset A Max Setpoint | Highest setpoint allowed, preset A | Write | ||
| AV | 179 | Setpoint Control 1 - Preset A Min Setpoint | Lowest setpoint allowed, preset A | Write | ||
| AV | 180 | Setpoint Control 1 - Preset B Setpoint | Control setpoint for preset B | Write | ||
| AV | 181 | Setpoint Control 1 - Preset B Max Setpoint | Highest setpoint allowed, preset B | Write | ||
| AV | 182 | Setpoint Control 1 - Preset B Min Setpoint | Lowest setpoint allowed, preset B | Write | ||
| AV | 183 | External Setpoint 1 BACnet Device Instance | Device instance of the external setpoint object | Write | ||
| AV | 184 | External Setpoint 1 BACnet Object Instance | Object instance of the external setpoint object | Write | ||
| AV | 185 | Setpoint Control 2 - Preset A Setpoint | Control setpoint for preset A | Write | ||
| AV | 186 | Setpoint Control 2 - Preset A Max Setpoint | Highest setpoint allowed, preset A | Write | ||
| AV | 187 | Setpoint Control 2 - Preset A Min Setpoint | Lowest setpoint allowed, preset A | Write | ||
| AV | 188 | Setpoint Control 2 - Preset B Setpoint | Control setpoint for preset B | Write | ||
| AV | 189 | Setpoint Control 2 - Preset B Max Setpoint | Highest setpoint allowed, preset B | Write | ||
| AV | 190 | Setpoint Control 2 - Preset B Min Setpoint | Lowest setpoint allowed, preset B | Write | ||
| AV | 191 | External Setpoint 2 BACnet Device Instance | Device instance of the external setpoint object | Write | ||
| AV | 192 | External Setpoint 2 BACnet Object Instance | Object instance of the external setpoint object | Write | ||
| AV | 193 | Setpoint Control 3 - Preset A Setpoint | Control setpoint for preset A | Write | ||
| AV | 194 | Setpoint Control 3 - Preset A Max Setpoint | Highest setpoint allowed, preset A | Write | ||
| AV | 195 | Setpoint Control 3 - Preset A Min Setpoint | Lowest setpoint allowed, preset A | Write | ||
| AV | 196 | Setpoint Control 3 - Preset B Setpoint | Control setpoint for preset B | Write | ||
| AV | 197 | Setpoint Control 3 - Preset B Max Setpoint | Highest setpoint allowed, preset B | Write | ||
| AV | 198 | Setpoint Control 3 - Preset B Min Setpoint | Lowest setpoint allowed, preset B | Write | ||
| AV | 199 | External Setpoint 3 BACnet Device Instance | Device instance of the external setpoint object | Write | ||
| AV | 200 | External Setpoint 3 BACnet Object Instance | Object instance of the external setpoint object | Write | ||
| AV | 201 | Setpoint Control 4 - Preset A Setpoint | Control setpoint for preset A | Write | ||
| AV | 202 | Setpoint Control 4 - Preset A Max Setpoint | Highest setpoint allowed, preset A | Write | ||
| AV | 203 | Setpoint Control 4 - Preset A Min Setpoint | Lowest setpoint allowed, preset A | Write | ||
| AV | 204 | Setpoint Control 4 - Preset B Setpoint | Control setpoint for preset B | Write | ||
| AV | 205 | Setpoint Control 4 - Preset B Max Setpoint | Highest setpoint allowed, preset B | Write | ||
| AV | 206 | Setpoint Control 4 - Preset B Min Setpoint | Lowest setpoint allowed, preset B | Write | ||
| AV | 207 | External Setpoint 4 BACnet Device Instance | Device instance of the external setpoint object | Write | ||
| AV | 208 | External Setpoint 4 BACnet Object Instance | Object instance of the external setpoint object | Write | ||
| BI | 2 | On-Board Digital Input 2 | On-board digital input | Read | Active, Inactive | |
| BI | 3 | On-Board Digital Input 3 | On-board digital input | Read | Active, Inactive | |
| BI | 4 | On-Board Digital Input 4 | On-board digital input | Read | Active, Inactive | |
| BImin | 13 | Room 1 Door Input | Door switch input | Read | Active, Inactive | |
| BI | 14 | Room 2 Door Input | Door switch input | Read | Active, Inactive | |
| BI | 15 | Room 3 Door Input | Door switch input | Read | Active, Inactive | |
| BO | 1 | On-Board Relay | On-board relay output | Write | 0=COM NO Shorted, 1=COM NC Shorted | |
| BV | 8 | Room 1 Pressure Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 9 | Room 1 Temperature Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 10 | Room 1 Humidity Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 11 | Room 1 ACH Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 12 | Room 1 User Defined 1 Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 13 | Room 1 User Defined 2 Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 14 | Room 2 Pressure Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 15 | Room 2 Temperature Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 16 | Room 2 Humidity Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 17 | Room 2 ACH Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 18 | Room 2 User Defined 1 Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 19 | Room 2 User Defined 2 Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 20 | Room 3 Pressure Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 21 | Room 3 Temperature Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 22 | Room 3 Humidity Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 23 | Room 3 ACH Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 24 | Room 3 User Defined 1 Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 25 | Room 3 User Defined 2 Parameter Enable | Show and monitor this room parameter | Write | 0=Disabled, 1=Enabled | |
| BV | 26 | Room 1 Pressure Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 27 | Room 1 Pressure High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 28 | Room 1 Temperature Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 29 | Room 1 Temperature High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 30 | Room 1 Humidity Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 31 | Room 1 Humidity High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 32 | Room 1 ACH Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 33 | Room 1 ACH High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 34 | Room 1 User Defined 1 Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 35 | Room 1 User Defined 1 High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 36 | Room 1 User Defined 2 Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 37 | Room 1 User Defined 2 High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 38 | Room 2 Pressure Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 39 | Room 2 Pressure High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 40 | Room 2 Temperature Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 41 | Room 2 Temperature High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 42 | Room 2 Humidity Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 43 | Room 2 Humidity High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 44 | Room 2 ACH Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 45 | Room 2 ACH High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 46 | Room 2 User Defined 1 Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 47 | Room 2 User Defined 1 High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 48 | Room 2 User Defined 2 Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 49 | Room 2 User Defined 2 High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 50 | Room 3 Pressure Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 51 | Room 3 Pressure High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 52 | Room 3 Temperature Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 53 | Room 3 Temperature High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 54 | Room 3 Humidity Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 55 | Room 3 Humidity High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 56 | Room 3 ACH Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 57 | Room 3 ACH High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 58 | Room 3 User Defined 1 Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 59 | Room 3 User Defined 1 High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 60 | Room 3 User Defined 2 Low Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 61 | Room 3 User Defined 2 High Limit Enable | Enable this alarm limit | Write | 0=Disabled, 1=Enabled | |
