- Home
- BACnet points lists
- Mitsubishi Electric
- BAC-HD150 BM Adapter
VRF BACnet IP gateway · BACnet points list
Mitsubishi Electric BAC-HD150 BM Adapter BACnet points list
Updated 28 October 2026
The BAC-HD150 sits on the M-NET bus of a CITY MULTI system and serves BACnet IP objects for each indoor unit group. Every group gets the same block of control and status objects, so the point list is one template repeated per group. Which objects actually respond depends on the group type and on BAC-HD150 Setting Tool options such as dual setpoint and Old Model Compatibility Mode.
This page lists 31 BACnet objects for the Mitsubishi Electric BAC-HD150 BM Adapter — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.
- Manufacturer
- Mitsubishi Electric
- Model
- BAC-HD150 BM Adapter
- Equipment
- VRF BACnet IP gateway
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 31 (19 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- BAC-HD150, BAC-HD/150, BACHD150, BM ADAPTER, CMCN BACnet points list, MEAPP0002
Instance calculator. This list prints one unit; the other units follow a formula. Mitsubishi Electric BAC-HD150 BM Adapter instance calculator →
Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.
BMS integration notes: Mitsubishi Electric BAC-HD150 BM Adapter
Set the BAC-HD150 IP addresses and groups with the BAC-HD150 Setting Tool, then map the same block of objects for each indoor unit group (instance MMGGPP). For a basic job you need On Off Setup/State, Operational Mode Setup/State, Set Temp (or Set Temp Cool/Heat for dual-setpoint groups), Room Temp and Alarm Signal. Space out requests: at least 200 ms per property.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 10101 | On Off Setup | Start/stop the group | Write |
| MO 10105 | Operational Mode Setup | Command the operating mode | Write |
| AV 10110 | Set Temp | Setpoint for single-setpoint groups | Write |
| AV 10124 | Set Temp Cool | Cooling setpoint for dual-setpoint groups | Write |
| AV 10125 | Set Temp Heat | Heating setpoint for dual-setpoint groups | Write |
| MO 10107 | Fan Speed Setup | Fan speed: 1 low, 2 high, 3 mid2, 4 mid1 | Write |
| BI 10102 | On Off State | Confirm run status | Read |
| AI 10109 | Room Temp | Room temperature (water temp on BU/AU groups) | Read |
| BI 10103 | Alarm Signal | Group fault alarm | Read |
| BI 10120 | M-NET Communication State | M-NET link to the group lost | Read |
Enable & remote start
No enable point is described; the BMS commands groups directly. Remote controller lockouts are separate Prohibition BVs (on/off, mode, filter reset, set temperature) per group, and System Forced Off works per group (MM GG 21) or for all groups (999921).
Network setup
- Factory IP addresses: LAN1 (BACnet) 192.168.1.254, LAN2 (Setting Tool / expansion controller) 192.168.200.212. Set both with the Setting Tool before connecting LAN1.
- UDP port 47808 for unicast and broadcast; 10BASE-T Ethernet; Class C private address recommended.
- Instance MMGGPP: M-NET number 01-03, group 01-50 (99 for collective), point number.
- Device instance is set with the BAC-HD150 Setting Tool; the instruction book does not give a default.
- If a superior system controller is present, register it in the Setting Tool and register the BAC-HD150 on that controller.
Watch out for
- Request interval: 200 ms per property or more; after a ReadPropertyMultiple of N properties wait N x 200 ms.
- If the M-NET line to the BAC-HD150 is lost, every group's Error Code reads 08 (Communication error); M-NET Communication State (point 20) shows the link status.
- Dual-setpoint groups need Set Temp Cool/Heat/Auto (24-26); writing those to single-setpoint groups returns an error. Enable Old Model Compatibility Mode if the BMS only handles one setpoint.
- With a PAC-YG50ECA expansion controller, dual setpoints are not supported; Old Model Compatibility Mode and Expansion Controller Settings must be enabled.
- Dry, Mid1/Mid2 fan speeds and Setback must be enabled in the Setting Tool. AHC is not supported.
