Variable frequency drive · BACnet points list
Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet points list
Updated 28 October 2026
The Altivar Process ATV600 drives talk BACnet MS/TP as a B-ASC with a fixed object list. It covers relay and logic input status, run/stop, direction and fault reset commands, a speed reference, motor measurements, the last three faults, two analog outputs, eight read and eight write comm-scanner values, and a mailbox (MBOX) for reading or writing any drive parameter.
This page lists 74 BACnet objects for the Schneider Electric Altivar Process ATV600 (BACnet MS/TP) — 29 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Schneider Electric’s own free documentation, linked below.
- Manufacturer
- Schneider Electric
- Model
- Altivar Process ATV600 (BACnet MS/TP)
- Equipment
- Variable frequency drive
- Equipment type
- VFDs & pumps
- BACnet objects
- 74 (29 writable)
- Transport
- BACnet MS/TP
- Firmware
- v1.7 (application software v1.1)
- Also known as
- ATV600, ATV630, ATV650, ATV660, ATV690, Altivar Process, Altivar 600, ATV6xx
Reference only, provided as-is: verify against Schneider Electric’s current documentation and the live device before use. Not official Schneider Electric information. Terms of use.
BMS integration notes: Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
Write BV 10 RUN/STOP CMD and AV 16 INPUT REF 1 (%), and read BV 0, BV 2, BV 4 and AV 1/AV 4/AV 6 for status, fault, hand/auto, frequency, current and power. BV 14 resets a fault on a rising edge; AV 18-20 hold the current and two previous faults. Any other drive parameter can be read or written through the MBOX objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10 | RUN/STOP CMD | Start/stop from the BMS | Command |
| AV 16 | INPUT REF 1 | Speed reference in % | Command |
| BV 14 | FAULT RESET | Reset a tripped drive (rising edge) | Write |
| BV 0 | RUN/STOP ACT | Running status | Read |
| BV 4 | HAND/AUTO ACT | Shows if the drive is in Hand | Read |
| AV 1 | OUTPUT FREQ | Output frequency in Hz | Read |
| AV 4 | CURRENT | Motor amps | Read |
| AV 6 | POWER | Motor power in % | Read |
| BV 2 | FAULT ACT | Any active drive fault | Read |
| AV 18 | LAST FAULT | Which fault is active | Read |
Sensors & values from the BMS
The BMS can write the process PID setpoint to AV 27 EXT PID STPT. The document lists no BMS-written PID feedback object; COM SCAN OUT1-8 can carry other values into mapped drive registers.
Network setup
- BACnet MS/TP master; baud rate Auto, 9600, 19200, 38400 or 76800.
- Segmented requests and responses are supported (window size 3); COV subscriptions are supported.
- Objects are static; none can be created or deleted.
Watch out for
- The PICS does not say which drive settings (command and reference channel) must point at the fieldbus for BV 10 and AV 16 to act; check the drive programming manual.
- To read a parameter: write its logic address to AV 25 MBOX PARAM, set BV 15 MBOX READ, then read AV 26 MBOX DATA.
- To write a parameter: write the address to AV 25, the value to AV 26, then set BV 16 MBOX WRITE.
- BV 15 and BV 16 drop back to inactive after the command is sent and always read 0.
- AV 6 POWER and the AV 7/AV 15 thermal states are in %, not kW or degrees.
Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | RO1 ACT | Status of relay R1 | Read | ON/OFF | |
| BI | 2 | RO2 ACT | Status of relay R2 | Read | ON/OFF | |
| BI | 3 | RO3 ACT | Status of relay R3 | Read | ON/OFF | |
| BI | 6 | DI 1 ACT | Status of logic input LI1 | Read | ON/OFF | |
| BI | 7 | DI 2 ACT | Status of logic input LI2 | Read | ON/OFF | |
| BI | 8 | DI 3 ACT | Status of logic input LI3 | Read | ON/OFF | |
| BI | 9 | DI 4 ACT | Status of logic input 4 (doc prints LI3) | Read | ON/OFF | |
| BI | 10 | DI 5 ACT | Status of logic input LI5 | Read | ON/OFF | |
| BI | 11 | DI 6 ACT | Status of logic input LI6 | Read | ON/OFF | |
| BO | 0 | RO1 CMD | Drives relay R1 when it has no other function assigned | Command | ON/OFF | |
| BO | 1 | RO2 CMD | Drives relay R2 when it has no other function assigned | Command | ON/OFF | |
| BO | 2 | RO3 CMD | Drives relay R3 when it has no other function assigned | Command | ON/OFF | |
| BVmin | 0 | RUN/STOP ACT | Drive running status | Read | RUNS/READY | |
| BV | 1 | FWD/REV ACT | Motor rotation direction | Read | REV/FWD | |
| BVmin | 2 | FAULT ACT | Drive fault status | Read | FAULTED/NONE | |
| BVmin | 4 | HAND/AUTO ACT | Shows if the drive is under local control | Read | HAND/AUTO | |
| BV | 7 | DRIVE READY | Drive ready and waiting for a start command | Read | READY/NOT READY | |
| BV | 8 | AT SETPOINT | Drive has reached the target speed | Read | REACHED/NO | |
| BVmin | 10 | RUN/STOP CMD | Start/stop command | Command | START/STOP | |
| BV | 11 | FWD/REV CMD | Motor direction command | Command | REV/FWD | |
| BVmin | 14 | FAULT RESET | Fault reset on rising edge | Write | RESET/NO | |
| BV | 15 | MBOX READ | Triggers a read of the parameter in MBOX PARAM | Write | READ/RESET | |
| BV | 16 | MBOX WRITE | Triggers a write of MBOX DATA to MBOX PARAM | Write | WRITE/RESET | |
| BV | 18 | C311CMD | Command word 3, bit 11 | Command | ON/OFF | |
| BV | 19 | C312CMD | Command word 3, bit 12 | Command | ON/OFF | |
| BV | 20 | C313CMD | Command word 3, bit 13 | Command | ON/OFF | |
| BV | 21 | C314CMD | Command word 3, bit 14 | Command | ON/OFF | |
| BV | 22 | C315CMD | Command word 3, bit 15 | Command | ON/OFF | |
| BV | 23 | STORE CONFIG | Store configuration (doc description only says HELP) | Read | INACTIVE/STORE | |
| AI | 0 | ANALOG INPUT 1 | Analog input 1 value | % | Read | |
| AI | 1 | ANALOG INPUT 2 | Analog input 2 value | % | Read | |
| AI | 2 | ANALOG INPUT 3 | Analog input 3 value | % | Read | |
| AI | 16 | ANALOG OUTPUT 1 | Analog output 1 status | % | Read | |
| AI | 17 | ANALOG OUTPUT 2 | Analog output 2 status | % | Read | |
| AO | 0 | AO1 COMMAND | Analog output 1 value from the BMS | % | Command | |
| AO | 1 | AO2 COMMAND | Analog output 2 value from the BMS | % | Command | |
| AV | 0 | OUTPUT SPEED | Motor speed | rpm | Read | |
| AVmin | 1 | OUTPUT FREQ | Output frequency | Hz | Read | |
| AV | 2 | DC BUS VOLT | DC bus voltage | V | Read | |
| AV | 3 | OUTPUT VOLT | Motor voltage | V | Read | |
| AVmin | 4 | CURRENT | Motor current | A | Read | |
| AV | 5 | TORQUE | Motor torque | % | Read | |
| AVmin | 6 | POWER | Motor power | % | Read | |
| AV | 7 | DRIVE TEMP | Drive thermal state | % | Read | |
| AV | 8 | KWH(R | Resettable energy counter | kWh | Read | |
| AV | 10 | PRC PID FBCK | Process PID feedback | Read | ||
| AV | 11 | PRC PID DEV | Process PID deviation (doc repeats the feedback text) | Read | ||
| AV | 14 | RUN TIME | Operating time | h | Read | |