| BV | 62 | Room 1 Door Enable | Enable door monitoring | Write | 0=Disabled, 1=Enabled | |
| BV | 63 | Room 2 Door Enable | Enable door monitoring | Write | 0=Disabled, 1=Enabled | |
| BV | 64 | Room 3 Door Enable | Enable door monitoring | Write | 0=Disabled, 1=Enabled | |
| BV | 65 | Room 1 Enable | Enable this room | Write | 0=Disabled, 1=Enabled | |
| BV | 66 | Room 2 Enable | Enable this room | Write | 0=Disabled, 1=Enabled | |
| BV | 67 | Room 3 Enable | Enable this room | Write | 0=Disabled, 1=Enabled | |
| BV | 68 | Room Profile 1 Alarm Enable | Enable alarms for this room profile | Write | 0=Disabled, 1=Enabled | |
| BV | 69 | Room Profile 2 Alarm Enable | Enable alarms for this room profile | Write | 0=Disabled, 1=Enabled | |
| BV | 70 | Room Profile 3 Alarm Enable | Enable alarms for this room profile | Write | 0=Disabled, 1=Enabled | |
| BV | 71 | Room Profile 4 Alarm Enable | Enable alarms for this room profile | Write | 0=Disabled, 1=Enabled | |
| BVmin | 72 | Room 1 Standby | Put the room in standby | Write | 0=Active, 1=Standby | |
| BV | 73 | Room 2 Standby | Put the room in standby | Write | 0=Active, 1=Standby | |
| BV | 74 | Room 3 Standby | Put the room in standby | Write | 0=Active, 1=Standby | |
| BV | 75 | Control Loop 1 Setpoint Type | Control by BACnet setpoint or PI loop | Write | 0=BACnet, 1=PI Loop | |
| BV | 76 | Control Loop 2 Setpoint Type | Control by BACnet setpoint or PI loop | Write | 0=BACnet, 1=PI Loop | |
| BV | 77 | Control Loop 3 Setpoint Type | Control by BACnet setpoint or PI loop | Write | 0=BACnet, 1=PI Loop | |
| BV | 78 | Control Loop 4 Setpoint Type | Control by BACnet setpoint or PI loop | Write | 0=BACnet, 1=PI Loop | |
| BV | 79 | Time Display Format | Decimal places shown | Write | 0 = Use 12-hour format, 1 = Use 24-hour format | |
| BV | 7 | Execute BACnet Time Sync? | Accept BACnet time synchronization | Write | 0 = Ignore BACnet Time Sync, 1 = Execute BACnet Time Sync | |
| BV | 80 | Display date on home screen | Show the date on the home screen | Write | 0=Date not displayed on home screen, 1=Date displayed on home screen | |
| BV | 81 | Display time on home screen | Show the time on the home screen | Write | 0=Time not displayed on home screen, 1=Time displayed on home screen | |
| BV | 82 | Room 1 Pressure Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 83 | Room 1 Temperature Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 84 | Room 1 Humidity Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 85 | Room 1 ACH Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 86 | Room 1 User Defined 1 Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 87 | Room 1 User Defined 2 Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 88 | Room 2 Pressure Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 89 | Room 2 Temperature Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 90 | Room 2 Humidity Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 91 | Room 2 ACH Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 92 | Room 2 User Defined 1 Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 93 | Room 2 User Defined 2 Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 94 | Room 3 Pressure Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 95 | Room 3 Temperature Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 96 | Room 3 Humidity Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 97 | Room 3 ACH Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 98 | Room 3 User Defined 1 Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| BV | 99 | Room 3 User Defined 2 Display Unit | Units set locally or read from BACnet source | Write | 0=Units updated for room 1 pressure parameter via local UI, 1=Obtain from BACnet source | |
| MI | 1 | Room 1 Pressure Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 2 | Room 1 Temperature Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 3 | Room 1 Humidity Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 4 | Room 1 ACH Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 5 | Room 1 User Defined 1 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 6 | Room 1 user Defined 2 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 7 | Room 2 Pressure Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 8 | Room 2 Temperature Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 9 | Room 2 Humidity Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 10 | Room 2 ACH Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 11 | Room 2 User Defined 1 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 12 | Room 2 user Defined 2 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 13 | Room 3 Pressure Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 14 | Room 3 Temperature Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 15 | Room 3 Humidity Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 16 | Room 3 ACH Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 17 | Room 3 User Defined 1 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 18 | Room 3 user Defined 2 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MImin | 19 | Room 1 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 20 | Room 2 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MI | 21 | Room 3 Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MImin | 22 | System Alarm State | Alarm state | Read | 1=Normal, 2=Warning, 3=Alarm, 4=Standby | |
| MV | 1 | Room 1 Pressure Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 2 | Room 1 Temperature Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 3 | Room 1 Humidity Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 4 | Room 1 ACH Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 5 | Room 1 User Defined 1 Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 6 | Room 1 User Defined 2 Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 7 | Room 2 Pressure Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 8 | Room 2 Temperature Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 9 | Room 2 Humidity Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 10 | Room 2 ACH Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 11 | Room 2 User Defined 1 Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 12 | Room 2 User Defined 2 Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 13 | Room 3 Pressure Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 14 | Room 3 Temperature Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 15 | Room 3 Humidity Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 16 | Room 3 ACH Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 17 | Room 3 User Defined 1 Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 18 | Room 3 User Defined 2 Source | Where this room parameter comes from | Write | 1=NONE, 2=On-Board AI-1, 3=On-Board UI-1, 4=On-Board UI-2, 5=On-Board UI-3, 6=BACnet | |
| MV | 83 | Room 1 Door Source | Input used for the door switch | Write | 1=NONE, 2=On-Board UI-1, 3=On-Board UI-2, 4=On-Board UI-3 | |
| MV | 84 | Room 2 Door Source | Input used for the door switch | Write | 1=NONE, 2=On-Board UI-1, 3=On-Board UI-2, 4=On-Board UI-3 | |
| MV | 85 | Room 3 Door Source | Input used for the door switch | Write | 1=NONE, 2=On-Board UI-1, 3=On-Board UI-2, 4=On-Board UI-3 | |
| MVmin | 19 | Room 1 Room Profile | Active room profile | Write | 1=Profile 1, 2=Profile 2, 3=Profile 3, 4=Profile 4 | |
| MV | 20 | Room 2 Room Profile | Active room profile | Write | 1=Profile 1, 2=Profile 2, 3=Profile 3, 4=Profile 4 | |
| MV | 21 | Room 3 Room Profile | Active room profile | Write | 1=Profile 1, 2=Profile 2, 3=Profile 3, 4=Profile 4 | |