- Use a UPS if the BAC-HD150 must keep running through power failures.
Mitsubishi Electric BAC-HD150 BM Adapter BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 10101 | On Off Setup | Start/stop command for the group | Write | Inactive=Stop, Active=Run | |
| BImin | 10102 | On Off State | Group run status | Read | Inactive=Stop, Active=Run | |
| BImin | 10103 | Alarm Signal | Group alarm | Read | Inactive=Normal, Active=Error | |
| MI | 10104 | Error Code | Error category for the group | Read | 1=Normal, 2=Other errors, 3=Refrigeration system fault, 4=Water system error, 5=Air system error, 6=Electronic system error, 7=Sensor fault, 8=Communication error, 9=System error | |
| MOmin | 10105 | Operational Mode Setup | Operating mode command | Write | 1=Cooling, 2=Heating, 3=Fan, 4=Auto, 5=Dry, 6=Setback | |
| MI | 10106 | Operational Mode State | Current operating mode | Read | 1=Cooling, 2=Heating, 3=Fan, 4=Auto, 5=Dry, 6=Setback | |
| MOmin | 10107 | Fan Speed Setup | Fan speed command | Write | 1=Low, 2=High, 3=Mid 2, 4=Mid 1 | |
| MI | 10108 | Fan Speed State | Current fan speed | Read | 1=Low, 2=High, 3=Mid 2, 4=Mid 1 | |
| AImin | 10109 | Room Temp | Room temperature (water temp for BU/AU groups) | °F/°C | Read | |
| AVmin | 10110 | Set Temp | Single setpoint (set water temp for BU/AU groups) | °F/°C | Write | |
| BI | 10111 | Filter Sign | Filter sign (circulating water exchange sign for BU/AU) | Read | Inactive=OFF, Active=ON | |
| BV | 10112 | Filter Sign Reset | Resets the filter sign | Write | Inactive=Reset, Active=Void | |
| BV | 10113 | Prohibition On Off | Locks out local on/off | Write | Inactive=Permit, Active=Prohibit | |
| BV | 10114 | Prohibition Mode | Locks out local mode change | Write | Inactive=Permit, Active=Prohibit | |
| BV | 10115 | Prohibition Filter Sign Reset | Locks out local filter sign reset | Write | Inactive=Permit, Active=Prohibit | |
| BV | 10116 | Prohibition Set Temperature | Locks out local setpoint change | Write | Inactive=Permit, Active=Prohibit | |
| BImin | 10120 | M-NET Communication State | M-NET communication status | Read | Inactive=Normal, Active=Error | |
| BV | 10121 | System Forced Off | Forced off, individual group | Write | Inactive=Reset, Active=Execute | |
| BV | 999921 | System Forced Off | Forced off, all groups (bundle) | Write | Inactive=Reset, Active=Execute | |
| MO | 10122 | Air Direction Setup | Vane direction command | Write | 1=Horizontal, 2=Downblow 60%, 3=Downblow 80%, 4=Downblow 100%, 5=Swing | |
| MI | 10123 | Air Direction State | Current vane direction | Read | 1=Horizontal, 2=Downblow 60%, 3=Downblow 80%, 4=Downblow 100%, 5=Swing | |
| AVmin | 10124 | Set Temp Cool | Cooling setpoint (dual setpoint groups) | °F/°C | Write | |
| AVmin | 10125 | Set Temp Heat | Heating setpoint (dual setpoint groups) | °F/°C | Write | |
| AV | 10126 | Set Temp Auto | Auto-mode setpoint (single setpoint auto) | °F/°C | Write | |
| AV | 10127 | Set High Limit Setback Temp | Upper setback limit | °F/°C | Write | |
| AV | 10128 | Set Low Limit Setback Temp | Lower setback limit | °F/°C | Write | |
| MO | 10135 | Ventilation Mode Setup | Lossnay ventilation mode command | Write | 1=Heat exchange, 2=Bypass, 3=Auto | |
| MI | 10136 | Ventilation Mode State | Current Lossnay ventilation mode | Read | 1=Heat exchange, 2=Bypass, 3=Auto | |
| MO | 10137 | Air To Water Mode Setup | Air To Water (PWFY) mode command | Write | 1=Heating, 2=Heating ECO, 3=Hot Water, 4=Antifreeze, 5=Cooling | |
| MI | 10138 | Air To Water Mode State | Current Air To Water mode | Read | 1=Heating, 2=Heating ECO, 3=Hot Water, 4=Antifreeze, 5=Cooling | |
| BI | 19981 | Expansion Controller Communication State | Expansion controller comms status | Read | Inactive=Normal, Active=Error |
No points match these filters.