| AV | 15 | MOTOR TEMP | Motor thermal state | % | Read | |
| AVmin | 16 | INPUT REF 1 | Speed/frequency reference from the BMS | % | Command | |
| AVmin | 18 | LAST FAULT | Current fault | Read | ||
| AV | 19 | PREV FLT 1 | Previous fault (n-1) | Read | ||
| AV | 20 | PREV FLT 2 | Previous fault (n-2) | Read | ||
| AV | 23 | ACCEL1 TIME | Acceleration ramp time | s | Write | |
| AV | 24 | DECEL1 TIME | Deceleration ramp time | s | Write | |
| AV | 25 | MBOX PARAM | Logic address of the parameter to read or write | Write | ||
| AV | 26 | MBOX DATA | Parameter value read, or value to write | Write | ||
| AV | 27 | EXT PID STPT | Process PID setpoint from the BMS | Command | ||
| AV | 28 | COM SCAN OUT1 | General-purpose value written to the drive comm scanner | Command | ||
| AV | 29 | COM SCAN OUT2 | General-purpose value written to the drive comm scanner | Command | ||
| AV | 30 | COM SCAN OUT3 | General-purpose value written to the drive comm scanner | Command | ||
| AV | 31 | COM SCAN OUT4 | General-purpose value written to the drive comm scanner | Command | ||
| AV | 32 | COM SCAN OUT5 | General-purpose value written to the drive comm scanner | Command | ||
| AV | 33 | COM SCAN OUT6 | General-purpose value written to the drive comm scanner | Command | ||
| AV | 34 | COM SCAN OUT7 | General-purpose value written to the drive comm scanner | Command | ||
| AV | 35 | COM SCAN OUT8 | General-purpose value written to the drive comm scanner | Command | ||
| AV | 36 | COM SCAN IN1 | General-purpose value read from the drive comm scanner | Read | ||
| AV | 37 | COM SCAN IN2 | General-purpose value read from the drive comm scanner | Read | ||
| AV | 38 | COM SCAN IN3 | General-purpose value read from the drive comm scanner | Read | ||
| AV | 39 | COM SCAN IN4 | General-purpose value read from the drive comm scanner | Read | ||
| AV | 40 | COM SCAN IN5 | General-purpose value read from the drive comm scanner | Read | ||
| AV | 41 | COM SCAN IN6 | General-purpose value read from the drive comm scanner | Read | ||
| AV | 42 | COM SCAN IN7 | General-purpose value read from the drive comm scanner | Read | ||
| AV | 43 | COM SCAN IN8 | General-purpose value read from the drive comm scanner | Read |
No points match these filters.
Object ID lookup: Schneider Electric Altivar Process ATV600 point IDs by name
BI1RO1 ACTBI2RO2 ACTBI3RO3 ACTBI6DI 1 ACTBI7DI 2 ACTBI8DI 3 ACTBI9DI 4 ACTBI10DI 5 ACTBI11DI 6 ACTBO0RO1 CMDBO1RO2 CMDBO2RO3 CMDBV0RUN/STOP ACTBV1FWD/REV ACTBV2FAULT ACTBV4HAND/AUTO ACTBV7DRIVE READYBV8AT SETPOINTBV10RUN/STOP CMDBV11FWD/REV CMDBV14FAULT RESETBV15MBOX READBV16MBOX WRITEBV18C311CMDBV19C312CMDBV20C313CMDBV21C314CMDBV22C315CMDBV23STORE CONFIGAI0ANALOG INPUT 1AI1ANALOG INPUT 2AI2ANALOG INPUT 3AI16ANALOG OUTPUT 1AI17ANALOG OUTPUT 2AO0AO1 COMMANDAO1AO2 COMMANDAV0OUTPUT SPEEDAV1OUTPUT FREQAV2DC BUS VOLTAV3OUTPUT VOLTAV4CURRENTAV5TORQUEAV6POWERAV7DRIVE TEMPAV8KWH(RAV10PRC PID FBCKAV11PRC PID DEVAV14RUN TIMEAV15MOTOR TEMPAV16INPUT REF 1AV18LAST FAULTAV19PREV FLT 1AV20PREV FLT 2AV23ACCEL1 TIMEAV24DECEL1 TIMEAV25MBOX PARAMAV26MBOX DATAAV27EXT PID STPTAV28COM SCAN OUT1AV29COM SCAN OUT2AV30COM SCAN OUT3AV31COM SCAN OUT4AV32COM SCAN OUT5AV33COM SCAN OUT6AV34COM SCAN OUT7AV35COM SCAN OUT8AV36COM SCAN IN1AV37COM SCAN IN2AV38COM SCAN IN3AV39COM SCAN IN4AV40COM SCAN IN5AV41COM SCAN IN6AV42COM SCAN IN7AV43COM SCAN IN8
Integration notes
- Access is as printed: R read-only, W writable, C commandable.