| MV | 22 | On-Board Analog Output Type | Output signal type | Write | 1=4 to 20mA, 2=0 to 5VDC, 3=0 to 10VDC | |
| MV | 27 | On-Board Analog Input 1 Type | Signal type of input 1 | Write | 1=None, 2=mA, 3=VDC, 4=Digital (MSV 28, 29, & 30 only) | |
| MV | 28 | On-Board Analog Input 2 Type | Signal type of input 2 | Write | 1=None, 2=mA, 3=VDC, 4=Digital (MSV 28, 29, & 30 only) | |
| MV | 29 | On-Board Analog Input 3 Type | Signal type of input 3 | Write | 1=None, 2=mA, 3=VDC, 4=Digital (MSV 28, 29, & 30 only) | |
| MV | 30 | On-Board Analog Input 4 Type | Signal type of input 4 | Write | 1=None, 2=mA, 3=VDC, 4=Digital (MSV 28, 29, & 30 only) | |
| MV | 39 | Room Profile 1 Icon | Icon shown for this profile | Write | 1=Icon 1, 2=Icon 2, 3=Icon 3, 4=Icon 4, 5=Icon 5, 6=Icon 6, 7=Icon 7, 8=Icon 8, 9=Icon 9, 10=Icon 10, 11=Icon 11, 12=Icon 12, 13=Icon 13, 14=Icon 14, 15=Icon 15, 16=Icon 16, 17=Icon 17, 18=Icon 18, 19=Icon 19, 20=Icon 20, 21=Icon 21, 22=Icon 22, 23=Icon 23, 24=Icon 24, 25=Icon 25, 26=Icon 26, 27=Icon 27, 28=Icon 28, 29=Icon 29, 30=Icon 30, 31=Icon 31, 32=Icon 32 | |
| MV | 40 | Room Profile 2 Icon | Icon shown for this profile | Write | 1=Icon 1, 2=Icon 2, 3=Icon 3, 4=Icon 4, 5=Icon 5, 6=Icon 6, 7=Icon 7, 8=Icon 8, 9=Icon 9, 10=Icon 10, 11=Icon 11, 12=Icon 12, 13=Icon 13, 14=Icon 14, 15=Icon 15, 16=Icon 16, 17=Icon 17, 18=Icon 18, 19=Icon 19, 20=Icon 20, 21=Icon 21, 22=Icon 22, 23=Icon 23, 24=Icon 24, 25=Icon 25, 26=Icon 26, 27=Icon 27, 28=Icon 28, 29=Icon 29, 30=Icon 30, 31=Icon 31, 32=Icon 32 | |
| MV | 41 | Room Profile 3 Icon | Icon shown for this profile | Write | 1=Icon 1, 2=Icon 2, 3=Icon 3, 4=Icon 4, 5=Icon 5, 6=Icon 6, 7=Icon 7, 8=Icon 8, 9=Icon 9, 10=Icon 10, 11=Icon 11, 12=Icon 12, 13=Icon 13, 14=Icon 14, 15=Icon 15, 16=Icon 16, 17=Icon 17, 18=Icon 18, 19=Icon 19, 20=Icon 20, 21=Icon 21, 22=Icon 22, 23=Icon 23, 24=Icon 24, 25=Icon 25, 26=Icon 26, 27=Icon 27, 28=Icon 28, 29=Icon 29, 30=Icon 30, 31=Icon 31, 32=Icon 32 | |
| MV | 42 | Room Profile 4 Icon | Icon shown for this profile | Write | 1=Icon 1, 2=Icon 2, 3=Icon 3, 4=Icon 4, 5=Icon 5, 6=Icon 6, 7=Icon 7, 8=Icon 8, 9=Icon 9, 10=Icon 10, 11=Icon 11, 12=Icon 12, 13=Icon 13, 14=Icon 14, 15=Icon 15, 16=Icon 16, 17=Icon 17, 18=Icon 18, 19=Icon 19, 20=Icon 20, 21=Icon 21, 22=Icon 22, 23=Icon 23, 24=Icon 24, 25=Icon 25, 26=Icon 26, 27=Icon 27, 28=Icon 28, 29=Icon 29, 30=Icon 30, 31=Icon 31, 32=Icon 32 | |
| MV | 43 | Room Profile 1 Color | Color shown for this profile | Write | 1=BLUE, 2=GREEN, 3=PURPLE | |
| MV | 44 | Room Profile 2 Color | Color shown for this profile | Write | 1=BLUE, 2=GREEN, 3=PURPLE | |
| MV | 45 | Room Profile 3 Color | Color shown for this profile | Write | 1=BLUE, 2=GREEN, 3=PURPLE | |
| MV | 46 | Room Profile 4 Color | Color shown for this profile | Write | 1=BLUE, 2=GREEN, 3=PURPLE | |
| MV | 47 | Room Profile 1 Control Preset | Preset level used by this profile | Write | 1=Level A, 2=Level B | |
| MV | 48 | Room Profile 2 Control Preset | Preset level used by this profile | Write | 1=Level A, 2=Level B | |
| MV | 49 | Room Profile 3 Control Preset | Preset level used by this profile | Write | 1=Level A, 2=Level B | |
| MV | 50 | Room Profile 3 Control Preset | Preset level used by this profile | Write | 1=Level A, 2=Level B | |
| MV | 51 | Room Profile 1 Monitor Preset | Preset level used by this profile | Write | 1=Level A, 2=Level B | |
| MV | 52 | Room Profile 2 Monitor Preset | Preset level used by this profile | Write | 1=Level A, 2=Level B | |
| MV | 53 | Room Profile 3 Monitor Preset | Preset level used by this profile | Write | 1=Level A, 2=Level B | |
| MV | 54 | Room Profile 4 Monitor Preset | Preset level used by this profile | Write | 1=Level A, 2=Level B | |
| MV | 55 | Room 1 Pressure Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 56 | Room 1 Temperature Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 57 | Room 1 Humidity Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 58 | Room 1 ACH Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 59 | Room 1 User Defined 1 Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 60 | Room 1 User Defined 2 Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 61 | Room 2 Pressure Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 62 | Room 2 Temperature Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 63 | Room 2 Humidity Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 64 | Room 2 ACH Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 65 | Room 2 User Defined 1 Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 66 | Room 2 User Defined 2 Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 67 | Room 3 Pressure Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 68 | Room 3 Temperature Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 69 | Room 3 Humidity Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 70 | Room 3 ACH Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 71 | Room 3 User Defined 1 Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 72 | Room 3 User Defined 2 Source BACnet Object Type | Object type of the BACnet source | Write | 1=Analog-Input, 2=Analog-Output, 3=Analog-Value | |
| MV | 73 | On-Board Analog Output Source | Value sent to the analog output | Write | 1=NONE, 2=Room 1 Pressure, 3=Room 1 Temperature, 4=Room 1 Humidity, 5=Room 1 ACH, 6=Room 1 User Defined 1, 7=Room 1 User Defined 2, 8=Room 2 Pressure, 9=Room 2 Temperature, 10=Room 2 Humidity, 11=Room 2 ACH, 12=Room 2 User Defined 1, 13=Room 2 User Defined 2, 14=Room 3 Pressure, 15=Room 3 Temperature, 16=Room 3 Humidity, 17=Room 3 ACH, 18=Room 3 User Defined 1, 19=Room 3 User Defined 2, 20=Control Loop 1, 21=Control Loop 2, 22=Control Loop 3, 23=Control Loop 4 | |
| MV | 78 | On-Board Relay Source | Event that drives the relay | Write | 1=NONE, 2=Room 1 Door, 3=Room 2 Door, 4=Room 3 Door, 5=Room 1 Alarm, 6=Room 2 Alarm, 7=Room 3 Alarm, 8=Master Alarm | |
| MV | 86 | Room 1 Pressure Mode | Room pressure mode (positive/negative/neutral) | Read | 1=POS (Positive), 2=NEG (Negative), 3=NEU (Neutral) | |
| MV | 87 | Room 2 Pressure Mode | Room pressure mode (positive/negative/neutral) | Read | 1=POS (Positive), 2=NEG (Negative), 3=NEU (Neutral) | |
| MV | 88 | Room 3 Pressure Mode | Room pressure mode (positive/negative/neutral) | Read | 1=POS (Positive), 2=NEG (Negative), 3=NEU (Neutral) | |
| MV | 89 | Language Selection | Display language | Write | 1=English, 2=French | |
| MV | 90 | BACnet Setpoint 1 Override Priority | Priority used to write the BACnet setpoint | Write | 1=Priority Level 1 (Manual-Life Safety), 2=Priority Level 2 (Automatic Life-Safety), 3=Priority Level 3, 4=Priority Level 4, 5=Priority Level 5 (Critical Equipment Control), 6=Priority Level 6 (Minimum On/Off), 7=Priority Level 7, 8=Priority Level 8 (Manual Operator), 9=Priority Level 9, 10=Priority Level 10, 11=Priority Level 11, 12=Priority Level 12, 13=Priority Level 13, 14=Priority Level 14, 15=Priority Level 15, 16=Priority Level 16, 17=NONE | |
| MV | 91 | BACnet Setpoint 2 Override Priority | Priority used to write the BACnet setpoint | Write | 1=Priority Level 1 (Manual-Life Safety), 2=Priority Level 2 (Automatic Life-Safety), 3=Priority Level 3, 4=Priority Level 4, 5=Priority Level 5 (Critical Equipment Control), 6=Priority Level 6 (Minimum On/Off), 7=Priority Level 7, 8=Priority Level 8 (Manual Operator), 9=Priority Level 9, 10=Priority Level 10, 11=Priority Level 11, 12=Priority Level 12, 13=Priority Level 13, 14=Priority Level 14, 15=Priority Level 15, 16=Priority Level 16, 17=NONE | |
| MV | 92 | BACnet Setpoint 3 Override Priority | Priority used to write the BACnet setpoint | Write | 1=Priority Level 1 (Manual-Life Safety), 2=Priority Level 2 (Automatic Life-Safety), 3=Priority Level 3, 4=Priority Level 4, 5=Priority Level 5 (Critical Equipment Control), 6=Priority Level 6 (Minimum On/Off), 7=Priority Level 7, 8=Priority Level 8 (Manual Operator), 9=Priority Level 9, 10=Priority Level 10, 11=Priority Level 11, 12=Priority Level 12, 13=Priority Level 13, 14=Priority Level 14, 15=Priority Level 15, 16=Priority Level 16, 17=NONE | |