Object ID lookup: Mitsubishi Electric BAC-HD150 BM Adapter point IDs by name
BO10101On Off SetupBI10102On Off StateBI10103Alarm SignalMI10104Error CodeMO10105Operational Mode SetupMI10106Operational Mode StateMO10107Fan Speed SetupMI10108Fan Speed StateAI10109Room TempAV10110Set TempBI10111Filter SignBV10112Filter Sign ResetBV10113Prohibition On OffBV10114Prohibition ModeBV10115Prohibition Filter Sign ResetBV10116Prohibition Set TemperatureBI10120M-NET Communication StateBV10121System Forced OffBV999921System Forced OffMO10122Air Direction SetupMI10123Air Direction StateAV10124Set Temp CoolAV10125Set Temp HeatAV10126Set Temp AutoAV10127Set High Limit Setback TempAV10128Set Low Limit Setback TempMO10135Ventilation Mode SetupMI10136Ventilation Mode StateMO10137Air To Water Mode SetupMI10138Air To Water Mode StateBI19981Expansion Controller Communication State
Integration notes
- Instance = 6 digits MMGGPP: MM = M-NET number (01-03), GG = group number (01-50, 99), PP = point number. Instances here use M-NET 01 / group 01 (e.g. 010101 = 10101).
- System Forced Off for all groups at once is fixed at 999921; Expansion Controller Communication State is MM9981 (19981 for M-NET 01).
- Set Temp Cool/Heat/Auto and the setback limits (24-28) only work with Old Model Compatibility Mode disabled; single-setpoint groups use Set Temp (10) and reject the dual-setpoint objects.
- Dry mode and Mid 1/Mid 2 fan speeds must be enabled in the BAC-HD150 Setting Tool; Setback needs compatibility mode off and a setback-capable unit.
- Mitsubishi Electric Canada's CMCN points list (MEAPP0002, Sept 2017) shows the same numbering without points 24-28 and Setback.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BAC-HD150 BM Adapter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Mitsubishi Electric BAC-HD150 BM Adapter
How many BACnet points does the Mitsubishi Electric BAC-HD150 BM Adapter have?
This list has 31 BACnet objects: 1 analog input, 6 analog values, 5 binary inputs, 1 binary output, 7 binary values, 6 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Mitsubishi Electric BAC-HD150 BM Adapter BACnet points are writable?
19 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Mitsubishi Electric BAC-HD150 BM Adapter BACnet documentation?
The source is Air-conditioner Control System BM ADAPTER BAC-HD150 Instruction Book (WT05542X04), published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/373.
What are the minimum BACnet points to integrate the Mitsubishi Electric BAC-HD150 BM Adapter?
Start with BO 10101 On Off Setup (Start/stop the group); MO 10105 Operational Mode Setup (Command the operating mode); AV 10110 Set Temp (Setpoint for single-setpoint groups); AV 10124 Set Temp Cool (Cooling setpoint for dual-setpoint groups); AV 10125 Set Temp Heat (Heating setpoint for dual-setpoint groups); MO 10107 Fan Speed Setup (Fan speed: 1 low, 2 high, 3 mid2, 4 mid1); BI 10102 On Off State (Confirm run status); AI 10109 Room Temp (Room temperature (water temp on BU/AU groups)); BI 10103 Alarm Signal (Group fault alarm); BI 10120 M-NET Communication State (M-NET link to the group lost).
How do I enable BMS control of the Mitsubishi Electric BAC-HD150 BM Adapter?