- Gaps in the instance numbering are not used; only the listed objects exist.
- AI 16 and AI 17 report the analog output values even though they are Analog Input objects.
- BO 0-2 only drive a relay when that relay has no other function assigned in the drive.
- COM SCAN OUT1-8 and IN1-8 carry whatever drive registers are mapped in the comm scanner.
- Names kept as printed, including 'KWH(R'. The doc gives both BI 8 and BI 9 the LI3 text and BV 23 only 'HELP'.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Altivar Process ATV600 (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Schneider Electric Altivar Process ATV600 (BACnet MS/TP)
How many BACnet points does the Schneider Electric Altivar Process ATV600 (BACnet MS/TP) have?
This list has 74 BACnet objects: 5 analog inputs, 2 analog outputs, 38 analog values, 9 binary inputs, 3 binary outputs, 17 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet points are writable?
29 of the 74 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Schneider Electric Altivar Process ATV600 (BACnet MS/TP) BACnet documentation?
The source is BACnet Protocol Implementation Conformance Statement, Altivar Process ATV630/ATV650/ATV660/ATV690, revision 2018-03-07, published free by Schneider Electric at https://www.bacnetinternational.net/catalog/manu/schneider%20electric/pics_atv6x.pdf.
What are the minimum BACnet points to integrate the Schneider Electric Altivar Process ATV600 (BACnet MS/TP)?
Start with BV 10 RUN/STOP CMD (Start/stop from the BMS); AV 16 INPUT REF 1 (Speed reference in %); BV 14 FAULT RESET (Reset a tripped drive (rising edge)); BV 0 RUN/STOP ACT (Running status); BV 4 HAND/AUTO ACT (Shows if the drive is in Hand); AV 1 OUTPUT FREQ (Output frequency in Hz); AV 4 CURRENT (Motor amps); AV 6 POWER (Motor power in %); BV 2 FAULT ACT (Any active drive fault); AV 18 LAST FAULT (Which fault is active).
Can the BMS supply sensor values to the Schneider Electric Altivar Process ATV600 (BACnet MS/TP)?
The BMS can write the process PID setpoint to AV 27 EXT PID STPT. The document lists no BMS-written PID feedback object; COM SCAN OUT1-8 can carry other values into mapped drive registers.
How do I check these points on the real Altivar Process ATV600 (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Schneider Electric BACnet points lists
- Power and energy meter (BACnet MS/TP)
Schneider Electric Acti 9 iEM3165 / iEM3265 / iEM3365 energy meter (BACnet MS/TP)
Schneider Electric iEM3165, iEM3265 and iEM3365 DIN-rail energy meters, the BACnet MS/TP models of the iEM3100/iEM3200/iEM3300 series.
Also known as: iEM3165, iEM3265, iEM3365, A9MEM3165, A9MEM3265, A9MEM3365, iEM3000 BACnet, Acti9 iEM3000 BACnet MS/TP, DOCA0005EN - Variable frequency drive (HVAC)
Schneider Electric Altivar 212 (embedded BACnet MS/TP)
Schneider Electric Altivar 212 HVAC fan and pump drives using the built-in open-style RS-485 terminals with F829 set to BACnet.