| MV | 93 | BACnet Setpoint 4 Override Priority | Priority used to write the BACnet setpoint | Write | 1=Priority Level 1 (Manual-Life Safety), 2=Priority Level 2 (Automatic Life-Safety), 3=Priority Level 3, 4=Priority Level 4, 5=Priority Level 5 (Critical Equipment Control), 6=Priority Level 6 (Minimum On/Off), 7=Priority Level 7, 8=Priority Level 8 (Manual Operator), 9=Priority Level 9, 10=Priority Level 10, 11=Priority Level 11, 12=Priority Level 12, 13=Priority Level 13, 14=Priority Level 14, 15=Priority Level 15, 16=Priority Level 16, 17=NONE | |
| MV | 94 | Room 1 Pressure Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 95 | Room 1 Temperature Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 96 | Room 1 Humidity Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 97 | Room 1 ACH Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 98 | Room 1 User Defined 1 Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 99 | Room 1 User Defined 2 Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 100 | Room 2 Pressure Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 101 | Room 2 Temperature Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 102 | Room 2 Humidity Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 103 | Room 2 ACH Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 104 | Room 2 User Defined 1 Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 105 | Room 2 User Defined 2 Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 106 | Room 3 Pressure Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 107 | Room 3 Temperature Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 108 | Room 3 Humidity Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 109 | Room 3 ACH Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 110 | Room 3 User Defined 1 Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 111 | Room 3 User Defined 2 Display Format | Decimal places shown | Write | 1=Read format from BACnet source (resolution), 2=1 (No decimal places), 3=0.1 (One decimal place), 4=0.01 (Two decimal places), 5=0.001 (Three decimal places), 6=0.0001 (Four decimal places) | |
| MV | 112 | Room 1 BACnet ACH Source type | BACnet ACH source given as ACH, volume or velocity | Write | 1=ACH, 2=Volumetric, 3=Velocity | |
| MV | 113 | Room 2 BACnet ACH Source type | BACnet ACH source given as ACH, volume or velocity | Write | 1=ACH, 2=Volumetric, 3=Velocity | |
| MV | 114 | Room 3 BACnet ACH Source type | BACnet ACH source given as ACH, volume or velocity | Write | 1=ACH, 2=Volumetric, 3=Velocity | |
| MV | 115 | Room 1 Pressure Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 116 | Room 1 Temperature Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 117 | Room 1 Humidity Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 118 | Room 1 ACH Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 119 | Room 1 User Defined 1 Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 120 | Room 1 User Defined 2 Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 121 | Room 2 Pressure Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 122 | Room 2 Temperature Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 123 | Room 2 Humidity Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 124 | Room 2 ACH Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 125 | Room 2 User Defined 1 Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 126 | Room 2 User Defined 2 Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 127 | Room 3 Pressure Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 128 | Room 3 Temperature Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 129 | Room 3 Humidity Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 130 | Room 3 ACH Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 131 | Room 3 User Defined 1 Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 132 | Room 3 User Defined 2 Alarm Warning Mode | Warning on delay or on deadband | Write | 1=On Delay, 2=On Deadband | |
| MV | 133 | Room 1 Door Alarm Action Type | What a door-open alarm does | Write | 1=Door Open Indicator only, 2=Go into Standby | |
| MV | 134 | Room 2 Door Alarm Action Type | What a door-open alarm does | Write | 1=Door Open Indicator only, 2=Go into Standby | |
| MV | 135 | Room 3 Door Alarm Action Type | What a door-open alarm does | Write | 1=Door Open Indicator only, 2=Go into Standby | |
| MV | 136 | Air Flow/Air Velocity Unit for On-Board Analog Input 1 | Airflow or velocity unit for this input | Write | 1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr | |
| MV | 137 | Air Flow/Air Velocity Unit for On-Board Universal Input 1 | Airflow or velocity unit for this input | Write | 1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr | |
| MV | 138 | Air Flow/Air Velocity Unit for On-Board Universal Input 2 | Airflow or velocity unit for this input | Write | 1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr | |
| MV | 139 | Air Flow/Air Velocity Unit for On-Board Universal Input 3 | Airflow or velocity unit for this input | Write | 1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr | |
| MV | 148 | Air Flow/Air Velocity Unit for Room 1 Volumetric/Velocity BACnet Point | Airflow or velocity unit for this input | Write | 1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr | |
| MV | 149 | Air Flow/Air Velocity Unit for Room 2 Volumetric/Velocity BACnet Point | Airflow or velocity unit for this input | Write | 1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr | |
| MV | 150 | Air Flow/Air Velocity Unit for Room 3 Volumetric/Velocity BACnet Point | Airflow or velocity unit for this input | Write | 1=ft/sec, 2=ft/min, 3=ft3/min, 4=m/sec, 5=liters/sec, 6=m3/sec, 7=m3/hr, 8=m3/min, 9=ft3/sec, 10=liters/min, 11=liters/hr, 12=m/min, 13=m/hr | |
| LO | 1 | Loop 1 | PI control loop | Write | ||
| LO | 2 | Loop 2 | PI control loop | Write | ||
| LO | 3 | Loop 3 | PI control loop | Write | ||
| LO | 4 | Loop 4 | PI control loop | Write | ||
| CSV | 1 | Room 1 Label | Display text | Write | ||
| CSV | 2 | Room 2 Label | Display text | Write | ||
| CSV | 3 | Room 3 Label | Display text | Write | ||
| CSV | 4 | Room Profile 1 Label | Display text | Write | ||
| CSV | 5 | Room Profile 2 Label | Display text | Write | ||
| CSV | 6 | Room Profile 3 Label | Display text | Write | ||
| CSV | 7 | Room Profile 4 Label | Display text | Write | ||
| CSV | 8 | Room Profile 1 Banner Label | Display text | Write | ||
| CSV | 9 | Room Profile 2 Banner Label | Display text | Write | ||
| CSV | 10 | Room Profile 3 Banner Label | Display text | Write | ||
| CSV | 11 | Room Profile 4 Banner Label | Display text | Write | ||
| CSV | 12 | Technical Support ID | Support contact text | Write | ||
| CSV | 13 | Audit Trail String 1 | Audit trail entry | Read | ||
| CSV | 14 | Audit Trail String 2 | Audit trail entry | Read | ||
| CSV | 15 | Audit Trail String 3 | Audit trail entry | Read | ||
| CSV | 16 | Audit Trail String 4 | Audit trail entry | Read | ||
| CSV | 17 | Audit Trail String 5 | Audit trail entry | Read | ||
| CSV | 18 | Operator Password | Operator password | Write | ||
| CSV | 19 | Room 1 User Defined 1 Badge Name | Name shown on the parameter badge | Write | ||
| CSV | 20 | Room 1 User Defined 2 Badge Name | Name shown on the parameter badge | Write | ||
| CSV | 21 | Room 2 User Defined 1 Badge Name | Name shown on the parameter badge | Write | ||
| CSV | 22 | Room 2 User Defined 2 Badge Name | Name shown on the parameter badge | Write | ||
| CSV | 23 | Room 3 User Defined 1 Badge Name | Name shown on the parameter badge | Write | ||
| CSV | 24 | Room 3 User Defined 2 Badge Name | Name shown on the parameter badge | Write |
No points match these filters.