No enable point is described; the BMS commands groups directly. Remote controller lockouts are separate Prohibition BVs (on/off, mode, filter reset, set temperature) per group, and System Forced Off works per group (MM GG 21) or for all groups (999921).
How do I check these points on the real BAC-HD150 BM Adapter?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Mitsubishi Electric BACnet points lists
- VRF central controller with BACnet IP
Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan)
Japan-market CITY MULTI building air conditioning groups, Lossnay ventilators, DT-R, hot water heat pumps and brine coolers managed by an AE-200J, AE-50J or EW-50J.
Also known as: AE-200J, AE-50J, EW-50J, AE-200J BACnet, 三菱電機 AE-200J BACnet機能 - VRF central controller with BACnet IP
Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50)
CITY MULTI VRF indoor unit groups, Lossnay, OA processing units, Air To Water and chiller units managed by an AE-C400 or EW-C50.
Also known as: AE-C400, AE-C400E, EW-C50, EW-C50E, BACS-AP50, BACS-AP50E, AE-C/EW-C BACnet - Variable frequency drive (inverter)
Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models)
Mitsubishi Electric FR-E800 compact inverters with the built-in Ethernet port (FR-E8xx-E and safety/IP67 Ethernet variants) set to BACnet/IP.
Also known as: FR-E800, FR-E800-E, FR-E820, FR-E840, FR-E860, IB-0600871ENG - Variable frequency drive (HVAC fan and pump)
Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)
Mitsubishi Electric FR-F800 fan and pump inverters (FR-F820/F840/F842/F846) on the RS-485 terminals, and FR-F800-E models on the built-in Ethernet port.
Also known as: FR-F800, FR-F800-E, FR-F820, FR-F840, FR-F842, FR-F846, FR-F820-E, FR-F840-E, FR-F842-E, FR-F846-E, Mitsubishi FR-F800 BACnet, IB-0600547ENG, IB-0600628ENG - VRF BACnet IP interface (legacy)
Mitsubishi Electric PAC-YG31CDA BACnet Interface
CITY MULTI indoor unit groups managed by up to ten G-50A central controllers.
Also known as: PAC-YG31CDA, G-50A BACnet, BACnet Interface for G-50A - Split air conditioner BACnet IP gateway (legacy)
Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM)
Mitsubishi Electric Mr. SLIM (A-control) split air conditioners, up to 50 outdoor units each fitted with a Sub I/F board.
Also known as: BAC-A/50, BACA50, Procon BAC A 50, RM2428 - VRF BACnet IP gateway (legacy)
Mitsubishi Electric Procon BAC-IP/50
CITY MULTI indoor units, Lossnay/OA units and heat-pump boilers connected to one G-50 central controller (up to 50 units).
Also known as: BAC-IP/50, BACIP50, Procon BAC IP 50 - Split / VRF indoor unit interface (single unit)
Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units
Mitsubishi Electric air-to-air split and indoor units connected one per adapter through the CN105 connector.
Also known as: A1M+, MelcoBEMS MINI A1M PLUS, MelcoBEMS MINI (A1M), Procon A1M - Air-to-water heat pump interface
Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units
Mitsubishi Electric air-to-water (Ecodan) heat pump systems with an FTC controller, one adapter per system.
Also known as: A1M+ ATW, MelcoBEMS MINI A1M PLUS Ecodan, Procon A1M+ Ecodan - Energy recovery ventilator interface
Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units
Mitsubishi Electric Lossnay energy recovery ventilators supported by the A1M+ (listed in the manual appendix).
Also known as: A1M+ Lossnay, MelcoBEMS MINI A1M PLUS Lossnay - VRF central controller gateway
Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway)
Mitsubishi Electric City Multi and split systems managed by an AE-C400/EW-C50, AE-200/EB50, AG-150A or GB-50ADA centralised controller (up to 50 groups).
Also known as: MelcoBEMS2, MelcoBEMS, Procon MelcoBEMS, MELCOBEMS
Source: Air-conditioner Control System BM ADAPTER BAC-HD150 Instruction Book · WT05542X04. Object names, instances and units are reproduced as published; descriptions are our own.