Also known as: ATV212, ATV 212, Altivar 212, ATV212H, ATV212W, S1A53845 - Variable frequency drive (BACnet MS/TP option card)
Schneider Electric Altivar 61 BACnet MS/TP card VW3A3319
Schneider Electric Altivar 61 HVAC drives fitted with the VW3A3319 BACnet MS/TP option card.
Also known as: ATV61 BACnet, VW3A3319, VW3 A3 319, Altivar 61 - Power and energy meter (BACnet IP)
Schneider Electric EM3570 series DIN Ethernet energy meter (BACnet IP)
Schneider Electric EM3570 series three-phase DIN-rail Ethernet energy meters (LVCT or Rogowski inputs, with or without power supply module), firmware 1.9.0.
Also known as: EM3570, METSEEM3570, METSEEM3570A, METSEEM3570X, METSEEM3570AX, EM70, EM3570 BACnet - Power and energy meter (BACnet MS/TP)
Schneider Electric iEM3465 / iEM3565 energy meter (BACnet MS/TP)
Schneider Electric iEM3465 (LVCT inputs) and iEM3565 (Rogowski coil inputs) DIN-rail energy meters, the BACnet MS/TP models of the iEM3400 / iEM3500 series.
Also known as: iEM3465, iEM3565, iEM3400 BACnet, iEM3500 BACnet, iEM3X65, 7EN02-0438 - Power and energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 energy meter (BACnet MS/TP)
Schneider Electric PowerLogic EM4200 series (EM42xx) power and energy meters with BACnet MS/TP.
Also known as: EM4200, EM42xx, PowerLogic EM4200, EM4200 BACnet, EM4200 BACnet object list, Schneider energy meter BACnet MS/TP - Multi-circuit branch power meter (high density)
Schneider Electric PowerLogic HDPM6000 high-density power meter (BACnet IP)
Schneider Electric (ex-Veris) PowerLogic HDPM6000 head units with busway, strip or retrofit measurement modules, on BACnet IP over Ethernet.
Also known as: HDPM6000, PowerLogic HDPM6000, HDPM6000B, HDPM6000S, HDPM6000S24, HDPM6000R, Veris HDPM6000, ZL0192 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5300 power meter (BACnet IP)
Schneider Electric PowerLogic PM5300 series power meters with the Ethernet port (PM5320, PM5340, PM5341) using BACnet IP.
Also known as: PM5300, PM5320, PM5340, PM5341, PowerLogic PM5320 BACnet, METSEPM5320, METSEPM5340 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM5500 / PM5600 / PM5700 power meter (BACnet IP)
Schneider Electric PowerLogic PM5500, PM5600 and PM5700 series power meters with Ethernet (PM5560-PM5761) using BACnet IP.
Also known as: PM5500, PM5560, PM5561, PM5562, PM5563, PM5570, PM5580, PM5650, PM5660, PM5661, PM5760, PM5761, PowerLogic PM5560 BACnet, METSEPM5560 - Power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM7000 series power and energy meter (BACnet IP)
Schneider Electric PowerLogic PM7000 series panel meters PM7351DUW, PM7252DUW, PM7151DUW and PM7142DUW with BACnet IP, firmware 1.0.1.
Also known as: PM7000, PM7351DUW, PM7252DUW, PM7151DUW, PM7142DUW, PM7351, PM7252, PM7151, PM7142, PowerLogic Intuitive PM7000 - Zone controller (room thermostat)
Schneider Electric SE7200 Series PIR Ready Zoning Controller
Schneider Electric PIR-ready SE7200 series 24 Vac zoning controllers (SE7200C5x45B, SE7200F5x45B).
Also known as: SE7200, SE7200C5x45B, SE7200F5x45B, SE7200C5045B, SE7200F5045B - Fan coil unit controller (room thermostat)
Schneider Electric SE7300 Series PIR Ready Fan Coil Controller
Schneider Electric PIR-ready SE7300 series 24 Vac fan coil controllers: SE7300, SE7305 (lodging), SE7350 and SE7355 (with humidity), C and F versions.