Object ID lookup: Setra FLEX Room Pressure Monitor point IDs by name
AI1On-Board Analog InputAI2On-Board Universal Input 1AI3On-Board Universal Input 2AI4On-Board Universal Input 3AI13Room 1 PressureAI14Room 1 TemperatureAI15Room 1 HumidityAI16Room 1 ACHAI17Room 1 User Defined 1AI18Room 1 User Defined 2AI19Room 2 PressureAI20Room 2 TemperatureAI21Room 2 HumidityAI22Room 2 ACHAI23Room 2 User Defined 1AI24Room 2 User Defined 2AI25Room 3 PressureAI26Room 3 TemperatureAI27Room 3 HumidityAI28Room 3 ACHAI29Room 3 User Defined 1AI30Room 3 User Defined 2AO1On-Board Analog OutputAV1Room 1 Pressure Low Limit - Monitor Preset AAV2Room 1 Pressure High Limit - Monitor Preset AAV3Room 1 Pressure Low Limit - Monitor Preset BAV4Room 1 Pressure High Limit - Monitor Preset BAV5Room 1 Pressure DeadbandAV6Room 1 Pressure To Off Normal DelayAV7Room 1 Pressure Return To Normal DelayAV8Room 1 Temperature Low Limit - Monitor Preset AAV9Room 1 Temperature High Limit - Monitor Preset AAV10Room 1 Temperature Low Limit - Monitor Preset BAV11Room 1 Temperature High Limit - Monitor Preset BAV12Room 1 Temperature DeadbandAV13Room 1 Temperature To Off Normal DelayAV14Room 1 Temperature Return To Normal DelayAV15Room 1 Humidity Low Limit - Monitor Preset AAV16Room 1 Humidity High Limit - Monitor Preset AAV17Room 1 Humidity Low Limit - Monitor Preset BAV18Room 1 Humidity High Limit - Monitor Preset BAV19Room 1 Humidity DeadbandAV20Room 1 Humidity To Off Normal DelayAV21Room 1 Humidity Return To Normal DelayAV22Room 1 ACH Low Limit - Monitor Preset AAV23Room 1 ACH High Limit - Monitor Preset AAV24Room 1 ACH Low Limit - Monitor Preset BAV25Room 1 ACH High Limit - Monitor Preset BAV26Room 1 ACH DeadbandAV27Room 1 ACH To Off Normal DelayAV28Room 1 ACH Return To Normal DelayAV29Room 1 User Defined 1 Low Limit - Monitor Preset AAV30Room 1 User Defined 1 High Limit - Monitor Preset AAV31Room 1 User Defined 1 Low Limit - Monitor Preset BAV32Room 1 User Defined 1 High Limit - Monitor Preset BAV33Room 1 User Defined 1 DeadbandAV34Room 1 User Defined 1 To Off Normal DelayAV35Room 1 User Defined 1 Return To Normal DelayAV36Room 1 User Defined 2 Low Limit - Monitor Preset AAV37Room 1 User Defined 2 High Limit - Monitor Preset AAV38Room 1 User Defined 2 Low Limit - Monitor Preset BAV39Room 1 User Defined 2 High Limit - Monitor Preset BAV40Room 1 User Defined 2 DeadbandAV41Room 1 User Defined 2 To Off Normal DelayAV42Room 1 User Defined 2 Return To Normal DelayAV43Room 2 Pressure Low Limit - Monitor Preset AAV44Room 2 Pressure High Limit - Monitor Preset AAV45Room 2 Pressure Low Limit - Monitor Preset BAV46Room 2 Pressure High Limit - Monitor Preset BAV47Room 2 Pressure DeadbandAV48Room 2 Pressure To Off Normal DelayAV49Room 2 Pressure Return To Normal DelayAV50Room 2 Temperature Low Limit - Monitor Preset AAV51Room 2 Temperature High Limit - Monitor Preset AAV52Room 2 Temperature Low Limit - Monitor Preset BAV53Room 2 Temperature High Limit - Monitor Preset BAV54Room 2 Temperature DeadbandAV55Room 2 Temperature To Off Normal DelayAV56Room 2 Temperature Return To Normal DelayAV57Room 2 Humidity Low Limit - Monitor Preset AAV58Room 2 Humidity High Limit - Monitor Preset AAV59Room 2 Humidity Low Limit - Monitor Preset BAV60Room 2 Humidity High Limit - Monitor Preset BAV61Room 2 Humidity DeadbandAV62Room 2 Humidity To Off Normal DelayAV63Room 2 Humidity Return To Normal DelayAV64Room 2 ACH Low Limit - Monitor Preset AAV65Room 2 ACH High Limit - Monitor Preset AAV66Room 2 ACH Low Limit - Monitor Preset BAV67Room 2 ACH High Limit - Monitor Preset BAV68Room 2 ACH DeadbandAV69Room 2 ACH To Off Normal DelayAV70Room 2 ACH Return To Normal DelayAV71Room 2 User Defined 1 Low Limit - Monitor Preset AAV72Room 2 User Defined 1 High Limit - Monitor Preset AAV73Room 2 User Defined 1 Low Limit - Monitor Preset BAV74Room 2 User Defined 1 High Limit - Monitor Preset BAV75Room 2 User Defined 1 DeadbandAV76Room 2 User Defined 1 To Off Normal DelayAV77Room 2 User Defined 1 Return To Normal DelayAV78Room 2 User Defined 2 Low Limit - Monitor Preset AAV79Room 2 User Defined 2 High Limit - Monitor Preset AAV80Room 2 User Defined 2 Low Limit - Monitor Preset BAV81Room 2 User Defined 2 High Limit - Monitor Preset BAV82Room 2 User Defined 2 DeadbandAV83Room 2 User Defined 2 To Off Normal DelayAV84Room 2 User Defined 2 Return To Normal DelayAV85Room 3 Pressure Low Limit - Monitor Preset AAV86Room 3 Pressure High Limit - Monitor Preset AAV87Room 3 Pressure Low Limit - Monitor Preset BAV88Room 3 Pressure High Limit - Monitor Preset BAV89Room 3 Pressure DeadbandAV90Room 3 Pressure To Off Normal DelayAV91Room 3 Pressure Return To Normal DelayAV92Room 3 Temperature Low Limit - Monitor Preset AAV93Room 3 Temperature High Limit - Monitor Preset AAV94Room 3 Temperature Low Limit - Monitor Preset BAV95Room 3 Temperature High Limit - Monitor Preset BAV96Room 3 Temperature DeadbandAV97Room 3 Temperature To Off Normal DelayAV98Room 3 Temperature Return To Normal DelayAV99Room 3 Humidity Low Limit - Monitor Preset AAV100Room 3 Humidity High Limit - Monitor Preset AAV101Room 3 Humidity Low Limit - Monitor Preset BAV102Room 3 Humidity High Limit - Monitor Preset BAV103Room 3 Humidity DeadbandAV104Room 3 Humidity To Off Normal DelayAV105Room 3 Humidity Return To Normal DelayAV106Room 3 ACH Low Limit - Monitor Preset AAV107Room 3 ACH High Limit - Monitor Preset AAV108Room 3 ACH Low Limit - Monitor Preset BAV109Room 3 ACH High Limit - Monitor Preset BAV110Room 3 ACH DeadbandAV111Room 3 ACH To Off Normal DelayAV112Room 3 ACH Return To Normal DelayAV113Room 3 User Defined 1 Low Limit - Monitor Preset AAV114Room 3 User Defined 1 High Limit - Monitor Preset AAV115Room 3 User Defined 1 Low Limit - Monitor Preset BAV116Room 3 User Defined 1 High Limit - Monitor Preset BAV117Room 3 User Defined 1 DeadbandAV118Room 3 User Defined 1 To Off Normal DelayAV119Room 3 User Defined 1 Return To Normal DelayAV120Room 3 User Defined 2 Low Limit - Monitor Preset AAV121Room 3 User Defined 2 High Limit - Monitor Preset AAV122Room 3 User Defined 2 Low Limit - Monitor Preset BAV123Room 3 User Defined 2 High Limit - Monitor Preset BAV124Room 3 User Defined 2 DeadbandAV125Room 3 User Defined 2 To Off Normal DelayAV126Room 3 User Defined 2 Return To Normal DelayAV127Room 1 LengthAV128Room 1 WidthAV129Room 1 HeightAV130Room 2 LengthAV131Room 2 WidthAV132Room 2 HeightAV133Room 3 LengthAV134Room 3 WidthAV135Room 3 HeightAV209Room 1 Duct Cross Sectional AreaAV210Room 2 Duct Cross Sectional AreaAV211Room 3 Duct Cross Sectional AreaAV136Mute Time OutAV138Brightness LevelAV139Home Screen TimeoutAV140Room Carousel IntervalAV212Turn Off Display After TimeoutBV1Latch Alarm EnableBV2Audible Alarm StatusBV3Mute Alarm EnableBV4Default To Full ScreenBV5Room CarouselBV100Display Turn Off EnableAV141Room 1 Pressure BACnet Device InstanceAV142Room 1 Pressure BACnet Object InstanceAV143Room 1 Temperature BACnet Device InstanceAV144Room 1 Temperature BACnet Object InstanceAV145Room 1 Humidity BACnet Device InstanceAV146Room 1 Humidity BACnet Object InstanceAV147Room 1 ACH BACnet Device InstanceAV148Room 1 ACH BACnet Object InstanceAV149Room 1 User Defined 1 BACnet Device InstanceAV150Room 1 User Defined 1 BACnet Object InstanceAV151Room 1 User Defined 2 BACnet Device InstanceAV152Room 1 User Defined 2 BACnet Object InstanceAV153Room 2 Pressure BACnet Device InstanceAV154Room 2 Pressure BACnet Object InstanceAV155Room 2 Temperature BACnet Device InstanceAV156Room 2 Temperature BACnet Object InstanceAV157Room 2 Humidity BACnet Device InstanceAV158Room 2 Humidity BACnet Object InstanceAV159Room 2 ACH BACnet Device InstanceAV160Room 2 ACH BACnet Object InstanceAV161Room 2 User Defined 1 BACnet Device InstanceAV162Room 2 User Defined 1 BACnet Object InstanceAV163Room 2 User Defined 2 BACnet Device InstanceAV164Room 2 User Defined 2 BACnet Object InstanceAV165Room 3 Pressure BACnet Device InstanceAV166Room 3 Pressure BACnet Object InstanceAV167Room 3 Temperature BACnet Device InstanceAV168Room 3 Temperature BACnet Object InstanceAV169Room 3 Humidity BACnet Device InstanceAV170Room 3 Humidity BACnet Object InstanceAV171Room 3 ACH BACnet Device InstanceAV172Room 3 ACH BACnet Object InstanceAV173Room 3 User Defined 1 BACnet Device InstanceAV174Room 3 User Defined 1 BACnet Object InstanceAV175Room 3 User Defined 2 BACnet Device InstanceAV176Room 3 User Defined 2 BACnet Object InstanceAV177Setpoint Control 1 - Preset A SetpointAV178Setpoint Control 1 - Preset A Max SetpointAV179Setpoint Control 1 - Preset A Min SetpointAV180Setpoint Control 1 - Preset B SetpointAV181Setpoint Control 1 - Preset B Max SetpointAV182Setpoint Control 1 - Preset B Min SetpointAV183External Setpoint 1 BACnet Device InstanceAV184External Setpoint 1 BACnet Object InstanceAV185Setpoint Control 2 - Preset A SetpointAV186Setpoint Control 2 - Preset A Max SetpointAV187Setpoint Control 2 - Preset A Min SetpointAV188Setpoint Control 2 - Preset B SetpointAV189Setpoint Control 2 - Preset B Max SetpointAV190Setpoint Control 2 - Preset B Min SetpointAV191External Setpoint 2 BACnet Device InstanceAV192External Setpoint 2 BACnet Object InstanceAV193Setpoint Control 3 - Preset A SetpointAV194Setpoint Control 3 - Preset A Max SetpointAV195Setpoint Control 3 - Preset A Min SetpointAV196Setpoint Control 3 - Preset B SetpointAV197Setpoint Control 3 - Preset B Max SetpointAV198Setpoint Control 3 - Preset B Min SetpointAV199External Setpoint 3 BACnet Device InstanceAV200External Setpoint 3 BACnet Object InstanceAV201Setpoint Control 4 - Preset A SetpointAV202Setpoint Control 4 - Preset A Max SetpointAV203Setpoint Control 4 - Preset A Min SetpointAV204Setpoint Control 4 - Preset B SetpointAV205Setpoint Control 4 - Preset B Max SetpointAV206Setpoint Control 4 - Preset B Min SetpointAV207External Setpoint 4 BACnet Device InstanceAV208External Setpoint 4 BACnet Object InstanceBI2On-Board Digital Input 2BI3On-Board Digital Input 3BI4On-Board Digital Input 4BI13Room 1 Door InputBI14Room 2 Door InputBI15Room 3 Door InputBO1On-Board RelayBV8Room 1 Pressure Parameter EnableBV9Room 1 Temperature Parameter EnableBV10Room 1 Humidity Parameter EnableBV11Room 1 ACH Parameter EnableBV12Room 1 User Defined 1 Parameter EnableBV13Room 1 User Defined 2 Parameter EnableBV14Room 2 Pressure Parameter EnableBV15Room 2 Temperature Parameter EnableBV16Room 2 Humidity Parameter EnableBV17Room 2 ACH Parameter EnableBV18Room 2 User Defined 1 Parameter EnableBV19Room 2 User Defined 2 Parameter EnableBV20Room 3 Pressure Parameter EnableBV21Room 3 Temperature Parameter EnableBV22Room 3 Humidity Parameter EnableBV23Room 3 ACH Parameter EnableBV24Room 3 User Defined 1 Parameter EnableBV25Room 3 User Defined 2 Parameter EnableBV26Room 1 Pressure Low Limit EnableBV27Room 1 Pressure High Limit EnableBV28Room 1 Temperature Low Limit EnableBV29Room 1 Temperature High Limit EnableBV30Room 1 Humidity Low Limit EnableBV31Room 1 Humidity High Limit EnableBV32Room 1 ACH Low Limit EnableBV33Room 1 ACH High Limit EnableBV34Room 1 User Defined 1 Low Limit EnableBV35Room 1 User Defined 1 High Limit EnableBV36Room 1 User Defined 2 Low Limit EnableBV37Room 1 User Defined 2 High Limit EnableBV38Room 2 Pressure Low Limit EnableBV39Room 2 Pressure High Limit EnableBV40Room 2 Temperature Low Limit EnableBV41Room 2 Temperature High Limit EnableBV42Room 2 Humidity Low Limit EnableBV43Room 2 Humidity High Limit EnableBV44Room 2 ACH Low Limit EnableBV45Room 2 ACH High Limit EnableBV46Room 2 User Defined 1 Low Limit EnableBV47Room 2 User Defined 1 High Limit EnableBV48Room 2 User Defined 2 Low Limit EnableBV49Room 2 User Defined 2 High Limit EnableBV50Room 3 Pressure Low Limit EnableBV51Room 3 Pressure High Limit EnableBV52Room 3 Temperature Low Limit EnableBV53Room 3 