Also known as: SE7300, SE7305, SE7350, SE7355, SE7300C5x45B, SE7300F5x45B, SE7350C5x45B, SE7355F5x45B - Fan coil unit controller (room thermostat)
Schneider Electric SER7300 Series PIR Ready Line Voltage Fan Coil Controller
Schneider Electric PIR-ready SER7300 series line-voltage fan coil controllers: SER7300, SER7305, SER7350 and SER7355 (A versions).
Also known as: SER7300, SER7305, SER7350, SER7355, SER7300A5x45B, SER7350A5x45B - Pressure-dependent VAV zone controller
Schneider Electric SEZ7260 Zoning System Zone Controller
Schneider Electric SEZ7260 zone controllers (F model with floating damper and AO2, C model) used with SEZ7656 rooftop controllers in pressure-dependent zoning systems.
Also known as: SEZ7260, SEZ7260F5045B, SEZ7260C5045B, SEZ7260F5x45B, SEZ7260C5x45B - Rooftop unit controller for zoning systems
Schneider Electric SEZ7656 Zoning System Rooftop Unit Controller
Schneider Electric SEZ7656 rooftop controllers (R conventional, H heat pump, F modulating heat, E economizer) that run a rooftop unit for a group of SEZ7260 zone controllers.
Also known as: SEZ7656, SEZ7656R1045B, SEZ7656H1045B, SEZ7656F1045B, SEZ7656E1045B - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SE8350 Fan Coil and Zone Controller
Schneider Electric SpaceLogic SE8000-series SE8350 room controllers for low-voltage (24 Vac) 2-pipe and 4-pipe fan coil units and zone control.
Also known as: SE8350, SpaceLogic SE8350, SE8000 SE8350, Schneider SE8350 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SER8350 Line Voltage Fan Coil Controller
Schneider Electric SpaceLogic SE8000-series SER8350 room controllers for line-voltage fan coil units.
Also known as: SER8350, SpaceLogic SER8350, SE8000 SER8350, Schneider SER8350 - Room humidity and temperature sensor (wall)
Schneider Electric SpaceLogic SLP Series humidity and temperature sensor (BACnet MS/TP)
Schneider Electric SpaceLogic SLP Series wall humidity/temperature sensors (with or without touchscreen) set to BACnet MS/TP.
Also known as: SpaceLogic SLP, SLP humidity temperature, SLP Series HT, Z207903 - Fan coil unit controller (room thermostat)
Schneider Electric SpaceLogic SXWTRC3500 Touchscreen Room Controller (fan coil)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 3500 (fan coil unit) version.
Also known as: SXWTRC3500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC fan coil - Rooftop unit controller (room thermostat, rooftop or heat-pump units)
Schneider Electric SpaceLogic SXWTRC6500 Touchscreen Room Controller (rooftop / heat pump)
Schneider Electric SpaceLogic SXWTRCn500 touchscreen room controllers in the 6500 (rooftop unit / heat pump) version.
Also known as: SXWTRC6500, SXWTRCn500, SpaceLogic touchscreen room controller, TRC rooftop heat pump - Fan coil thermostat
Schneider Electric SpaceLogic TC900 Protocol Series fan coil thermostat (TC903 / TC907)
Schneider Electric SpaceLogic TC903 and TC907 Protocol Series fan coil thermostats (on/off or proportional valves, 3-speed or EC fan, 2-pipe or 4-pipe).
Also known as: TC900, TC903, TC907, TC903-EF4LDPSA, TC903-EF4PDPSA, TC903-3A4LXPXA, TC903-3A4LDPSA, TC903-3A4PDPSA, TC907-EF4LDPSAB, TC907-EF4PDPSAB, TC907-3A4LDPSAB, TC907-3A4PDPSAB, F-28335
Source: BACnet Protocol Implementation Conformance Statement, Altivar Process ATV630/ATV650/ATV660/ATV690 · rev. 2018-03-07. Object names, instances and units are reproduced as published; descriptions are our own.