Temperature High Limit EnableBV54Room 3 Humidity Low Limit EnableBV55Room 3 Humidity High Limit EnableBV56Room 3 ACH Low Limit EnableBV57Room 3 ACH High Limit EnableBV58Room 3 User Defined 1 Low Limit EnableBV59Room 3 User Defined 1 High Limit EnableBV60Room 3 User Defined 2 Low Limit EnableBV61Room 3 User Defined 2 High Limit EnableBV62Room 1 Door EnableBV63Room 2 Door EnableBV64Room 3 Door EnableBV65Room 1 EnableBV66Room 2 EnableBV67Room 3 EnableBV68Room Profile 1 Alarm EnableBV69Room Profile 2 Alarm EnableBV70Room Profile 3 Alarm EnableBV71Room Profile 4 Alarm EnableBV72Room 1 StandbyBV73Room 2 StandbyBV74Room 3 StandbyBV75Control Loop 1 Setpoint TypeBV76Control Loop 2 Setpoint TypeBV77Control Loop 3 Setpoint TypeBV78Control Loop 4 Setpoint TypeBV79Time Display FormatBV7Execute BACnet Time Sync?BV80Display date on home screenBV81Display time on home screenBV82Room 1 Pressure Display UnitBV83Room 1 Temperature Display UnitBV84Room 1 Humidity Display UnitBV85Room 1 ACH Display UnitBV86Room 1 User Defined 1 Display UnitBV87Room 1 User Defined 2 Display UnitBV88Room 2 Pressure Display UnitBV89Room 2 Temperature Display UnitBV90Room 2 Humidity Display UnitBV91Room 2 ACH Display UnitBV92Room 2 User Defined 1 Display UnitBV93Room 2 User Defined 2 Display UnitBV94Room 3 Pressure Display UnitBV95Room 3 Temperature Display UnitBV96Room 3 Humidity Display UnitBV97Room 3 ACH Display UnitBV98Room 3 User Defined 1 Display UnitBV99Room 3 User Defined 2 Display UnitMI1Room 1 Pressure Alarm StateMI2Room 1 Temperature Alarm StateMI3Room 1 Humidity Alarm StateMI4Room 1 ACH Alarm StateMI5Room 1 User Defined 1 Alarm StateMI6Room 1 user Defined 2 Alarm StateMI7Room 2 Pressure Alarm StateMI8Room 2 Temperature Alarm StateMI9Room 2 Humidity Alarm StateMI10Room 2 ACH Alarm StateMI11Room 2 User Defined 1 Alarm StateMI12Room 2 user Defined 2 Alarm StateMI13Room 3 Pressure Alarm StateMI14Room 3 Temperature Alarm StateMI15Room 3 Humidity Alarm StateMI16Room 3 ACH Alarm StateMI17Room 3 User Defined 1 Alarm StateMI18Room 3 user Defined 2 Alarm StateMI19Room 1 Alarm StateMI20Room 2 Alarm StateMI21Room 3 Alarm StateMI22System Alarm StateMV1Room 1 Pressure SourceMV2Room 1 Temperature SourceMV3Room 1 Humidity SourceMV4Room 1 ACH SourceMV5Room 1 User Defined 1 SourceMV6Room 1 User Defined 2 SourceMV7Room 2 Pressure SourceMV8Room 2 Temperature SourceMV9Room 2 Humidity SourceMV10Room 2 ACH SourceMV11Room 2 User Defined 1 SourceMV12Room 2 User Defined 2 SourceMV13Room 3 Pressure SourceMV14Room 3 Temperature SourceMV15Room 3 Humidity SourceMV16Room 3 ACH SourceMV17Room 3 User Defined 1 SourceMV18Room 3 User Defined 2 SourceMV83Room 1 Door SourceMV84Room 2 Door SourceMV85Room 3 Door SourceMV19Room 1 Room ProfileMV20Room 2 Room ProfileMV21Room 3 Room ProfileMV22On-Board Analog Output TypeMV27On-Board Analog Input 1 TypeMV28On-Board Analog Input 2 TypeMV29On-Board Analog Input 3 TypeMV30On-Board Analog Input 4 TypeMV39Room Profile 1 IconMV40Room Profile 2 IconMV41Room Profile 3 IconMV42Room Profile 4 IconMV43Room Profile 1 ColorMV44Room Profile 2 ColorMV45Room Profile 3 ColorMV46Room Profile 4 ColorMV47Room Profile 1 Control PresetMV48Room Profile 2 Control PresetMV49Room Profile 3 Control PresetMV50Room Profile 3 Control PresetMV51Room Profile 1 Monitor PresetMV52Room Profile 2 Monitor PresetMV53Room Profile 3 Monitor PresetMV54Room Profile 4 Monitor PresetMV55Room 1 Pressure Source BACnet Object TypeMV56Room 1 Temperature Source BACnet Object TypeMV57Room 1 Humidity Source BACnet Object TypeMV58Room 1 ACH Source BACnet Object TypeMV59Room 1 User Defined 1 Source BACnet Object TypeMV60Room 1 User Defined 2 Source BACnet Object TypeMV61Room 2 Pressure Source BACnet Object TypeMV62Room 2 Temperature Source BACnet Object TypeMV63Room 2 Humidity Source BACnet Object TypeMV64Room 2 ACH Source BACnet Object TypeMV65Room 2 User Defined 1 Source BACnet Object TypeMV66Room 2 User Defined 2 Source BACnet Object TypeMV67Room 3 Pressure Source BACnet Object TypeMV68Room 3 Temperature Source BACnet Object TypeMV69Room 3 Humidity Source BACnet Object TypeMV70Room 3 ACH Source BACnet Object TypeMV71Room 3 User Defined 1 Source BACnet Object TypeMV72Room 3 User Defined 2 Source BACnet Object TypeMV73On-Board Analog Output SourceMV78On-Board Relay SourceMV86Room 1 Pressure ModeMV87Room 2 Pressure ModeMV88Room 3 Pressure ModeMV89Language SelectionMV90BACnet Setpoint 1 Override PriorityMV91BACnet Setpoint 2 Override PriorityMV92BACnet Setpoint 3 Override PriorityMV93BACnet Setpoint 4 Override PriorityMV94Room 1 Pressure Display FormatMV95Room 1 Temperature Display FormatMV96Room 1 Humidity Display FormatMV97Room 1 ACH Display FormatMV98Room 1 User Defined 1 Display FormatMV99Room 1 User Defined 2 Display FormatMV100Room 2 Pressure Display FormatMV101Room 2 Temperature Display FormatMV102Room 2 Humidity Display FormatMV103Room 2 ACH Display FormatMV104Room 2 User Defined 1 Display FormatMV105Room 2 User Defined 2 Display FormatMV106Room 3 Pressure Display FormatMV107Room 3 Temperature Display FormatMV108Room 3 Humidity Display FormatMV109Room 3 ACH Display FormatMV110Room 3 User Defined 1 Display FormatMV111Room 3 User Defined 2 Display FormatMV112Room 1 BACnet ACH Source typeMV113Room 2 BACnet ACH Source typeMV114Room 3 BACnet ACH Source typeMV115Room 1 Pressure Alarm Warning ModeMV116Room 1 Temperature Alarm Warning ModeMV117Room 1 Humidity Alarm Warning ModeMV118Room 1 ACH Alarm Warning ModeMV119Room 1 User Defined 1 Alarm Warning ModeMV120Room 1 User Defined 2 Alarm Warning ModeMV121Room 2 Pressure Alarm Warning ModeMV122Room 2 Temperature Alarm Warning ModeMV123Room 2 Humidity Alarm Warning ModeMV124Room 2 ACH Alarm Warning ModeMV125Room 2 User Defined 1 Alarm Warning ModeMV126Room 2 User Defined 2 Alarm Warning ModeMV127Room 3 Pressure Alarm Warning ModeMV128Room 3 Temperature Alarm Warning ModeMV129Room 3 Humidity Alarm Warning ModeMV130Room 3 ACH Alarm Warning ModeMV131Room 3 User Defined 1 Alarm Warning ModeMV132Room 3 User Defined 2 Alarm Warning ModeMV133Room 1 Door Alarm Action TypeMV134Room 2 Door Alarm Action TypeMV135Room 3 Door Alarm Action TypeMV136Air Flow/Air Velocity Unit for On-Board Analog Input 1MV137Air Flow/Air Velocity Unit for On-Board Universal Input 1MV138Air Flow/Air Velocity Unit for On-Board Universal Input 2MV139Air Flow/Air Velocity Unit for On-Board Universal Input 3MV148Air Flow/Air Velocity Unit for Room 1 Volumetric/Velocity BACnet PointMV149Air Flow/Air Velocity Unit for Room 2 Volumetric/Velocity BACnet PointMV150Air Flow/Air Velocity Unit for Room 3 Volumetric/Velocity BACnet PointLO1Loop 1LO2Loop 2LO3Loop 3LO4Loop 4CSV1Room 1 LabelCSV2Room 2 LabelCSV3Room 3 LabelCSV4Room Profile 1 LabelCSV5Room Profile 2 LabelCSV6Room Profile 3 LabelCSV7Room Profile 4 LabelCSV8Room Profile 1 Banner LabelCSV9Room Profile 2 Banner LabelCSV10Room Profile 3 Banner LabelCSV11Room Profile 4 Banner LabelCSV12Technical Support IDCSV13Audit Trail String 1CSV14Audit Trail String 2CSV15Audit Trail String 3CSV16Audit Trail String 4CSV17Audit Trail String 5CSV18Operator PasswordCSV19Room 1 User Defined 1 Badge NameCSV20Room 1 User Defined 2 Badge NameCSV21Room 2 User Defined 1 Badge NameCSV22Room 2 User Defined 2 Badge NameCSV23Room 3 User Defined 1 Badge NameCSV24Room 3 User Defined 2 Badge Name
Integration notes
- Access is taken from the list's Writable column. AI, BI and MI objects are marked writable only when out of service; they are shown here as read-only.
- The list gives no engineering units; room values follow the units of their configured source (BV 82-99 choose local or BACnet-source units).
- Analog input and alarm-limit values are bounded by each object's min-pres-value and max-pres-value.
- Room parameters, alarm limits and source settings repeat for Room 1, 2 and 3; profile settings repeat for profiles 1-4.
- MV 49 and MV 50 are both printed as "Room Profile 3 Control Preset"; names are kept as printed.
- The Loop rows print "Loop 1" to "Loop 4" in the type/instance column (without the hyphen the other rows use); they are read here as Loop instances 1-4.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Setra FLEX Room Pressure Monitor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Setra FLEX Room Pressure Monitor
How many BACnet points does the Setra FLEX Room Pressure Monitor have?
This list has 513 BACnet objects: 22 analog inputs, 1 analog output, 211 analog values, 6 binary inputs, 1 binary output, 99 binary values, 1 device, 4 loops, 22 multi-state inputs, 122 multi-state values, 24 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Setra FLEX Room Pressure Monitor BACnet points are writable?
455 of the 513 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Setra FLEX Room Pressure Monitor BACnet documentation?
The source is SetraFLEX Master BACnet Object List (SS-FLEX-BAC-OBJ), revision print D, published free by Setra at https://www.setra.com/hubfs/SS-FLEX-BAC-OBJ_D.pdf.
What are the minimum BACnet points to integrate the Setra FLEX Room Pressure Monitor?
Start with BV 72 Room 1 Standby (Room 1 standby: 1 = Standby, 0 = Active); MV 19 Room 1 Room Profile (Active room profile 1-4 (e.g. occupied/unoccupied)); AV 177 Setpoint Control 1 - Preset A Setpoint (Control 1 setpoint, preset A (FLEX-RC)); AI 13 Room 1 Pressure (Room 1 differential pressure); AI 14 Room 1 Temperature (Room 1 temperature, from its configured source); AI 15 Room 1 Humidity (Room 1 humidity, from its configured source); BI 13 Room 1 Door Input (Room 1 door switch); MI 19 Room 1 Alarm State (Room 1: 1 Normal, 2 Warning, 3 Alarm, 4 Standby); MI 22 System Alarm State (Whole-unit alarm state, same states).
How do I enable BMS control of the Setra FLEX Room Pressure Monitor?
Room 1-3 Standby (BV 72-74) put a room in standby, and Room 1-3 Room Profile (MV 19-21) pick which of the four profiles (alarm limits and control presets) is active.
Can the BMS supply sensor values to the Setra FLEX Room Pressure Monitor?
Each room parameter has a source selector (MV 1-18, 6 = BACnet). With BACnet selected, the FLEX reads the value from another device set by the matching device instance, object instance and object type objects (AV 141-176, MV 55-72). The four setpoint controls point at external BACnet setpoint objects set by AV 183/184, 191/192, 199/200 and 207/208 (device and object instance).
How do I check these points on the real Setra FLEX Room Pressure Monitor?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Setra BACnet points lists
- Multi-load power meter
Setra Power Meter (SPM) - load device
Setra Power Meter (SPM) multi-load electrical meters; this entry covers each virtual load device (one per configured load).
Also known as: SPM, Setra SPM, Setra Power Meter, SPM load - Multi-load power meter
Setra Power Meter (SPM) - root device
Setra Power Meter (SPM) multi-load electrical meters; this entry covers the root device that carries the voltage inputs.
Also known as: SPM, Setra SPM, Setra Power Meter, Setra multi-load power meter - Room pressure monitor (room condition monitor)
Setra SRCM Room Condition Monitor (two-room)
Setra SRCM room condition monitors watching pressure, temperature and humidity in a primary and a secondary room.
Also known as: SRCM, Setra SRCM, Room Condition Monitor, Setra Room Condition Monitor - Humidity / temperature sensor
Setra SRH300D / SRH200D humidity and temperature transmitter (BACnet MS/TP)
Setra SRH300 and SRH200 humidity/temperature transmitters with the RS-485 BACnet MS/TP output (SRH300D / SRH200D).
Also known as: SRH300D, SRH200D, SRH300, SRH200, Setra SRH BACnet
Source: SetraFLEX Master BACnet Object List · SS-FLEX-BAC-OBJ · rev. print D. Object names, instances and units are reproduced as published; descriptions are our own.